EVC40 EMERGENCY VOICE COMMUNICATION SYSTEM



Similar documents
FIREDEX Conventional Fire Panels

LIEBERT VNSA Installation Sheet

HM-W536 Install Guide

PS 29M DUAL CHANNEL BELTPACK IN METAL CASE

LOXONE 12 Channel Amplifier

Emergency Voice Communication Systems EVCS Network 8 Data Sheet

How To Power A Power Control On An Ip40 (Ipl) With A Power Supply (Iplug) With An Ip20 Controller (Iphones) With Power Control (Power Control) With No Antenna) With The Ip20 (Power)

Drayton Digistat +2RF/+3RF

INTRODUCTION. The data provided is for The Standard Products and any variation will be dealt with at the end of this manual.

BARDIC. 4 & 8 Zone Fire Panels Zircon range. Data, installation, operation and maintenance. by Honeywell

CX Zoner Installation & User Guide

3. MOUNTING THE FIRE ALARM PANEL PLANNING CABLE ENTRY 3.2 FIXING THE BACKBOX TO THE WALL

Alarm over IP. IRIS Touch Home Installation Manual. Version 1.0 ENGLISH. Now certified and compliant with EN50131, EN50136 Security Grade 4 ATS6

VEGA Analogue Addressable Control Panels

Power Socket (2 Gang)

TS510 & TS500. Installation & User Guide. Compatible Equipment

2013 Wireless Video Intercom INSTALLATION GUIDE

OPERATING INSTRUCTIONS

162 CB CABLE TRACER. Filter Probe & Tone Generator INSTRUCTION MANUAL

INTELLIGENT FIRE ALARM CONTROL PANELS. MR-2100/MR-2200 Intelligent Fire Alarm Control Panels MEA. Features. Description

Operating Instructions

Stand Alone POTS Fiber Optic System. P31372 Station (Subscriber) Unit P31379 Remote (Exchanger) Unit. Description & Installation

VoCALL - CFVCM/CFVCWM & CFVCX8. Fire Telephone & Disabled Refuge Network System. User Manual & Log Book

ST Series POWER SUPPLIES USER INSTRUCTIONS

PROXIMITY CARD READERS C-10, C-20, C60, C70

GUARDIAN REFUGE & EMERGENCY VOICE COMMUNICATION SYSTEMS

Communication A BRITISH MANUFACTURER. Features:

Advantium 2 Plus Alarm

INSTALLATION GUIDE. Card Reader & Controller with KIM Swipe Reader for Solitaire 850 / 950 / 850L Learnlok PK2930

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & Instructions For Installation, Operation & Maintenance

1. Connect the charger to the battery. 2. Connect the charger to the wall socket. 3. Press the MODE-button to select charging program.

Analogue addressable devices

MANUAL. * Supply plugs may differ to suit your wall socket. EN 3. Continue to press the MODE-button to combine charging program with charging options.

Instruction Manual. 2in1 LAN Tester & Multimeter. Model: LA-1011

Sound Engineering for 60 Years EmerCall Disabled Refuge and Fire Telephone System

Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points

FIRE ALARM SYSTEM TECHNICAL SPECIFICATIONS Page 1 of 10

HMI display Installation Guide

T0118 T2118 T3118. Instruction Manual

Loc-1Tx/Loc-5Tx/Loc-10Tx Data Sheet V3.3

Linear Luminaire for Fluorescent Lamps Series EXLUX 6001

Installation, operation and maintenance manual TX 35A

3x cinch/s-video socket Order no.: xx. USB/3.5 mm audio socket Order no.: xx. VGA socket Order no.: xx

CONTENTS. GST102A/104A/108A/116A Conventional Fire Alarm Control Panel Installation and Operation Manual

AC-115 Compact Networked Single Door Controller. Installation and User Manual

TrueAlarm Fire Alarm Systems

VLT Series 3500 Adjustable Frequency Drive Instruction Manual

ADS8 IP54 Direct-On-Line Starter Technical Focus. Replaces ADS7 Rated up to 9kW

33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application

Disabled Toilet Alarm. Contractor Pack. Installation & Operating Instructions

MANUAL EN 3 SUPPLY PLUG* MAINS CABLE CTEK COMFORT CONNECT ABSORPTION, READY TO USE ANALYSE FLOAT, FULLY CHARGED PULSE, MAINTENANCE CHARGING

FN2001-A1 Network module (SAFEDLINK) Mounting Installation

SECTION DETECTION AND ALARM

Daker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF

Solar Home System. User Manual. AEH-SHS01-10W2L Solar Home System 2 Lamps

Installation Handbook. Interactive Fire Alarm System Release 3. Repeater Panel BU-320 / Information Panel BV-320

SP4-LOC SAFEPATH4 REMOTE MICROPHONE AND LOCAL OPERATOR CONSOLE

BeoLab 1. User s guide

MICROSENS. Central 48 V DC Power Supplies for PoE-Components. Description. Features

LINE POWERED ADA TELEPHONE USER S MANUAL Use With Part Numbers , , , , , and

INSTRUCTIONS FOR USE Pro-Ject Tube Box S

DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS

UT202A Operating Manual. Contents

PCS300 Universal IP Reporting Module V1.0

TMS TANK MANAGEMENT SYSTEM

ESP 120 M1, ESP 208 M1, ESP 240 M1, ESP 415 M1, ESP 277 M1, ESP 480 M1 and M1R variants. Installation instructions ESP M1/M1R mains protectors

Emergency voice communications Product Name

HP UPS R1500 Generation 3

TS93 EMR T/PT/TDE. Surface applied door closer

INSTALLATION AND OPERATING INSTRUCTIONS For Model GL1 Gate Locks

T7560A,B,C Digital Wall Module

How To Use A Power Supply Unit (Upu)

InnoMedia ESBC B. Quick Install Guide. 1

INSTRUCTIONS FOR URMET DOMUS DEVICE INTERCHANGEABILITY

Installation instructions, accessories - Handsfree for cellular phone, system B, entry level

FLUORESCENT UV- RING LIGHT OPERATING INSTRUCTION

CA-6050 Solar Power Unit. User Guide. Designed to work with the Norsonic range of sound level meters to provide a DC supply in remote locations.

* DISCLAIMER: Contents. How to Use This Guide: COMMERCIAL INSTALL GUIDE 2

Handheld portable appliance testers

Remote Monitoring and REC 501 Control Unit Product Guide

Daily use. Never use alcohol or other solvents to clean any part of the loudspeakers!

ABB Stotz-Kontakt GmbH ABB safe&smart Project planning of security systems

D7050/D7050TH. Installation Instructions. Multiplex Photoelectric Smoke Detectors

Product Specification instalert Rapid Messenger Variable Message Sign

Masterseal Plus TM. ingress protected wiring devices. technical hotline +44 (0) IP66. Improved catch.

Wolflite Safety Handlamp H-251E

Detector transparent with Color Inserts. FAA 500 TR P Trim Ring transparent with Color Inserts. FCA 500 / FCA 500 E Detector Bases

Mobile Data Power Model: MDP-25

OEM Manual MODEL 2350 ELECTRONIC DUAL CYLINDER SCALE

ADA COMPLIANT BOX STYLE TELEPHONE INSTALLATION, PROGRAMMING AND OPERATING INSTRUCTIONS FOR MODEL PBX

MXS 3. MANUAL FULLY CHARGED PULSE, MAINTENANCE CHARGING EN 3 SUPPLY PLUG* MAINS CABLE CTEK COMFORT CONNECT CHARGE CABLE ERROR LAMP MODE- BUTTON

(68.52) X. June 2000 Supercedes February xenex CONVENTIONAL FIRE DETECTION & ALARM SYSTEM. we business differently

Rack mounted telephone- and leased line modem for industrial applications

LS1024B / LS2024B/ LS3024B. Solar Charge Controller USER MANUAL

CONNECTOR AMPLIFIER FOR PROPORTIONAL VALVES (4-20 ma Input Version)

Repeaters and Mimics Data Sheet

PROFESSIONAL HOME ALARM SYSTEM. Important! Please read these instructions carefully.

WIRELESS ALARM KIT INSTRUCTION MANUAL COMPLETE ALARM SYSTEM FOR HOME OR BUSINESS. Model Number: IT214054

MagIC Installation Manual. Point of Sales Terminals TD06014B

DBS720 / FDS221-R / FDS221-W Sounder base, Alarm sounders

Transcription:

EVC40 EMERGENCY VOICE COMMUNICATION SYSTEM INSTALLATION MANUAL Protec Fire Detection PLC, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT. Telephone: +44 (0) 1282 717171 Fax: +44 (0) 1282 717273 Web: www.protec.co.uk Email: sales@protec.co.uk

Document Revision Details Issue Modification Detail Author Date 1 Document Creation JLH 10/10/10 2 Added reference to BS5839-9:2011 clause 14c on cabling JLH 10/06/11 N93-347-81 Issue 2 Page 2 of 14 Copyright Protec Fire Detection PLC 2010

Table of Contents 1.0 INTRODUCTION... 4 1.1 The EVC40 System... 4 2.0 CABLING... 5 2.1 Cabling requirements summary... 6 3.0 INSTALLATION PROCEDURE... 7 3.1 Panels... 7 3.2 Outstations... 8 4.0 CABLE TEST... 9 5.0 CONNECTION...10 5.1 Panels...10 5.2 Outstation and Control Loops...10 5.3 Outstations...11 5.4 Power Supply Cabling (Remote Charger Only)...12 6.0 COMMISSIONING REQUIREMENTS...13 7.0 EVC40 SPECIFICATION...14 N93-347-81 Issue 2 Page 3 of 14 Copyright Protec Fire Detection PLC 2010

1.0 Introduction This document describes the methods to be employed when installing and connecting equipment associated with the PROTEC EVC40 Disabled Refuge / Fire Telephone System. 1.1 The EVC40 System The EVC40 is a fire telephone and disabled refuge emergency voice communication system fully compliant to BS5839 Part 9. This has been designed to cater for the existing fire telephone market, stadium steward s telephone and also offers a solution to the requirements of the Disability Discrimination Act. It features a bespoke two-wire audio and data bus to minimises the wiring requirements, whilst maintaining full addressability and monitoring. Each outstation is setup using its address switch and the panel communicates with each device by this Address Number. As well as audio the outstations communicate digital data so the panel is able to control and track any changes at the device and initiate all necessary actions. The system is capable of driving up to 40 outstations per panel, and 4 panels can be networked together to give a total of 160 outstations. N93-347-81 Issue 2 Page 4 of 14 Copyright Protec Fire Detection PLC 2010

2.0 Cabling All cable (both outstation loop and the control loop) must be 2 core, screened, soft skinned, enhanced grade fire rated cable except for the certain situations were standard fire resisting cable may be used. (Refer to BS5839-9:2011 clause 14c). All loops must be wired in a separate pair. As with any audio system it is of paramount importance that strict earthing protocols are followed to avoid producing earth loops. An earth loop occurs when the ground potential between two pieces of equipment is not identical. Audio-frequency earth loop problems are typically in the millivolt range, so there does not have to be much interference to cause problems in audio systems. Earth loops are the most common cause of AC line frequency hum in sound systems and make the system sensitive to interference from mains wiring which can lead to erratic operation of the equipment or even cause damage. To minimise this the cable screen must be continuous over its full length and not earthed at any point over its run. Soft skinned cable is recommended, the use of any hard skinned cable is to be avoided as this is difficult to keep separate from earth. Outstation loops up to 2km maximum use 2.5mm cable. 1km max use 1.5mm² cable. Note that if the run is greater than 1km the whole rum must be in 2.5mm² cable. Up to 4 panels can be connected together. Up to 500m is allowed between panels and panel to panel connection is wired in 1.5mm² cable. All external wiring associated with the system must conform to the current I.E.E Regulations and cabling must conform to the relevant BS specifications. ECA recommended Cable Separation for Electromagnetic Compatibility in Buildings, must be followed. All cabling must be fully phased. Identify and mark ends of cables ready for the commissioning stage. Although no connections are to be made to the panel until the commissioning stage it is important that cables are left long enough to connect directly to the relevant terminals. To ensure that cable tails are left with sufficient length all cable tails must be a minimum of 500mm. See Section 5 for terminal locations. N93-347-81 Issue 2 Page 5 of 14 Copyright Protec Fire Detection PLC 2010

2.1 Cabling requirements summary 1. All loops must be wired in a separate 2 core, screened, soft skinned, enhanced grade fire rated cable except for certain situations were standard fire resisting cable may be used. (BS5839-9:2011 clause 14c). 2. The cable screen must be continuous over its full length and must not earthed at any point along its entire run. Outstation Loops Cable Up to 2km use 2.5mm² cable. Less than 1km total 1.5mm² use cable. Control Loops Maximum 500m between panels wired in 1.5mm² cable The installer must mark up on the as fitted drawings the panel number (if more than one) and address of each device. N93-347-81 Issue 2 Page 6 of 14 Copyright Protec Fire Detection PLC 2010

3.0 Installation Procedure 3.1 Panels The panel is supplied complete and fully assembled in one box. The box also contains an installation template showing mounting hole & cable entry positions with spirit level and plumb bob references. 1) Unpacking Remove the installation template from the packaging - leaving the panel in the box for protection. 2) Preparing The Mounting Position Use the installation template together with a spirit level etc. to mark, drill and plug the 3 mounting holes in the desired position. 3) Removal Of The Door Remove the panel from the packaging. Use the key supplied to unlock the outer door, remove the door by extracting the hinge pins and place the door back in the box for protection. 4) Removal Of The Inner Door Unscrew the 3 fixings on the metal inner door at the lock side of the door. Open the inner door and disconnect the earthing point on the door and the wide ribbon cable that connects the main board on the door to the back of the enclosure. Close the door and extract the 2 remaining hinge pins. Carefully remove the inner door from the unit including all circuit boards fitted to it and place it back in the box for protection. 5) Removal Of The Battery Clamp And Gear-Tray Remove the two screws holding the battery clamp (if supplied) and carefully withdraw the clamp ensuring that it cannot short out the battery terminals. Remove the 2 screws from the bottom of the gear-tray (in the back of the enclosure) and loosen the two at the top (key-hole fixings). Disconnect the earth connection from the gear-tray to the enclosure. Remove the gear-tray from the enclosure including the attached circuit boards. 6) Preparing and Fixing The Unit Using the installation template, mark out suitable positions for cable entry on the back of the enclosure i.e. not behind the gear-tray. Cut out the cable entry positions and mount the enclosure at the position prepared in (2) feeding cables through into the box. 7) Re-Fitting The Gear-Tray And Battery Clamp. Re-fit the gear tray (re-fit is reversal of 5). Ensure that the earth removed in (5) is re-connected DO NOT CONNECT ANY NON-EARTH TERMINALS. Refit the battery clamp (refit is reversal of 5) ensuring that the clamp cannot touch the battery terminals. DO NOT CONNECT THE BATTERIES 8) Re-fitting the Inner Door Re-fit the inner door (re-fit is reversal of 4) ENSURE THAT ALL EARTHING POINTS ARE RE-CONNECTED. 9) Re-Fitting The Door Re-fit the outer door by offering the door up to the hinges and inserting the 2 hinge pins. N93-347-81 Issue 2 Page 7 of 14 Copyright Protec Fire Detection PLC 2010

3.2 Outstations Carefully remove the front cover of the refuge outstation or inner plate of the fire telephone and disconnect the 14 way ribbon cable and earth cable from the assembly. Mark the backbox fixings on the wall, then remove the backbox from the drilling area and drill the fixing holes. Mount the backbox on the wall and remove all debris from the backbox. For the IP65 fire rated telephone, the box mounting holes must be sealed after installation to maintain the IP rating. Do not terminate any cable at this time. The ribbon connector on the terminal board can be plugged into the TEST socket on the terminal board to allow continuity through for testing the cabling. N93-347-81 Issue 2 Page 8 of 14 Copyright Protec Fire Detection PLC 2010

4.0 CABLE TEST Before connecting external cables to any field device, tests must be carried out using a 500V DC insulation tester (Megger). The readings between each cable core, and each core and screen must be greater than 10M ohms (record the readings). Equipment connected to the cabling during insulation tests could be damaged with the high voltages produced. Great care must be taken after insulation tests to discharge the cables, since charged cable may damage electronic equipment upon connection. N93-347-81 Issue 2 Page 9 of 14 Copyright Protec Fire Detection PLC 2010

5.0 CONNECTION 5.1 Panels Wiring details are supplied for reference only. 5.2 Outstation and Control Loops DO NOT MAKE ANY CONNECTIONS TO THE CONTROL PANEL. The outstation loop location in the panel as shown. Outstation Loop Outstation Loop Control Loop Control Loop The control loop positioned as shown. Route the power cables to the power supply unit. N93-347-81 Issue 2 Page 10 of 14 Copyright Protec Fire Detection PLC 2010

5.3 Outstations All metal termination boxes and detector bases should be securely fastened to the mounting surface and earthed as required. Connection details are shown below for information only. OUTSTATIONS MUST NOT BE CONNECTED AT THIS STAGE. N93-347-81 Issue 2 Page 11 of 14 Copyright Protec Fire Detection PLC 2010

5.4 Power Supply Cabling (Remote Charger Only) If the panel has an external charger it will require two separate +24V supplies. This is a requirement of En54. These two supplies must not be wired in the same fire rated cable. In addition there is a fault signal SF from the charger to the panel. This signal can be combined with one of the +24V supplies into a 4-core fire rated cable. The maximum length of cable between the charger and the panel will depend upon the volt drop along the cable. No more than 3A must be supplied to a panel and no more than two panels must be fed from the same charger. N93-347-81 Issue 2 Page 12 of 14 Copyright Protec Fire Detection PLC 2010

6.0 COMMISSIONING REQUIREMENTS Refer to the supplied copy of COMMISSIONING STANDARD TERMS for details of requirements before commissioning can take place. Note: The Commissioning Application form must be completed and returned 14 days before a commissioning engineer can attend. Note that this can be done online at www.protec.co.uk/commissioning.htm. N93-347-81 Issue 2 Page 13 of 14 Copyright Protec Fire Detection PLC 2010

7.0 EVC40 Specification Power Supply 230 AC / 24V DC operation (battery support for 24hrs standby and 3 hrs continuous use) Integral Charger 3A switch mode, temperature compensated Maximum Battery Size 2 x 12V 18Ah Fault Indication By lamp, buzzer and LCD display LCD Display 240 x 64 bit graphical Call Features All Call facility to outstations with a loudspeaker, Group Call to selected units Microphone Frequency Response 250Hz to 4kHz +/- 3dB IP Rating Outstations protected to IP33 (indoor) & IP65 (external with separate enclosure) Cable Type 2 Core, enhanced grade, fire rated cable for loops and network Master Panel Dimensions 440(W) x 385(H) x 110(D)mm Emergency Refuge Station Dimensions Flush - 150(W) x 220(H) x 1.5(D)mm, Surface - 130(W) x 200(H) x 1.5(D)mm Backbox - 130(W) x 200(H) x 50(D)mm Fire Emergency Telephone Dimensions 180(W) x 260(H) x 95(D)mm Maximum Loop Cable Length 2km max with 2.5mm2cable, 1km max with 1.5mm2cable Temperature Range 0 to 40 C Humidity Limit 85% Non-condensing Maximum Loop Cable Capacitance 0.27µf Maximum Loop Cable Resistance 15Ω per conductor N93-347-81 Issue 2 Page 14 of 14 Copyright Protec Fire Detection PLC 2010