S&C IntelliLink Remote Setup Software Installation Table of Contents Section Page Section Page Introduction Qualified Persons.... 2 Read this Instruction Sheet.... 2 Retain this Instruction Sheet.... 2 Warranty.... 3 Safety Information Understanding Safety-Alert Messages.... 4 Following Safety Instructions... 4 Replacement Instructions and Labels.... 4 License Key for IntelliLink 5 and Below IntelliRupter Software.... 5 Other S&C Automatic Control Software... 6 Installing an IntelliLink 6 Activation File IntelliLink Remote License Activation.... 7 Installing a License Activation File... 8 Using IntelliLink Remote Connecting to an IntelliRupter PulseCloser... 10 Serial Connection to a 6800 Series Control.... 10 Connecting to a DNP Network Entry Point.... 11 Connecting Via DNP Without IntelliRupter Software.... 12 Configuring IntelliLink Remote Setting Screen Refresh Options.... 15 Setting Security Options for Legacy Products.... 16 Security Options Setup.... 17 Remote Operation IntelliRupter Operation.... 18 August 12, 2013 S&C Electric Company Instruction Sheet 1032-500
Introduction With S&C IntelliLink Remote Setup Software, you can access every S&C automation product that communicates using DNP3 Protocol, remotely from a computer connected to your DNP network. You will be able to configure controls, access historical and real-time data, and troubleshoot equipment. Optional password protection can be activated to prevent unauthorized use of IntelliLink Remote software. To activate IntelliLink Remote, you need to purchase a software license from S&C. A temporary license is available at no charge for evaluation. S&C Automation Controls with software revision 3.4.x and lower register IntelliLInk5 Remote operation with a license key. Controls with software revision 3.5.x and higher enable IntelliLink6 Remote operation by registering the MAC Address of the computer IntelliLink Remote is installed on. Contact your local S&C Sales Office for more information. IntelliLink Remote communicates with the following S&C products operating under DNP3 Protocol: S&C IntelliRupter PulseClosers S&C 5800 Series and 6800 Series Automatic Switch Controls S&C IntelliNode Interface Modules and Universal Interface Modules M Series Switch Operators S&C Model 4801 Remote Switch Controls BankGuard Plus Controls IntelliCap Plus and IntelliCap 2000 Automatic Capacitor Controls Superseded EnergyLine 1000 Series Capacitor Controls Superseded EnergyLine 2851 and 2852 Automatic Switch Controls. Qualified Persons Ç WARNING The equipment covered by this publication must be installed, operated, and maintained by qualified persons who are knowledgeable in the installation, operation, and maintenance of overhead electric power distribution equipment along with the associated hazards. A qualified person is one who is trained and competent in: The skills and techniques necessary to distinguish exposed live parts from non-live parts of electrical equipment. The skills and techniques necessary to determine the proper approach distances corresponding to the voltages to which the qualified person will be exposed. The proper use of the special precautionary techniques, per sonal protective equipment, insulating and shielding materials, and insulated tools for working on or near exposed energized parts of electrical equipment. These instructions are intended only for such qualified persons. They are not intended to be a substitute for adequate training and experience in safety procedures for this type of equipment. Read this Instruction Sheet Retain this Instruction Sheet Read this instruction sheet thoroughly and carefully before installing or operating your S&C IntelliLink Remote Setup Software. Familiarize yourself with SAFETY INFORMATION on page 4. The latest version of this publication is available online in PDF format at sandc.com/support/product-literature.asp This instruction sheet is a permanent part of your S&C automation product installation. Designate a location where you can easily retrieve and refer to this publication. 2 S&C Instruction Sheet 1032-500
Introduction Warranty SPECIAL WARRANTY PROVISIONS: The standard warranty contained in S&C s standard conditions of sale, as set forth in Price Sheet 150, applies to S&C IntelliLink Remote Setup Software. The first paragraph of said warranty is replaced by the following: (1) General: Seller warrants to immediate purchaser or end user for a period of 10 years from the date of shipment that the equipment delivered will be of the kind and quality specified in the contract description and will be free of defects of workmanship and material. Should any failure to conform to this warranty appear under proper and normal use within ten years after the date of shipment the seller agrees, upon prompt notification thereof and confirmation that the equipment has been stored, installed, operated, and maintained in accordance with recommendations of the seller and standard industry practice, to correct the nonconformity either by repairing any damaged or defective parts of the equipment or (at seller s option) by shipment of necessary replacement parts. The seller s warranty does not apply to any equipment that has been disassembled, repaired, or altered by anyone other than the seller. This limited warranty is granted only to the immediate purchaser or, if the equipment is purchased by a third party for installation in third-party equipment, the end user of the equipment. The seller s duty to perform under any warranty may be delayed, at the seller s sole option, until the seller has been paid in full for all goods purchased by the immediate purchaser. No such delay shall extend the warranty period. Seller further warrants to the immediate purchaser or end user that for a period of two years from the date of shipment the Software will perform substantially in accordance with the then-current release of specifications if properly used in accordance with the procedures described in seller s instructions. Seller s liability regarding any of the Software is expressly limited to exercising its reasonable efforts in supplying or replacing any media found to be physically defective or in correcting defects in the Software during the warranty period. Seller does not warrant the use of the Software will be uninterrupted or error-free WARRANTY QUALIFICATIONS: Warranty of S&C IntelliLink Remote Setup Software is contingent upon the installation, configuration, and use of the control or software in accordance with S&C s applicable instruction sheets. This warranty does not apply to major components not of S&C manufacture, such as batteries, communication devices, and remote terminal units. However, S&C will assign to immediate purchaser or end user all manufacturers warranties that apply to such major components. END USER LICENSE AGREEMENT: End user is granted a nontransferable, non-sublicensable, nonexclusive license to use the LinkStart Connection Management Software, IntelliLink Remote Setup Software, IntelliTeam Automatic Restoration Software, and/or other Software furnished with IntelliTeam SG Automatic Restoration System only upon acceptance of all the terms and conditions of the seller s end user license agreement set forth in Price Sheet 155. S&C Instruction Sheet 1032-500 3
Safety Information Understanding Safety-Alert Messages There are several types of safety-alert messages which may appear throughout this instruction sheet as well as on labels and tags attached to the S&C IntelliLink Remote Setup Software. Familiarize yourself with these types of messages and the importance of the various signal words, as explained below. Ç DANGER DANGER identifies the most serious and immediate hazards which will likely result in serious personal injury or death if in structions, including recommended precautions, are not followed. Ç WARNING WARNING identifies hazards or unsafe practices which can re sult in serious personal injury or death if instructions, including recommended precautions, are not followed. Ç CAUTION CAUTION identifies hazards or unsafe practices which can result in minor personal injury or product or property damage if instruc tions, including recommended precautions, are not followed. NOTICE NOTICE identifies important procedures or requirements that, if not followed, can result in product or property damage if instruc tions are not followed. Following Safety Instructions If you do not understand any portion of this instruction sheet and need assistance, contact your nearest S&C Sales Office or S&C Autho rized Distributor, or call S&C Headquarters at (773) 338-1000, Monday through Friday between 8:30 AM and 5:00 PM Central Standard Time. (In Canada, call S&C Electric Canada Ltd. at (416) 249-9171, Monday through Friday between 8:00 AM and 5:00 PM Eastern Standard Time.) NOTICE Read this instruction sheet thoroughly and carefully before installing and op erating your S&C IntelliLink Remote Setup Software. Replacement Instructions and Labels If you need additional copies of this instruction sheet, contact your nearest S&C Sales Office, S&C Authorized Distributor, S&C Head quarters, or S&C Electric Canada Ltd. It is important that any missing, damaged, or faded labels on the equipment be replaced immediately. Replacement labels are available by contacting your nearest S&C Sales Office, S&C Authorized Distrib utor, S&C Headquarters, or S&C Electric Canada Ltd. 4 S&C Instruction Sheet 1032-500
License Key for IntelliLink 5 and Below IntelliRupter Software The IntelliRupter software installer, for sortware revision 3.4.x and lower, also installs the correct version of IntelliLink Setup Software for IntelliRupters. IntelliLink Remote functionality is built into all IntelliLink Software, but is not available until activated with a license key. Follow these steps to enter the license key and activate IntelliLink Remote functionality. If you also operate other S&C controls, use the instructions on page 6 to enable IntelliLink Remote for them. Step 1 Obtain a license key from S&C Electric Company. Contact your local S&C Sales Office. Step 2 Open Windows Explorer, and go to the C:\Program Files\S&C Electric\IntelliLink. Look for the program OptionSetup.exe. Step 2 To enable IntelliLink Remote functionality, run OptionSetup.exe. Open the Options Setup program by double-clicking it. If you are using Windows 7 right-click OptionsSetup. exe and open as administrator. (If you double-click, it will not activate the license key and will return an error.) When the Option Setup dialog box appears, enter the license key supplied by S&C (the entry is case-sensitive), and click the Activate button. See Figure 1. Figure 1. Option Setup dialog box for entering your software license key. When you start IntelliLink by selecting the Start Button > Programs > S&C Electric > IntelliLink, see Figure 2 if IntelliLink Remote has been activated, the dialog box that opens will give you the choice to select Remote Connection. See Figure 3. Figure 2. Selection path to IntelliLink from the desktop Start button. Figure 3. The Remote Connection button starts an IntelliLink Remote session, and is available when IntelliLink Setup Software starts, after IntelliLink Remote has been enabled. Remote Connection starts the IntelliLink Remote session. S&C Instruction Sheet 1032-500 5
License Key for IntelliLink 5 and Below Other S&C Automatic Control Software S&C software installers also install the correct version of IntelliLink Setup Software. IntelliLink Remote functionality is built into all IntelliLink Software, but is not available until activated with a license key. Follow these steps to enter the license key and activate IntelliLink Remote functionality. If you also operate IntelliRupters, use the instructions on page 5 to enable IntelliLink Remote for them. Step 1 Obtain a license key from S&C Electric Company. Contact your local S&C Sales Office. Step 2 Open Windows Explorer, and go to the C:\ELine folder, or the folder where you have installed your S&C software. Look for the program OptionSetup.exe. If it is listed, proceed to Step 4 to enter your IntelliLink Remote license key. Step 3 If OptionSetup.exe is not listed, you will need to upgrade your version of IntelliLink. To upgrade, go to the S&C Automation Customer Support Portal d, open the IntelliLink Update Utility folder, located in the IntelliLink Software workspace. Download the program ILUpdatennn.exe to your computer. Run this program and install the software in the folder on your hard drive where you have installed IntelliLink (c:\eline is the default). The ILUpdatennn.exe program will update IntelliLink to the most recent revision, and place the program OptionSetup.exe on your hard drive. NOTICE With some of the very old S&C product software installed on your computer IntelliLink may not start after having been updated with ILUpdate326.exe. Contact S&C Electric Company at (773) 338-1000 to resolve this problem. Step 4 To enable IntelliLink Remote functionality, run the OptionSetup.exe utility in your C:\ ELine folder (or the folder where you have installed IntelliLink). Open the Options Setup program by double-clicking it. If you are using Windows 7 right-click OptionsSetup. exe and open as administrator. (If you double-click, it will not activate the license key and will return an error.) When the Option Setup dialog box appears, enter the license key supplied by S&C (the entry is case-sensitive), and click the Activate button. See Figure 4. Figure 4. Option Setup dialog box for entering your software license key. NOTICE If a license key was activated for products other than IntelliRupter and IntelliNode, installing IntelliRupter or IntelliNode software will require re-activation of the IntelliLink Remote license key. 6 S&C Instruction Sheet 1032-500 d The S&C Automation Customer Support Portal is a password-protected on-line library of software and documentation for S&C Automation Products, and is accessible from the S&C website: www.sandc.com at the Support tab. To obtain your User ID and password for the Portal, submit the on-line password request form.
Installing an IntelliLink 6 Activation File IntelliLink Remote License Activation NOTICE If you have been using IntelliLink Remote, you need to obtain a License Activation File to enable IntelliLink Remote for IntelliRupter, IntelliNode, or 6800 Series Software versions 3.5.x and higher. If you are using IntelliLink Remote with IntelliCap Plus, or any other products with older Software versions in conjunction with products using software versions 3.5.x and higher, you need to use both the IntelliLink Remote License Key and an Activation File. You need an account on the S&C Automation Customer Support Portal to obtain a License Activation File. If you do not have an account, use this link to request a password: sandc.com/support/automation-customer-support-portal.asp. The first step is to register the computers that will use IntelliLink Remote. You register a computer with its MAC address for the Local Area Ethernet adapter. The MAC address can be obtained by entering the command ipconfig/all in the command prompt. Make sure you get the MAC Address for the onboard physical adapter and not the addon or wireless adapter. If you are unfamiliar with the command prompt, you can download the S&C CheckMacAddress utility, from the IntelliTeam SG Software workspace on the S&C Automation Customer Support Portal. See Figure 5. When you have the MAC address, send an e-mail to customersupport@sandc.com with the name of the company that owns the IntelliLink Remote License, the name of the primary computer user, and the computer user s e-mail address and phone number. To see if your computer has already been registered, select the Licensing tab to view a list of computers registered to your account. Look for the designation INTELLILINK REMOTE next to the computer s MAC address. Figure 5. IntelliTeam SG Software workspace on the S&C Automation Customer Support Portal. The next step is to download and save your License Activation file: ActivationFile.xml, as directed in the Installing a License Activation File section below. You will receive an e-mail notification that your Activation File is ready, then you login to your S&C Automation Customer Support Portal account and follow the steps on page 8. After you have installed your IntelliRupter, 6800, or IntelliNode software version 3.5.x or above, and saved your License Activation file, you can then use IntelliLink Remote with those products. S&C Instruction Sheet 1032-500 7
Installing an IntelliLink 6 Activation File Installing a License Activation File Go to sandc.com, click the Support tab, and then click S&C Automation Customer Support Portal in the left column. Enter your User Name and Password to gain access. Select the Licensing tab and verify that you have a valid license association, and the correct MAC Address for your computer. Select the Activation File tab. This generates a new License Activation File with the current information displayed at the Licensing tab. Then a File Download dialog box will open. Click the Save button and a Save As dialog box will open, save ActivationFile.xml on your desktop. Copy ActivationFile.xml, and paste it in the folder(s) as shown below. Username is your name as registered for your computer. Note that AppData is a hidden system file and will need to be exposed for this step. In Windows File Explorer select Tools>Folder options to access the Folder Options dialog. See Figure 6. On the View tab select Show hidden files, folders, and drives to expose the AppData folder. See Figure 7. Figure 6. Windows File Explore Tools > Folder options. Figure 7. Windows Folder Options dialog box. 8 S&C Instruction Sheet 1032-500
Installing an IntelliLink 6 Activation File For Windows 7 and Windows 2008 save ActivationFile.xml at: (for 32 bit) C:\Program Files\S&C Electric\IntelliLink6 and C:\Program Files\S&C Electric\IntelliTeam Designer (for 64 bit) C:\Program Files (x86)\s&c Electric\IntelliLink6 and C:\Program Files (x86)\s&c Electric\IntelliTeam Designer or if you do not have Administrative Privilege, save it at: C:\Users\username\AppData\Local\S&C Electric For Windows XP save ActivationFile.xml at: (for 32 bit) C:\Program Files\S&C Electric\IntelliLink6 and C:\Program Files\S&C Electric\IntelliTeam Designer (for 64 bit) C:\Program Files (x86)\s&c Electric\IntelliLink6 and C:\Program Files (x86)\s&c Electric\IntelliTeam Designer or if you do not have Administrative Privilege, save it at: C:\Documents and Settings\username\Local Settings\Application Data\S&C Electric S&C Instruction Sheet 1032-500 9
Using IntelliLink Remote Connecting to an IntelliRupter PulseCloser When you connect to an IntelliRupter with the WiFi link, the IntelliRupter does not function as a DNP network entry point. You can configure that IntelliRupter, but you cannot use IntelliLink Remote to connect to other IntelliRupters or S&C controls. With an all IntelliRupter system, your computer will be connected to a gateway or headend radio for IntelliLink Remote access to the DNP network. See Figure 8. Then you can connect to a specific IntelliRupter, or other S&C control, by entering its DNP address. IntelliRupter PulseCloser & SpeedNet Radio S&C M Series & SpeedNet Radio IntelliCap 2000 & SpeedNet Radio S&C 6800 Series & SpeedNet Radio SpeedNet/DNP Computer DNP over UDP/IP, TCP/IP, or Serial DNP Entry Point DNP SpeedNet Headend Radio or direct DNP connection Figure 8. Connected to a DNP entry point or to the headend radio. Serial Connection to a 6800 Series Control S&C IntelliLink Remote can be used with a variety of S&C controls. Figure 9 on page 11 shows a computer connected to the SCADA Communication Port of a 6800 Series Automatic Switch Control. An S&C Serial to SCADA Port cable is required, Catalog Number 07-001355-01. The serial link to the SCADA Port can also be sent over a fiber-optic transceiver, point-to-point radio, or modem. Your computer must have a DNP address that is registered with the S&C controls it will contact through IntelliLink Remote. The 6800 Series Automatic Switch Control is the DNP router, sending messages through its other SCADA port to its DNP radio, which communicates to the other S&C controls. With this setup, you can configure and troubleshoot all your DNP controls, by connecting to one control. You do not affect this control s participation in IntelliTeam and its team does not go Out-of-READY. 10 S&C Instruction Sheet 1032-500
Using IntelliLink Remote IntelliRupter PulseCloser & SpeedNet Radio S&C 6800 Series & SpeedNet Radio S&C 6800 Series & SpeedNet Radio IntelliCap 2000 & SpeedNet Radio SpeedNet/DNP Serial/DNP S&C 6800 Series & SpeedNet Radio Computer Figure 9. Connected to the SCADA communication port of a 6800 Series Automatic Switch Control. NOTICE If you connect your computer to a radio in a switch control or the headend radio and disconnect the control or SCADA system, the team or SCADA system normally connected to that radio will not be able to perform its normal function. The team will go Out-of- READY, or the SCADA system will not be able to communicate. S&C recommends that you connect your computer to a separate dedicated radio. With UtiliNet radios, the DNP address of this radio must be listed in the Frame Recognition DCW of each radio you will communicate with. For S&C SpeedNet radios the DNP and IP address of the dedicated radio must be listed in the routing table. Connecting to a DNP Network Entry Point Figure 8 on page 10 shows a computer connected via Ethernet UDP/IP, Ethernet TCP/ IP, or a Serial connection through a DNP network entry point to the headend radio. The DNP network entry point can be a Device Terminal Server, a DNP Proxy Server, or the computer can also be directly connected to a dedicated radio. You can configure and troubleshoot an entire network through a DNP radio. When a DNP master station is also accessing information from the S&C control equipment, the communication link must be capable of properly routing both DNP message streams. Please contact your local S&C Sales Office for information about applications that involve more complex communication systems. S&C Instruction Sheet 1032-500 11
Using IntelliLink Remote Connecting Via DNP Without IntelliRupter Software IntelliLink Remote allows you to connect locally to a device that uses DNP3 Protocol, and remotely access another control by calling its DNP address. You can then change set points, monitor real-time data, view event logs, and generate reports as if you were connected directly to the faceplate of that control. Step 1 Connect your computer to the device that is your entry point to the DNP network. S&C Automation Device Use the SCADA Port (Port A) on the control. You will need a DB9 to 6-pin IDC cable, S&C Catalog Number 007-001355-01. Headend DNP Radio Use the appropriate cable. Remote Terminal Server Configure your computer to communicate with the server. Step 2 Start IntelliLink, if it is not already running. IntelliLink will attempt to connect using the communication parameters that it saved the last time it connected. If you want to change to a different DNP address, select Cancel, and change parameters. Figure 10. Communication dialog box for IntelliLink 5 and below. If you have a Universal Interface Module installed, this dialog box will look different. Step 3 From IntelliLink, select Tools > Options. See Figure 10 for IntelliLink 5 and below, or Figure 11 on page 13 for IntelliLink 6. Step 4 In the Communications tab of the Options dialog box, select DNP as the Protocol. Step 5 Set the Connection type. If you are connecting directly to a 6800 Series Control or to a DNP radio, select Serial. If you are connecting to a server, select TCP/IP or UDP/IP, depending on your network configuration. 12 S&C Instruction Sheet 1032-500
Using IntelliLink Remote Figure 11. Communication dialog box for IntelliLink 6 and higher. Step 6a If you selected Serial in Step 5, enter the following: Port This is the port on your computer to which the DNP communication cable is connected. Baud Rate This is the baud rate between the switch control and the directly connected communication device (radio, modem, etc.). Step6b If you selected TCP/IP or UDP/IP in Step 5, enter the following: Peer IP or DNS Name Enter the IP or DNS name of the server. Peer Port Enter the server s TCP or UDP port number. Our Port Enter your computer s UDP port number. Step 7 Use Default Timeout Check this box to use the default timeout value. Unless you are connecting directly to a control (TTY for software versions below 3.5.x), it is recommended that you set the timeout value manually (see below). Timeout The timeout duration (in milliseconds) for communications. Retries The number of times that the switch control tries to connect with the remote device, or send a request when there is no response. Our Address The DNP address associated with the local computer (that is, the master station address). Set this unique value according to the routing configuration in your DNP network. S&C Instruction Sheet 1032-500 13
Using IntelliLink Remote Step 8 Set the Destination Address This is the DNP/RTU address for the control with which you want to communicate. (To communicate with a control you are locally connected to, andyou do not know its DNP/RTU address, set the Destination Address value to SELF.) The Destination Address field is actually a drop-down menu which automatically stores the last several DNP addresses that have been visited. Step 9 Click Connect. Once connected, you can view IntelliLink screens as if connected directly to the remote switch control. NOTICE IntelliLink Remote Setup Software will communicate with all versions of DNP control software installed in these S&C Automation Products: IntelliCap Plus and IntelliCap 2000 Automatic Capacitor Controls. IntelliRupter PulseClosers BankGuard Plus Controls. M Series Switch Operators. IntelliLink Remote Setup Software will communicate with the following and later versions of DNP control software installed in these S&C Automation Products: S&C 5800 Series Automatic Switch Control Software Revision 2.16. EnergyLine 2851 and 2852 Automatic Switch Control Software Revision 2.16. S&C Model 4801 Remote Switch Control Software Revision 2.23. EnergyLine 1000 Series Capacitor Control Software Revisions C35Dxxxx, K41Dxxxx, N47Dxxxx, and V47Dxxxx. If IntelliLink Remote Setup Software does not communicate with your controls, please contact S&C Electric Company at (773) 338-1000 for further information and assistance. Step 10 Repeat Steps 7 through 9 for each switch control whose status you wish to review. 14 S&C Instruction Sheet 1032-500
Configuring IntelliLink Remote Setting Screen Refresh Options NOTICE The default refresh rate of 1000 ms is intended for use with local connections where the channel bandwidth is dedicated to the connection. When connecting over a newtwork it is recommended that the manual refresh be used or the refresh rate extended to avoid putting excessive strain on the network. IntelliLink Remote offers several options for refreshing data: From IntelliLink, select Tools > Options. Click the Screen Refresh tab of the Options dialog box. See Figure 12 and Figure 13 on page 16. The parameters on these screens include: Fill On Open When checked or Yes, all the data on a screen is requested whenever a new screen is called up. Refresh Mode On Start Up ( Refresh Mode for software 3.5.x and higher) By selecting Once, the data on a screen is requested only when a new screen is called up. By selecting Auto, the screen is updated after the interval specified in Delay between consecutive screen refreshes. You can also toggle between Once and Auto by using the buttons at the bottom of the IntelliLink Remote data screen. Delay between consecutive screen refreshes If Refresh Mode is set to Auto, the data is gathered at this interval. Show Refresh Progress (software versions below 3.5.x) When checked, the status bar at the bottom right of the IntelliLink Remote data screen shows the progress of the Refresh operation. If the Refresh Mode is not set to Auto, you may refresh the screen manually by clicking the Once button at the bottom of the IntelliLink Remote data screen. You can also refresh just one specific parameter by right-clicking the parameter and selecting Refresh Item. Figure 12. Refresh screen for software versions below 3.5.x. S&C Instruction Sheet 1032-500 15
Configuring IntelliLink Remote Figure 13. Refresh screen for software version 3.5.x and higher. Setting Security Options for Legacy Products The IntelliLink Access Passwords feature, which only prevents unauthorized access to IntelliLink Software, does not function in the IntelliLink Software used for IntelliRupters. Access to an IntelliRupter is protected by the IntelliRupter s security system, and you will not be asked for a password when you launch IntelliLink. You must then enter a User Name and Password when you attempt to communicate with the IntelliRupter. For other S&C Controls, IntelliLink has three Access Password levels. From IntelliLink, select Tools > Security. The dialog box Set Access Passwords will be displayed. See Figure 14 on page 17. The parameters on this screen include: Master Password Setting a master password enables password security. Once the master password has been set, you will not be able to start IntelliLink Setup Software again without using the master password or one of the other configured passwords. The master password is required to enable, disable, or change other passwords, and to disable the master password itself which will remove password protection. NOTICE Be sure to record your master password. Without it you will not be able to change passwords or remove password protection. Read/Write Password A user who logs in with this password can view screens and change set points but not change passwords. This password cannot be set until you have set the master password. Read-Only Password A user who logs in with this password can view screens but cannot change set points. This password cannot be set until you have set the master password. 16 S&C Instruction Sheet 1032-500
Configuring IntelliLink Remote Figure 14. Passwords screen. Security Options Setup Security setting for IntelliRupter and 6800 Automatic Switch controls are set on the Setup>Security screen. See the Security section of S&C Instruction Bulletin 766-530 for IntelliRupter, and 1045-530 for 6800 Automatic Switch controls. S&C Instruction Sheet 1032-500 17
Remote Operation IntelliLink Remote can remotely operate IntelliCap Plus and IntelliCap 2000 Automatic Capacitor Controls. Other S&C Automatic Controls cannot be operated by IntelliLink Remote, but can be operated over a SCADA system by device specific DNP commands. IntelliCap 2000 Automatic Capacitor Controls, IntelliRupters, and 6800 Series Automatic Switch Controls using software revision 3.5.x and higher can be operated by IntelliLink Remote commands when the IntelliLink Remote Commands setting, on the Setup > Security screen, has been set to Enabled. IntelliRupter Operation Because these commands do not operate the IntelliRupter, they can always be used by IntelliLink Remote: Validate Settings Apply Settings Reset Buffer All Log Screen Functions Functions on all File, Connections, Data, and Tools menus. These commands operate the IntelliRupter, and can only be used by IntelliLink Remote when the IntelliLink Remote Commands setting, on the Setup > Security screen, has been set to Enabled: Open Operation Close Operation Ground Trip Enable or Disable Second Closing Profile On or Off Circuit Testing Enable or Disable est on Backfeed Enable or Disable Protection Profile Selection Hot Line Tag Enable or Disable Remote Operation On or Off Run PulseClose Test Run Battery Test Prohibit or Enable Restoration Clear Manual Operation SEF Trip Enable or Disable Single Phase Trip Enable or Disable Loop Restoration Enable or Disable. 18 S&C Instruction Sheet 1032-500