SECTION COMMUNICATIONS HORIZONTAL CABLING
|
|
|
- Marsha Rosalind Scott
- 9 years ago
- Views:
Transcription
1 SECTION PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Pathways. 2. UTP cabling. 3. Coaxial cable. 4. Cable connecting hardware, patch panels, and cross-connects. 5. Telecommunications outlet/connectors. 6. Cabling system identification products. 7. Cable management system. 1.2 DEFINITIONS A. Basket Cable Tray: A fabricated structure consisting of wire mesh bottom and side rails. B. BICSI: Building Industry Consulting Service International. C. Channel Cable Tray: A fabricated structure consisting of a one-piece, ventilated-bottom or solid-bottom channel. D. Consolidation Point: A location for interconnection between horizontal cables extending from building pathways and horizontal cables extending into furniture pathways. E. Cross-Connect: A facility enabling the termination of cable elements and their interconnection or cross-connection. F. EMI: Electromagnetic interference. G. IDC: Insulation displacement connector. H. Ladder Cable Tray: A fabricated structure consisting of two longitudinal side rails connected by individual transverse members (rungs). I. LAN: Local area network. J. NECA: National Electrical Contractors Association. K. Outlet/Connectors: A connecting device in the work area on which horizontal cable or outlet cable terminates. L. RCDD: Registered Communications Distribution Designer. M. UTP: Unshielded twisted pair. N. Owner: Salt River Project
2 1.3 HORIZONTAL CABLING DESCRIPTION A. Horizontal cable and its connecting hardware provide the means of transporting signals between the telecommunications outlet/connector and the horizontal cross-connect located in the communications equipment room. This cabling and its connecting hardware are called "permanent link," a term that is used in the testing protocols. 1. Minimum of three telecommunications outlet/connectors be installed for each work area. (one voice / two data) 2. Horizontal cabling shall contain no transition point or consolidation point between the horizontal cross-connect and the telecommunications outlet/connector. 3. Bridged taps and splices shall not be installed in the horizontal cabling. 4. Splitters shall not be installed as part of the optical fiber cabling. B. A work area includes the components that extend from the telecommunications outlet/connectors to the station equipment. C. The maximum allowable horizontal cable length is 295 feet (90 m). This maximum allowable length does not include an allowance for the length of 16 feet (4.9 m) to the workstation equipment. The maximum allowable length does not include an allowance for the length of 16 feet (4.9 m) in the horizontal cross-connect. 1.4 PERFORMANCE REQUIREMENTS A. General Performance: Horizontal cabling system shall comply with transmission standards in TIA/EIA-568-B.1, when tested according to test procedures of this standard. 1.5 SUBMITTALS A. Product Data: For each type of product indicated. B. Shop Drawings: 1. System Labeling Schedules: Electronic copy of labeling schedules, in software and format selected by Owner. 2. System Labeling Schedules: Electronic copy of labeling schedules that are part of the cabling and asset identification system of the software. 3. Cabling administration drawings and printouts. 4. Cross-connects and patch panels. Detail mounting assemblies, and show elevations and physical relationship between the installed components. C. Source quality-control reports. D. Field quality-control reports. E. Maintenance Data: For splices and connectors to include in maintenance manuals. F. Testing Documentation 1. Provide three hard copies and one electronic copy (CD-rom) of test reports for horizontal UTP cables, coaxial cables, and fiber-optic cables. Test reports provided in electronic
3 format shall include a shareware copy of the appropriate software for managing the reports in CSV format. 2. Documentation (printed form) shall be submitted to the Architect within five working days of the completion of each testing phase (e.g., subsystem, cable type, area, floor, etc.). 1.6 QUALITY CONTROL A. Surface-Burning Characteristics: As determined by testing identical products according to ASTM E 84 by a qualified testing agency. Identify products with appropriate markings of applicable testing agency. 1. Flame-Spread Index: 25 or less. 2. Smoke-Developed Index: 450 or less. B. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application. C. Telecommunications Pathways and Spaces: Comply with TIA/EIA-569-A. D. Grounding: Comply with ANSI-J-STD-607-A. 1.7 DELIVERY, STORAGE, AND HANDLING A. Test cables upon receipt at Project site. 1. Test each pair of UTP cable for open and short circuits. 2. Delivery and receipt of products shall be at the site described in the Scope section. 3. Cable shall be stored according to manufacturers recommendations as a minimum. In addition, cable must be stored in a location protected from vandalism and weather. Air temperature at cable storage location shall not exceed 50 F minimum, 130 F maximum. Storage location shall be well ventilated to prevent condensation. If necessary, cable shall be stored offsite at the Contractor s expense. 1.8 PROJECT CONDITIONS A. Environmental Limitations: Do not deliver or install cables and connecting materials until wet work in spaces is complete and dry, and temporary HVAC system is operating and maintaining ambient temperature and humidity conditions at occupancy levels during the remainder of the construction period. B. Cable shall be stored according to manufacturer s recommendations as a minimum. In addition, cable must be stored in a location protected from vandalism and weather. Air temperature at cable storage location shall not exceed 50 F minimum, 130 F maximum. Storage location shall be well ventilated to prevent condensation. If necessary, cable shall be stored offsite at the Contractor s expense. 1.9 COORDINATION A. Coordinate layout and installation of telecommunications pathways and cabling with Owner's telecommunications and LAN equipment and service suppliers
4 B. Coordinate telecommunications outlet/connector locations with location of power receptacles at each work area. C. Refer to Division 27 Section Communication Services. PART 2 - PRODUCTS 2.1 UTP CABLE A. Manufacturers: Subject to compliance with requirements, provide products by: 1. Berk-Tek; a Nexans company. B. Description: 100-ohm, 4-pair UTP, covered with a blue thermoplastic jacket. 1. Comply with ICEA S for mechanical properties. 2. Comply with TIA/EIA-568-B.1 for performance specifications. 3. Comply with TIA/EIA-568-B.2, Category 5e for renovation of existing facility and Category 6 for new construction. 4. Listed and labeled by an NRTL acceptable to authorities having jurisdiction as complying with UL 444 and NFPA 70 for the following types: a. Communications, Plenum Rated: Type CMP, complying with NFPA 262. b. Communications, Riser Rated: Type CMR, complying with UL c. Communications, Limited Purpose: Type CMX. d. Multipurpose: Type MP or MPG. e. Multipurpose, Plenum Rated: Type MPP, complying with NFPA 262. f. Multipurpose, Riser Rated: Type MPR, complying with UL UTP CABLE HARDWARE A. Manufacturers: Subject to compliance with requirements, provide products by one of the following: 1. Ortronics. B. General Requirements for Cable Connecting Hardware: Comply with TIA/EIA-568-B.2, IDC type, with modules designed for punch-down caps or tools. Cables shall be terminated with connecting hardware of same category or higher. C. Patch Panel: Modular panels housing multiple-numbered jack units with IDC-type connectors at each jack for permanent termination of pair groups of installed cables. 1. Number of Jacks per Field: One for each four-pair UTP cable indicated. D. Jacks and Jack Assemblies: Modular, color-coded, eight-position modular receptacle units with integral IDC-type terminals. E. Patch Cords: Factory-made, four-pair cables in [36-inch (900 mm)] [48-inch (1200-mm)] Length as directed by SRP; terminated with eight-position modular plug at each end
5 1. Patch cords shall have bend-relief-compliant boots and color-coded icons to ensure Category 6 performance. Patch cords shall have latch guards to protect against snagging. 2. Patch cords shall have color-coded boots for circuit identification. 2.3 COAXIAL CABLE A. Manufacturers: Subject to compliance with requirements, provide products by one of the following: 1. Belden CDT Inc.; Electronics Division. 2. CommScope, Inc. 3. Berk-Tek A Nexans Company B. Cable Characteristics: Broadband type, recommended by cable manufacturer specifically for broadband data transmission applications. Coaxial cable and accessories shall have 75-ohm nominal impedance with a return loss of 20 db maximum from 7 to 806 MHz. C. RG-6/U: NFPA 70, Type CATVP. 1. No. 16 AWG, solid, copper-covered steel conductor; gas-injected, foam-pe insulation. 2. Double shielded with 100 percent aluminum-foil shield and 60 percent aluminum braid. 3. Jacketed with Copolymer jacket. 4. Suitable for indoor installations. D. RG59/U (Plenum Rated): NFPA 70, Type CMP. 1. No. 20 AWG, solid, copper-covered steel conductor; foam fluorinated ethylene propylene insulation. 2. Double shielded with 100 percent aluminum-foil shield and 65 percent aluminum braid. 3. Copolymer jacket. E. NFPA and UL compliance, listed and labeled by an NRTL acceptable to authorities having jurisdiction as complying with UL 1655 and with NFPA 70 "Radio and Television Equipment" and "Community Antenna Television and Radio Distribution" Articles. Types are as follows: 1. CATV Plenum Rated: Type CATVP, complying with NFPA COAXIAL CABLE HARDWARE A. Manufacturers: Subject to compliance with requirements, provide products by one of the following: 1. Ortronics. 2. Blonder Tongue. 3. Pico Macom. B. Coaxial-Cable Connectors: Type BNC, 75 ohms
6 2.5 TELECOMMUNICATIONS OUTLET/CONNECTORS A. Jacks: 100-ohm, balanced, twisted-pair connector; four-pair, eight-position modular. Comply with TIA/EIA-568-B.1. B. Workstation Outlets: Four port-connector assemblies mounted in single faceplate. 1. Plastic Faceplate: High-impact plastic. Coordinate color with Division 26 Section "Wiring Devices." 2. For use with snap-in jacks accommodating any combination of UTP, optical fiber, and coaxial work area cords. a. Flush mounting jacks, positioning the cord at a 90-degree angle. 3. Legend: Machine printed, in the field, using adhesive-tape label for cable. 4. Legend: Snap-in, clear-label covers and machine-printed paper inserts for faceplate. 2.6 IDENTIFICATION PRODUCTS A. Comply with TIA/EIA-606-A and UL 969 for labeling materials, including label stocks, laminating adhesives, and inks used by label printers. B. Comply with requirements in Division 26 Section "Identification for Electrical Systems." C. Cable identification shall be by means of permanently applied, pre-printed, wraparound wire markers (i.e., "Brady-Wrap" B-292, LAT-18, or LAT-19 self-laminating markers). These labels must withstand the requirements of UL 969 as outlined in the EIA/TIA-606 Standard. D. Patch panel labels shall be pre-printed and enclosed in self-adhesive clear strips (Panduit, Ortronics or as accepted by the Engineer). E. Data/Telecommunications Outlet Face Plates: Permanent, clear, pre-printed laminated label with black lettering (Brady Label #CL or LAT , or as accepted by the Engineer). 2.7 SOURCE QUALITY CONTROL A. Factory test UTP on reels according to TIA/EIA-568-B.1. B. Factory test UTP cables according to TIA/EIA-568-B.2. C. Factory-sweep test coaxial cables at frequencies from 5 MHz to 1 GHz. Sweep test shall test the frequency response, or attenuation over frequency, of a cable by generating a voltage whose frequency is varied through the specified frequency range and graphing the results. D. Cable will be considered defective if it does not pass tests and inspections. E. Prepare test and inspection reports. Provide software to read original test results on disc provided to owner
7 PART 3 - EXECUTION 3.1 WIRING METHODS A. Wiring Method: Install cables in raceways and cable trays except within consoles, cabinets, desks, and counters and except in accessible ceiling spaces. Conceal raceway and cables except in unfinished spaces. 1. Install plenum cable in environmental air spaces, including plenum ceilings. 2. Comply with requirements for raceways and boxes specified in Division 26 Section "Raceway and Boxes for Electrical Systems." B. Wiring Method: Conceal conductors and cables in accessible ceilings, walls, and floors where possible. C. Wiring within Enclosures: Bundle, lace, and train cables to terminal points with no excess and without exceeding manufacturer's limitations on bending radii. Provide and use lacing bars and distribution spools. 3.2 INSTALLATION OF CABLES A. Comply with NECA 1. B. General Requirements for Cabling: 1. Comply with TIA/EIA-568-B Comply with BICSI ITSIM, Ch. 6, "Cable Termination Practices." 3. Install 110-style IDC termination hardware unless otherwise indicated. 4. Terminate all conductors; no cable shall contain unterminated elements. Make terminations only at indicated outlets, terminals, cross-connects, and patch panels. 5. Cables may not be spliced. Cabling shall be installed in continuous runs from crossconnect fields to cross-connect fields, to patch panels, workstation outlets, etc. Cabling shall be free from splices, taps, splitters, baluns and any other in-line connections. 6. Secure and support cables at intervals not exceeding 30 inches (760 mm) and not more than 6 inches (150 mm) from cabinets, boxes, fittings, outlets, racks, frames, and terminals. 7. Unsupported spans between cable trays and conduit sleeves shall not exceed 12" (305 mm) horizontally, 24" (607 mm) vertically. 8. All cables shall be new and as specified on the drawings. Cables shall be shipped on 1,000 ft. reels or boxed. Coiled cables are not acceptable. Factory shorts and/or factory seconds, salvaged, leftover and reused cables are not acceptable. Cables of a given type shall be of a single manufacturer and part number. All unapproved or unacceptable cable shall be removed and replaced at the Contractor s expense. 9. Cables routed above a suspended ceiling in exposed space, and not installed in a conduit system, shall be supported by a cable tray, channel or hangers. 10. Cables shall not be supported from ceiling support wires, lighting fixture support wires, ductwork, plumbing line, fire suppression systems, mechanical systems or electrical conduits. Cables shall not come in contact with ductwork or piping, or lay on top of ceiling systems and lighting fixtures. 11. Where cables are routed through inaccessible ceilings, the Contractor shall install conduit sleeves extending 1 foot beyond the inaccessible area, sized in accordance with ANSI/TIA/EIA-569-A Guidelines, as outlined in Table 1. Install insulated conduit bushing
8 on both ends of sleeve and ground conduit per Division 27 Specification Section Grounding & Bonding for Communications Systems. 12. Install conduit sleeves where cables pass through walls. Conduits shall be sized in accordance with ANSI/TIA/EIA-569-A Guidelines, as outlined in Division 27 Specification Section Pathways for Communications Systems Table 1. Install insulated conduit bushing on both ends of sleeve and ground conduit per Division 27 Specification Section Grounding & Bonding for Communications Systems. 13. Cables supported by hangers shall utilize Caddy Cable-Cat hangers or approved equal communication cable hangers. Hangers shall be supported from the building structure. Hangers shall not utilize other system support wires or rods. 14. A maximum of 36 (three groups of 12) cables shall be supported in a single hanger with a spacing of 48" on center. Cables shall be loosely bundled. 15. Install lacing bars to restrain cables, to prevent straining connections, and to prevent bending cables to smaller radii than minimums recommended by manufacturer. 16. Bundle, lace, and train conductors to terminal points without exceeding manufacturer's limitations on bending radii, but not less than radii specified in BICSI ITSIM, "Cabling Termination Practices" Chapter. Use lacing bars and distribution spools. 17. Do not install bruised, kinked, scored, deformed, or abraded cable. Do not splice cable between termination, tap, or junction points. Remove and discard cable if damaged during installation and replace it with new cable. 18. Cold-Weather Installation: Bring cable to room temperature before de-reeling. Heat lamps shall not be used for heating. 19. In the communications equipment room, install a 10-foot- (3-m-) long service loop on each end of voice cable. 20. Pulling Cable: Comply with BICSI ITSIM, Ch. 4, "Pulling Cable." Monitor cable pull tensions. 21. Cables requiring additional length shall be stored in an extended loop or in a "Figure 8" configuration. Do not store additional length in bundled loops. Each individual loop shall be tagged with cable number. 22. The Contractor shall make certain that during the installation and upon completion, all cables have been installed in good condition, free from jacket cuts or tears, kinks, twist, knots, sharp bends, etc., or any other physical damage. During the installation, the Contractor shall not allow the cables to be exposed to foot, vehicle or equipment traffic, or be exposed to any other form of abuse which shall cause damage to cables, altering the electrical characteristics. Cables exhibiting such damage or an attempt by the Contractor to correct, hide or otherwise conceal such damage, shall result in cables being replaced at the Contractor s expense. 23. Cable pulls shall not exceed 100 feet in length. Cables shall be neatly coiled in a figure "8" pattern at the completion of a pull in preparation for the next pull. 24. Data/telecommunication and fiber-optic cables shall not be stored or installed in an unheated building where the temperature is less than 40 F. The structure and the cable must be brought to a minimum 50 F ambient for a minimum of 48 hours prior to installation of the cables. Failure to observe this precaution may result in damage to the cable and shall result in the cable being replaced at the Contractor s expense. C. UTP Cable Installation: 1. Comply with TIA/EIA-568-B Do not untwist UTP cables more than 1/2 inch (12 mm) from the point of termination to maintain cable geometry. D. Open-Cable Installation:
9 1. Install cabling with horizontal and vertical cable guides in telecommunications spaces with terminating hardware and interconnection equipment. 2. Suspend UTP cable not in a wireway or pathway a minimum of 8 inches (200 mm) above ceilings by cable supports not more than 48 inches (1524 mm) ] apart. Refer to Part B Item 10 for support requirements. 3. Cable shall not be run through structural members or in contact with pipes, ducts, or other potentially damaging items. E. Installation of Cable Routed Exposed under Raised Floors: 1. Install plenum-rated cable only. 2. Install cabling after the flooring system has been installed in raised floor areas. 3. Coil cable [6 feet (1800 mm)] long in Figure 8 configuration not less than [12 inches (300 mm) ] in diameter below each feed point. F. Group connecting hardware for cables into separate logical fields. G. Separation from EMI Sources: 1. Comply with BICSI TDMM and TIA/EIA-569-A for separating unshielded copper voice and data communication cable from potential EMI sources, including electrical power lines and equipment. 2. Separation between open communications cables or cables in nonmetallic raceways and unshielded power conductors and electrical equipment shall be as follows: a. Electrical Equipment Rating Less Than 2 kva: A minimum of 5 inches (127 mm). b. Electrical Equipment Rating between 2 and 5 kva: A minimum of 12 inches (300 mm). c. Electrical Equipment Rating More Than 5 kva: A minimum of 24 inches (610 mm). 3. Separation between communications cables in grounded metallic raceways and unshielded power lines or electrical equipment shall be as follows: a. Electrical Equipment Rating Less Than 2 kva: A minimum of 2-1/2 inches (64 mm). b. Electrical Equipment Rating between 2 and 5 kva: A minimum of 6 inches (150 mm). c. Electrical Equipment Rating More Than 5 kva: A minimum of 12 inches (300 mm). 4. Separation between communications cables in grounded metallic raceways and power lines and electrical equipment located in grounded metallic conduits or enclosures shall be as follows: a. Electrical Equipment Rating Less Than 2 kva: No requirement. b. Electrical Equipment Rating between 2 and 5 kva: A minimum of 3 inches (76 mm). c. Electrical Equipment Rating More Than 5 kva: A minimum of 6 inches (150 mm). 5. Separation between Communications Cables and Electrical Motors and Transformers, 5 kva or HP and Larger: A minimum of 48 inches (1200 mm). 6. Separation between Communications Cables and Fluorescent Fixtures: A minimum of 5 inches (127 mm)
10 3.3 FIRESTOPPING A. Comply with requirements in Division 07 Section "Penetration Firestopping." B. Comply with TIA/EIA-569-A, Annex A, "Firestopping." C. Comply with BICSI TDMM, Chapter 11 "Firestopping Systems" Article. 3.4 IDENTIFICATION A. Identify system components, wiring, and cabling complying with TIA/EIA-606-A. Comply with requirements for identification specified in Division 26 Section "Identification for Electrical Systems." 1. Administration Class: Color-code cross-connect fields. Apply colors to voice and data service backboards, connections, covers, and labels. B. Using cable management system software specified in Part 2, develop Cabling Administration Drawings for system identification, testing, and management. Use unique, alphanumeric designation for each cable and label cable, jacks, connectors, and terminals to which it connects with same designation. At completion, cable and asset management software shall reflect as-built conditions. C. Comply with requirements in Division 09 Section "Interior Painting" for painting backboards. For fire-resistant plywood, do not paint over manufacturer's label. D. Paint and label colors for equipment identification shall comply with TIA/EIA-606-A for Class 4 level of administration. E. Cable Schedule: Post in prominent location in each equipment room and wiring closet. List incoming and outgoing cables and their designations, origins, and destinations. Protect with rigid frame and clear plastic cover. Furnish an electronic copy of final comprehensive schedules for Project. F. Cabling Administration Drawings: Show building floor plans with cabling administration-point labeling. Identify labeling convention and show labels for telecommunications closets, backbone pathways and cables, entrance pathways and cables, terminal hardware and positions, horizontal cables, work areas and workstation terminal positions, grounding buses and pathways, and equipment grounding conductors. Follow convention of TIA/EIA-606-A. Furnish electronic record of all drawings, in software and format selected by Owner. G. Cable and Wire Identification: 1. Label each cable within 4 inches (100 mm) of each termination point. 2. Exposed Backbone Cables and Cables in Cable Trays and Wire Troughs: Label each cable at intervals not exceeding 15 feet (4.5 m). 3. Label each terminal strip and screw terminal in each cabinet, rack, or panel. a. Individually number wiring conductors connected to terminal strips, and identify each cable or wiring group being extended from a panel or cabinet to a buildingmounted device shall be identified with name and number of particular device as shown. b. Label each unit and field within distribution racks and frames
11 4. Identification within Connector Fields in Equipment Rooms and Wiring Closets: Label each connector and each discrete unit of cable-terminating and connecting hardware. Where similar jacks and plugs are used for both voice and data communication cabling, use a different color for jacks and plugs of each service. H. Labels shall be preprinted or computer-printed type with printing area and font color that contrasts with cable jacket color but still complies with requirements in TIA/EIA-606-A. 1. Cables use flexible vinyl or polyester that flex as cables are bent. 3.5 FIELD QUALITY CONTROL A. Testing Agency: Installing Contractor to perform tests and inspections. B. Perform tests and inspections. C. Tests and Inspections: 1. Visually inspect UTP and optical fiber cable jacket materials for NRTL certification markings. Inspect cabling terminations in communications equipment rooms for compliance with color-coding for pin assignments, and inspect cabling connections for compliance with TIA/EIA-568-B Visually confirm Category 5e or Category 6, marking of outlets, cover plates, outlet/connectors, and patch panels. 3. Visually inspect cable placement, cable termination, grounding and bonding, equipment and patch cords, and labeling of all components. 4. Test UTP backbone copper cabling for DC loop resistance, shorts, opens, intermittent faults, and polarity between conductors. Test operation of shorting bars in connection blocks. Test cables after termination but not cross-connection. a. Test instruments shall meet or exceed applicable requirements in TIA/EIA-568-B.2. Perform tests with a tester that complies with performance requirements in "Test Instruments (Normative)" Annex, complying with measurement accuracy specified in "Measurement Accuracy (Informative)" Annex. Use only test cords and adapters that are qualified by test equipment manufacturer for channel or link test configuration. 5. UTP Performance Tests: a. Test for each outlet. Perform the following tests according to TIA/EIA-568-B.1 and TIA/EIA-568-B.2: 1) Wire map. 2) Length (physical vs. electrical, and length requirements). 3) Insertion loss. 4) Near-end crosstalk (NEXT) loss. 5) Power sum near-end crosstalk (PSNEXT) loss. 6) Equal-level far-end crosstalk (ELFEXT). 7) Power sum equal-level far-end crosstalk (PSELFEXT). 8) Return loss. 9) Propagation delay. 10) Delay skew
12 6. Coaxial Cable Tests: Conduct tests according to Division 27 Section "Master Antenna Television System." D. Document data for each measurement. Data for submittals shall be printed in a summary report that is formatted similar to Table 10.1 in BICSI TDMM, or transferred from the instrument to the computer, saved as text files, and printed and submitted. E. End-to-end cabling will be considered defective if it does not pass tests and inspections. Minimum acceptable level above testing standard is 3dBA. Although test equipment may pass a cable based on standard valves, SRP reserves the right to reject any cable test report indicating 3.0 dba or less. Contractor shall repair or replace unaccepted cable at their expense. F. Prepare test and inspection reports. END OF SECTION
B. Cross-Connect: A facility enabling the termination of cable elements and their interconnection or cross-connection.
DIVISION 16 ELECTRICAL Section 16740 Telephone System PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
DIVISION 26 - ELECTRICAL SECTION 26 05 20 CABLES FOR INSTRUMENTATION
DIVISION 26 - ELECTRICAL PART 1 - GENERAL 1.01 SUMMARY A. Section Includes 1. Instrumentation Cables 1.02 SUBMITTALS A. Submit in accordance with requirements of Section 01 33 00. B. Product Data: Submit
SECTION 16750 VOICE AND DATA COMMUNICATION CABLING
SECTION 16750 VOICE AND DATA COMMUNICATION CABLING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Store drawing set and general provisions of the Contract, including General and Supplementary Conditions and
Cable Installation Project
Cable Installation Project 1. Intent. It is the intent of the U.S. Court of Appeals to install Category 6 (CAT6) data cabling in the Robert F. Peckham Federal Building and United States Courthouse, 280
UNIFIED FACILITIES GUIDE SPECIFICATIONS
USACE / NAVFAC / AFCEC / NASA UFGS-27 05 14.00 10 (April 2006) -------------------------------- Preparing Activity: USACE Superseding UFGS-27 05 14.00 10 (April 2004) UNIFIED FACILITIES GUIDE SPECIFICATIONS
ANSI/TIA/EIA - 568-A, Commercial Building Telecommunications Cabling Standard.
WIRING STANDARD INTRODUCTION This standard defines a telecommunications wiring system for North Dakota State Agencies, offices or buildings that will support a multi-product environment. The purpose of
1.1 SYSTEM DESCRIPTION.1 Data system includes data outlets and wiring for office and school applications.
Issued 2005/06/01 Section 16743 Data System Page 1 of 7 PART 1 GENERAL 1.1 SYSTEM DESCRIPTION.1 Data system includes data outlets and wiring for office and school applications..2 Data system equipment
Presenters Brett Weiss, Gabe Martinez, Brian Kroeger.
1 Presenters Brett Weiss, Gabe Martinez, Brian Kroeger. Topics to be covered: Cable identification Purpose of the various cable types Installation techniques Building Infrastructure Overview of networking
DIVISION 27 COMMUNICATIONS. A. System design shall be completed by a Registered Communications Distribution Designer (RCDD).
DIVISION 27 COMMUNICATIONS 27 00 00 COMMUNICATIONS A. System design shall be completed by a Registered Communications Distribution Designer (RCDD). B. Comply with American National Standards Institute
ANSI/TIA/EIA-570. 570-A A Revisited. Residential Telecommunications Cabling Standard (Draft 6/22/99) Larry L. Hamlin, RCDD
BICS I CABLING INSTALLATION PROGRAM ANSI/TIA/EIA-570 Residential Telecommunications Cabling Standard (Draft 6/22/99) Larry L. Hamlin, RCDD Copyright BICSI, October 1999 -A Revisited 1.1 Purpose standardize
TCTC Cabling Specifications
TCTC Cabling Specifications Purpose: To provide a standard specification that will be used for all Tri County Technical College (TCTC) facilities requiring structured cabling installation. Product specifications,
SYSTIMAX SCS PowerSum and GigaSPEED XL Cabling Installation Guidelines
SYSTIMAX SCS PowerSum and GigaSPEED XL Cabling Installation Guidelines This document contains critical information regarding the installation of a certified SYSTIMAX SCS that meets or exceeds performance
SECTION 25110 TELECOMMUNICATION ROOMS
PART 1 - GENERAL 1.1 SUMMARY A. SCOPE SECTION 25110 TELECOMMUNICATION ROOMS 1. This section includes the minimum installation requirements for equipment and cabling infrastructure in Telecommunication
B. PART 1 - GENERAL of SECTION 271300 BACKBONE COMMUNICATIONS CABLING shall also apply to this section.
SECTION 271500 - HORIZONTAL UTP CABLING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
800 Communications Circuits
ARTICLE 800 Communications Circuits INTRODUCTION TO ARTICLE 800 COMMUNICATIONS CIRCUITS This article has its roots in telephone technology. Consequently, it addresses telephone and related systems that
HIGH SPEED COMMUNICATIONS PLENUM CABLE CATEGORY 5e CMP FEP JACKETED, PVC-FREE UNSHIELDED TWISTED PAIR (UTP)
Cable Specification Category 5e CMP HIGH SPEED COMMUNICATIONS PLENUM CABLE CATEGORY 5e CMP FEP JACKETED, PVC-FREE UNSHIELDED TWISTED PAIR (UTP) This cable specification complies with the electrical transmission
SECTION 17400 ACCESS CONTROL SYSTEM. CONDITIONS OF THE CONTRACT AND DIVISION 1, as applicable, apply to this Section.
SECTION 17400 ACCESS CONTROL SYSTEM CONDITIONS OF THE CONTRACT AND DIVISION 1, as applicable, apply to this Section. PART 1 - GENERAL 1.1 RELATED WORK A. 16060 Grounding and Bonding B. 16070 Electrical
1. Furnish and install faceplate and modular jacks at each single gang outlet as described below:
Washington University in St. Louis Building: Communication Specification: Research Voice/Network/Typical 1. Furnish and install faceplate and modular jacks at each single gang outlet as described below:
HOUSTON COMMUNITY COLLEGE HCC ALIEF CAMPUS MAIN BUILDING, FIRST, SECOND & FOURTH FLOORS RENOVATION ISSUE DATE: 10.17.12
SECTION 27 05 26 - GROUNDING AND BONDING FOR COMMUNICATIONS SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes grounding and bonding products, design requirements and installation for communications
The Evolution of Copper Cabling Systems from Cat5 to Cat5e to Cat6 Copper Cabling Standards and Technical Aspects
The Evolution of Copper Cabling Systems from Cat5 to Cat5e to Cat6 Copper Cabling Standards and Technical Aspects White Paper /7/0 Executive Summary Now that the TIA/EIA-568-B.- Category 6 Copper Cabling
TELECOMMUNICATIONS STRUCTURED CABLING GUIDELINES AND SPECIFICATIONS. University of Chicago IT Services Infrastructure Services October 2011
TELECOMMUNICATIONS STRUCTURED CABLING GUIDELINES AND SPECIFICATIONS IT Services Infrastructure Services October 2011 Table of Contents 1 Introduction... 4 1.1 Planning and Design... 4 1.2.1 Roles and Responsibilities...
SECTION 28 05 00 COMMON WORK RESULTS FOR ELECTRONIC SAFETY AND SECURITY
SECTION 28 05 00 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specifications Sections, apply
FIREFINDER XLS ADDRESSABLE FIRE ALARM SYSTEM SECTION 13851
FIREFINDER XLS ADDRESSABLE FIRE ALARM SYSTEM SECTION 13851 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and
Division 27 Master Specification for
Division 27 Master Specification for Information Transport Systems and Spaces May 1, 2014 1 Table of Contents 1 Section 27 10 01 Structured Cabling General Requirements 1.1 Scope 1.2 Approved Contractor
BIX Cross-Connect System Distribution Connectors, Multiplying Connectors and Modular Jack Connectors
C O M M E R C I A L N E T W O R K I N G C O P P E R 15.13 Distribution Connectors, Multiplying Connectors and Modular Jack Connectors A0393146 QCBIX1A4 Connector BIX Distribution Connector The BIX Distribution
Cable Products HONEYWELL SECURITY & CUSTOM ELECTRONICS. Honeywell's Genesis Series provides a full range
HONEYWELL SECURITY & CUSTOM ELECTRONICS Cable Products Honeywell's Genesis Series provides a full range of low voltage cables for security, fire, sound, voice and data, video, structured cabling and other
SECTION 16750. TELECOMMUNICATIONS SYSTEM (Cat 6)
SECTION 16750 TELECOMMUNICATIONS SYSTEM (Cat 6) PART 1 - GENERAL 1.01 REQUIREMENTS A. The general provisions of the Contract, including General and Supplementary Conditions and General Requirements, apply
TIA 569 Standards Update Pathways & Spaces. Ignacio Diaz, RCDD April 25, 2012
TIA 569 Standards Update Pathways & Spaces Ignacio Diaz, RCDD April 25, 2012 The purpose of this Standard is to standardize specific pathway and space design and construction practices in support of telecommunications
Specifying an IT Cabling System
Specifying an IT Cabling System This guide will help you produce a specification for an IT cabling system that meets your organisation s needs and gives you value for money. You will be able to give your
RoHS DATA, COAXIAL AND ELECTRONIC M.R. D A TA, C O A X I A L, ECOLGICAL Telecom Cables A N D EL E CTRON I C. Cables
RoHS DATA, COAXIAL AND ELECTRONIC D A TA, C O A X I A L, A N D EL E CTRON I C Cables Index SOLID MULTI-CONDUCTOR CABLES STRANDED MULTI-CONDUCTOR CABLES SPEAKER/ZIP WIRE THERMOSTAT CABLE FIRE ALARM CABLE
Errata NFPA 70. Proposed 2014 Edition
Errata NFPA 70 National Electrical Code (Report on Proposals) Reference: 12-109 (Log #1618) Panel Meeting Action Proposed 2014 Edition The National Electrical Code Technical Correlating Committee notes
Category 6 Solutions. 4. Category 6 Solutions. 09/08 400836IN TrueNet Structured Cabling. Introduction... 4.2. Cable... 4.3. Patch Panels... 4.
Category 6 Solutions Introduction... 4.2 Cable... 4.3 Patch Panels... 4.4 Modules... 4.6 Patch Cords... 4.12 Outlets... 4.16 Faceplates...4.18 4. 1 Search Category 6 Solutions Introduction ADC KRONE s
Building Telecommunications Infrastructure Requirements
Building Telecommunications Infrastructure Requirements This page identifies specific requirements for the design of telecommunications infrastructure for buildings at Clemson University. (Revised October,
Innovative Connectivity Solution for Maximum Performance and Security
Innovative Connectivity Solution for Maximum Performance and Security Financial Institutions Supports high performance backbone which enables transfer of real-time financial information through voice,
Structured Cabling Statement of Work
Structured Cabling Statement of Work Multiple Locations June 15, 2010 Page 1 A. GENERAL a. San Joaquin County (referred to as Owner ) is requesting proposals for a new structured cabling infrastructure
Specifications for Communication Cabling Distribution Systems
Washington University in St. Louis Specifications for Communication Cabling Distribution Systems General Overview Listed below are the separate sub-systems of Washington University s structured cabling
Minimum Standards for Data/Voice Infrastructure in New Building Construction
UNIVERSITY OF WATERLOO Minimum Standards for Data/Voice Infrastructure in New Building Construction 12/17/2012 Offices 1. Two Work Area Outlets (WAO) on opposite walls, each with 2 jacks 2. Each WAO shall
SECTION 27 13 24 COMMUNICATIONS OPTICAL FIBER OSP CABLING
SECTION 27 13 24 COMMUNICATIONS OPTICAL FIBER OSP CABLING PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications includes all labor necessary to perform and complete
UT Southwestern Medical Center Information Resources Cable Installation Standard
UT Southwestern Medical Center Information Resources Cable Installation Standard PART 1- GENERAL 1.01 SUMMARY A. Furnish and install wire, cable, devices, equipment, and accessories for a complete system
SECTION 27 05 36 CABLE TRAYS FOR COMMUNICATIONS SYSTEMS
SECTION 27 05 36 CABLE TRAYS FOR COMMUNICATIONS SYSTEMS PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications includes all labor necessary to perform and complete such
SECTION 16715 TELECOMMUNICATIONS ACCEPTANCE TESTING
PART 1 - GENERAL 1.1 SECTION INCLUDES A. Testing Publications and Standards B. Inspection and testing procedures for copper and fiber optic cable, RF CATV / MATV systems, and the antenna systems. C. Documentation
PANDUIT TX6 10GIG SHIELDED COPPER CABLING SYSTEM. Innovative Connectivity Solution for Maximum Performance and Security
PANDUIT TX6 GIG SHIELDED COPPER CABLING SYSTEM Innovative Connectivity Solution for Maximum Performance and Security Gigabit Ethernet over Copper With ever increasing bandwidth requirements, advancements
SECTION 271525 OPTICAL FIBER CABLES AND ACCESSORIES. A. Interior Raceways, Fittings, and Accessories: Section 260532.
SECTION 271525 OPTICAL FIBER CABLES AND ACCESSORIES PART 1 GENERAL 1.01 RELATED WORK SPECIFIED ELSEWHERE A. Interior Raceways, Fittings, and Accessories: Section 260532. B. Wiring, General - 600 Volts
A. Shop Drawing submittals shall include, but not be limited to, the following:
SECTION 26 05 53 IDENTIFICATION FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical
Purpose of the ANSI/TIA/EIA-569-A Standard
For more information, see anixter.com/standards Purpose of the ANSI/TIA/EIA-569-A Standard As the complexity of voice and data telecommunications has increased, standards have been established to ensure
Standards. www.nordx.com 5 ANSI/TIA/EIA-569-A (CSA T530)
The primary focus of this standard is to provide design specifications and guidance for all building facilities relating to telecommunications cabling systems and components. This standard identifies and
ATT-TP-76440 Ethernet Copper Cable & Ethernet Copper Assembly Specification
ATT-TP-76440 Ethernet Copper Cable & Ethernet Copper Assembly Specification Abstract Presented in this document are the standards to implement Electrical & Optical Ethernet components, cabling, connections,
Specification SFTP CAT6 Network Cable 23AWG CU
Specification SFTP CAT6 Network Cable 23AWG CU S/FTP CAT6 Shielded S/FTP PVC Cable 23AWG 4pair Solid, Wooden drum 1000 Grey CAT6 600MHZ CM Shielded (S/FTP) Solid Cable: Our CAT6 600MHZ Shielded (S/FTP)
March 2007. 27 08 00 Commissioning of Communications. See Appendix E3. 27 08 00-1
March 2007 27 08 00 Commissioning of Communications See Appendix E3. 27 08 00-1 27 11 00 Communications Equipment Room Fittings 1.0 General TELEPHONE RISERS: A. All copper telephone riser cables must be
with Component Rating A Simple Perspective
Cat-6A UTP and Shielded with Component Rating A Simple Perspective Asef Baddar RCDD, DCD Sr. Technical Manager Leviton Middle East Category Specifications Agenda Terminology International & North America
Terminating 25-Pair Cable and 4-Pair Cross Connects
Terminating 25-Pair Cable and 4-Pair Cross Connects Estimated Time: 90 minutes Number of Teams: 2 Number of Team Members: one to four This Lab has four major parts that will be addressed separately. 1.
Network Design. Yiannos Mylonas
Network Design Yiannos Mylonas Physical Topologies There are two parts to the topology definition: the physical topology, which is the actual layout of the wire (media), and the logical topology, which
Intelligent Cable Management Systems
Intelligent Cable Management Systems Bringing Practical Application Karen Pearson - Leviton Why Cable Management Matters Performance Cooling and air-handling Maintenance ANSI/TIA 569* Telecommunication
270526-TC Grounding and Bonding for Telecommunications Systems
270526-TC Grounding and Bonding for Telecommunications Systems Part 1 - General Related Documents The following related sections of the OT standards shall also be applicable to this section. OT Engineer
Disclaimer This information is collected and composed by QUANG DUNG TECHNOLOGY from Cablingdb.com. All information is copyrighted by Cablingdb.com.
Commercial Building Telecommunications Cabling Standard Disclaimer This information is collected and composed by QUANG DUNG TECHNOLOGY from Cablingdb.com. All information is copyrighted by Cablingdb.com.
All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.
DIVISION 16 ELECTRICAL SECTION 16100 - ELECTRICAL PART 1 - GENERAL SCOPE All electrical work as shown on the drawings and as necessary to provide a complete electrical system. Include primary service,
E Series. E Series. Category 6 and 5e. Features
E Series Category 6 and 5e CommScope, world leader in copper and fiber connectivity, offers the E Series product line as the ideal solution to all your infrastructure needs for safe and reliable data transmission.
Testing 10 Gb/s Performance of Category 6 and 6A Structured Copper Cabling Systems within the Unified Physical Infrastructure SM (UPI)
within the Unified Physical Infrastructure SM (UPI) www.panduit.com WP-11 April 2007 Introduction With the ratification of the IEEE 802.3an 10GBASE-T copper standard, end users now have more media options
NORTH ORANGE COUNTY COMMUNITY COLLEGE DISTRICT SECTION 27 10 00 STRUCTURE CABLING TESTING
RELATED SECTIONS: NORTH ORANGE COUNTY COMMUNITY COLLEGE DISTRICT Section 27 00 00 General Requirements Section 27 02 00 General Communication Requirements Section 27 05 26 Grounding and Bonding for Communications
DEPARTMENTAL REGULATION
U.S. DEPARTMENT OF AGRICULTURE WASHINGTON, D.C. 20250 DEPARTMENTAL REGULATION SUBJECT: Service Center Technology Modernization Project (SCTMP) Wiring/Cabling Specifications for Service Center Agencies
Master Format Division 27 - Communications
CLEMSON UNIVERSITY Master Format Division 27 - Communications Charlie Breece, RCDD CCIT Network Services and Telecommunications Revised 10-2013 Master Format Division 27 Communications DIVISION 27 COMMUNICATIONS
SECTION 27 20 00 - DATA COMMUNICATIONS. A. Complete vertical and horizontal Communication/Data Network System as indicated.
SECTION 27 20 00 - PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this
The National Armored Cable Manufacturers Association Presents. Installation Standard for Types AC and MC Cables
The National Armored Cable Manufacturers Association Presents Installation Standard for Types AC and MC Cables An ANSI Standard Original document jointly produced by NECA and NACMA as Standard for Installing
FTE Cabling Best Practices Author: Todd Bill, RCDD/NTS
FTE Cabling Best Practices Author: Todd Bill, RCDD/NTS Document ID: WP-07-01-ENG Original Issue Date: May 2007 Version: 1.0 FTE Cabling Best Practices 1 Table of Contents Introduction and Applicable Standards...3
Panduit 28 AWG Patch Cords Installation Guideline
Panduit 28 AWG Installation Guideline Introduction Panduit is a leading supplier of Structured Cabling Systems and Unified Physical Infrastructure. Panduit solutions enable the physical infrastructure
Communication, Signal & Data Cables
Communication, Signal & Data Cables Used for indoor installation and interconnection of transmission, telephone, telegraph and electronic equipment as well as media equipments www.alfanar.com Communication
Installing Commercial Building Telecommunications Cabling
ANSI/NECA/BICSI 568-2001 Standard for Installing Commercial Building Telecommunications Cabling Published by BICSI A Telecommunications Association Jointly developed with National Electrical Contractors
1 Campus Cabling Systems Introduction
1 Campus Cabling Systems Introduction This document represents the campus cable and infrastructure standards adopted and supported by the XXXX. All new construction and renovation should conform to these
4 Installation Requirements
4 Installation Requirements 9 4.1 Code Reference The authority having jurisdiction should be referenced to determine what law, ordinance or code shall apply in the use of flexible duct. Ducts conforming
Data Center. Pre-terminated. Patch Panel System. Cabling Systems Simplified. Patch Panels. 10G + Gigabit. Patch Cords. Plug & Play Installation
Data Center Pre-terminated Patch Panel System Patch Panels Plug & Play Installation 10G + Gigabit Patch Cords Bundled + Labeled Cabling Systems Simplified Our Mission At Cablesys, our mission is to simplify
Part 1: General Requirements TELECOMMUNICATIONS INDUSTRY ASSOCIATION
TIA/EIA STANDARD ANSI/TIA/EIA-568-B.1-2001 Approved: April 12, 2001 TIA/EIA-568-B.1 Commercial Building Telecommunications Cabling Standard Part 1: General Requirements TIA/EIA-568-B.1 (Revision of TIA/EIA-568-A)
TELUS Residential Service Conduit Requirements for Stand Alone Homes and Duplexes in Fibre Only Communities
1 TELUS Residential Service Conduit Requirements for Stand Alone Homes and Duplexes in Fibre Only Communities Beginning in January 2010 TELUS began designing new subdivisions within the Top 48 population
STANDARDS FOR STRUCTURED CABLING FOR GOVERNMENT, MINISTRIES, DEPARTMENTS AND AGENCIES
STANDARDS FOR STRUCTURED CABLING FOR GOVERNMENT, MINISTRIES, DEPARTMENTS AND AGENCIES 2013 DOCUMENT DETAILS Security Classification Authority Author Documentation Status Government/Public National Information
Cabling Requirements for the District of Columbia on behalf of the Criminal Justice Coordinating Council
Cabling Requirements for the District of Columbia on behalf of the Criminal Justice Coordinating Council Date: 6/19/2013 Version: 1.0 Prepared by: Gregory Cotten Department of General Services District
Standards and Guidelines for Telecommunications Wiring Design and Installation Montana State University-Bozeman
Standards and Guidelines for Telecommunications Wiring Design and Installation Montana State University-Bozeman This document defines the standards used for voice and data wiring in buildings used by MSU
ATTACHMENT F 050R6800016 - CABLE AND WIRING SERVICES FUNCTIONAL AREA I PRICE PROPOSAL FORM Amendment 6
050R6800016 CABLE AND WIRING SERVICES (Column A) (Column B) (Column C) (Column D) (Column E) (Column F) (Column G) (B+C+D+E)*F= G Item Description PER 100' RUN PER 150' RUN PER 200' RUN PER 300' RUN QUANTITY
FIRE ALARM AND DETECTION SYSTEMS SECTION 16721
PART 1 - GENERAL 1.01 WORK INCLUDED FIRE ALARM AND DETECTION SYSTEMS SECTION 16721 A. Provide a complete fully addressable, power limited, fire detection and evacuation system. The system shall be connected
POWER DISTRIBUTION. Power and Undercarpet Products POWER AND UNDERCARPET PRODUCTS. Chapter Summary
Power and Undercarpet Products POWER AND UNDERCARPET PRODUCTS AMPINNERGY Modular Power Distribution System................... 270 Raised Access Floor/Zone Wiring Distribution System................ 270
SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM
SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM ENGINEERING SPECIFICATION INTELLIGENT REPORTING FIRE DETECTION SYSTEM PART 1 GENERAL 1.1 DESCRIPTION A. This specification includes the furnishing,
Generic Category 5e Cabling Specification
Telecommunications Cabling System Technical Specification Category 5e Tyco Electronics Corporation provides this information as a courtesy to its customers and potential customers. Customer should review
2011 National Electrical Code
2011 National Electrical Code Changes of Interest to Data/Comm Cabling Contractors, Users and Code Enforcement Officials The National Electrical Code is published by the National Fire Protection Association
Victor Elementary School District. Technology Infrastructure Standards 02-26-03. Victor Elementary School District
15579 Eighth Street Victorville, CA 92392 Phone 760. 245-1691 Fax 760.245-6245 www.vesd.net 02-26-03 TABLE OF CONTENTS Introduction 3 Overview of Standards 3 Equipment Specifications 4 Material Specifications
electrics P OW E R E N T RY B A S I C S P OW E R & C O M M U N I C AT I O N S B A S I C S P OW E R D I S T R I B U T I O N B A S I C S
P RO D U C T M A P / TA B L E O F C O N T E N T S..................6 8 6 E L E C T R I C S & C O M M U N I C AT I O N S O V E RV I E W.............6 8 9 P OW E R E N T RY B A S I C S PA N E L - M O U N
Installation Effects Upon Alien Crosstalk and Equal Level Far End Crosstalk
Installation Effects Upon Alien Crosstalk and Equal Level Far End Crosstalk Paul Vanderlaan Product Development Engineer Belden Presented at BICSI January 20, 1999 Introduction New Parameters involving
Standards Affecting a Premise T-1 Installation
Standards Affecting a Premise T-1 Installation The T-carrier system originated many years ago as a technology developed by AT&T. The intended use of the scheme was to increase the voice channel capacity
SPACE TYPE: AUTOMATED DATA PROCESSING CENTER (ADP) (MAINFRAME)
SPACE TYPE: AUTOMATED DATA PROCESSING CENTER (ADP) (MAINFRAME) Construction Criteria The unit costs for ADP Mainframe space types are based on the construction quality and design features in the following
Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016. Underground branch circuit feeding a detached garage:
Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016 * Garage construction requires permits (electrical, building) * Permits must be applied for at the time. * Dial
DESIGN GUIDELINES. Local Area Network
DESIGN GUIDELINES Local Area Network The total oversight and management responsibilities for information assurance (IA) and protection of DoDEA s critical infrastructure fall under the purview of the DoDEA
TELECOMMUNICATIONS NETWORK STANDARDS AND GUIDELINES FOR THE NEW ADMINISTRATION BULDING
TELECOMMUNICATIONS NETWORK STANDARDS AND GUIDELINES FOR THE NEW ADMINISTRATION BULDING October 1998 Table of Contents SECTION I: New Construction Programming 1.0 New Construction 1.1 Design Elements..................................
FIRE ALARM SYSTEM. A. Shop drawings shall be submitted as follows: 1. Manufacturer's published literature. for aspproval.
Polk School District Specifications for the New Fire Alarm in the Existing Building Eastside Elementary School FIRE ALARM SYSTEM 1.01 SUBMITTALS A. Shop drawings shall be submitted as follows: 1. Manufacturer's
The Telecommunications Closet and Building Services
APPENDIX G Telecommunications Building & Network Standards 1. Expectations...2 2. Definitions...2 3. Contractor Requirements...2 4. Design Elements...3 4.1. Spaces...3 4.1.1. Building Service Entrance...3