Energy Systems Engineering Technology



Similar documents
Flow Measurement Options for Pipeline and Open Channel Flow

Chapter 10. Flow Rate. Flow Rate. Flow Measurements. The velocity of the flow is described at any

Michael Montgomery Marketing Product Manager Rosemount Inc. Russ Evans Manager of Engineering and Design Rosemount Inc.

FLUID FLOW Introduction General Description

Grant Agreement No SFERA. Solar Facilities for the European Research Area SEVENTH FRAMEWORK PROGRAMME. Capacities Specific Programme

Fluid Flow Instrumentation

Using meters to measure steam flow

Flow Measurement in Pipes and Ducts. Flow Measurement in Pipes and Ducts, Course #503. Presented by:

Thermal Dispersion Mass Flow

Laminar and Turbulent flow. Flow Sensors. Reynolds Number. Thermal flow Sensor. Flow and Flow rate. R = Mass Flow controllers

C. starting positive displacement pumps with the discharge valve closed.

ABB Flowmeters Review of industrial processing flowmeters

Aeration Air & Digester Gas Flow Metering Using Thermal Mass Technology. HWEA 2011 Conference Craig S. Johnson

Energy and Flow Measurement for Hydronic Systems

A LAMINAR FLOW ELEMENT WITH A LINEAR PRESSURE DROP VERSUS VOLUMETRIC FLOW ASME Fluids Engineering Division Summer Meeting

Liquid Flowmeters A Guide for Selecting a Flowmeter for Pressurized Systems

The Versatile Differential Pressure Transmitter. By David Gunn Honeywell Process Solutions

Fundamentals of Mass Flow Control

The Unique Accelabar Flow Meter

Advanced Differential Pressure Flowmeter Technology V-CONE FLOW METER TECHNICAL BRIEF

Application of the Orifice Meter for Accurate Gas Flow Measurement page 1. Application of the Orifice Meter for Accurate Gas Flow Measurement.

Valve Sizing. Te chnic al Bulletin. Flow Calculation Principles. Scope. Sizing Valves. Safe Product Selection.

CO MPa (abs) 20 C

Air Eliminators and Combination Air Eliminators Strainers

191: Calibration and Standards in Flow Measurement. Richard Paton National Engineering Laboratory, Scotland, UK 1 GENERAL PRINCIPLES

Head Loss in Pipe Flow ME 123: Mechanical Engineering Laboratory II: Fluids

High Speed Aerodynamics Prof. K. P. Sinhamahapatra Department of Aerospace Engineering Indian Institute of Technology, Kharagpur

Gas Custody Transfer Calibration

Stack Sampling Stack sampling or source sampling

Experiment (13): Flow channel

Theory overview of flow measurement using differential pressure devices based on ISO-5167 standard.

Experiment 3 Pipe Friction

SIZING AND CAPACITIES OF GAS PIPING

A basic introduction to steam

TOPIC: KNOWLEDGE: K1.01 [3.3/3.5] Which one of the following contains indications of cavitation in an operating centrifugal pump?

The Fundamentals of Gas Flow Calibration

FLOW METER SPECIFICATION AND APPLICATION ANALYSIS Class #41

Equivalents & Conversion Factors 406 Capacity Formulas for Steam Loads 407 Formulas for Control Valve Sizing

Accurate Air Flow Measurement in Electronics Cooling

ngenieros Ingenieros Asociados De Control S.L.

Guidance Notes For Provision Of Water Expansion For 10 & 15 Litre Unvented Hot Water Heaters

Chapter 3.5: Fans and Blowers

Flow Sensors. - mass flow rate - volume flow rate - velocity. - stream line parabolic velocity profile - turbulent vortices. Methods of measurement

Sentinel LCT. Panametrics Ultrasonic Flowmeter for Liquid Custody Transfer Measurement. GE Measurement & Control Solutions. Benefits.

User s Manual Laminar Flow Elements

Steven R. McManus Environmental Product Support Teledyne Isco

ORIFICE PLATES. CONCENTRIC BORE: For standard fluid conditions an Orifice Plate would have a centrally located orifice bore.

Flow. 1.1 Introduction. 1.2 Units of Flow. 1.3 Measurement of Flow

FUNDAMENTALS OF GAS TURBINE METERS John Gorham Sensus Metering Systems 805 Liberty Blvd. DuBois, PA 15801

HYDRAULICS. H91.8D/C - Computerized Open Surface Tilting Flow Channel - 10, 12.5, 15 and 20 m long

Tadahiro Yasuda. Introduction. Overview of Criterion D200. Feature Article

Custody Transfer Measurement. with the V-Cone Flowmeter

CENTRIFUGAL PUMP OVERVIEW Presented by Matt Prosoli Of Pumps Plus Inc.

Lecture 6 - Boundary Conditions. Applied Computational Fluid Dynamics

4.What is the appropriate dimensionless parameter to use in comparing flow types? YOUR ANSWER: The Reynolds Number, Re.

Chapter 5 MASS, BERNOULLI AND ENERGY EQUATIONS

Gertrudys B. Adkins, Ph.D. Division of Water Rights 2006

F ox W hi t e Paper. Reduce Energy Costs and Enhance Emissions Monitoring Systems

AN INSTRUMENT FOR GRAVIMETRIC CALIBRATION OF FLOW DEVICES WITH CORROSIVE GASES. J. O. Hylton C. J. Remenyik Oak Ridge National Laboratory *

Fluid Mechanics Prof. S. K. Som Department of Mechanical Engineering Indian Institute of Technology, Kharagpur

COMBIMASS. Technical Data COMBIMASS eco-bio +

BASIC UNDERSTANDING OF FLOW CALCULATIONS AND ESTIMATES MAKES SIZING VALVES SIMPLER

Flashing and Cavitation

Chapter 8: Flow in Pipes

جامعة البلقاء التطبيقية

MTI10 Insertion and MTL10 In-line Thermal Mass Flowmeter and Temperature Transmitter

Module 9: Basics of Pumps and Hydraulics Instructor Guide

XI / PHYSICS FLUIDS IN MOTION 11/PA

Understanding the Flo-Dar Flow Measuring System

Heat Transfer Prof. Dr. Ale Kumar Ghosal Department of Chemical Engineering Indian Institute of Technology, Guwahati

FORMATION DAMAGE AND WELL TREATMENT SYSTEM

Chapter 19 Purging Air from Piping and Vessels in Hydrocarbon Service

2.0 BASIC CONCEPTS OF OPEN CHANNEL FLOW MEASUREMENT

Differential Relations for Fluid Flow. Acceleration field of a fluid. The differential equation of mass conservation

THE THERMAL FLOW METER, A GAS METER FOR ENERGY MEASUREMENT

Index Page. Pumping Systems Intensifiers Gas Boosters High Pressure Generators

Fluids and Solids: Fundamentals

HEAVY OIL FLOW MEASUREMENT CHALLENGES

DIRECT STEAM INJECTION HOT WATER SYSTEMS FOR JACKETED HEATING

Sulfur Tail Gas Thermal Oxidizer Systems By Peter Pickard

COUNTERBALANCE VALVES

INDIAN STANDARDS FOR NATURAL GAS PIPELINE SYSTEM

Fundamentals of Orifice Meter Measurement page 1. Fundamentals of Orifice Meter Measurement. What is an Orifice Meter? How does it work?

Ve-Lock manufactures Needle Valves from Solid bar stock Materials & all parts details are as below:

Minor losses include head losses through/past hydrants, couplers, valves,

Methodology for Liquid Ultrasonic Flow Measurement within the Laminar to Turbulent Transitional Zone

Experiment # 3: Pipe Flow

For Multi-Parameter Meters see mvx

du u U 0 U dy y b 0 b

TABLE OF CONTENT

ELECTRIC/DIESEL FIRE PUMP CHECK LIST

Flue gas measurement and control Partial-insertion pitot tubes in CEMS applications

Centrifugal Fans and Pumps are sized to meet the maximum

Lecture 5 Hemodynamics. Description of fluid flow. The equation of continuity

Flow Measurement Calibration and Measurement

SIZING AND CAPACITIES OF GAS PIPING

Pump ED 101. Positive Displacement Pumps. Part I Reciprocating Pumps

Transcription:

College of Technology Instrumentation and Control Module # 4 Flow Measurement Document Intent: The intent of this document is to provide an example of how a subject matter expert might teach Flow Measurement. This approach is what Idaho State University College of Technology is using to teach its Energy Systems Instrumentation and Control curriculum for Flow Measurement. The approach is based on a Systematic Approach to Training where training is developed and delivered in a two step process. This document depicts the two step approach with knowledge objectives being presented first followed by skill objectives. Step one teaches essential knowledge objectives to prepare students for the application of that knowledge. Step two is to let students apply what they have learned with actual hands on experiences in a controlled laboratory setting. Examples used are equivalent to equipment and resources available to instructional staff members at Idaho State University. Flow Measurement Introduction: This module covers aspects of Flow measurement as used in process instrumentation and control. Flow measurement addresses essential knowledge and skill elements associated with measuring Flow. Students will be taught the fundamentals of Flow measurement using classroom instruction, demonstration, and laboratory exercises to demonstrate knowledge and skill mastery of Flow measurement. Completion of this module will allow students to demonstrate mastery of knowledge and skill objectives by completing a series of tasks using calibration/test equipment, Flow indicating, and Flow transmitting devices. Flow Module Page 1

References This document includes knowledge and skill sections with objectives, information, and examples of how pressure measurement could be taught in a vocational or industry setting. This document has been developed by Idaho State University s College of Technology. Reference material used includes information from: American Technical Publication Instrumentation, Fourth Edition, by Franklyn W. Kirk, Thomas A Weedon, and Philip Kirk, ISBN 979-0-8269-3423-9 (Chapter 5) Department of Energy Fundamentals Handbook, Instrumentation and Control, DOE- HDBK-1013/1-92 JUNE 1992, Re-Distributed by http://www.tpub.com Flow Module Page 2

STEP ONE Flow Measurement Course Knowledge Objectives Knowledge Terminal Objective (KTO) KTO 4. Given examples, EVALUATE Flow measurement fundamentals as they apply to measuring Flow process variables to determine advantages and disadvantages associated with different types of devices used to indicate, measure, and transmit Flow. Knowledge Enabling Objectives (KEO) KEO 4.1. KEO 4.2. KEO 4.3. KEO 4.4. KEO 4.5. KEO 4.6. KEO 4.7. KEO 4.8. KEO 4.9. KEO 4.10. KEO 4.11. DEFINE FLUID FLOW and its importance as a process variable. DESCRIBE FLOW RATE as it applies to flow measurement. DESCRIBE TOTAL FLOW as it applies to flow measurement. DESCRIBE the characteristics of FLUID FLOW to include Physical Properties, Reynolds Number, and Compressibility. DESCRIBE how pressure, temperature, and volume define GAS LAWS for Boyle s Law, Charles Law, Gay-Lussac s Law, and the Combined Law. DESCRIBE the concept associated with DIFFERENTIAL PRESSURE FLOWMETERS. DEFINE what a PRIMARY FLOW ELEMENT is. DESCRIBE what an ORIFICE PLATE is and how it used to measure flow. DESCRIBE what a FLOW NOZZLE is and how it used to measure flow. DESCRIBE what a VENTURI TUBE is and how it used to measure flow. DESCRIBE what a LOW-LOSS FLOW TUBE is and how it used to measure flow. Flow Module Page 3

KEO 4.12. DESCRIBE what a PITOT TUBE is and how it used to measure flow. KEO 4.13. KEO 4.14. KEO 4.15. KEO 4.16. KEO 4.17. KEO 4.18. KEO 4.19. KEO 4.20. KEO 4.21. KEO 4.22. KEO 4.23. KEO 4.24. DESCRIBE OPERATING PRINCIPLES associated with DIFFERENTIAL PRESSURE FLOWMETERS to include the Bernoulli Equation and the Vena Contracta Point. DESCRIBE why locations for DIFFERENTIAL PRESSURE CONNECTIONS of FLOWMETERS vary. DESCRIBE how DIFFEENTIAL INSTRUMENT LOCATIONS are determined for Liquid, Gas, and Steam flow applications. DESCRIBE how BLOCKING VALVES AND MANIFOLDS are used for measuring differential measurements associated with flow. DESCRIBE how VARIABLE-AREA FLOWMETERS maintain a constant differential pressure and allows the flow area to change with flow rate. DESCRIBE how ROTAMETERS are used and how they measure flow. DESCRIBE how MODIFIED ROTAMETERS are used as PURGE OR BYPASS METERS. DESCRIBE how METERING-CONE and SHAPTE-FLOAT & ORIFICE VARIABLE-AREA METERS measure flow. EXPLAIN operating principles associated with VARIABLE-AREA FLOWMETERS. DESCRIBE how MECHANICAL FLOWMETERS measure flow to include the following Positive-Displacement Flometers: Nutating Disc, Rotating- Impeller, and Sliding Vane. DESCRIBE how TURBINE METERS and PADDLE WHEEL METERS measure flow. DESCRIBE how MAGNETIC METERS measure flow. Flow Module Page 4

KEO 4.25. KEO 4.26. KEO 4.27. KEO 4.28. KEO 4.29. KEO 4.30. KEO 4.31. DESCRIBE how MAGNETIC VORTEX SHEDDING METERS measure flow. DESCRIBE how ULTRASONIC FLOWMETERS measure flow. DESCRIBE how MASS FLOWMETERS measure flow to include a CORIOLIS METER and a THERMAL MASS METER. DESCRIBE how ACCESSORY FLOW DEVICES function and how they are used. EXPLAIN how different FLOW SWITCHS function and how they are used to include: DIFFERENTIAL PRESSURE SWITCHES, BLADE SWITCHES, THEREMAL SWITCHES, and ROTAMETER SWITCHES. EXPLAIN how OPEN-CHANEL WEIRS and PARSHALL FLUME FLOW MEASUREMTNS function and how they are used. EXPLAIN how a BELT WEIGHING SYSTEM is used to measure a solids flow. Flow Module Page 5

FLOW MEASURMENT KEO 4.1. DEFINE FLUID FLOW and its importance as a process variable. FLUID FLOW is the movement of liquids in pipes or channels, and gases or vapors in pipes or ducts. A fluid is a material that flows and takes the shape of its container. All liquids and gases are fluids. Measuring flow is an important process variable which requires the use of many types of instruments and scientific principles. It is often more convenient to measure the flow of a fluid by measuring some other characteristic that varies in a predictable and reliable way with the rate of flow, such as a drop in pressure caused by restriction in a pipeline. This is drop in pressure is commonly used as well as a host of other methods. FLUID FLOW is an important process variable that needs to be monitored and controlled not only in our homes and communities, but throughout all aspects of industry in the world. Fluids can be harmless, toxic, caustic, acidic, or volatile and to measuring them requires not only accuracy, but constant control at all times. KEO 4.2. DESCRIBE FLOW RATE as it applies to flow measurement. FLOW RATE is the quantity of fluid passing a point at a particular moment. Flow rate is expressed in volumetric or mass units. The common volumetric units used in the United States are Gallons per Minute (gpm) or Gallons per Hour (gph). Also in the United States metric units used are Liters per Minute, Cubic Meters per Hour, and Cubic Centimeters per Minute. The unit of Mass in the United States is Pounds per Hour and the Metric unit of Mass is Kilograms per Hour. KEO 4.3. DESCRIBE TOTAL FLOW as it applies to flow measurement. TOTAL FLOW is the quantity of fluid that passes a point during a specific time interval. An example would be the Flow Rate of pumping a fluid may be given in gallons per hour and the Total Flow is the total gallons pumped. Flow Module Page 6

Flow is measured in many units. Conversion tables like the table below are used to convert from one unit to another: Figure 5-1 page 167 SUMMARY Fluid flow is the movement of liquids in pipes or channels, and gases or vapors in pipes or ducts. A fluid is a material that flows and takes the shape of its container. All liquids and gases are fluids. Flow rate is the quantity of fluid passing a point at a particular moment. Total flow is the quantity of fluid that passes a point during a specific time interval. KEO 4.4. DESCRIBE the characteristics of FLUID FLOW to include Physical Properties, Reynolds Number, and Compressibility. Flow Module Page 7

A FLUID FLOW s most important characteristic that affects its flow is whether the fluid is a liquid, gas, or vapor. This is because at certain temperatures and pressures, most fluids can change phase between vapor, liquid, or solid. An example would be water that when heated becomes steam and when cooled becomes ice. Gases can also be condensed to a liquid like liquid nitrogen or liquid oxygen, or a solid like dry ice. A number of Physical Properties common to most fluids that influence the selection of the method chosen to measure fluid flow include: Pressure, Velocity, Density, Viscosity, Compressibility, Electrical Capacitance and Conductance, Thermal Conductivity, and the response to Sonic Impulses, Light, or Mechanical Vibration. All of these properties allow for the measurement of these fluids to determine Flow Rate and Total Flow. The fact that so many properties and characteristics can be measured account for the wide variety of flowmeters. In addition to Physical Properties of fluids, there are other factors that affect flow. They include configuration o the pipes or ducts; the location, style, and number of valves; and changes in elevation of the fluid. The most important factors affecting fluid flow are the properties of the fluid, the Reynolds Number describing the type of flow, and the Compressibility of the fluid. Physical Properties greatly affecting the measurement of flow include Density, Specific Gravity, and Viscosity. Density is a measurement of Mass per Volume with common units of density being pounds per cubic foot (lb/ft 3 or lb/cu ft) and grams per cubic centimeter (g/cm 3 or g/cu cm). Density varies with changes in temperature. Specific Gravity is the ratio of density of a fluid to the density of a reference fluid. For liquids this reference is usually water. For gases, the reference fluid is dry air. When two liquids that do not mix are in a container, the one with the lowest specific gravity will float on top of the one with the greater specific gravity. An example would be most oils having a specific gravity of from 0.75 to 0.85 at ambient temperature mixed with a fluid like water having a specific gravity of 0.998 the oil will rise to the top and float on the surface of the water. Gasoline would also float on top of water. Oils and fuel are examples of fluids called organic fluids and solutions containing water are called aqueous fluids. Absolute Viscosity is the resistance to flow of a fluid and has units of Centipoise (cp). Kinematic Viscosity is the ration of absolute viscosity to fluid density and has units of Centistokes (cs). Flow Module Page 8

The following picture illustrates how Viscosity is affected by temperature and other factors which normally decreases with increasing temperatures: Figure 5-2 page 168 Many fluids must be preheated before being pumped. A property of fluid flow that describes the type of flow is the Reynolds Number. The Reynolds Number of a fluid is the ratio between the inertial forces moving a fluid and viscous forces resisting that movement. The Reynolds Number describes the nature of the fluid flow. This number has no units of measure and is calculated from velocity or flow rate, density, viscosity, and the inside diameter of the pipe. Reynolds Numbers commonly range from 100 to 1,000,000. However, they can be higher or lower than these values. The following picture illustrates the relationship of Reynolds Number and Flow Profiles: Flow Module Page 9

Figure 5-3 page 169 Velocity is the speed of fluid in the direction of flow and typically is expressed in ft/sec. A Streamline is a line that shows the direction and magnitude of smooth flow at every point across a pipe profile. A Flow Profile is a representation of the Velocity of a fluid at different points across the pipe or duct as depicted in the above picture. Laminar Flow is the smooth fluid flow that has a Flow Profile that is parabolic in shape with no mixing between the stream lines. Laminar Flow in pipes occurs at Reynolds Numbers below Flow Module Page 10

about 2100. A cross section of a Laminar Flow is a parabolic Flow Profile, with the maximum Velocity in the center and the minimum Velocity at the pipe walls. Turbulent Flow is fluid flow in which the Flow Profile is a flattened parabola, the streamlines are not present, and the fluid is freely intermixing. Turbulent Flow in pipes typically occurs at Reynolds Numbers above about 4000. The exact shape of the flattened profile depends on the Reynolds Number. There is a sudden transition between Laminar Flow and Turbulent Flow as the flow rate increases and normally occurs at Reynolds Numbers between 2100 and 4000. Many Flowmeters require Turbulent Flow and specify Reynolds Numbers above 10,000 to ensure that Turbulent Flow is the prevailing condition. Compressibility is a determination as to whether or not a fluid can be compressed. An incompressible fluid is a liquid fluid where there is very little change in pressure. Liquids are essentially incompressible. As an example, fluid power systems transmit power through an impressible hydraulic fluid. A compressible fluid is a fluid where the volume and density change when subjected to a change in pressure. Gases and Vapors are examples of compressible fluids. A Flowing Condition is the pressure and temperature of the gas or vapor at the point of measurement. A Standard Condition is when an acceptable set of temperature and pressure condition is used as a basis for measurement. Flow Module Page 11

SUMMARY A fluid flow s most important characteristic that affects its flow is whether the fluid is a liquid, gas, or vapor. Physical properties common to most fluids that influence the selection of the method chosen to measure fluid flow include: o Pressure, Velocity, Density, Viscosity, Compressibility, Electrical Capacitance and Conductance, Thermal Conductivity, and the response to Sonic Impulses, Light, or Mechanical Vibration. The most important factors affecting fluid flow are the properties of the fluid, the Reynolds Number describing the type of flow, and the Compressibility of the fluid. The Reynolds Number of a fluid is the ratio between the inertial forces moving a fluid and viscous forces resisting that movement and describes the nature of the fluid flow. Compressibility is a determination as to whether or not a fluid can be compressed. An incompressible fluid is a liquid fluid where there is very little change in pressure. Liquids are essentially incompressible. A compressible fluid is a fluid where the volume and density change when subjected to a change in pressure. Gases and Vapors are examples of compressible fluids. Flow Module Page 12

KEO 4.5. DESCRIBE how pressure, temperature, and volume define GAS LAWS for Boyle s Law, Charles Law, Gay-Lussac s Law, and the Combined Law. Gas Laws show how gases behave with changes in temperature, pressure and volume. Gas Laws are used to determine the volume of gas at one set of pressure and temperature conditions when data from another set of conditions are known. The following figure depicts three gas laws, Boyle s, Charles, and Gay-Lussac s with their corresponding calculations: Figure 5-4 Page 171 Flow Module Page 13

Boyle s Law is a gas law that states that the absolute pressure of a given quantity of gas varies inversely with its volume provided the temperature remains constant. P 2 = Final Pressure (in psia) P 1 = Initial Pressure (in psia) V 2 = Final Volume (in cubic units) V 1 = Initial Volume (in cubic units) Boyle s Law Charles Law is a gas law that states the volume of a given quantity of gas varies directly with its absolute temperature provided the pressure remains constant. Charles Law T 2 = Final Temperature (in o R) T 1 = Initial Temperature (in o R) V 2 = Final Volume (in cubic units) V 1 = Initial Volume (in cubic units) Gay-Lussac s Law is a gas law that states that the absolute pressure of a given quantity of a gas varies directly with its absolute temperature provided the volume remains constant. Gay-Lussac s Law Flow Module Page 14

T 2 = Final Temperature (in o R) T 1 = Initial Temperature (in o R) V 2 = Final Volume (in psia) V 1 = Initial Volume (in psia) The three gas laws can be combined into one equation, called the Combined Gas Law in order to simplify calculations as depicted below: Figure 5-5 page 172 Combined Law Flow Module Page 15

V = Volume (in ft 3 or other volumetric terms) P = Pressure (in psia or other absolute pressure terms) T = Temperature (in o R or o K) All Subscripts refer to different sets of conditions. SUMMARY Gas Laws show how gases behave with changes in temperature, pressure and volume. Gas Laws are used to determine the volume of gas at one set of pressure and temperature conditions when data from another set of conditions are known. Boyle s Law is a gas law that states that the absolute pressure of a given quantity of gas varies inversely with its volume provided the temperature remains constant. Charles Law is a gas law that states the volume of a given quantity of gas varies directly with its absolute temperature provided the pressure remains constant. Gay-Lussac s Law is a gas law that states that the absolute pressure of a given quantity of a gas varies directly with its absolute temperature provided the volume remains constant. The three gas laws can be combined into one equation, called the Combined Gas Law in order to simplify calculations. KEO 4.6. DESCRIBE the concept associated with DIFFERENTIAL PRESSURE FLOWMETERS. A pressure difference is created when a fluid passes through a restriction in a pipe. The point of maximum developed differential pressure is between the upstream of the restriction and the pressure downstream of the restriction, at the point of highest velocity. The shape and configuration of the restriction affects the magnitude of the differential pressure and how much of the differential is recoverable. Differential Pressure flowmeters are commonly used throughout industry and are called Differential Pressure Transmitters or DP Cells. Devices that restrict a flow and measure its differential pressure are called primary flow elements and they work together with the DP Devices to provide critical measurement and control of fluids. KEO 4.7. DEFINE what a PRIMARY FLOW ELEMENT is. Flow Module Page 16

Primary Flow Elements are devices that create or detect a pressure drop as fluid flows through a pipeline. Primary Flow Elements are designed to provide accuracy, low cost, ease of use, and pressure recovery, but not necessarily all in the same element. Examples of Primary Flow elements include: Orifice Plates, Flow Nozzles, Venturi Tubes, Low-Loss Flow Tubes, and Pitot Tubes. KEO 4.8. DESCRIBE what an ORIFICE PLATE is and how it used to measure flow. An ORIFICE PLATE is a primary flow element consisting of a thin circular metal plate with a sharp-edged round hole in it and a tab that protrudes from the flanges. The tab has orifice plate information stamped onto it. This information usually includes: Pipe Size, Bore Size, Material, and Type of Orifice. Orifice plates are not always reversible so the stamping information is on the upstream face of the plate. The Orifice is held in place between two special pipe flanges called orifice flanges. The below picture illustrates flow being straightened after going through pipe 90 o fittings to allow a smooth non turbulent flow upstream of the orifice plate (Straightening Vanes remove flow disturbances upstream of an orifice plate): Figure 5-6 page 173. Flow Module Page 17

Orifice Plates are simple, inexpensive, and replaceable. The hole in the plate is generally in the center (concentric) by may be off-center (eccentric). Eccentric plates are usually used to prevent excessive build up of foreign material or gases on the inlet side of the orifice. Some orifice plates will have a smaller hole near the top of the plate to release any build up of gases that may be present. Orifice Plates have a straight run requirement of about 20 times the pipe diameter before the orifice and 6 times the pipe diameter after the orifice plate to provide the most accurate differential pressure. Orifice plates have the poorest recovery of differential pressure (50%) of any of the primary flow elements. KEO 4.9. DESCRIBE what a FLOW NOZZLE is and how it used to measure flow. A similar primary flow element to the orifice plate is the Flow Nozzle. A Flow Nozzle is a primary flow element consisting of a restriction shaped like a curved funnel that allows a little more flow than an orifice plate and reduces the straight run pipe requirements associated with orifice plates. The Flow Nozzle is mounted between a pair of flanges like an orifice plate. The pressure sensing taps are located in the piping a fixed distance upstream and downstream of the flow nozzle. The following picture depicts a typical Flow Nozzle: Figure 5-7 page 174 Flow Module Page 18

KEO 4.10. DESCRIBE what a VENTURI TUBE is and how it used to measure flow. A VENTURI TUBE is a primary flow element consisting of a fabricated pipe section with a converging inlet section, a straight throat, and a diverging outlet section. The static pressure connection is located at the entrance to the inlet section. The reduced pressure connection is in the throat. Venturi tubes are much more expensive than orifice plates, but are more accurate and recover 90% or more of the differential pressure. This recovery reduces the burden on pumps and the cost of power to run them. Venturi Tubes are frequently used to measure large flows of water. A Venturi Tube is depicted below: Figure 5-7 page 174 Flow Module Page 19

KEO 4.11. DESCRIBE what a LOW-LOSS FLOW TUBE is and how it used to measure flow. A LOW-LOSS FLOW TUBE is a primary flow element consisting of an aerodynamic internal cross section with the low-pressure at the throat as depicted below: Figure 5-7 page 174 Low-Loss Flow Tubes are used for a higher energy efficiency of up to 97%, but are very expensive. Low-Loss Flow Tubes are often used in applications where the line pressure is low and therefore the pressure recovery must be high. Low-Loss Flow Tubes can often pay for themselves in energy savings in a short time as the following picture illustrates: Figure 5-8 page 174 Venturi Tube and Low-Loss Flow Tubes are the most efficient Primary Flow Element Flow Module Page 20

KEO 4.12. DESCRIBE what a PITOT TUBE is and how it used to measure flow. A PITOT TUBE is a tube inserted into the piping or water flow to measure the impact pressure. A Pitot Tube is a flow element consisting of a small bent tube with a nozzle opening facing into the flow stream. NOTE: Pitot Tubes are also used in other applications to measure water flow of a river or stream and on air craft to measure air flow to determine the speed of an aircraft is flying. The Pitot Tube Nozzle is called the impact opening and senses the velocity pressure plus the static pressure. The Static Pressure is sensed at the pipe wall perpendicular to the fluid stream. Pitot tubes are commonly used to measure air velocity in ducts and for measuring air speed of planes in flight. A Standard Pitot Tube is depicted below: Figure 5-9 page 175 A standard Pitot Tube senses the impact pressure at only one point in the center of the flow path. This is the high pressure tap as the pressure is greater in the center as it is on the walls of the pipe due to pipe resistance to the flow. Even though the velocity varies across the whole stream, it is greater in the middle of the flow stream. For example if a Pitot Tube were used to measure river water flow, the impact opening would be inserted the middle of the river as the water moves faster there than at the sides of the river banks due to the resistance of the river banks. Flow Module Page 21

To overcome the disadvantage of only having one impact point to measure the flow, an Averaging Pitot Tube was developed as depicted below: Figure 5-9 page 175 The advantage of the Averaging Pitot Tube is that you have several sensing points to average the flow reading for a more accurate flow rate reading; therefore they are improved devices for measuring flow. Flow Module Page 22

SUMMARY A pressure difference is created when a fluid passes through a restriction in a pipe. The point of maximum developed differential pressure is between the upstream of the restriction and the pressure downstream of the restriction, at the point of highest velocity. Primary Flow Elements are devices that create or detect a pressure drop as fluid flows through a pipeline. An Orifice Plate is a primary flow element consisting of a thin circular metal plate with a sharp-edged round hole in it and a tab that protrudes from the flanges and this tab has orifice plate information stamped onto it. Orifice plates are not always reversible so the stamping information is on the upstream face of the plate. Orifice plates have the poorest recovery of differential pressure (50%) of any of the primary flow elements. A Flow Nozzle is a primary flow element consisting of a restriction shaped like a curved funnel that allows a little more flow than an orifice plate. A Venturi Tube is a primary flow element consisting of a fabricated pipe section with a converging inlet section, a straight throat, and a diverging outlet section. Venturi tubes are much more expensive than orifice plates, but are more accurate and recover 90% or more of the differential pressure. Venturi Tubes are frequently used to measure large flows of water. Low-Loss Flow Tubes are used for a higher energy efficiency of up to 97%, but are very expensive. Low-Loss Flow Tubes are often used in applications where the line pressure is low and therefore the pressure recovery must be high. A Pitot Tube is a tube inserted into the piping or water flow to measure the impact pressure. A Pitot Tube is a flow element consisting of a small bent tube with a nozzle opening facing into the flow stream. There are two types of Pitot Tubes: A Standard Pitot Tube and an Averaging Pitot Tube. Flow Module Page 23

KEO 4.13. DESCRIBE OPERATING PRINCIPLES associated with DIFFERENTIAL PRESSURE FLOWMETERS to include the Bernoulli Equation and the Vena Contracta Point. OPERATING PRINCIPLES of all differential pressure flowmeters are based on equations developed by Daniel Bernoulli, a late 18 th century Swiss Scientist. His experiments related to the pressure and velocity of flowing water. He determined that at any point in a closed pipe there were three types of head pressure present: 1. Static Head Pressure due to elevation 2. Static Head Pressure due to applied pressure 3. Velocity Head Pressure. The different types of head pressure can be converted to each other by changes in flow. The Bernoulli Equation states that the sum of the heads of an enclosed flowing fluid is the same at any two locations. Differential Pressure Flowmeters primary flow elements, have pressure measured upstream and downstream of the flow element. The flow steam contracts slightly before it passes through the flow element and continues to do so until it reaches maximum contraction, and then slowly expands until it again fills the pipe. This concept is depicted below: Figure 5-10 page 176 The Vena Contracta is the point of lowest pressure and the highest velocity downstream frfom a primary flow element. According to the Bernoulli Equation, the velocity increases and the Flow Module Page 24

pressure decreases as fluid flows through the restriction. The actual location of the Vena Contracta point varies with flow rate and design of the flow element. Differential Pressure Measurements: For turbulent flow, the flow rate is proportional to the square root of the differential pressure. This square root relationship affects the Rangeability of the flow metering system. Rangeability or Turndown, is the ratio of the maximum flow to the minimum measurable flow at the desired measurement accuracy. This is a Characteristic of the Instrument and is not adjustable. For example, if the maximum measurable flow rate of a flowmeter were 100 gpm of water and the minimum rate were 20 gpm of water, the Rangeability or Turndown, is 5 to 1 (5:1) as depicted in the below picture: Figure 5-11 page 178 The above picture depicts how flow varies with the square root of pressure drop, restricting the meter from full flow to 20% if flow. Flow measurement is only accurate as long as the flowing conditions remain the same as when the system was designed. Changes in pressures and temperature are common in gas and vapor flow measurements. Liquid flow measurements are usually more consistent. Flowing conditions that differ from the original flowmeter design calculation can result in significant errors. When the original design conditions and the actual flowing conditions are known, the flowmeters displayed flow rate can be changed to the correct value. To obtain the correct flow, multiply the corrections factors for PC (Pressure Correction) and TC (Temperature Correction) times the displayed flow to obtain the correct flow as depicted in the below picture: Flow Module Page 25

Figure 5-12 page 179 The above picture illustrates how to use the correction formulas to correct Gas and Vapor flows from measured conditions to design flow conditions. SUMMARY Flow Module Page 26

Daniel Bernoulli determined that at any point in a closed pipe there were three types of head pressure present: 1. Static Head Pressure due to elevation 2. Static Head Pressure due to applied pressure 3. Velocity Head Pressure. Bernoulli Equation states that the sum of the heads of an enclosed flowing fluid is the same at any two locations. The Vena Contracta is the point of lowest pressure and the highest velocity downstream from a primary flow element. According to the Bernoulli Equation, the velocity increases and the pressure decreases as fluid flows through the restriction. Differential Pressure Measurements: For turbulent flow, the flow rate is proportional to the square root of the differential pressure. Flow measurement is only accurate as long as the flowing conditions remain the same as when the system was designed. To obtain the correct flow, multiply the corrections factors for PC (Pressure Correction) and TC (Temperature Correction) times the displayed flow to obtain the correct flow KEO 4.14. DESCRIBE why locations for DIFFERENTIAL PRESSURE CONNECTIONS of FLOWMETERS vary. DIFFERENTIAL PRESSURE CONNECTIONS of FLOWMETERS vary as there are two locations selected depending of the application. There are two different connections used to measure the high pressure (Static Pressure in the pipe) and the low pressure (to measure the reduced pressure developed by the flow through the flow element). Not all connection locations are the same and are based on the type of flow element used and manufacture specifications. Pitot Tubes vary from the standard Pitot Tube to the Averaging Pitot Tube. The standard Pitot Tube uses two taps and the averaging Pitot Tube uses just one. When dealing with Orifice Tap Locations, there are Flange Taps, Vena Contracta Taps, and Pipe Taps located at different positions for measuring pressure drops. Flange Taps are in the two flanges between the Orifice Plate. These tap connections requires the distance to be 1 inch upstream of the Orifice Plate, and 1 inch downstream of the Orifice Plate. Vena Contracta Taps are located at 1 pipe diameter upstream of the Orifice Plate and ½ the pipe diameter downstream of the Orifice Plate. Pipe Taps are located at 2 ½ times the pipe diameter upstream of the Orifice Plate and 8 times the pipe diameter downstream of the Orifice Plate. Flow Module Page 27

NOTE Pipe Tap Locations are generally specified by the manufacture for Flow Nozzles and Low-Loss Flow tubes, whereas pipe taps for Venturi Tubes are manufactured with the tubes purchased. The following picture illustrates Orifice Plate Tap Locations: Figure 5-13 page 179 KEO 4.15. DESCRIBE how DIFFEENTIAL INSTRUMENT LOCATIONS are determined for Liquid, Gas, and Steam flow applications. Flow Module Page 28

When installing Differential Pressure Instruments/Transmitters, there are different requirements for Liquid, Gas and Steam flow applications. The following picture illustrates how they are to be connected to the process flow in order to accurately measure flow: Figure 5-14 page 181 Location of a flow transmitter varies with the type of flowing fluid Liquid Flow Transmitter location must be mounted below the elevation of the flow element, and the impulse lines must be filled with the liquid being measured as depicted below: Flow Module Page 29

Care must be exercised to ensure that no bubbles are trapped in the instrument or impulse lines. This is accomplished via special valves for venting and releasing any air that may have entered the transmitter or impulse lines. A discuss later on will address how transmitter manifold assemblies can accomplish this or the use of special vent release fittings on a transmitter. The length of the transmitter impulse lines has no effect on the measurement accuracy as long as the two impulse lines start and end at equal elevations as indicated in the above picture. Gas Flow Transmitter location must be mounted above the elevation of the flow element and the diameter of the impulse lines must be large enough and routed so that any liquids which may condense in the impulse lines drain freely into the main piping as depicted below: Flow Module Page 30

Steam Flow Transmitter location must be located below the elevation of the flow element even though the fluid is a vapor. This is because steam condenses to water very easy, and mounting it below the flow element allows the instrument and impulse lines to fill with condensate. Flow Module Page 31

The steam condensate protects the instrument from coming in contact with the hot steam. The best way to set up this transmitter is to manually backfill the impulse lines with water. The following picture illustrates how to correctly locate the Steam Flow Transmitter: Flow Module Page 32

SUMMARY The standard Pitot Tube uses two taps and the averaging Pitot Tube uses just one. When dealing with Orifice Tap Locations, there are Flange Taps, Vena Contracta Taps, and Pipe Taps located at different positions for measuring pressure drops. Flange Taps are in the two flanges between the Orifice Plate. These tap connections requires the distance to be 1 inch upstream of the Orifice Plate, and 1 inch downstream of the Orifice Plate. Vena Contracta Taps are located at 1 pipe diameter upstream of the Orifice Plate and ½ the pipe diameter downstream of the Orifice Plate. Pipe Taps are located at 2 ½ times the pipe diameter upstream of the Orifice Plate and 8 times the pipe diameter downstream of the Orifice Plate. Pipe Tap Locations are generally specified by the manufacture for Flow Nozzles and Low-Loss Flow tubes, whereas pipe taps for Venturi Tubes are manufactured with the tubes purchased. When installing Differential Pressure Instruments/Transmitters, there are different requirements for Liquid, Gas and Steam flow applications. Liquid Flow Transmitter location must be mounted below the elevation of the flow element, and the impulse lines must be filled with the liquid being measured. Gas Flow Transmitter location must be mounted above the elevation of the flow element and the diameter of the impulse lines must be large enough and routed so that any liquids which may condense in the impulse lines drain freely into the main piping. Steam Flow Transmitter location must be located below the elevation of the flow element even though the fluid is a vapor. This is because steam condenses to water very easy, and mounting it below the flow element allows the instrument and impulse lines to fill with condensate. The steam condensate protects the instrument from coming in contact with the hot steam. KEO 4.16. DESCRIBE how BLOCKING VALVES AND MANIFOLDS are used for measuring differential measurements associated with flow. A Blocking Valve is a valve used at the differential measuring instrument (transmitter, gauge, or sensor) to provide a convenient location to isolate the instrument from the impulse, equalizing, or venting lines and to provide a method to equalize the high and low pressure sides of the differential instrument. Flow Module Page 33

Equalizing instrument pressure is necessary so that the instrument can be periodically calibrated and its zero status checked. Blocking valves may be connected with individual pipe fittings and valves or can be part of a manifold assembly in one block that can be attached to a differential pressure device. Typical blocking valves are single-valve equalizers or three, four, or five valve manifolds. They are essential in setting up and maintaining process flow instrumentation. The below picture illustrates manifold valves: Figure 5-15 page 182 The One-Valve is for equalizing pressure to perform a static test. The Three-Valve is for equalizing, static testing, and isolating and is most commonly used. The Five-Valve provides the Three-Valve function and adds the ability to vent and test. Flow Module Page 34

The following picture depicts a typical Differential Pressure Transmitter configured to measure flow with a three valve manifold and an Integral Orifice: Picture page 188 KEO 4.17. DESCRIBE how VARIABLE-AREA FLOWMETERS maintain a constant differential pressure and allows the flow area to change with flow rate. VARIABLE-AREA FLOWMETERS maintain a constant differential pressure through the flow of some type of flow restriction that repositions with changes in flow. This can be accomplished by a fixed-size plug that moves in a tapered tube, a shaped plug that partially blocks an orifice, or a restriction that moves up and down on a cone. The most common type of Variable-Area Flowmeter is a ROTAMETER. KEO 4.18. DESCRIBE how ROTAMETERS are used and how they measure flow. A ROTAMETER is a tapered tube and a float with a fixed diameter. The float of the rotameter changes its position in the tube to keep the forces acting on the float in equilibrium. One of forces is gravity and the other force is produced by the velocity of the process fluid. Flow Module Page 35

The following picture illustrates three types of floats depicting the fact that Rotameter floats have different configurations for different fluids and applications and shows where on the float a reading is taken: Figure 5-16 page 183 As a rule, when reading floats, most floats have a sharp edge at the point where the reading should be made on a scale. The exception is a round float and the reading would be directly in the center. In the floats pictured above, the general rule is the widest point on a float is where the reading reference point is. There are also Guided Rod Glass Tube Rotameters. Flow Module Page 36

There are Clear-Glass Tube Rotameters, Plastic Tube Rotameters, and Metal Tube Rotameters as depicted below: Figure 5-17 page 184 Glass Tube Rotameters are selected for fluids that are glass compatible. High temperatures water with a high ph will actually soften glass. For non-glass compatible fluids, Plastic Tube Rotameters are selected and are usually used with high temperatures, high ph, wet steam, caustic soda, and hydrofluoric acid. Metal-Tube tapered Rotameters consist of a metal tapered tube and a rod-guided float. A rod is attached to the float passes through top and bottom guides in the tube. A magnet in the float is coupled to a matching magnetic and indicator located outside the tube. Magnetic-Coupled Rotameters cannot be used in areas where strong magnetic fields are generated. Variations on Metal-Tube Rotameters include PVC Flanged Bodies and floats or with stainless steel bodies and matching floats. Additionally, an indicating electrical transmitter is often substituted for the visual indicator. Metal Tube Rotameters are selected for applications involving fluids which obscure the float or those too hot, too corrosive, or involving high Flow Module Page 37

pressures. A disadvantage to using magnetic coupled metal tube rotameters is that high temperature can diminish the magnetic coupling effect. SUMMARY A Blocking Valve is a valve used at the differential measuring instrument (transmitter, gauge, or sensor) to provide a convenient location to isolate the instrument from the impulse, equalizing, or venting lines and to provide a method to equalize the high and low pressure sides of the differential instrument. Blocking valves may be connected with individual pipe fittings and valves or can be part of a manifold assembly in one block that can be attached to a differential pressure device. The One-Valve is for equalizing pressure to perform a static test. The Three-Valve is for equalizing, static testing, and isolating and is most commonly used. The Five-Valve provides the Three-Valve function and adds the ability to vent and test. VARIABLE-AREA FLOWMETERS maintain a constant differential pressure through the flow of some type of flow restriction that repositions with changes in flow. The most common type of Variable-Area Flowmeter is a ROTAMETER. A ROTAMETER is a tapered tube and a float with a fixed diameter. The float of the rotameter changes its position in the tube to keep the forces acting on the float in equilibrium. One of forces is gravity and the other force is produced by the velocity of the process fluid. As a rule, when reading floats, most floats have a sharp edge at the point where the reading should be made on a scale. The exception is a round float and the reading would be directly in the center. The general rule is the widest point on a float is where the reading reference point is. Glass Tube Rotameters are selected for fluids that are glass compatible. High temperature water with a high ph will actually soften glass. For non-glass compatible fluids, Plastic Tube Rotameters are selected and are usually used with high temperatures, high ph, wet steam, caustic soda, and hydrofluoric acid. Metal-Tube Rotameters consist of a metal tapered tube and a rod-guided float. A rod is attached to the float passes through top and bottom guides in the tube. A magnet in the float is coupled to a matching magnetic and indicator located outside the tube. Flow Module Page 38

KEO 4.19. DESCRIBE how MODIFIED ROTAMETERS are used as PURGE OR BYPASS METERS. MODIFIED ROTAMETERS combine a standard rotameter with another device or the rotameter itself is modified to achieve a specific function. Two common modified rotameters are the Purge Meter and the Bypass Meter as depicted below: Figure 5-18 page 185 A Purge Meter is a small metal or plastic rotameter with an adjustable valve at the inlet or outlet of the meter to control the flow rate of the purge fluid. A Purge Meter is used for purging applications such as regulating a small flow of nitrogen or air into an enclosure to prevent the buildup of hazardous or noxious gases. Purge Meters are often used in a bubbler level measuring system. A small bead or ball moves in the fluid stream to indicate the flow rate which is accomplished by adjusting a small needle valve. Purge Meters also keep hazardous fumes and fluids from entering the impulse lines or transmitting devices. Flow Module Page 39

A Bypass Meter is a combination of a rotameter with an orifice plate used to measure flow rates through large pipes. How this works is the differential pressure across the main pipe line is matched to the differential pressure across the rotameter at the maximum flow rate. The rotameter manufacture must provide a metering orifice plate at the inlet to the rotameter to accomplish this matching of differential pressures. KEO 4.20. DESCRIBE how METERING-CONE and SHAPTE-FLOAT & ORIFICE VARIABLE-AREA METERS measure flow. Other Variable-Area Meters use principles similar to those used in rotameters to measure flow rate. Different from Rotameters, they consist of a straight tube meter body with other types of movable parts. Two Common Other Variable-Area Meters are the Metering-Cone Meter, and the Shaped-Float and Orifice Meter. The Metering Cone Meter is depicted below: Figure 5-19 page 186 The Metering-Cone Meter is a flowmeter consisting of a straight tube and a tapered cone, instead of a tapered tube, with an indicator that moves up and down the cone with changes in flow. The variable area is the annular space between the flat and the tapered cone. The indicator is often spring-loaded to allow the meter to be mounted at any angle. The indicator is often spring loaded to allow the meter to be mounted at any angle. Flow Module Page 40

A Shaped-Float and Orifice Meter is a flowmeter consisting of an orifice as part of the float assembly that acts as a guide. Instead of a tapered tube, the float has a shaped profile that provides more open flowing area as the float rises. The variable area is the annular space between the float and the disk. The picture below depicts the Shaped-Float and Orifice Meter: Figure 5-19 page 186 The Shaped-Float and Orifice Meter can provide external readouts as indicators or transmitters with or without alarms. SUMMARY MODIFIED ROTAMETERS combine a standard rotameter with another device or the rotameter itself is modified to achieve a specific function. Two common modified rotameters are the Purge Meter and the Bypass Meter A Purge Meter is a small metal or plastic rotameter with an adjustable valve at the inlet or outlet of the meter to control the flow rate of the purge fluid. A Purge Meter is used for purging applications such as regulating a small flow of nitrogen or air into an enclosure to prevent the buildup of hazardous or noxious gases. Purge Meters are often used in a bubbler level measuring systems. A Bypass Meter is a combination of a rotameter with an orifice plate used to measure flow rates through large pipes. How this works is the differential pressure across the main pipe line is matched to the differential pressure across the rotameter at the maximum flow rate. Flow Module Page 41

The Metering-Cone Meter is a flowmeter consisting of a straight tube and a tapered cone, instead of a tapered tube, with an indicator that moves up and down the cone with changes in flow. The indicator is often spring loaded to allow the meter to be mounted at any angle. A Shaped-Float and Orifice Meter is a flowmeter consisting of an orifice as part of the float assembly that acts as a guide. Instead of a tapered tube, the float has a shaped profile that provides more open flowing area as the float rises. The Shaped-Float and Orifice Meter can provide external readouts as indicators or transmitters with or without alarms KEO 4.21. EXPLAIN operating principles associated with VARIABLE-AREA FLOWMETERS. The operating principles of a variable area flowmeters are different from the operating principles of a differential pressure flowmeter. A differential pressure flowmeter maintains a constant flow area and measures the differential pressure. A variable area flowmeter maintains a constant differential pressure and allows the area to change with the flow rate. Rotameters can only provide correct flow rates for compressible gases and vapors when the flowing conditions are the same as the design conditions. When flowing conditions have changed, the pressure and temperature correction factors described for orifices are also valid for rotameters. KEO 4.22. DESCRIBE how MECHANICAL FLOWMETERS measure flow to include the following Positive-Displacement Flometers: Nutating Disc, Rotating- Impeller, and Sliding Vane. A MECHANICAL FLOWMETER is a flowmeter that uses the force of the flowing fluid, usually liquid, to drive the meter. Positive Displacement Flowmeters include: Nutating Disc, Rotating-Impeller, and Sliding Vane. Positive Displacement Flowmeters separate the flowing stream into equal-volume segments which are then mechanically counted. The velocity of the flowing material drives the propeller, turbine or paddle wheel and the rotational speed can be measured mechanically or electronically. A Positive Displacement Flowmeter is a mechanical flowmeter that admits fluid into a chamber of known volume and then discharges it. The number of times the chamber is filled during a given interval is counted. These types of meters are commonly used for measuring total flow in homes and factories. The chambers are arranged so that as one if filling, the other is being Flow Module Page 42

emptied. This action is registered by a counting mechanism. The Total Flow is then determined by reading the counters. The following picture illustrates how fluid flows through typical types of Positive Displacement Flowmeters: Figure 5-20 page 189 Flow Module Page 43

A Nutating Disc Meter is a positive displacement flowmeter for liquids where the liquid flows through the chambers, causing a disk to rotate and wobble (nutate). This wobble momentarily forms a filled chamber. The rotation of the disc moves the chamber through the meter body. As the chamber is releasing liquid, another chamber is being formed. A counter indicates the number the chamber has released its volume of fluid. The rotation motion resembles that of a spinning coin just before it stops. This type of meter us usually used as a domestic water meter. A Rotating Impeller Meter is a positive displacement flowmeter for liquids where the liquid flows into the chambers defined by the shape of the impellers. The impellers rotate, allowing fluid to flow into the chambers. The fluid measurement chambers are created in the space between the lobes and the housing. A counter indicates the number of times the fluid fills and discharges the chambers. A Sliding Vane Meter is a positive displacement flowmeter for liquids where the fluid fills a chamber formed by sliding vanes mounted on a common hub rotated by the fluid. As the first chamber fills, the hub rotates on a fixed cam, moving the chambers around the meter. One revolution of the hub is equal to four times the chamber volume. A counter mechanism registers each revolution. NOTE All Positive Displacement Flowmeters have chambers that alternately fill and empty. KEO 4.23. DESCRIBE how TURBINE METERS and PADDLE WHEEL METERS measure flow. A Turbine Meter is another example of a mechanical flowmeter. It consists of turbine blades mounted on a wheel that measures the velocity of a liquid stream by counting pulses produced by the blades as they pass an electromagnetic pickup. Flow Module Page 44

The Turbine Wheel is suspended between bearings in a tubular body. The electromagnetic pickup is threaded into the tube wall perpendicular to the wheel as illustrated below: Figure 5-21 page 191 Flow straighteners are added before and after a turbine wheel to ensure that the velocity of steam is the sole cause of its rotation. Turbine Meters are widely used in blending applications. A Paddle Wheel Meter is another example of a mechanical flowmeter. It consists of a number of paddles mounted on a shaft fastened in a housing, which can be inserted into a straight section of piping. The housing is inserted so that only half of the paddles are exposed to the liquid velocity. The following picture illustrates the Paddle Wheel Meter functionality below: Figure 5-21 page 191 Flow Module Page 45

The paddles rotate in proportion to the liquid velocity like an old fashioned water wheel. This rotation can then be detected by two methods. In one method, magnets are imbedded in the tips of plastic paddles and are sensed by an electromagnetic coil housing. In the other method, has a coil mounted in the housing that creates a magnetic field. The passage of the metal tips disrupts the magnetic field. In both methods, the frequency generated by moving paddles is linearly related to the liquid flow rate. Paddle Wheel Meters are only used for measuring liquid flows and then only for the less critical applications. SUMMARY A differential pressure flowmeter maintains a constant flow area and measures the differential pressure. A variable area flowmeter maintains a constant differential pressure and allows the area to change with the flow rate. A MECHANICAL FLOWMETER is a flowmeter that uses the force of the flowing fluid, usually liquid, to drive the meter. Positive Displacement Flowmeters separate the flowing stream into equal-volume segments which are then mechanically counted. A Positive Displacement Flowmeter is a mechanical flowmeter that admits fluid into a chamber of known volume and then discharges it. The number of times the chamber is filled during a given interval is counted. A Nutating Disc Meter is a positive displacement flowmeter for liquids where the liquid flows through the chambers, causing a disk to rotate and wobble (nutate). This wobble momentarily forms a filled chamber. A Rotating Impeller Meter is a positive displacement flowmeter for liquids where the liquid flows into the chambers defined by the shape of the impellers. The impellers rotate, allowing fluid to flow into the chambers. A Sliding Vane Meter is a positive displacement flowmeter for liquids where the fluid fills a chamber formed by sliding vanes mounted on a common hub rotated by the fluid. As the first chamber fills, the hub rotates on a fixed cam, moving the chambers around the meter. One revolution of the hub is equal to four times the chamber volume. All Positive Displacement Flowmeters have chambers that alternately fill and empty. A Turbine Meter is another example of a mechanical flowmeter. It consists of turbine blades mounted on a wheel that measures the velocity of a liquid stream by counting pulses produced by the blades as they pass an electromagnetic pickup. A Paddle Wheel Meter is another example of a mechanical flowmeter. It consists of a number of paddles mounted on a shaft fastened in a housing. The paddles rotate in proportion to the liquid velocity like an old fashioned water wheel. Flow Module Page 46

KEO 4.24. DESCRIBE how MAGNETIC METERS measure flow. Electrical Flowmeters are Magnetic Meters, Voretx Shedding Meters, and Ultrasonic Flowmeters. Magnetic Flowmeters are based on the electrical principle of voltage generation by a conductor moving through a magnetic fluid. Magnetic Meters is commonly called a MAGMETER and is an electromagnetic flowmeter consisting of a stainless steel tube lined with a non-conductive material, with two coils mounted on the tube like a saddle. Two Electrodes in contact with the electrically conductive fluid but insulated from the metal tubes are located opposite one another and at right angles to the flow and magnetic field as depicted below: Figure 5-22 page 192 As the conductive fluid passes through the magnetic field created by the coils, a voltage is induced into and detected by the electrodes. When the magnetic field strength, the position of the electrodes, and the liquid s conductivity remain constant, the generated voltage is linearly related to the velocity of the liquid stream. Flow Module Page 47

Magnetic Flowmeters (Magmeter) has no moving parts and now flow restricting components, and they are not adversely affected by complicated piping configurations. They are used in many water supply and waste water facilities and are somewhat immune to internal buildups. KEO 4.25. DESCRIBE how MAGNETIC VORTEX SHEDDING METERS measure flow. A Vortex Shedding Meter is an electrical flowmeter consisting of a pipe section with symmetrical vertical bluff body (a partial dam) across the flowing stream. A Vortex Shedding Meter uses the formation of vortices as its principle of operation. A Vortex is a fluid moving in a whirlpool or whirlwind motion. A Vortex Shedding Meter is depicted below: Figure 5-23 page 192 A common way to describe how a Vortex Shedding Meter works is to look at a flag blowing in the wind. The flag ripples faster when the wind is blowing because of the increase in vortices formed along the flag. A common Bluff Body shape is a triangular block with the broad surface facing upstream. As the fluid in impeded by the bluff body, a vortex forms on one side of the body. It increases in size until it becomes too large to remain attached to the bluff body and breaks away. Flow Module Page 48

The information of a vortex on one side of the bluff body alters the flowing stream so that another vortex is created on the other side of the bluff body and acts similarly. The alternating vortices are formed and travel downstream at a frequency that is linearly proportional to the speed of the flowing fluid and is inversely linearly proportional to the width of the body. The frequency of release of the vortices can be measured using Temperature, Pressure, Ultrasonic, Crystal, or Stain Gauge sensor. The Vortex Shedding Meter has been used successfully to measure the flow of a wide variety of fluids such as Steam, Hot Oil, and Liquefied gases such as Chlorine. KEO 4.26. DESCRIBE how ULTRASONIC FLOWMETERS measure flow. Ultrasonic Flowmeters are electronic flowmeters that uses the principle of sound transmission in liquids to measure flow. They use either the change in frequency or a sound reflected from moving elements or measure the change in the speed of sound in a moving liquid. One major advantage of Ultrasonic Flowmeters is that nothing protrudes into the flowing liquid. There are two types of Ultrasonic Flowmeters commonly used in industry. They are Doppler Ultrasonic Meters and Transit Time Ultrasonic Meters. A Doppler Ultrasonic Flowmeter is an electronic flowmeter that transmits an ultrasonic pulse diagonally across the flow stream, which reflects off turbulence, bubbles, or suspended particles and is detected by a receiving crystal. The frequency of the reflected pulses, when compared to the transmitted pulses, results in a Doppler Frequency shift that is proportional to the velocity of the flowing stream. This is the same principle as radar used to measure the speed of vehicles on the highway, but with different frequencies. Knowing the pipe size and velocity is sufficient to determine the volumetric flow rate. The success of this meter is dependent on the presence of particles or bubbles in the flowing liquid. Clear liquids or liquids with high solids entrapped cannot be measured with a Doppler Meter. Flow Module Page 49

A Doppler Ultrasonic Meter is depicted below: Figure 5-24 page 193 A Transit Time Ultrasonic Flowmeter is an electronic meter consisting of two sets of transmitting and receiving crystals, one set aimed diagonally upstream and the other aimed diagonally downstream. The liquid velocity slows the upstream signal and increases the received frequency while speeding up the downstream signal and decreasing the received frequency. The difference in the measured frequencies is used to calculate the transit time of the ultrasonic beams and thus the liquid velocity. A Transit Time Ultrasonic Flowmeter is depicted below: Figure 5-24 page 193 Flow Module Page 50

The flowmeter circuitry is able to convert this information to a flow rate by multiplying the velocity by the pipe area. This measurement method has been applied successfully to very large pipes carrying clean, noncorrosive, bubble free liquids. SUMMARY Magnetic Flowmeters are based on the electrical principle of voltage generation by a conductor moving through a magnetic fluid. Magnetic Meters is commonly called a MAGMETER and is an electromagnetic flowmeter consisting of a stainless steel tube lined with a non-conductive material, with two coils mounted on the tube like a saddle. Magnetic Flowmeters (Magmeter) has no moving parts and now flow restricting components, and they are not adversely affected by complicated piping configurations. A Vortex Shedding Meter is an electrical flowmeter consisting of a pipe section with symmetrical vertical bluff body (a partial dam) across the flowing stream. A Vortex Shedding Meter uses the formation of vortices as its principle of operation. A Vortex is a fluid moving in a whirlpool or whirlwind motion. Ultrasonic Flowmeters are electronic flowmeters that uses the principle of sound transmission in liquids to measure flow. They use either the change in frequency or a sound reflected from moving elements or measure the change in the speed of sound in a moving liquid. A Doppler Ultrasonic Flowmeter is an electronic flowmeter that transmits an ultrasonic pulse diagonally across the flow stream, which reflects off turbulence, bubbles, or suspended particles and is detected by a receiving crystal. A Transit Time Ultrasonic Flowmeter is an electronic meter consisting of two sets of transmitting and receiving crystals, one set aimed diagonally upstream and the other aimed diagonally downstream. The liquid velocity in the Transit Time Flowmeter slows the upstream signal and increases the received frequency while speeding up the downstream signal and decreasing the received frequency. The difference in the measured frequencies is used to calculate the transit time of the ultrasonic beams and thus the liquid velocity. Flow Module Page 51

KEO 4.27. DESCRIBE how MASS FLOWMETERS measure flow to include a CORIOLIS METER and a THERMAL MASS METER. A MASS FLOWMETER is a flowmeter that measures the actual quality of mass of a flowing fluid. Mass Flow measurement is a better way to determine the quantity of material than volumetric flow measurement. Changes in pressure and temperature can affect density, which then introduces errors into calculations that convert volumetric flow to actual quantity of material. Two common types of mass flowmeters are the Coriolis Meter and the Thermal Mass Meter. A Coriolis Meter is a mass flowmeter consisting of specially formed tubing that is oscillated at a right angle to the flowing mass of fluid. Coriolis Force is the force generated by the inertia of fluid particles as the fluid moves toward or away from the axis of oscillation. The following picture illustrates how Mass Flow through a meter causes a phase shift between the inlet and outlet velocity sensors: Figure 5-25 page 194 Flow Module Page 52

A Coriolis Mass Flowmeter uses the vibrations and twist of a tube to measure flow. Flow is divided and then passes through two tubes of equal length and shape. The tubes are firmly attached to the meter body (a section of pipe). The two tube sections of tubing are made to oscillate at their natural frequency in opposite directions from each other. The fluid accelerates as it is vibrated and causes the tubing to twist back and forth while the tube oscillates. Two detectors, one on the inlet and one on the outlet, consist of a magnet and a coil mounted on each tubing section at the points of maximum motion. Each of these detectors develops a sine wave current due to the opposite oscillations of the two sections of tubing as depicted in the picture above. The sine waves are in phase when there is no flow. When flow is present, the tubes twist in opposite directions, resulting in the sine waves being out of phase. The degree of phase shift varies with the mass flow through the meter. A Coriolis Mass Flowmeter accurately measures the flow of either liquids or gasses and can also measure fluid density. Thermal Mass Meter A Thermal Mass Meter is a mass flowmeter consisting of two RTD (Resistance Temperature Detector) probes and a heating element that measure the heat loss to the fluid mass. Thermal Mass Meters are predominantly used for measuring gas flow. Flow Module Page 53

The two RTD s are immersed in the flow stream. One probe is in an assembly that includes an adjacent heating element that is measured by the RDT. The other probe is spate and it measures the temperature of the flowing fluid as depicted below: Figure 5-26 page 195 The heated probe looses heat to the stream by convection. The electrical circuitry is designed to maintain a constant difference in temperature between the two probes by varying the power to the heating element. The power becomes the measured variable of the system and variations in power are proportional to the variations in mass flow. Its circuitry includes corrections for thermal conductivity, viscosity, and density. Flow Module Page 54

Thermal Mass Meters are less accurate than many other types of flow metering devices, but can be used to measure some low-pressure gases that are not dense enough for a Coriolis Flow Meter. KEO 4.28. DESCRIBE how ACCESSORY FLOW DEVICES function and how they are used. ACCESSORY FLOW DEVICES are instruments that do not actually measure flow, but use flow principles to obtain information. Examples are devices that measure total flow and flow switches that can be configured to trigger an alarm or a switch. An Accessory Flow Integrator is depicted below: Figure 5-27 page 197 An Integrator is a calculating device that totalizes the amount of flow during a specified time period. Integrators are available for use with pulse output as produced by turbine flowmeters or analog outputs (linear or square root) from orifice meters equipped with analog to digital converters. When an Integrator is used for flow calculations, they can be either electronic or pneumatic integrators to convert a differential pressure measurement to a flow rate. Flow Module Page 55

The principle requirements for Integrators are: an accurate measurement of the differential pressure, a conversion to flow rate, a constant time input, and an easy to read counter. KEO 4.29. EXPLAIN how different FLOW SWITCHS function and how they are used to include: DIFFERENTIAL PRESSURE SWITCHES, BLADE SWITCHES, THEREMAL SWITCHES, and ROTAMETER SWITCHES. FLOW SWITCHS are devices used to monitor flowing stream to provide a discrete electrical or pneumatic output action at a predetermined flow rate. Flow rate switches are used to generate alarms or shutdown signals for high or low flows. Flow switch functions are dependent on measurement principles such as an orifice plate or a differential pressure switch as depicted below: Figure 5-28 page 198 Flow Module Page 56

A DIFFERENTIAL PRESSURE SWITCH is a flow switch consisting of a pair of pressure sensing element and an adjustable spring that can be set at a specific value to operate an output switch. The differential pressure switch measures the pressure drop across a primary flow element. A BLADE SWITCH is a flow switch consisting of a thin, flexible blade inserted into a pipeline. The fluid flow develops a force which presses against the blade. The motion of the blade is transferred through a sea and is opposed by an adjustable spring which establishes the trip point. An electrical or pneumatic switch can sense the blade motion. A THERMAL SWITCH is a flow switch consisting of a heated temperature sensor. The flowing fluid carries away heat from the heated temperature sensor. The electronic circuits in the switch can be set to trip at some predetermined flow rate. A ROTAMETER SWITCH is a flow switch that consists of a shaped float, a fixed orifice, and a magnetic sensing switch outside the tube to activate a flow circuit at a predetermined flow rate. SUMMARY A Coriolis Meter is a mass flowmeter consisting of specially formed tubing that is oscillated at a right angle to the flowing mass of fluid. A Coriolis Mass Flowmeter uses the vibrations and twist of a tube to measure flow. A Thermal Mass Meter is a mass flowmeter consisting of two RTD (Resistance Temperature Detector) probes and a heating element that measure the heat loss to the fluid mass. Thermal Mass Meters are predominantly used for measuring gas flow. ACCESSORY FLOW DEVICES are instruments that do not actually measure flow, but use flow principles to obtain information. An Integrator is a calculating device that totalizes the amount of flow during a specified time period. The principle requirements for Integrators are: an accurate measurement of the differential pressure, a conversion to flow rate, a constant time input, and an easy to read counter. FLOW SWITCHS are devices used to monitor flowing stream to provide a discrete electrical or pneumatic output action at a predetermined flow rate. A DIFFERENTIAL PRESSURE SWITCH is a flow switch consisting of a pair of pressure sensing element and an adjustable spring that can be set at a specific value to operate an output switch. A BLADE SWITCH is a flow switch consisting of a thin, flexible blade inserted into a pipeline. Flow Module Page 57

A THERMAL SWITCH is a flow switch consisting of a heated temperature sensor. The flowing fluid carries away heat from the heated temperature sensor. A ROTAMETER SWITCH is a flow switch that consists of a shaped float, a fixed orifice, and a magnetic sensing switch outside the tube to activate a flow circuit at a predetermined flow rate KEO 4.30. EXPLAIN how OPEN-CHANEL WEIRS and PARSHALL FLUME FLOW MEASUREMTNS function and how they are used. OPEN-CHANEL WEIRS use a restriction to create a head of liquid. A WEIR is an OPEN- CHANEL device consisting of a flat plate that has a notch cut into the top edge as depicted below: Figure 5-29 page 199 The rate of flow is determined by measuring the height of liquid in the stilling basin upstream of the Weir. The crest is the bottom of the Weir. A Weir can be notched as a rectangular, trapezoidal, or triangular and has a sharp upstream edge (similar to an orifice plate). The Weir is installed in the outlet of a stilling basin. The flow is related to the height of the water above the bottom of the Weir Notch measured at a point upstream of the Weir where the water has no draw-down. Flow Module Page 58

Weir Height Measurements are made a distance upstream equal to four times the height of the water above the Crest. A PARSHALL FLUME is a special form of an open-channel flow element that requires much less channel elevation than a Weir. A PARSHALL FLUME has a horizontal configuration similar to a Venturi Tube, with converging inlet walls, a parallel throat, and diverging outlet walls as depicted below: Figure 5-29 page 199 The bottom profile is specially designed to generate a hydraulic jump in the throat. Flow can be calculated from a measurement of the elevation of the inlet water at a specific point. PARSHALL FLUMES are much less subject to problems from dirt or other fouling factors than a Weir and have the ability to measure much larger flows. Flow Module Page 59

KEO 4.31. EXPLAIN how a BELT WEIGHING SYSTEM is used to measure a solids flow. A BELT WEIGHING SYSTEM is used to measure the flow of solids like granular (bulk) solids. Measuring solids is a different task because of the basic properties solids consist of. Bulk solids vary greatly in flow properties. Some are sticky and do not flow well, and others are so fine and slippery that they flow like liquids. Bulk Solids are usually transported by a belt, screw, or a drag conveyor. The most successful flow measurement is by the use of a BELT WEIGHING SYSTEM. A BELT WEIGHING SYSTEM is a solids flow meter consisting of a specially constructed belt conveyer and a section that is support by electronic weight cells as depicted below: Figure 5-30 page 200 The conveyer belt is designed to minimize the transfer of the weight of the unmeasured section of the conveyer. Solids are deposited on the conveyer and carried onto the weighing section. Flow Module Page 60