DESCRIPTION DWG DESCRIPTION DWG



Similar documents
ELECTRICAL INSULATION TESTING OF HV EQUIPMENT UP TO 33kV

ES281 COMPANY-SPECIFIC APPENDICES TO ENA ENGINEERING RECOMMENDATION G81 PART 1

COMMISSIONING TESTS FOR HV UNDERGROUND CABLES (UP TO 33KV) SWP

Product brochure Multi Functional Switchgear PASS M kv Flexible and compact switchgear solutions for windfarms

Reyrolle Protection Devices. 7PG17 - XR Intertripping, Interposing, Supervision and Special Purpose Relays. Answers for energy

7. Reactive energy compensation

Unified requirements for systems with voltages above 1 kv up to 15 kv

2. A conductor of length 2m moves at 4m/s at 30 to a uniform magnetic field of 0.1T. Which one of the following gives the e.m.f. generated?

How To Understand The Electrical Power Supply Of A Power Supply System

Instrument Transformers Application Guide

Short Circuit Current Calculations

How To Choose A Transformer

AMSC s Superconductor Cable Technologies for Electric Utilities

Discussion on Class I & II Terminology. IEEE PES Transformers Committee Fall Meeting 2011 Boston, MA

Tutorial One: Calculation of leakage inductance of transformer using FEM MVA, 132 kv/33kv, Y/, Ampere-turns: , No.

Code of Practice Electricity transmission and distribution asset management. February 2009

INTERNATIONAL STANDARD

Earthing Guidance Notes

Physics 25 Exam 3 November 3, 2009

Objectives. Capacitors 262 CHAPTER 5 ENERGY

ENERGY NETWORKS ASSOCIATION. Electricity Industry EMF Measurement Protocol for High Field Areas

Simulation of Cable Overloading Problem on a University Distribution System

Vrieswijk, T & Srinivasan,A Amerongen,NL, 25 januari 2012

Secondary Unit Substations

Eðlisfræði 2, vor 2007

Assessment of the Technical Issues relating to Significant Amounts of EHV Underground Cable in the All-island Electricity Transmission System

ELECTRICAL ENGINEERING DESIGN CRITERIA APPENDIX F

Power Voltage Transformers for Air Insulated Substations. THE PROVEN POWER.

NATIONAL CERTIFICATE (VOCATIONAL)

EMTP STUDIES PERFORMED TO INSERT LONG AC CABLES IN THE FRENCH GRID

The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies

CAPACITOR BANK TESTING SWP

Earth Fault Detection Basics in Theory

3. TYPES OF SERVICE AVAILABLE. 3.1 Scope

Chapter 24. Three-Phase Voltage Generation

ACCURACY OF POTENTIALTRANSFORMERS

The Intelligent AX1 Switchgear for Medium Voltage

Hyperlinks are Inactive

Joslyn Clark Controls, Inc.

SURGE PROTECTIVE DEVICES

Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components

PHYS 222 Spring 2012 Final Exam. Closed books, notes, etc. No electronic device except a calculator.

Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading. Ramandeep Kaur Aujla S.NO

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

SHORT CIRCUIT CURRENT CALCULATION AND PREVENTION IN HIGH VOLTAGE POWER NETS

DIRECT CURRENT GENERATORS

Connection of micro-generation to the electricity distribution network

Distribution Design Manual

Power transformers. Special transformers Railway

EARTHING AND BONDING AT SECONDARY SUBSTATIONS

Prediction of Core Losses of Three-Phase Distribution Transformer

Presentation to CIGRE Next Generation Network. Visit of Seine substation

8 Speed control of Induction Machines

Physics 6C, Summer 2006 Homework 2 Solutions

DRY TYPE TRANSFORMER

GENERATOR SELECTION. a. Three phase - 120/208V, 3 phase, 4W wye; 277/408, 3 phase, 4W wye; * 120/240V 3 phase, 4W Delta

DC GENERATOR THEORY. LIST the three conditions necessary to induce a voltage into a conductor.

SUITABILITY OF DIFFERENT TEST VOLTAGES FOR ON-SITE TESTING OF XLPE CABLE SYSTEMS

13. Electrical network design methodology and application example

SIZING THE PRIMARY POWER SYSTEM FOR RESISTANCE WELDERS

Power products and systems. Intelligent solutions for power distribution Zone concept

ESB Networks Ltd Statement of Charges

How To Get A Power Line Extension

Electric Power Distribution

Distribution Substation Manual (DSM) Section I - Introduction

LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS

High Voltage Circuit Breakers 3AP Type 72.5 kv to 800 kv Answers for energy.

CHAPTER VIII LINE PLANT SYSTEM COMMUNICATION THROUGH RE CABLE

Manual motor starter MS116

POWER FACTOR CORRECTION

EDS KV TRIPLEX CABLE

ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU

Edmund Li. Where is defined as the mutual inductance between and and has the SI units of Henries (H).

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application

Line Reactors and AC Drives

11. Assessment of service 12. S-phase supply 13. Water heaters NORTHERN TERRITORY OF AUSTRALIA ELECTRICITY BY-LAWS T ABLE OF PROVISIONS

CONNECTING YOU TO SPECIALIST ELECTRICAL SUPPORT services

HAZARDS, INCLUDING SHOCK, ARC FLASH AND FIRE

The Electrical Safety Regulation (pre and post 1 January 2014)

SYNCHRONOUS MACHINES

AC Generators. Basic Generator

4.5 Transformer Connections

MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING

The following table shows approximate percentage wise the

New Distribution Class Arrester Ground Lead Disconnector Design Enhances Detonation Reliability and Improves Arrester Performance

How To Understand And Understand The Theory Of Electricity

THE PER-UNIT SYSTEM. (2) The per-unit values for various components lie within a narrow range regardless of the equipment rating.

40 Series - Miniature PCB/Plug-in relays A. Features

Single and Three Phase Transformer Testing Using Static Motor Circuit Analysis Techniques

Cables, Cable Laying & Accessories Manual

Fault location on power cables. Fault location on power cables

Presentation of the France Transfo factories

OPITO APPROVED STANDARD

MOBILE SYSTEM FOR DIAGNOSIS OF HIGH VOLTAGE CABLES (132KV/220KV) VLF-200 HVCD

4160: THE GREEN 480 MEDIUM VOLTAGE ELECTRICAL SYSTEMS

Equipment: Power Supply, DAI, Transformer (8341), Variable resistance (8311), Variable inductance (8321), Variable capacitance (8331)

EFFICIENT ELECTRICAL ENERGY TRANSMISSION AND DISTRIBUTION INTERNATIONAL ELECTROTECHNICAL COMMISSION

BASIC NEC CODE RULES AND DESIGN PRACTICE

The purposes of this experiment are to test Faraday's Law qualitatively and to test Lenz's Law.

12 SOLAR PHOTOVOLTAIC POWER SUPPLY SYSTEMS by John Ware. PV modules are current-limiting

Transcription:

DESCRIPTION DWG DESCRIPTION DWG Ferroresonance 3451/1 3451/2 3451/3 Electro-magnetic Fields (EMF) 3462/1 HV & LV Insulators (Links) 3463/1 A ORIGINAL ISSUE B 14.07.09 APPROVED DATE J. Brooks 25.02.03 INDEX C. Noel DRAWN M. St John FILE: 5 48 3452 1 Index Sh 1 B

1. FERRORESONANCE which under no load can be represented by an iron cored inductance, in series with the core-sheath capacitance of the cable. [Note that this circuit applies to 3-core screened and single core cables, ie. There is no core to core capacitance.] The three-phase equivalent circuit is shown in Figure 1. The phenomenon of ferroresonance is the occurrence of high voltages which may occur when a modest size capacitance is either in series or in parallel with nonlinear inductance, such as an iron cored transformer. In power systems, the most common place to find ferroresonance is with a three phase distribution transformer energised through an underground cable of moderate length. Under no load, or very light load conditions, the capacitance of the cable is sufficient to precipitate ferroresonant behaviour under single phase switching conditions (eg. the operation of an HV fuse or asynchronous operation of singlephase 11kV switches such as a drop-out fuse unit.) The trend towards undergrounding of distribution assets and the increasing installation of URD has resulted in a higher incidence of situations where single phase switching of the cable connecting transformer could result in dangerous overvoltage due to ferroresonance. The simplest form of occurrence of a ferroresonance circuit in a URD distribution system is when the single-phase operating switchgear or switch fuses are located some distance away from the transformer itself, with a length of cable joining the switchgear and transformer. A circuit of this sort could occur, for example, where a substation is supplied from a set of EDO s on a cable termination pole. In the case where single phase switching is performed directly at the transformer terminals, there is no capacitance in circuit and as a result no abnormal circuit. Since the equivalent circuit of a cable under no load conditions is essentially a capacitive circuit, the presence of the cable introduces a capacitance into the circuit and forms a series LC circuit consisting of the transformer winding, Figure 1.1 With one phase energised (R phase for example as shown in Figure 1.1) a series circuit is formed consisting of the magnetised inductance L m between R and Y phases and the Y phase core-to-sheath cable capacitance. In parallel with this circuit is a second identical series circuit consisting of the magnetised inductance L m between R and B phases and the B phase core-to-sheath capacitance. Since each branch of this parallel circuit is identical, the potential between the points Y and B is zero and therefore the magnetising inductance L m between Y and B phases does not enter into the circuit. Combining the circuit components results in an equivalent series circuit consisting of a capacitance in series with a nonlinear inductance which is therefore the ferroresonant circuit. A ORIGINAL ISSUE APPROVED DATE 14/03/03 FERRORESONANCE C.Noel Dwg Sh 1 DRAWN FILE: 5 48 3451 1 3451

Three-phase Switching The use of ganged three-phase switching is one of the most effective and commonly used methods of avoiding ferroresonance. Single Phase Switching at Transformers The practice of switching at the transformer terminals themselves, is a particularly effective means of controlling ferroresonance. By doing this, the cable length between the transformer and the switch is essentially zero and the only possible capacitance in the network is that of the internal capacitance of the transformer. Figure 1.2 It is the interaction of this non-linear inductance in series with the capacitance of the cable that can cause severe overexcitation of the transformer and impose large overvoltages on the HV and LV systems. 1.1 Methods Of Controlling Ferroresonance The four most effective methods of controlling ferroresonance are: a) three-phase switching; b) single-phase switching at transformers; c) resistive load on the transformer; and d) limiting cable length. Methods (a) and (d) require action on the part of the system designer. Methods (b) and (c) require special operating procedures to ensure that there is effectively no length of cable being energised or de-energised at the same time as the transformer, or the presence of some load. This is a particularly suitable method and can be applied in distribution systems using single-phase switchgear. Where a cable transformer combination is to be energised, the cable only should be energised and then the transformer. Conversely on de-energising, the transformer only should be de-energised first and then the cable. Both sets of switchgear can then be single phase operating. Since the critical cable length, which is actually proportional to the critical cable capacitance, is inversely a function of the square of the voltage, the critical capacitance for higher system voltages is quite small and the transformer capacitance can become significant. Resistive Load on the Transformer A resistive loading of 2 to 3% is generally sufficient to control ferroresonance. However in a distribution network, alternative supply is often provided by paralleling the low voltage network to adjoining substations. Should the LV network not be disconnected before HV switching, back energisation of the transformer would occur. Therefore this option is generally unavailable. Similarly on commissioning a transformer, there is usually no load available for this option to be used. A ORIGINAL ISSUE APPROVED DATE 14/03/03 FERRORESONANCE C.Noel Dwg Sh 2 DRAWN FILE: 5 48 3451 2 3451

Limiting Cable Length The derivation of the formula for the critical cable length assumes that the critical length is that which will result in a ferroresonant overvoltage of 2.73 times rated phase-to-ground system voltage. For an 11kV system this is 17.4kV phase-to-ground. This is also equal to the maximum acceptable power frequency voltage on the system. The expression for critical cable length is given by: l crit Where: 0.6I mag % kv. Ar1000 Ccc 2 1.58 62.8kVr C C cs cs metres I mag % = transformer magnetising current (typically 0.8% of rated current) kv.a r = 3-phase transformer rating (kv.a) C cc = core-core capacitance (F/km) C cs = core-sheath capacitance (F/km) kv r = system nominal voltage (kv) Inspection of the formula shows that the critical length is: i) directly proportional to transformer capacity and therefore the cable length for small transformers can be quite small; ii) directly proportional to transformer exciting current. (Old transformers which were manufactured before cold rolled grain oriented steel was used and had magnetising currents of typically up to 5%, allowed for considerably longer cables than for modern transformers); iii) inversely proportional to the square of the rated system voltage. (22kV and 33kV systems therefore can have iv) maximum cable lengths of only one quarter and one ninth respectively of the 11kV cable length); and inversely proportional to the cable core-to-sheath capacitance (since cable capacitance is a logarithmic function of the cable size, this is the least sensitive term in the expression). Critical Cable Lengths of 11kV XLPE Insulated Cables (Metres) Distribution Transformer Size (kva) 100 200 315 500 750 1000 1500 Cable mm² TRIPLEX 35 Al 12 24 38 60 90 119 179 TRIPLEX 185 Al 7 13 21 51 51 67 101 Critical Cable Lengths of 22kV XLPE Insulated Cables (Metres) Distribution Transformer Size (kva) 200 315 500 750 1000 1500 Cable mm² TRIPLEX 35 Al 7 11 18 26 35 53 TRIPLEX 185 Al 4 6 10 15 21 31 Note: The cable lengths given in the above tables are less than the values calculated using the equation. The cables lengths have been adjusted to suit the over voltage withstand capability of the surge arresters. A ORIGINAL ISSUE APPROVED DATE 14/03/03 FERRORESONANCE C.Noel Dwg Sh 3 DRAWN FILE: 5 48 3451 3 3451

ELECTRO-MAGNETIC FIELDS (EMF) Magnetic Fields are fields, resulting from the flow of current through wires or electrical devices, which increases in strength as the current increases. Magnetic fields emitted by underground cables are directly proportional to the distance between underground. The smaller the distance between the cables the smaller the magnetic field emitted at a given point. Magnetic fields are measured in units of Gauss (G) or Tesla (T). Gauss is the unit most commonly used in Australia. Tesla is the internationally accepted scientific term. Since most environmental EMF exposures involve magnetic fields that are only a fraction of a Tesla or a Gauss, these are commonly measured in units of microtesla (μt) or milligauss (mg), multiply by 10. That is 1μT = 10mG. Reference document ME000301R123 EMF Layout Design Recommendations lists the distances from Electricity infrastructure at which point it can be expected that magnetic field strength levels will fall below the recommended level for continuous exposure. This applies to electrical infrastructure in the Ergon Energy network and relates to extremely low frequency (under 3 khz), electric and magnetic fields. For multiple circuits Ergon Energy Electrical System Designers can use ME000301F105 Magnetic Field Calculator. A ORIGINAL ISSUE APPROVED DATE DRAWN J. Brooks 31/07/09 C. Noel M. St John DISTRIBUTION DESIGN - UNDERGROUND ELECTRO-MAGNETIC FIELDS (EMF) FILE: 5 48 3462 1 Dwg 3462 A

HV & LV ISOLATORS (LINKS) HV isolators or links are only capable of opening and closing a circuit with negligible current when no significant change occurs in the voltage across the terminals. The definition given in the Australian Standard AS 62271.102 High voltage switchgear and controlgear - Alternating current disconnectors and earthing switches for neligible current implies currents such as the capacitive currents of very short lengths of cable for rated voltages 420kV and below is 0.5A. HV isolators or links are also capable of carrying currents under normal circuit conditions and carrying for a specified time currents under abnormal conditions such as those of short circuit. Capacitive current on UG cable is dependent on cable size and cable length. The size relates to the distance between cable core and copper wire screens. Therefore the bigger the cable size (the larger the distance between cable core and screens) and/or the longer the cable route length, the quicker the 0.5A limit is reached. For Ergon Energy standard UG cables the maximum allowable cable length connected to HV or LV isolators are given on the tables below. Capacitance per phase in microfarads per 1000 metres at 20 C NON INSECT PROTECTED LV CABLE 6.35/11 (12) kv CABLE 12.7/22 (24) kv CABLE 16mm² Cu 240mm² Al 35mm² Al 185mm² Al 630mm² Al 185mm² Al μf/km 0.2869 0.7231 0.202 0.369 0.417 0.257 Charging current A/km/phase 0.05 0.14 0.403 0.736 1.664 1.026 Maximum allowable cable length (m) m 10000 3500 1200 675 300 475 Capacitance per phase in microfarads per 1000 metres at 20 C INSECT PROTECTED LV CABLE 6.35/11 (12) kv CABLE 12.7/22 (24) kv CABLE 16mm² Cu 50mm² Cu 240mm² Al 35mm² Al 185mm² Al 240mm² Cu 400mm² Cu 35mm² Al μf/km 0.2869 0.4293 0.7231 0.201 0.369 0.417 0.514 0.144 Charging current A/km/phase 0.05 0.08 0.14 0.401 0.736 0.832 1.026 0.575 Maximum allowable cable length (m) m 10000 6250 3500 1200 675 600 475 850 A APPROVED J Brooks ORIGINAL ISSUE DISTRIBUTION DESIGN - UNDERGROUND DATE 31/7/09 HV & LV ISOLATORS (LINKS) C Noel SHEET 1 OF 1 Dwg DRAWN M St John FILE: 5 48 3463 1 3463 A