Smoke Detector PSD 2 & 4 Wire Units



Similar documents
4-Wire Air Duct Smoke Detector. Protection Systems. A UTC Fire & Security Company. Models DH-60 FEATURES APPLICATION DESCRIPTION SAMPLING TUBES

Smoke Detectors Ordering Information DS230 DS230 Series Heat Detectors DS230F DS233F Peripheral Accessories EOL200 TP280 Bases Features

SECTION FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines

D7050/D7050TH. Installation Instructions. Multiplex Photoelectric Smoke Detectors

E-PDD Duct Smoke Detector Installation Sheet

DUCT SMOKE DETECTOR D4120

D287/D288/D292/D293A/D293E

FIRE ALARM AND DETECTION SYSTEMS SECTION 16721

Detector transparent with Color Inserts. FAA 500 TR P Trim Ring transparent with Color Inserts. FCA 500 / FCA 500 E Detector Bases

Protection Systems. A UTC Fire & Security Company F Linear Heat Detector FEATURES DESCRIPTION APPLICATIONS BENEFITS

SECTION ZONED (DC LOOP) FIREALARM SYSTEM

FIRE ALARM SYSTEM TECHNICAL SPECIFICATIONS Page 1 of 10

SECTION FIRE ALARM AND SMOKE DETECTION SYSTEMS

FIRE ALARM SYSTEM. A. Shop drawings shall be submitted as follows: 1. Manufacturer's published literature. for aspproval.

BELMONT FIRE DEPARTMENT FIRE ALARM SYSTEM REQUIREMENTS BFD-OFM

SMOKE DETECTOR INSTALLATION PROGRAM The Burlington Ordinance Perspective

IS3016A Passive Infrared Motion Sensor with Anti-Mask - Installation Instructions

FIRERAY 2000 Installation Guide

8900 EMR (WITH DETECTOR)

TrueAlarm Fire Alarm Systems

INTELLIGENT FIRE ALARM CONTROL PANELS. MR-2100/MR-2200 Intelligent Fire Alarm Control Panels MEA. Features. Description

(68.52) X. June 2000 Supercedes February xenex CONVENTIONAL FIRE DETECTION & ALARM SYSTEM. we business differently

Fire & Security DETECTORS

SECTION FIRE DETECTION AND ALARM SYSTEM PART 1 - GENERAL 1.01 DESCRIPTION

C. Conform to requirements of Americans with Disabilities Act (ADA).

SECTION FIRE ALARM AND DETECTION SYSTEM

Fire detection equipment

FSD Circular Letter No. 7/95 Automatic Fire Detection System - Design and Maintenance Considerations

FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL

ESL 500 Series. Smoke Detector. Installation Instructions

OPAL TM Detector range

DTW Works Master Specification Version 2006

EMF/EMR. Holder/Release Devices with Integral Door Closers

DH100ACDCLP Air Duct Smoke Detector with Extended Air Speed Range

Manual for Fire Suppression & Methane Detection System

FC-72 SERIES FIRE ALARM SYSTEM

Y7230A CO 2 Alarm System

Holder/Release Devices with Integral Door Closers DORMA EMF/ EMR

conventional system operation

Small Building Life Safety Solutions. GE Security. Affordable FireShield Conventional Fire Alarm Control Panels. imagination at work

HONEYWELL COMMERCIAL FIRE/BURG PANEL UL LISTING REQUIREMENTS (Compiled from VistaFBPT Installation Instructions V1 Rev A 11/12)

DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS

PowerCode Wireless. Fully supervised wireless system. Features

SMART SENSOR COLLECTION

ENGINEERING SPECIFICATIONS

Ventostat Wall Mount. Telaire Wall Mount CO 2. , Humidity and Temperature Transmitters. GE Measurement & Control. Features:

Fire Alarm System Plans Submittal Guidelines For New and Existing Systems

Carbon Monoxide (CO) Detection PRODUCTS. Accessories Conventional Detectors

SECTION FIRE ALARM AND DETECTION SYSTEMS

D4120 Duct Smoke Detector D4S Sensor Component D4P120 Power Board Component

Operating Instructions

SECTION FIRE ALARM AND DETECTION SYSTEM

Fire Control Panels. Remote Annunciator Panels. UL, ULC, CSFM Listed; FM Approved; MEA (NYC) Acceptance* Features. Introduction

AlarmLine Addressable Linear Heat Detector

Fire Alarm FAQs. Q: How many zone/circuit fire alarm panel do I need? Q: What candela strobes do I need?

DH100ACDCLWP Watertight Air Duct Smoke Detector with Extended Air Speed Range

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH CHEETAH Xi CONTROL PANEL

2.0 Installation 1. Remove the cover using a small flat blade screwdriver. Figure 2: Cover Removal

Life Alarm Fire Alarm Controls

SPECIFICATION FOR A TOTAL FLOOD HFC-227ea CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE Cheetah Xi CONTROL PANEL SYSTEM

LANTANA LUMINAIRE HI-LUME 1% ECOSYSTEM LED DRIVER L3DA4U1UMN-XXXXX

Release Control Fire Alarm Systems

HERNANDO COUNTY FIRE ALARM GUIDELINES

12S, 14S, 15S Series. Time Delay Relays and Sequencers. Time Delay Relays and Sequencers. Features and Benefits. Switch Actions and Configurations

INTRUSION DETECTION SYSTEM Section

D4120 Duct Smoke Detector D4S Sensor Component D4P120 Power Board Component

Model 201 Wiegand Touchpad Reader Installation Guide

FVSU REPAIR & UPGRADE FIBER OPTIC SECTION FIRE ALARM SYSTEM CONNECTIVITY

MODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE

QCS Section 23 Part 2 Fire Alarm and Detection Systems Page 1 2. FIRE ALARM DETECTION SYSTEMS...2

SP4-LOC SAFEPATH4 REMOTE MICROPHONE AND LOCAL OPERATOR CONSOLE

ESL 429/449 Series Self-Diagnostic Photoelectric Smoke Detectors Installation Instructions

CalMod Design-Build Electrification Services

Fire Alarm System Accessories

rpsa FIRE PROTECTION ENGINEERS

Industrial-Grade UPS System Heavy-duty power protection for harsh industrial environments

FAAST. Fire Alarm Aspiration Sensing Technology

University of Houston Master Construction Specifications Insert Project Name

SILENT KNIGHT MODEL 5207

SFC-200 SERIES FIRE ALARM CONTROL PANELS. SFC-200 Series Fire Alarm Control Panels. Features. Description

Water Leak Detection System

MINERVA MX MX Virtual Multi-Sensor Detectors

SECTION FIRE ALARM SYSTEM

Simon XTi Installation Guide

EDWARDS SIGNAL SOLUTIONS DISTRIBUTED BY: Lee Dan Communications, Inc. Toll-Free:

Commander 2000 Control Panel

Arc Terminator Active Arc-Resistant Switchgear

TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST

SLIM LINE FUME HOOD MONITOR

SECTION DETECTION AND ALARM

BERMAD Fire Protection

RI-215A Operator s Manual. Part Number: RK Revision 0 Released: 10/3/05

TS93 EMR T/PT/TDE. Surface applied door closer

NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems

Rancho Cucamonga Fire Protection District Prevention Bureau Standard

Operating Instructions

Motion Detector 360 Degrees 5420/360. Installation Instructions REGISTERED DESIGN REGISTERED PATENT

UNIFIED FACILITIES GUIDE SPECIFICATIONS

527 CMR: BOARD OF FIRE PREVENTION REGULATIONS

Transcription:

Smoke Detector PSD 2 & 4 Wire Units

Advanced Photoelectric Smoke Detectors Models PSD-7157 and PSD-7157D F-70.02 FEATURES Approvals/Listing US and Canadian UL Listed (culus) FM Approved CSFM Approved NYC MEA Accepted Dual Ionization Chamber Technology Nominal Sensitivity PSD-7157: 3.25% per ft. Obscuration PSD-7157D: 2.40% per ft. Obscuration Sensitivity Measurement/Testing Wireless Measurement in %/ft. Obscuration Remote and Local Functional Test Capability Wide Range of Input Voltage 10.2 to 36.8 Vdc Low Current Design Dual Response LEDs Allow 360-degree Viewing Trouble Indication Low Profile Appearance Using Surface Mount Technology Electrically and Mechanically Compatible with all Fenwal Smoke and Electronic Heat Detectors and Bases Interchangeable 2-Wire and 4-Wire Bases Universal Relay Modules Non Polarized Locking Feature for Vandal Resistance Fine Mesh Insect Screen EMI and RFI Resistant DESCRIPTION The Fenwal Models PSD-7157 and PSD-7157D Photoelectric Smoke Detectors respond to a broad spectrum of both flaming and smoldering fire conditions. The Detectors have advanced solid-state, low-voltage, surfacemount circuitry and are designed for 2-Wire and 4-Wire installation using the appropriate Detector base. The characteristic 360-degree detector design permits smoke entry from any direction. A unique sensing chamber design permits the operation of the Models PSD-7157 and PSD-7157D in open areas with air velocities from 0 to 300 fpm and 0 to 4000 fpm respectively. The Model PSD-7157D is also suitable for duct housing applications in air velocities from 500 to 4000 fpm. The Detectors are designed for open area/duct housing applications per UL268/UL268A and may be installed in systems intended for Releasing Device Service through use of compatible Fire Alarm Control Panels. TM Effective: May 2007 Protection Systems A UTC Fire & Security Company Two Red Light Emitting Diodes are located diametrically opposite each other so as to allow 360-degree viewing. Both LEDs continuously indicate the operating condition of the Detector. During standby, the LEDs flash once every six seconds. During alarm, both LEDs light steady at full brilliance. A double flash every six seconds indicates a detector with a sensitivity threshold outside acceptable limits. A unique gated output circuit design provides improved stability and transient suppression. Special signal processing techniques verify the presence of smoke before the detector will alarm. A fine mesh insect screen protects the chamber area and is used to avoid potential nuisance alarms. The detector head is installed into the base with a simple twist-lock action. A locking feature is provided for vandal resistant security. CONTROL UNITS The Models PSD-7157 and PSD-7157D Detectors are designed for operation with control units and releasing devices having specific voltage and current characteristics that are compatible with the detector circuitry. The Detectors are compatible with the Fenwal control units and interface modules listed in Table 1. DETECTOR BASE OPTIONS The Models PSD-7157 and PSD-7157D can be used with the detector base options and accessories in Tables 3 and 4. Various base options are available to provide auxiliary relay and/or remote indication and remote test feature. R

The Models PSD-7157 and PSD-7157D Photoelectric Smoke Detectors may be interchanged with other Fenwal Series THD-705X Electronic Heat Detectors and Series CPD-705X Ionization Smoke Detectors when using multifunction base configuration. SPACING (OPEN AREA LOCATION) The Models PSD-7157 and PSD-7157D Detectors are listed to be installed on maximum 30 foot (9.1 m) centers, typically on smooth ceilings up to 15 feet (4.6 m) high and will operate with minimum air circulation. Resultant maximum 900 square foot (83.6 m 2 ) spacing may be used as a reasonable guide for comparable applications. Where special conditions exist (ceiling obstructions, high air exchange rates, etc.), reduced spacing must be used to achieve adequate protection. Computer rooms and other such installations may require spacing with a maximum of 200 square feet (18.6 m 2 ) due to high air exchange rates. Detectors should not be located in areas with excessive exhaust fumes, kitchen areas, near fireplaces or furnace rooms and within three (3) feet (.9 m) of air supply ducts or air diffusers. For additional information, consult the Fenwal Automatic Fire Detection Application Engineering Manual MC-402, NFPA-72 and the local Authority Having Jurisdiction. WIRING DIAGRAMS For detailed wiring diagrams with Fenwal 2- and 4-wire bases, please refer Fenwal Document 70.104 INSTALLATION Detector bases are directly mounted on the electrical junction boxes (3-inch, 3-1/2-inch and 4-inch octagonal, 3-inch round or 4-inch square) (76 mm, 89 mm, 102 mm octagonal, 76 mm round or 102 mm square) without the need for any mechanical adapter required. Refer Fenwal Document 06-235056-001 for additional details. The detector bases also include a locking feature that prevents removal of the detector without use of a tool. TESTING AND MAINTENANCE Testing shall be performed upon installation of the detector and once a year thereafter as stated in NFPA-72 latest edition. Detector sensitivity shall be checked within one year of installation and every alternative year thereafter as stated in NFPA 72. Refer Fenwal Documents 06-236524-001 and 06-235056-001 for details on using the Infrared Wireless Sensitivity Tester Model DST-003. The tester provides direct readout in percent per foot obscuration from a distance of 15-feet without removing the detector from its base. A go/no-go test can be performed using a test magnet. The recommended requirement for detector maintenance consists of an annual cleaning of dust from the detector head by using the suction of a vacuum cleaner. Cleaning programs should be geared to the individual environment in conformance with NFPA 72. CAUTION Do not attempt disassembly of the factory sealed smoke detector. This assembly is sealed for your protection and should not be opened for servicing. Opening of the detector will void its warranty. SPARE PARTS The Models PSD-7157 and PSD-7157D Detectors are factory repairable only and have no field serviceable spare parts. No field repair should therefore be attempted. For service, return detector head intact to Fenwal. ARCHITECT/ENGINEER SPECIFICATIONS The contractor shall furnish and install where indicated on the plans, UL268/UL268A listed dual-chamber, Ionization Smoke Detectors, Fenwal Models PSD-7157 and PSD-7157D. Photoelectric Smoke Detectors containing a radioactive source of strength greater than 0.8 microcuries (29.6 kbq) shall not be acceptable. The combination detector head and twist-lock base shall be UL Listed compatible with a UL Listed fire alarm control unit. The Models PSD-7157 and PSD-7157D Photoelectric Smoke Detectors shall share interchangeable bases with the CPD-7054 and CPD-7054D Ionization Smoke Detectors and the THD-7052 and THD-7053 Heat Detectors. The Fenwal Models PSD-7157 and PSD-7157D Photoelectric Smoke Detectors shall have two Red LEDs located diametrically opposite each other so as to allow 360-degree viewing. The LEDs shall continuously indicate the operating condition of the Detector. During standby, the LEDs shall flash once every six seconds. During alarm, both LEDs shall light steady at full brilliance. If the sensitivity of the detector drifts outside acceptable limits, the LEDs shall double flash every six seconds. The detector may be reset by actuating the control panel reset switch. The vandal-resistant security locking feature shall be used in those areas as indicated on the drawings. The locking feature shall be field removable when not required. It shall be possible to measure the sensitivity of the Fenwal Models PSD-7157 and PSD-7157D Photoelectric Smoke Detectors from a distance of up to 15 feet (4.6 m) without removal from the base. Measurement shall be accomplished with a wireless infrared Fenwal Sensitivity Tester (DST-003) allowing direct measurement in percent - 2 -

per foot obscuration. Sensitivity measurement techniques requiring wiring between the Detector-Base combination and the Tester shall not be acceptable. It shall also be possible to perform a functional test of the detector without the need for generating smoke. The Fenwal Models PSD-7157 and PSD-7157D Photoelectric Smoke Detectors shall operate over an input voltage range from 10.2 to 36.8 Vdc. Voltage and RF transient suppression techniques to withstand up to 20 volt/meter shall be employed to minimize susceptibility to false alarms.. Table 1: Control Unit Control Unit Compatibility Identifier Number Maximum Detectors per Loop 2210/2212 C10FE1 40 2410/2412 C10FE1 40 2320 C30FE1 15 3210 ZDM01, ZDMD01, VZM01 25 3220 C32FE1 40 Note: Please refer to Document F-70-63 for compatibility with other Fire Alarm Control Panels. - 3 -

Table 2: Technical Specification Model Number PSD-7157 PSD-7157D Part Number 71-570000-001 71-570000-002 Detection Photoelectric Photoelectric Approvals culus, FM, CSFM, MEA-NYC culus, FM, CSFM, MEA-NYC UL Compatibility I.D. P55FE1 P55FE1 Listed Spacing 30 ft. (9.1 m) centers or 900 ft. 2 (83.6 m 2 ) 30 ft. (9.1 m) centers or 900 ft. 2 (83.6 m 2 ) Nominal Sensitivity Standby Voltage (Vdc) Using 2WB: Using 4WRB: 3.25% + 0.45% - 1.78% per foot Obscuration 10.2 to 36.8 16.8 to 36.8 2.40% + 0.04% - 1.34% per foot Obscuration 10.2 to 36.8 16.8 to 36.8 Maximum Current Standby: Alarm: 70 µa 100 ma 70 µa 100 ma Response Indicators Quantity: Standby Condition: Thermistor Trouble: Alarm Condition: Operating Environment Operating Temperature: Storage Temperature: Relative Humidity: 2 external LEDs One flash every 6 seconds Double flash every 6 seconds Steady at full brilliance 32 to 120 F (0 to 49 C) -20 to 180 F (-29 to 82 C) 0 to 93% Non-condensing 2 external LEDs One flash every 6 seconds Double flash every 6 seconds Steady at full brilliance 32 to 120 F (0 to 49 C) -20 to 180 F (-29 to 82 C) 0 to 93% Non-condensing Air Velocity Open Area: Duct Housing: Altitude: 0 to 300 fpm (0 to 1.5 m/s) N/A Up to 7,500 feet (2,286 m) 0 to 500 fpm (0 to 2.5 m/s) 500 to 4000 fpm (2.5 to 20 m/s) Up to 7,500 feet (2,286 m) Physical Characteristics Material and Finish: Weight: High-impact, flame-retardant plastic, off white 35.3 oz. (110g) w/o base High-impact, flame-retardant plastic, off white 35.3 oz. (110g) w/o base Dimensions Detector Height: Detector Diameter: Base Height: Base Diameter: 1-3/8 in. (35 mm) 3-29/32 in. (99 mm) 3/64 in. (11 mm) 5-29/32 in. (150 mm) 1-3/8 in. (35 mm) 3-29/32 in. (99 mm) 3/64 in. (11 mm) 5-29/32 in. (150 mm) - 4 -

Table 3: Detector Base Options Part Number Model CID Description 70-501000-001 2-Wire FE51A 2-W Base. Connects to circuit via screw terminals. 70-501000-002 2WRLT FE52A 2-W Base w/ Remote LED & Test capabilitiess. Connects to detection via screw terminals. Minimum Alarm Current 15 ma @ 24 Vdc. 70-501000-005 2WRB FE55A 2-W Base w/2wrm, Remote LED & Test capabilities.connects to detection circuit via pigtail leads. Minimum Alarm Current 19 ma @ 24 Vdc. 70-501000-101 4WRB N/A 4-W Base w/4wrm, Remote LED & Test capabilities. Connects to detection circuit via pigtail leads. Minimum Alarm Current 35 ma @ 24 Vdc. 70-500000-004 2WRM N/A SPDT Relay for 2WRB Bases. Contacts rated 1.0 A, 30 Vdc/0.5 A, 125 Vac. 70-500000-102 4WRM N/A SPDT Relay for 4WRB Bases. Contacts rated 1.0 A, 30 Vdc/0.5 A, 125 Vac. 70-501000-003 MA-001 MAFE1 Mechanical Adapter allows CPD-705X and PSD-715X Detectors to physically connect to Base P/Ns 70-201000-001, -002, -003, -005 & DH-22. Table 4: Ordering Information Part Number Model Description Detector Heads - Ionization Smoke 70-540000-001 CPD-7054 Ionization Advanced Smoke Detector (culus) : item discontinued!! 70-540000-002 CPD-7054D Ionization Advanced Smoke Detector (culus) : item discontinued!! Detector Heads - Photoelectric Smoke 71-570000-001 PSD-7157 Photoelectric Advanced Smoke Detector (culus) - our Standard!! 71-570000-002 PSD-7157D Photoelectric Advanced Smoke Detector (culus) Detector Heads - Heat 70-520000-001 THD-7052 135 F (57 C) Fixed Heat Detector, 15 F (-9 C) Rate of Rise (culus) 70-530000-001 THD-7053 135 F (57 C) Fixed Heat Detector (culus) Detector Bases 70-501000-001 2-Wire 2-Wire Standard Base 70-501000-002 2WRLT 2-Wire Base with Remote LED and Test Capabilities 70-501000-005 2WRB 2-Wire Base with Auxiliary Relay, Remote LED and Test Capabilities 70-501000-101 4WRB 4-Wire Base with Auxiliary Relay, Remote LED and Test Capabilies 70-500000-004 2WRM Spare 2-Wire Relay Module 70-500000-102 4WRM Spare 4-Wire Relay Module - 5 -

Table 4: Ordering Information (Continued) Part Number Model Description Detector Accessories 06-117883-001 Test Magnet 29-116788-001 EOL Supervisory Relay 70-200000-911 RA-911 Remote Alarm Indicator 70-200000-914 RA-914 Remote Alarm Indicator with Smoke Detector Switch 70-500000-003 DST-003 Advanced Handheld Wireless Smoke Detector Sensitivity Tester 70-501000-003 MA-001 Mechanical Retrofit Adapter TM R Protection Systems This literature is provided for informational purposes only. KIDDE-FENWAL, INC. assumes no responsibility for the product s suitability for a particular application. The product must be properly applied to work correctly. If you need more information on this product, or if you have a particular problem or question, contact LICO at office@lico.at or Tel +43 1 706 43 000. F-70.02 Rev AC 2007 Kidde-Fenwal Inc. Printed in USA TM Protection Systems LICO www.mess-regeltechnik.at office@lico.at Tel +43 1 706 43 000 office@lico.hu Tel +36 23 520 113 office@lico.ro Tel +40 365 807 497