Quick Start Guide 00825-0100-4764, Rev DA March 2014. Rosemount 8714D (Calibration Standard) Magnetic Flowtube Simulator



Similar documents
Rosemount 333 HART Tri-Loop

Rosemount 5300 and 5400 Series Terminal Compartment Spare Part Instruction

Techniques for Interconnecting Smart Wireless Gateways to ProSoft RadioLinx Devices

THE WORLD'S FIRST WIRELESS GUIDED WAVE RADAR

Rosemount 333 HART Tri-Loop

Best Practices for Reducing Transmitter Life Cycle Costs

Replacing Displacers with Guided Wave Radar

Rosemount 1199 Submersible Seal

Model 3051 Pressure Transmitter with HART Protocol

Reliable Pressure Measurement with Remote Diaphragm Seals in Cold Weather Applications

Guidelines for Choosing and Installing Radar in Stilling Wells and Bypass Chambers

Contents. Document information

Loop Calibration and Maintenance

VOLTAGE/CURRENT CALIBRATOR ISO-TECH ILC-421

Rosemount D Solids Scanners for Bulk Solids Inventory and Financial Reporting

CONTENTS. PAGE Chapter 1 General Information 1. Chapter 2 Setup 4 DP450-VDC 7 DP450-VAC 7 DP450-DCC 7 DP450-F 8 DP450-HACC 9 DP450-HDCC 11 DP450-E 13

Isolated AC Sine Wave Input 3B42 / 3B43 / 3B44 FEATURES APPLICATIONS PRODUCT OVERVIEW FUNCTIONAL BLOCK DIAGRAM

RI-215A Operator s Manual. Part Number: RK Revision 0 Released: 10/3/05

FAQ s on Siemens Magmeters

Rosemount 751 Field Signal Indicator

Combustible Gas Transmitter RK-05

LEVEL AND VOLUME MEASUREMENTS OF BULK SOLIDS

CONNECTOR AMPLIFIER FOR PROPORTIONAL VALVES (4-20 ma Input Version)

MTII4200 level Transmitter Installation, Operation & Maintenance Instructions

AIR QUALITY SURVEILLANCE BRANCH ACCEPTANCE TEST PROCEDURE (ATP) FOR. Teledyne Advanced Pollution Instruments Model 400 E Ozone Analyzer AQSB ATP 002

How to use the OMEGALOG software with the OM-SQ2010/SQ2020/SQ2040 Data Loggers.

MTI10 Insertion and MTL10 In-line Thermal Mass Flowmeter and Temperature Transmitter

ATEX Installation Instructions for Micro Motion ELITE CMFS Sensors

EMERSON S ROSEMOUNT PROJECT MANAGEMENT OFFICE. Delivering project success for your instrumentation

Rosemount 752 FOUNDATION fieldbus Remote Indicator

PART 1 - INTRODUCTION...

PORTER MASS FLOW MEASUREMENT AND CONTROL SYSTEMS

Mobrey Ultrasonic. MSP900SH Level and MSP900FH Flow Transmitters. Product Data Sheet February 2015 IP2032, Rev BA

OEM Manual MODEL 2350 ELECTRONIC DUAL CYLINDER SCALE

Transmitter Interface Program

Installation Instructions. Before Installation. Read these installation instructions carefully before commissioning the pressure transmitter.

S-series Mass Connection Solutions

THERMAL ANEMOMETRY ELECTRONICS, SOFTWARE AND ACCESSORIES

Smart Wireless Solutions. Intelligent Well Production Starts Here

Rosemount 1199 Submersible Seal

3500/62 Process Variable Monitor

Density Measurement. Technology: Pressure. Technical Data Sheet INTRODUCTION. S min =1.0 S max =1.2 CONSTANT LEVEL APPLICATIONS

ATEX Zone 2 and 22 Installation Drawings and Instructions

Model SRMD Setra Remote Monitoring Display

RAEGuard EC FGM-13XX

Models SFP33 & SFP32 Pressure Transmitters

Toroidal Conductivity Sensor

Essential Electrical Concepts

Electro-Magnetic Flowmeters COPA-XT 2-Wire DT43

Duct Humidity Transmitter

P R O D U C T S P E C I F I C A T I O N MSA Ultima X Series Sensor/Transmitter Specification

Manual Ranging MultiMeter

TECHNICAL DATASHEET #TD1404AX PWM CONTROLLED SOLENOID DRIVER

Import the Gateway Certificate to the Browser

Monitoring Water Quality For Today s Demanding World

DPI 260 SERIES: Digital Pressure Indicators

How To Connect An Hart Tri Loop To A Model 333 Hart To Analog Signal Converter

Micro Motion Model 2200S Transmitters

MODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE

EMERGENCY EGRESS LIGHTING POWER SUPPLY PART NO COMPONENT MAINTENANCE MANUAL WITH ILLUSTRATED PARTS LIST

TraceTek TTDM Series Leak Detection and Location Modules Replacement Parts Installation Instructions

ATL Fuel Level Sender Probes

T7560A,B,C Digital Wall Module

ProLink II Software for Micro Motion Transmitters

PIEZOMETER AIRFLOW MEASURING RING

IPX AUTOMATIC IP NETWORK LOSS BACKUP A/B SWITCH INSTRUCTION BOOK IB

I nstallation. M100Q Series Proportional Actuator with R81Q Controller Board for Thermistor Sensor Applications. Tools Needed.

ROC800-Series Advanced Pulse Module

RGC-IR Remote Gas Calibrator for IR400

Rain+Birdt. Simple To Set Timer (SST) Setup & Operation Instructions. English RAIN BIRD ( ) or visit

PHYSICS 111 LABORATORY Experiment #3 Current, Voltage and Resistance in Series and Parallel Circuits

Physical Specifications (Custom design available.)

Process Tools Selection Guide. inside for: for industrial instrumentation and electrical technicians. Loop Calibrators. Pressure Calibrators

Inductors in AC Circuits

Wahl C50 Calibrator FEATURES

AutoRanging Digital MultiMeter

PTU Series Ultrahigh-Purity Pressure Transducers

OPERATION MANUAL. VDA-106A Video Distribution Amplifier. 1 st Edition - Rev.1

Digital I/O: OUTPUT: Basic, Count, Count+, Smart+

Automatic Transfer Switch FT-10 Network Control Communications Module (CCM-T) Kit

Technical Note Series

2002 IS Catalog. Page

CX Zoner Installation & User Guide

PREMIUM CLEAN ROOM MONITOR MODELS 8630-CRM-S 8630-CRM-P

713 Open Channel Flowmeter and Transmitter. All-in-one package for open channel flow measurement.

AN2680 Application note

Experiment 5. Strain Gage Measurements

DMP 331. Industrial Pressure Transmitter for Low Pressure. Stainless Steel Sensor

DISCONTINUED PRODUCT. Infrastructure Management & Monitoring For Business-Critical Continuity. Liebert icom-do. User Manual

LM134-LM234-LM334. Three terminal adjustable current sources. Features. Description

Streaming Potential System (SPT1000, SPD1000)

The DL8000 Preset Controller. The Ideal Device for Controlling and Measuring the Loading of Liquid Hydrocarbons into Transporting Tankers

PMP 4000 Series. Druck Amplified Output Pressure Transducers. GE Sensing. Applications. Features

Rosemount 2088 Absolute and Gage Pressure Transmitter

Level Instrumentation for the Refining Industry

DVI DA2 and DVI DA 4 User Guide

Model 111 Mass Flow Instruments

ECR Shelf System Installation Guide Centralized Rack Mount Call Recording

PERF10 Rubidium Atomic Clock

Transcription:

Quick Start Guide 00825-0100-4764, Rev DA Rosemount 8714D (Calibration Standard) Magnetic Flowtube Simulator

Quick Start Guide NOTICE This document provides basic guidelines for the Rosemount 8714D. It does not provide instructions for detailed configuration, diagnostics, maintenance, service, troubleshooting. This QSG is also available electronically on www.rosemount.com. Explosions could result in death or serious injury. Installation of this device in an explosive environment must be in accordance with the appropriate local, national, and international standards, codes, and practices. Please review the Product Certifications section for any restrictions associated with a safe installation. Before connecting a Field Communicator in an explosive atmosphere, ensure the instruments are installed in accordance with intrinsically safe or non-incendive field wiring practices. Electrical shock can result in death or serious injury. Avoid contact with the leads and terminals. High voltage that may be present on leads can cause electrical shock. Contents 8714D introduction................. page 3 Step 1: Change transmitter parameters page 3 Step 2: Connect wiring and power-up.. page 3 Step 3: Perform electronics trim....... page 4 Step 4: Verify Rosemount 8714D flowtube simulator........................... page 5 2

Quick Start Guide 8714D introduction The Rosemount 8714D is a high-precision instrument that can be used to recalibrate the following transmitters 8712 C/D/E, 8732 C/E, and the 8742C. The 8714D supplies an exact voltage, precisely simulating flow rates of 0.00 ft/s, 3.00 ft/s, 10.00 ft/s, and 30.00 ft/s. The precise 30.00 ft/s voltage signal may be used to recalibrate or verify operation of the transmitter. Perform this procedure only if you believe that the transmitter is no longer accurate. Step 1: Change transmitter parameters 1. Use a Field Communicator or Local Operator Interface (LOI) to change the parameters of the transmitter to the following: Tube Calibration Number: 1000015010000000 Units: ft/s Analog Output Range: 20mA = 30.00 ft/s Analog Output Zero: 4mA = 0 ft/s Coil Pulse Mode: 5 Hz (6Hz 8712C only) 2. Set the loop to manual (if necessary). 3. Power down the transmitter. Step 2: Connect wiring and power-up 1. Insert the metal end of the wiring assembly into the 8714D Calibration Standard. 2. Connect the transmitter. For 8712, see Figure 1. For 8732/8742, see Figure 2. Rosemount 8712 (Figure 1) Use the six contact pin terminal plug-style wiring assembly. Follow the numeric convention for the 8712 so the plugs match the terminal block. Figure 1. 8712 Terminal Block 3

Quick Start Guide Rosemount 8732/8742 (Figure 2) Use the two black connector-style wiring assembly (one connector has four contacts, the other has three.) Remove the electronics side cover (furthest away from the conduit plugs). If you do not have a LOI, the connectors will be clearly visible on the bottom side of the board. If you have a LOI, remove the three mounting screws from the LOI assembly and pull the display assembly away from the connector assembly until the connector assembly on the back of the board is fully released. Then, plug the calibrator connectors into the appropriate receptacles. Figure 2. Rosemount 8732E Electronics Attempting an electronics trim without a Rosemount 8714D may result in an inaccurate transmitter. It may also generate a DIGITAL TRIM FAILURE message. If this message appears, no values were changed in the transmitter. Simply power down the transmitter to clear the message. If the trim was completed, or no error message was generated, correction requires a Rosemount 8714D. Step 3: Perform electronics trim 1. Set the Rosemount 8714D to simulate a flow rate of 30 ft/s. 2. Power up the transmitter with the Rosemount 8714D connected. Allow the electronics 30 minutes to warm-up before reading the flow rate. 3. Read the flow rate. It should be between 29.97 and 30.03 ft/s. If the reading is within this range, return the transmitter to the original configuration. If the reading is not within this range, continue to Step 4: Verify Rosemount 8714D flowtube simulator page 5. 4. Initiate an electronics trim with the LOI or Field communicator. The electronics trim takes about six minutes to complete. No transmitter adjustments are required. HART Fast Keys 1.5 LOI Auxiliary Function 4

Quick Start Guide Step 4: Verify Rosemount 8714D flowtube simulator Procedure for verifying the Model 8714D flowtube simulator The Rosemount model 8714D Flowtube Simulator is a Calibration Standard made to operate specifically with the Rosemount models 8712 C/D/E, 8732 C/E, and the 8742C Magnetic Flowmeter Transmitters. The 8714D simulates a sensor coil load. It accurately produces a simulated flow signal for the purpose of transmitter calibration. Note Rosemount strongly encourages the 8714D be sent back to the factory to be calibrated. Typically on a yearly basis. Method 1 verification: required equipment NIST* traceable DC current source capable of sourcing 500mA. Accuracy should be +/- 0.1%. NIST traceable DMM (voltmeter). For example the Agilent 34401A or equivalent. *NIST stands for National Institute of Standards and Technology Limitations Current thru terminals 1 and 2 should not exceed 600mA. Limit the output voltage on the current source to 12 VDC max. This is to protect the 8714D input at pins 1 and 2 and also for operator safety. Calibration shall occur with the 8714D standard set at 30 per feet per second. Figure 3. Test setup for method 1 and the front panel connection Test setup for method 1 Front panel connections 5

Quick Start Guide Method 1 - verification procedure 1. Set the output voltage limit on the current source to 12VDC max. 2. Set the current source output to 500mA dc. 3. Connect the current source to the 8714D input terminals 1 and 2 as shown in the test setup diagram. 4. Allow the 8714D to stabilize for 30 minutes. 5. Measure and record the average voltage at pins 18 and 19 over a 5 minute span. 6. The value should equate to 1.078mV ±.05%. Note If your device does not operate within this specification, return the Rosemount 8714D to the Rosemount factory for calibration. Method 2 verification: required equipment DC voltage source. Set current limit to 600mA NIST traceable 1 ohm, 1 watt precision resistor; 10ppm, measurable to 5 digits (for example the Tegam SR1-1) NIST traceable DMM(s) (voltmeter); (for example, the Agilent 33401A or equivalent) Limitations Current through terminals 1 and 2 should not exceed 600mA. Calibration shall occur with the 8714D standard set at 30 per feet per second. Figure 4. Test setup for method 2 Test setup for method 1 6 Method 2 - verification procedure: 1. Verify the DC power supply is at 0 volts. 2. Connect the supply as shown in the above diagram. 3. Gradually increase the DC power supply voltage until 0.5V is measured across the 1 ohm sense resistor (R in ).

Quick Start Guide 4. Allow the 8714D to stabilize for 30 minutes. 5. Re-verify the voltage across R in = 0.5V. 6. Measure and record the average voltage at pins 18 and 19 over a 5 minute span. Also, measure and record the average voltage across R in over the same 5 minute span. This will be VR in. 7. Calculate IR in as (VR in / 1Ω). 8. Due to the possible variation of IR in over the 5 minute time period, the expected value at pins 18 and 19 can be calculated as: [(IR in /0.500)*1.078mV] = expected value across pins 18 and 19 ± 0.05%. 9. For example: If the measured current through R in is 499mA, then: [(0.499)/(0.500)]*1.078mV=1.075mV ± 0.05% at pins 18 and 19 If the measured current through R in is 501mA, then: [(0.501)/(0.500)]*1.078mV=1.080mV ± 0.05% at pins 18 and 19 If the measured current through R in is 500mA, then: [(0.500)/(0.500)]*1.078mV=1.078mV ± 0.05% at pins 18 and 19 Note If your device does not operate within this specification, return the Rosemount 8714D to the Rosemount factory for calibration. Within the United States, Rosemount Inc. has two toll-free assistance numbers. Customer Support Center: North American Response Center: Tel (USA) 800 522 6277 (7:00 a.m. to 7:00 p.m. CST) Technical support, quoting, and order-related questions. 1-800-654-7768 (24 hours a day - Includes Canada) Equipment service needs. 7

?00825-0100-4764I? Quick Start Guide 00825-0100-4764, Rev DA Emerson Process Management Rosemount Inc. 8200 Market Boulevard Chanhassen, MN 55317 USA www.rosemount.com T (USA) +1 800 522 6277 T (International) +1 (303) 527 5200 F +1 (303) 530 8459 Emerson Process Management Latin America Multipark Office Center Turrubares Building, 3rd & 4th floor Guachipelin de Escazu, Costa Rica T+(506) 2505-6962 international.mmicam@emersonprocess.com Emerson Process Management Asia Pacific Private Limited 1 Pandan Crescent Singapore 128461 T (65) 6777 8211 F (65) 6777 0947 Enquiries@AP.EmersonProcess.com Emerson Process Management Flow B. V. Neonstraat 1 6718 WX Ede The Netherlands T +31 (0) 318 495555 F +31 (0) 318 495556 Emerson FZE P.O. Box 17033 Jebel Ali Free Zone Dubai UAE T +971 4 811 8100 F +971 4 886 5465 FlowCustomerCare.MEA@Emerson.com 2014 Rosemount Inc. All rights reserved. All marks property of owner. The Emerson logo is a trade mark and service mark of Emerson Electric Co Rosemount and the Rosemount logotype are registered trademarks of Rosemount Inc.