with Component Rating A Simple Perspective
|
|
- Katherine Harris
- 8 years ago
- Views:
Transcription
1 Cat-6A UTP and Shielded with Component Rating A Simple Perspective Asef Baddar RCDD, DCD Sr. Technical Manager Leviton Middle East
2 Category Specifications Agenda Terminology International & North America Category 6A and Component Rating Shielded Solutions compared to UTP solutions for Structured Cabling Shielded System Pro s and Con s Bonding & Grounding Summary
3 International Standards TIA is the Telecommunications Industry Association (North America) EIA is the Electronics Industry Alliance (North America) ISO is the International Standards Organization (TIA equivalent) IEC is the International ti Electro Technical Commission i (IEEE equivalent) European Committee for Electrotechnical Standardization (CENELEC) is the standards setting body of the European Union (EU). BICSI equivalent and uses the EN designation.
4 Category Classification ISO and TIA TIA classification of cabling classes: Category 3 is specified up to 16 MHz Category 5e is specified up to 100 MHz Category 6 is specified up to 250 MHz Category 6A is specified up to 500 MHz Category 7 No plans to develop under TIA. (CAT 7 is referenced in BICSI TDMM and ISO as a Class F and FA equivalent) ISO classifications of cabling classes: Class C is specified up to 16 MHz (similar to Cat-3) Class D is specified up to 100 MHz (similar to Cat-5e) Class E is specified up to 250 MHz (similar to Cat-6) Class E A is specified up to 500 MHz (similar to Cat-6A) Class F is specified up to 600 MHz Class F A is specified up to 1000 MHz
5 Market Segment by Category Cat-5e and Cat-6 are so far dominating Cat-6A on the increase
6 TIA Cat-6A
7 Category 6A Cabling classification designed to support high-speed applications, such as 10GBase-T, over 100 meter channels Unshielded or Shielded Twisted Pair Requirements are for 4-pair 100 Ω CAT6A cabling, cables, cords and connecting hardware up to 500 MHz Several new parameters introduced such as: o alien crosstalk near and far Published in Apr 2008
8 Designing to the Cat 6A Standard The TIA 568 Standards ensure applications will run, and products from different manufacturers work together. These standards build in extra performance margin than is typically required by applications such as 10G Ethernet. A range of performance is specified individually for plugs, jacks, cords, and cables.
9 Designing to the Cat 6A Standard This range allows trade-offs in the design process optimize for all products across the range, or optimize for a specific value within the range. Most manufacturers, choose to optimize for their own component values so their system performance is optimized. Connectors, cords, patch panels, cables can be designed to work best together.
10 Designing to the Cat 6A Standard Range of Connector Values A Range of Cable Values A Range of Connector Values B Range of Cable Values B When products from different manufacturers are combined, overall performance margin can drop due to the need to work together with connectivity that can be anywhere in the performance envelope. Competent manufacturers will design extra margin into component-rated products to provide excellent performance margin with their own products, and with those from other manufacturers.
11 Comp. Guarantee Channel Perform.? Alien Crosstalk (AXT) is new to Cat 6A. It was not previously specified in earlier categories for 4pr UTP cables. Other types of Crosstalk, such as NEXT and FEXT, are generated WITHIN the cable jacket, connector, cord, or panel. NEXT and FEXT can be predicted, and can therefore be reduced through noise cancellation within the active equipment.
12 Comp. Guarantee Channel Perform.? In some instances, meeting component requirements for AXT DOES NOT guarantee the resulting channel or link will meet AXT limits. In addition to meeting the component requirements, all connecting hardware and cable should also be verified for link and channel AXT performance. This is because Alien Crosstalk coupling can take several different forms. The most significant of these forms are common mode and differential mode noise, and differential to common mode conversion.
13 Differential Mode Signals Current flow in UTP cabling induces a magnetic field around the conductors. The spiral form created by the twisted pairs to some extent keeps the magnetic field contained within the spiral. The containment is not perfect, and a magnetic field also exists outside the spiral.
14 Common Mode Signals Common mode noise flows in both conductors in the same direction, and returns to ground via parasitic capacitance. Both conductors generate a magnetic field with equal magnitude and polarity, and do not cancel each other out. The spiral wound pair acts just like an antenna.
15 Common to Differential Conversion The better the electrical balance of the cable, connector, and cord, the better they are able to reject these forms of AXT, and the better the AXT margin of the entire channel.
16 AXT Testing at the Component Level AXT testing for hardware includes setups for ANEXT and AFEXT. To understand the tests, we need to introduce two terms: disturber and victim. In this photo, the V marks the victim port, and the surrounding ports are the disturbers. AXT from each surrounding port is measured and summed.
17 AXT Testing at the Component Level Not all nearby ports have a significant ifi effect on AXT, and are not included. The standards define what s called significant disturbers. For the curious - defined as 90-20log(f/100) In panels and wall plates they re generally the nearby ports.
18 Show Me the Channel A typical worst-case Cat 6A channel as defined in the standards includes 4 connectors, in a 6-around-1 topology.
19 UTP & Shielded System
20 Growth of Shielded System (US) In 2006, Shielded Systems were about 1% of the US business. o All Categories (5e/6/6A) Shielded solutions business increased in 2009 but still expected to be the same in 2012 o This increase contributed t to Cat-6A
21 Terminology
22 Terminology ISO and N. America Flavors
23 End to End Channel
24 4-Connector Channel Channel is the same for UTP and Shielded Devise or Field Tester Work Area Outlet Patch Cord Length 5m max Consolidation Point Horizontal Cable Testing Length 328 ft (100m) Maximum Patch Panel Port 1 Telecommunications Closet Patch Panel Port 2 Patch Cord Length 5m max Total Active or Field Tester
25 What is the Noise all About EMC - Electromagnetic Compatibility o o Immunity - Susceptibility to interference from outside noise sources. Emissions Potential to disturb outside sources EMI / RFI Electromagnetic Interference / Radio Frequency Interference o o The disruption of operation of an electronic device when it is in the vicinity of an electromagnetic field (EM field) in the radio frequency (RF) spectrum that is caused by another electronic device. Causes an undesirable response, malfunctioning or degradation in the performance of electrical equipment.
26 What is a Shield? Used to block RF Electromagnetic radiation from corrupting data signals traveling on core conductors Used to prevent the leakage of signal from core conductors onto other channels in close proximity Reduction of RF/E radiation depends very much upon the material used, its thickness, and the frequency spectrum
27 Shield? STRENGTHS EMI/RFI Protection o Noise immunity from outside electrical noise Security o Data security in secure network applications Alien Crosstalk (Cat 6A) o Mitigates AXT in high frequency applications (500 MHz) Smaller Cable O.D. (Cat 6A) Fill it i P th & S ( o Fill capacity in Pathways & Spaces (vs. Cat 6A UTP cable)
28 Shield? WEAKNESSES Cost o Shielded systems generally 30-40% higher vs. UTP. Shielded Cat-6A is typically higher by about 10% o Labor - Additional labor/cost to terminate t (cable prep, foil, drain wire, rework) o Training - May require additional installer training Availability o Shielded products are stocked in o Shielded products are stocked in smaller quantities than UTP.
29 Foil Most common today Shield Types o Better flexibility but not as rugged o Excellent for mitigating high frequencies o Screen must be folded onto itself for full shield effect o 1.5 or 2.0 mil aluminum foil shield Braids o Good flexibility and rugged o Lower DC resistance than foiled screens o Excellent for mitigating noise at low frequencies o Use higher braid coverage percentage for maximum protection Combination braid/foil il construction ti o Maximum effectiveness of shielding o More bulky difficult to work with o More costly
30 Shield Market Sector Financial o Trading desks, high speed data close to other cables. Govt. o Secure network applications, EMI/RFI immunity. Healthcare o Application near ambient electrical noise; MRI equipment, etc. Gaming o High concentration of electrical noise Lights, slot machines, cameras, ATMs, etc. Industrial o Motors, generator, fluorescent lights
31 Why Bonding & Grounding? Life safety requirements o NEC (NFPA 70) Article 250 Protection of People & Property o Life Safety Prevent severe injury or possible death for building occupants. o Equipment Prevent equipment from being damaged or destroyed.
32 Who will do Bonding & Grounding? The electrician on a project is responsible for Bonding & Grounding as part of the building infrastructure o o National & local codes should always be followed. Contact AHJ if there is question on a specific project. This is typically done before the communications installer arrives on the job site. A primary responsibility of the designer is safeguarding personnel, property, and equipment from foreign electrical voltages and currents. (BICSI TDM, 10 th edition, page 10-2)
33 Bonding Definition The permanent joining of metallic parts to form an electrically conductive path that ensures electrical continuity and the capacity to conduct safely an current likely to be imposed. (NEC Article 100 definition) Purpose o Eliminate voltage potentials across all systems which can cause: Equipment damage Electrical noise Intermittent operation System degradation
34 Grounding (Earthing) Definition A conducting connection, whether intentional or incidental, between an electrical circuit or equipment and the earth, or to some conducting body that serves in place of the earth. Purpose o Establish and maintain the potential of the earth on conductors connected to it. o Conducting ground current to and from the earth A floating gground system is one that is not connected to Earth.
35 Rack Level View of shielded system Grounding Patch Panels
36 Grounding at the Work Area A ground at the Work Area is not required Grounding is done when shielded patch cord connect PL to PC (NIC). The computer is grounded through the electrical receptacle. If shielded patch cord is not used or the PC is not grounded, the channel is tied to the ground in the TR.
37 Summary Component rating is necessary to achieve good channel margin Both Cat-6A Shielded and Unshielded Cables are used world wide Majority of installs are UTP Some regions prefer Unshielded and some prefer just Shielded Introduction ti of Cat-6A, increased the use of shielded d solutions as it was easier to meet alien crosstalk in early Both Shielded and UTP Cat-6A solutions supports 10G applications UTP recommended for installations where no noise is present and Shielded is recommended for installations in noisy environments
38
White Paper: What Component Compliance Means for CAT6A System Performance
White Paper: What Component Compliance Means for CAT6A System Performance Gary Bernstein, RCDD Director of Product Management Copper Systems Leviton Network Solutions Jeff Seefried Development Engineering
More informationData Communications Competence Center
Importance of Cable Balance For Improving Noise Susceptibility Data Communications Competence Center DCCC03101702 July 11, 2007 Summary In a study of category 5e and category 6 UTP cables, a strong correlation
More informationSession 2; Cabling Technology in the Data Centre Media Choices; Copper Twisted Pair
Presentation; Session 2; Cabling Technology in the Data Centre Media Choices; Copper Twisted Pair 5 th April 2010 Paul Mathews MInstSMM, CCNA, MIEEE Global Channel Manager Media Types Physical Layer Cabling;
More informationWhite Paper: 10 Gigabit Ethernet over Twisted Pair Copper Systems
White Paper: 10 Gigabit Ethernet over Twisted Pair Copper Systems Asef Baddar, RCDD Principal Engineer / Applications Engineering Supervisor Leviton Network Solutions C/7 - #1928 Table of Contents Background
More informationAn Engineer s Guide to Full Compliance for CAT 6A Connecting Hardware
for CAT 6A Connecting Hardware Written by: Antoine Pelletier Engineer, Global Cabling Products Intertek www.intertek-etlsemko.com 1-800-WORLDLAB Introduction The telecommunication industry recently achieved
More informationMixed High-Speed Ethernet Operations over Different Categories of Bundled UTP Cable
Mixed High-Speed Ethernet Operations over Different Categories of Bundled UTP Cable June 10, 2010 Contributors: Yinglin (Frank) Yang CommScope, Inc. Charles Seifert Ixia Ethernet Alliance 3855 SW 153 rd
More informationEthernet Patch Cord Wiring
Ethernet Patch Cord Wiring C ONTENTS Ethernet Patch Cords & RJ-45 Connectors... 2 Ethernet Patch Cords and UTP Cabling... 3 What s all the twisting about?... 4 Ethernet Applications... 5 568A & 568B Wiring
More informationG019.A (4/99) UNDERSTANDING COMMON MODE NOISE
UNDERSTANDING COMMON MODE NOISE PAGE 2 OF 7 TABLE OF CONTENTS 1 INTRODUCTION 2 DIFFERENTIAL MODE AND COMMON MODE SIGNALS 2.1 Differential Mode signals 2.2 Common Mode signals 3 DIFFERENTIAL AND COMMON
More informationHIGHSPEED ETHERNET THE NEED FOR SPEED. Jim Duran, Product Manager - Americas WHITE PAPER. Molex Premise Networks
HIGHSPEED ETHERNET THE NEED FOR SPEED Jim Duran, Product Manager - Americas WHITE PAPER Molex Premise Networks EXECUTIVE SUMMARY Over the years structured cabling systems have evolved significantly. This
More informationHow to Choose the Right Cable Category
How to Choose the Right Cable Category Why do I need a different category of cable? Not too long ago, when local area networks were being designed, each work area outlet typically consisted of one Category
More informationWhite paper. Shielded or unshielded network cables A matter of choice, electromagnetic environment and compatibility
White paper Shielded or unshielded network cables A matter of choice, electromagnetic environment and compatibility Table of contents 1. Introduction 3 2. Shielded versus unshielded network cables 3 3.
More informationPresenters Brett Weiss, Gabe Martinez, Brian Kroeger.
1 Presenters Brett Weiss, Gabe Martinez, Brian Kroeger. Topics to be covered: Cable identification Purpose of the various cable types Installation techniques Building Infrastructure Overview of networking
More informationTesting 10 Gb/s Performance of Category 6 and 6A Structured Copper Cabling Systems within the Unified Physical Infrastructure SM (UPI)
within the Unified Physical Infrastructure SM (UPI) www.panduit.com WP-11 April 2007 Introduction With the ratification of the IEEE 802.3an 10GBASE-T copper standard, end users now have more media options
More informationSolving Signal Problems Effective shielding is key to enhancing the reliability and performance of broadcast cables.
Solving Signal Problems Effective shielding is key to enhancing the reliability and performance of broadcast cables. by Marty Van Der Burgt Belden Article for Broadcast Engineering There is perhaps no
More informationNetwork Design. Yiannos Mylonas
Network Design Yiannos Mylonas Physical Topologies There are two parts to the topology definition: the physical topology, which is the actual layout of the wire (media), and the logical topology, which
More informationANSI/TIA/EIA - 568-A, Commercial Building Telecommunications Cabling Standard.
WIRING STANDARD INTRODUCTION This standard defines a telecommunications wiring system for North Dakota State Agencies, offices or buildings that will support a multi-product environment. The purpose of
More informationMYTHBUSTING Takes on Shielded Cabling
MYTHBUSTING Takes on Shielded Cabling Herb Congdon Brian Davis Objectives Take on myths of shielded cabling and use modern-day science to show what's real and what's fiction - through trial and error actually
More informationThe Evolution of Copper Cabling Systems from Cat5 to Cat5e to Cat6 Copper Cabling Standards and Technical Aspects
The Evolution of Copper Cabling Systems from Cat5 to Cat5e to Cat6 Copper Cabling Standards and Technical Aspects White Paper /7/0 Executive Summary Now that the TIA/EIA-568-B.- Category 6 Copper Cabling
More informationCat7/Class F New Installation Concept New infrastructure. Handbook
Cat7/Class F New Installation Concept New infrastructure Handbook contents 1 Introduction 3 2 What is the Cat7/Class F installation concept 3 3 Distribution centre 3 3.1 Patch Modules 3 4 How to handle
More informationRunning 1000BASE-T Gigabit Ethernet over Copper Cabling 30 March 1999 Colin Mick/The Mick Group with Bruce Tolley/3Com and Willem Wery/Intel
Running 1000BASE-T Gigabit Ethernet over Copper Cabling 30 March 1999 Colin Mick/The Mick Group with Bruce Tolley/3Com and Willem Wery/Intel Introduction When network managers decide on a cabling system,
More informationEvolution of Cabling Standards TIA/EIA ISO/IEC CENELEC. by Paul Kish NORDX/CDT Chair TIA TR 41.8
Evolution of Cabling Standards TIA/EIA ISO/IEC CENELEC by Paul Kish NORDX/CDT Chair TIA TR 41.8 Outline Market trends Standards development where we were where we are where we are going Beyond Category
More informationDIVISION 26 - ELECTRICAL SECTION 26 05 20 CABLES FOR INSTRUMENTATION
DIVISION 26 - ELECTRICAL PART 1 - GENERAL 1.01 SUMMARY A. Section Includes 1. Instrumentation Cables 1.02 SUBMITTALS A. Submit in accordance with requirements of Section 01 33 00. B. Product Data: Submit
More informationPlanning for 10Gbps Ethernet over UTP Questions to Ask When Planning the Cabling Plant WHITE PAPER
Planning for 10Gbps Ethernet over UTP Questions to Ask When Planning the Cabling Plant WHITE PAPER Questions to Ask When Planning the Cabling Plant Planning a copper cabling plant to support 10Gbps transmission
More informationChapter 4 Connecting to the Internet through an ISP
Chapter 4 Connecting to the Internet through an ISP 1. According to Cisco what two things are essential to gaining access to the internet? a. ISPs are essential to gaining access to the Internet. b. No
More informationEMC STANDARDS STANDARDS AND STANDARD MAKING BODIES. International. International Electrotechnical Commission (IEC) http://www.iec.
EMC STANDARDS The EMC standards that a particular electronic product must meet depend on the product application (commercial or military) and the country in which the product is to be used. These EMC regulatory
More information10 Gigabit Ethernet over copper: Unshielded, unprotected?
Technical Article 10 Gigabit Ethernet over copper: Unshielded, unprotected? Copyright 2005 Reichle & De-Massari AG (R&M). All rights reserved. Transmission and reproduction of this publication or parts
More informationNexus Technology Review -- Exhibit A
Nexus Technology Review -- Exhibit A Background A. Types of DSL Lines DSL comes in many flavors: ADSL, ADSL2, ADSL2+, VDSL and VDSL2. Each DSL variant respectively operates up a higher frequency level.
More informationCabling Standards Update 2014
Cabling Standards Update 2014 Dimitris Filippou Technical Director, Ltd. IEEE Member, BICSI Country Chair, ELOT Technical Committee TC93 Member, CENELEC TC215 Delegate of Greek National Committee, CENELEC
More informationCable Sharing in Commercial Building Environments
Cable Sharing in Commercial Building Environments Reducing Cost, Simplifying Cable Management, and Converging Applications onto Twisted-Pair Media Cable sharing describes the practice of running more than
More informationUnderstanding Shielded Cable
Understanding Shielded Cable Industrial applications such as the factory floor are typically electrically noisy environments. Electrical noise, either radiated or conducted as electromagnetic interference
More informationDATA CENTER NETWORK INFRASTRUCTURE. Cable and Connectivity for the Most Demanding Networks. BerkTekLevitonTechnologies.com
DATA CENTER NETWORK INFRASTRUCTURE Cable and Connectivity for the Most Demanding Networks Customer-focused, technology-driven, quality-assured for an unparalleled RETURN ON infrastructure investment DATA
More informationAn Ethernet Cable Discharge Event (CDE) Test and Measurement System
An Ethernet Cable Discharge Event (CDE) Test and Measurement System Wei Huang, Jerry Tichenor ESDEMC Technology LLC Rolla, MO, USA whuang@esdemc.com Abstract A Cable Discharge Event (CDE) is an electrostatic
More informationCategory 8 Cable Transmission Measurements Comparative Study between 4-port single wire measurements and 2-port balun measurements
Category 8 Cable Transmission Measurements Comparative Study between 4-port single wire measurements and 2-port balun measurements Stefan Estevanovich Rafael Herrera, Nadim Kafati Hitachi Cable USA NDC
More informationAccelerating Light. Copper Cabling Solutions. Category 6A
Accelerating Light Copper Cabling Solutions Category 6A Category 6A Copper Cabling Solutions Fibernet designs and manufactures premium, high performance copper communication infrastructure and connectivity
More informationHow To Get 40G Over Copper (Wired) And 40G On Coaxian (Wireless) Cable (Wired Coaxian) (Wired Cable) (Wireline) (Powerline) And 50G Over Coaxian Cable (Wire Coaxian
Copper for Beyond 10GBASE-T David Zambrano Agenda Market Drivers Standards Cabling and Ethernet Field Test Considerations Agenda Market Drivers Standards Cabling and Ethernet Field Test Considerations
More informationCable Solutions for Servo and Variable Frequency Drives (VFD)
Cable Solutions for Servo and Variable Frequency Drives (VFD) Electric drive systems with continuous torque and speed control are widespread today. They allow an optimal adjustment of the drive with respect
More informationGigabit Ethernet on Copper Cabling Infrastructures
Gigabit Ethernet on Copper Cabling Infrastructures Overview of Gigabit Ethernet (1000Base-T) Ethernet was developed by the Xerox Corporation in the early 1970 s and has emerged as the dominant networking
More informationStructured Cabling, Earthing & Equipotential Bonding
White Paper Information and Communication Technology Structured Cabling, Earthing & Equipotential Bonding English Rev. 1.0.1 / 2012-06-01 1 Abstract All Dallmeier network products (PoE cameras, recorders,
More informationWhite Paper: Electrical Ground Rules
Acromag, Incorporated 30765 S Wixom Rd, Wixom, MI 48393 USA Tel: 248-295-0880 Fax: 248-624-9234 www.acromag.com White Paper: Electrical Ground Rules Best Practices for Grounding Your Electrical Equipment
More informationNetworks. The two main network types are: Peer networks
Networks Networking is all about sharing information and resources. Computers connected to a network can avail of many facilities not available to standalone computers: Share a printer or a plotter among
More informationNew Technology Developments and How They Impact Your Structured Wiring Choices
New Technology Developments and How They Impact Your Structured Wiring Choices Author: Rob Wessels Vice President of Engineering Structured wiring has come a long way since the days when Category 3 and
More informationNetwork Engineers Everywhere:
Network Engineers Everywhere: Relax Your Minds Not Your Standards DataMax Commercial Ethernet Patch Cable The Strongest Link. DataMax Commercial Ethernet Patch Cable The Strongest Link. DataMax Patch Cable
More informationSquare D Clipsal DIN-Rail Four-Channel Auxiliary Input Unit
Square D Clipsal DIN-Rail Four-Channel Auxiliary Input Unit SLCLE5504AUX for Use with Wired C-Bus Networks Instruction Bulletin Retain for future use. Square D Clipsal DIN-Rail Four-Channel Auxiliary Input
More informationCommon Mode Choke Filtering Improves CMRR in Ethernet Transformer Applications. Application Note. June 2011
Common Mode Choke Filtering Improves CMRR in Ethernet Transformer Applications June 2011 Application Note Common mode chokes provide an effective EMI filtering solution for Ethernet transformer applications.
More informationR&Mfreenet Advanced Cat 6 A Unshielded Connection Module
R&Mfreenet Advanced R&Mfreenet Advanced Cat 6 A Connection Module The R&Mfreenet Cat 6 A unshielded connection modules, part of the Advanced cabling system, are ideal for voice, fast data transmissions
More informationBalanced vs. Unbalanced Audio Interconnections
Revised 7/2/08 Balanced vs. Unbalanced Audio Interconnections In discussing the characteristics and performance of various interconnect systems; two points should be kept in mind. Balance is defined in
More informationEMC Standards: Standards of good EMC engineering
Electromagnetic Compatibility (EMC) IEEE Definition Origin, control, and measurement of electromagnetic effects on electronic and biologic systems. IEEE EMC Society Areas of Interest EMC Standards: Standards
More informationEnhanced Category 5 Cabling System Engineering for Performance
Engineering for Performance Table of Contents 2 Introduction 2 Where Did It Come From? 2 Enhanced Category 5 Performance What to Test The Link The Channel Don t Forget the Cable Assembly 4 Performance
More informationData Center. Pre-terminated. Patch Panel System. Cabling Systems Simplified. Patch Panels. 10G + Gigabit. Patch Cords. Plug & Play Installation
Data Center Pre-terminated Patch Panel System Patch Panels Plug & Play Installation 10G + Gigabit Patch Cords Bundled + Labeled Cabling Systems Simplified Our Mission At Cablesys, our mission is to simplify
More informationAXIS T81B22 DC 30W Midspan
INSTALLATION GUIDE AXIS T81B22 DC 30W Midspan ENGLISH About this Document This document includes instructions for installing AXIS T81B22 on your network. Previous experience of networking will be beneficial
More information30 In Compliance October 2014 www.incompliancemag.com
30 In Compliance October 2014 www.incompliancemag.com Medical Devices in a Wireless World BY IVAYLO TANKOV While wireless technology is now an integral component of a wide variety of manufactured products,
More informationPANDUIT TX6 10GIG SHIELDED COPPER CABLING SYSTEM. Innovative Connectivity Solution for Maximum Performance and Security
PANDUIT TX6 GIG SHIELDED COPPER CABLING SYSTEM Innovative Connectivity Solution for Maximum Performance and Security Gigabit Ethernet over Copper With ever increasing bandwidth requirements, advancements
More informationIT Cabling Solutions
IT Cabling Solutions Signamax & Hitachi Cable America System Performance Signamax & Hitachi Cable America (Hitachi) system quality assurance testing is based on the worst-case model - four-connector 100-meter
More informationGrounding Demystified
Grounding Demystified 3-1 Importance Of Grounding Techniques 45 40 35 30 25 20 15 10 5 0 Grounding 42% Case 22% Cable 18% Percent Used Filter 12% PCB 6% Grounding 42% Case Shield 22% Cable Shielding 18%
More informationWhite Paper. Power over Ethernet Plus Update and Cabling Considerations
White Paper Power over Ethernet Plus Update and Cabling Considerations Power over Ethernet Plus Update and Cabling Considerations TABLE OF CONTENTS 1. Introduction...3 2. Application Objectives...5 3.
More informationThe Permanent Link in Field Certification Reasons, Advantages, Testing Challenges
The Permanent Link in Field Certification Reasons, Advantages, Testing Challenges Table of contents Channel, Basic Link and Permanent Link defined....................... 2 Critical Performance Parameters......
More informationThis paper will explain some of the more important factors on how UTP wires work; specifically it will cover the following:
UTP Technology In the late 1970s, unshielded twisted pair (UTP) cabling originated in the computer industry as a means of transmitting digital data over computer networks. This cable was designed to be
More informationGrounding and Shield Termination. Application Note 51204
Grounding and Shield Termination Application Note 51204 DEFINITIONS This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this
More informationSpecifying an IT Cabling System
Specifying an IT Cabling System This guide will help you produce a specification for an IT cabling system that meets your organisation s needs and gives you value for money. You will be able to give your
More informationCat 5, 6 or 7? Standards. Background. A University Standard for Structured Wiring. Network Points Installed. British Standards.
Cat 5, 6 or 7? A University Standard for Structured Wiring. Background isolutions recently formed Incorporates all IT service providers within the University. Focus on all ICT needs of the user and the
More informationSending A/V Signals Over Twisted Pair Cables: An Introduction. What is A/V over twisted pair?... 2
Sending A/V Signals Over Twisted Pair s: An Introduction Table of Contents What is A/V over twisted pair?... 2 What can be accommodated with A/V over twisted pair?... 3 What applications can effectively
More informationFrequently Asked Questions
Frequently Asked Questions Wire and Installation What kind of wire to use with SC&T Twisted Pair Transmission products? Use UTP (unshielded twisted pair) CAT 5 24 AWG (or over) to have the best transmission
More informationIndustrial Ethernet The Perfect Cable for an Imperfect Environment
1 Industrial Ethernet The Perfect Cable for an Imperfect Environment Written by: David Fausz, Engineer, Communications Products TABLE OF CONTENTS BACKGROUND 1 APPLICATIONS AND 2 ELECTRICAL PERFORMANCE
More informationIssues and Solutions for Dealing With a Highly Capacitive Transmission Cable
Issues and Solutions for Dealing With a Highly Capacitive Transmission Cable F.N. Morgan and K.C. Cameron, Advanced Energy Industries, Inc., Fort Collins, CO ABSTRACT For glass coaters, the transmission
More informationSHEET 1 COMMUNICATION NETWORKS COMPUTER AND TELEPHONE SYSTEMS
STRUCTURED CABLING SHEET 1 COMMUNICATION NETWORKS COMPUTER AND TELEPHONE SYSTEMS INTRODUCTION In recent years, communications have taken on a crucial role in development for businesses. Communications
More informationWhite Paper: DC Resistance Unbalance Testing: Easy, Low-Cost Insurance for Your PoE Systems
White Paper: DC Resistance Unbalance Testing: Easy, Low-Cost Insurance for Your PoE Systems Originally ratified by IEEE in 1999 and 2003 respectively, gigabit Ethernet (1000BASE-T) and power over Ethernet
More informationLVDS Technology Solves Typical EMI Problems Associated with Cell Phone Cameras and Displays
AN-5059 Fairchild Semiconductor Application Note May 2005 Revised May 2005 LVDS Technology Solves Typical EMI Problems Associated with Cell Phone Cameras and Displays Differential technologies such as
More informationUnderstanding SMD Power Inductors. Application Note. July 2011
Understanding SMD Power Inductors July 2011 Application Note Power inductors play an important role in voltage conversion applications by yielding lower core losses. They are also used to store energy,
More informationCabling for 10GBASE-T and Beyond - A Tangled Web
Augmented Category 6 Category 6 A CLC TR 50173-99-1 TIA/EIA-TSB-155 TIA/EIA-568-B.2-10 ISO/IEC 11801 A1.1 Class E A Class F A ISO/IEC 11801 A1.2 Category 7 A ISO/IEC TR 24750 ISO/IEC 11801 Cabling for
More informationMethod for improving Return Loss in order to reduce PHY power Ron Nordin Panduit Bob Wagner Panduit Paul Vanderlaan Berk-Tek
Method for improving Return Loss in order to reduce PHY power Ron Nordin Panduit Bob Wagner Panduit Paul Vanderlaan Berk-Tek Supporters Mike Grimwood Broadcom Will Bliss Broadcom Dariush Dabiri APM Dan
More informationInnovative Connectivity Solution for Maximum Performance and Security
Innovative Connectivity Solution for Maximum Performance and Security Financial Institutions Supports high performance backbone which enables transfer of real-time financial information through voice,
More informationCable Discharge Event
Cable Discharge Event 1.0 Introduction The widespread use of electronic equipment in various environments exposes semiconductor devices to potentially destructive Electro Static Discharge (ESD). Semiconductor
More informationRTEX Cable 2015/10/1. Motor Business Unit Automotive & Industrial Systems Company Panasonic Corporation
RTEX Cable 2015/10/1 Motor Business Unit Automotive & Industrial Systems Company Panasonic Corporation Cable and Connector Page 2 2015/10/1 Rev. 5 Motor Business Unit, AIS Company The Kind of Ethernet
More informationWhite Paper. Cat. 6A vs. Cat. 6 A. What s the Difference and Why Should I Care?
White Paper Cat. 6A vs. Cat. 6 A What s the Difference and Why Should I Care? Cat. 6A vs. Cat. 6 A What s the Difference and Why Should I Care? TABLE OF CONTENTS 1. Introduction...3 2. Component Standards
More informationMeasurement setup for differential-mode and common-mode channels
Measurement setup for differential-mode and common-mode channels Vincent Le Nir, Marc Moonen 1 Abstract Since there is no model available for mixed differential-mode and common-mode transmission, this
More informationAMP CO Plus Insert for Cat. 6 A Applications
Product Specification 108-93039 10/Mar/2011 Rev F AMP CO Plus Insert for Cat. 6 A Applications 1. SCOPE 1.1 Content This specification covers performance, tests and quality requirements for AMP* CO Plus
More informationTechnical Description. Transistor D.C. Chopper Controller Type GS 24 S
Technical Description Transistor D.C. Chopper Controller Type GS 24 S Table of contents 1. Getting started guide 2. General information 2.1. Characteristics 2.2. Accessories 3. Information about the Machine
More informationPerformance Verification of GigaSPEED X10D Installations with Fluke Networks DTX 1800 CableAnalyzer
SYSTIMAX Solutions Performance Verification of GigaSPEED X10D Installations with Fluke Networks DTX 1800 CableAnalyzer Issue 2 Draft 1 June 2010 Contents Overview 3 GigaSPEED X10D Guaranteed Channel Performance
More informationVIDEO SURVEILLANCE OVER UTP WHITE PAPER INTRODUCING VIPER VIDEO SURVEILLANCE
VIDEO SURVEILLANCE OVER UTP WHITE PAPER INTRODUCING VIPER VIDEO SURVEILLANCE 1 C O N T E N T S Security Systems can be integrated into any IT Network The Network Manager s New Responsibility The Problem
More informationEMC Installation / Application Guidelines VECTORSTAR (VSA) Series Electronics MVS001H. EMC / CE Guidelines
EMC Installation / Application Guidelines VECTORSTAR (VSA) Series Electronics MVS001H EMC / CE Guidelines CONTENTS 1 Introduction... 3 2 Installation / Mounting... 3 3 Power Supply Filtering... 3 4 Motor
More informationUNDERSTANDING AND CONTROLLING COMMON-MODE EMISSIONS IN HIGH-POWER ELECTRONICS
Page 1 UNDERSTANDING AND CONTROLLING COMMON-MODE EMISSIONS IN HIGH-POWER ELECTRONICS By Henry Ott Consultants Livingston, NJ 07039 (973) 992-1793 www.hottconsultants.com hott@ieee.org Page 2 THE BASIC
More informationKVM Cable Length Best Practices Guide
Infrastructure Management & Monitoring for Business-Critical Continuity TM KVM Cable Length Best Practices Guide What Customers Need to Know About Cable Length and Video Quality Cable Length and Video
More informationUnarmored Variable Frequency Drive (VFD) Cable Termination Guide
Authorized Distributor Unarmored Variable Frequency Drive (VFD) Cable Termination Guide Be Certain with Belden A Step-by-Step Look at the Connection/Termination of Unarmored VFD Cables Terminating Unarmored
More information2 Network Media. Copper Core Cable
Network Media Copper Core Cable After studying this chapter, you will be able to: Match the five forms of electronic signals to the media types on which they travel. Describe the major differences between
More informationPanduit 28 AWG Patch Cords Installation Guideline
Panduit 28 AWG Installation Guideline Introduction Panduit is a leading supplier of Structured Cabling Systems and Unified Physical Infrastructure. Panduit solutions enable the physical infrastructure
More informationCategory-6 / Class-E Cabling
Category-6 / Class-E Cabling IEEE 802 Tutorial July 7, 1998 San Diego, CA by: Luc Adriaenssens SYSTIMAX Systems Applications Director Bell Labs of Lucent Technologies How were the ISO Cat-6 Targets set?
More informationOutdoor Carrier Class Shielded Ethernet Cable. Datasheet. Models: PRO, CARRIER, Connectors. Increase Performance. Extreme Weatherproof
Datasheet Outdoor Carrier Class Shielded Ethernet Cable Models: PRO, CARRIER, Connectors Increase Performance Extreme Weatherproof ESD Damage Protection Extended Cable Support 1 2Datasheet Protect your
More informationThis application note is written for a reader that is familiar with Ethernet hardware design.
AN18.6 SMSC Ethernet Physical Layer Layout Guidelines 1 Introduction 1.1 Audience 1.2 Overview SMSC Ethernet products are highly-integrated devices designed for 10 or 100 Mbps Ethernet systems. They are
More informationApplication Note: Modbus/RS485 Wiring for Conext Core XC Series Inverters
Application Note: Modbus/RS485 Wiring for Conext Core XC Series Inverters AP-XC-025 Revision B DANGER RISK OF ELECTRIC SHOCK, EXPLOSION, ARC FLASH, AND FIRE This Application Note is in addition to, and
More informationNetworking 101 (Networking Basics) Presentation to UCHUG - 1/03/07 G. Skalka
Networking 101 (Networking Basics) Presentation to UCHUG - 1/03/07 G. Skalka What is a network? A computer network is two or more computers connected together using a telecommunication system for the purpose
More informationFrom OPEN Alliance BroadR-Reach PHYs to IEEE 802.3bp RTPGE
From OPEN Alliance BroadR-Reach PHYs to IEEE 802.3bp RTPGE The Development of Next-Generation Automotive Ethernet PHYs Mehmet Tazebay, Sesha Panguluri, and Ali Abaye Infrastructure & Networking Group September
More informationSecurity & Surveillance Cabling Systems
Security & Surveillance Cabling Systems Security and Surveillance Cabling Systems The video security industry is growing and ever-changing, offering a wealth of opportunity for today s security professionals.
More informationFN2001-A1 Network module (SAFEDLINK) Mounting Installation
FN00-A Network module (SAFEDLINK) Mounting Installation A6V050_f_en_-- 05-0-6 Building Technologies Division Legal notice Legal notice Technical specifications and availability subject to change without
More informationLocoNet, the Digitrax Difference
LocoNet, the Digitrax Difference LocoNet is Digitrax's method of communication between LocoNet compatible devices on a model railroad layout. LocoNet Compatible devices are designed to work together on
More informationPower Supply V- Bonding, Hum, Buzz, and RFI Should We Bond V- at the Power Supply or Not? Jim Brown K9YC
Power Supply V- Bonding, Hum, Buzz, and RFI Should We Bond V- at the Power Supply or Not? Jim Brown K9YC I've seen numerous anecdotal comments suggesting that all might not be right with the grounding
More informationImplementing Fast Ethernet
Implementing Fast Ethernet R The Next Generation of Ethernet Fast Ethernet (also known as IEEE 802.3u or 100BASE-T) is quickly becoming the successor to Ethernet as the network topology of choice. Fast
More informationLevelOne IFE-0500 4-Port PoE + 1-Port TP Industrial Fast Ethernet Switch User Manual
LevelOne IFE-0500 4-Port PoE + 1-Port TP Industrial Fast Ethernet Switch User Manual Ver. 1.0.0-0711 1 FCC Warning This Equipment has been tested and found to comply with the limits for a Class-A digital
More informationVerizon NEBS TM Compliance: Data Center Equipment NEBS Requirements Verizon Technical Purchasing Requirements VZ.TPR.9703 Issue 2, March 2012
Verizon NEBS TM Compliance: Data Center Equipment NEBS Requirements Verizon Technical Purchasing Requirements VZ.TPR.9703 Issue 2, March 2012 CHANGE CONTROL RECORD: Version Date Action* Reason for Revision
More informationAVX EMI SOLUTIONS Ron Demcko, Fellow of AVX Corporation Chris Mello, Principal Engineer, AVX Corporation Brian Ward, Business Manager, AVX Corporation
AVX EMI SOLUTIONS Ron Demcko, Fellow of AVX Corporation Chris Mello, Principal Engineer, AVX Corporation Brian Ward, Business Manager, AVX Corporation Abstract EMC compatibility is becoming a key design
More informationUnderstanding the Electrical Performance of Category Cables
Understanding the Electrical Performance of Category Cables By: Mike Levesque, Mike Karg & Himmeler Themistocle Obsessed with cable solutions. Understanding the Electrical Performance of Category Cables
More information