THE REPLACEMENT OF R-22



Similar documents
RS-44 (R424A) : Q & A

RS-24 (R426A): Q & A

RS-52 (R428A) RS-52: PHYSICAL PROPERTIES RS-52 R502 Molecular weight Temperature glide o C Boiling point (1 atm)

SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS

R407C GUIDELINES FOR UTILIZATION OF. DATE: August 2009 REFERENCE DOCUMENT NO. RD-0005-E GUIDELINES FOR UTILIZATION OF R407C

Performance of R-438A in R-22 Refrigeration and Air Conditioning Systems

Repair, Retrofit, or Replace Choices for Servicing R-22 Equipment

Environmental and Safety Impacts of HFC Emission Reduction Options for Air Conditioning and Heat Pump Systems

The EC Ozone Regulation. Legislative Update and Strategies for HCFC Phase-out

Low GWP Replacements for R404A in Commercial Refrigeration Applications

Guidance for Stationary Refrigeration & Air- Conditioning

PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM WITH R404A, R407C AND R410A

Planning for the ban on R22 in building air conditioning

Mohan Chandrasekharan #1

EU f-gas regulation EN 517/2014.

Commercial refrigeration has been in the environmental. Refrigerant. as a. Basics Considerations PART 1:

Performance of R-438A in R-22 Refrigeration and Air Conditioning Systems

Automobile Air Conditioning Primer

PG Student (Heat Power Engg.), Mechanical Engineering Department Jabalpur Engineering College, India. Jabalpur Engineering College, India.

Low-GWP Refrigerants for Air Conditioning and Refrigeration Applications. Samuel F Yana Motta

Technical Note: Comparing R407C and R410A as Alternatives for R22. A Technical Note from the Experts in Business-Critical Continuity

REFRIGERANT REFERENCE GUIDE

Refrigerant identification and equipment issues in relation to HCFC phase-out. Ole Reinholdt Nielsen

HCFC-22 Retrofits. There has been increased emphasis on retrofitting R-22

Patech. Our Conviction. Quality Service Innovation PATECH FINE CHEMICALS CO., LTD

Refrigerant Changeover Guidelines R-22 to R-407C. Leading the Industry with Environmentally Responsible Refrigerant Solutions

Refrigerant Changeover Guidelines HCFC R-22 to HFC R-404A/R-507. Leading the Industry with Environmentally Responsible Refrigerant Solutions

THEORETICAL AND EXPERIMENTAL EVALUATION OF AUTOMOBILE AIR-CONDITIONING SYSTEM USING R134A

The Development of Heat Pump Water Heaters Using CO 2 Refrigerant

Engineers Newsletter. HVAC Refrigerants: A Balanced Approach. providing insights for today s hvac system designer. volume Refrigerant History

Refrigerant Changeover Guidelines R-22 to R-407C. Leading the Industry with Environmentally Responsible Refrigerant Solutions

TEST REPORT #31. System Drop-in Test of Refrigerant R-32 in Split Air-conditioning System

Part A: Fluid properties

DuPont Opteon XP10: A new option for more environmentally sustainable commercial refrigeration

Variable Capacity Compressors, a new dimension for refrigeration engineers to explore

P08 Köldmedier med låg växthuseffekter

A Performance Comparison of Vapour Compression Refrigeration System Using Eco Friendly Refrigerants of Low Global Warming Potential

HCFC phase-out has started.

EU F-Gas Regulation Guidance Information Sheet 5: Stationary Air-conditioning and Heat Pumps

Guidance for Stationary Refrigeration & Air-Conditioning

Analysis of Alternative Refrigerants to HCFC-22

REFRIGERATION (& HEAT PUMPS)

REFRIGERANT 410A. Refrigeration Service Engineers Society 1666 Rand Road Des Plaines, Illinois Information compiled by Frank Prah, CMS

Refrigerants for Residential and Commercial Air Conditioning Applications

Evaluation of HFO-1234yf as a Potential Replacement for R-134a in Refrigeration Applications

Scroll compressors for Low GWP Heat Pumps using R290 natural refrigerant. Pierre Ginies, Next Heat Pump Generation 2015

Guide to good leak testing

Why and How we Use Capacity Control

TRAINING, EXAMINATION AND CERTIFICATION

Refrigeration and Airconditioning Prof. M. Ramgopal Department of Mechanical Engineering Indian Institute of Technology, Kharagpur

EU F-Gas Regulation Guidance Information Sheet 14: Refrigeration, Air-Conditioning and Heat Pump Contractors

Chapter 3.4: HVAC & Refrigeration System

Lesson. 11 Vapour Compression Refrigeration Systems: Performance Aspects And Cycle Modifications. Version 1 ME, IIT Kharagpur 1

Industry insight. Refrigerant gases: an industry in transition.

Refrigeration and air-conditioning. Alfa Laval s offering at a glance

Regency TAFE, SA. An evaluation of the effects of PermaFrost treatment on a Fujitsu Heat Pump. July Prepared by

Update on a Low GWP Refrigerant: Fluid H

TECHNICAL INFORMATION

CPX/HT Series. REFRIGERATED AND HIGH TEMPERATURE DRYER 12 to 2400 CFM. High-performance products. Designed for you!

Commercial CO 2 Refrigeration Systems

Troubleshooting HVAC/R systems using refrigerant superheat and subcooling

USC CFC Leak Repair and Recordkeeping Procedures

TEST REPORT #44. System Drop-in Tests of Refrigerant R-32 in Single Packaged Vertical Heat Pump (SPVH)

R-32. The next generation refrigerant for air conditioners and heat pumps

News in Data Center Cooling

HFCS, REFRIGERATION AND AIR-CONDITIONING: MINIMISING CLIMATE IMPACT, MAXIMISING SAFETY

Cold Room & Refrigeration System (Casserole Assembly) No of units: 1

Recommended Compressor Installation Practices

HVAC For Schools How to purchase an HVAC system that meets your school s unique requirements and stays within your budget

Air Conditioning & Refrigeration Master Catalog. Catalog CIC /USA April 2003

D A T A S H E E T. TX6 Thermo Expansion Valves. Alco Controls TX6. Features. Introduction. Construction

TECHNICAL ANNEX. Alternatives to HCFCs/HFCs in unitary air conditioning equipment at high ambient temperatures. November 2014

HVAC-02, Air Conditioning Troubleshooting and Repair

Rusty Walker, Corporate Trainer Hill PHOENIX

Heat Recovery In Retail Refrigeration

Guide to updated EU f-gas regulation (517/2014).

SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS

A Comparison of an R22 and an R410A Air Conditioner Operating at High Ambient Temperatures

COURSE TITLE : REFRIGERATION AND AIR CONDITIONING COURSE CODE : 4029 COURSECATEGORY : A PERIODS/WEEK : 5 PERIODS/SEMESTER : 90 CREDITS : 4 OBJECTIVES

Waste Heat Recovery through Air Conditioning System

D A T A S H E E T. TX3 Thermo Expansion Valves. Alco Controls TX3. Features. Introduction. Description of bulb charges

Heating and Air Conditioning

EU F-Gas Regulation Guidance Information Sheet 15: Fire Protection System Contractors

How does solar air conditioning work?

SERVICE BULLETIN AIR CONDITIONER COMPRESSOR FAILURES ALSO SEE BULLETIN #SB3-304AS (SYSTEM CONTAMINATION)

AUTOMOTIVE AIR CONDITIONING

UNDERSTANDING REFRIGERANT TABLES

Commercial CO2 Refrigeration Systems. Guide for Subcritical and Transcritical CO2 Applications

Flushing and Cleaning the A/C System

Ground-breaking conversion of critical Data Room WaterChiller from R22 to R422D / MO29

Refrigerant Choices for Commercial Refrigeration. Finding the Right Balance

NOTE: If the HF body is stamped HFK, then the cage is replaceable. HF N E S C B 2 H C 5 FT 3/8 x 1/2 ODF S/T Valve Series

Impacts of Refrigerant Charge on Air Conditioner and Heat Pump Performance

F-Gas Compliance. To provide a process for F-Gas Leak Testing in accordance with legislative requirements.

A car air-conditioning system based on an absorption refrigeration cycle using energy from exhaust gas of an internal combustion engine

MIDLAND COLLEGE SYLLABUS DEMR 1323 AUTOMOTIVE HEATING AND AIR CONDITIONING 2-4

Refrigerants for residential and commercial air conditioning applications

Get the FACTS about SEER and Deliver Better Customer Value

DESIGN AND APPLICATION OF AMMONIA HEAT PUMP SYSTEMS FOR HEATING AND COOLING OF NON-RESIDENTIAL BUILDINGS

THE POSSIBILITY OF USING LIQUIFIED PETROLEUM GAS IN DOMESTIC REFRIGERATION SYSTEMS

Transcription:

ENGLISH TRANSLATION OF ARTICLE IN FRIO-CALOR AIRE ACONDICIONDAO BY GAS-SERVEI, S.A JUNE 2010 THE REPLACEMENT OF R-22 Courtesy of D. Lluis Giralt Lopez (Chemical Engineering Industrial) Gas Technical Department of Gas Servei S.A. Following the entry into force of European Regulation No. 2037/2000, from 1 January 2010, the sale & use of virgin R-22, as well as the rest of all newly produced HCFCs, has been banned. This regulation seeks to protect the atmospheric environment by reducing emissions that affect ozone destruction and the greenhouse effect (GWP). Concerned about the difficulty this will produce in the future, for more than 11 years GAS-SERVEI, SA, has been actively involved in the development, testing and practical application of most of the solutions offered by the chemical industry, the sole purpose of which is to extend the life of refrigerating and air conditioning installations which have been originally designed & manufactured for use with HCFC refrigerants. This wealth of expertise and practice has resulted in a range of substitutes which are effective & easy to apply. Consequently, considering that most contractors & and users require equivalent cooling, no oil change & a simple retrofit, published in this article is a comparative study of the two most recognized product lines in the market, the RS series & ISCEON range of refrigerants with their own characteristics and benefits. In this article we focus on the substitution of R-22 (HCFC). Of the comparative properties to take into account when selecting the appropriate refrigerant, it is important to consider the temperature glide because the larger the glide the greater the chance of fractionation during leakage. If the glide is very high, the gas charged in the system needs to be recovered & replaced with a fresh charge of refrigerant. In addition to the beneficial properties of the refrigerant, selection of which solution to apply will also be determined by the total cost of the retrofit & the time involved. All refrigerants discussed in this article have an A1 safety classification, that is to say, of low toxicity & nonflammable. DEFINITIVE SOLUTIONS HFC Among the possible solutions using HFC substitutes, we find two alternatives: Refrigerants which require replacement of mineral oil with POE, called Indirect. Refrigerants which can be used with mineral oil, which does not need to be replaced, called Direct.

2 Refrigerants requiring an oil change to replace R-22, Indirect solutions In air conditioning applications at average temperatures: R-407C &R-427A. These refrigerants are very similar in performance, as can be seen in Table I, & both products will fractionate in the case of leakage due to their high temperature glide. Table I Refrigerant Components Composition GWP R-507C R-125:R-143a 50:50 3850 R-404A R-125:R-143a:R-134a 44:52:4 3784 R-407C R125:R134a:R32 25:52:23 1523 R-427A R125:R134a:R32:R143a 25:50:15:10 2013 R-417A R125:R134a:R600 46.6:50:3.4 2234 R-422D R125:R134a:R600a 65.1:31.5:3.4 2623 R-424A R125:R134a:R600a:R600:R601a 50.5:47:0.9:1.0:0.6 2328 R-434A R125:R143a:R134a:R600a 63.2:18:16:2.8 3131 Temperature Glide R- 434A (RS-45) R-424A(RS-44) R-422D(l-29) R-422D (I-29) R-417A(l-59) R-427A R-407C R-507 R-404A Refrigeration, medium & low temperatures: R404A & R507. These refrigerants are ideal for new installations. Amongst other things, for systems operating on R22, there needs to be two or three oil changes, safety valves & pressures checked & the condenser to be oversized.

3 Refrigerants which do NOT need an oil change when replacing R22, Direct solutions Installations with a fixed orifice or capillary tube at temperatures down to - 15C: R424A (RS-44) & R417 (Isceon 59) Installations with an adjustable expansion device at temperatures down to - 35C: R434A (RS-45) & R422D (Isceon 29) The temperature glides of the various alternatives can be seen in Table 1. Advantages of Direct replacements Rapid, definitive, simple & economic replacement HFCs not harmful to the ozone layer No need to change the oil in the majority of cases, compatible with traditional & new lubricants Maintains existing equipment Test by manufacturer show that R424A & R434A can be mixed with r22 in any proportion Discharge temperatures are significantly lower than R-22, which extends compressor life The capacity & efficiency of R-22 can be reached in most systems. To continue we will comment on the differences between the main properties of both sets of replacements for direct substitution of R22. R424A (RS-44) & R417A (Isceon 59) Both products will have a slight loss of capacity which will depend upon the design of the equipment. Because R424A contains a little more R125 in its formulation, the loss of capacity will be less than when using R417A. Both products have a temperature glide of 3 0 C, so that the charge does not need to be replaced in the event of a leak, The different studies recommend if required the possibility of recharging a leakage of R-22 with R-434A (RS-45), which provides a quick & economic solution.

4 R434A (RS-45) & R422D (Isceon 29) It is important to use both of these refrigerants with adjustable expansion devices in order to set the correct superheat. It is advisable not to use these products with capillary tubes because they are more dense than R22 with a higher mass flow. There are 2 important differences between these products: Temperature glide: R422D has a glide of 4.5 0 C which compares with 1.5 0 C for R434A. Refrigerating capacity: R434A has the same capacity as R22. On the other hand, R422D can show a reduction of 5 0 C when evaporating at 7 0 C, & this lack of capacity increases to 9 0 C at -35 0 C evap. Table II: Comparative performances of alternatives in refrigeration -35 0 C Evaporating -35 0 R-22 R-434A R-422D R-404A R507 C Condensing Discharge pressure (bar) 14.07 15.55 14.26 16.78 17.22 Discharge temp ( 0 C) 197.0 119.06 120 123.5 121.6 Cooling capacity Kj/m 3 619 632 562 705 729 % of R-22 100 102 91 114 117 COP 1.27 1.28 1.29 1.27 1.26 Compression ratio 11.4 11.4 12.3 10.7 10.5 Temperature glide ( 0 C) 0 1.50 4.5 0.5 0 Flow rate 5.67 7.92 7.88 7.57 7.79 Mineral oil Yes Yes Yes No No POE Yes Yes Yes Yes Yes

5 Table III: Comparative performances of alternatives in airconditioning +7 0 C Evaporating +45 0 R-22 R-424A R-434A R-422D R-417A R-407C R-427A C Condensing Discharge pressure (bar) 17.91 16.25 19.81 18.24 15.74 19.3 18.63 Discharge temp ( 0 C) 111.4 83.9 81.9 81.5 84.0 97.7 93.7 Cooling capacity Kj/m 3 3062 2654 3115 2912 2500 3189 3065 % of R-22 87 102 95 85 104 100 COP 3.20 3.23 3.12 3.17 3.25 3.19 3.2 Compression ratio 3.00 3.21 3.00 3.11 3.21 3.20 3.18 Temperature glide ( 0 C) 0 3.0 1.5 4.5 3.0 7.4 7.1 Boiling point ( 0 C) -40.80-38.70-44.90-45.70-38.40-43.70-42.70 Mineral oil Yes Yes Yes Yes Yes No No POE Yes Yes Yes Yes Yes Yes Yes What do these differences imply? R422D, evaporating at positive temperatures, has some loss of capacity which, although bearable, is not found with R434A. In regard to refrigeration applications, many installation contractors have not been considering R422D as a possible replacement for R22 due to the lack of refrigerating capacity & are resorting to r404a & R507 as the only solutions. With no lack of capacity, R434A is the only possible direct solution on the market for the range of temperatures and especially in high performance equipment, such as flooded evaporators. The different studies recommend if required the possibility of recharging a leakage of R-22 with R-434A (RS-45), which provides a quick & economic solution. What problems are there with direct replacements? Oil return depends on certain conditions of design & operation of equipment. In some systems with long and complex pipelines, flooded evaporators, operating at low temperatures or containing a low pressure received, we recommend the replacement of whole or part (approx. 25%) of the existing oil with POE. The orifice of the refrigerant expansion device may require changing to the equivalent of R- 404A or replacing with a new valve able to accommodate the higher flow rate of R-404A.

6 What problems can be found in solutions of direct and indirect substitution? * Depending on the age & condition of the installation, it may be required to replace all gaskets. Some elastomeric seals are not compatible with HFCs. The plastics (teflon, viton, HNBR, etc.) are appropriate. Looking at Tables II and III, all data is taken from manufacturers information, the latest edition of Refrigerant Report 15th edition by Bitzer and the software programme Refprop, CONCLUSIONS We are aware that indirect solutions for retrofitting, especially for replacing R22 in refrigeration, tend to be expensive, slow, and can result in problems such as leakage, the effect of POE oils on old facilities. As we experience difficult economic times, many users still have not made any decision to replace R22, and summer is already in full swing. Therefore, there will not be any other solution than direct substitutes. The RS series, due to their excellent performance and low temperature glide, are the perfect products, together with Series 9 (ISCEON) to meet the urgent situation which has arisen due to the lack of reclaimed R-22 in order to maintain equipment in service. Only small amounts of reclaimed R22 available will remain on the market in July.