HCFC-22 Retrofits. There has been increased emphasis on retrofitting R-22
|
|
|
- Gervase Kelly
- 10 years ago
- Views:
Transcription
1 HCFC-22 Retrofits A c l o s e l o o k a t t h e r e f r i g e r a n t / l u b r i c a n t i n t e r a c t i o n s. B y S a m u e l F. Y a n a M o t t a, E l i z a b e t D. V e r a B e c e r r a, R o n V o g l a n d M a r k W. S p a t z All images courtesy of Honeywell International. There has been increased emphasis on retrofitting R-22 systems; this applies to both air-conditioning and refrigeration systems. Some end-users are performing retrofits without considering all the effects of the refrigerant change. Of particular concern are the blends of HFC with small amounts of hydrocarbons (HFC/HC blends). Some of these blends claim to be the best match to R-22 even when used with the existing mineral oil. There are differences between the performance of these refrigerants and the original R-22. In short, the systems under consideration for retrofit were designed to operate with R-22 and mineral-based oil. The HFC/hydrocarbon blend R-422A includes a small amount of hydrocarbon (isobutane), which is added to a mixture of HFC refrigerants (R-125, R-134a). Hydrocarbons that are Figure 1 Miscible and immiscible conditions. 14 RSES Journal MAY 2013 Mineral Oil Some end-users are performing retrofits without considering all the effects of the refrigerant change. miscible with mineral oils thin the mineral oil, helping its return back to the compressor. However, the small amount of HC included in R-422A does not make the blend itself miscible with mineral oils. Furthermore, the amount of hydrocarbon that can be added is typically limited to a few % to maintain an A1 (non-flammable) ASHRAE rating. Fundamentals definitions Solubility When applied to refrigerants and lubricant oils used in refrigeration systems, solubility is the property of the refrigerant (solute) to dissolve in the lubricant oil (solvent). The extent of the refrigerant solubility in the oil without seeing two phases is known as the saturation concentration. Immiscibility/Miscibility When the refrigerant reaches its solubility limit in the lubricant oil, adding more refrigerant results in precipitation, or phase separation, and this is typically referred to as an immiscible condition. On the other hand when you can keep adding refrigerant to the lubricant oil and still have a single liquid phase, it means that the refrigerant is fully miscible in the oil.
2 Practical cases of miscibility Refrigeration systems are usually designed for refrigerant/lubricant oil pairs that are fully miscible, or that otherwise show acceptable miscibility, at least at the concentration of lubricant oil circulating in the system and in the coolest parts of the system, but preferably over the range of operating conditions (evaporating and condensing temperatures). This will ensure proper oil return to the compressor as the refrigerant is able to carry the oil through the system. As for what is found in the field, Figure 1 shows the two most common cases: 1. A typical case of full miscibility is observed with R-22 and mineral oil. It is also observed with R-407C in POE oil. 2. On the opposite side, R-407C was found to be immiscible with mineral oil. This is also the case with the HFC/HC blend R-422A, which has some improved solubility due to the hydrocarbon presence. Still, it is fundamentally immiscible in mineral oil. System After Oil Separator Before Oil Separator Low Temperature 0.36% 0.47% Medium Temperature 0.05% 0.17% Table 1 Oil circulation ratio measured in a supermarket refrigerant: R-22 / oil: mineral oil. How much oil is in circulation in real systems? What is actually happening in a refrigeration system depends on several factors, for example: 1. Working fluids (refrigerant, lubricant); 2. Hardware (compressor type and age, connecting lines, heat exchangers, oil separators); and 3. Operating conditions. All systems have lubricant in circulation and the type and amount of lubricant varies with the above-listed parameters. Table 1 shows results of field studies performed in supermarket systems. The two supermarket systems studied used reciprocating compressors that were 10 years old on average. Samples were taken before and after the oil separators. This would allow studying systems with and without an oil separator. These findings show the worst-case scenario being low-temperature systems where the oil circulation ratio, or OCR, Circle Reader Service No. 39 MAY 2013 RSES Journal 15
3 can be as high as 0.47% when no oil separator is used, and 0.36% when using an oil separator (see Table 1). It can be concluded that systems with oil separators have lower OCRs than systems with no oil separators. Nevertheless, few old-wear compressors where OCR values were as high as 3.5% were also observed. Such compressors should be replaced, but this hardly happens in practical applications, as detecting these high OCRs is difficult. Even higher values are also mentioned in the field (e.g. up to around 8%), but no detailed description of the compressor type and age is usually shown. Figure 2 Pressure-drop penalty due to excessive oil hold-up in the suction line when using HFC/HC blend R-422A. Refrigerant/oil relationship in systems What happens in simple systems without a liquid receiver? Figure 3 Observations and results for a horizontal liquid receiver when working with the three refrigerants indicated and mineral oil. Outlet Inlet 16 RSES Journal MAY 2013
4 Refrigerant Inlet OCR (% by weight) Horizontal Receiver Outlet OCR (% by weight) R % 0.40% R-407C 0.40% 0.00% R-422A 0.40% 0.33% Table 2 Oil circulation ratio measured before and after the high-side liquid receiver for R-22, R-407C and R-422A with mineral oil. To investigate the effectiveness of the HFC/HC blend R- 422A, an R-22 low-temperature refrigeration system that uses mineral oil was used as a baseline. Both oil retention in vertical riser and the resultant pressure drop were measured. Overall, the system performed adequately with no significant drop in oil level in the compressor. R-422A was tested next. Figure 2 shows the additional pressure drop due to oil retention in vertical suction lines when employing this HFC/HC blend (R-422A) with the same mineral oil. The OCR simulated in this test was of 3.5% (oil in the refrigerant flow by weight). Oil retention was 30% higher than for R-22. Moreover, pressure drop was 70% mtwfsusa.com DON T MISS US AT NRA MAY BOOTH 3401/3601 Overachieving undercounter Presenting NEO, the everywhere you need ice machine. By providing increased levels in performance, intelligence and convenience, Manitowoc s new ice machine offers an all-in-one solution to your undercounter ice cube needs Manitowoc Ice All Rights Reserved Thirsty for more? Talk with Manitowoc Ice ManitowocIce.com/NEO Overachieve_7.125x4.875.indd 1 Circle Reader Service No. 40 4/11/13 8:04 AM MAY 2013 RSES Journal 17
5 Figure 4 Capacity and cop penalty due to mineral oil circulating in the system with ocr up to 3.5%. higher. In looking at these results, one could conclude that systems with no liquid receiver may be successfully retrofitted to this HFC/HC blend (R-422A) if the system is close coupled and the oil circulation rate is low enough. Still, the overall performance will be affected due to the additional pressure drop in the suction line, and also due to oil logging in the evaporator, which can negatively affect heat transfer and pressure drop. What happens in systems with high-side liquid receivers? As mentioned before, the small amount of hydrocarbon used in the HFC/HC blend R-422A is not enough to make it fully miscible with mineral oils. This is clearly shown in high-side liquid receivers where a significant retention of mineral oil is observed. These studies (Figure 3) show that a layer of oil will form on the surface of the liquid R-407C or HFC/HC blend R-422A. These studies were done using a horizontal liquid receiver, which was modified to add large sight glasses in the two extremes. Tests were done using oilcirculation values for a system with an oil separator (Table 2). The OCR values shown were measured by sampling before and after the liquid receiver. Looking at the imbalance of OCRs for R-407C and the HFC/HC blend R-422A (OCR at inlet higher than OCR at outlet), one can conclude that these blends are not reliable for retrofitting systems that use mineral oil as lubricant. Performance Some HFC blends such as R-407C come close to duplicating R-22 s performance at certain operating conditions, however a closer look will show that both the system capacity and efficiency may have been impacted due to oil circulation. 18 RSES Journal MAY 2013 Figure 4 shows how much the performance is affected because of the presence of oil in circulation. These tests were performed in a 1.8-ton refrigeration system. Three cases were considered: R-22/MO, R-407C/MO and R-422A/MO. The initial tests were performed using two very-high-efficiency oil separators so OCR was near zero. These initial points represent the performance of each fluid without any oil effects. When oil is taken into account, all the refrigerants experience some reduction of capacity and efficiency. Even R-22 would suffer some degradation when oil accumulates in the suction line for usual OCRs (1% 2%). Moreover, with the HFC/HC blend R-422A, a more dramatic degradation was observed, as more oil accumulates in the system, causing an increase of pressure drop. General guidelines/conclusions Giving a general recipe for R-22 retrofits is not possible, but general recommendations are possible, from the results of these studies, and other in-house technical knowledge: Air-conditioners and refrigeration systems without liquid receiver According to these studies, the least demanding system would be a typical air-conditioner without a liquid receiver where the main effects would be on the connecting lines. In general, the effects would not be as dramatic due to the relatively high evaporating temperatures (example: 45 F SST). At these conditions, any solubility of the refrigerant like R-422A in the oil will be reasonable. Next, refrigeration systems without a liquid receiver were considered, where the additional challenge is the fact that the evaporating temperatures can be significantly lower (example:
6 Giving a general recipe for R-22 retrofits is not possible, but general recommendations are possible, from the results of these studies, and other in-house technical knowledge. -25 F SST). In these systems, the HFC/HC blend R-422A can be used, because the compressor will get the desired oil return. Still, the user will experience some performance degradation as shown in the previous section (see Figure 3). Refrigeration systems with high-side liquid receiver Next in the degree of difficulty are systems with a high-side liquid receiver. These systems will need a greater degree of solubility in the oil, which could not be provided by the HFC/HC blend R-422A that were studied. In these cases, based on this work, adding some amount of POE oil would help to increase solubility to the point to get the oil through the liquid receiver. Tests indicated that at least 20% of the oil system needs to be of the POE type. Heat pumps with low-side suction accumulator Even more difficult are the systems with a low-side suction accumulator where the liquid accumulation occurs at low temperatures and pressures. At these conditions, any solubility of the refrigerant in the oil will be reduced. For these types of systems, a greater degree of solubility is needed. Based on this work, a full change to POE oil would advisable for refrigerants such as R-407C and R-422A. In conclusion, there is no perfect replacement for R-22. These findings indicate that the performance of certain HFC and HFC/HC blends, namely R-407C and R-422A, can be impacted by the type and amount of oil in circulation (OCR). If economically feasible, a change to POE oil will result in the best system performance, durability and trouble-free operation for refrigerants such as R-407C and R-422A. As for the HFC/HC blend R-422A, some specific A/C and refrigeration systems (no liquid receivers or suction accumulators) have been identified where they can be cautiously used. Still users should be aware of some system performance impact coming from this choice. DISCLAIMER: Although all statements and information contained herein are believed to be accurate and reliable, they are presented without guarantee or warranty of any kind, expressed or implied. Information provided herein does not relieve the user from the responsibility of carrying out their own tests and experiments, and the user assumes all risks and liability for use of the information and results obtained. Statements or suggestions concerning the use of materials and processes are made without representation or warranty that any such use is free of patent infringement and are not recommendations to infringe on any patents. The user should not assume that all toxicity data and safety measures are indicated herein or that other measures may not be required. Samuel F. Yana Motta, Refrigerants R&D Leader; Elizabet D. Vera Becerra, Engineer R&D; Ron Vogl, Refrigerants Marketing Manager; and Mark W. Spatz, Refrigerants Technology Leader, work with Honeywell International located in Buffalo, NY. The research discussed in this feature occurred at Honeywell s Buffalo Research Laboratory. For more information, samuel. [email protected] or visit Circle Reader Service No. 41 MAY 2013 RSES Journal 19
Low GWP Replacements for R404A in Commercial Refrigeration Applications
Low GWP Replacements for R404A in Commercial Refrigeration Applications Samuel YANA MOTTA, Mark SPATZ Honeywell International, 20 Peabody Street, Buffalo, NY 14210, [email protected] Abstract
Low-GWP Refrigerants for Air Conditioning and Refrigeration Applications. Samuel F Yana Motta
Low-GWP Refrigerants for Air Conditioning and Refrigeration Applications Samuel F Yana Motta Refrigerants for Stationary Applications HONEYWELL CONFIDENTIAL N Series L Series Current Product Reduced GWP
Repair, Retrofit, or Replace Choices for Servicing R-22 Equipment
Repair, Retrofit, or Replace Choices for Servicing R-22 Equipment Brett Van Horn Market Manager HVAC Arkema Inc. 900 First Ave King of Prussia, PA 19406 Topics Covered Today R-22 Phase-out EPA Allowances
Performance of R-438A in R-22 Refrigeration and Air Conditioning Systems
Performance of R-438A in R-22 Refrigeration and Air Conditioning Systems Dr. Charles C. Allgood 1, C. Curtis Lawson 2 1 DuPont Fluorochemicals, Wilmington, DE, USA E-mail: [email protected]
Performance of R-438A in R-22 Refrigeration and Air Conditioning Systems
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 21 Performance of R-438A in R-22 Refrigeration and Air Conditioning Systems
Environmental and Safety Impacts of HFC Emission Reduction Options for Air Conditioning and Heat Pump Systems
Environmental and Safety Impacts of HFC Emission Reduction Options for Air Conditioning and Heat Pump Systems William M. Corcoran, George Rusch, Mark W. Spatz, and Tim Vink AlliedSignal, Inc. ABSTRACT
RS-24 (R426A): Q & A
RS-24 (R426A): Q & A 1 Q: What is RS-24? A: RS-24 is a non ozone depleting Drop-in replacement for R12 in all applications including mobile air conditioning. 2 Q: Yes, but what does RS-24 contain? A: RS-24
RS-52 (R428A) RS-52: PHYSICAL PROPERTIES RS-52 R502 Molecular weight 107.5 111.6 Temperature glide o C 0.5 0.2 Boiling point (1 atm)
RS-52 (R428A) COMPOSITION % HFC 125 77.5 HFC 143a 20.0 R600a 1.9 R290 0.6 HCFC replacement Temperature glide R22, 502 & interim blends Approximately 0.8 o C Drop-in or long term Both Lubricant MO/AB/POE
Scroll compressors for Low GWP Heat Pumps using R290 natural refrigerant. Pierre Ginies, Next Heat Pump Generation 2015 p.ginies@danfoss.
Scroll compressors for Low GWP Heat Pumps using R290 natural refrigerant Pierre Ginies, Next Heat Pump Generation 2015 [email protected] Danfoss Commercial Compressors Leading compressor R&D and manufacturing
THE REPLACEMENT OF R-22
ENGLISH TRANSLATION OF ARTICLE IN FRIO-CALOR AIRE ACONDICIONDAO BY GAS-SERVEI, S.A JUNE 2010 THE REPLACEMENT OF R-22 Courtesy of D. Lluis Giralt Lopez (Chemical Engineering Industrial) Gas Technical Department
SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS
SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS 2009 Tecumseh Products Company. All rights reserved. Page 1 of 8 Refrigerant R22 is widely used for residential and commercial air conditioning, as
RS-44 (R424A) : Q & A
RS-44 (R424A) : Q & A 1 Q: What is RS-44? A: RS-44 is a non ozone depleting Drop-in replacement for R22 in most applications. 2 Q: Yes, but what does RS-44 contain? A: RS-44 is a blend of HFC134a, HFC125,
Analysis of Alternative Refrigerants to HCFC-22
2014 3rd International Conference on Informatics, Environment, Energy and Applications IPCBEE vol.66 (2014) (2014) IACSIT Press, Singapore DOI: 10.7763/IPCBEE. 2014. V66. 34 Analysis of Alternative Refrigerants
Refrigerant Changeover Guidelines R-22 to R-407C. Leading the Industry with Environmentally Responsible Refrigerant Solutions
Refrigerant Changeover Guidelines R-22 to R-407C Leading the Industry with Environmentally Responsible Refrigerant Solutions Copeland does not CFC advocate the wholesale changeover of HCFC HCFC refrigerants
How To Design A Refrigeration System
AIRAH Refrigeration (in HVAC) Back to Basics For the First Time Terms of Reference What this session is NOT about Detailed Refrigeration Design Detailed analysis of various Refrigants properties Comparison
Refrigerant Changeover Guidelines R-22 to R-407C. Leading the Industry with Environmentally Responsible Refrigerant Solutions
Refrigerant Changeover Guidelines R-22 to R-407C Leading the Industry with Environmentally Responsible Refrigerant Solutions Emerson Climate CFC Technologies, Inc. does not advocate the HCFC wholesale
PG Student (Heat Power Engg.), Mechanical Engineering Department Jabalpur Engineering College, India. Jabalpur Engineering College, India.
International Journal of Emerging Trends in Engineering and Development Issue 3, Vol. (January 23) EFFECT OF SUB COOLING AND SUPERHEATING ON VAPOUR COMPRESSION REFRIGERATION SYSTEMS USING 22 ALTERNATIVE
Refrigerant Changeover Guidelines HCFC R-22 to HFC R-404A/R-507. Leading the Industry with Environmentally Responsible Refrigerant Solutions
Refrigerant Changeover Guidelines HCFC R-22 to HFC R-404A/R-507 Leading the Industry with Environmentally Responsible Refrigerant Solutions Copeland does not advocate the wholesale changeover of HCFCs
STUDY OF LUBRICANT CIRCULATION IN HVAC SYSTEMS
STUDY OF LUBRICANT CIRCULATION IN HVAC SYSTEMS Volume I - Description of Technical Effort and Results Final Technical Report March 1995 - April 1996 Frank R. Biancardi H. Harvey Michels Tobias H. Sienel
REFRIGERANT REFERENCE GUIDE
REFRIGERANT REFERENCE GUIDE WORLWIDE REFRIGERANT SUPPLIER 2004 FOURTH EDITION 2004 DISCLAIMER This publication is designed to provide accurate and authoritative information. It is not to be construed as
Scroll Compressor Development for Air-Source Heat Pump Water Heater Applications
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2008 Scroll Compressor Development for Air-Source Heat Pump Water Heater Applications
R407C GUIDELINES FOR UTILIZATION OF. DATE: August 2009 REFERENCE DOCUMENT NO. RD-0005-E GUIDELINES FOR UTILIZATION OF R407C
GUIDELINES FOR UTILIZATION OF R407C 2009 Tecumseh Products Company. All rights reserved. Page 1 of 6 After many years of testing and investigation, R407C is recognized as a suitable alternative refrigerant
Mohan Chandrasekharan #1
International Journal of Students Research in Technology & Management Exergy Analysis of Vapor Compression Refrigeration System Using R12 and R134a as Refrigerants Mohan Chandrasekharan #1 # Department
Engineering Recommendation on: Accumulators Revised 6-17-99 Issued January 10, 1979 Page 1 of 7
Issued January 10, 1979 Page 1 of 7 Accumulators have long been recognized by the industry as an effective means of maintaining good system balance by storing excess refrigerant as the condenser or evaporator
UNIT 2 REFRIGERATION CYCLE
UNIT 2 REFRIGERATION CYCLE Refrigeration Cycle Structure 2. Introduction Objectives 2.2 Vapour Compression Cycle 2.2. Simple Vapour Compression Refrigeration Cycle 2.2.2 Theoretical Vapour Compression
Commercial refrigeration has been in the environmental. Refrigerant. as a. Basics Considerations PART 1:
PART 1: CO 2 Commercial refrigeration has been in the environmental spotlight for more than a decade, especially as leakage studies have revealed the true effects of hydrofluorocarbon (HFC) emissions.
Chapter 3.4: HVAC & Refrigeration System
Chapter 3.4: HVAC & Refrigeration System Part I: Objective type questions and answers 1. One ton of refrigeration (TR) is equal to. a) Kcal/h b) 3.51 kw c) 120oo BTU/h d) all 2. The driving force for refrigeration
A Performance Comparison of Vapour Compression Refrigeration System Using Eco Friendly Refrigerants of Low Global Warming Potential
International Journal of Scientific and Research Publications, Volume 2, Issue 9, September 2012 1 A Performance Comparison of Vapour Compression Refrigeration System Using Eco Friendly Refrigerants of
Troubleshooting an Air Conditioning system. R D Holder Eng. Roger D Holder MSME
Troubleshooting an Air Conditioning system R D Holder Eng. Roger D Holder MSME Troubleshooting of an air conditioning system is a step by step procedure. I have found that a 4 step procedure is the best
Todd M. Rossi, Ph.D. President
Residential Air Conditioning Fault Detection and Diagnostics (FDD) and Protocols to Support Efficient Operation DOE - Building America Program Residential Buildings Integration Meeting - July 20-22, 2010
Refrigerants for Residential and Commercial Air Conditioning Applications
Refrigerants for Residential and Commercial Air Conditioning Applications October 2008 Table of contents Executive summary 2 Introduction and background 3 Environmental drivers 4 Regulatory update 8 Criteria
Automobile Air Conditioning Primer
Automobile Air Conditioning Primer An air conditioner is basically a refrigerator without the insulated box. It uses the evaporation of a refrigerant, like Freon, to provide cooling. The mechanics of the
PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM WITH R404A, R407C AND R410A
Int. J. Mech. Eng. & Rob. Res. 213 Jyoti Soni and R C Gupta, 213 Research Paper ISSN 2278 149 www.ijmerr.com Vol. 2, No. 1, January 213 213 IJMERR. All Rights Reserved PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION
Impacts of Refrigerant Charge on Air Conditioner and Heat Pump Performance
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2010 Impacts of Refrigerant Charge on Air Conditioner and Heat Pump Performance
Patech. Our Conviction. Quality Service Innovation PATECH FINE CHEMICALS CO., LTD
Our Conviction Quality Service Innovation Product Categories Refrigeration Lubricants POE for HFC Refrigerants POE for HCFC Refrigerants POE for HFO Refrigerants Special Plasticizers Nontoxic Plasticizer
Refrigerant System for Vehicle Air- Conditioning NISSAN / ZEXEL. Phoenix Alternate Refrigerant Forum June,28----July,1 Phoenix, AZ
A CO 2 Refrigerant System for Vehicle Air- Conditioning NISSAN / ZEXEL Phoenix Alternate Refrigerant Forum June,28----July, Phoenix, AZ Outline ZEXEL Activities for Environment Protection 99 Model of CO
CONTAMINANT REMOVAL FROM CENTRIFUGAL SYSTEMS
CONTAMINANT REMOVAL FROM CENTRIFUGAL SYSTEMS BULLETIN 240-10-3 June 2004 Supersedes June 1983 Many centrifugal systems get little maintenance. As a result they operate with the refrigerant highly contaminated
Characteristics of Evaporators
Characteristics of Evaporators Roger D. Holder, CM, MSME 10-28-2003 Heat or Energy In this paper, we will discuss the characteristics of an evaporator coil. The variance of the operational condenses of
Estimation Method For Thermal Stability Of Refrigeration Oil And Automatic Sealed Glass Tube Processing Device
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2002 Estimation Method For Thermal Stability Of Refrigeration Oil And Automatic
A Comparison of an R22 and an R410A Air Conditioner Operating at High Ambient Temperatures
R2-1 A Comparison of an R22 and an R410A Air Conditioner Operating at High Ambient Temperatures W. Vance Payne and Piotr A. Domanski National Institute of Standards and Technology Building Environment
THEORETICAL AND EXPERIMENTAL EVALUATION OF AUTOMOBILE AIR-CONDITIONING SYSTEM USING R134A
THEORETICAL AND EXPERIMENTAL EVALUATION OF AUTOMOBILE AIR-CONDITIONING SYSTEM USING R134A Jignesh K. Vaghela Assistant Professor, Mechanical Engineering Department, SVMIT, Bharuch-392001, (India) ABSTRACT
2004 Standard For Performance Rating Of Positive Displacement Refrigerant Compressors And Compressor Units
2004 Standard For Performance Rating Of Positive Displacement Refrigerant Compressors And Compressor Units ANSI/AHRI Standard 540 (formerly ARI Standard 540) IMPORTANT SAFETY RECOMMENDATIONS ARI does not
Subject: 2005 Air Conditioning Service Guidelines
Date: June 27, 2005 Bulletin Number: 05D-J-114 To: DDG Headquarters and Branches and Jobbers Category: Service From: Steve Sigg, Product Service and Training Line(s): 10 and 15 Subject: 2005 Air Conditioning
Refrigerant Changeover Guidelines R-502 to R-402A/R-408A. Leading the Industry with Environmentally Responsible Refrigerant Solutions
Refrigerant Changeover Guidelines R-502 to R-402A/R-408A Leading the Industry with Environmentally Responsible Refrigerant Solutions Copeland does not advocate the wholesale CFC changeover of CFC HCFC
Rating Water-Source Heat Pumps Using ARI Standard 320 and ISO Standard 13256-1
Rating Water-Source Heat Pumps Using ARI Standard 320 and ISO Standard 13256-1 W. Vance Payne and Piotr A. Domanski National Institute of Standards and Technology Building and Fire Research Laboratory
Refrigeration and Airconditioning Prof. M. Ramgopal Department of Mechanical Engineering Indian Institute of Technology, Kharagpur
Refrigeration and Airconditioning Prof. M. Ramgopal Department of Mechanical Engineering Indian Institute of Technology, Kharagpur Lecture No. # 22 Refrigeration System Components: Compressor (Continued)
Chapter 2 P-H Diagram Refrigeration Cycle Analysis & Refrigerant Flow Diagram
Chapter 2 P-H Diagram Refrigeration Cycle Analysis & Refrigerant Flow Diagram Copy Right By: Thomas T.S. Wan 温 到 祥 著 Sept. 3, 2008 All rights reserved Industrial refrigeration system design starts from
Centrifugal Water Chillers. Scott Meyerkord
Centrifugal Water Chillers Scott Meyerkord Trane Account Manager Chilled Water System absorption centrifugal helical-rotary Centrifugal Water Chillers Centrifugal Water Chillers Components components of
SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS
SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS UNIT OBJECTIVES After studying this unit, the reader should be able to explain the purpose of the condenser in a refrigeration system. describe differences
Johnson Controls Parts Centre. Sabroe S68 refrigeration oil
Johnson Controls Parts Centre refrigeration oil Hydro-treated, high performance oil for refrigeration Sabroe offers the highest quality lubricants available for today s refrigeration market. The increased
Maintenance for Energy Efficiency
Maintenance for Energy Efficiency Institute of Hospital Engineering, Australia (IHEA) Seminar Asset Management & Energy Efficiency Exclusive Trane distributor Australia/New Zealand. The TRANE trade mark
Technical Note: Comparing R407C and R410A as Alternatives for R22. A Technical Note from the Experts in Business-Critical Continuity
Technical Note: Comparing R407C and R410A as Alternatives for R22 A Technical Note from the Experts in Business-Critical Continuity Purpose The purpose of this document is to provide a brief overview of
P08 Köldmedier med låg växthuseffekter
P08 Köldmedier med låg växthuseffekter Pavel Makhnatch Tranås, 17-18 May Reference: IPCC, 2013 3 4 5 Growth of climate change commitments from HFC banks and emissions Reference: Velders et al. 2014 6
ThermoStar Refrigeration Air Dryers
ThermoStar Refrigeration Air Dryers Why dry compressed air? Contamination Reduces Efficiency The air we breathe contains contamination in the form of water vapour and airborne particles. These problems
D A T A S H E E T. TX6 Thermo Expansion Valves. Alco Controls TX6. Features. Introduction. Construction
ALCO s series of Thermo -Expansion Valves are designed for air conditioning, chillers, rooftops, close control, A/C transportation, heat pumps, industrial cooling process and refrigeration applications.
How does solar air conditioning work?
How does solar air conditioning work? In a conventional air conditioning system; The working fluid arrives at the compressor as a cool, low-pressure gas. The compressor is powered by electricity to squeeze
A car air-conditioning system based on an absorption refrigeration cycle using energy from exhaust gas of an internal combustion engine
A car air-conditioning system based on an absorption refrigeration cycle using energy from exhaust gas of an internal combustion engine G Vicatos J Gryzagoridis S Wang Department of Mechanical Engineering,
TEST REPORT #31. System Drop-in Test of Refrigerant R-32 in Split Air-conditioning System
Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #31 System Drop-in Test of Refrigerant R-32 in Split Air-conditioning
How To Clean Water From An Ammonia Refrigeration System
Water Contamination and Water Removal in Industrial Ammonia Refrigeration Systems By Ray Ficker, PE Effects of Water Contamination Water contamination in an industrial ammonia refrigeration system can
Engineers Newsletter. HVAC Refrigerants: A Balanced Approach. providing insights for today s hvac system designer. volume 40 2. Refrigerant History
providing insights for today s hvac system designer Engineers Newsletter volume 40 2 HVAC Refrigerants: A Balanced Approach One of the constant themes throughout the history of the HVAC industry is the
It will be available soon as an 8.5 X 11 paperback. For easier navigation through the e book, use the table of contents.
The System Evaluation Manual and Chiller Evaluation Manual have been revised and combined into this new book; the Air Conditioning and Refrigeration System Evaluation Guide. It will be available soon as
Recommended Compressor Installation Practices
ASPEN COMPRESSOR, LLC Phone: 508.481.5058 Fax: 508.480.0328 Email:[email protected] Website: www.aspencompressor.com Recommended Compressor Installation Practices 1. COMPRESSOR SELECTION AND USE
TEST REPORT #44. System Drop-in Tests of Refrigerant R-32 in Single Packaged Vertical Heat Pump (SPVH)
Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #44 System Drop-in Tests of Refrigerant R-32 in Single Packaged
Update on a Low GWP Refrigerant: Fluid H
Update on a Low GWP Refrigerant: Fluid H Mark W. Spatz Global Leader Refrigerant Technology Honeywell Fluorine Products SAE 2007 Alternatives Refrigerant Systems Symposium July 17-19, 2007 1 Agenda Material
Lesson. 11 Vapour Compression Refrigeration Systems: Performance Aspects And Cycle Modifications. Version 1 ME, IIT Kharagpur 1
Lesson Vapour Compression Refrigeration Systems: Performance Aspects And Cycle Modifications Version ME, IIT Kharagpur The objectives of this lecture are to discuss. Performance aspects of SSS cycle and
Experimental Analysis of an Automotive Air Conditioning System With Two-Phase Flow Measurements
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering Experimental Analysis of an Automotive Air Conditioning System With Two-Phase
REFRIGERANT 410A. Refrigeration Service Engineers Society 1666 Rand Road Des Plaines, Illinois 60016. Information compiled by Frank Prah, CMS
Refrigeration Service Engineers Society 1666 Rand Road Des Plaines, Illinois 60016 REFRIGERANT 410A Information compiled by Frank Prah, CMS INTRODUCTION Recently a new refrigerant, R-410A, has been formulated
Evaluation Of Hybrid Air- Cooled Flash/Binary Power Cycle
INL/CON-05-00740 PREPRINT Evaluation Of Hybrid Air- Cooled Flash/Binary Power Cycle Geothermal Resources Council Annual Meeting Greg Mines October 2005 This is a preprint of a paper intended for publication
Low Global Warming Fluids for Replacement of HFC-245fa and HFC-134a in ORC Applications
Low Global Warming Fluids for Replacement of HFC-245fa and HFC-134a in ORC Applications *Honeywell, 20 Peabody St., Buffalo, NY USA 14210 e-mail: [email protected] Gary Zyhowski* and Andrew Brown
Guide to good leak testing
Page 0 Guide to good leak testing The Institute of Refrigeration, working with the Carbon Trust, brings you REAL Zero Refrigerant Emission and Loss Zero. The aim of this project is in the title zero refrigerant
Production of R-134a
Production of R-134a Background In the 1930 s, chlorofluorocarbons (CFC s) were developed as a supposedly safe alternative to ammonia and sulfur dioxide refrigerants. While sulfur dioxide is toxic and
Why and How we Use Capacity Control
Why and How we Use Capacity Control On refrigeration and air conditioning applications where the load may vary over a wide range, due to lighting, occupancy, product loading, ambient weather variations,
Ingersoll Rand. Heat-Of-Compression Air Dryers
Heat-Of-Compression Air Dryers Air Quality Solutions by Heat-of-compression (HOC) dryers are dual-tower, desiccant designs. The HOC dryer is the most energy-efficient dryer available. It recovers the heat
Part A: Fluid properties
UNEP Ozone Secretariat UNEP Ozone Secretariat Background Workshop Material on HFC for management: HFC Workshop, technical 2015 issues Bangkok, 20 and 21 April 2015 FACT SHEET 15 Glossary of terms and technical
8. Heat pumps, heat pipes, cold thermal energy storage
Kylteknik ( KYL ) Refrigeration course # 424503.0 v. 2014 8. Heat pumps, heat pipes, cold thermal energy storage Ron Zevenhoven Åbo Akademi University Thermal and Flow Engineering Laboratory / Värme- och
COMMERCIAL HVAC CHILLER EQUIPMENT. Air-Cooled Chillers
COMMERCIAL HVAC CHILLER EQUIPMENT Air-Cooled Chillers Technical Development Programs (TDP) are modules of technical training on HVAC theory, system design, equipment selection and application topics. They
HOW HVAC WORKS. How HVAC. Works PAGE 1
How HVAC Works PAGE 1 Heat - What is it? Heat is more than a physical concept - it is a feeling. Heat is taught to us at a very young age as a danger to be avoided. Yet, have you ever stopped and thought
DERON Air/Water Swimming pool Heat Pump. CY/DY series for Heating/Cooling. Description
Description Compact air/water heat pump for outside installation. With suction gas cooled rotary compressor. With extensive aluminium/cu lamellar tube evaporator and PVC Titanium condenser. Axial fan Refrigerant
UNDERSTANDING REFRIGERANT TABLES
Refrigeration Service Engineers Society 1666 Rand Road Des Plaines, Illinois 60016 UNDERSTANDING REFRIGERANT TABLES INTRODUCTION A Mollier diagram is a graphical representation of the properties of a refrigerant,
DESIGN OF AIR CONDITIONING SYSTEM IN AUTOMOBILE
DESIGN OF AIR CONDITIONING SYSTEM IN AUTOMOBILE Md Shahid Imam, Dr.M.Shameer Basha, Dr.Md.Azizuddin, Dr. K.Vijaya Kumar Reddy 4 M.Tech HVAC II Yr, Royal Institute of Technology & Science Chevella R.R Dist
Flushing and Cleaning the A/C System
Flushing and Cleaning the A/C System Once an AC system has been contaminated or has suffered a failure, the most important part of the AC service to restore the cooling performance to the system = FLUSHING
Refrigerant Charging Unit ICOGD. 020AH1000 Operating Manual. FR.8.2.4-09 İ-COLD 12.03.2014 Rev. 00
E Refrigerant Charging Unit ICOGD 020AH1000 Operating Manual FR.8.2.4-09 İ-COLD 12.03.2014 Rev. 00 Contents Technical Specifications... 20 Safety... 21 A/C System... 22 Components... 23 Control Panel...
AUTOMOTIVE AIR CONDITIONING
3rd Edition 3rd Edition Resources available For the instructor Register online at: www.cengagebrain.com for the study tools that come with your textbook! Companion website: includes weblinks and downloadable
SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM
SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop air conditioning unit (5 tons and smaller). 2. Roof curb. 1.2
Access Server Rack Cabinet Compatibility Guide
Access Server Rack Cabinet Compatibility Guide A Guide to the Selection and Evaluation of Access Server Rack Cabinets for Compatibility and Use with Third Party Server Chassis Kalkenstraat 91-93 B-8800
DEVELOPMENT OF A TWIN SCREW EXPRESSOR AS A THROTTLE VALVE REPLACEMENT FOR WATER-COOLED CHILLERS
DEVELOPMENT OF A TWIN SCREW EXPRESSOR AS A THROTTLE VALVE REPLACEMENT FOR WATER-COOLED CHILLERS J J Brasz, Carrier Corporation, Syracuse, NY, 13221, USA [email protected] I K Smith and N Stosic
How To Understand Evaporator
SECTION 5 COMMERCIAL REFRIGERATION UNIT 21 EVAPORATORS AND THE REFRIGERATION SYSTEM UNIT OBJECTIVES After studying this unit, the reader should be able to Define high-, medium-, and low-temperature refrigeration.
Refrigeration Basics 101. By: Eric Nelson
Refrigeration Basics 101 By: Eric Nelson Basics Refrigeration is the removal of heat from a material or space, so that it s temperature is lower than that of it s surroundings. When refrigerant absorbs
Refrigerant identification and equipment issues in relation to HCFC phase-out. Ole Reinholdt Nielsen
Refrigerant identification and equipment issues in relation to HCFC phase-out Ole Reinholdt Nielsen Belize, March 3, 2010 Outline Brief introduction; Refrigerant identification: Historically; Options for
ASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014
ASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014 Explanation of the refrigeration cycle. Compressors. Benefits and operating characteristics. -Reciprocating
THE POSSIBILITY OF USING LIQUIFIED PETROLEUM GAS IN DOMESTIC REFRIGERATION SYSTEMS
www.arpapress.com/volumes/vol9issue3/ijrras_9_3_02.pdf THE POSSIBILITY OF USING LIQUIFIED PETROLEUM GAS IN DOMESTIC REFRIGERATION SYSTEMS Zainal Zakaria 1 & Zulaikha Shahrum 2 Department of Gas Engineering,
PRETREATMENT TECHNICAL DATA SHEET WATER EMULSIFIABLE RUST PREVENTATIVE PRODUCT DESCRIPTION
INDUSTRIAL COATINGS RA260 WATER EMULSIFIABLE RUST PREVENTATIVE PRODUCT DESCRIPTION is water emulsifiable rust preventative oil, which provides outstanding corrosion protection for all phosphate metals.
Nordic Heat Pump Product Guide
Nordic Heat Pump Product Guide About Maritime Geothermal Maritime Geothermal is a privately owned, Canadian based manufacturer of geothermal heat pumps. We began manufacturing the Nordic line of heat pumps
2010 Report of the Refrigeration, Air Conditioning and Heat Pumps Technical Options Committee (RTOC)
2010 Report of the Refrigeration, Air Conditioning and Heat Pumps Technical Options Committee (RTOC) 2010 Assessment Montreal Protocol on Substances that Deplete the Ozone Layer Celebrating 25 years of
The Trouble with R407c
The Trouble with R407c You might find this a bit long winded, and certainly a bit controversial. What do you think? Please click on the link at the end. Trevor Dann ThermaCom Ltd - June 2003 The Trouble
D A T A S H E E T. TX3 Thermo Expansion Valves. Alco Controls TX3. Features. Introduction. Description of bulb charges
ALCO s TX3 series of Thermo -Expansion Valves are designed for air conditioning, heat pumps and commercial refrigeration applications. The TX3 is ideal for those applications requiring hermetic / compact
A/C refrigerant system, overview
Page 1 of 19 87-18 A/C refrigerant system, overview A/C refrigerant system, identification Typical A/C refrigerant system with expansion valve and receiver drier 1 - Evaporator 2 - Expansion valve 3 -
Laboratory Test Report for Fujitsu 12RLS and Mitsubishi FE12NA Mini-Split Heat Pumps
Laboratory Test Report for Fujitsu 12RLS and Mitsubishi FE12NA Mini-Split Heat Pumps Jon Winkler, Ph.D. September 2011 NOTICE This report was prepared as an account of work sponsored by an agency of the
In recent years, formicary corrosion has wreaked havoc on. Micro-channel
As seen in the October issue of Micro-channel Evaporator-coil Technology An overview of all-aluminum micro-channel evaporator-coil technology, including technical differences HVAC professionals need to