User Manual Connection to Beckhoff ADS serial



Similar documents
User Manuals. Connection to Siemens S5 PU (AS511) Part Number: Version: 2. Date:

Library ModbusRTUlib Modbus RTU master communication. TXV rd Issue February 2010 All rights reserved

Omron I/O Driver (Series 2) Programmable Serial Interface Card

ETHERNET WEATHER STATION CONNECTIONS Application Note 33

USER GUIDE. Ethernet Configuration Guide (Lantronix) P/N: Rev 6

BIT COMMANDER. Serial RS232 / RS485 to Ethernet Converter

Toshiba Serial Driver Help Kepware Technologies

How To Set Up A Modbus Cda On A Pc Or Maca (Powerline) With A Powerline (Powergen) And A Powergen (Powerbee) (Powernet) (Operating System) (Control Microsci

Introduction: Implementation of the MVI56-MCM module for modbus communications:

F2103 GPRS DTU USER MANUAL

Modbus Communications for PanelView Terminals

Micro800 Programmable Controllers: Getting Started with CIP Client Messaging

VisorALARM-Manager Application Quick Guide. (Ver. 1.3) Dm 380-I. V:3.0

MS830 / MS833 Barcode Reader v1.0 9-December-2014

Microsoft SQL connection to Sysmac NJ Quick Start Guide

FINS Gateway For OMRON PLCs

MBP_MSTR: Modbus Plus Master 12

Ethernet. Customer Provided Equipment Configuring the Ethernet port.

Applications & Tools. Configuration of Messages and Alarms in WinCC (TIA Portal) WinCC (TIA Portal) Application description December 2012

Configuring CSS Remote Access Methods

7.7 Ethernet Communication (AFPX-COM5)

Siemens S7 TCP/IP Master with TIA S7 Tag Import Communications Driver

OfficeServ Link. User Guide. Version 2.1 June 2005

ModBus Server - KNX. Gateway for integration of KNX equipment into Modbus (RTU and TCP) control systems.

Profinet to EDV111 Series LED Signs Siemens Function Block Software Manual

TCP/IP MODULE CA-ETHR-A INSTALLATION MANUAL

How To Connect A Directsofl To A Powerpoint With An Acd With An Ctel With An Dm-Tel Modem On A Pc Or Ipad Or Ipa (Powerpoint) With A Powerline 2 (Powerline

Modbus and ION Technology

Application Note. Terminal Server G6

Programming and Using the Courier V.Everything Modem for Remote Operation of DDF6000

PCMCIA 1 Port RS EDITION OCTOBER 1999

RS-232 Communications Using BobCAD-CAM. RS-232 Introduction

Siemens S7 MPI Driver Help Kepware Technologies

RS232C < - > RS485 CONVERTER S MANUAL. Model: LD15U. Phone: / 97 / 98 (M)

Additional Setup Instructions for Modbus: RTU, ASCII, TCP, Omni & Enron

Manual TC3 PLC HMI. TwinCAT 3. Version: Date: Order No.: TF1800

SEC 4100 SYSTEM MONITOR Programmable Serial Interface Card Series 2

Modbus ASCII Driver Kepware, Inc.

16-Port RS232 to USB2.0 High Speed Multi Serial Adapter (w/ Metal Case) Installation Guide

LINDY ELECTRONICS LIMITED & LINDY-ELEKTRONIK GMBH - SECOND EDITION

IP Link Device Interface Communication Sheet

ENTBUS PLUS SOFTWARE FOR ENERGY MONITORING AND RECORDING INSTALLATION AND OPERATING MANUAL

User s Manual TCP/IP TO RS-232/422/485 CONVERTER. 1.1 Introduction. 1.2 Main features. Dynamic DNS


SenseLink TM. End-Point Controller. Addendum

Custom Solutions Center. Users Guide. Low Cost OEM PackML Templates L02 Release. Version LC-1.0

PFB366 Profibus-DP Gateway User Manual

Ethernet Port Quick Start Manual

Using Logix5000 Controllers as Masters or Slaves on Modbus

ENET-710. ENET Ethernet Module ENET-710 JAN / 06 FOUNDATION

Accessing EtherNet/IP Network Variables in a WAGO with a ControlLogix PLC Application note

WA Manager Alarming System Management Software Windows 98, NT, XP, 2000 User Guide

User Manual Revision English Converter / Adapter Ethernet to RS232 / RS485 (Order Code: HD HD M HD HD M)

How to use KEPServerEX OPC Server (Kepware) with iologik 4000 (Modbus TCP/IP NA-4010 and Modbus Serial NA-4020/NA-4021)

OCS Training Workshop LAB14. Setup

Using IDENT M System T with Modbus/TCP

Hypercom Key Loading and Management (HKLM) RS232 PPP Key Injection PC Setup Guide

ipad Installation and Setup

Using a Laptop Computer with a USB or Serial Port Adapter to Communicate With the Eagle System

Using HyperTerminal with Agilent General Purpose Instruments

SUDT AccessPort TM Advanced Terminal / Monitor / Debugger Version 1.37 User Manual

3.1 RS-232/422/485 Pinout:PORT1-4(RJ-45) RJ-45 RS-232 RS-422 RS-485 PIN1 TXD PIN2 RXD PIN3 GND PIN4 PIN5 T PIN6 T PIN7 R+ PIN8 R-

Getting Started with IntelleView POS Administrator Software

CMC-DN01 DeviceNet Slave Communication Card Operation Manual

DNP Master Ethernet Driver Help Kepware Technologies

MAX T1/E1. Quick Start Guide. VoIP Gateway. Version 1.0

How to setup a serial Bluetooth adapter Master Guide

1 Serial RS232 to Ethernet Adapter Installation Guide

Kepware Technologies Optimizing KEPServerEX V5 Projects

Operation Manual of EX-9132C-2. Serial to TCP/IP Converter

isco Connecting Routers Back to Back Through the AUX P

2-Port RS232/422/485 Combo Serial to USB2.0 Adapter (w/ Metal Case and Screw Lock Mechanism) Installation Guide

Using the WAGO PROFINET Coupler as Remote I/O with a Siemens S7 PLC

Advantech WebAccess Device Driver Guide. BwSNMP Advantech WebAccess to SNMP Agent (Simple Network Management Protocol) Device Driver Guide

Load Balancing. Outlook Web Access. Web Mail Using Equalizer

EMG Ethernet Modbus Gateway User Manual

Arduino Wifi shield And reciever. 5V adapter. Connecting wifi module on shield: Make sure the wifi unit is connected the following way on the shield:

R&S AFQ100A, R&S AFQ100B I/Q Modulation Generator Supplement

WHQL Certification Approval...2 User Interface...3 SUNIX s COMLab..4

Quick Installation. A Series of Intelligent Bar Code Reader with NeuroFuzzy Decoding. Quick Installation

How-To Set Custom Scale Format for FedEx Ship Manager

CONTROL MICROSYSTEMS DNP3. User and Reference Manual

1-Port R422/485 Serial PCIe Card

Vicon Flash Upgrade Software

ACU-1000 Manual Addendum Replacement of CPM-2 with CPM-4

User Manual Software for DSL Digital Speed Switch

PRODUCT MANUAL SKX OPEN SKX ADVANCE ZN1RX-SKXOPEN. Edition 2 Version 1.1

Siemens S (Ethernet)

Debugging Network Communications. 1 Check the Network Cabling

Kaspersky Lab Mobile Device Management Deployment Guide

Table of Contents. Safety Warnings..3. Introduction.. 4. Host-side Remote Desktop Connection.. 5. Setting Date and Time... 7

L5354 ControlNet Communications Interface

TCP/IP Converter DDS EX-9132 Operation Manual for 8051 Series

UPS Network Interface. Quick InstallationGuide

WIZnet S2E (Serial-to-Ethernet) Device s Configuration Tool Programming Guide

TSM for Windows Installation Instructions: Download the latest TSM Client Using the following link:

IP SERIAL DEVICE SERVER

IP Configuration Manual

Configuring Static and Dynamic NAT Simultaneously

Modbus and ION Technology

Transcription:

User Manual Connection to Beckhoff ADS serial Part Number: 80 860.665 Version: 2 Date: 22.11.2005 Valid for: TSwin.net 4.0x TSwin.net 4.1x

Version Date Modifications 1 21.09.2005 First edition 2 22.11.2005 Validation extended, chapter "Important Notes added, protocol parameters corrected This manual, including all illustrations contained herein, is copyright protected. Use of this manual by any third party in departure from the copyright provision is forbidden. No part of this manual may be reproduced, translated or electronically or photographically archived or altered without the express written consent from Sütron electronic GmbH. Violations shall be cause for damage liability. Sütron electronic reserves the right to make any changes that contribute to technical improvement.

Overall Table of Contents Overall Table of Contents 1 Important Notes... 1-1 1.1 Symbols... 1-1 1.2 Safety Notes... 1-1 1.3 Intended Use... 1-1 1.4 Target Group... 1-2 2 Beckhoff... 2-1 2.1 Data Types... 2-1 2.2 Programming... 2-3 2.2.1 Protocol Parameters... 2-3 2.2.1.1 Baud Rate...2-3 2.2.1.2 Parity...2-3 2.2.1.3 Data Bits...2-4 2.2.1.4 Stop Bits...2-4 2.2.1.5 Delay until Connection Set-Up...2-4 2.2.1.6 Maximum Waiting Time For Response...2-4 2.2.1.7 Connection Type...2-4 2.2.1.8 AMS Net Id...2-5 2.2.1.9 Port Number...2-6 2.2.1.10 Device Address...2-6 2.2.2 Variables List... 2-6 2.2.3 Poll Area... 2-6 2.2.4 Physical Connection... 2-7 2.2.4.1 Pin Assignment for Operating Devices with an Universal Interface...2-7 2.2.4.2 Cabel RS232 - Beckhoff BX8000...2-7 2.3 Error Messages... 2-8 2.4 Applications... 2-11 2.4.1 Connection by AMS serial... 2-11 A Index...A-1 i

Overall Table of Contents ii

Important Notes 1 Important Notes 1.1 Symbols The symbols in this manual are used to draw your attention on notes and dangers. Danger This symbol is used to refer to instructions wich, if ignored or not carfully followed could result in personal injury. Note This symbol indicates application tips or supplementary notes. Reference to source of information This symbol refers to detailed sources of information on the current topic. 1.2 Safety Notes Read this manual carefully before using the operating device. Keep this manual in a place where it is always accessible to all users. Proper transportation, handling and storage, placement and installation of this product are prerequisites for its subsequent flawless and safe operation. This user manual contains the most important information for the safe operation of the device. The user manual, in particular the safety notes, must be observed by all personnel working with the device. Observe the accident prevention rules and regulations that apply to the operating site. Installation and operation must only be carried out by qualified and trained personnel. 1.3 Intended Use The device is designed for use in the industry. The device is state-of-the art and has been built to the latest standard safety requirements. However, dangerous situations or damage to the machine itself or other property can arise from the use of this device. The device fulfills the requirements of the EMC directives and harmonized European standards. Any modifications to the system can influence the EMC behavior. 1-1

Important Notes 1.4 Target Group All configuration and programming work in connection with the automation system must be performed by trained personnel only (e.g. qualified electricians, electrical engineers). The configuration and programming personnel must be familiar with the safety concepts of automation technology. 1-2

2 Beckhoff ADS serial The Beckhoff ADS serial protocol connects TesiMod operating devices with RISC CPU and ARM9 CPU respectively and TesiPan operating devices to the Beckhoff TwinCat controller family. A serial connection via the RS232 or RS485 interface is used. The serial ADS driver has to be installed on the controller. The Beckhoff ADS serial protocol supports the synchronous services. The programming software takes the data objects of the file [NAME].TPY which is generated as a XML file automatically. The connected control unit accesses both to a data object both via the symbolic name and directly to addresses. 2.1 Data Types Direct access is possible to the following data types. Table 2-1 Data types for Beckhoff ADS serial Data Type Index Group(s) Index Offset Value Range Size BOOL Inputs 0x000F021 0x00000000 to Outputs 0x000F031 0xFFFFFFFF Flags Inputs Outputs Flags 0x0004021 0x000F020 0x000F030 0x0004020 Data Block 0x000F003 0x00000000 BYTE Inputs 0x000F020 0x00000000 to Outputs 0x000F030 0xFFFFFFFF Flags 0x0004020 Data Block 0x000F003 0x00000000 DATE Data Block 0x000F003 0x00000000 D#1970-01-01 to D#2106-02-06 DATE_AND _TIME / DT 0 / 1 8 Bit 0 to 255 1 Byte Data Block 0x000F003 0x00000000 DT#1970-01-01-00:00 to D#2106-02-06-06:28:15 DINT Inputs 0x000F020 0x00000000 to Outputs 0x000F030 0xFFFFFFFF Flags 0x0004020 Data Block 0x000F003 0x00000000-2147483648 to 2147483647 4 Byte 4 Byte 4 Byte 2-1

Table 2-1 Data types for Beckhoff ADS serial Data Type Index Group(s) Index Offset Value Range Size DWORD Inputs 0x000F020 0x00000000 to Outputs 0x000F030 0xFFFFFFFF Flags 0x0004020 Data Block 0x000F003 0x00000000 INT Inputs 0x000F020 0x00000000 to Outputs 0x000F030 0xFFFFFFFF Flags 0x0004020 Data Block 0x000F003 0x00000000 0 to 4294967295 4 Byte -32768 to 32767 2 Byte LREAL Data Block 0x000F003 0x00000000 ~ -1.79769313486231E308 to ~ 1.79769313486232E308 SINT Inputs 0x000F020 0x00000000 to Outputs 0x000F030 0xFFFFFFFF Flags 0x0004020 Data Block 0x000F003 0x00000000 8 Byte -128 to 127 1 Byte STRING Data Block 0x000F003 0x00000000 1 Byte per Character (Size at Declaration) +1 Byte for Zero Termination TIME Data Block 0x000F003 0x00000000 T#0ms to T#71582m47s295ms TIME_OF_D AY / TOD Data Block 0x000F003 0x00000000 TOD#00:00 to TOD#1193:02:47.295 UDINT Inputs 0x000F020 0x00000000 to Outputs 0x000F030 0xFFFFFFFF Flags 0x0004020 Data Block 0x000F003 0x00000000 UINT Inputs 0x000F020 0x00000000 to Outputs 0x000F030 0xFFFFFFFF Flags 0x0004020 Data Block 0x000F003 0x00000000 USINT Inputs 0x000F020 0x00000000 to Outputs 0x000F030 0xFFFFFFFF Flags 0x0004020 Data Block 0x000F003 0x00000000 n Byte 4 Byte 4 Byte 0 to 4294967295 4 Byte 0 to 65535 2 Byte 0 to 255 1 Byte 2-2

Table 2-1 Data types for Beckhoff ADS serial Data Type Index Group(s) Index Offset Value Range Size WORD Inputs Outputs 0x000F020 0x000F030 0x00000000 to 0xFFFFFFFF Flags 0x0004020 Data Block 0x000F003 0x00000000 0 to 65535 2 Byte 2.2 Programming 2.2.1 Protocol Parameters 2.2.1.1 Baud Rate This parameter specifies the communication rate. Table 2-2 Baud rate Configurable values (Baud) Default Value 9600 19200 38400 X 57600 2.2.1.2 Parity This parameter specifies the parity used to control the communication. Table 2-3 Parity Configurable Values None Even Odd Default Value X 2.2.1.3 Data Bits This parameter specifies the number of data bits. Table 2-4 Data bits Configurable Values Default Value 5 6 7 8 X 2-3

2.2.1.4 Stop Bits This parameter specifies the number of stop bits. Table 2-5 Stop bits Configurable Values Default Value 1 X 1.5 2 2.2.1.5 Delay until Connection Set-Up This parameter specifies the waiting time after which the operating device starts the communication. Table 2-6 Delay until connection set-up Configurable Values Default Value 5 s to 255 s 5 s 2.2.1.6 Maximum Waiting Time For Response This parameter specifies how long the operating device waits for a response from the controller. Table 2-7 Maximum waiting time for response Configurable Values Default Value 100 ms to 25500 ms 1000 ms 2.2.1.7 Connection Type For a point to point connection only those protocol parameters are available in the dialog which are necessary. Table 2-8 Connection type Configurable Values Point to Point Default Value X Multiple link 2.2.1.8 AMS Net Id This parameter indicates the individual IP-address of the operating device. This address is also used in the telegram header of the serial protocol. However the AMS Net ID different from a normal IP-address consists of 6 group numbers. Use the IP address of the operating device for the first 4 group numbers and assign a 1 for each of the last 2 group numbers. Example: 192.168.100.155.1.1 You can obtain the IP address of the operating device as follows: For TesiPan devices in standard mode, 1st possibility: 1. Start the device again. 2. Read the IP address while start process (line IPAD). 2-4

For TesiPan devices in standard mode, 2nd possibility: 1. Press the service tool key (key). 2. Enter the password. 3. Click on the IPConfig symbol. 4. Read the IP address (line IP Address). For ARM9 devices, 1st possibility: 1. Start the device again. 2. Read the IP address while start process (line IPAD). For ARM9 devices, 2nd possibility: 1. Start the device again. 2. Start the launch program while booting process. 3. Navigate to the IP Settings button. 4. Press the Enter key. 5. Navigate to the Current IP button. 6. Press the Enter key. 7. Read the IP address (line IP:) Table 2-9 AMS Net Id Configurable Values 000.000.000.000.1.1 to 255.255.255.255.1.1 Default Value No Default Value Always enter the first four group numbers of the IP address with 3 digit values. Example: 192.168.100.88.1.1 = 192.168.100.088.1.1 2.2.1.9 Port Number This parameter specifies the port number with up to 5 digits, which is used to communicate with the operating device. You can choose the port number freely. Table 2-10 Port number Configurable Values Point to Point: 32768 to 65535 Multiple link: 0 to 65535 Default Value 32768 2.2.1.10 Device Address This parameter sets the address of the operating device and is only valid for multiple links. Table 2-11 Device address Configurable Values Default Value 0 to 255 0 2-5

2.2.2 Variables List Only those variables are put from the TPY file into the variables list of the programming software, which have the following declaration: (*~( SuetronVar)*) Example: VAR_GLOBAL Input1 AT %IX30.0 : BOOL; (* ~(SuetronVar ) *) Output1 AT %QX30.0 : BOOL; (* ~(SuetronVar ) *) Output2 AT %QX30.1 : BOOL; (* ~(SuetronVar ) *) END_VAR The take-over of the variables is always carried out when the variables list is opened in the programming software. If you made changes to the controller software and therefore created new variables or deleted variables, you have to update the variables list by opening it once again! Afterwards you have to compile the project again so that the changes are taken on. In connection with a BX controller only global variables which are assigned to the areas of input (% I), output (% Q) or flag (% M) are allowed. 2.2.3 Polling Area You should use the SINT data type If you like to use the poll area function. Please enter the start address of the data block in Additional Functions, Polling Area. 2-6

2.2.4 Physical Connection Plug-in connectors on the operating device for connection to the controller. 2.2.4.1 Pin Assignment for Operating Devices with an Universal Interface Table 2-12 Pin assignment RS232 Pin Designation Function 6 TD Transmitted Data 15 CTS Clear to send 17 RTS Request to send 18 RD Received data 25 SGND Signal Ground 2.2.4.2 Cabel RS232 - Beckhoff BX8000 The following cabling diagram applies to operating devices with an universal interface only. Operating device Beckhoff BX8000 RD 18 BN BN 8 TxD TD 6 WH WH 7 RxD SGND 25 GNYE GNYE 9 GND D-SUB male connector 25 pin D-SUB male connector 9 pin Both ends of the shield are connected to the metallic housing. 2-7

2.3 Error Messages Error messages are displayed on the operating device along with a code and subcode. Error messages are composed as follows: Communication Error Code Subcode Retries XXXXX XXXXX XXXXX Table 2-13 Error messages for Beckhoff ADS serial Code Subcode Description Possible Cause 50 03 Framing error on serial interface Line disturbance. Wrong baud rate. 06 Parity error on serial interface Line disturbance. Different parity settings for communication participants 60 10 Wrong telegram length 20 Wrong telegram header Line disturbance 40 Wrong checksum Line disturbance 60 Timout: no response Line interrupt. Connection interrupt. Loading a new project. Controller not started. Connection data in the controller missing or invalid. 70 Wrong transmitter address A different controller transmits data to the operating device. 70 Errors from the controller The subcode contains the error number of the controller 0 No error 1 Internal error 2 No Rtime 3 Allocation locked memory error 4 Insert mailbox error 5 Wrong receive HMSG 6 Target port not found 7 Target machine not found 8 Unknown command ID 9 Bad task ID 10 No IO 2-8

Table 2-13 Error messages for Beckhoff ADS serial Code Subcode Description Possible Cause 70 11 Unknown AMS command 12 Win 32 error 13 Port not connected 14 Invalid AMS length 15 Invalid AMS Net ID 16 Low installation level 17 No debug available 18 Port disabled 19 Port already connected 20 AMS Sync Win 32 error 21 AMS Sync timeout 22 AMS Sync AMS error 23 AMS Sync no index map 24 Invalid AMS port 25 No memory 26 TCP send error 27 Host unreachable 1280 Router: no locked memory 1282 Router: mailbox full 1792 Error class <device error> 1793 Service is not supported by server 1794 Invalid index group 1795 Invalid index offset 1796 Reading/writing not permitted 1797 Parameter size not correct 1798 Invalid parameter value(s) 1799 Device is not in a ready state 1800 Device is busy 1801 Invalid context (must be in Windows) 1802 Out of memory 1803 Invalid parameter value(s) 1804 Not found (files, etc.) 1805 syntax error in command or file 1806 Objects do not match 1807 Object already exists 2-9

Table 2-13 Error messages for Beckhoff ADS serial Code Subcode Description Possible Cause 70 1808 Symbol not found 1809 Symbol version invalid 1810 Server is in invalid state 1811 AdsTransMode not supported 1812 Notification handle is invalid 1813 Notification client not registered 1814 No more notification handles 1815 Size for watch too big 1816 Device not initialized 1817 Device has a timeout 1818 Query interface failed 1819 Wrong interface required 1820 Class ID is invalid 1821 Object ID is invalid 1822 Request is pending 1823 Request is aborted 1824 Signal warning 1825 Invalid array index 1856 Error class <client error> 1857 Invalid parameter at service 1858 Polling list is empty 1859 Var connection already in use 1860 Invoke ID in use 1861 Timeout elapsed 1862 Error in Win 32 subsystem 1864 Ads port not opened 1872 Internal error in ads sync 1873 Hash table overflow 1874 Key not found in hash 1875 No more symbols in cache 2-10

2.4 Applications 2.4.1 Connection by AMS serial For a connection by AMS serial you have to assign the AMS Net ID of the controller computer and the port number of the corresponding controller. These data is read out of the TPY file by the programming software. The data is included by the tags <RoutingInfo> </RoutingInfo>. Example: <RoutingInfo> <AdsInfo> <NetId>192.168.100.155.1.1</NetId> <Port>801</Port> </AdsInfo> </(RoutingInfo> Additionally you have to enter a Net ID and a port number for the operating device, even if you don t connect it by ethernet. For the port number of the operating device you enter a value greater or even 32768 in the programming software. TwinCat System Control Enter the parameters for the controller computer in the TwinCat System Control as follows: 1. Start the program TwinCat System Control on the controller computer. The window TwinCat System Properties opens. Figure 2-1 Window TwinCat System Properties 2. Open the AMS Router tab. 3. Click on the Add button. 2-11

The Properties of remote connection dialog opens. You cannot enter any strings in the address field at the first call of the dialog. Enter the Name, AMS Net ID and Transport first and close the dialog. You can assign your COM interface at the second call. Figure 2-2 Properties of remote connection dialog 4. Enter a name for the controller computer in the Remote name field. 5. Enter a 6 digit ID in the AMS Net ID field. Take into account that the last two digits must have the value 1. 6. Select the item COM-PORT in the Transmission field. 7. Confirm with OK. You return to the TwinCat System Properties window. 8. Select the new item in the Remote Computer field. 9. Click on the Properties button. 10. Enter the serial interface with any communication parameters in the Address field. The format is <COM-Port:>,<Baud rate>,<parity>,<data bits>,<stop bits>. 11. Confirm with OK. You return to the TwinCat System Properties window. Figure 2-3 TwinCat System Properties window with entry 12. Confirm with OK. You load the project (Bootproject) of TwinCAT PLC Control in the controller via this connection. Connect the control computer and the controller with the programming cable. After you have loaded the project of TwinCAT PLC Control into the controller and the project of TSwin into the operating terminal, you can connect the control with the control unit. 2-12

Index A Index B Beckhoff... 2-1 Connection by AMS serial... 2-11 C Cable RS232 Beckhoff BX8000... 2-7 I Important notes... 1-1 Intended use... 1-1 P Protocol parameters Beckhoff... 2-3 S Safety notes... 1-1 Symbols... 1-1 T Target group... 1-2 A-1

Index A-2

Sütron electronic GmbH Kurze Straße 29 D-70794 Filderstadt Phone: 0049 711 / 77098-0 Fax: 0049 711 / 77098-60 E-mail: doku@suetron.de Internet: www.suetron.com