IDEA Presentation SMALL CAMPUS CHILLED WATER PLANT OPTIMIZATION.

Similar documents
HIGH PERFORMANCE CHILLED WATER SYSTEMS. EarthWise HVAC. EarthWise HVAC High Performance CHW Plants

CHILLER PLANT CONTROL MULTIPLE CHILLER CONTROLS

Wet Bulb Temperature and Its Impact on Building Performance

ULTRA-EFFICIENT HVAC DESIGN AND CONTROL

Tips and Tricks for Estimating Energy Savings. Celeste Cizik, P.E. Project Manager E M C Engineers, Inc.

HVAC Systems: Overview

Optimizing Design & Control Of Chilled Water Plants Part 5: Optimized Control Sequences

Optimization of Water - Cooled Chiller Cooling Tower Combinations

Commissioning - Construction Documents (Page 1 of 6)

Chapter 3.4: HVAC & Refrigeration System

Chilled Water System Commissioning: Variable Primary Flow. John D. Villani, P.E. Associate Grumman/Butkus Associates

Life Cycle Costing Analysis of Water-cooled Chillers. Chillventa Nuremburg, Germany

What are the Carrier ChillerVu Energy Dashboards?

OPTIMIZING CONDENSER WATER FLOW RATES. W. A. Liegois, P.E. Stanley Consultants, Inc. Muscatine, Iowa


COMMERCIAL HVAC CHILLER EQUIPMENT. Air-Cooled Chillers

The Chilled Water and Hot Water Building Deferential Pressure Setpoint Calculation Chilled Water and Hot Water Pump Speed Control

REAL OPERATING COST SAVINGS FROM RETRO- COMMISSIONING OPPORTUNITIES FOR SAVINGS IN ACADEMIC MEDICAL CENTERS

Hines Property Management, NYC

Heating, Ventilation & Air Conditioning Equipment

Example Retrocommissioning Measure: Opening Throttled Discharge Valves

Agenda. Part I: Introduction to OptimumHVAC. Part II: Initial Energy Savings Analysis for MCO Main Terminal. Part III: Case Studies & Conclusion

Analysis of data centre cooling energy efficiency

Creating Efficient HVAC Systems

KU DESIGN GUIDELINES APPENDIX XVI RECOMMENDED BAS I/O CONTROL POINTS BY EQUIPMENT / SYSTEM

Data Center. Ultra-Efficient chilled water system optimization. White paper. File No: Date: december 03, 2015 Supersedes: new Date: new

Data Realty Colocation Data Center Ignition Park, South Bend, IN. Owner: Data Realty Engineer: ESD Architect: BSA LifeStructures

Water cooled chiller plant (cp/vs)

DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER

See any red flags? Let s take a look at the problems that occurred on the job and how to avoid making the same mistakes.

National Grid Your Partner in Energy Solutions

Measurement & Verification Plan

Automated Commissioning for Energy (ACE) Platform for Large Retail Property. Overview

Texas State University Utility Analysis. Sheri Lara, CEM, CEFP Texas State University Morgan Stinson, PE, LEED AP - EEA Todd Schmitt, PE, LEED AP EEA

Section 2: Estimating Energy Savings and Incentives

Data Center Design Guide featuring Water-Side Economizer Solutions. with Dynamic Economizer Cooling

Printing and Publishing Energy Savings Guide

Heating, Ventilation & Air Conditioning Equipment

ASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014

Cooling Systems 2/18/2014. Cooling Water Systems. Jim Lukanich, CWT ChemCal, Inc. Grapevine, TX

Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia

By Steven C. Severini, P.E., Member ASHRAE

COMMERCIAL HVAC EQUIPMENT. Condensers and Cooling Towers

Denver International Airport Total Facility Optimization. Josh Foerschler Aurom Mahobian

Energy Audits Waste Water Treatment Plants

HVACPowDen.xls An Easy-to-Use Tool for Recognizing Energy Efficient Buildings and HVAC Systems

Model-Based Performance Monitoring: Review of Diagnostic Methods and Chiller Case Study

White Paper #10. Energy Efficiency in Computer Data Centers

STULZ Water-Side Economizer Solutions

Heating & Cooling Efficiency

3/29/2012 INTRODUCTION HVAC BASICS

Dallas/Fort Worth International Airport District Energy Plant Upgrades Project Making More with Less Sustainable Communities Conference Dallas, TX

Building Performance With District Cooling

Benefits of Water-Cooled Systems vs. Air-Cooled Systems for Air-Conditioning Applications

POLK STATE COLLEGE CHILLER PLANT EVALUATION WINTER HAVEN, FLORIDA APRIL 2, C arastro & A ssociates, C&A# 5747

Chapter 2 P-H Diagram Refrigeration Cycle Analysis & Refrigerant Flow Diagram

State of the Art Energy Efficient Data Centre Air Conditioning

Ener.co & Viridian Energy & Env. Using Data Loggers to Improve Chilled Water Plant Efficiency. Randy Mead, C.E.M, CMVP

AIRAH Presentation April 30 th 2014

9. ENERGY PERFORMANCE ASSESSMENT OF HVAC SYSTEMS

Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect

Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks

Large Energy Savings Per Installation VFDs for Large Chillers

Dr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida

Building Analytics Improve the efficiency, occupant comfort, and financial well-being of your building.

Benefits. Air-Cooled Systems

The sample report format is applicable to many different building types and systems and the examples provided cover a variety of applications.

Maintenance for Energy Efficiency

Federal Wage System Job Grading Standards for Air Conditioning Equipment Operating, Table of Contents

Energy Impact of Increased Server Inlet Temperature

Mixing Valves. ARGUS Application Note: Mixing Valves

How To Design A Building In New Delhi

CHILLED WATER PLANT PUMPING SCHEMES. James J. Nonnenmann, PE Stanley Consultants, Inc. Muscatine, Iowa

ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE

85 F 80 F 50% 75 F 70 F 73.0/ F 10% Figure 1

HEAT RECOVERY FROM CHILLED WATER SYSTEMS. Applications for Heat Reclaim Chillers

*At the AHRI Standard flow rate of 3 gpm/ton, using today s efficient chillers, the ΔT is 9.3 F rather than the 10 F often assumed.

District Cooling Plant : Refrigeration Plant Simulation

Defining Quality. Building Comfort. Precision. Air Conditioning

Free Cooling in Data Centers. John Speck, RCDD, DCDC JFC Solutions

Easy Save Plus Energy Efficiency Program Paul Geary

Rittal White Paper 508: Economized Data Center Cooling Defining Methods & Implementation Practices By: Daniel Kennedy

Engineering White Paper UTILIZING ECONOMIZERS EFFECTIVELY IN THE DATA CENTER

Building Energy Systems. - HVAC: Heating, Distribution -

Energy Efficiency Best Practice Guide Industrial Refrigeration

Continuous Commissioning of the Dallas/Fort Worth International Airport

Xcel Business Customers: Program and Rebate Summary

Columbia University Master Planning & Optimization

How to Build a Data Centre Cooling Budget. Ian Cathcart

VARIABLE VOLUME / VARIABLE SPEED SYSTEMS APPLICATIONS

Modeling and Simulation of HVAC Faulty Operations and Performance Degradation due to Maintenance Issues

HEATING AND COOLING GENERATION AND DISTRIBUTION SYSTEMS

How To Save Energy On A Power Supply

How To Test A Theory Of Power Supply

Maximize energy savings Increase life of cooling equipment More reliable for extreme cold weather conditions There are disadvantages

Appendix C. Minimum Equipment Efficiency Standards

Transcription:

IDEA Presentation SMALL CAMPUS CHILLED WATER PLANT OPTIMIZATION.

Pre-Project Details Hawaiian Community College Campus consisting of 16 individual buildings totaling 308,000 sq.ft of conditioned space. Prior to upgrade the central plant consisted of three 15yr to 20yr old chillers & constant primary pumping: Carrier Constant Speed Centrifugal 400Ton York Constant Speed Centrifugal 250Ton Carrier Reciprocating Chiller 100Ton. All cooling valves in the buildings 3-way. Extremely poor performance as a result of deferred maintenance and age of the equipment. Typical central plant performance in the range of 0.9 kw/ton and 1.5 kw/ton. College expansion taking place 2011~2012. Expansion requires additional pumping head to service newly attached buildings.

LCC Campus

Load Profile Equipment Selection Challenge

Proposed Solution Complete central plant upgrade: Two new variable speed chillers. New cooling towers selected for low approach with variable speed drives. Pumping system upgraded to a variable primary/ variable secondary system with 175FT of capability. Air handlers and fan coil units all upgraded to 2-way valves. New campus wide automation system. Central plant M&V equipment installed alongside a chiller plant optimization server.

Proposed Plant Configurations Lowest Cost Const Speed Variable Speed Plant Premium Optimized Plant Two equal sized constant speed centrifugal chillers. Full load = 0.57 kw/ton NLPV = 0.49 kw/ton Primary/ Secondary Chilled water pumping with variable speed secondary pumps. Constant speed condenser water pumps. Two equal sized cooling towers. Tower temperature control 10 F offset from wet bulb. Constant chilled water pump differential pressure set point. Two equal sized variable speed centrifugal chillers. Full load = 0.575 kw/ton NLPV = 0.37 kw/ton Primary/ Secondary Chilled water pumping with variable speed secondary pumps. Constant speed condenser water pumps. Two equal sized cooling towers. Tower temperature control 10 F offset from wet bulb. Constant chilled water pump differential pressure set point. Variable speed magnetic bearing & traditional VFD chiller. Full load = 0.58 kw/ton NLPV = 0.32 kw/ton Primary/ Secondary Chilled water pumping with variable speed secondary pumps. Variable speed condenser water pumps. Four cooling towers. Tower temperature control via optimization loop. Variable chilled water pump differential pressure set point based on AHU valve position.

Performance Comparisons Annual performance : 0.75kW/Ton Annual performance : 0.66kW/Ton Annual performance : 0.56kW/Ton

Proposed Plant Configurations Lowest Cost Const Speed Variable Speed Plant Premium Optimized Plant Annual power consumption: 1,086,855 kwh First cost differential $0 25yr estimated energy cost: $12,680,293 USD Annual power consumption: 960,487 kwh First cost differential $112,500 25yr estimated energy cost: $11,205,974 USD Annual power consumption: 824,967 kwh First cost differential $333,000 25yr estimated energy cost: $9,624,865 USD SIMPLE ROI: 4.2 YRS Vs Lowest Cost Plant SIMPLE ROI: 4.2 YRS Vs Lowest cost Plant 4.8 YRS Vs Variable speed Plant

Chiller Plant Details 1x 400Ton Mag Bearing Oil Free Chiller 1x 400Ton York Chiller with VFD 4 x Low Approach Towers with large flow range Variable speed primary, secondary & condenser pumps. HVAC System optimization/ condition monitoring

Optimization - Strategies Applied Variable primary pumping control with reset based on weighted AHU & FCU valve position. Optimized cooling tower temperature control that utilizes chiller load data and actual cooling tower off design correlations (merkel equations). Optimized sequencing of chillers & pumps using 15min buffered data and actual equipment models. Variable speed condenser water control for part load optimization. Chilled water reset based on AHU fan power, discharge air set point and percentage cooling valve position.

Variable Primary Pumping ΔP Reset Looks at all the AHU & FCU valves in the system. Attempt to maintain valves between 80% and 90% open. Moves the system curve continuously! Resets must take place at a controlled rate and upper and lower limits need to be set. Error conditions such as a stuck open valve need to be detected and handled. Should be implemented along side an air side optimization program that includes AHU condition monitoring.

Variable Primary Pumping ΔP Reset Maintain at 80% to 90% Via dp reset strategy.

Variable Primary Pumping ΔP Reset Reduced head moving system curve limits the system valve throttling and unnecessary pump work. New System Curve

Optimized Tower Control Optimized approach accepts that tower approach at constant load varies with wet bulb temperature. Airs ability to take on heat decreases as wet bulb temperature decreases. Use of constant wet bulb offset results in non optimal control on in many instances. Wet bulb calculation relies on RH% & dry bulb temperature measurements. Commercial grade sensors (capacitive or resistive type) frequently lose calibration or delivered accuracy is less than acceptable error for low approach tower selections

Optimized Tower Control Tower approach and optimal temperature control even more complex when tower water flow is varied. Varying L/G ratio s and the tower performance model is a little understood concept in the common HVAC engineering world. Specialized tools required to perform analysis, tower manufactures programs typically only support selections within +/- 20% of design flow. Only known analysis tools specific to chiller plants: Kiltech Inc: 4years to assemble a field tested and validate tool. Taylor Engineering cooltools (inhouse program database).

Optimized Tower Control

Finding the Energy Sweet spot

Optimized Chiller Sequencing When applied to variable speed chillers algorithm needs to accept that chiller performance on a VFD centrifugal varies greatly with lift (CWRT CHWST). Constantly changing sequence point! Compressor operation at higher lift have smaller operating envelopes (compressors run closer to the surge line). Optimized sequencing needs to look at load, condenser water flow rate and lift.

Optimized Chiller Sequencing CPECS uses a multivariate regression model to predict chiller performance based on: CHWST CWST CWRT Power Input Evaporator and Condenser Approach temperatures. CAPFT = a + b*chws + c*chws^2 + d*cwrt + e*cwrt^2 + f*chws*cwrt Standard DOE models never used as they are EIRFT = a + b*chws + c*chws^2 + d*cwrt + e*cwrt^2 + f*chws*cwrt EIRFPLR made = a at + b*plr constant + c*plr^2 condenser + d*dt + e*dt^2 + water f*plr*dt flow rate and do not adjust to real world tube fouling.

Typical Chiller Performance Model at fixed leaving chilled water temperature

Optimized Chiller Sequencing Putting the chiller performance models to work

Optimized Chiller Sequencing How does it work? 15min rolling averaged conditions are used in an iterative algorithm that seeks to select the right number of chillers that satisfy the cooling load at the lowest kw input. Minimum chiller flows must be taken into account. Additional loads such as dedicated primary pumps or condenser water pumps should be included. Predicted demand and time of day useful to avoid short cycling

Variable Speed Condenser Water Pumping Needs to be carefully analyzed against load profile prior to selection of strategy. 30% of surveyed applications should not adopt this. Needs to be made in conjunction with tower control optimization strategy. 15% error on flow can result in operation less efficient than constant speed pumping. Tower minimum flow (fill coverage) needs to be closely adhered to. Chiller minimum flow and fouling avoidance needs to be taken into account know your condenser design tube velocity.

Variable Speed Condenser Water Pumping VFD chiller performance changes rapidly with lift! Lift is based on leaving condenser water temperature not entering low condenser water temperature at low flow might get you the same result as full flow with a higher temperature (less fan power). Algorithm seeks to achieve lowest: CHILLER KW + TOWER KW + COND PUMP KW

Putting it all together

Optimization How do we know it works? Continuous feedback. Displayed target values. Visual Real-time Comparison to baseline performance models. Reporting with traceable accuracies. Beware of the green washers

Comparison with actual results equest Vs Actual

APRIL 2013

APRIL 2013 Actual operating hours greater than original model. Peak load within 4% of model. Increase in Ton-hrs proportional to the increase in operating hours. Modeled performance Vs actual performance for month of April was 0.55kW/Ton Vs 0.53kW/Ton. Actual performance within 4.3% of initial analysis.