ABB i-bus KNX Switch Actuator, x-fold, 16/20 A, MDRC SA/S x.16.6.1, 2CDG 110 1xx R0011



Similar documents
ABB i-bus KNX SA/S Switch Actuators Product Manual

ABB i-bus KNX Switch Actuator, x-fold, 16 A, MDRC SA/S x , 2CDG1101xxR0011

ABB i-bus KNX Fan Coil Actuator, MDRC FCA/S 1.1M, 2CDG R0011

ABB i-bus KNX Switch Actuators SA/S Product Information

ABB i-bus KNX Switch Actuators SA/S Product Information

ABB i-bus EIB / KNX EIB Monitoring Unit EUB/S 1.1

Product Manual. ABB i-bus KNX Data Logging Unit BDB/S 1.1. Intelligent Installation Systems ABB

ABB i-bus EIB / KNX Analogue Input AE/S 4.2

ABB STOTZ-KONTAKT GmbH ABB i-bus KNX Switch Actuators SA/S

Product Manual. ABB i-bus KNX. Universal Dim Actuator, MDRC UD/S Intelligent Installation Systems ABB

Switch Actuator, 8-fold, 10 A, MDRC AT/S , GH Q R0111

ABB i-bus KNX Security Terminals MT/U , MT/S M and M Product Manual

Product Manual. ABB i-bus KNX IP Interface IPS/S 2.1. Intelligent Installation Systems ABB

Three-phase monitoring relay CM-PFE

Analogue Input, 4-fold, MDRC AE/S 4.1, GH Q R0001

Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact

Electronic timer CT-VBS OFF-delayed without auxiliary voltage, for DC contactors Data sheet

Product and functional description

ABB i-bus EIB Shutter Actuators JA/S , JA/S , JA/S , JA/S M, JA/S M, JA/S

RM17TE V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC

ABB i-bus EIB / KNX DALI-Gateway DG/S 8.1

38 Series - Relay interface modules A

Shutter Actuator Standard, 4-fold, 230 VAC, MDRC RA/S , GH Q R0111. ABB i-bus EIB

STEP-PS/1AC/12DC/1.5. Extract from the online catalog. Order No.: DIN rail power supply unit 12 V DC/1.5 A, primary switched-mode, 1- phase

Installation Contactors. Technical Catalogue. Type ESB. abb. ABB STOTZ-KONTAKT GmbH 1 2CDC C0201

HSP GmbH Zum Handwerkerhof Wendelstein Tel / Fax: / Web: HSP@hsshsp.de NTG-3000.

15 Series - Electronic step relay and dimmer. Features SERIE

VEO. V4PF480Y/277VSYTK02 Art.Nr.: V4PF480Y/277VSYTK02P Art.Nr.: TECHNICAL DATA

RM4TG20 three-phase network control relay RM4-T - range V

pole, 8 A Safety relay. Screw terminal. 35 mm rail (EN 60715) mounting. 2 CO (DPDT) 8/15 250/400 2, /0.65/0.

34 Series - Slim electromechanical PCB relays 6 A. Features SERIES 34.51

38 Series - Relay interface modules A

Product and Applications Description. Application Programs. Example of Operation. GAMMA instabus Technical Product-Information.

Catalog. Modular DIN rail components Installation contactors

0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N

R.C.C.B. s two-pole LEXIC

Voltage monitoring relays CM-ESS.M For single-phase AC/DC voltages

Safety technique. Emergency stop module BO 5988 safemaster

RM35UA13MW. range V. Main. Product or component type. Relay monitored parameters

Technical Manual Functional Description for S800-RSU-H / S800W-RSU 2CCC413022M Schaffhausen 1 / 10

Thermistor motor protection relays CM-MSS.22 and CM-MSS.23

Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection)

49 Series - Relay interface modules A. Features

Push button 3gang standard flush-mounted xx

ABB 1. Three-phase monitoring relay CM-PFS. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories. Application.

MULTIFUNCTION TIME RELAY CRM-93H

MILLENIUM INSTALLATION MANUAL NTR 735 A. Simple Automation Control Module (MAS)

Type: DILM32 10(24V50HZ) Article No.:

PHOENIX CONTACT Features

BETA Switching. Switching Devices. 5TT5 8 Insta contactors, AC technology. Overview

E-STOP relays, safety gate monitors

Adjustment functions for both span and shift have been incorporated

Quick Connect. quick - simple - efficient.

48 SERIES Relay interface modules 10 A

DALI RC BASIC SO. Control unit Operating instructions

CONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE. General purpose single phase thyristors and solid state relays Product data.

DALI DIM/CONVERTER CONTROL (DC NV) 1 10V (0-10 V) analog DALI Converter with (Multi-) Sensor-control and 1 and 2-Switch dim functions

LC1D65AM7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 65 A V AC coil

ABB i-bus EIB / KNX Switch Actuator Modules for the Room Controller SA/M ES/M , ES/M

of the LED control gear Compact dimming Uconverter LCAI 55W 900mA 1750mA ECO SR ECO series

Single-phase ( V) voltage monitoring: Undervoltage Overvoltage Window mode (overvoltage + undervoltage) Voltage fault memory selectable

HDL KNX / EIB BUS. Switch Actuators. Guangzhou Hedong Electronic Co.,Ltd (HDL) 1/50

FL ballasts Electronic dimming. PCA T5 BASIC lp Y II, W BASIC T5

Fixed - Over/Under voltage limits, ( ) U N respectivity Link selectable - 5 min or 10 min delay. Fixed limits

Your Advantages For safety application up to PL e / Cat. 4 e.g. SIL 3 Manual or automatic start * see variants. Applications.

RY2 miniature industrial relays

Example of use: Fuse for a solenoid valve. If the fuse is defective, no information is sent to the electronic component.

Safety Manual BT50(T) Safety relay / Expansion relay

MasterINTERFACE 39 Series - Relay interface modules

Type: EASY719 DC RC Article No.: Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description

Analog signal converters CC-E I/I Current / current isolators

PCAN-B10011S Bus Converter High-speed CAN to Truck Trailer CAN. User Manual. Document version ( )

5SV Residual Current Protective Devices

650W Single Output Power Supply 15V 24V. 27V 48V Rated Current. 0 ~ 100A 0 ~ 50A 0 ~ 40A 0 ~ 27A 0 ~ 24A 0 ~ 13.6A Rated Power

Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages

Cross-beam scanning system to detect slim objects. 100 mm in

ABB i-bus KNX DALI Gateway Emergency Lighting DGN/S Product Manual

Thermistor motor protection

13 SERIES. Electronic step relays A

Fieldbus slave modules with I/Os, DIO

MasterINTERFACE 39 Series - Relay interface modules

ESB and EN installation contactors Application handbook

Throughbeam photoelectric sensors. Dimensioned drawing. Electrical connection

J TB/TW Temperature limiter, temperature monitor

LED Driver Compact dimming. Udriver LCAI 100W 900mA 1750mA ECO SR ECO series

ISL Insulation monitoring devices Continuous monitoring of IT systems from photovoltaic to industrial applications.

Actuator-Sensor-Interface

1000W Single Output Power Supply 15V 24V. Protection type: Total Power limit, Latch-style (Recovery after reset AC power ON or inhibit)

Electronic overload relay EF19 and EF45

TM7BDM8B expansion block - TM7 - IP67-8 DI/DO - 24V DC A - M8 connector

Automation System TROVIS 6400 TROVIS 6493 Compact Controller

ABB 1 NEW. Three-phase monitoring relay for grid feeding CM-UFS.1. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories

Power Supply Unit, Primary Switched, Narrow Design MINI-PS-12-24DC/24DC/1

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous

Panel Meters and Controllers Modular Panel Meter Type EDM 35

LINETRAXX VMD460-NA. Network and system protection (NS protection) for monitoring the power feed-in of power generation systems

DEK-REL- 24/1/SEN. Extract from the online catalog. Order No.:

ABB i-bus KNX IP Router IPR/S 2.1

RISH CON - Hz. Salient Features : Application : Product Features: FREQUENCY TRANSDUCER

Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points

Transcription:

, 2CDG 110 1xx R0011 SA/S 8.16.6.1 2CDC 071 006 S0010 The 16/20 A Switch actuators are modular installation devices in Pro M Design for installation in the distribution board. The devices are especially suitable for switching loads with high peak inrush currents such as lighting equipment with compensation capacitors or fluorescent lamp loads (AX) to EN 60 669. The Switch actuators feature one load current detection per output. The maximum load current per output is 20 A. Manual actuation of the switch actuator is possible using a button. This simultaneously indicates the switching state. The Switch actuators can switch up to 12 independent electrical loads via floating contacts. The maximum load current per output is 20 A. The connection of the outputs is implemented using universal head screw terminals. Each output is controlled separately via the KNX. Individual outputs can be copied or exchanged to reduce the programming effort withn the devices. The device does not require an additional power supply and is ready for immediate use, after the bus voltage has been applied. The Switch actuators are parameterized via the ETS. The connection to the KNX is implemented using the bus connection terminal on the front. Technical data Supply KNX bus voltage 21...31 V DC Current consumption via bus < 12 ma Power consumption via bus Maximum 250 mw Output nominal values SA/S type 2.16.6.1 4.16.6.1 8.16.6.1 12.16.6.1 Current detection yes yes yes yes Number (floating contacts 2 per group) 2 4 8 12 U n rated voltage 250/440 V AC (50/60 Hz) I n rated current 16/20 AX, C-Load Leakage loss per device at max. load 16 A 2.0 W 4.0 W 8.0 W 12.0 W Leakage loss per device at max. load 20 A Output switching current AC3 1) operation (cos j = 0.45) EN 60 947-4-1 AC1 1) operation (cos j = 0.8) EN 60 947-4-1 Fluorescent lighting load AX to EN 60 669-1 Minimum switching power 3.0 W 5.5 W 11.0 W 16.0 W 16 A/230 V AC 16/20 A/230 V AC 16/20 AX/250 V (200 mf) 2) 100 ma/12 V AC 100 ma/24 V AC Output service life DC current switching capacity (resistive load) Mechanical service life Electronic endurance to IEC 60 947-4-1 AC1 1) (240 V/cos j = 0.8) AC3 1) (240 V/cos j = 0.45) AC5a 1) (240 V/cos j = 0.45) 20 A/24 V AC > 10 6 > 10 5 > 3 x 10 4 > 3 x 10 4 Page 1 of 6

, 2CDG 110 1xx R0011 Current detection (load current) Output switching times 3) Connections Operating and display elements Detection range (sine effective value) Accuracy Frequency 2 byte representation (figure value, DTP 7.012) in ma or 4 byte representation (floating value, DTP 14.019) Measurement speed - Low-pass filter transient response with τ - Scanning frequency of the current value Maximum relay position change of output and minute if all relays are switched simultaneously. The position changes should be distributed equally within the minute. Maximum relay position change per output and minute if only one relay is switched. 1) Further information concerning electronic endurance to IEC 60 947-4-1 can be found at in the product manual: AC1, AC3, AX, C-Load specifications. 2) The maximum peak inrush current may not be exceeded, see product manual: Lamp load output. KNX Load current circuits (2 terminal per relay) Ferrules without/with plastic sleeves TWIN ferrules Tightening torque Programming button/led Switch position display 0.02 20 A +/- 2 % of actual current value (sine) and +/- 20 ma 50/60 Hz 300 ms 320 ms 2.16.6.1 4.16.6.1 8.16.6.1 12.16.6.1 30 15 7 5 60 60 60 60 Via bus connection terminals 0.8 mm Ø, solid Universal head screw terminal (PZ 1) 0.2 4 mm 2 stranded, 2 x 0.2 2.5 mm 2 0.2 6 mm 2 solid, 2 x 0.2 4 mm 2 0.25...2.5/4 mm 2 0.5...2.5 mm 2 Contact pin length min. 10 mm Maximum 0.6 Nm For assignment of the physical address Relay operator Enclosure IP 20 To EN 60 529 Safety class II To EN 61 140 Insulation category KNX safety extra low voltage Temperature range Overvoltage category Pollution degree SELV 24 V DC Operation Storage Transport III to EN 60 664-1 2 to EN 60 664-1 -5 C +45 C -25 C +55 C -25 C +70 C Ambient conditions Maximum air humidity 95 %, no condensation allowed Design Modular installation device (MDRC) SA/S type Dimensions Width W in mm Mounting width in space units (modules at 18 mm) Mounting depth in mm Modular installation device, Pro M 2.16.6.1 4.16.6.1 8.16.6.1 12.16.6.1 90 x W x 64.5 mm (H x W x D) 36 72 144 216 2 4 8 12 64.5 64.5 64.5 64.5 Weight in kg 0.2 0.34 0.64 0.75 Installation On 35 mm mounting rail To EN 60 715 Mounting position Housing/colour as required Plastic housing, grey Approvals KNX to EN 50 090-1, -2 Certification CE mark In accordance with the EMC guideline and low voltage guideline 3) The specifications apply only after the bus voltage has been applied to the device for at least 30 seconds. Typical delay of the relay is approx. 20 ms. Page 2 of 6

, 2CDG 110 1xx R0011 Output lamp load 16/20 A Lamps Incandescent lamp load Fluorescent lamps T5/T8 Low-voltage halogen lamps Dulux lamps Marcury-vapour lamps Switching capacity (switching contact) Number of electronic ballasts (T5/T8, single element) 1) Uncorrected Parallel compensated DUO circuit Inductive transformer Electronic transformer Halogen lamps 230 V Uncorrected Parallel compensated Uncorrected Parallel compensated Maximum peak inrush current I p (150 µs) Maximum peak inrush current I p (250 µs) Maximum peak inrush current I p (600 µs) 18 W (ABB EVG 1 x 18 CF) 24 W (ABB EVG-T5 1 x 24 CY) 36 W (ABB EVG 1 x 36 CF) 58 W (ABB EVG 1 x 58 CF) 80 W (Helvar EL 1 x 80 SC) 2500 W 2000 W 2500 W 3000 W 1) For multiple element lamps or other types, the number of electronic ballasts must be determined using the peak inrush current of the electronic ballasts, see product manual: Ballast calculation. 2) The number of ballasts is limited by the protection with B16 circuit-breakers. 600 A 480 A 300 A 26 2) 26 2) 22 12 2) 10 2) Device type Application program Max. number of communication objects Max. number of group addresses SA/S 2.16.6.1 Switch 2f 16CS/ * 40 254 254 SA/S 4.16.6.1 Switch 4f 16CS/ * 76 254 254 SA/S 8.16.6.1 Switch 8f 16CS/ * 148 254 254 SA/S 12.16.6.1 Switch 12f 16CS/ * 220 254 254 Max. number of associations * = current version number of the application program. Please observe the software information on our homepage for this purpose. Note For a detailed description of the application program see the Switch Actuator SA/S product manual. It is available free-of-charge at www.abb.com/knx. The ETS and the current version of the device application program are required for programming. The current application program is available for download on the internet at www.abb.com/knx. After import in the ETS, it is available in the ETS under ABB/Output/Binary output xf 16CS/ * (x = 2, 4, 8 or 12). The device does not support the locking function of a KNX device in the ETS. If you inhibit access to all devices of the project with a BCU code, it has no effect on this device. Data can still be read and programmed. Page 3 of 6

, 2CDG 110 1xx R0011 Important The Switch actuator types differentiate from the predecessor types SA/S x.16.5s by new hardware and software. While there have been few changes to the functions of the software, the hardware has been redesigned for load currents up to 20 A. Furthermore, the current detection has been optimised and its accuracy has been enhanced by a factor of four. Existing projects can be converted to ensure operation with the new hardware / software. For further information refer to the product manual: Conversion of previous application program versions. For faster and simpler commissioning, it is also possible to copy the parameter settings of the outputs to others or to exchange them with another output. For further information refer to the product manual: Copying and exchanging parameter settings. Note Only load currents with a sine wave characteristic can be detected correctly. On other signal types, e.g. phase angle or inverse phase angle control signals, the detected current value is distorted. In this case, the measured value is meaningless. Current values less than 20 ma are indicated as a 0 ma value on the KNX. For small load currents that are just above the minimum detection threshold of 20 ma, it is possible that a value of 0 ma is displayed due to the inaccuracies, even though a current is flowing. Example: A current of 25 ma is flowing. The Switch Actuator detects 5 ma due to the tolerances. This value is less than the minimum current detection limit of 20 ma and is thus sent as a 0 ma value on the KNX. Important The function current detection and monitoring should not be used for safety-relevant applications. The Switch actuator cannot assume the function of a circuit-breaker or RCD (earth-leakage circuit breaker). If the load current detection is used for equipment fault detection that only causes a slight change of under 30 ma, mains voltage and current fluctuations due to ambient influences, e.g. temperature, natural ageing of the device or a non-sinusoidal current, play a significant role. Even when the current changes are detected by the Switch actuator, the detected current changes do not necessarily mean that a device has malfunctioned. Page 4 of 6

, 2CDG 110 1xx R0011 Circuit diagram 2CDC 072 086 F0011 1 Label carrier 2 Button Programming 3 LED Programming (red) 4 Bus connection terminal 5 Switch position display and manual operation 6 Load current circuits, for every 2 connection terminals Danger Touch voltages. Danger of injury. Observe all-pole disconnection. Page 5 of 6

, 2CDG 110 1xx R0011 Dimension drawing B 2CDC 072 087 F0011 Width W Mounting width (modules at 18 mm) SA/S 2.16.6.1 SA/S 4.16.6.1 SA/S 8.16.6.1 SA/S 12.16.6.1 36 mm 72 mm 144 mm 216 mm 2 space units 4 space units 8 space units 12 space units Page 6 of 6