Contents. Clean Control Center Harmonic Correction Unit. Selection Dimensions Specifications. Description



Similar documents
BT300 HVAC Drives Conventional Bypass (C-Bypass) Options

LTR Series Uninterruptible Power Systems 700 VA KVA. General Specification

MTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL MTE Corporation

Submit shop drawings for equipment provided under this section Shop drawings shall indicate:

Specification guide no. 9 Active harmonic conditioner from 20 to 480 A

SECTION VARIABLE FREQUENCY DRIVES

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation

Low Voltage Products

Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000

VARIABLE FREQUENCY DRIVES Revised 4/30/ Mechanical Systems

City of Leesburg, Florida I.T. Data Center APPENDIX A TOSHIBA UPS INFORMATION

32VFD Variable Frequency Drives for Centrifugal Chillers

APC Smart-UPS RT. GUIDE SPECIFICATIONS FOR 3000VA, 5000VA and 6000 VA Smart-UPS RT 230VAC Uninterruptible Power Supply

GTEC transfer switch open transition

Power Management Module 2. Installation

Industrial-Grade UPS System Heavy-duty power protection for harsh industrial environments

Sample - No Commercial Use

CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH

Project Name: Nortrax Section Project No: SURGE PROTECTION DEVICES Page 1

FFI. Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars. Presented By: Greg Pelster & Robert Schmid

CONSTRUCTION STANDARDS DIVISION 23 HEATING VENTILATING AND AIR CONDITIONING

The HVAC SOLUTION DELIVERING POWER...SAVING ENERGY

Suitable for Emergency, Peak and Prime Power System Applications. Low Voltage Automatic Transfer Switch Systems

SmartOnline V 6kVA 4.2kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 6U Rack/Tower, DB9 Serial, Hardwire

SECTION STATIC UNINTERRUPTIBLE POWER SUPPLY SYSTEM

SmartOnline Expandable Rack / Tower UPS System Online, double-conversion protection for mission critical applications

How To Operate A Gec Transfer Switch Open Transition Amp Power Supply

Arc Terminator Active Arc-Resistant Switchgear

Engineers Edge, LLC PDH & Professional Training

SmartPro 120V 2.2kVA 1.92kW Line-Interactive Sine Wave UPS, SNMP, Webcard option, 2U Rack/Tower, LCD, USB, DB9 Serial

APC Matrix-UPS 5kVA 208V/240V In 120/208/240V Out

TOSHIBA G /100/160/225 kva

SmartOnline V 5kVA 4.5kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 4U Rack/Tower, USB, DB9 Serial

Daker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF

SECTION POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL

How To Test A Power Switch On A Power Supply

8146/5 Series Breaker Panelboards

Parallel Redundant Uninterruptible Power Supply

RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features:

Specification Requirements DBL 700MX and 1000MX Series UPS

Uninterruptible Power Supply

AIS 3000 APC AIS kVA 208V w/2 Batt. Module Exp. To 4, Start-Up 5X8, Internal Maintenance Bypass

Thyristor-controlled power supplies and battery chargers

What are the basic electrical safety issues and remedies in solar photovoltaic installations?

AMFA-27 AMFA-29. Operator s Manual & Installation Instructions. Rev. 2.5

Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller

SWITCHGEAR. EGP Switchgear

APC Smart-UPS RT. GUIDE SPECIFICATIONS FOR 15kVA and 20kVA Smart-UPS RT 230VAC Uninterruptible Power Supply

Circuit Breakers and Switchgear. Thomas Greer Director of Engineering TLG Services

Unified requirements for systems with voltages above 1 kv up to 15 kv

MCC Ratings. Voltage Rating

Secondary Unit Substations

Transfer Equipment Controls

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV a. Section INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

Learning Module 13: Panelboards and Switchboards. 101 Basic Series

32:(5#5$7,1* 4833#USP283#+] 4;33#USP293#+] 3ULPH 113 kva, 90 kw 124 kva, 99 kw 6WDQGE\ 114 kva, 91 kw 125 kva, 100 kw

PREFACE. Your comments or suggestions are welcome and appreciated. They should be sent to:

ATC-300 Automatic Transfer Switch Controller

Product Description Primary Resistance Starting Electric Fire Pump Controllers FTA1500

MAJORSINE Power Inverter

Short Circuit Current Calculations

ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013

Uninterruptible Power Supply. 500 kva kva

Power Quality for Information Technology System

Limited Service Fire Pump Controllers Features

Liebert PPC Second Generation Power Distribution Cabinet

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Metering and Monitoring. Basis of Design

UNINTERRUPTIBLE POWER SUPPLIES >9900AUPS UNINTERRUPTIBLE POWER SUPPLIES

SmartPro 120V 1kVA 800W Line-Interactive Sine Wave UPS, SNMP, Webcard, 1U Rack, USB, DB9 Serial

SmartPro 120V 750VA 600W Line-Interactive Sine Wave UPS, SNMP, Webcard, 1U Rack-Mount, USB, DB9 Serial

ASCO SERIES 185 Power Transfer Switches

SmartPro 120V 750VA 600W Line-Interactive Sine Wave UPS, 1U Rackmount, SNMPWEBCARD Option, USB, DB9 Serial

RIELLO ELETTRONICA. Master HP

NGC-30-CR -CRM -CRMS -CTM -CVM

QuickSpecs. Overview. HP Power Distribution Rack. HP Power Distribution Rack. DA North America Version 5 August 22, 2008 Page 1

TAA-Compliant SmartPro 120V 1kVA.8kW Line-Interactive Sine Wave UPS, SNMP, Webcard, 1U Rack, USB, DB9 Serial

LOXONE 12 Channel Amplifier

SmartPro 230V 3kVA 2.25kW Line-Interactive UPS, Extended Run, SNMP, Webcard, Tower, USB, DB9 Serial

Applications. Remote Display Mounting Kits

Power Meter Series 700

Power-monitoring unit PowerLogic System. Technical data sheet. Power Meter Series 800

SWITCHGEAR SOLUTIONS FOR MISSION CRITICAL APPLICATIONS. Presented by SAI Advanced Power Solutions

Always On UPS Systems Inc., # Campion Road, Kelowna, BC Canada V1X 7S8

Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000

Multi DIALOG MDM/MDT. MDM 10-20kVA single/single-phase and three/single-phase MDT 10-80kVA three/three-phase NETWORK RANGE

Audio/Video AVR Series UPS - Intelligent Automatic Voltage Regulated Power Management System

CONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE. General purpose single phase thyristors and solid state relays Product data.

SmartPro 230V 1000VA 900W Line-Interactive Sine Wave UPS, SNMP, Webcard, 2U Rack/Tower, USB, DB9 Serial

SURGE PROTECTIVE DEVICES (SPDs) LOW VOLTAGE AC INTEGRATED SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS SECTION 16671A SECTION 16671A

Surgelogic Surge Protective Device (SPD)

Diesel Engine Driven Generators Page 1 of 6

SWITCHGEAR Section 16. SECTION INCLUDES This Section includes service and distribution switchboards rated 600 V and less.

Galaxy VM. Three-phase power protection. schneider-electric.com

ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL

Sentron Series Circuit Breakers

SOLAR PV STANDARD ELECTRICAL PLAN Microinverter Systems for Single Family Dwellings

Product Description Digital Solid State Starting Electric Fire Pump Controllers FTA1930

Remote Monitoring and REC 501 Control Unit Product Guide

Bussmann. All-In-One Module. Bussmann Power Module Switch. How to configure Part Numbers: Step 1: Select Switch Amperage 1

SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches

Transcription:

lean ontrol enter Harmonic orrection Unit Technical Data Selection Dimensions Specifications ontents Description Page lean ontrol enter Specifications Harmonic orrection Unit...... 2 Sizing and Selection........................................... 2 Installation and Power ircuit Diagrams........................... 2 lean ontrol enter with Active Harmonic ontrol................. 3 50 Ampere lean ontrol enter Layout Dimensions.............. 4 100 Ampere lean ontrol enter Layout Dimensions............. 5 Guide Specifications........................................... 6 lean ontrol enter For more information contact utler-hammer at: www.ch.cutler-hammer.com

Page 2 ffective: October 2001 Harmonic orrection Unit Specifications The lean ontrol enter utilizes a harmonic correction unit to provide harmonic cancellation directly on the Motor ontrol enter Horizontal Bus. The harmonic correction unit senses the load current and injects into the A lines a synthesized waveform that is inverted compared to the remaining signal. The result is a clean waveform as seen by the upstream electrical system. Single or multiple harmonic correction units may be applied within a lean ontrol enter providing an economical solution to excessive harmonics due to A drives or other non-linear loads. Use of the lean ontrol enter will provide compliance to the most stringent 5% Total Demand Distortion (TDD) requirements of I 519. Table 1. lean ontrol enter Harmonic orrection Unit Specifications Safety Agency lectrical nvironment UL: SA: Voltage: Frequency: Requires series input line reactor or D bus choke in each A drive for optimum performance. Sizing and Selection Ambient Temperature: Storage Temperature: Relative Humidity: Altitude: Vibration: Approved Approved 208 480V +/- 10% 50/60 Hz, +/- 3 Hz 0º to 40º nclosed -40º to 65º to 95% Non-condensing to 1000 Meters Seismic Zone 4 Packaging Standard nclosure: Motor ontrol enter NMA Type 1 Protection Input Fuses Molded ase Switch Disconnect: Surge Withstand apacity: Logic Ride-Through: Output apacity: 600V, 200,000 AI, lass T 150A (50/100A Models) I 62.41-1991 30 Seconds Upon Full Loss of Input Voltage Self-limited to 100% Rated Performance orrective apability: <5% TDD and Near Unity Displacement Power Factor Information/ontrol Display: Operators: Indicator LD: Information Diagnostics: Output ontacts: ommunications: 2 Line, 20 haracter/line Alphanumeric Run, Stop, Setup, nter Up and Down Scroll Run (green) nglish Power On, Run, Fault, at Maximum apacity RS-485 Port Table 2. Harmonic orrection Unit Ratings Model Voltage Frequency Total urrent Amperes (rms) Watt Losses (kw) xterior Dimensions in Inches (H x W x D) nclosure Type Shipping Weight (Lbs.) Disconnect (150A Molded ase Switch) HU050AM 208 480 50/60 50 2.03 90 x 24 x 21 M onstruction 385 X HU100AM 208 480 50/60 100 3.20 90 x 24 x 21 M onstruction 495 X lean ontrol enter model includes 24-inch wide M structure, current transformers and door-mounted digital interface panel. Note: urrent transformers are rated for 400 Hz. Two current transformers are required for 3-phase loads. Three current transformers are required when single-phase loads are present. Load(s) Source XFMR Typical T Placement A Lines Fuse Fuse Fuse Line Inductor Pre-charge ontactor Inductor S1 S3 S5 + Alternate T Placement HU Filter Board S2 S4 S6 Figure 1. Installation Diagram Figure 2. Power ircuit Diagram For more information contact utler-hammer at: www.ch.cutler-hammer.com

ffective: October 2001 Page 3 lean ontrol enter with Active Harmonic ontrol Typical Layout Source Side Harmonics Attenuated Load Side Harmonics Present Main Breaker Panelboard Harmonic orrection Unit 100A SV9000 A Drive (30 Hp) SV9000 A Drive (150 Hp) SV9000 A Drive (250 Hp) Starter TVSS Protection Module Distribution Transformer Starter SV9000 A Drive (30 Hp) Starter Feeder Breaker 20.0 20.0 24.0 20.0 20.0 28.0 20.0 Figure 3. lean ontrol enter with Active Harmonic ontrol Dimensions in Inches The layout above is a typical arrangement for a lean ontrol enter including harmonic correction units for non-linear loads such as A Variable Frequency Drives. The horizontal bus of the lean ontrol enter is virtually free of harmonic current content at the point where the Harmonic orrection Unit connects to the bus. From this point to the connection at the utility bus, the lean ontrol enter complies with the most stringent requirements of I 519 and provides a clean waveform to the upstream distribution system. Harmonic orrection may be applied to loads fed directly from the M (e.g. M mounted A drives) or loads fed indirectly from the M (e.g. M mounted circuit breakers feeding remote A drives). Multiple correction units may be used to achieve the level of harmonic correction as required by the amount of non-linear loads within the M lineup. For more information contact utler-hammer at: www.ch.cutler-hammer.com

Page 4 ffective: October 2001 lean ontrol enter 50 Ampere Harmonic orrection Unit Layout Dimensions The HU050AM unit provides up to 50 amperes of harmonic correction current in a convenient and labor savings Motor ontrol enter package. M units include horizontal bus, molded case input disconnect, horizontal bus connected current transformers and digital operator panel for control, diagnostics and programming. 24.0 (609.6) 21.0 (533.4) 90.0 (2286.0) Figure 4. 50 Ampere lean ontrol enter Harmonic orrection Unit Dimensions in Inches (mm) For more information contact utler-hammer at: www.ch.cutler-hammer.com

ffective: October 2001 Page 5 lean ontrol enter 100 Ampere Harmonic orrection Unit Layout Dimensions The HU100AM unit provides up to 100 amperes of harmonic correction current in a convenient and labor savings Motor ontrol enter package. M units include horizontal bus, molded case input disconnect, horizontal bus connected current transformers and digital operator panel for control diagnostics, and programming. 24.0 (609.6) 21.0 (533.4) 90.0 (2286.0) Figure 5. 100 Ampere lean ontrol enter Harmonic orrection Unit Dimensions in Inches (mm) For more information contact utler-hammer at: www.ch.cutler-hammer.com

Page 6 ffective: October 2001 lean ontrol enter (Harmonic orrection Unit) Guide Specifications To reduce current harmonics and correct power factor on low voltage electrical systems. 1.0 General 1.1 Summary This specification defines the electrical and mechanical characteristics and requirements for harmonic correction units in order to meet 5% total demand distortion [TDD], and <5% total harmonic voltage distortion [THD(V)] levels at selected points within the electrical system. The harmonic correction assembly shall be UL 845 listed and integral to utler-hammer Series 2100 Motor ontrol enters. 1.2 Standards The harmonic correction unit shall be designed in accordance with the applicable sections of the following documents. Where a conflict arises between these documents and statements made herein, the statements made in this specification shall govern. ANSI I standard 62.41-1991 [surge withstand capacity] SA 22.2, No. 14 and 66 [SA requirements for power electronics] F Part 15, Sub Part J, lass A [RFI/MI emission standards] ANSI I standard 519-1992 [harmonic limits] UL 845 [UL requirements for motor control centers] I 529, IP20 (NMA 1) [type of enclosure] IBO Building ode, Section 16, Seismic Zone 4 [vibration standard] The products shall include third party approvals by UL or SA. 1.3 System Description 1.3.1 System Description A. Voltage: 480V, 3-phase, 3-wire, plus ground. B. Output Load apacity: Rated capacity shall be the specified current capacity at the voltage required as indicated within this specification and shown on the respective electrical drawings included within this document.. Field Installable apacity Upgrade: Additional power correction capacity shall be added by installing additional units in parallel to previously installed power correction systems. A maximum of 3 units shall be installed in parallel per set of current transformers. D. urrent Transformers: 1. Split core type current transformers shall be installed as defined herein and shown in the electrical drawings contained in these documents. 2. Two current transformers per power correction system location are required and mounted on phases A and B. 3. A third current transformer is required if single- or 3-phase line to neutral connected loads are present downstream from the location of the Ts. 4. urrent ratings of the current transformers shall be according to full load current of the circuit on which installed. 5. urrent transformers rated for 400 Hz shall be used. 1.3.2 Modes of Operation A. The harmonic correction unit shall be designed to electronically inject harmonic current to cancel load produced harmonic current such that the upstream power harmonic current and voltage are reduced to below 5% TDD and 5% THD(V) as defined by ANSI I standard 519-1992 for load demand and voltage distortion limits. TDD as used herein refers to the total load demand of the applied circuit. The applied circuit may be a single non-linear load, an entire distribution bus load, or the facility load at the point-ofcommon coupling (P). B. Reactive current compensation (aka displacement power factor correction) shall be activated via a digital keypad/display mounted on the door of the enclosure. When reactive current compensation is activated, the harmonic correction unit shall first perform harmonic current correction and then use the remaining capacity to inject reactive current compensation to the specified level herein defined. 1.3.3 Performance Requirements A. Input Power: 1. Voltage: 208 480V, 3-phase, plus ground. 2. Voltage Tolerance: +/- 10% of nominal. 3. Frequency: 50/60 Hz, +/- 5%. 4. urrent Limit: 100% of rating. 5. Surge Withstand apability: ANSI/ I standard 62.41-1991 without damage. 6. Input Fuses: Rated at 200,000 AI (amperes interrupting capacity), lass T. B. Output Performance 1. Performance of the harmonic correction unit shall be independent of the impedance of the power source. All performance levels shall be attained whether on the A lines or backup generator or output of UPS. 2. Harmonic orrection: a. Limit 2nd through 50th order harmonic current to <5% TDD as defined in ANSI/I standard 519-1992 at each installed location. Harmonic levels for individual harmonic orders shall comply with respective levels established in ANSI/I standard 519-1992. b. Limit the THD(V) added to the electrical system immediately upstream of the power correction system location(s) to less than or equal to 5% as defined in ANSI/I standard 519-1992. The power correction system shall not correct for utility supplied voltage distortion levels. c. Reactive urrent ompensation: to.90 lagging displacement power factor. Leading power factor is not permitted. For more information contact utler-hammer at: www.ch.cutler-hammer.com

ffective: October 2001 Page 7. urrent Transformers 1. urrent transformers shall be rated for the total rated rms current of the total load at each installed location. 2. Two current transformers, mounted on phases A and B, are to be installed per location. 3. A third current transformer is required if single- or 3-phase line to neutral connected loads are present downstream from the location of the Ts. 4. ach current transformer shall have a current output of 5 amperes. urrent capacity of each current transformer shall be 5000, 3000, 1000 or 500, as required for the electrical system where installed. No other ratings are acceptable. 5. ach current transformer shall be rated for 400 Hz. 1.4 nvironmental onditions The harmonic correction unit shall be able to withstand the following environmental conditions without damage or degradation of operating characteristics or life. 1. Operating Ambient Temperature: 0º (32ºF) to 40º (104ºF). 2. Storage Temperature: -40º (-40ºF) to 65º (149ºF). 3. Relative Humidity: 0 to 95%, non-condensing. 4. Altitude: Operating to 1000 meters (3,300 feet). Derated for higher elevations. 5. Audible Noise: Generated by power correction system not to exceed 65 dba measured 1 meter (3 feet) from surface of unit. 6. Vibration: Seismic Zone 4. 1.5 Submittals 1.5.1 Approval Submittals Submittals for approvals shall include: a. System configuration in a single line diagram. b. Size and weights of shipping units to be handled by installer. c. Dimensional drawings with installed weight and heat dissipation for each size provided. d. Detailed layouts of customer power and control connections. e. Detailed installation drawings including all terminal locations. 1.5.2 Delivery Submittals Submittals upon delivery of power correction system shall include: a. omplete set of corrected proposal submittal drawings. b. Two (2) sets of Installation and Operation Manuals. Manuals shall include a functional description of equipment with block diagrams, safety precautions, installation instructions, start-up instructions, and troubleshooting guide. 2.0 Product 2.1 onstruction A. The lean ontrol enter shall consist of a utler-hammer Series 2100 Motor ontrol enter and integral harmonic correction unit for the attenuation of harmonics induced by non-linear loads such as A Adjustable Frequency Drives. B. The harmonic correction unit for the lean ontrol enter shall be in a totally enclosed deadfront, free-standing M assembly. Structures shall be 90 inches high and 20 inches deep for frontmounted units. Structures shall contain a horizontal wireway at the top, isolated from the horizontal bus and shall be readily accessible through a hinged cover. Adequate space for conduit and wiring to enter the top or bottom shall be provided without structural interference.. An operating mechanism shall be mounted on the primary of each harmonic correction unit. It shall be mechanically interlocked with the door to prevent access unless the disconnect is in the OFF position. A defeater shall be provided to bypass this interlock. With the door open, an interlock shall be provided to prevent inadvertent closing of the disconnect. Padlocking facilities shall be provided to positively lock the disconnect in the OFF position with from one (1) to three (3) padlocks with the door open or closed. D. Harmonic orrection Units shall be disconnected from the power source by a molded case switch.. ach structure shall contain a main horizontal copper tinplated or copper silver-plated bus, with minimum ampacity of 600 amperes or rated up to 3200 amperes as shown on the drawings. The horizontal bus shall be rated at 65º or 50º temperature rise over a 40º ambient in compliance with UL standards. F. Buses shall be braced for 65,000 or 100,000 amperes rms symmetrical. G. All units shall meet Seismic Zone 4 vibration requirements when installed according to installation requirements defined herein. H. Motor ontrol enter units shall include lifting provisions by forklift truck and lifting lugs. I. All units shall include 200,000 AI rated fuses with lass T actuation. J. All units shall be provided with a grounding lug. Grounding by the contractor is to be performed according to local and national standards. K. The paint shall be ASA61. 2.2 Operator ontrols and Interface A. All units shall include a digital interface model (DIM) that includes an alphanumeric display consisting of 2-lines with 20 characters per line. All information shall be in nglish. Operators include run, stop, setup, enter, and up/down scroll. B. The display shall provide operating data while functioning. Standard operating parameters available for display are A line voltage, total rms load current, harmonic current of load, reactive current of load, output harmonic and reactive current of power correction system.. When the output of the power correction unit is at full rated capacity, the display shall indicate an atmaximum capacity and actuate an at-maximum capacity relay. D. All fault conditions shall be displayed as they occur. Diagnostic information shall be provided in nglish and clearly indicate the nature of the fault.. The run pushbutton shall include a green LD. LD shall be lighted when unit is running. For more information contact utler-hammer at: www.ch.cutler-hammer.com

Page 8 ffective: October 2001 F. ontacts shall be provided for operator information for poweron, run, fault and at-maximum capacity. ach contact shall be rated for 1 ampere at 120/240 volts. One form contact shall be provided for each relay. G. An RS485 serial communication port shall be provided for remote control and diagnostic information. 2.3 Design A. ach unit of the harmonic correction units shall meet F Part 15, Sub Part J, lass A requirements for both radiated and conducted MI. B. All harmonic correction units shall be defined as a power electronic device consisting of power semiconductors that switch into the A lines to modulate its output to cancel detrimental harmonic and/or reactive currents. A D bus shall store power for power semiconductor switching. A microprocessor shall control the operation of the power converter.. ach unit shall be designed with a current limiting function to protect the semiconductors. When this level is attained, a message shall be displayed indicating the output capacity is at-maximum capacity and actuate the at-maximum capacity relay. Operation shall continue indefinitely at this level without tripoff or destruction of the power correction unit. D. Two distinct levels of faults shall be employed. Non-critical level faults will provide automatic restart and a return to normal operation upon automatic fault clearance. ritical level faults stop the function of the unit and await operator action. 1. Faults such as A line overvoltage, A line undervoltage, A line power loss, and A line phase imbalance shall be automatically restarted. Upon removal of these fault conditions, the power correction system shall restart without user action. Automatic restart will not occur if 5 faults have occurred in less than 5 minutes. During the fault condition, except line loss, the display shall state the type of fault and indicate that automatic restart will occur. The run relay and run LD shall be disabled. The fault relay shall not be enabled unless time out occurs. Upon A line loss, the power-on relay shall be disabled and no display shall be provided. 2. All other types of faults shall be considered critical and stop the power correction system. The display shall indicate the fault condition and stop. The run LD and relay shall be disabled and the fault relay enabled. User shall be required to initiate a power reset (turn power off and on) to restart the power correction system.. The logic of the harmonic correction unit shall monitor the load current by utilizing two (2) current transformers (Ts) mounted on phases A and B to direct the function of the power electronic converter. A third current transformer is required if single- or 3-phase line to neutral connected loads are present downstream from the location of the Ts. The ratio of the Ts must be entered into the logic via the digital keypad/display to calibrate the operation of the power correction system. The output of the current transformers shall be 5 amperes. F. Up to 3 harmonic correction units may be installed in parallel to inject current according to the information received from one set of Ts. The units will function independently. If one unit is stopped or faulted, the remaining units will adjust accordingly to maintain optimum harmonic cancellation levels up to the capacity of the remaining units. aton orporation utler-hammer business unit 1000 herrington Parkway Moon Township, PA 15108-4312 USA tel: 1-800-525-2000 www.ch.cutler-hammer.com 2001 aton orporation All Rights Reserved Printed in USA Publication No. October 2001