PERCENT OUTDOOR AIR (%OA) CALCULATION AND ITS USE
|
|
|
- Edward Patrick
- 10 years ago
- Views:
Transcription
1 PERCENT OUTDOOR AIR (%OA) CALCULATION AND ITS USE APPLICATION NOTE TI-138 TSI s IAQ-CALC TM Indoor Air Quality Meter and TH-CALC TM Thermohygrometer calculate Percent Outdoor Air (%OA). In order to take advantage of this feature, it is important to first understand what % Outdoor Air is, why it is important, and how to use these instruments to calculate %OA. In the 1970s, energy consumption was a serious concern and every step was taken to reduce energy use and energy costs. Economizers became popular during this time because they re-circulated valuable conditioned air in the summer and the winter when heating or cooling costs were high. While this was going on, building designers were designing new buildings to be more efficient by sealing windows and doors better and by sealing other leaky spots. This reduced the amount of infiltration, which is how the majority of outdoor air entered these buildings. This appeared to make the buildings more efficient because heating and cooling costs were reduced. However, it wasn t until years after these changes were made that the HVAC industry began to notice a trend in these airtight buildings with economizers. Occupants complained of headaches and nauseous feelings. Shutting off the outdoor air intake and sealing the building resulted in an insufficient amount of outdoor air to dilute indoor contamination. This led to Sick Building Syndrome and other Indoor Air Quality complaints. Perhaps the somewhat infamous quote, The Solution to Pollution is Dilution, may sum up the whole idea behind the importance of fresh outdoor air. We may not go as far as to say that indoor environments have pollution, but we might want to consider the effects of the indoor air components that can t be filtered out. These include CO 2, body odors, chemicals from photocopiers and cleaners, and so on. Most of these components alone wouldn t make someone sick over short periods of time. However, after long periods of exposure, like in a workplace where 40-hour workweeks are typical, these components have the capacity to make occupants tired, nauseous, and otherwise not as healthy. Eventually, these air components can wear down a person s immune system and can eventually make occupants sick. The best way to minimize these bad air components is to dilute them with adequate fresh air. This will probably never completely remove the contaminants, but rather, it will keep the components at a level low enough as not to affect occupants. These days economizers still exist, but they have evolved to recirculate as much conditioned air as possible and still deliver at least the minimum amount of fresh outdoor air recommended by ASHRAE.
2 ASHRAE, the American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc., has a standard called ASHRAE 62 Ventilation for Acceptable Indoor Air Quality. This standard recommends a minimum amount of fresh air per person for defined spaces. For example, the minimum amount of fresh outdoor air recommended for office spaces is 20 CFM/person. One method used to calculate the volume of fresh outdoor air entering a system is to take a duct traverse of the outdoor air duct intake. However, this is not always feasible, because there may not be sufficient straight ducting to do a good duct traverse 1 of either the return air or the outdoor air. Often, there is not even a duct for outdoor air, so it is essentially impossible to determine the volume of outdoor air that is entering the system. For an alternative way to determine how much fresh outdoor air is entering a space, use the following equation: Volume Fresh Outdoor Air =Volume of delivered air x % Outdoor Air of delivered air The volume of fresh outdoor air entering a space equals the volume of delivered air (ft 3 /min, m 3 /hr, m 3 /min or L/s) times the % outdoor air. Let s look at each of these items separately. The total volume of delivered air is the total volume of both outdoor air and return air entering a space. To determine the total volume of supply air entering a building, do a duct traverse using a VELOCICALC Plus Rotating Vane Anemometer or a DP-CALC TM Micromanometer right after the Air Handling Unit and before the duct branches off. Another method to determine the total volume of delivered air is to use the ACCUBALANCE Air Capture Hood at each supply diffuser and to take the sum of the readings. Percent outdoor air is the % of the total volume of delivered air that is outdoor air. There is more than one way to measure %OA. One method is to use a tracer gas like SF 6. This gas would be used to saturate the system at a set concentration and to record how the concentration decreases over time. Using this information, one can figure out what the %OA is. This can also be done with CO 2 if the concentration is high enough and there are no occupants. Perhaps a better option is to take three readings of CO 2 concentration and plug them into an equation. The three reading locations include outdoor air, supply air, and return air. Another option is to take temperature readings at those same three locations and use a similar equation. This Application Note describes these last two methods of determining %OA. To calculate the %OA, use the following equation for CO 2 or temperature: Where: XS) % OA x100% XO) X R = Return air CO 2 concentration OR temperature X S = Supply air CO 2 concentration OR temperature X O = Outdoor air CO 2 concentration OR temperature As of December, 2000, ASHRAE s recommendation for minimum amount of fresh outdoor air for office spaces is 20 CFM/person. These recommendations may change over time and are different for different defined spaces including smoking areas, restrooms, and many more. Please refer to the most current ASHRAE 62 guideline for minimum outdoor air recommendations for your specific Application. -2-
3 Let s look at an example. An industrial hygienist takes three samples with the following values: Outdoor air CO 2 level = X O = 400 ppm Supply air CO 2 level = X S = 645 ppm Return air CO 2 level = X R = 823 ppm XS) ( ) (178) Then % OA x100 % x100% x 100% 42.1% XO) ( ) (423) And we can try this equation out using temperature measurements, too. Let s say that these measurements are taken in cold climates in the winter: Outdoor air temperature = X O = 35 ºF Supply air temperature (before conditioning) = X S = 55 F Return air temperature = X R = 70 F XS) (70 55) 15 Then % OA x100 % x 100% x100% 42.9% XO) (70 35) 35 And we can try out the equation using summer temperature measurements as well: Outdoor air temperature = X O = 93 ºF Supply air temperature (before conditioning) = X S = 81 F Return air temperature = X R = 70 F XS) (70 81) ( 11) Then % OA x100 % 47.8% XO) (70 93) ( 23) To make sure the %OA measurement is done properly, the readings need to be taken at the appropriate locations. Outdoor air should always be taken away from the building exhaust vents. The location for supply and return may vary if the %OA value you are interested in getting is from using CO 2 or temperature. For CO 2, the return air reading should be taken inside the return duct or well before the air mixes with the outdoor air. These locations ensure a stable reading. The supply reading should be taken inside the supply duct. RA (RETURN AIR) DAMPER MOTOR X R RA DAMPER SUPPLY AIR FAN OA (OUTSIDE AIR) X S C H SA (SUPPLY AIR) C C OA DAMPER FILTER CHILLED WATER COIL HOT WATER COIL Illustration 1: Air Handling Unit Schematic If temperature is the measurement used, then the return air value should be taken as close to the air handling unit as possible before the air is mixed with outdoor air. In the illustration given, the return air temperature (X R ) would best be taken in the return air duct just upstream of the return air damper. The supply air should be measured before the air has been conditioned. Temperature measurements should also be taken before any fans, since a fan can increase the temperature up to a few degrees. In the illustration given, the supply air temperature (X S ) would best be taken between the filter and the chilled water coil. -3-
4 If the equation results in a negative percentage or a percent above 100%, then this is an equation error. If the supply air value does not fall between the return air value and the outdoor air value, then an error will occur. Typically, if all three measurements are retaken, the issue will resolve itself. If not, then consider which of the following might apply to the situation: If using temperature to calculate %OA: Air has been conditioned before measurement take measurement closer to the air handling unit. Supply air has been mixed with room air take supply measurement closer to diffuser or inside duct. Return air has not been mixed enough take return air measurement in duct to assure proper mixing. Outdoor and inside temperatures are too close to one another use CO 2 values as a base for %OA calculations. If using CO 2: Supply air is mixing with room air take measurement closer to diffuser or inside supply duct. Return air is not mixed well take measurement inside return duct. Outdoor air measurement is tainted make sure air entering outdoor air intake is fresh and clean. Not enough occupants to generate CO 2 use temperature values as a base for %OA calculations. When using a TSI IAQ-CALC TM or TH-CALC TM meter, the general procedure is to take a sample in each of four modes. The modes are return air, outdoor air, supply air, and %OA. Pressing the SAMPLE key while in %OA mode will store all four sample values. You may use the and keys to move from mode to mode. Press TEMP or CO 2 at any time to move from calculating %OA from TEMP to CO 2 or from CO 2 to TEMP. You may press the %OA key at any time to exit back to normal sampling. Details on the procedure are as follows: Note: You may press the %OA key at any time during the following procedure to exit without saving any data and to return to normal sampling. Press the %OA key once to put the instrument in return mode. The IAQ-CALC meter defaults to measuring %OA using CO 2 readings. To calculate %OA using temperature, press the TEMP key. Note: The TEMP key may be pressed at any time during this procedure to begin using temperature for the %OA calculation. In return air mode, RETURN will appear on the display. The current temperature or CO 2 value will display on the bottom line of the display. Previously taken values will display on the top line, or if this is the first time this mode has been used, ---- will display on the top line. Note: Do not breathe on the probe at any time during this process. CO2 concentrations in the breath are very high and this could significantly alter the results. Insert the probe into the return air duct, then press the SAMPLE key to take a sample once the reading has stabilized. Now the sampled value will display on the top line. If the sample is not acceptable or the reading is not yet stable, wait a minute and take another sample to overwrite the value on the top line. Once the top line value is acceptable, press the key to advance to outdoor air mode. Proceed to an outdoor location for the outdoor air sample. In outdoor air mode, OA will appear on the display along with the current reading on the bottom line. Previously taken values will display on the top line, or if this is the first time this mode has been used, ---- will display on the top line. Press the SAMPLE key once the reading has stabilized in the outdoor location. The sampled value for outdoor air will display on the top line with the current reading on the bottom line. If the sample is not acceptable or the reading is not yet stable, wait a minute and then take another sample to overwrite the value on the top line. Once the value is acceptable, press the key to advance to supply air mode. Move to the appropriate location for a supply sample and insert the probe into the supply duct. In supply mode, SUPPLY will appear on the display along with the current reading on the bottom line and ---- on -4-
5 the top line. Previously taken values will display on the top line, or if this is the first time this mode has been used, ---- will display on the top line. Press the SAMPLE key once the reading has stabilized. The sampled value for supply air will display on the top line with the current reading on the bottom line. If the sample is not acceptable or the reading is not yet stable, wait a minute and then take another sample to overwrite the value on the top line. Once the value is acceptable, press the key to advance to %OA mode. OA% will appear on the display along with the % outdoor air value. Press the SAMPLE key while in this mode to put all four samples into memory. Note: OA Err means that the calculation does not make sense with the values stored. Retake all 3 measurements or use another parameter to measure %OA. To make changes to one of the other three readings without putting them to memory, move to the appropriate location where the sample was taken, press the or keys to review the values and press SAMPLE to overwrite values if necessary. To make another % outdoor air calculation, make sure you pressed SAMPLE to save your current values. Then use and to review the measurements and take new samples for supply and return. If you suspect the outdoor air value has changed, you will have to retake that sample as well. Percent outdoor air can be calculated using either CO 2 or using temperature. There are some benefits to both of these methods and it s important to understand when to use one over the other. Generally, CO 2 should be used when the building that you are interested in has a lot of occupants. This ensures that the CO 2 concentration values of outdoor air and return air are far apart. If there are a sufficient number of occupants then outdoor air should always be the lowest value, and return air should always be the highest. The further these two values are apart, the more accurate the %OA value will be. If there are few or no occupants, then there is little accumulation of CO 2 and the accuracy will not be as good. Similarly, temperature should be used when the building or room of interest has a big difference in temperature from outdoor air temperatures. This means when it is hot or when it is cold outdoors, then it is a good time to use temperature as a means to calculate %OA. To take a temperature calculated %OA value, take the measurements at the Air Handling Unit. This means that the measurement will indicate the %OA for an entire area of the building, or the entire building depending on what area or areas the air handling unit serves. The reason the measurements need to be taken at the air handling unit is because there are often heating or cooling coils in the ducts or near the diffusers in some buildings which would adversely affect the readings and it is difficult to verify if they are present or not. This is a popular question and it does not have an easy answer. There is no ideal %OA value because it depends on the air flow. If your air flow is high for the number of occupants, you may not need a high %OA. For instance, if you are delivering 1,000 CFM and there are 10 occupants in an office area, you would only need 20% OA to achieve the ASHRAE recommended 20 CFM/person. (1,000CFM x 20%OA) /10 people = 20CFM/person However, if you are only delivering 250 CFM in this same scenario with 10 occupants in the same office area, you would need 80% OA to achieve the 20 CFM/person recommendation. (250CFM x 80%OA) / 10 people = 20 CFM/person -5-
6 There is no easy answer to this question because the answer varies with the air flow and the maximum number of occupants. The best thing to do is to measure the air flow and find the maximum number of people that will be in the room. Then the following equation can be used to find the %OA that would be needed: %OA = (CFM/person OA recommended x maximum number of occupants) / air flow As an example, consider an office space where 20 CFM/person of outdoor air is recommended, where the maximum number of occupants is 30 and the air flow is 1,800 CFM: %OA recommended = (20 CFM/person x 30) / 1,800 CFM = 33.3% outdoor air recommended To determine whether a building meets current ASHRAE recommendations of Outdoor Air, measure the volume of air entering a space as well as the %OA. Perhaps the easiest way to measure %OA is to take three samples of supply air, return air and outdoor air and to plug them into the given equation. TSI instruments will automatically do this calculation to save time. TSI was the first company to make instruments to do this calculation automatically and TSI continues to create and improve its instruments to meet the needs of the market. 1 TSI Application Note Traversing a Duct to Determine Average Air Velocity or Volume. TI-106. TSI, TSI logo, VELOCICALC, DP-CALC, ACCUBALANCE, IAQ-CALC, and TH-CALC are trademarks of TSI Incorporated. TSI Incorporated Visit our website for more information. USA Tel: UK Tel: France Tel: Germany Tel: India Tel: China Tel: Singapore Tel: TI-138 Rev. C 2013 TSI Incorporated Printed in U.S.A.
HVAC Systems and Indoor Air Quality. Douglas K. Spratt, M.Sc., P.Eng.
HVAC Systems and Indoor Air Quality Douglas K. Spratt, M.Sc., P.Eng. The 5 Senses Architecture Electrical Structural Mechanical Hearing Seeing Smelling Feeling Tasting HVAC Systems are Dynamic Heat Gains
THE LEADER IN PERFORMANCE INDOOR AIR QUALITY MEASUREMENTS
THE LEADER IN PERFORMANCE INDOOR AIR QUALITY MEASUREMENTS INDOOR AIR QUALITY INSTRUMENTS UNDERSTANDING, ACCELERATED BREATHE A LITTLE EASIER WITH TSI Indoor air quality is a growing concern. With the increasing
HVAC Systems in Schools & Commercial Buildings and Radon
HVAC Systems in Schools & Commercial Buildings and Radon References US EPA Radon Prevention in the Design and Construction of Schools and Other Large Buildings http://www.epa.gov/ordntrnt/ord/nrmrl/pubs/1993/air/
Why Measure Carbon Dioxide Inside Buildings? By Rich Prill, Washington State University Extension Energy Program
Why Measure Carbon Dioxide Inside Buildings? By Rich Prill, Indoor air quality Workers and students spend about half their waking hours at work or school. Therefore, maintaining adequate indoor air quality
Bring the fresh in. Dedicated Outside Air Systems
Bring the fresh in. Dedicated Outside Air Systems The inside story on outside air. On average, we breathe in 3,400 gallons of air each day. Ambient indoor air pollution is a major problem, affecting health
Climate solutions. evaporative cooling, adiabatic humidification and programmable controllers. energy saving solutions for data centers. carel.
Climate solutions evaporative cooling, adiabatic humidification and programmable controllers energy saving solutions for data centers carel.com Data center air-conditioning Data center air-conditioning
THE APPLICATION OF OZONE FOR AIR TREATMENT: CASE STUDY OF A BINGO HALL HVAC SYSTEM
1 Application Note AT-102 THE APPLICATION OF OZONE FOR AIR TREATMENT: CASE STUDY OF A BINGO HALL HVAC SYSTEM Lawrence B. Kilham 1 and Randall M. Dodd 2 1 Eco Sensors, Inc. Santa Fe, New Mexico, USA [email protected]
INDOOR AIR QUALITY ASSESSMENT
INDOOR AIR QUALITY ASSESSMENT Massachusetts Criminal Justice Training Council at the Boylston Town Offices Building 221 Main Street Boylston, Massachusetts Prepared by: Massachusetts Department of Public
Advanced Energy Design Guide LEED Strategies for Schools. and High Performance Buildings
Advanced Energy Design Guide LEED Strategies for Schools and High Performance Buildings Today s Presenters Stephen Koontz, LEED AP Energy Services Leader Tampa Bay Trane Allen Irvine General Sales Manager
NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES
NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES 8.1 INTRODUCTION Testing, adjusting, and balancing of HVAC systems can best be accomplished by following a series of systematic procedures. The NEBB TAB
White Paper: Free Cooling and the Efficiency of your Data Centre
AIT Partnership Group Ltd White Paper: Free Cooling and the Efficiency of your Data Centre Using free cooling methods to increase environmental sustainability and reduce operational cost. Contents 1. Summary...
INDOOR AIR QUALITY INTRODUCTION WHAT ARE THE SYMPTOMS OF SICK BUILDING SYNDROME? WHEN DID POOR INDOOR AIR QUALITY BECOME A PROBLEM?
INDOOR AIR QUALITY Public Employees Occupational Safety and Health Program Richard J. Codey Acting Governor November, 2004 INTRODUCTION The average person sends approximately 90% of their time indoors.
HVAC Checklist - Long Form
HVAC Checklist - Long Form Page 1 of 14 Appendix B discusses HVAC system components in relation to indoor air quality. utside Air Intake Location pen during occupied hours? Unobstructed? Standing water,
DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER
DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER DATA CENTERS 2009 IT Emissions = Aviation Industry Emissions Nations Largest Commercial Consumers of Electric Power Greenpeace estimates
Information paper 20. Prepared by: David Clark. book:
Information paper 20 Ventilation rates in offices and natural mechanical Prepared by: David Clark A paper referenced in the book: Cundall Johnston & Partners LLP. 2013 Issue 1.0: 29 July 2013 This information
Radford University. Indoor Air Quality Management Plan
Radford University Indoor Air Quality Management Plan Spring 2015 Introduction Concerns with Indoor Air Quality (IAQ) have increased since energy conservation measures were instituted in office buildings
UNIVERSITY OF MISSOURI 23 0000 - Heating Ventilating and Air-Conditioning (HVAC) March 2015.01
GENERAL: This section provides general standards for overall sizing and design of Heating, Ventilating, and Air Conditioning (HVAC) systems. Other sections contain specific standards for each system per
Innovent LASER Packaged Fresh Air Conditioning Units
LASER Latent And Sensible Energy Reduction Latent And Sensible Energy Reduction For Outside Air Innovent LASER Packaged Fresh Air Conditioning Units Innovent LASER units provide both sensible and latent
Modeling and Simulation of HVAC Faulty Operations and Performance Degradation due to Maintenance Issues
LBNL-6129E ERNEST ORLANDO LAWRENCE BERKELEY NATIONAL LABORATORY Modeling and Simulation of HVAC Faulty Operations and Performance Degradation due to Maintenance Issues Liping Wang, Tianzhen Hong Environmental
Mechanical and Natural Ventilation
BBSE3006: Air Conditioning and Refrigeration II http://www.hku.hk/bse/bbse3006/ Mechanical and Natural Ventilation Dr. Sam C. M. Hui Department of Mechanical Engineering The University of Hong Kong E-mail:
Energy Saving Fact Sheet Air Conditioning
Energy Saving Fact Sheet Air Conditioning Get your air conditioning into better shape Everyone wants air conditioning. But don t let your existing system, or one that you re considering installing, burn
Direct Fresh Air Free Cooling of Data Centres
White Paper Introduction There have been many different cooling systems deployed in Data Centres in the past to maintain an acceptable environment for the equipment and for Data Centre operatives. The
APPLICATION GUIDE. Comparison of Latent Cooling Performance of Various HVAC systems in a Classroom Application
APPLICATION GUIDE Comparison of Latent Cooling Performance of Various HVAC systems in a Classroom Application Section Comparison of Latent Cooling Performance of Introduction Most commercial HVAC systems
SECTION 23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION
SECTION 23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION The purpose of this guide specification is to assist the specifier in correctly specifying Mechanical System Testing
Venice Library Humidity Study. for Williams Building Diagnostics, LLC 305 15 th Street West Bradenton, FL 34205. Report April 13, 2015
for Williams Building Diagnostics, LLC 305 15 th Street West Bradenton, FL 34205 Report April 13, 2015 Moses & Associates, Inc. 2209 NW 40 th Terrace, Suite A Gainesville, FL 32605 FL License EB-0003097
CETA Application Guide for the Exhaust System Requirements of Class II, Type B Biosafety Cabinets CAG-007-2010 March 24, 2010
CETA Application Guide for the Exhaust System Requirements of Class II, Type B Biosafety Cabinets CAG-007-2010 March 24, 2010 1. Background Class II Type B Biosafety Cabinets (BSCs) are unique laboratory
CONTAMINATION CONTROL FOR ELECTRONIC AND SEMICONDUCTOR APPLICATIONS
CONTAMINATION CONTROL FOR ELECTRONIC AND SEMICONDUCTOR APPLICATIONS UNDERSTANDING, ACCELERATED TSI SETS THE STANDARD FOR PARTICLE COUNTING Performance Semiconductor, hard disk drive, and flat panel manufacturers
Impacts of Static Pressure Set Level on the HVAC Energy Consumption and Indoor Conditions
Impacts of Static Pressure Set Level on the HVAC Energy Consumption and Indoor Conditions M. Liu, Y. Zhu, D. E. Claridge Energy Systems Laboratory Texas A&M University Ed. White Energy Management Operation
Subpart 1. Installation. All plumbing systems must be. installed and tested according to this chapter and chapter 4715,
4658.4500 PLUMBING SYSTEMS; NEW CONSTRUCTION. Subpart 1. Installation. All plumbing systems must be installed and tested according to this chapter and chapter 4715, the Minnesota Plumbing Code. Subp. 2.
WORKSHEET FOR RESIDENTIAL AIR SYSTEM DESIGN page 1
WORKSHEET FOR RESIDENTIAL AIR SYSTEM DESIGN page 1 Wallet card photocopy Inspection Authority: Signature: Date: / / Submitted For: ( Owner ) Name Address City Prov Postal code Phone ( ) Fax ( ) Designer/Signature:
Enclosed Football Stadium Design History and Lessons Learned
Enclosed Football Stadium Design History and Lessons Learned Robert L. Towell, P.E., LEED AP, QCxP [email protected] CxE Group LLC St. Louis, Missouri 314-436-6543 With thanks to the St. Louis Convention
Indoor air quality monitoring made easy
Indoor air quality monitoring made easy with the Fluke 985 Particle Counter Application Note Introduction Energy savings is top of facilities owners agenda. HVAC system tends to be the largest contributor
Alerts and Delta T Diagnostics with the Prestige 2.0 IAQ Thermostat
Alerts and Delta T Diagnostics with the Prestige 2.0 IAQ Thermostat MOUNTING LOCATIONS Refer to the guidelines below and Fig. 1 5 for mounting locations of the Discharge and Return Air Temperature Sensors.
Integrating Kitchen Exhaust Systems with Building HVAC
Design Guide 3 Improving Commercial Kitchen Ventilation System Performance Integrating Kitchen Exhaust Systems with Building HVAC This design guide provides information that may help achieve optimum performance
Makeup Air For Exhaust Systems In Tight Houses. Tony Jellen Engineering Projects
Makeup Air For Exhaust Systems In Tight Houses Tony Jellen Engineering Projects PA Housing & Land Development Conference February 23, 2012 Effects of Kitchen Ventilation on Residential Dwellings Anthony
COMPARISON OF DIFFERENT HVAC SYSTEMS IN MULTI- STOREY APARTMENT BUILDINGS IN HELSINKI
Proceedings of Healthy Buildings 2000, Vol. 2 675 COMPARISON OF DIFFERENT HVAC SYSTEMS IN MULTI- STOREY APARTMENT BUILDINGS IN HELSINKI Mikko Saari 1, Juhani Laine 1, Sami Karjalainen 1 and Klaus Hamström
DRYER VENTING SPECIFICATIONS DRYER SAFETY
DRYER VENTING SPECIFICATIONS Table of Contents DRYER SAFETY...1 INSTALLATION REQUIREMENTS...4 Venting Requirements...5 DRYER INSPECTION AND CLEANING...7 Frequency of Exhaust System Cleaning...7 Inspecting
- White Paper - Data Centre Cooling. Best Practice
- White Paper - Data Centre Cooling Best Practice Release 2, April 2008 Contents INTRODUCTION... 3 1. AIR FLOW LEAKAGE... 3 2. PERFORATED TILES: NUMBER AND OPENING FACTOR... 4 3. PERFORATED TILES: WITH
Glossary of HVAC Terms
Glossary of HVAC Terms Heating, Ventilation and Air Conditioning (HVAC) is a major sub- discipline of mechanical engineering. The goal of HVAC design is to balance indoor environmental comfort with other
Energy Efficiency in Industrial HVAC Systems
Energy Efficiency in Industrial HVAC Systems Heating, ventilation and air conditioning (HVAC) constitutes up to 35 percent of energy used in manufacturing facilities. This fact sheet is geared towards
How To Design A Building In New Delhi
ENERGY EFFICIENT HVAC DESIGN FOR COMPOSITE CLIMATE Overview of Design Conditions: Air conditioning system consumes most of the energy that a building needs in its operation. In order to reduce energy consumption
ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE
ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE Overview of Design Conditions: Air conditioning system consumes most of the energy that a building needs in its operation. In order to reduce
Causes of High Relative Humidity Inside Air Conditioned Buildings. Roger G.Morse AIA, Paul Haas CSP, CIH Morse Zehnter Associates
Causes of High Relative Humidity Inside Air Conditioned Buildings Roger G.Morse AIA, Paul Haas CSP, CIH Morse Zehnter Associates S. FLORIDA AVE. AMBIENT 91 F db / 78 F wb 16,000 HOURS ANNUALLY THAT wb
Installation, operation and maintenance manual TX 35A
Installation, operation and maintenance manual TX 35A Rev.10 may 2012 Page 1 of 18 1.0.0 Table of contents INSTALLATION, OPERATION AND MAINTENANCE MANUAL...1 1.0.0 TABLE OF CONTENTS...2 2.0.0 ILLUSTRATIONS...2
Variable Air Volume - VAV
Mode Enable Sensor Options Variable Air Volume - VAV The temperature of this sensor will determine if the unit is in heating, cooling or vent mode during occupied operation. The following options are available:
Dr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida
Optimizing 100% Outside Air Systems with Heat Pipes Dr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida Introduction To meet increasingly rigorous building codes
Energy Efficient Server Room and Data Centre Cooling. Computer Room Evaporative Cooler. EcoCooling
Energy Efficient Server Room and Data Centre Cooling Computer Room Evaporative Cooler EcoCooling EcoCooling CREC Computer Room Evaporative Cooler Reduce your cooling costs by over 90% Did you know? An
SAM HOUSTON STATE UNIVERSITY
PART 1: GENERAL 1.01 General Requirements A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the
about your house How to Get the Ventilation That You Need in Your House Figure 1 Infiltration and exfiltration of air in a house
about your house CE 64 How to Get the Ventilation That You Need in Your House Canadian houses are relatively airtight, and have been for years. The old farmhouses where people lived several generations
Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks
Presentation Outline Common Terms / Concepts HVAC Building Blocks Plant Level Building Blocks Description / Application Data Green opportunities Selection Criteria Air Distribution Building Blocks same
CHAPTER 4 VENTILATION
CHAPTER 4 VENTILATION SECTION 401 GENERAL 401.1 Scope. This chapter, in conjunction with the building code, shall govern the ventilation of spaces within a building intended to be occupied. Mechanical
GREEN BAY AREA PUBLIC SCHOOL DISTRICT Board Policy Manual ENERGY MANAGEMENT
GREEN BAY AREA PUBLIC SCHOOL DISTRICT Board Policy Manual 733 ENERGY MANAGEMENT Energy management is necessary in order for the District to: minimize the impact energy cost increases will have on the budget,
GENERAL VENTILATION HSG202
GENERAL VENTILATION G U I D A N C E F O R E M P L O Y E R S HSG202 Crown copyright 2000 Applications for reproduction should be made in writing to: Copyright Unit, Her Majesty's Stationery Office, St.
HVAC Costs. Reducing Building. Building owners are caught between two powerful forces the need to lower energy costs. By Stephen J.
Reducing Building HVAC Costs of site rec By Stephen J. Pargeter Building owners are caught between two powerful forces the need to lower energy costs and the need to meet or exceed outdoor air ventilation
Power and Cooling for Ultra-High Density Racks and Blade Servers
Power and Cooling for Ultra-High Density Racks and Blade Servers White Paper #46 Introduction The Problem Average rack in a typical data center is under 2 kw Dense deployment of blade servers (10-20 kw
Kitchen Ventilation Systems: Part 2 Providing Adequate Makeup Air
The Pennsylvania Housing Research Center Kitchen Ventilation Systems: Part 2 Providing Adequate Makeup Air Builder Brief: April 2012 Anthony C. Jellen, PE & Brian M. Wolfgang, EIT, Michael A. Turns, MS
International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS
International Telecommunication Union ITU-T TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU Technical Paper (13 December 2013) SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES
AG-TQS-IAQ-00 March 4, 2002. Application Guide. TQS with IAQ Inlet
Application Guide TQS with IAQ Inlet Table of Contents Introduction 2 ASHRAE Standard 62 2 Outdoor Air Requirements For Ventilation For Commercial Buildings 3 EPA Report Energy Costs and IAQ Performance
Pool Dehumidification Basics
Copyright 2009 Wescor. All rights reserved. Permission granted to reproduce for personal and educational use only. When energy costs were low, many pool owners considered only first cost when choosing
HVAC Systems: Overview
HVAC Systems: Overview Michael J. Brandemuehl, Ph.D, P.E. University of Colorado Boulder, CO, USA Overview System Description Secondary HVAC Systems Air distribution Room diffusers and air terminals Duct
Design Guide. Retrofitting Options For HVAC Systems In Live Performance Venues
Design Guide Retrofitting Options For HVAC Systems In Live Performance Venues Heating, ventilation and air conditioning (HVAC) systems are major energy consumers in live performance venues. For this reason,
How to Measure HVAC System Airflow
How to Measure HVAC System Airflow About National Comfort Institute National Comfort Institute is an international training Since our and beginning development in 1994 company we have trained with and
HVAC Processes. Lecture 7
HVAC Processes Lecture 7 Targets of Lecture General understanding about HVAC systems: Typical HVAC processes Air handling units, fan coil units, exhaust fans Typical plumbing systems Transfer pumps, sump
USER S MANUAL HSC-24A
AIRREX AIR CONDITIONER USER S MANUAL HSC-24A Thank you for purchasing an AIRREX AIR CONDITIONER. BEFORE operation please read this user s manual carefully. Keep this manual readily available. It is ESSENTIAL
06150 PORVOO, FINLAND Pelican eco ED(D), Pelican eco EDE(D), Pelican eco EDW(D), Pelican eco EDX(D)
Certificate Certified Passive House Component For cool, temperate climates, valid until 31 December 2013 Passive House Institute Dr. Wolfgang Feist 64283 Darmstadt GERMANY Category: Manufacturer: Heat
Charles McCammon, Ph.D., CIH
This Health Hazard Evaluation (HHE) report and any recommendations made herein are for the specific facility evaluated and may not be universally applicable. Any recommendations made are not to to be considered
PRICE LIST Test & Balance Report TEST AND BALANCE REPORT Melink Corporation (513) 271-1615 www.melinkcorp.com
PRICE LIST Test & Balance Report TEST AND BALANCE REPORT HOW TO DETERMINE LIST PRICING Determining the price of Melink T&B services is as easy as 1-2-3. Simply determine the Air Conditioning Tons and Exhaust
Engineering White Paper UTILIZING ECONOMIZERS EFFECTIVELY IN THE DATA CENTER
Engineering White Paper UTILIZING ECONOMIZERS EFFECTIVELY IN THE DATA CENTER SUMMARY A proper balance of temperature and humidity control is essential for efficient data center operation, and integral
FAQ' s. Frequently Asked Questions. A1 Control Units. Pge 1 of 7 PUMPKIN HOOK ROAD PO BOX OGD VAN HORNESVILLE NY 13475 USA 315-858-1002
Frequently Asked Questions FAQ' s A1 Control Units Pge 1 of 7 Table of Contents Q-1 Who are OGD and V-HVAC? 3 Q-2 Why do I need the A1 Control Unit and what are the benefits? 3 Q-3 How is the A1 Control
How To Get A Passive House
Certificate Certified Passive House Component For cool, temperate climates, valid until 31 December 2015 Passive House Institute Dr. Wolfgang Feist 64283 Darmstadt GERMANY Category: Manufacturer: Product
ENHANCED LABORATORY HVAC SYSTEM
ENHANCED LABORATORY HVAC SYSTEM INTRODUCTION Since the early 1980's the attention to more energy efficient laboratory designs has been on the rise due to the increase in energy cost and the emergence of
Attached is a link to student educational curriculum on plug load that provides additional information and an example of how to estimate plug load:
Energy Conservation Tip #1 Always turn off all lights when you leave a room or when they are not needed. It is estimated that 26% of a building s electricity is used for lighting. For D-11 this equals
COMPARATIVE LIFE-CYCLE ANALYSIS OF ENERGY-EFFICIENCY MEASURES AT TVA S CHATTANOOGA OFFICE COMPLEX: PHASE II RESULTS & FINAL DESIGN
COMPARATIVE LIFE-CYCLE ANALYSIS OF ENERGY-EFFICIENCY MEASURES AT TVA S CHATTANOOGA OFFICE COMPLEX: PHASE II RESULTS & FINAL DESIGN Umesh Atre Innovative Design Inc 850 W Morgan St Raleigh, NC 27603 [email protected]
Free Cooling in Data Centers. John Speck, RCDD, DCDC JFC Solutions
Free Cooling in Data Centers John Speck, RCDD, DCDC JFC Solutions Why this topic Many data center projects or retrofits do not have a comprehensive analyses of systems power consumption completed in the
85 F 80 F 50% 75 F 70 F 73.0/61.8 45 F 10% Figure 1
Feb. 07 INTRODUCTION: Wrap around heat pipes are air-to-air heat exchangers that are installed in the airstream upstream and downstream of a cooling coil to deliberately reduce the Sensible Heat Ratio
Molds and mildew are fungi that grow
Appendix C: Moisture, Mold and Mildew Molds and mildew are fungi that grow on the surfaces of objects, within pores, and in deteriorated materials. They can cause discoloration and odor problems, deteriorate
Element D Services Heating, Ventilating, and Air Conditioning
Load Calculation Criteria PART 1 - GENERAL 1.01 OVERVIEW A. This section includes requirements for calculating HVAC cooling and heating loads. B. Load calculations must be performed in accordance with
HVACPowDen.xls An Easy-to-Use Tool for Recognizing Energy Efficient Buildings and HVAC Systems
HVACPowDen.xls An Easy-to-Use Tool for Recognizing Energy Efficient Buildings and HVAC Systems Fundamental Principles of Environmentally Responsible, Energy Efficient Buildings 1. Energy efficiency is
AIR CONDITIONING EFFICIENCY F8 Energy eco-efficiency opportunities in Queensland Foundries
AIR CONDITIONING EFFICIENCY F8 Energy eco-efficiency opportunities in Queensland Foundries Hot tips and cool ideas to save energy and money! Air conditioning units or systems are often used by foundries
Flexibility, Efficiency In San Antonio Arena
2005, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Reprinted by permission from ASHRAE Journal, (Vol. 47, No. 9, September 2005). This article may not
Subtropical Cities September 2006. Design for Energy Efficiency in Commercial Buildings in Queensland
Subtropical Cities September 2006 Design for Energy Efficiency in Commercial Buildings in Queensland Contents Typical Building Constraints & Requirements Understanding Energy Consumption in Buildings HVAC
air conditioners how to choose a cooling system
air conditioners how to choose a cooling system taking responsibility As an individual, your efficient use of energy brings benefits such as lower bills, improved comfort levels in your home and a reduced
CHAPTER 8 HVAC (Heating, Ventilation, and Air-Conditioning)
CHAPTER 8 HVAC (Heating, Ventilation, and Air-Conditioning) Objectives Survey current HVAC system(s), operating procedures, and maintenance schedule. Analyze results of energy audit for HVAC system(s)
Exhaust Calculation Booklet
Exhaust Calculation Booklet American Dryer Corporation 88 Currant Road Fall River MA 02720-4781 Telephone: (508) 678-9000 / Fax: (508) 678-9447 e-mail: [email protected] ADC Part No. 450450 Exhaust
APPLICATION GUIDE. Moisture Management in Waterborne Climate Systems
APPLICATION GUIDE Moisture Management in Waterborne Climate Systems Contents Introduction 3 WBCS Concept 3 Condensation 4 Moisture Sources in the Space 4 Impact of a High Moisture Load 5 Designing to Manage
PREMIUM CLEAN ROOM MONITOR MODELS 8630-CRM-S 8630-CRM-P
PREMIUM CLEAN ROOM MONITOR MODELS 8630-CRM-S 8630-CRM-P MANUAL SUPPLEMENT Contents of this manual supplement include: Sequence of Operation Menu Structure Description of New Software Items Deleted Software
ASTACEA4 Inspect complex/central air conditioning systems
Overview This Unit covers the competences required to inspect complex/central air conditioning systems as defined by the CIBSE TM 44 Figure 1.1: Summary of system types and their component parts. The air
QUESTIONS TO ASK WHEN REPLACING YOUR HVAC TOGETHERWESAVE.COM
QUESTIONS TO ASK WHEN REPLACING YOUR HVAC TOGETHERWESAVE.COM TOGETHERWESAVE.COM IS IT TIME TO REPLACE YOUR HVAC SYSTEM? If your heating and cooling system is 15 to 20 years old and is experiencing problems,
Answers to Your Questions from the Webinar
2008 Desert Aire and USA Swimming. Used by permission. Desert Aire & USA Swimming - Aquatics Webinar - Answers to Your Questions Answers to Your Questions from the Webinar Thank you for your interest in
KU DESIGN GUIDELINES APPENDIX XVI RECOMMENDED BAS I/O CONTROL POINTS BY EQUIPMENT / SYSTEM
KU DESIGN GUIDELINES APPENDIX XVI RECOMMENDED BAS I/O CONTROL POINTS BY EQUIPMENT / SYSTEM AIR HANDLING UNITS... 1 CHILLERS... 2 COOLING TOWERS... 2 CLOSED LOOP COOLERS... 2 MISCELLANEOUS SUPPLY FANS...
Energy Efficiency HOSPITALITY. www.energia.ie
Energy Efficiency HOSPITALITY www.energia.ie Your chance to reduce your business energy usage by as much as 20%! 20% is a significant figure and reducing your energy bill by this amount could make a real
Benefits of. Air Flow Management. Data Center
Benefits of Passive Air Flow Management in the Data Center Learning Objectives At the end of this program, participants will be able to: Readily identify if opportunities i where networking equipment
Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings
WHITE PAPER Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings By Lars Strong, P.E., Upsite Technologies, Inc. Kenneth G. Brill, Upsite Technologies, Inc. 505.798.0200
IAQ - indoor ventilation Air contaminants Molds Requirements for growth Health effects Mold prevention - moisture EH&S mold checks & removal
Indoor Air Quality & Mold Class Spring 2012 Building Monitors Meeting Presentation Agenda IAQ - indoor ventilation Air contaminants Molds Requirements for growth Health effects Mold prevention - moisture
Best Practices in HVAC Design/Retrofit
Best Practices in HVAC Design/Retrofit Little Server Room BIG $AVINGS Justin Lewis, P.E., LEED AP, DCEP Sr Energy Project Manager C:530.400.6042 O:530.754.4870 [email protected] 1 What s the problem here?
for K-12 School Buildings
Advanced Energy Design Guide for K-12 School Buildings HVAC Section John Murphy Applications Engineer, LEED AP Trane La Crosse, Wisconsin [email protected] www.trane.com AEDG-K12 HVAC Subcommittee John
Building Re-Tuning Training Guide: AHU Heating and Cooling Control
Building Re-Tuning Training Guide: AHU Heating and Cooling Control Summary The purpose of the air-handling unit (AHU) heating and cooling control guide is to show, through examples of good and bad operations,