Information for HFO-1234yf Automotive Plant and Service Shop Implementation



Similar documents
Low-GWP Refrigerants for Air Conditioning and Refrigeration Applications. Samuel F Yana Motta

HFO-1234yf. A Low GWP Refrigerant For MAC. Honeywell / DuPont Joint Collaboration February, 2008

International Refrigerant Standards and their Influence on the Global HVAC Industry and Refrigerant Replacement

Low Global Warming Fluids for Replacement of HFC-245fa and HFC-134a in ORC Applications

The ADREA-HF CFD code An overview

Low GWP Replacements for R404A in Commercial Refrigeration Applications

Risk Assessment of Residential Heat Pump Systems Using 2L Flammable Refrigerants

Certification in the safe and efficient use of alternative refrigerants

Guidelines for Use and Handling of HFO-1234yf

APPLICATION OF QUALITATIVE AND QUANTITATIVE RISK ANALYSIS TECHNIQUES TO BUILDING SITING STUDIES

Evaluation of HFO-1234yf as a Potential Replacement for R-134a in Refrigeration Applications

TOXIC AND FLAMMABLE GAS CLOUD DETECTORS LAYOUT OPTIMIZATION USING CFD

Safety issues of hydrogen in vehicles Frano Barbir Energy Partners 1501 Northpoint Pkwy, #102 West Palm Beach, FL 33407, U.S.A.

RGC-IR Remote Gas Calibrator for IR400

Part A: Fluid properties

Modeling and Simulation of HVAC Faulty Operations and Performance Degradation due to Maintenance Issues

The Behaviour Of Vertical Jet Fires Under Sonic And Subsonic Regimes

AMCA International. Investigation of the Impact of Building Entrance Air Curtain on Whole Building Energy Use AIR MOVEMENT AND CONTROL

STTH1R04-Y. Automotive ultrafast recovery diode. Features. Description

GAS DISPERSION WITH OPENFOAM

HFO-1234yf. A Low GWP Refrigerant For MAC. Honeywell / DuPont Joint Collaboration

EzFlex Combustible Gas Leak Detector Model EZ40

Using CFD in Platform Design

Ultrasonic Gas Leak Detection

HCFC-22 Retrofits. There has been increased emphasis on retrofitting R-22

EU f-gas regulation EN 517/2014.

Environmental and Safety Impacts of HFC Emission Reduction Options for Air Conditioning and Heat Pump Systems

Case Studies: Infrared Heating in Industrial Applications

PDS5100H. Product Summary. Features and Benefits. Mechanical Data. Description and Applications. Ordering Information (Note 5) Marking Information

Math 115 Extra Problems for 5.5

Improving Data Center Energy Efficiency Through Environmental Optimization

TSM2N7002K 60V N-Channel MOSFET

Battery Thermal Management System Design Modeling

LM135-LM235-LM335. Precision temperature sensors. Features. Description

DESIGN OF NATURAL VENTILATION WITH CFD CHAPTER SEVEN. Qingyan Chen. difficult to understand and model, even for simple

P3.8 INTEGRATING A DOPPLER SODAR WITH NUCLEAR POWER PLANT METEOROLOGICAL DATA. Thomas E. Bellinger

CHAPTER 4: OFFSITE CONSEQUENCE ANALYSIS

Vehicle Maintenance Facilities Requirements for CNG and LNG Vehicles

AC : MATERIAL SELECTION FOR A PRESSURE VESSEL

Commercial Garages, Repair, and Storage

MATERIAL SAFETY DATA SHEET

AE R6 December Digital Capacity Control for Copeland Scroll Refrigeration Compressors AE R6

COLORADO APCD IR Camera Survey Program Guidance/Protocol (rev. 11/8/11)

PSAC/SAIT Well Testing Training Program Learning Outcomes/Objectives Level D

SINTEF Energy Research Life Cycle Climate Performance (LCCP) of Mobile Air-Conditioning Systems

CNG & Hydrogen Tank Safety, R&D, and Testing

Consequence Analysis: Comparison of Methodologies under API Standard and Commercial Software

Thermal Mass Availability for Cooling Data Centers during Power Shutdown

FEASIBILITY OF A BRAYTON CYCLE AUTOMOTIVE AIR CONDITIONING SYSTEM

Tools & Equipment Robinair

Energy efficiency and fuel consumption of fuel cells powered test railway vehicle

FAC 2.1: Data Center Cooling Simulation. Jacob Harris, Application Engineer Yue Ma, Senior Product Manager

THEORETICAL AND EXPERIMENTAL EVALUATION OF AUTOMOBILE AIR-CONDITIONING SYSTEM USING R134A

HAZARDOUS AREA CLASSIFICATION OF LOW PRESSURE NATURAL GAS SYSTEMS USING CFD PREDICTIONS

3.1 MAXIMUM, MINIMUM AND INFLECTION POINT & SKETCHING THE GRAPH. In Isaac Newton's day, one of the biggest problems was poor navigation at sea.

Eco Pelmet Modelling and Assessment. CFD Based Study. Report Number R1D1. 13 January 2015

INITIAL ASSESSMENT OF THE IMPACT OF JET FLAME HAZARD FROM HYDROGEN CARS IN ROAD TUNNELS AND THE IMPLICATION ON HYDROGEN CAR DESIGN

EE-SPY801/802. Photomicrosensors for detecting wafer-carrier mounting. Wafer-carrier Mounting Photomicrosensors. Ordering Information.

How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions

Major Hazard Risk Assessment on Ammonia Storage at Jordan Phosphate Mines Company (JPMC) in Aqaba, Jordan

How To Plan For A Mobile Payment System

HVAC Technologies for Building Energy Efficiency Improvements 2013 National Symposium on Market Transformation. Richard Lord Carrier Fellow

Refrigerant System for Vehicle Air- Conditioning NISSAN / ZEXEL. Phoenix Alternate Refrigerant Forum June,28----July,1 Phoenix, AZ

Application Engineering

MAHLE Aftermarket now also offers Behr HVAC service units.

SOLIDWORKS SOFTWARE OPTIMIZATION

CFD AND MULTI-ZONE MODELLING OF FOG FORMATION RISK IN A NATURALLY VENTILATED INDUSTRIAL BUILDING

MOSFET N-channel enhancement switching transistor IMPORTANT NOTICE. use

Development of a model for the simulation of Organic Rankine Cycles based on group contribution techniques

NUD4011. Low Current LED Driver

STTH2R06. High efficiency ultrafast diode. Features. Description

PROPANE AUTOGAS REPAIR AND MAINTENANCE FACILITY REQUIREMENTS

A car air-conditioning system based on an absorption refrigeration cycle using energy from exhaust gas of an internal combustion engine

HP switch LP switch Discharge thermo Comp. Surface thermo

How High Temperature Data Centers and Intel Technologies Decrease Operating Costs

Automobile Air Conditioning Primer

Modeling Guide for Daikin VRV in EnergyPro 6

Access Server Rack Cabinet Compatibility Guide

Principles of Ventilation. Patrick N. Breysse, PhD, CIH Peter S.J. Lees, PhD, CIH Johns Hopkins University

Air-Conditioning Buying Guide

1 Form A Solid State Relay

Handheld Shock Control Design Guide

CAN DEMAND CONTROLLED VENTILATION REPLACE SPACE HEATING IN OFFICE BUILDINGS WITH LOW HEATING DEMAND?

Refrigeration and Air Conditioning with Reduced Environmental Impact

Ultra Coolant. The Best Performance. The Best Cost. The Best Coolant.

Fire & Explosion Risks in Service Stations

STPS5L60. Power Schottky rectifier. Description. Features

CHAPTER 3. BUILDING THERMAL LOAD ESTIMATION

Optocoupler, Phototransistor Output, with Base Connection

Unique Airflow Visualization Techniques for the Design and Validation of Above-Plenum Data Center CFD Models

Compressed Gas Cylinder Safety

The Kinetics of Atmospheric Ozone

Gas Discharge Tubes GTCX36-XXXM-R05 Series

Engineers Newsletter. HVAC Refrigerants: A Balanced Approach. providing insights for today s hvac system designer. volume Refrigerant History

Transcription:

Information for HFO-1234yf Automotive Plant and Service Shop Implementation Mary Koban, Automotive Sr Technical Engineer DuPont Fluoroproducts, Wilmington,DE

2 Agenda HFO-1234yf Properties Flammability Comparison OEM Plant Implementation Strategies Potential Service Implementation Needs CFD AC Leak Modeling CFD Results Summary

HFO-1234yf Properties 3 Same operating conditions as 134a (similar P/T curve) 3.5 Vapor Pressure Thermally stable under extreme use conditions in a MAC system Pressure (MPa) 3 2.5 2 1.5 1 0.5 REFPROP Equation Of State available HFC-134a HFO-1234yf Cooling capacity equivalent to 134a Energy efficiency better or equivalent to 134a Only modest design changes required in MAC Temperature, o C 0-40 -20 0 20 40 60 80 100 HFO-1234yf has vapor pressure, toxicity class A, similar to R-134a, but has mild flammability

Flammability Comparison 4 HFO-1234yf flammability characteristics are milder than those of hydrocarbon gases or other commonly used products within the service repair shop.

HFO-1234yf Automotive OEM Plant Implementation 5 Strategy employed will depend on location, volume, potential amount of refrigerant in area, potential leak scenarios, etc.

Potential EU Automotive Plant Implementation Strategies 6 Various HFO-1234yf plant implementation strategies can be employed. It is important to consult with appropriate regulatory agencies regarding strategies and limitations

EU Service Shop Potential Implementation Needs Depending on the service shop (size of shop, amount of refrigerant used, regional/country regulations) a risk assessment may need to be performed. - While HFO-1234yf is very similar to R-134a, it is mildly flammable and this will need to be considered during usage - Local, regional or country regulations may require storage limits, etc, and may also require risk assessments (flammable products routinely used in automotive) Therefore, understanding potential service leak scenarios will be valuable for any necessary service risk assessments and subsequent service implementation. Methods for automotive plant and service risk assessment are outlined in SAE J1739 and soon to be published ISO 13043. -These standards suggest that potential ignition scenario events should be considered in risk assessments. To successfully develop and understand potential ignition scenarios, it is helpful to determine potential flammable zone if release occurred during service. 7

HFO-1234yf Automotive Service Implementation- Potential Leakage Scenarios 8 CFD-Computational Fluid Dynamics DuPont conducted CFD modeling to understand potential flammable region of a leak from a severed AC line under various leakage scenarios Three Scenarios evaluated 1. Leak from a point in open space (simulating vehicle with potential leak sitting outdoors) 2. Leak from a point in bounded space (simulating potential leak in garage or mfr plant) 3. Leak from a point under an open car hood and impinging on a surface (in a service garage) CFD Model Output Refrigerant concentration at several distances (x,y and z directions) from the leak point during leak event. Size of refrigerant plume above lower flammability limit (LFL) Results useful as input for risk assessments

CFD MODEL DEVELOPMENT- Service Shop 9 Assumptions for all three scenarios 600 g total refrigerant leaked 12.4 g/s of HFO-1234yf total time of leak 48.4 secs Air exchange rate was zero, or low wind field (<0.5 m/sec) for unbounded leak Release Details HFO-1234yf will create a two phase leak when released under a severed line situation. The release plume was modeled as vapor phase, since initial modeling did not show large differences in shape of jet plume

Diagram of Scenario-Leak in Garage 10 Dimensions of a single bay garage (7 x 4 x 3 m). Leak source pointsevered A/C line Refrigerant plume Small holes at bottom of box keep pressure from building up Release modeled as bounded vapor release using referenced paper Venetsanos, A. G., et al, An inter-comparison exercise on the capabilities of CFD models to predict the short and long term distribution and mixing of hydrogen in a garage

Leak in Garage- Leak does not hit surface 11 10 vol% 6.3 vol% 4.0 vol% 2.5 vol% 1.6 vol% Below 1.0 vol% Time of leak t=48.0 sec Lower conc c=1 vol% (light blue) ACH rate r=0 Plume extends approximately 1.0 m from release point

Plume Profile Bounded Leak HFO-1234yf Conc. >10 vol% 10 vol% 6.3 vol% 4.0 vol% 2.5 vol% 1.6 vol% 12 Air Velocity >100 m/sec 100 m/sec 10 m/sec 1.0 m/sec 0.1 m/sec meters Below 0.1 m/s Plume above LFL is very small (10 cm in x direction, 2 cm in z)

Plume Profile Bounded Leak Impinged on a Surface (0.1m) HFO-1234yf Concentration 13 Distance to surface = 0.1m 10 vol% 6.3 vol% 4.0 vol% 2.5 vol% 1.6 vol% Below 1.0 vol% Plume is continually dispersed by surface, almost no flammable zone available

Diagram of Scenario Leak Impinges on Surface (Car Hood) 14 Dimensions of a single bay garage (7 x 4 x 3 m) Surface that leak impinges upon Leak source severed A/C line Small holes at bottom of box keep pressure from building up

Leak in Garage- Leak does hit surface 15 Distance to surface = 0.1m 10 vol% 6.3 vol% 4.0 vol% Time of leak t=48 sec ACH rate r= 0 2.5 vol% 1.6 vol% Below 1.0 vol% Plume continually dispersed by surface, almost no flammable zone available

Leak in Garage- Leak does hit surface 16 Distance to surface = 0.22m 10 vol% 6.3 vol% 4.0 vol% 2.5 vol% Time of leak t=48 sec ACH rate r= 0 1.6 vol% Below 1.0 vol%

Leak in Garage- Leak does hit surface 17 Distance to surface = 0.85m 10 vol% 6.3 vol% 4.0 vol% 2.5 vol% Time of leak t=48 sec ACH rate r= 0 1.6 vol% Below 1.0 vol% Plume fully formed but less extension vs non-impingement case

CFD Model Results 18 Actual results will depend on the size/shape of the hole and direction of the release versus air currents. Resultant refrigerant plumes are highly affected by distance to impinging surface. When the leak is in a garage and does not hit a surface, the plume is about 1m from the leak point. The flammable portion is 10 cm in x direction, 2 cm (+/-1 cm) in z direction When the leak source is within 0.1 m from the surface, the plume is continually dispersed by surface. There is almost no flammable zone available and the flammable zone extends about 2-4 cm from the leak point When leak source is within 0.22 m from surface, there is quick initial plume dispersion, then the plume feeds back within itself. There is almost no flammable zone available and the flammable zone extends about 2cm from the leak point When the leak source is within 0.85 m from surface, the plume is formed, but there is less extension of the plume versus the non-impingement scenario. Flammable portion is <10cm x direction

Summary 19 OEM Implementation Three basic potential automotive OEM plant implementation strategieshave been listed along with a high-level overview of potential automotive implementation strategies. Different refrigerant implementation methods can be employed. Service Implementation Depending on the service shop (size of shop, amount of refrigerant used, regional/country regulations) a risk assessment may need to be performed. - While HFO-1234yf is very similar to R-134a, it is mildly flammable - Local, regional or country regulations may be different for usage limits, storage, etc, which may also require risk assessments Understanding potential service leak scenarios will be valuable for any necessary service risk assessments and subsequent service implementation. CFD modeling was used to simulate releases of HFO-1234yf under some potential air-conditioning (A/C) line rupture scenarios. Refrigerant concentration was determined as a function of distance from the leak point during the leak event. The size and shape of the portion of the refrigerant plume above the lower flammability limit (LFL) was also noted. Results from all simulations show an extremely small flammability envelope, on the order of centimeters.

20 More information can be found at: www.refrigerants.dupont.com www.smartautoac.com Author contact information: mary.e.koban@usa.dupont.com Thank You! Disclaimer: The information set forth herein is furnished free of charge and based on technical data that DuPont believes to be reliable. It is intended for use by persons having technical skill, at their own risk. Since conditions of use are outside our control, DuPont make no warranties, expressed or implied and assume no liability in connection with any use of this information. Nothing herein is to be taken as a license to operate under, or a recommendation to infringe any patents or patent applications.