DIVISION 26 - ELECTRICAL SECTION 26 05 20 CABLES FOR INSTRUMENTATION

Similar documents
B. Cross-Connect: A facility enabling the termination of cable elements and their interconnection or cross-connection.

The Evolution of Copper Cabling Systems from Cat5 to Cat5e to Cat6 Copper Cabling Standards and Technical Aspects

SECTION VOICE AND DATA COMMUNICATION CABLING

Unarmored Variable Frequency Drive (VFD) Cable Termination Guide

DIVISION 27 COMMUNICATIONS. A. System design shall be completed by a Registered Communications Distribution Designer (RCDD).

Presenters Brett Weiss, Gabe Martinez, Brian Kroeger.

ANSI/TIA/EIA A, Commercial Building Telecommunications Cabling Standard.

TC Grounding and Bonding for Telecommunications Systems

Terminating 25-Pair Cable and 4-Pair Cross Connects

SECTION SIGNAL WIRE AND CABLE

SECTION COMMUNICATIONS HORIZONTAL CABLING

HOUSTON COMMUNITY COLLEGE HCC ALIEF CAMPUS MAIN BUILDING, FIRST, SECOND & FOURTH FLOORS RENOVATION ISSUE DATE:

HIGH SPEED COMMUNICATIONS PLENUM CABLE CATEGORY 5e CMP FEP JACKETED, PVC-FREE UNSHIELDED TWISTED PAIR (UTP)

AC and DC Drive System Installation Information

FTE Cabling Best Practices Author: Todd Bill, RCDD/NTS

SYSTIMAX SCS PowerSum and GigaSPEED XL Cabling Installation Guidelines

The National Armored Cable Manufacturers Association Presents. Installation Standard for Types AC and MC Cables

Chapter 4 Connecting to the Internet through an ISP

FIREFINDER XLS ADDRESSABLE FIRE ALARM SYSTEM SECTION 13851

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.

Innovative Connectivity Solution for Maximum Performance and Security

Specifying an IT Cabling System

East Central College HANSEN HALL LEVEL 300/400 RENOVATIONS PACKAGE

Cable Installation Project

READ THIS MANUAL BEFORE PROCEEDING WITH THE INSTALLATION. FAILURE TO FOLLOW THE INSTALLATION INSTRUCTIONS MAY VOID YOUR WARRANTY!

The Permanent Link in Field Certification Reasons, Advantages, Testing Challenges

CONTENTS. Yale University Design Standards. Underground Electrical Duct Bank. A. Summary. B. System Design and Performance Requirements

The Contractor shall furnish and install all shielded power cable suitable for use on this project.

SECTION /600 VOLT CABLE, WIRE AND CONNECTORS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: 1.2 DESCRIPTION OF WORK: 1.

Cable Products HONEYWELL SECURITY & CUSTOM ELECTRONICS. Honeywell's Genesis Series provides a full range

This paper will explain some of the more important factors on how UTP wires work; specifically it will cover the following:

E Series. E Series. Category 6 and 5e. Features

Standards Affecting a Premise T-1 Installation

STREETLIGHT SYSTEM GROUNDING AND BONDING

PANDUIT TX6 10GIG SHIELDED COPPER CABLING SYSTEM. Innovative Connectivity Solution for Maximum Performance and Security

Category 6 Solutions. 4. Category 6 Solutions. 09/ IN TrueNet Structured Cabling. Introduction Cable Patch Panels... 4.

B. PART 1 - GENERAL of SECTION BACKBONE COMMUNICATIONS CABLING shall also apply to this section.

Standard Buccaneer - Ethernet

RoHS DATA, COAXIAL AND ELECTRONIC M.R. D A TA, C O A X I A L, ECOLGICAL Telecom Cables A N D EL E CTRON I C. Cables

WIRE, TERMINAL AND CONNECTOR REPAIR CONDUCTORS

Requirements for Modular Patch Cords (e.g. RJ45 patch cords for Cat5 and Cat6 cabling systems)

LEAD FREE FIREX. Interlock Armored Cables TECK90 and MC Industrial Cables. w w w. n e x a n s e n e r g y. c o m

Specification SFTP CAT6 Network Cable 23AWG CU

Gigabit Ethernet on Copper Cabling Infrastructures

1.1 SYSTEM DESCRIPTION.1 Data system includes data outlets and wiring for office and school applications.

NORTH ORANGE COUNTY COMMUNITY COLLEGE DISTRICT SECTION STRUCTURE CABLING TESTING

SECTION TELECOMMUNICATION ROOMS

Communication, Signal & Data Cables

INDOOR PHONE INSTALLATION (CONCEALED) TECHNICAL SPECIFICATION

100% EMI Emission Containment

CIR. Index. Gexol. Standard CIR UL Listed Type TC-ER. Crush and Impact Resistant Without External Armoring. Arctic CIR UL Listed Type TC-ER-HL*

How to Choose the Right Cable Category

SUBJECT: NO MORE 300 VOLTS IN PLTC PRINT LEGEND

DEPARTMENTAL REGULATION

Electrical Grounding. Appendix C

IEEE POWER ENGINEERING SOCIETY CHICAGO CHAPTER THE OKONITE COMPANY WEDNESDAY JANUARY 11, 2006 JIM FITZGERALD ENGINEERING LINGO

Running 1000BASE-T Gigabit Ethernet over Copper Cabling 30 March 1999 Colin Mick/The Mick Group with Bruce Tolley/3Com and Willem Wery/Intel

SECTION LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES

with Component Rating A Simple Perspective

POWER DISTRIBUTION. Power and Undercarpet Products POWER AND UNDERCARPET PRODUCTS. Chapter Summary

CTI TECHNICAL BULLETIN Number 9: A publication of the Cable Tray Institute

Purpose of the ANSI/TIA/EIA-569-A Standard

Lightning Arresters P KVA P KVA. Description & Installation

Testing 10 Gb/s Performance of Category 6 and 6A Structured Copper Cabling Systems within the Unified Physical Infrastructure SM (UPI)

Session 2; Cabling Technology in the Data Centre Media Choices; Copper Twisted Pair

Chapter 9. Bonding and Grounding

1. Furnish and install faceplate and modular jacks at each single gang outlet as described below:

Security & Surveillance Cabling Systems

SECTION TELECOMMUNICATIONS SYSTEM (Cat 6)

Part 1: General Requirements TELECOMMUNICATIONS INDUSTRY ASSOCIATION

TECHNICAL SPECIFICATION

GUIDELINES HAS/PDC/DESIGN DIVISION TITLE

800 Communications Circuits

Outside Telephone Cable

Medium Voltage Electrical Distribution

Division 27 Master Specification for

SECTION LOW VOLTAGE LIGHTING CONTROLS

Ethernet Patch Cord Wiring

Panduit 28 AWG Patch Cords Installation Guideline

Generic Category 5e Cabling Specification

Building Cables and Wires

R&Mfreenet Advanced Cat 6 A Unshielded Connection Module

SPECIFICATION STANDARD OPTICAL FIBER BACKBONE CABLING

Network Design. Yiannos Mylonas

ELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS:

KSR-SK-DB In-Line Splice Kit KSR Snow Melting Cable INSTALLATION PROCEDURES

TELECOMMUNICATIONS STRUCTURED CABLING GUIDELINES AND SPECIFICATIONS. University of Chicago IT Services Infrastructure Services October 2011

ANSI/TIA-942 Telecommunications Infrastructure Standard for Data Centers

SECTION POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL

GUIDELINES FOR UTILITY INSTALLATIONS Part 1 - Wire Lines and Communications Cables

Specifications for Communication Cabling Distribution Systems

National Craft Assessment and Certification Program S P E C I F I C A T I O N S

CCNA Discovery Chapter Four

1 Campus Cabling Systems Introduction

ATT-TP Ethernet Copper Cable & Ethernet Copper Assembly Specification

6000 Series Buccaneer

Section Grounding and Bonding for Communications

Transcription:

DIVISION 26 - ELECTRICAL PART 1 - GENERAL 1.01 SUMMARY A. Section Includes 1. Instrumentation Cables 1.02 SUBMITTALS A. Submit in accordance with requirements of Section 01 33 00. B. Product Data: Submit for each type of product to be used. C. Field quality control test reports. D. Submit fiber optic cable installation plan 1. Cable pulling plan that specifies the sequence of work tasks, materials, and equipment. 2. Provide an optical link analysis for each fiber optic link. a. Calculate point-to-point (transmit/receive) optical power loss of each fiber link using proposed installed cable lengths. b. Include all losses through connectors. c. Submit calculated values including sketches graphically showing the proposed cable route. PART 2 - PRODUCTS 2.01 INSTRUMENTATION CABLES A. These cables shall be used for all analog signal wiring. B. Single Pair or Triad - Overall Shield 1. Conductors shall be single twisted pair or triad tinned copper with an overall shield. The insulation shall be rated at 300V. Conductors shall be bare soft annealed copper, Class B, 19 strand concentric. Insulation shall be 15 mil nominal thickness, 90 C temperature rating and flame retardant. 2. Cable shield shall be 1.35 mil blue aluminum-polyester tape overlapped to provide 100% coverage, and a 7 strand tinned copper drain wire, two sizes smaller than the conductor. Herbert, Rowland & Grubic, Inc. 26 05 20-1 UAJA Standard Specification

3. Overall jacket shall be flame retardant, 90 C temperature rated and UL listed. 4. The minimum size conductor shall be 18 AWG for shielded instrumentation cable unless otherwise noted. C. Multi Pairs or Triads - Overall Shield 1. Conductor shall be tinned copper, 19-strand concentric. Insulation shall be flame retardant PVC insulation, 15 mils nominal thickness and a nylon jacket, 4 mil nominal thickness rated 300 volts. Insulation shall have 90 C temperature rating per UL 1277. 2. Cable shield shall be 2.35 mil blue aluminum polyester tape overlapped to provide 100% coverage and a 7-strand tinned cover drain wire same as conductors. 3. Overall jacket shall be flame retardant, 90 C temperature rated and UL listed. 4. The minimum size conductor for shielded pairs or triad shall be 18 AWG unless otherwise noted. D. Acceptable Manufacturer 1. All instrumentation cable and conductors shall be as manufactured by Okonite Company, Belden Electronic Wire and Cable Company or equal. All instrumentation cable and conductors to be installed in cable trays shall be NEC approved for this use. 2.02 ETHERNET CABLE A. Unshielded Twisted-Pair Cabling 1. No. 24 AWG, 100 ohm, four pair. 2. Cable Jacket Color: Gray. 3. Comply with TIA/EIA-568-B.2, Category 5e 4. Comply with UL 444. 5. Belden Inc.; General Cable Technologies Corp, or Approved Equal B. Terminal Connectors: Modular, color-coded, RJ-45 plug. 1. AMP Company, Cooper Wiring Devices; or approved equal PART 3 - EXECUTION 3.01 SIGNAL AND CONTROL CABLE A. General Herbert, Rowland & Grubic, Inc. 26 05 20-2 UAJA Standard Specification

1. Size cable and its conduit to keep pulling tension within manufacturer's recommended limits. 2. Use cable of sufficient length to make a continuous run. Splicing of shielded signal cable will not be permitted. 3. Furnish a separate raceway system for shielded signal cable. Do not run in the same conduit with power cable. 4. Where telemetry cables are run in the same duct bank with power cables, use galvanized steel conduit. Use junction boxes and "LB" fittings in manholes to maintain a continuous steel raceway system for signal cables. 5. Ground cable shield at termination of instrumentation cabinet only using a soldered pigtail with spade lug for ground connection. Solder joint and ground connection should be visible. B. Telemetry and Instrumentation Signal Systems 1. Separate conduit and wireway runs are required for this category. All wiring is to be isolated from all power systems. C. Control Wiring 1. Control wiring may be pulled in the power conduits and wireways providing the highest voltage of the adjacent wires is not more than 120 volts. D. Power Control Systems 1. The wiring of this category (single conductor, or multiple conductor) is to be installed in accordance with the NEC. 3.02 ETHERNET CABLE A. Installation 1. Comply with NECA 1. B. Cable Installation: 1. Install exposed cables parallel and perpendicular to surfaces or exposed structural members and follow surface contours where possible. 2. Make splices, taps, and terminations only at indicated outlets, terminals, and cross-connect and patch panels. 3. Pulling Cable: Do not exceed manufacturer's written recommended pulling tensions. Do not install bruised, kinked, scored, deformed, or abraded cable. Do not splice cable between termination, tap, or junction points. Remove and discard cable if damaged during installation and replace it with new cable. Herbert, Rowland & Grubic, Inc. 26 05 20-3 UAJA Standard Specification

C. Conduit D. Testing DIVISION 26 ELECTRICAL 4. Secure and support cables at intervals not exceeding 30 inches and not more than 6 inches from cabinets, boxes, fittings, outlets, racks, frames, and terminals. 5. Install UTP cables using techniques, practices, and methods that are consistent with Category 5e rating of components and that ensure Category 5e performance of completed and linked signal paths, end to end. a. Do not untwist more than 1/2 inch of Categories 5e and 6 cables at connector terminations. 6. Separation from EMI Sources: Comply with BICSI TDM and TIA/EIA-569-A recommendations for separating unshielded copper voice and data communication cable from potential EMI sources, including electrical power lines and equipment. Comply with the following minimum separation distances from possible sources of EMI: a. Separation between unshielded power lines or electrical equipment in proximity to open cables or cables in nonmetallic raceways is as follows: 1) Electrical Equipment Rating Less Than 2 kva: 5 inches. 2) Electrical Equipment Rating between 2 and 5 kva: 12 inches. 3) Electrical Equipment Rating More Than 5 kva: 24 inches. b. Separation between unshielded power lines or electrical equipment in proximity to cables in grounded metallic raceways is as follows: 1) Electrical Equipment Rating Less Than 2 kva: 2-1/2 inches. 2) Electrical Equipment Rating between 2 and 5 kva: 6 inches. 3) Electrical Equipment Rating More Than 5 kva: 12 inches. c. Separation between power lines and electrical equipment located in grounded metallic conduits or enclosures in proximity to cables in grounded metallic raceways is as follows: 1) Electrical Equipment Rating Less Than 2 kva: No requirement. 2) Electrical Equipment Rating between 2 and 5 kva: 3 inches. 3) Electrical Equipment Rating More Than 5 kva: 6 inches. d. Electrical Motors and Transformers, 5 kva or HP and Larger: 48 inches. e. Fluorescent Fixtures: 5 inches. 1. Comply with TIA/EIA-569-A for maximum length of conduit and bends between pull points, and for pull-box sizing. 2. Use manufactured conduit sweeps and long-radius ells whenever possible. Herbert, Rowland & Grubic, Inc. 26 05 20-4 UAJA Standard Specification

1. Perform the following field tests and inspections and prepare test reports: 2. Category 5e UTP Cabling Tests: a. Test instruments shall meet or exceed applicable requirements in TIA/EIA-568-B.2. Perform tests with a tester that complies with performance requirements in Annex I, complying with measurement accuracy specified in Annex H. Use only test cords and adapters that are qualified by test equipment manufacturer for channel or link test configuration. b. Visually inspect cable placement, cable termination, grounding and bonding, equipment and patch cords, and labeling of all components. c. Wire-map test that reports open circuits, short circuits, crossed pairs, reversed pairs, split pairs, and improper terminations. d. Channel and permanent link tests for cable length, insertion loss, near-end crosstalk loss, power sum near-end crosstalk loss, equal-level far-end crosstalk loss, power sum equal-level far-end crosstalk, return loss, propagation delay, and delay skew. Performance shall comply with minimum criteria in TIA/EIA-568- B.2. 3. Data for each measurement shall be documented. Data for submittals shall be printed in a summary report that is formatted similar to Table 10.1 in BICSI TDM, or transferred from the instrument to the computer, saved as text files, and printed and submitted. 4. Remove and replace cabling where test results indicate that they do not comply with specified requirements. 5. Retest and inspect cabling to determine compliance of replaced or additional work with specified requirements. END OF SECTION Herbert, Rowland & Grubic, Inc. 26 05 20-5 UAJA Standard Specification