Resolution of comments 242 and 267 on Insertion loss measurements of installed fiber cables. Steve Swanson May 5, 2009



Similar documents
Migration Strategy for 40G and 100G Ethernet over Multimode Fiber

Fibre optic testing best practices

FIBER OPTIC SYSTEM TEST PROCEDURES

What testing is required for PREMISES Fiber Optic Cabling and the standards used

The Need for Speed Drives High-Density OM3/OM4 Optical Connectivity in the Data Center

Optical Fiber Data Center Field Testing. ANSI/BICSI Data Center Design and Implementation Best Practices

How To Properly Maintain A Fiber Optic Infrastructure

USE OF FIBRE OPTICS INTERNATIONAL STANDARDS FOR CALIBRATION LABORATORY ACCREDITATION INTERNATIONAL ELECTROTECHNICAL COMMISSION

NORTH ORANGE COUNTY COMMUNITY COLLEGE DISTRICT SECTION STRUCTURE CABLING TESTING

Migration to 40/100G in the Data Center with OM3 and OM4 Optical Connectivity

SECTION TESTING OF FIBER OPTIC CABLES

Guidelines. LANscape Solutions Recommended Fiber Optic Test Guidelines. Table of Contents. 1. Introduction. 2. Why Test? 1. Introduction...

CISCO 10GBASE X2 MODULES

Field Measurements of Deployed Fiber

Data Center Design for 40/100G

12 Fibre MTP Jumper, MTP (non-pinned) to MTP (pinned)

Splicing and Fiber Assembly Compatibility for Non-Zero Dispersion-Shifted Fiber and Standard Single-Mode Fiber

How To Make A Data Center More Efficient

Fiber in the Data Center

The Need for Low-Loss Multifiber Connectivity

Four Ways To Test Installed Fiber Optic Cables And How The Results Will Differ With Each Method

Attaching the PA-A1-ATM Interface Cables

Specifying Optical Fiber for Data Center Applications Tony Irujo Sales Engineer

99 Washington Street Melrose, MA Phone Toll Free Visit us at

Will Your Fiber Optic Cable Plant Support Gigabit Ethernet?

Physical Infrastructure trends and evolving certification requirements for Datacenters Ravi Doddavaram

Patch Cords for Data Center Applications

Best Practices for Ensuring Fiber Optic System Performance. David Zambrano

Upgrading Path to High Speed Fiber Optic Networks

Cabling & Test Considerations for 10 Gigabit Ethernet LAN

The Optical Fiber Ribbon Solution for the 10G to 40/100G Migration

Loss & Continuity Testing with MPO/ MTP Connectors

The migration path from 10G to 40G and beyond for InstaPATCH 360, InstaPATCH Plus and ReadyPATCH installations

The Evolution of Copper Cabling Systems from Cat5 to Cat5e to Cat6 Copper Cabling Standards and Technical Aspects

Highlights: ISO/IEC SC25/WG3 Meeting Berlin: May Customer Premises Cabling -

Obsolete Fiber Technology? Not in my Data Center!

European Normative EN system

Field Testing Multimode 10 Gb/s (and beyond) Fiber Permanent Links

Cisco SFP Optics for Gigabit Ethernet Applications

Special Specification 6033 Computerized Transportation Management System

MTP Optical Fibre Configurations

Removing the Mystery from OTDR Measurements. Keith Foord Product Manager Greenlee Communications

Design Guide. SYSTIMAX InstaPATCH 360 Traffic Access Point (TAP) Solution.

Cisco Small Form-Factor Pluggable Modules for Gigabit Ethernet Applications

Accurately Testing fibre Optic Cables

Fiber-to-the-Home/FTTH

Measuring of optical output and attenuation

Dat Da a t Cen t Cen er t St andar St d andar s d R o R undup o BICSI, TIA, CENELEC CENELE, ISO Steve Kepekci, RCDD

Cabling Standards Update 2014

Polymer Coated Fiber Cable (PCF)

Service Description blizznetdarkfiber

Fibre Channel Fiber Cabling

Requirements for Modular Patch Cords (e.g. RJ45 patch cords for Cat5 and Cat6 cabling systems)

Enterprise Networks EMEA. Core Products FOR DATA CENTRES

MPO. Fast Fibre Solution for Data Centres

MTS/T-BERD Platforms Very Long Range (VLR) OTDR Module

Plug & Play Gigabit Ethernet Media Conversion Module. Application Note

Managing High-Density Fiber in the Data Center: Three Real-World Case Studies

Method for improving Return Loss in order to reduce PHY power Ron Nordin Panduit Bob Wagner Panduit Paul Vanderlaan Berk-Tek

The ABC of Direct Attach Cables

Specifying Optical Fiber for Data Center Applications Tony Irujo Sales Engineer

FRONTIER TELEPHONE COMPANIES TARIFF FCC NO. 6 Original Page 19-1 ACCESS SERVICE INTERCONNECTION BETWEEN COLLOCATED SPACES

White Paper: 10GbE Fiber A Practical Understanding and Functional Approach

The Importance of minembc Laser Bandwidth Measured Multimode Fiber for High Performance Premises Networks White Paper

PURE : REliable planning of data center cabling

Understanding Fiber Polarity: Implications at 10G, 40G, & 100G

Overcoming OM3 Performance Challenges

CISCO DWDM XENPAK. Main features of the Cisco DWDM XENPAK include:

HUBER+SUHNER AG Phil Ward

Structured Connectivity Solutions Field Testing Guidelines for Fiber-Optic Cabling Systems

Ethernet 301: 40/100GbE Fiber Cabling and Migration Practices

Module 13 : Measurements on Fiber Optic Systems

SECTION TELECOMMUNICATIONS ACCEPTANCE TESTING

How To Make A Fibre Cable For A Data Centre

CABLE ASSET MANAGEMENT PREDICT WITH CERTAINTY. Kuljit Singh BSc Honours MIEE(IET,UK) 5 June 2014

USB 3.0 Cables. Color. Black Black Black Black Black Black Black Black Black Black

Fibre Channel Fiber-to-Fiber Media Converters

Cabcon. Data Centre Solutions. an acal group company UK +44 (0) IRE (00353)

Data Centre Cabling. 20 August 2015 Stefan Naude RCDD The SIEMON Company

Tapping Technology. Just the Facts about the Pretium EDGE Tap Module

Data Center Optimization: Component Choice. Innovative Design. Enabling Infrastructure

Optical Fiber. Smart cabling: constructing a cost-effective, reliable and upgradeable cable infrastructure for your enterprise network

As today s evolving data centers

Fiber Optic Cable Assemblies. Pigtails, Jumpers (simplex and duplex), Fanouts, Pre-connectorized Multi-Fiber Cable

Physical Infrastructure trends and certification requirements for Datacenters. Psiber s Global Village

Technical Bulletin. Guidelines For Testing And Troubleshooting Fiber Optic Installations

Optimizing Infrastructure Support For Storage Area Networks

ANSI/TIA/EIA A A Revisited. Residential Telecommunications Cabling Standard (Draft 6/22/99) Larry L. Hamlin, RCDD

TIA Releases Guidelines for Maintaining Polarity Using Array Connectors

Optical Communications Analysis of transmission systems. Henrique Salgado Point-to-point system

Ethernet/IEEE evolution

Table of Contents. Fiber Trunking 2. Copper Trunking 5. H-Series Enclosures 6. H-Series Mods/Adapter Panels 7. RSD Enclosures 8

Cascade Profiler Fibre Channel SAN Attached Storage Installation Guide. Version 8.2 March 2009

Billions of arithmetic operations per second what s their value without cabling?

USB 3.1 Channel Loss Budgets

Gigabit Passive Optical Networks

DIVISION 27 COMMUNICATIONS. A. System design shall be completed by a Registered Communications Distribution Designer (RCDD).

Cable Assemblies. Features and Benefits

How To Get A Better Signal From A Fiber To A Coax Cable

Plug - Type (Male/Female) Attenuators CAA series Singlemode

Transcription:

Resolution of comments 242 and 267 on Insertion loss measurements of installed fiber cables Steve Swanson May 5, 2009

Current text in 86.10.1 Insertion loss measurements of installed fiber cables are made in accordance with IEC 61280-4-1/Method 2. The fiber optic cabling (channel) contains 4 or 10 optical fibers for each direction to support 40GBASE-SR4 or 100GBASE-SR10, respectively. The fiber optic cabling interconnects the transmitters at the MDI on one end of the channel to the receivers at the MDI on the other end of the channel. As defined in clause 86.10.3, the optical lanes appear in defined locations at the MDI but the locations are intentionally not assigned specific lane numbers within this standard because any transmitter lane may be connected to any receiver lane. [Editor s note (to be removed prior to publication) - IEC 61280-4-1/Method 2 will be renamed IEC 61280-4- 1/Annex A when a revised IEC 61280-4-1 (currently at FDIS stage) is published.] 2

Comments on 86.10.1 Swanson comment 242 We need to allow both the 1 jumper method and the 3 jumper method for the measurement of insertion loss because field test equipment may not have the MPO connector. Coleman comment 267 Referenced 1 jumper method is restrictive as it requires usage of field test equipment with MPO connector interfaces. To my knowledge, field test equipment with a MPO interface is not commercially available now or in the near future. Recommend inclusion of the 3 jumper method to accommodate utilization of legacy and existing commercial field test equipment. 3

IEC 61280-4-1 Four measurement methods are designated. The four measurement methods use test cords to interface to the cable plant and are designated as follows: one-cord reference method; three-cord reference method; two-cord reference method; optical time domain reflectometer (OTDR) method. The main functional difference between these methods is the way the input power level, known as the reference power level, is measured and hence the inclusion or exclusion of the losses associated with the connections to the cabling under test, and the associated uncertainties of these connections. 4

Overview of test methods A 1-jumper reference typically provides the most accurate and appropriate test for your system. A 2-jumper reference should only be used when your system begins at a patch panel and ends directly in end-equipment. A 3-jumper reference should be used when your system begins and ends directly in the end equipment. 5

1-jumper vs. 3-jumper test method The one-cord reference method includes the attenuation associated with connections at both ends of the cabling under test. The three-cord reference method attempts to exclude the attenuation of the connections of both ends of the cabling under test. The maximum allowed cabling attenuation specified (e.g. optical power budget or channel insertion loss) for a transmission system normally excludes the connections made to the transmission equipment. It is therefore appropriate to use the three cord reference method where the cabling under test is intended to be connected directly to transmission equipment. Either method can be used adjustments are needed 6

1-jumper test configuration 7

3-jumper test configuration 8

Cabling configurations 9

RTMs 10

Example for 1-jumper test A multimode cabling system 100 m long is terminated in a patch panel at each end. The expected loss, assuming standard grade connectors, would be a total of up to 1,35 db, assuming 3,5 db/km cabled optical fibre loss and 0,5 db per connection. If this system is measured using the one test cord reference method as described, and using reference grade terminations on the test leads, then the loss will be up to 0,95 db (0,35 db for the 100 m of optical fibre plus 0,3 db for each connection between reference grade and standard grade terminations). For each reference grade to standard grade connection, i.e. in the measurement configuration, an adjustment of 0,2 db should be subtracted from the acceptance figure. 11

Example for 3-jumper test Consider the above cabling system but with equipment connection cords with standard grade terminations connected into the patch panels. The loss excluding the terminal connectors will be the same as in example 1, i.e. 1,35 db. If this is tested as a cabling system terminated with connector plugs using the three-test-cord reference method, then the measured loss will 1,75 db. This assumes 1,35 db for the cabling as before, plus 2 0,2 db, since two reference-grade-to-reference-grade connections were included in the reference measurement, which are replaced by two reference-grade-to standard grade connections in the measured power level through the cabling. For each reference-grade-to-reference-grade connection in the reference measurement that is replaced by a reference-grade-to-standard grade connection in the measurement configuration, an adjustment of 0,2 db should be added to the acceptance figure. 12

Summary Either method can be used provided the results are adjusted to reflect what is being measured For the 1-jumper method, the acceptance figure is adjusted down For the 3-jumper method, the the acceptance figure is adjusted up 1-jumper is preferred if cable plant can be plugged directly to power meter (same connectors) 3-jumper is preferred if cable plant cannot be plugged directly to power meter (different connectors) 13