F-Gas Compliance. To provide a process for F-Gas Leak Testing in accordance with legislative requirements.
|
|
|
- Shauna Armstrong
- 9 years ago
- Views:
Transcription
1 F-Gas Compliance EMS DOCUMENT TYPE: ENVIRONMENTAL ASPECT: PURPOSE: Operational Control Document Emissions to Air To provide a process for F-Gas Leak Testing in accordance with legislative requirements. Record of changes made to this document: NH Minor amends following meeting with current contractors NH Minor Amends in respect of SF6 Responsibilities NH Major amends to reflect legislative and procedural changes Introduction: This operational control document implements the requirements of the The Fluorinated Greenhouse Gases Regulations These Regulations revoke and replace the Fluorinated Greenhouse Gases Regulations 2009 and help to enforce Regulation (EU) 517/2014 on fluorinated greenhouse gases. These new Regulations update the qualification requirements, and set out details of offences and how they will be enforced. The Regulations addresses the use of fluorinated gases, including HFCs, PFCs and SF₆, (hydrofluorocarbons, perfluorocarbons and sulphur hexafluoride). This guidance focuses on installations and equipment that use refrigeration, air conditioning and heat pump technology. However, certain fire protection equipment that contains F-gases may also be subject to the legislation. The University should be particularly concerned with two sources of F-Gases : Stationary refrigeration (e.g cold stores) and air conditioning (RAC) SF 6 as an insulating medium in HV switchgear The generic obligations regarding RAC systems are: Take steps to prevent F-gas leakage and repair leakages as soon as possible. Regularly check for leakages. Fit auto leak detection systems on large systems. Keep certain records about known F-gas locations. Recover F gases during servicing, maintenance and end of life. Use appropriate qualified personnel to carry out installation, servicing, maintenance and leakage checking. Label new equipment adjacent to service point and instruction manuals. Requirements for Leak Testing: Previous legislation had the frequency for leak testing based on the quantity in Kg of F-gas contained within a system. The legislation now requires testing to be based on the environmental impact of the F-gas, this is calculated using a defined value of global warming potential (GWP) specific to each gas which can be multiplied by the volume of gas held in each piece of equipment. The calculating equation is: GWP x (Quantity of F-gas in Kg / 1000) = CO 2 e (Environmental Impact) A table detailing the GWP values for key F-gases can be seen in Appendix 1. Leak checks must be carried out with the following frequency, for equipment that contains fluorinated greenhouse gases in quantities of: Copyright Loughborough University Page 1 of 6
2 5-50 tonnes of CO 2 e or more: at least every 12 months, or where a leakage detection system is installed, at least every 24 months; tonnes of CO 2 e at least every six months or, where a leakage detection system is installed, at least every 12 months; Hermetically sealed equipment that contains fluorinated greenhouse gases in quantities of less than 10 tonnes of CO 2 e will not be subject to leak checks, provided the equipment is labelled as hermetically sealed. Electrical switchgear will not be subject to leak checks provided it: has a tested leakage rate of less than 0,1 % per year as set out in the technical specification of the manufacturer and is labelled accordingly; is equipped with a pressure or density monitoring device; or contains less than 6kg of fluorinated greenhouse gases. By way of derogation, until 31 December 2016, equipment that contains less than 3 kg of fluorinated greenhouse gases or hermetically sealed equipment, which is labelled accordingly and contains less than 6kg of fluorinated greenhouse gases will not be subject to leak checks. Where the CO 2 e is 500 tonnes or more a leakage detection system must be fitted which alerts the operator or a service company of any leakage. Loughborough University s Process: 1. The University contracts out the maintenance, service and proactive leak testing of Switchgear, Refrigeration and Air Conditioning equipment. 2. The contractors used are to provide both company certification and individual certification for all engineers working on our site. These will be checked annually by the Maintenance Contracts Manager or Environmental Manager. Further details on certification can be seen in Appendix The University will maintain a register of all units containing F-gases and review this regularly to ensure it is upto date. Responsibility for ensuring this is updated ultimately rests with the Duty Authorised Person but others have roles as follows: a. Contracts Manager is to ensure the register is upto date before it is issued to any contractor. b. SMS Administrator will support the maintenance of the register in SMS. c. Any department who adds, removes or modifies equipment is to provide details of the changes made to the SMS administrator, (this includes but is not limited to Schools, FM Development, Technical Services, Asset Care). d. Contractor is to report any evidence of additions, removals or modifications to the equipment on the register. The register template is detailed in Appendix 3. The Register is stored in the following location: \\ws7.lboro.ac.uk\fm-maintenanceservices\historic Files from X Drive\Service Records\Air Con\F Gas Register 4. The contractors will provide, or will be set, a schedule of works which details when Leak Testing is to be undertaken on all units containing F-gases. 5. Leak Tests are required with a frequency which meets the requirements as set out above, however the University currently services all units every 6 months.. 6. The University is in the process of developing a labelling system to ensure all units containing an F-gas are clearly labelled with the Asset Reference, type and volume of F-gas used, and the next service date. 7. Service records are to be provided for each unit detailing the leak test and confirming the outcome of the test. These are to be provided and stored electronically, and kept for a period of 5 years, in the same location detailed above using the following file Copyright Loughborough University Page 2 of 6
3 format. Building.Year.Month.Date (Eg. S Building pdf) 8. Maintenance records are to be provided when any works or recharging is undertaken. Where a leak is discovered the system must be fully repaired and pressure tested before being recharged. The equipment must be retested within one month to verify its integrity. These records are to be provided and stored electronically, and kept for a period of 5 years, in the same location detailed above using the following file format. Building.(M).Year.Month.Date (Eg. S Building.(M) pdf) These will then be stored in a separate folder alongside the servicing records. 9. Automatic leak detection is required for any units installed with a CO 2 e over 500 and as best practice on areas containing multiple systems (e.g. 3 units containing 50Kg in one room) or high risk installations. 10. Any equipment containing R22 / R408A will after the end of 2014 not be able to be re-gassed (see Appendix 4) and will need replacing. Schools and Service Departments: If you have equipment containing F-gases as detailed in this process please contact the University Environmental Manager to arrange for these to be added to the F-Gas register. If you have any queries with regards to this process do not hesitate to contact the Environmental Manager. A failure to comply with this process is a failure to comply with our duties under the legislation and could result in a statutory fine or unlimited fine if taken to Crown Court. Obligations for SF 6 The generic obligations regarding SF 6 systems are less onerous, but as part of best practice the University : Takes steps to prevent SF 6 leakage and repair leakages as soon as possible. Checks for leakages as part of routine maintenance Keeps certain records about known usage. Recovers SF 6 during servicing, maintenance and end of life. Uses appropriate qualified personnel to carry out installation, servicing and maintenance. Labels new equipment adjacent to service point and instruction manuals. Receives records detailing the maintenance of these systems detailing inspections, any SF 6 added or recovered Copyright Loughborough University Page 3 of 6
4 Appendix 1: F gas global warming potential 5-50 tonnes of CO 2e or more: at least every 12 months, or where a leakage detection system is installed, at least every 24 months. Hermetically sealed equipment that contains fluorinated greenhouse gases in quantities of less than 10 tonnes of CO 2e, will not be subject to leak checks, provided the equipment is labelled as hermetically sealed. to 5 tonnes CO 2 to 10 tonnes CO 2 to 50 tonnes CO tonnes of CO 2e at least every six months or, where a leakage detection system is installed, at least every 12 months; to 500 tonnes CO 2 SF6 22, HFC 23 14, HFC 508B 13, HFC 143a 4, HFC 507A 3, HFC 404A 3, HFC 428A 3, HFC 125 3, HFC 434A 3, HFC 227ea 3, HFC 422A 3, HFC 422D 2, HFC 417A 2, HFC 423A 2, HFC 438A 2, HFC 427A 2, HFC 407A 2, HFC 410A 2, HFC 442A 1, HFC 407F 1, HFC 437A 1, HFC 407C 1, HFC 426A 1, HFC 134a 1, HFC 245fa 1, HFC 365mfc HFC HFC 152a ,032 Highlighted lines are the gasses commonly used on the Loughborough University Campus. Copyright Loughborough University Page 4 of 6
5 Appendix 2: Certification and evaluation bodies: statutory refrigeration, air conditioning and heat pump equipment The certification and evaluation bodies for the purposes of Regulation (EC) 303/2008 on requirements and conditions for the certification of companies and personnel as regards stationary refrigeration, air conditioning and heat pump equipment containing certain fluorinated greenhouse gases, specifically the provision on personnel certificates are the: City and Guilds of London Institute; Level 2 - This level will suit you if you are working, or looking to work, as a refrigeration, air-conditioning and heat pump system engineer and have some relevant skills and knowledge. You need this qualification as a licence to practise with f-gases and ODSs. There are four pathways available: Award in F-Gas and ODS Regulations: Category I - Leak checking, recovery, installation, service, maintenance of equipment Award in F-Gas and ODS Regulations: Category II - Installation, service, maintenance of equipment with a charge of less than 3kg (6kg if hermetically sealed) and leakage checking Award in F-Gas and ODS Regulations: Category III - Recovery of refrigerant Award in F-Gas and ODS Regulations: Category IV - Leakage checking. Construction Industry Training Board. The certification bodies for Regulation (EC) 303/2008, specifically the provision on company certificates, are: Bureau Veritas UK Limited (Company Number: ); Quidos Limited (Company Number: ); Refcom Limited (Company Number: ). Refcom: Website: Tel: or [email protected] Bureau Veritas: Website: Tel:: or [email protected] Quidos: Website: Tel: or [email protected] For contractors working on HV Switchgear in respect of SF 6 the same rules exist pertaining to individual and company certification. Details of the training providers and the courses they run are available from DEFRA, the current guidance on this is available here: Copyright Loughborough University Page 5 of 6
6 Appendix 3: Building No. Building Name Location Manufacturer Model Serial No. Gas Quantity (Kg) Gas Type CO2e Maintenance Information Check Type Date Checked Sheet No. Date next check due Hazlegrave N1.09 Mitsubishi PEAD-RP125JAQ 1G02404 R410A 0 6 Monthly 04/11/2014 D18362 May-15 Hazlegrave N1.09 Mitsubishi PEAD-RP125JAQ 1G02380 R410A 0 6 Monthly 04/11/2014 D18362 May-15 Hazlegrave Outside - Roof Mitsubishi PUHZ-RP125YKA 15U R410A Monthly 31/10/2014 D18359 Apr-15 Hazlegrave N1.12 Mitsubishi PEAD-RP125JAQ 1G02403 R410A 0 6 Monthly 04/11/2014 D18362 May-15 Hazlegrave Outside - Roof Mitsubishi SUZ-KA25VA2 21P R410A Monthly 31/10/2014 D18359 Apr-15 Hazlegrave N1.11 Mitsubishi PEAD-RP50JAQ 1F01535 R410A 0 6 Monthly 04/11/2014 D18362 May-15 Hazlegrave Outside - Roof Mitsubishi PUHZ-RP250YKA 17U R410A Monthly 31/10/2014 D18359 Apr-15 Hazlegrave N1.16 (Main Computer Room) Denco Unit No.1 35 R407c Monthly 05/11/2014 D18362 May-15 Hazlegrave Outside - Roof Denco DCRA BP0537 R407c 0 6 Monthly 31/10/2014 D18359 Apr-15 Where a unit is part of a system containing F-Gas the quantity will be logged against the main device. Appendix 4: F-Gas usage: The following is a quick synopsis of F-Gas usage and phase out: The Montreal Protocol agreed that ozone-depleting substances (ODS) including CFC s (chlorofluorocarbons) and HCFC s (hydrochlorofluorocarbons) would be phased out globally. In Europe, CFC s (e.g. R12, R502) have been banned since 1994 and HCFC use (e.g. R22, R408A) has been banned in new equipment since From the end of 2009 the use of virgin HCFCs to service and maintain existing refrigeration and air-conditioning (RAC) equipment is banned in all EU Member States. Only reclaimed and recycled HCFCs may be used. From 1 st January 2015 it will be illegal to use any HCFCs to service RAC equipment. HFCs were developed in the 1990s to substitute substances such as CFCs and HCFCs. HFC s used on the University include R407C, R404A, R134A and R410A. In order for the University to comply with the above regs all R22 and R408A containing equipment will need to be replaced either proactively or as it breaks down as it will not be able to be re-gassed. Copyright Loughborough University Page 6 of 6
Guidance for Stationary Refrigeration & Air-Conditioning
Information Sheet RAC 3 Key Obligations Guidance for Stationary Refrigeration & Air-Conditioning This Information Sheet provides a description of the key obligations under the EC F gas and Ozone Regulations
Guidance for Stationary Refrigeration & Air- Conditioning
Department for Environment, Food and Rural Affairs Guidance for Stationary Refrigeration & Air- Conditioning Guidance: F Gas and Ozone Regulations Information Sheet RAC 5: Qualifications & Certificates
EU F-Gas Regulation Guidance Information Sheet 14: Refrigeration, Air-Conditioning and Heat Pump Contractors
Information Sheet 14: Refrigeration, Air-Conditioning and Heat Pump Contractors Target audience for this Information Sheet This Information Sheet is aimed at contractors that carry out installation, maintenance
EU F-Gas Regulation Guidance Information Sheet 5: Stationary Air-conditioning and Heat Pumps
Information Sheet 5: Stationary Air-conditioning and Heat Pumps Target audience for this Information Sheet This Information Sheet is aimed at organisations that are operators (usually the owner) of stationary
EU F-Gas Regulation Guidance Information Sheet 15: Fire Protection System Contractors
Information Sheet 15: Fire Protection System Contractors Target audience for this Information Sheet This Information Sheet is aimed at contractors that carry out installation, maintenance and decommissioning
EU F-Gas Regulation Guidance Information Sheet 21: Training and Certification Requirements for Refrigeration, Air-Conditioning and Heat Pumps
Information Sheet 21: Training and Certification Requirements for Refrigeration, Air-Conditioning and Heat Pumps Target audience for this Information Sheet This Information Sheet is aimed at individuals
The EC Ozone Regulation. Legislative Update and Strategies for HCFC Phase-out
Information Sheet RAC 8 R22 Phase-out The EC Ozone Regulation Legislative Update and Strategies for HCFC Phase-out 1. Background to HCFC Phase Out The EC Ozone Regulation (EC/2037/2000) provides the legislative
Guidance for Mobile Air Conditioning (MAC) Sectors. Guidance: F Gas and Ozone Regulations Information Sheet MAC 3: Key Obligations
Department for Environment, Food and Rural Affairs Guidance for Mobile Air Conditioning (MAC) Sectors Guidance: F Gas and Ozone Regulations Information Sheet MAC 3: Key Obligations April 2012 Contents
The phase out of R22. Phase out of HCFCs
The phase out of R22 The Montreal Protocol on Substances that Deplete the Ozone Layer is widely regarded as the world s most successful environment protection agreement. It is the only treaty with universal
Guidance for Stationary Refrigeration & Air- Conditioning
Department for Environment, Food and Rural Affairs Guidance for Stationary Refrigeration & Air- Conditioning The EU Ozone Regulation: Legislative update and strategies for HCFC Phase-out Information Sheet
Refrigeration, Air-conditioning and Heat Pump Sector. The Environmental Protection Agency
The COMPLYING WITH REGULATIONS CONTROLLING FLUORINATED GREENHOUSE GASES AND OZONE DEPLETING SUBSTANCES A GUIDANCE NOTE FOR CONTRACTORS IN THE Refrigeration, Air-conditioning and Heat Pump Sector The (EPA)
EU f-gas regulation EN 517/2014.
F-gas regulation EU f-gas regulation EN 517/2014. Helping you meet your environmental obligations. 02 EU f-gas regulation EU f-gas regulation. Reducing your environmental impact. The updated f-gas regulation
THE F-GAS REGULATION AND ITS IMPLICATIONS IN FIRE SUPPRESSION APPLICATIONS
THE F-GAS REGULATION AND ITS IMPLICATIONS IN FIRE SUPPRESSION APPLICATIONS Mark L. Robin, Ph.D. DuPont Fluoroproducts P.O. Box 80711, Wilmington, DE 19880-0711 Tel: 302-999-5002; Fax 302-999-2093 [email protected]
Guide to good leak testing
Page 0 Guide to good leak testing The Institute of Refrigeration, working with the Carbon Trust, brings you REAL Zero Refrigerant Emission and Loss Zero. The aim of this project is in the title zero refrigerant
HFCS, REFRIGERATION AND AIR-CONDITIONING: MINIMISING CLIMATE IMPACT, MAXIMISING SAFETY
HFCS, REFRIGERATION AND AIR-CONDITIONING: MINIMISING CLIMATE IMPACT, MAXIMISING SAFETY HFCS, REFRIGERATION AND AIR-CONDITIONING: MINIMISING CLIMATE IMPACT, MAXIMISING SAFETY The impact of refrigeration
EU F-Gas Regulation Guidance Information Sheet 17: F-Gas Producers, Importers and Exporters
Information Sheet 17: F-Gas Producers, Importers and Exporters Target audience for this Information Sheet This information sheet is aimed at organisations that are producers, importers and exporters of
Guide to updated EU f-gas regulation (517/2014).
Guide to updated EU f-gas regulation (517/2014). Date July 2014 02 Contents Contents. 03 Introduction 04 F-gas regulation update: key changes 05 Regulation structure 06 Product and equipment bans 09 Service
Calculating HFC and PFC Emissions from the Manufacturing, Installation, Operation and Disposal of Refrigeration & Airconditioning
Calculating HFC and PFC Emissions from the Manufacturing, Installation, Operation and Disposal of Refrigeration & Airconditioning Equipment (Version 1.0) Guide to calculation worksheets (January 2005)
Certification based on F-gas regulation the Czech Republic experience
Certification based on F-gas regulation the Czech Republic experience Jana Borská [email protected] Ministry of the Environment of the Czech Republic Department of Air Protection 1. Situation before
New EU Legislation on F- Gases
New EU Legislation on F- Gases motivation, objectives, impacts, innovation Arno Kaschl European Commission DG Climate Action Tel Aviv 31 March 2014 Climate Action Relevance of fluorinated gases (F-gases)
Information for technicians and users of refrigeration, air conditioning and heat pump equipment containing fluorinated greenhouse gases
Information for technicians and users of refrigeration, air conditioning and heat pump equipment containing fluorinated greenhouse gases (January 2015) Summary Regulation (EU) No 517/2014 on fluorinated
Carbon Footprint Report 2011 2012
Carbon Footprint Report 2011 2012 Electricity North West Carbon Footprint Report 2011-2012 1. Introduction This report details the carbon consumption arising from the undertakings of Electricity North
EU F-Gas Regulation Guidance Information Sheet 22: Training and Certification Requirements for Mobile Air-Conditioning Systems
Information Sheet 22: Training and Certification Requirements for Mobile Air-Conditioning Systems Target audience for this Information Sheet This Information Sheet is aimed at individuals and organisations
AREA F-Gas GUIDE A practical guide on the application of the new F-Gas Regulation to refrigeration, air conditioning & heat pump contractors
The European voice of refrigeration, air conditioning and heat pumps contractors AREA F-Gas GUIDE A practical guide on the application of the new F-Gas Regulation to refrigeration, air conditioning & heat
A guide to synthetic greenhouse gas activities in the New Zealand Emissions Trading Scheme
A guide to synthetic greenhouse gas activities in the New Zealand Emissions Trading Scheme This report may be cited as: Ministry for the Environment. 2010. A guide to synthetic greenhouse gas activities
R-32. The next generation refrigerant for air conditioners and heat pumps. Superior energy efficiency and low GWP
R-32 The next generation refrigerant for air conditioners and heat pumps Superior energy efficiency and low GWP HFC phase-down and the introduction of R32 The European phase-down of HFCs, which will see
Planning for the ban on R22 in building air conditioning
- ACHPI 32 Planning for the ban on R22 in building air conditioning Those responsible for cooling and heating commercial properties are under increased pressure to improve energy efficiency and negotiate
Guidance for Mobile Air Conditioning (MAC) Sectors. Guidance: F Gas and Ozone Regulations Information Sheet MAC 5: Qualifications & Certificates
Department for Environment, Food and Rural Affairs Guidance for Mobile Air Conditioning (MAC) Sectors Guidance: F Gas and Ozone Regulations Information Sheet MAC 5: Qualifications & Certificates April
Engineers Newsletter. HVAC Refrigerants: A Balanced Approach. providing insights for today s hvac system designer. volume 40 2. Refrigerant History
providing insights for today s hvac system designer Engineers Newsletter volume 40 2 HVAC Refrigerants: A Balanced Approach One of the constant themes throughout the history of the HVAC industry is the
DEVELOPMENT OF THE GHG REFRIGERATION
DEVELOPMENT OF THE GHG REFRIGERATION AND AIR CONDITIONING MODEL FINAL REPORT December 2011 Prepared for the Department of Energy and Climate Change By ICF International Table of Contents Executive Summary...
Electricity North West Carbon Footprint Report 2013-2014
Electricity North West Carbon Footprint Report 2013-2014 1. Introduction This report details the carbon consumption arising from the undertakings of Electricity North West Limited for the financial year
R-32. The next generation refrigerant for air conditioners and heat pumps
R-32 The next generation refrigerant for air conditioners and heat pumps Daikin is the first company in the world to launch heat pumps and air conditioners charged with R-32. This refrigerant has several
Guidance for Mobile Air Conditioning (MAC) Sectors
Information Sheet MAC 5 Quals. & Certs. Guidance for Mobile Air Conditioning (MAC) Sectors This Information Sheet provides guidance on the interim and full minimum requirements for training and certification
USC CFC Leak Repair and Recordkeeping Procedures
USC CFC Leak Repair and Recordkeeping Procedures I. Introduction Chlorofluorocarbons (CFCs) released into the atmosphere can damage the ozone layer that protects the earth from the penetration of harmful
Submission by Norway to the ADP
Submission by Norway to the ADP Norway s Intended Nationally Determined Contribution 1. Introduction Norway is fully committed to the UNFCCC negotiation process towards adopting at COP21 a protocol, another
Carbon Footprint Calculator for Royal Society of Arts
Carbon Footprint Calculator for Royal Society of Arts This Carbon Calculator has been produced for Royal Society of Arts to enable the company to better understand its environmental performance in terms
Certification in the safe and efficient use of alternative refrigerants
Certification in the safe and efficient use of alternative refrigerants Dubai, 29th Oct 2014 Marco Buoni VicePresident, AREA Air Conditioning & Refrigeration European contractors Association (www.area-eur.be)
Syston Dry Cleaners and Laundry Schedule 1 CHARNWOOD BOROUGH COUNCIL POLLUTION PREVENTION AND CONTROL ACT 1999
CHARNWOOD BOROUGH COUNCIL POLLUTION PREVENTION AND CONTROL ACT 1999 ENVIRONMENTAL PERMITTING (ENGLAND AND WALES) REGULATIONS 2010 (As Amended) PERMIT REF. NO. 123 Charnwood Borough Council hereby permits,
Refrigerant Compliance Policy
Refrigerant Compliance Policy Updated: July 12, 2012 TABLE OF CONTENTS I. SCOPE... 1 A. Relevant Subparts of 40 CFR Part 82... 1 B. Technician Training and Certification... 1 C. Recycling and Recovery
Food Safety Act 1990. (as amended) Code of Practice No. 7: Sampling for Analysis or Examination (Revised October 2000)
Food Safety Act 1990 (as amended) Code of Practice No. 7: Sampling for Analysis or Examination (Revised October 2000) Further copies may be obtained from: Local Authority Enforcement (Support) Division
HCFC phase-out has started.
HCFC phase-out has started. 02 HCFC phase-out has started. HCFC phase-out has started. Are you prepared? Global phase-out of HCFCs is already underway. This will impact the availability and pricing of
Environmental and Safety Impacts of HFC Emission Reduction Options for Air Conditioning and Heat Pump Systems
Environmental and Safety Impacts of HFC Emission Reduction Options for Air Conditioning and Heat Pump Systems William M. Corcoran, George Rusch, Mark W. Spatz, and Tim Vink AlliedSignal, Inc. ABSTRACT
THE REPLACEMENT OF R-22
ENGLISH TRANSLATION OF ARTICLE IN FRIO-CALOR AIRE ACONDICIONDAO BY GAS-SERVEI, S.A JUNE 2010 THE REPLACEMENT OF R-22 Courtesy of D. Lluis Giralt Lopez (Chemical Engineering Industrial) Gas Technical Department
Part A: Fluid properties
UNEP Ozone Secretariat UNEP Ozone Secretariat Background Workshop Material on HFC for management: HFC Workshop, technical 2015 issues Bangkok, 20 and 21 April 2015 FACT SHEET 15 Glossary of terms and technical
Industry insight. Refrigerant gases: an industry in transition.
Industry insight. Refrigerant gases: an industry in transition. Author Jon Black, Global Head of Chemicals and Refrigerants Date June 2012 First Published by CryoGas International, July 2012 Refrigerant
History of Chlorofluorocarbons
History of Chlorofluorocarbons 1928 : Chlorofluorocarbons () were invented. were developed as ideal gases used as refrigerants for refrigerators. Because of their special characteristics, inflammability
7. COST AND EMISSION REDUCTION ANALYSIS OF HFC EMISSIONS FROM REFRIGERATION AND AIR-CONDITIONING IN THE UNITED STATES... 7-1 7.1 INTRODUCTION...
7. COST AND EMISSION REDUCTION ANALYSIS OF HFC EMISSIONS FROM REFRIGERATION AND AIR-CONDITIONING IN THE UNITED STATES... 7-1 7.1 INTRODUCTION... 7-1 7.2 HISTORICAL AND BASELINE HFC EMISSION ESTIMATES...
How To Know If Cfc 12 Is Still Needed
Mobile Air Conditioning James A. Baker Delphi Corporation 19 th OORG Meeting March 2002 Presentation Topics Estimating CFC-12 Needs for Developing Countries The Effectiveness of Refrigerant Recycling Challenges
CLIMATE CHANGE POLICY FRAMEWORK FOR REFRIGERATION AND AIR CONDITIONING SECTOR
European Partnership CLIMATE CHANGE POLICY FRAMEWORK FOR REFRIGERATION AND AIR CONDITIONING SECTOR A proposal by the European Partnership (EPEE) for action in the European Union I. INTRODUCTION Set out
TECHNICAL ANNEX. Alternatives to HCFCs/HFCs in unitary air conditioning equipment at high ambient temperatures. November 2014
TECHNICAL ANNEX Alternatives to HCFCs/HFCs in unitary air conditioning equipment at high ambient temperatures November 2014 Authors: Bastian Zeiger, Barbara Gschrey, Winfried Schwarz Öko-Recherche, Frankfurt/Main,
ADVANCING FLAMMABLE REFRIGERANT ADOPTION IN NORTH AMERICA
NEW SCIENCE SUSTAINABLE ENERGY ARTICLE ADVANCING FLAMMABLE REFRIGERANT ADOPTION IN NORTH AMERICA SUMMER 2013 UL.COM/NEWSCIENCE NEW SCIENCE SUSTAINABLE ENERGY OVERVIEW Rising costs, energy efficiency and
APPENDIX X INTRODUCTION. Purpose
APPENDIX X CLEAN AIR ACT CIVIL PENALTY POLICY FOR VIOLATIONS OF 40 C.F.R. PART 82, SUBPART F: MAINTENANCE, SERVICE, REPAIR, AND DISPOSAL OF APPLIANCES CONTAINING REFRIGERANT June 1, 1994 INTRODUCTION Purpose
COMPETENCY ANALYSIS PROFILE Refrigeration and Air Conditioning Systems Mechanic - Branch 1 313A
COMPETENCY ANALYSIS PROFILE Refrigeration and Air Conditioning Systems Mechanic - Branch 1 313A (All unshaded skill sets must be demonstrated/completed) PROTECT SELF AND OTHERS Identify, interpret, and
Environmental Guideline for Ozone Depleting Substances (ODS s) and Halocarbon Alternatives
Environmental Guideline for Ozone Depleting Substances (ODS s) and Halocarbon Alternatives 1 Introduction 1.1 Background 1.2 Guideline Purpose 1.3 Definitions 2 Roles and Responsibilities 2.1 Department
Building Service & Maintenance
Building Service & Maintenance the management process procedure flow chart introduction Jupiter Facilities Management Ltd is the one stop contact for Facilities Managers looking to outsource the management
Mechanisms for assessment, classification and labeling of chemicals, including initiatives for harmonized classification and labeling of chemicals
CHEMICALS Risk assessment of chemicals including Mechanisms for assessment, classification and labeling of chemicals, including initiatives for harmonized classification and labeling of chemicals The Global
Greenhouse Gas Reporting Criteria
Greenhouse Gas Reporting Criteria Version 2.0 Approved by AMP Environment Leadership Team October 2014 AMP Greenhouse Gas Reporting Criteria 2014 v2.0 (final) - 1-2/04/2015 Document Change Control The
Prepared by: ICF International. Prepared for: The European Commission. May 2010. Final Report
Identifying and Assessing Policy Options for Promoting the Recovery and Destruction of Ozone Depleting Substances (ODS) and Certain Fluorinated Greenhouse Gases (F-Gases) Banked In Products and Equipment
RS-52 (R428A) RS-52: PHYSICAL PROPERTIES RS-52 R502 Molecular weight 107.5 111.6 Temperature glide o C 0.5 0.2 Boiling point (1 atm)
RS-52 (R428A) COMPOSITION % HFC 125 77.5 HFC 143a 20.0 R600a 1.9 R290 0.6 HCFC replacement Temperature glide R22, 502 & interim blends Approximately 0.8 o C Drop-in or long term Both Lubricant MO/AB/POE
Electrical Safety Policy
Electrical Safety Policy Version Number: V2 Name of originator/author: Director of Estates and Facilities Name of responsible committee: Estates and Facilities Committee Name of executive lead: Chief Operating
Guide to Chemicals (Asbestos Articles) Regulations 2011. S.I. No. 248 of 2011
Guide to Chemicals (Asbestos Articles) Regulations 2011 S.I. No. 248 of 2011 Version 1 Guide to Chemicals (Asbestos Articles) Regulations 2011 Page 1 of 18 Table of Contents Introduction... 3 Background...
Extracts from the FINAL REPORT. Denis CLODIC, Stephanie BARRAULT, Sabine SABA. tonnes. CO2 Eq. Emissions. CFC HCFC HFC Others 1 200
CENTRE ENERGETIQUE ET PROCEDES Global inventories of the worldwide fleets of refrigerating and airconditioning equipment in order to determine refrigerant emissions. The to 26 updating. Mise à jour des
Fujitsu General New Zealand Ltd
Fujitsu General New Zealand Ltd Ozone layer protection Global warming prevention HCFC (R22) Ozone depletion potential : 0.055 Global warming potential : 1,810 1987 Montreal Protocol adoption Complete abolishment
AHRI Project 8018 Final Report
AHRI Project 8018 Final Report Review of Refrigerant Management Programs Prepared for: Navigant Consulting, Inc. 77 South Bedford St. Suite 400 Burlington, MA 01803 781.270.0101 navigant.com Reference
Lawful Development Certificates
Lawful Development Certificates A User s Guide www.communities.gov.uk community, opportunity, prosperity Lawful Development Certificates A User s Guide December 2007 Communities and Local Government:
Calculating Greenhouse Gas Emissions
GIIRS Emerging Market Assessment Resource Guide: What s in this Guide? I. Definition: What Are Greenhouse Gas (GHG) Emissions? II. Why Calculate GHGs? III. How to Calculate Company-wide GHGs IV. Outsourcing
Scope 1 describes direct greenhouse gas emissions from sources that are owned by or under the direct control of the reporting entity;
9 Greenhouse Gas Assessment 9.1 Introduction This chapter presents an assessment of the potential greenhouse gas emissions associated with the Simandou Railway and evaluates the significance of these in
Improving the energy efficiency of our buildings
Improving the energy efficiency of our buildings A guide to air conditioning inspections for buildings December, 2012 Department for Communities and Local Government Crown copyright, 2012 Copyright in
(WHO Technical Report Series, No. 961, 2011), Annex 9. Temperature and humidity monitoring systems for fixed storage areas 107
Annex 5 Technical supplements to Model guidance for the storage and transport of timeand temperature-sensitive pharmaceutical products (WHO Technical Report Series, No. 961, 2011), Annex 9 1. The technical
JFK High School, Environmental Science, Mr. Kent Name : Period: Date: 3. Why is ozone important to us and other organisms?
JFK High School, Environmental Science, Mr. Kent Name : Period: Date: AIM: How have people been destroying the ozone layer? HW: 39e 1. What chemical is ozone? 2. How does ozone form in the atmosphere?
Air conditioning is AIR CONDITIONING GUIDE
ool Air conditioning is AIR CONDITIONING GUIDE ool Contents Making the right decisions for the right reasons Keep a cool head 2 Buying 3 Be a cool customer Installation 5 For a licensed technician, installation
Hot water supply, distribution and use
Guidance Leaflet Reducing use Hot supply, distribution and use All businesses use hot in some way, whether for domestic use, in the manufacturing process or for ancillary activities. As there are considerable
MANAGEMENT AND REDUCTION OF GREENHOUSE GASES BILL. No. 95
1 BILL No. 95 An Act respecting the Management and Reduction of Greenhouse Gases and Adaptation to Climate Change TABLE OF CONTENTS 1 Short title 2 Interpretation 3 Crown bound PART I Preliminary Matters
Technical Note: Comparing R407C and R410A as Alternatives for R22. A Technical Note from the Experts in Business-Critical Continuity
Technical Note: Comparing R407C and R410A as Alternatives for R22 A Technical Note from the Experts in Business-Critical Continuity Purpose The purpose of this document is to provide a brief overview of
Environmental perspective in intelligent products and processes
Environmental perspective in intelligent products and processes Climate changes and refrigeration technology Ole M. Daugbjerg, Corporate Vice President Communications & Reputation Management Danfoss Refrigeration
REFERENCE NUMBER : PPC/54. POLLUTION PREVENTION AND CONTROL ACT 1999 POLLUTION PREVENTION & CONTROL (ENGLAND AND WALES) REGULATIONS 2000(as amended)
LOCAL AUTHORITY POLLUTION PREENTION AND CONTROL PERMIT Yeovil Motor Company REFERENCE NUMBER : PPC/54 POLLUTION PREENTION AND CONTROL ACT 1999 POLLUTION PREENTION & CONTROL (ENGLAND AND WALES) REGULATIONS
How to Prepare a Good Proposal?
How to Prepare a Good Proposal? Danmark, 11. juni 2015 Bent Jepsen, NEEMO-ELLE Facts of LIFE 1) There is significant competition for LIFE funds 2 Submission Trend 2007 2014 (Total) CLIMA proposals are
SSE s criteria used for GHG emissions reporting
SSE s criteria used for reporting 1 Introduction This document details the annual greenhouse gas emissions reporting approach used by SSE Plc to report the tonnes of carbon dioxide equivalent (CO2e) during
Inspect and Test FPAS Units of Competencies descriptions
Inspect and Test FPAS Units of Competencies descriptions FPAS incorporates the following units of competency across ten (10) categories of inspect and test activities. CPPCMN2002A Participate in workplace
Guidance for Electrical Contractors on Emergency Lighting Legislation
Guidance for Electrical Contractors on Emergency Lighting Legislation Issued in the interests of safety by in conjunction with the Industry Committee for Emergency Lighting ECA / ICEL Guidance For Electrical
P08 Köldmedier med låg växthuseffekter
P08 Köldmedier med låg växthuseffekter Pavel Makhnatch Tranås, 17-18 May Reference: IPCC, 2013 3 4 5 Growth of climate change commitments from HFC banks and emissions Reference: Velders et al. 2014 6
Refrigeration and Air Conditioning with Reduced Environmental Impact
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2000 Refrigeration and Air Conditioning with Reduced Environmental Impact D.
GREEN PROCUREMENT GUIDELINES
EKSS-013 GREEN PROCUREMENT GUIDELINES (FOR SUPPLIERS) Ver. 5 August. 2010 NEC Display Solutions, Ltd. Table of Contents 1. Introduction 3 2. Scope of Application 3 3. Terms and Definitions 3 4. Essential
Refrigerant Changeover Guidelines R-22 to R-407C. Leading the Industry with Environmentally Responsible Refrigerant Solutions
Refrigerant Changeover Guidelines R-22 to R-407C Leading the Industry with Environmentally Responsible Refrigerant Solutions Emerson Climate CFC Technologies, Inc. does not advocate the HCFC wholesale
OH&S MANAGEMENT SYSTEM CHECKLIST - AS 4801:2001 (STATUS A = Acceptable; N = Not Acceptable; N/A = Not Applicable)
OH&S MANAGEMENT SYSTEM CHECKLIST - AS 4801:2001 (STATUS A = Acceptable; N = Not Acceptable; N/A = Not Applicable) 4.1 General Requirements 4.2 OHS policy Has the organisation an established and maintained
equivalents (CO2e) emitted by a person or business. Usually expressed in the number of CO2e tons emitted per unit of time (per year) or
Greenhouse Gas Reporting and Carbon Footprints Douglas A. McWilliams Squire, Sanders & Dempsey L.L.P. January ar 11, 2010 What is a carbon footprint? An estimate of the amount of carbon dioxide equivalents
Repairs a guide for landlords and tenants. housing
Repairs a guide for landlords and tenants housing This booklet does not give an authoritative interpretation of the law; only the courts can do that. Nor does it cover every case. If you are in doubt about