Detector transparent with Color Inserts. FAA 500 TR P Trim Ring transparent with Color Inserts. FCA 500 / FCA 500 E Detector Bases



Similar documents
D7050/D7050TH. Installation Instructions. Multiplex Photoelectric Smoke Detectors

D287/D288/D292/D293A/D293E

2.0 Installation 1. Remove the cover using a small flat blade screwdriver. Figure 2: Cover Removal

E-PDD Duct Smoke Detector Installation Sheet

FIRERAY 2000 Installation Guide

el-720 Carbon Dioxide Gas Leak Detector User s Guide

Cross-beam scanning system to detect slim objects. 100 mm in

FN2001-A1 Network module (SAFEDLINK) Mounting Installation

Signaling Lights. LH Series Surface Mount Indicators. Part Numbers. Jumbo Dome (one color) Jumbo Dome (two color)

GENUINE PARTS INSTALLATION INSTRUCTIONS

SP4-LOC SAFEPATH4 REMOTE MICROPHONE AND LOCAL OPERATOR CONSOLE

Drayton Digistat +2RF/+3RF

12 Volt 30 Amp Digital Solar Charge Controller

Product and Applications Description. Application Programs. Example of Operation. GAMMA instabus Technical Product-Information.

Basic Specifications. Electrical. EPSON Perfection Color EPSON MatrixCCD TM line sensor. device Effective pixels

Manual for Fire Suppression & Methane Detection System

Fire & Security DETECTORS

12 Volt 30 Amp Digital Solar Charge Controller Installation & Operation Manual

8900 EMR (WITH DETECTOR)

Roof Top Air Conditioner INSTALLATION AND OPERATING INSTRUCTIONS

4.3-inch Back-Up Camera

TS93 EMR T/PT/TDE. Surface applied door closer

Product and functional description

Clear Glass Sensor. Ordering Information E3S-CR67/62. Optimum Sensor for Detecting Transparent Glass and Plastic Bottles

Color Mark Sensor with Red or Green LED E3S-VS

Radiant Temperature Sensor TY7321

Capacitive Prox E2K-X

tidesmarine Smart Seal Temperature Alarm System Generation II Installation Instructions Starboard side cable

USER GUIDE. Studio Hotline Multi-line System Phone Flasher and Door/Alert Indicator Input Module and Indicator. DM Engineering. Version 1.

Operating Instructions. Room temperature controller

Combi B Alarm box. Mounting instructions

2M IR Mini Dome Quick Installation Guide

SECURITY CAMERA INSTRUCTION MANUAL ENGLISH VERSION 1.0 LBC

MOUNTING AND OPERATING INSTRUCTIONS

Determine the desired location fixture and center the coaxial cord location to the electrical box.

Modular I/O System Analog and Digital Interface Modules

TECHNICAL INFORMATION

EVC40 EMERGENCY VOICE COMMUNICATION SYSTEM

Arecont Vision H.264 Color or Day/Night SurroundVideo Series Installation Manual

GST301. (Single Protection Zone) Operation Manual

Analogue addressable devices

FCC COMPLIANCE STATEMENT FOR AMERICAN USERS


Product and Application Description

OPERATING INSTRUCTIONS

Smoke detector 500 Series The art of invisible fire detection

Table of Contents. What to Expect with. Preparation. Tools Needed. Wiring. Hanging the Fan. Blades. Motor Housing.

Duct Humidity Transmitter

2013 Wireless Video Intercom INSTALLATION GUIDE

MODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE

Smoke Detectors Ordering Information DS230 DS230 Series Heat Detectors DS230F DS233F Peripheral Accessories EOL200 TP280 Bases Features

Digital Keypad Use s Manual

BBWX1 Satellite Weather Receiver. Installation and Maintenance Guide

Installation instruction do88 Intercooler for Volvo S40 / V50 / C30

1. SAFETY RULES WARNING TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK OR PERSONAL INJURY, MOUNT FAN TO OUTLET BOX MARKED "ACCEPTABLE FOR FAN SUPPORT".

GE Wireless Devices Battery Replacement

Thermal-Magnetic Circuit Breaker M1-..

Solar Home System. User Manual. AEH-SHS01-10W2L Solar Home System 2 Lamps

BUSINESS. Elektronisches Türschloss. Installation and User Manual. Ingeniously safe. Ingeniously simple.

Installation Instructions. Thermo Call TC3

Small Building Life Safety Solutions. GE Security. Affordable FireShield Conventional Fire Alarm Control Panels. imagination at work

Stove Guard Kit User Manual

AMPSEAL* Automotive Plug Connector and Header Assembly

COLOR VIDEO DOOR PHONE CDV-71BE/D

TrueAlarm Fire Alarm Systems

How To Read A Pipe From A Sensor

CM705B - Universal Expander Module CM707B - Plug On Zone Expander Security Systems

How To Power A Power Control On An Ip40 (Ipl) With A Power Supply (Iplug) With An Ip20 Controller (Iphones) With Power Control (Power Control) With No Antenna) With The Ip20 (Power)

WIRELESS SENSOR BATTERY REPLACEMENT INSTRUCTIONS For Safewatch Residential and Small Business Control Panels

Connecting the Channel A

FIRE ALARM SYSTEM TECHNICAL SPECIFICATIONS Page 1 of 10

Owner s Guide and Installation Manual. Vancouver Model Name , Model No. English Español

ALARM SYSTEM INSTALLATION GUIDE

Installation Instructions. ThermoCall TC4. Entry/Advanced

Smoke Detector PSD 2 & 4 Wire Units

Miniature High-Resolution Registration Mark Sensor White LED AUTOSET Remote Setup Option

GAERTNER SCIENTIFIC CORPORATION 3650 Jarvis Ave. Skokie, Illinois U.S.A. tel: fax: @gaertnerscientific.

COMPALARM AP GENERAL MAIN FEATURES

SECTION FIRE ALARM AND SMOKE DETECTION SYSTEMS

Shunt lock function 3066

SFC-200 SERIES FIRE ALARM CONTROL PANELS. SFC-200 Series Fire Alarm Control Panels. Features. Description

ASSEMBLY MANUAL SE-4S35

DUCT SMOKE DETECTOR D4120

MAINTENANCE & TROUBLESHOOTING

User s Manual Before using the inverter, you need to read and save the safety instructions.

SECTION FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines

Model 201 Wiegand Touchpad Reader Installation Guide

Y7230A CO 2 Alarm System

Chromalox. Installation, Operation. Portable Industrial Unit Blower Air Heater Type DRA RENEWAL PARTS IDENTIFICATION

Water Leak Detector BA/LDT Accessories Termination and Troubleshooting

FC18 Controller(Interlocking) Product Manual

ABB Stotz-Kontakt GmbH ABB safe&smart Project planning of security systems

Fire Alarm System Plans Review Checklist Property location Date of Review

SECTION G2: CABLE PROCESSOR MODULE MAINTENANCE

08. SEK IDC CONNECTORS

Fire detection equipment

AUTODIALLER / QUICKDIALLER - SA132

162 CB CABLE TRACER. Filter Probe & Tone Generator INSTRUCTION MANUAL

LIEBERT VNSA Installation Sheet

RayClic Connection System Installation Instructions

Transcription:

Detector Color Detector transparent with Color Inserts FAA 500 TR W Trim Ring FAA 500 TR P Trim Ring transparent with Color Inserts FAA 500 BB Ceiling Mount Back Box FCA 500 / FCA 500 E Detector Bases Photoelectric Detector Photoelectric Detector with Carbon Monoxide Detection The CO sensor has not been evaluated to the requirements of UL 2075 or for its ability to detect a fire. Page 1 of 6

1. Specifications Models: Photoelectric Detector with Carbon Monoxide Detection: FCP 500 C Color 4.998.150.703 FCP 500 C P transparent with Color Inserts 4.998.150.705 Photoelectric Detector only: FCP 500 Color 4.998.150.702 FCP 500 P transparent with Color Inserts 4.998.150.704 Operating Voltage: 9.7 V DC to 30 V DC Current Consumption: Standby Alarm/Trouble FCA 500 / FCA 500 with DRA 5 3 ma / 3 ma 47 ma / 52 ma FCA 500 E / FCA 500 E with DRA 5 24 ma / 24 ma 47 ma / 58 ma Alarm Output: Alarm resistance 680 or 0 (US only) Remote LED Output: maximum 20 ma Rating of trouble/alarm relay: 1 A @ 30 V DC Reset Time: The detector resets if power is interrupted for at least 2 sec. Max. Start up Time: 22 sec Sensitivity: 1.3...2.9 %/ft (4.3... 9.5 %/m) Mounting Locations: Refer to NFPA 72 guidelines. Maximum Mounting Height: Refer to NFPA 72 guidelines. Minimum Mounting Height: 9.0 ft (2,7 m) Maximum Thickness of False Ceiling: 1.25 in. (32 mm), flush mount applications only Minimum Clearance for False Ceiling: 6 in. (15.2 cm) Required Hole 5 1 / 16 in., tolerance 1 / 16 in. to + 3 / 16 in. (130 mm, tolerance 1 mm to +5 mm) Minimum Distance from Lamps: 1.6 ft (0.5 m) Maximum Airflow: 300 ft/min (1.5 m/s) Operating Temperature: +32 F to +100 F (0 C to +38 C) Humidity: < 95% (non condensing) Protection Category (IEC 60 529): FCP 500 C and FCP 500 C P: IP 33 FCP 500 and FCP 500 P: IP 53 Dimensions: Detector only: 4.5 in. x 2.2 in. (113 mm x 55 mm) Detector with Trim Ring: 5.9 in. x 2.2 in. (150 mm x 55 mm) Detector with Trim Ring and Base: 5.9 in. x 2.75 in. (150 mm x 70 mm) with base Compliance: UL 268 Options: Included: Ceiling Mount Back Box for US FAA 500 BB UL F.01U.510.767 Four Wire Base FCA 500 4.998.151.300 Four Wire EOL Base FCA 500 E 4.998.151.301 Trim Ring, FAA 500 TR W 4.998.151.295 Trim Ring, transparent with Color Inserts FAA 500 TR P 4.998.151.296 Optional: Remote LED Annunciator DRA 5 Test Adapter with Magnet FAA 500 TTL F.01U.508.725 Removal Tool FAA 500 RTL F.01U.508.720 The CO sensor has not been evaluated to the requirements of UL 2075 or for its ability to detect a fire. The FCP 500 C and FCP 500 C P detect CO as a component of a fire. Do not use the FCP 500 C and FCP 500 C P as CO detectors. Page 2 of 6

2. Installation Considerations For proper installation, read and understand NFPA 72, The National Fire Alarm Code before installation. Caution: Do not remove the plastic film from the detector head until construction of the installation area is finished. Protect the detector sensor windows from paint or contaminates. Remove the detector head during remodelling and store it in a clean dry location. If you do not follow these cautions, the detector might not operate. Detector Location and Spacing: BOSCH recommends spacing the sensors in compliance with NFPA 72. In low air flow applications with smooth ceilings, space sensors with a maximum distance of 30 ft. For specific information regarding sensor spacing, placement and special application refer to NFPA 72. Detector Not suitable for outdoor use. Ceiling Do not install in areas where the detector is pointed at direct or ÏÏÏÏÏÏÏÏÏÏÏ indirect sunlight. ÏÏÏÏÏÏÏÏÏÏÏ Do not mount detector in a cone of light from a lamp. ÏÏÏÏÏÏÏÏÏÏÏ Maintain a hemispherical radius of at least 19 in. (50 cm) around the detector (see Fig. 1). ÏÏÏÏÏÏÏÏÏÏÏ Insure that this area in front and to the sides of the detector is ÏÏÏÏÏÏÏÏÏÏÏ kept clear of all obstructions (see Fig. 1). Further Considerations: Fig. ÏÏÏÏÏÏÏÏÏÏÏ 1 Free space Only use end of line (EOL) resistors supplied or specified by the control panel manufacturer. Smoke detectors are not to be used with detector guards unless the combination has been evaluated and found suitable for that purpose. This detector must be installed in compliance with the control panel system installation manual. Install, test and maintain this device according to this installation guide, NFPA 72, Local Codes and the Authority Having Jurisdiction (AHJ). Failure to follow these procedures may cause the device to not function properly. Bosch Security Systems is not responsible for any devices that are improperly installed, tested or maintained. 3. Installation Dismantling Detector 1. Push on the center of the detector s front plate. The detector head springs out of the base. 2. Remove the detector head from the base. 3. Lift the trim ring by the edge to remove it from the base. 4. Loosen the four screws holding the base to the backbox. 5. Turn the base counter clockwise until the screws line up with the large end of the slots. Remove the base from the back box. 19 in.(50 cm) Inserting Color Rings (FCP 500 C P and FCP 500 P) 1. Select a color. 2. From the selected color, insert the largest color ring in the trim ring. 3. Remove the detector front plate: Insert the enclosed small opener tool (2) into the slot (3) above the snap fit (1) and secure it with your thumb. Grasp the edges of the detector front plate, push gently, turn counter clockwise, and lift. 4. From the selected color, insert the larger color ring in the outer ring, and the smaller color ring in the inner ring of the detector front plate(see Fig. 3). 5. Replace the front plate cover. Ensure the tabs on the cover align with the grooves in the detector head. The cover will lie flat on the detector head. 6. Turn the cover clockwise to lock it into place. Note: If the cover aligns properly, all the sensor openings in the detector head are clearly exposed. 1 Fig. 2 2 3 Ceiling Mount Back Box (FAA 500 BB UL) For installation, refer to the FAA 500 BB UL Installation Guide (P/N 601 F.01U.003.008). Fig. 3 Page 3 of 6

Wiring the Base (FCA 500 and FCA 500 E) In applications which require UL listed units, the power of all connections (detector power, trouble and alarm relay) must be taken from power limited supplies when the cable is carried through the grommets. Please check with the local authorities to insure mounting without the conduit connector is allowed. Note: Do not twist or loop the wires around the terminals. The wires for terminal connection must be cut, stripped, and inserted as individual ends. Use the cable holders on the base for strain relief for the wires. EOL resistor: For the last base on the stub line (FCA 500 E), place the EOL resistor between the two screw clamps (see Fig. 4). Alarm resistor: If neccessary, change the alarm contact resistance from 0 to 680 by breaking off the printed circuit board tongue (see Fig. 4). Table 1: Wiring Connections (Inner Ring for Conventional) Connection Terminal Wire Alarm relay b1/b2 yellow (normally open) a1/a2 Shielding not used Indicator output c Voltage + +V red Voltage + +V red Voltage 0V black t 0 (not connected) Trouble relay (normally closed) t 1 (common) * green t 2 (normally closed) green * Connect terminal b1/b2 of the last detector base with terminal t 1 of the first detector base of the stub (see blue wire in the diagram). For 680 Ω break off alarm resistor here! Connection terminals Holder for cable ties Lettering on conventional connections Fastening slot EOL resistor Fig. 4 Fig. 5 to Power Supply FCA 500 red FCA 500 red FCA 500 E black black red yellow green green blue to Control Panel Fig. 6 Mounting the Base (FCA 500 and FCA 500 E) 1. Insert the base in the back box so that it fits over the four screws. 2. Turn the base clockwise until it stops to lock it in place. 3. Repeat steps 1 and 2 if you install multiple detectors in a line. 4. Slightly turn each base until the mark on the base aligns with the other detectors marks (see Fig. 7). 5. Tighten the screws with the supplied wrench. Alignment mark Fig. 7 Page 4 of 6

Inserting the Detector Head 1. Remove the protective film from the detector head. 2. Snap the trim ring into place on the base. 3. Place the detector head in the base and turn it until the detector head drops into the alignment grooves. 4. Push the center of the detector until it locks into place. It clicks and springs up. Start up 1. Check the wiring from the control panel to the last head on the run for proper polarity and continuity. 2. Make sure each run terminates with an EOL resistor as specified by the control panel manufacturer. 3. Apply power to the system. Check for alarm and troubles. 4. If single detectors alarmed or went in trouble, check if there is a free space of at least 19 in. (50 cm) around these detectors. If the problem persists, replace these detectors or swap them with known good units. If also the good units alarm or go in trouble, the sensitivity may have been affected by the surrounding environment. Recheck if there are any obstructions around the detector which may reflect the light emitted by the detector. 5. Switch the dry reed contact of every detector within the installation with a magnet (see Section 5., Dry Reed Contact and Section 6., Electronical Function Test ) for at least 10 sec until the detector alarms. Then reset the detector by removing the power for at least 2 seconds. After the reset, the detector will adjust its operating baseline in dependence of the surrounding environment.. Make sure that no objects or obstructions (like the test tool SOLO330 itself) are ahead of the detector during reset. After installation, the operating baseline must be adjusted once at every detector to the correct level. If there are any obstacles ahead of the detector when resetting an alarm caused by the Electronical Function Test (see Section 6.), the sensitivity of the detector may be affected. 6. Perform the sensitivity test described in Section 7. at every detector. 4. Maintenance and Service Trained personnel should perform a visual and physical test according Table 2 as recommended by NFPA 72 (National Fire Alarm Code). For cleaning the detector surface, use a common window cleaner and a soft, clean cloth. Notify all concerned parties before any maintenance or testing of the fire alarm system, and after completion of these activities. Note: The FCP 500 C and FCP 500 C P must be replaced every five years. The chemical (CO) sensor turns off at five years of operation. The LED double flashes every 8 to 12 sec, indicating trouble, and the detector continues to function as an optical (O) detector. Table 2: Testing Detector Test Steps FCP 500 FCP 500 P Detector Type FCP 500 C FCP 500 C P 1 Check the LED (see Table 3) X X 2 Check the detector s mounting X X 3 Visually check for damage or contamination of the detector surface X X 4 Check the area for factors (such as lightening) that could inhibit the detector s performance X X 5 Perform Electronic Functional Test (see Section 6.) X X 6 Perform Sensitivity Test (see Section 7.) X X 7 Test the optical detector (see Section 8.) X X 8 Test the CO detector (see Section 9.) X Table 3: LED Operation Status Normal Alarm Trouble Test mode LED green, flashes every 8 sec red, steady green, double flash every 8 to12 sec green, flashes once every second Page 5 of 6

Notify all concerned parties before any maintenance or testing of the fire alarm system, and after completion of these activities. 5. Dry Reed Contact 1. Place the test tool with the FAA 500 TTL test adapter with magnet up against the detector head. 2. Turn the test tool until the magnet activates the dry reed contact (see Fig. 8). Normally the green LED flashes once every 8 to 12 sec. When the dry reed contact activates, the LED flashes once every second. 6. Electronic Functional Test 1. Activate the dry reed contact (Section 5, Dry Reed Contact). 2. Leave the magnet on the test tool by the dry reed contact for 10 sec. Count 10 flashes of the LED. The detector activates a test alarm and the LED turns red. CO sensor (only FCP 500 C detectors) LED Fig. 8 dry reed contact 7. Sensitivity Test 1. Activate the dry reed contact (Section 5, Dry Reed Contact). 2. Leave the magnet on the test tool by the dry reed contact for 5 sec. Count 5 flashes of the LED. 3. Remove the test tool. Refer to Table 4 for the LED Display. Table 4: Sensitivity Test LED Display Number of Red LED Flashes Detector s State 1 to 3 Operating normally with little or no dirt contamination 4 to 6 Dirty, needs immediate cleaning 7 to 10 Trouble condition, very dirty, clean and check detector immediately 8. Smoke Test for the FCP 500 / FCP 500 P Note: No testing gas is required! For testing use only: Test tool for optical smoke detectors Solo 330 (product ID 4.998.112.071) with FAA 500 TTL test adapter with magnet (product ID F.01U.508.725) 1. Activate the dry reed contact (Section 5., Dry Reed Contact). 2. Leave the magnet on the test tool by the dry reed contact for at least 2 sec and not more than 4 sec. Count two flashes of the LED. The detector stays in test mode for 60 sec. The green LED blinks once a second. 3. Hold the test tool under the detector so that the test beaker is flush with the trim ring. Note: Do not tip the test tool, or the detector might come loose. 4. By covering the scattered light areas, both optical sensors are triggered simultaneously (no O testing gas is required). 5. This can take up to 20 sec. An alarm activates and the red LED lights. If the panel is in test mode, the alarm resets automatically. 9. CO and Smoke Test for the FCP 500 C / FCP 500 C P The CO sensor has not been evaluated to the requirements of UL 2075 or for its ability to detect a fire. The FCP 500 C and FCP 500 C P detect CO as a component of a fire. In dependence of the measured CO concentration the sensitivity of the smoke sensor is adjusted. Perform the CO sensor test once a year to confirm that the sensor is functioning. Note: For testing use only: Test tool for optical smoke detectors Solo 330 (product ID 4.998.112.071) with FAA 500 TTL test adapter with magnet (product ID F.01U.508.725) 1. Conduct step 1 to 5 of Section 8. (Smoke Test) to ensure that the smoke sensor is functioning. After this an alarm activates and the red LED lights steady. Don t reset the detector. 2. If over 70 ppm of carbon monoxide is applied to the detector, the red LED of the detector starts flashing. This indicates that the carbon monoxide sensor is working. 3. Reset the detector by removing the power. Bosch Security Systems 130 Perinton Parkway Customer Service: (800) 289 0096 Fairport, NY 14450 9199 Technical Support: (888) 886 6189 Page 6 of 6