1 Guidelines for Specifying Data Center Criticality / Tier Levels White Paper 122 Revision 2 by Victor Avelar > Executive summary A framework for benchmarking a future data center s operational performance is essential for effective planning and decision making. Currently available or tier methods do not provide defensible specifications for validating data center performance. An appropriate specification for data center should provide unambiguous defensible language for the design and installation of a data center. This paper analyzes and compares existing tier methods, describes how to choose a level, and proposes a defensible data center specification. Maintaining a data center s is also discussed. Contents Click on a section to jump to it Introduction 2 Common classification methods Balanced 5 Suggested approach for choosing Specifying and verifying Maintaining a specified Conclusion 9 Resources 10 Appendix 11 white papers are now part of the Schneider Electric white paper library produced by Schneider Electric s Data Center Science Center [email protected]
2 Introduction Terms like availability, reliability, mean time between failure (MTBF), and others are oftentimes used interchangeably to describe data center performance. These terms are quantitative measures of performance that are difficult for data center managers to calculate. An alternative and simplified approach is to categorize data center performance in tiers or levels. This paper proposes that the term be used to subjectively describe data center performance. A data center s has arguably the strongest influence on lifetime total cost of ownership (TCO). For example, a fully redundant (2N) power architecture could more than double the 10-year TCO of a non-redundant (1N) power architecture. Although a significant cost penalty for 2N power is the doubling of electrical equipment capital costs, the greater impact comes from the energy costs associated with operating and maintaining the power equipment at 2N. Therefore, when choosing a data center s, a data center designer or owner needs to weigh both the costs and the in order to establish a true cost / benefit analysis. This paper describes and compares three common methods for specifying data center. Guidance is given on how to choose a by presenting typical levels for various applications and environments. Defensible approaches for specifying data center performance are discussed. Data center project planning In a data center construction or upgrade project, it is the first half of the process the planning portion that offers the greatest opportunity for errors and oversights and is when a data center s should be specified. 1 (See Figure 1) Specifically, a needs assessment identifies and quantifies the constraints and preferences related to the data center plan. A specification is then generated that satisfies these constraints and preferences. When the specification is agreed upon, a detailed design can proceed and finally be implemented. Once the data center is built it can be validated against the specification. Validation against a specification allows legal recourse against substandard or deceptive workmanship. Related resource White Paper 142 Data Center Projects: System Planning Choosing a data center s represents a major decision in the planning process since it impacts so many other decisions especially for green-field projects including location, building type, fire suppression, security system, and many others. The planning phase allows designers to balance the TCO of a data center with the preferences and constraints of a business s availability requirements. It is through this iterative planning exercise that a final is specified. The subject of data center planning is discussed further in White Paper 142, Data Center Projects: System Planning. 1 Excerpted from White Paper 142, Data Center Projects: System Planning, 2007 (link in Resources section at end of paper) Schneider Electric Data Center Science Center White Paper 122 Rev 2 2
3 C 1 C 2 C 3 C 4 A level is chosen based on a balance between the cost of downtime to a business and the TCO of the infrastructure required to support a given. Criticality Capacity Growth plan Figure 1 Choosing a is a key step in the system planning Reference design Room Identify needs Preferences Constraints COMPLETE SYSTEM SPECIFICATION DETAILED DESIGN Common classification methods Historically, the performance of a data center depended largely on the people involved in the design process. To craft a solution, individuals generally fell back on unique personal experiences, anecdote, hearsay, and legend, placing special emphasis on the design attributes that they historically understood were the most important drivers of downtime. The result is enormous variation in data center designs, even when the same requirements are stated. This has prompted the development of various or tier categories to help specify the availability and reliability performance of data center designs. Specification of data center performance becomes easier by having simple categories of design architectures that can be benchmarked against each other. There have been various methods introduced throughout the mission critical facility industry some better known than others. Three more commonly known methods are The Uptime Schneider Electric Data Center Science Center White Paper 122 Rev 2 3
4 Institute s Tier Data Center Site Infrastructure Tier Standard, TIA 942, and Syska Hennessy Group s Criticality Levels. The Uptime Institute s Data Center Site Infrastructure Tier Standard 2 Though not a standards body, The Uptime Institute pioneered its tier classification method in 1995 and has become widely referenced in the data center construction industry. Uptime s standard includes four tiers; Tier 1 through Tier 4, which have evolved over the years through various data center projects. This standard provides a high level guideline but does not provide specific design details for each Tier. TIA 942 The four tier levels described in TIA 942 revision 5 are based on Uptime Institute s Tier Standard. Although 942 is a standard, the four tier levels described in appendix G are informative and not considered to be requirements of this Standard 3. Nonetheless, appendix G does provide specific design criteria that can help designers build to a specific tier level and allows data center owners to evaluate their own design. Syska Hennessy Group s Criticality Levels Syska s ten levels build on Uptime s four tiers by considering recent data center trends such as high density computing and flexible architectures. Although the Syska method includes ten levels, it maps the first of its ten levels to Uptime s four tiers 4. Syska also includes more comprehensive elements that evaluate the maintenance and operation of a data center and not just the upfront components and construction. In addition, they pioneered the balance sheet approach to data center levels by recognizing that data center performance is only as strong as its weakest element. Syska s Criticality Levels are described at a high level and lack the specificity of TIA-942. Comparison of methods Overall, all three methods support the idea that there are four common levels, numbered (1, 2, 3, and 4) of / tiers commonly used today. The biggest problem encountered with the Uptime method and Syska method, is the lack of detail needed to articulate the differences between levels. The TIA-942, in contrast, provides specific details at every tier level and across a wide range of elements including telecom, architectural, electrical, mechanical, monitoring, and operations. For example, the TIA-942 specifies that a tier 2 data center should have two access provider entrance pathways that are at least 20 m (66 ft) apart. Syska also specifies that a tier 2 data center should have two entrance pathways but adds no other detail. Publicly available Uptime documentation does not provide guidance for access provider entrance pathways. Syska Hennessy Group first explained the importance of balancing the levels of the various systems that make up a data center. Uptime later discussed this concept of balancing in its 2006 standard. Overall, based on the available literature, no major design practices from these methods conflict with each other. For a full comparison of these three methods against various characteristics see Table A1 in the appendix of this paper. Ultimately, these three organizations, and others like them, have advanced the data center industry towards a higher level of performance. Difference between shall and should It is important to understand that a data center manager cannot verify compliance against any of the methods described above. In order to verify compliance, and be legally defensible, detailed specifications are required. Specifications for a level 1, 2, 3, or 4 data center project 2 Turner, Seader, Renaud, Data Center Site Infrastructure Tier Standard: Topology, TIA-942, Telecommunications Infrastructure Standard for Data Centers, April 2005, p Syska Hennessy Group, Inc., Syska Criticality Level Definitions, April 2005, p. 13 Schneider Electric Data Center Science Center White Paper 122 Rev 2 4
5 set a requirement for how the final data center performs. In order for specifications to hold up in the court of law, they must use the word shall or must rather than should. The word should or may conveys a recommendation and is not legally binding. The word shall or must conveys an action that is binding and legally defensible. This is the type of specification language that allows a data center manager to legally verify and mandate that their data center is in compliance with the design specifications. For example, assume a contractor was hired to convert a conference room into a 2 data center; the bulleted specification below would apply. If the contractor were using specification 1a and did not remove all the windows (assuming windows weren t required by safety code), the contractor would be legally held responsible for removing the windows. If specification 1b were used, there would be no legal recourse for the data center owner. 1a. Data center shall have no exterior doors or exterior windows, unless required by safety code. 1b. Data center should have no exterior doors or exterior windows, unless required by safety code. In the case of Syska literature, there are no formal specifications as in the example above, nor does the literature use the word shall or must. Although TIA does provide some detailed specifications, they use the word should instead of shall. For example Tier 3 installations should meet all requirements of tier 2. Balanced When specifying a data center s, all attributes should be considered as links in a chain and that the overall data center performance is only as strong as its weakest link. Syska Hennessy developed this notion of a comprehensive balance between all parameters in their Criticality Levels approach. A very serious pitfall in designing data centers is that the investments are imbalanced, and great expense is invested in one area of data center design while another area is overlooked. Oftentimes decisions are made to enhance the availability of a particular system without giving thought to other systems in a data center. A classic example is spending a disproportional amount of engineering focus and expense on the UPS system compared to cooling and security systems. This oversight creates false expectations because IT managers believe their entire data center is at the same level of as the UPS only to be disappointed when a security breach results in downtime. Without the ability to find and quantify the weak link, data centers provide sub-optimal business results. However, there are instances when it is appropriate to over-specify the of a particular system. For example, a 1 may be all that is required for a remote data center. Yet, the IT manager may require a 3 for the management system to allow control and monitoring of systems that are not easily reachable by other personnel. In another example, a manager may require a 2 data center which calls for a single power path. However, due to a high likelihood of human error taking down the power system, the manager may opt for a 3 or 4 power path which includes dual (2N) power paths. Suggested approach for choosing Choosing an optimal is a balance between a business cost of downtime and a data center s total cost of ownership. However, the choices may be limited depending on whether a new data center is being built, or changes are being made to an existing one. In reviewing the available literature, it is clear that all three methods discussed in the previous section share a common understanding of what it means to be a / tier level 1, 2, 3, or 4. Table 1 provides business characteristics for each and the overall effect on system design. Schneider Electric Data Center Science Center White Paper 122 Rev 2 5
6 Table 1 Summary of criticalities Criticality Business characteristics Effect of system design 1. (Lowest) (Highest) Typically small businesses Mostly cash-based Limited online presence Low dependence on IT Perceive downtime as a tolerable inconvenience Some amount of online revenue generation Multiple servers Phone system vital to business Dependent on Some tolerance to scheduled downtime World-wide presence Majority of revenue from online business VoIP phone system High dependence on IT High cost of downtime Highly recognized brand Multi-million dollar business Majority of revenues from electronic transactions Business model entirely dependent on IT Extremely high cost of downtime Numerous single points of failure in all aspects of design No generator if UPS has 8 minutes of backup time Extremely vulnerable to inclement weather conditions Generally unable to sustain more than a 10 minute power outage Some redundancy in power and cooling systems Generator backup Able to sustain 24 hour power outage Minimal thought to site selection Vapor barrier Formal data room separate from other areas Two utility paths (active and passive) Redundant power and cooling systems Redundant service providers Able to sustain 72-hour power outage Careful site selection planning One-hour fire rating Allows for concurrent maintenance Two independent utility paths 2N power and cooling systems Able to sustain 96 hour power outage Stringent site selection criteria Minimum two-hour fire rating High level of physical security 24/7 onsite maintenance staff Greenfield data center projects Building a new data center presents few constraints to choosing a data center. Generally this decision comes down to what type of business the data center is supporting. Choosing a associated with a critical business characteristic provides a fairly accurate and easy starting point. Table 2 provides costs estimates for each level of. 5 It is important understand the assumptions behind these costs estimates. Table 3 associates various business applications with specific criticalities. Table 2 Estimated construction costs for each level of Fit out of physical infrastructure i.e. power, cooling ( $ / watt ) Land Item C1 C2 C3 C4 $11.5 $12.5 $25 $28 Strongly dependent on location Building core and shell ($ / ft2 ) [ $ / m2 ] $300 [$2,880] 5 Turner, Brill, Cost model: Dollars per kw plus Dollars per Square Foot of Computer Floor, White paper available at Schneider Electric Data Center Science Center White Paper 122 Rev 2 6
7 Table 3 Typical levels of for different applications Applications C1 C2 C3 C4 Descriptions Professional services Construction & engineering Branch office (financial) Point of sale Customer Resource Management (CRM) 7x24 support centers University data center Enterprise Resource Planning (ERP) Online hospitality & travel reservations Local real time media Online data vaulting and recovery Insurance Work-in-progress tracking (manufacturing) Global real time media Voice over IP (VoIP) Online banking Hospital data center Medical records Global supply chain E-commerce Emergency call center Energy utilities Electronic funds transfer Global package tracking Securities trading and settlement Consulting, property management Mission critical facility designers Local neighborhood bank office Department store, home goods Customer data Dell customer service Online assignments, , tuition Business dashboards, metrics Online airline ticketing Local news channel Consumer and company backup Auto and home insurance Automobile manufacturer Nationwide news show Converged network Checking, bill pay, transfers Hospital in metropolitan area Health insurance Jetliner manufacturer Online book store 911 (U.S), 112 (E.U.) Electric, gas, water Credit cards, electronic checks Letters, parcels, freight Equities, bonds, commodities Schneider Electric Data Center Science Center White Paper 122 Rev 2 7
8 Existing data center projects In general, for existing data center projects (i.e. retrofit), choosing a is limited to the constraints of the existing structure. For example, if an existing structure is located in a 100- year flood plain, it could not be a 2 data center. Those responsible for articulating the proposed data center must first identify the major constraints, such as this one, and decide if the resulting data center is an acceptable risk to the business. In this case, if a 1 data center is too risky, then the constraint could be removed by choosing an alternate location that allowed for a 2 data center. Specifying and verifying Once a has been chosen, the next steps are to specify the, build the data center, and validate it against the specification. Validation against a specification allows legal recourse against substandard or deceptive workmanship. Simply choosing a Criticality Level from Syska, or some other organization, does not constitute a verifiable and defensible specification. These are methods of categorizing data center performance and do not include detailed specifications written in shall or must language against which a constructed data center can be validated. If a data center was specified by choosing a particular level or tier, verifying that the as-built data center meets that level or tier is impossible without the creators of the method verifying it themselves. A verifiable and defensible specification would allow anyone to validate a data center. In general, a data center specification describes the essential requirements of performance, interoperability, and best practice that will allow all physical infrastructure elements to work together as an integrated whole. An effective specification is void of detailed descriptions of specific products and instead defines a data center by using unambiguous, point-by-point specification of its physical systems in combination with a standardized process for executing the steps of its deployment. The baseline specifications should describe a 1 data center, and provide additional specifications identifying higher level numbers (i.e. 2, 3, and 4). Higher level specifications should be clearly labeled with some kind of symbol to alert the reader. The numbered bullets below show an example of a baseline specification item followed by its associated high-level item. The symbol C3+ indicates that the specification applies to both 3 and Generator(s) installed outdoors shall be sheltered by an enclosure. 2. Walk-in enclosures shall house all generator mechanical, electrical, and fuel systems. C 3+ Business managers that are beginning a data center project can obtain a data center specification in several ways. If the business has a corporate real estate department, it may have personnel with experience in designing and building data centers. These individuals could create a data center specification described above. Architectural & engineering firms that specialize in critical facilities, such as Syska Hennessy Group, can create a data center specification for businesses that do not possess this expertise in house. Alternatively, businesses that are planning a small to medium sized data center project and are able to adopt standardized specifications, can obtain a complete specification for little to no cost. An example of a specification meeting the requirements above is Schneider Electric s Small / Medium Data Center System Specification and Project Manual. Schneider Electric Data Center Science Center White Paper 122 Rev 2 8
9 Maintaining a specified Even after building a data center and validating it against a defensible specification, it is possible and probable that the data center will fall below the it is was originally designed for. Over time, changes in business initiatives, technology, personnel, and management, all contribute to this problem. For example, many companies have migrated to higher density IT equipment to conserve floor space, which has led to the loss of cooling redundancy. As rack power densities increase, the redundant capacity of data center cooling units is used instead to provide additional airflow to these high density racks. Even redundant power architectures are susceptible to being demoted from N+1 to 1N due to IT refreshes. Unless physical infrastructure systems are monitored by a capacity management system, it becomes increasingly difficult to maintain a specified. Capacity management systems provide trending analysis and threshold violation information on parameters such as redundancy, air temperature, power distribution, runtime, battery voltage, and any others that affect a data center s over time. This ensures adequate advance notice and information necessary for procurement and deployment of additional capacity. In fact, a data center cannot achieve a of 4 unless it is monitored by a capacity management system. Large enterprises usually have a building management system (BMS) which can serve as a capacity management system. For smaller businesses, a centralized physical infrastructure management platform can provide capacity management at a lower price per data point. An example a centralized management platform with capacity management is StruxtureWare Central. Conclusion One of the key inputs to planning a data center is. Conventional or tier methods for specifying and validating data center performance are ambiguous and indefensible because they lack detailed specifications. An effective specification for data center should provide unambiguous defensible language using the word shall or must. It is with this type of specification that the as-built of a data center can be validated. Given the rate of IT refreshes, it is equally important to maintain a data center s over time. A capacity management system can monitor and track changes to a data center s physical infrastructure and notify managers when a data center s falls below thresholds. About the author Victor Avelar is a Senior Research Analyst at Schneider Electric. He is responsible for data center design and operations research, and consults with clients on risk assessment and design practices to optimize the availability and efficiency of their data center environments. Victor holds a Bachelor s degree in Mechanical Engineering from Rensselaer Polytechnic Institute and an MBA from Babson College. He is a member of AFCOM and the American Society for Quality. Schneider Electric Data Center Science Center White Paper 122 Rev 2 9
10 Resources Click on icon to link to resource Data Center Projects: System Planning White Paper 142 Browse all white papers whitepapers.apc.com Browse all TradeOff Tools tools.apc.com Contact us For feedback and comments about the content of this white paper: Data Center Science Center If you are a customer and have questions specific to your data center project: Contact your Schneider Electric representative Schneider Electric Data Center Science Center White Paper 122 Rev 2 10
11 Appendix Characteristic TIA / EIA 942 Uptime tiers Available defensible specifications to validate a data center design Offers guidelines but are not written in defensible language No specifications but Uptime reserves the right to determine Tier ranking and to certify sites as meeting Tier requirements Syska levels No specifications but Syska uses evaluation teams to assign the level to data centers Balance of Based on weakest infrastructure component or system Based on weakest infrastructure component or system Based on weakest infrastructure component or system IT processes used in determination of rating No No Used in level evaluation Table A1 Comparison of three approaches Floor loading capacity used in determination of rating Maintenance processes (documentation upkeep and organization) used in determination of rating Yes No No Not used Used in verification of site sustainability but not part of the site infrastructure Tier classification Used in level evaluation Site selection Discussed in depth in annex F as part of the overall tier guidelines Used in verification of site sustainability but not part of the site infrastructure Tier classification but provides no written guidance Used in level evaluation but provides no written guidance Issued by an official standards body Yes No No Discrepancies between methods Utility entrance Requires two utility services in Tier 3, and 4 Independent of utility services 6 Level 3 and 4 Inconsistent with TIA and Uptime Redundant IT power inputs Required in Tier 2, 3, and 4 Required in Tier III and IV Required in Level 3 and 4 (i.e. Tier 3 and 4) Standby power (generator) Required for all Tiers Required for all Tiers Not required for Level 1 (i.e. Tier 1) 2N CRAC / CRAH unit redundancy Required in Tier 4 Unknown Required in Level 4 Note: Shading indicates best performance for the characteristic 6 Not based on component count but whether data center can withstand concurrent maintenance Schneider Electric Data Center Science Center White Paper 122 Rev 2 11
Guidelines for Specifying Data Center Criticality / Tier Levels
Guidelines for Specifying Data Center Criticality / Tier Levels By Victor Avelar White Paper #122 Executive Summary A framework for benchmarking a future data center s operational performance is essential
plantemoran.com {Data center. } Design standards
plantemoran.com {Data center. } Design standards IT systems have become critical for the day-to-day operations of today s organizations. {Data center.} Design standards IT systems are critical for the
The Data Center Tier Performance Standards and Their Importance to the Owner s Project Requirements
The Data Center Tier Performance Standards and Their Importance to the Owner s Project Requirements Edward P Rafter, P.E. CxAP Tier IV Consulting Group Synopsis The data center industry has experienced
How To Calculate Total Cooling Requirements For Data Center
Calculating Total Cooling Requirements for Data Centers White Paper 25 Revision 3 by Neil Rasmussen > Executive summary This document describes how to estimate heat output from information technology (IT)
Presented by Edward P. Rafter, P.E., CxAP Tier IV Consulting Group
Presented by Edward P. Rafter, P.E., CxAP Tier IV Consulting Group The data center industry has experienced several evolutions over the past 20 years. One principal change has been the development of the
Avoiding Costs from Oversizing Data Center and Network Room Infrastructure
Avoiding Costs from Oversizing Data Center and Network Room Infrastructure White Paper 37 Revision 7 by Neil Rasmussen > Executive summary The physical infrastructure of data centers and network rooms
Avoiding Costs from Oversizing Data Center and Network Room Infrastructure
Avoiding Costs from Oversizing Data Center and Network Room Infrastructure White Paper 37 Revision 6 by Neil Rasmussen > Executive summary The physical and power infrastructure of data centers and network
A Quick Primer on Data Center Tier Classifications
A Quick Primer on Data Center Tier Classifications What You Should Know Before Starting a Data Center Project White Paper Abstract Data center facility projects are often driven by the Uptime Institute
Building a Tier 4 Data Center on a Tier 1 Budget
Building a Tier 4 Data Center on a Tier 1 Budget A Walk Through of TIA-942 Peter P. Charland III, RCDD/NTS/WD, CET RTKL Associates Inc. March 27, 2008 BICSI South Central Region Meeting Denver, CO TIA-942
Dynamic Power Variations in Data Centers and Network Rooms
Dynamic Power Variations in Data Centers and Network Rooms White Paper 43 Revision 3 by James Spitaels > Executive summary The power requirement required by data centers and network rooms varies on a minute
Guidance for Calculation of Efficiency (PUE) in Data Centers
Guidance for Calculation of Efficiency (PUE) in Data Centers White Paper 158 Revision 1 by Victor Avelar > Executive summary Before data center infrastructure efficiency can be benchmarked using PUE or
Types of Prefabricated Modular Data Centers
Types of Prefabricated Modular Data Centers White Paper 165 Revision 0 by Wendy Torell Executive summary Data center systems or subsystems that are preassembled in a factory are often described with terms
Guidance for Calculation of Efficiency (PUE) in Data Centers
Guidance for Calculation of Efficiency (PUE) in Data Centers White Paper 158 Revision 3 by Victor Avelar Executive summary Before data center infrastructure efficiency can be benchmarked using PUE or other
Power to the adaptable data center
Business Unit Manager, Data Center Solutions, Eaton s electrical group IT managers have more options than ever to tailor the power infrastructure to their unique data center and business requirements.
COMMODITIZING THE DATACENTER. Exploring the Impacts of the Shift to Virtualization and Cloud Computing
COMMODITIZING THE DATACENTER Exploring the Impacts of the Shift to Virtualization and Cloud Computing 3/5/2015 AGENDA Changing Environments What Is The Datacenter Why Do We Use Them Adapting To A Changing
Data Center Site Infrastructure Tier Standard: Topology
U P T I M E I N S T I T U T E, L L C Data Center Site Infrastructure Tier Standard: Topology Prepared by Uptime Institute Professional Services, LLC Copyright 2009-2012 by Uptime Institute, LLC 20 West
Data Centre Outsourcing a Buyer s Guide
Data Centre Outsourcing a Buyer s Guide The inside guide to deciding whether to outsource your data centre facility and operations and how to select an appropriate partner. This Guide will help you Determine
Enabling an agile Data Centre in a (Fr)agile market
Enabling an agile Data Centre in a (Fr)agile market Phil Dodsworth Director, Data Centre Solutions 2008 Hewlett-Packard Development Company, L.P. The information contained herein is subject to change without
Power and Cooling Guidelines for Deploying IT in Colocation Data Centers
Power and Cooling Guidelines for Deploying IT in Colocation Data Centers White Paper 173 Revision 0 by Paul Lin and Victor Avelar Executive summary Some prospective colocation data center tenants view
TIA-942 Data Centre Standards Overview WHITE PAPER
TIA-942 Data Centre Standards Overview WHITE PAPER TIA-942 Data Centre Standards Overview For the past 20 years, cabling standards have been the cornerstone of ensuring proper design, installation, and
Data Center Site Infrastructure Tier Standard: Topology
U P T I M E I N S T I T U T E, L L C Data Center Site Infrastructure Tier Standard: Topology Prepared by Uptime Institute Professional Services, LLC Copyright 2010 by Uptime Institute, LLC 20 West 37th
Top 10 Mistakes in Data Center Operations: Operating Efficient and Effective Data Centers
Top 10 Mistakes in Data Center Operations: Operating Efficient and Effective Data White Paper 2 Revision 0 by Bob Woolley > Executive summary How can you avoid making major mistakes when operating and
Colocation. Scalable Solutions for a Shared IT Infrastructure. Enterprise. Colocation
Scalable Solutions for a Shared IT Infrastructure Global and domestic competition, rising real estate and power costs, and shrinking IT budgets are causing today s businesses to seek alternatives to building
Calculating Total Power Requirements for Data Centers
Calculating Total Power Requirements for Data Centers By Richard Sawyer White Paper #3 Executive Summary Part of data center planning and design is to align the power and cooling requirements of the IT
Subject: County of Los Angeles Data Center Space Requirement
Subject: County of Los Angeles Data Center Space Requirement The County of Los Angeles, Chief Executive Office, Real Estate Division (CEO-RED) is issuing this Property Search for the purchase of a vacant,
Redundancy and Reliability for an HPC Data Centre
Available online at www.prace-ri.eu Partnership for Advanced Computing in Europe Redundancy and Reliability for an HPC Data Centre Erhan Yılmaz* 1 Ladina Gilly** 2 * National High Performance Computing
Determining Total Cost of Ownership for Data Center and Network Room Infrastructure
Determining Total Cost of Ownership for Data Center and Network Room Infrastructure White Paper #6 Revision 3 Executive Summary An improved method for measuring Total Cost of Ownership of data center and
Data Center Projects: System Planning
Data Center Projects: System Planning By Neil Rasmussen Suzanne Niles White Paper #142 Business NEED Detailed DESIGN Executive Summary System planning is the Achilles heel of a data center physical infrastructure
Data Center Physical Infrastructure: Optimizing Business Value
Data Center Physical Infrastructure: Optimizing Business Value White Paper 117 Revision 1 by Wendy Torell > Executive summary To stay competitive in today s rapidly changing business world, companies must
Which Data Center? Key factors in choosing who to trust with your IT Infrastructure
Which Data Center? Key factors in choosing who to trust with your IT Infrastructure Tarif Abboushi Vice-President of Data Center Infrastructure NTT America May, 2009 Which Data Center? Key factors in choosing
Essential NCPI Management Requirements for Next Generation Data Centers
Essential NCPI Requirements for Next Generation Data Centers By Ted Ives White Paper #14 1 Executive Summary The management of physical infrastructure in data centers can no longer be considered independently
How Row-based Data Center Cooling Works
How Row-based Data Center Cooling Works White Paper 208 Revision 0 by Paul Lin and Victor Avelar Executive summary Row-based data center cooling is normally regarded as a cold air supply architecture that
STATEMENT OF. Dr. David McClure Associate Administrator Office of Citizen Services and Innovative Technologies General Services Administration
STATEMENT OF Dr. David McClure Associate Administrator Office of Citizen Services and Innovative Technologies General Services Administration BEFORE THE HOUSE COMMITTEE ON OVERSIGHT AND GOVERNMENT REFORM
Backup and Redundancy
Backup and Redundancy White Paper NEC s UC for Business Backup and Redundancy allow businesses to operate with confidence, providing security for themselves and their customers. When a server goes down
Upgrading the PRS datacentres: space requirement. S. S. Mathur, GM-IT, CRIS
Upgrading the PRS datacentres: space requirement S. S. Mathur, GM-IT, CRIS PRS / UTS scenario: then and now Year 2000 PRS: 600 locations UTS: 0 locations Year 2008 PRS 1600 locations E-ticketing Passengers
Data center outages impact, causes, costs, and how to mitigate
Data center outages impact, causes, costs, and how to mitigate Data centers sometimes fail. You can build in safeguards and fail safe mechanisms and redundancy through backup systems but like all engineered
Colocation. Scalable Solutions for Shared IT Infrastructure. Enterprise. Colocation
Scalable Solutions for Shared IT Infrastructure Global competition, rising real estate and power costs, and shrinking IT budgets are causing today s businesses to seek alternatives to building their own
Reducing Data Center Energy Consumption
Reducing Data Center Energy Consumption By John Judge, Member ASHRAE; Jack Pouchet, Anand Ekbote, and Sachin Dixit Rising data center energy consumption and increasing energy costs have combined to elevate
Designing Fault-Tolerant Power Infrastructure
Designing Fault-Tolerant Power Infrastructure System Analysis and New Standards Enable Maximization of Operating Dependability for Data Centers & Other Mission Critical Facilities J.F. Christin (Author)
A Framework for Developing and Evaluating Data Center Maintenance Programs
A Framework for Developing and Evaluating Data Center Maintenance Programs White Paper 178 Revision 0 by Bob Woolley > Executive summary Inadequate maintenance and risk mitigation processes can quickly
IT White Paper IP TELEPHONY AND RELIABILITY: PROTECTING MISSION-CRITICAL PHONE SYSTEMS FROM POWER THREATS
IT White Paper IP TELEPHONY AND RELIABILITY: PROTECTING MISSION-CRITICAL PHONE SYSTEMS FROM POWER THREATS Executive Summary IT managers who are used to implementing power protection for IT network or data
Data Center Colocation Build vs. Buy
Data Center Colocation Build vs. Buy Comparing the total cost of ownership of building your own data center vs. buying third-party colocation services Executive Summary As businesses grow, the need for
Classification of Data Center Infrastructure Management (DCIM) Tools
Classification of Infrastructure Management (DCIM) Tools White Paper 104 Revision 3 by Kevin Brown Dennis Bouley > Executive summary Data centers today lack a formal system for classifying infrastructure
7QUESTIONSYOUNEEDTOASKBEFORE CHOOSINGACOLOCATIONFACILITY FORYOURBUSINESS
7QUESTIONSYOUNEEDTOASKBEFORE CHOOSINGACOLOCATIONFACILITY FORYOURBUSINESS ExecutiveBrief P a g e 1 Executive Brief 7 Questions You Need to Ask Before Choosing a Colocation Facility for Your Business Choosing
Power and Cooling for Ultra-High Density Racks and Blade Servers
Power and Cooling for Ultra-High Density Racks and Blade Servers White Paper #46 Introduction The Problem Average rack in a typical data center is under 2 kw Dense deployment of blade servers (10-20 kw
A Scalable, Reconfigurable, and Efficient Data Center Power Distribution Architecture
A Scalable, Reconfigurable, and Efficient Data Center Power Distribution Architecture White Paper 129 Revision 1 by Neil Rasmussen > Executive summary Significant improvements in efficiency, power density,
Guidelines for Specification of Data Center Power Density
Guidelines for Specification of Data Center Power Density White Paper 120 Revision 1 by Neil Rasmussen > Executive summary Conventional methods for specifying data center density are ambiguous and misleading.
Tier Classifications Define Site Infrastructure Performance
By W. Pitt Turner IV, P.E., John H. Seader, P.E., and Kenneth G. Brill Widely accepted within the uninterruptible industry, The Uptime Institute s Tier Performance Standards are an objective basis for
How Proactive Business Continuity Can Protect and Grow Your Business. A CenturyLink White Paper
How Proactive Business Continuity Can Protect and Grow Your Business For most companies, business continuity planning is instantly equated with disaster recovery the reactive ability of a business to continue
Sovereign. The made to measure data centre
Sovereign D ATA C O N N E C T The made to measure data centre Prime Location Within touching distance of everything that s important. 2 Your Customer-Centric Data Centre For the vast majority of organisations
TIA-942: Data Center Standards
plantemoran.com TIA-942: Data Center Standards Sri Chalasani Merit 2010 Conference May 25, 2010 Objectives What are concerns in the data center? Data center standards & best Practices Data Center Definition
Classification of Data Center Operations Technology (OT) Management Tools
Classification of Data Center Operations Technology (OT) Management Tools White Paper 104 Revision 0 by Kevin Brown Dennis Bouley > Executive summary Data centers today lack a formal system for classifying
Engineering & Support Services
Engineering & Support Services Expert Project, Engineering & Customer Support Services Providing a range of Engineering and Support Services for:- Mission Critical Environments Data Centres & Server Room
How To Write An Infrastructural Standard For Data Center Infrastructure
Infrastructure Standard for Data Centers ANSI/CSA/EIA/TIA-942 (PN-3-0092) Introduction When approved, the standard will be: ANSI/CSA/EIA/TIA-942 Telecommunications Infrastructure Standard for Data Centers
Network Router Monitoring & Management Services
Network Router Monitoring & Management Services Get different parameters of routers monitored and managed, and protect your business from planned and unplanned downtime. SERVICE DEFINITION: NETWORK ROUTER
Designed for uptime. Defining data center availability via a tier classification system
Defining data center availability via a tier classification system MIETEK GLIKOWSKI All systems can fail this is a simple fact that every industry must deal with. The paramount concern for the data center
The Data Center Migration (DCM) Evaluation Tool
The Data Center Migration (DCM) Evaluation Tool The DCM Evaluation Tool is a series of targeted questions intended to establish a baseline for your migration s scope, schedule and cost. The questions are
OPERATOR - FACILITY ADDRESS - DATE
. Facility Criteria (RFP).0 Location Characteristics Criteria Requirements 1 Ownership and Management: Please identify the owner(s) and managers of the property and indicate if there is on-site management.
Cooling Strategies for IT Wiring Closets and Small Rooms
Cooling Strategies for IT Wiring Closets and Small Rooms White Paper 68 Revision 1 by Neil Rasmussen and Brian Standley > Executive summary Cooling for IT wiring closets is rarely planned and typically
Smart Data Center Solutions
Smart Data Center Solutions New Data Center Challenges Require New Solutions Data Center Architecture. Inside and Out. Data centers are mission-critical facilities. A silo-based approach to designing,
ASSET Connect. The next level in Critical Environment Operational Efficiency
Connect The next level in Critical Environment Operational Efficiency 10-30% is the potential efficiency gain from optimized Data Centers and Critical Environments Operational Efficiency of Your Critical
Top 10 Disaster Recovery Pitfalls
Top 10 Disaster Recovery Pitfalls The key to successful disaster recovery is good planning. But with so much at stake for your business, how do you plan with confidence and ensure all stakeholders know
High-Efficiency AC Power Distribution for Data Centers
High-Efficiency AC Power Distribution for Data Centers White Paper 128 Revision 2 by Neil Rasmussen > Executive summary The use of 240 volt power distribution for data centers saves floor space, simplifies
White Paper. Co-location. Co-location. Co-location. Considerations That Impact Your Business
White Paper Co-location. Co-location. Co-location. Considerations That Impact Your Business Your Business is Dynamic - Is your IT Infrastructure Keeping Pace? Whether you operate a small or medium-sized
Increasing Energ y Efficiency In Data Centers
The following article was published in ASHRAE Journal, December 2007. Copyright 2007 American Society of Heating, Refrigerating and Air- Conditioning Engineers, Inc. It is presented for educational purposes
Benefits of Deploying VirtualWisdom with HP Converged Infrastructure March, 2015
Benefits of Deploying VirtualWisdom with HP Converged Infrastructure March, 2015 Version 1 Introduction: Yesterday was Silos, Today is integrated! Business needs today can't be met with yesterday's IT.
How green is your data center?
Siemens Answers: Sustainable Future How green is your data center? Istanbul June 01, 2010 Agenda 1 Solution 2 Siemens Data Center Approach 2 Designing with multiple power density zones can reduce energy
About Injazat. Enterprise Cloud Services. Premier Data Center. IT Outsourcing. Learning and Development Services. Enterprise Application Services
About Injazat Injazat Data Systems is an industry-recognized market leader in the region for Information Technology Outsourcing, Cloud and Data Center Managed Services delivered from the region s 1st Tier
Fall 2014 Data Center Users Group Survey Results October 2014
Fall 04 Data Center Users Group Survey Results October 04 The Data Center Users Group (DCUG) is a collection of influential data center, IT and facility managers formed by Emerson Network Power. Founded
Types of Electrical Meters in Data Centers
Types of Electrical Meters in Data Centers White Paper 172 Revision 1 by David Kidd and Wendy Torell > Executive summary There are several different types of meters that can be designed into a data center,
Data Centre Issues supported in TIA-942 : "Telecommunications Infrastructure for Data Centre s"
Data Centre Issues supported in TIA-942 : "Telecommunications Infrastructure for Data Centre s" Data centre Standard EN50173-5 : "Telecommunications Infrastructure for Data Centre s Due, 2006 Gary Highton,
Tier Classifications Define Site Infrastructure Performance
By W. Pitt Turner IV, P.E., John H. Seader, P.E., and Kenneth G. Brill Widely accepted within the uninterruptible industry, The Uptime Institute s Tier Performance Standards are an objective basis for
Calculating Total Cooling Requirements for Data Centers
Calculating Total Cooling Requirements for Data Centers By Neil Rasmussen White Paper #25 Revision 2 Executive Summary This document describes how to estimate heat output from Information Technology equipment
Site Preparation Management Co., Ltd. March 1st 2013 By Nara Nonnapha, ATD UPTIME
Site Preparation Management Co., Ltd. March 1st 2013 By Nara Nonnapha, ATD UPTIME 2 AGENDA SESSION -1 What is Data Center? SESSION -2 Equipment and Components SESSION -3 Standard in designing Data Center
LEVEL 3 DATA CENTER SERVICES IN SAN FRANCISCO HOUSE POWER-INTENSIVE APPLICATIONS AND SUPPORT BUSINESS CONTINUITY
LEVEL 3 DATA CENTER SERVICES IN SAN FRANCISCO HOUSE POWER-INTENSIVE APPLICATIONS AND SUPPORT BUSINESS CONTINUITY THE SCALE TO SUPPORT GLOBAL ENTERPRISE IT THE SCALE TO SUPPORT FLEXIBLE ENTERPRISE IT It
DISASTER RECOVERY PLANNING GUIDE
DISASTER RECOVERY PLANNING GUIDE AN INTRODUCTION TO BUSINESS CONTINUITY PLANNING FOR JD EDWARDS SOFTWARE CUSTOMERS www.wts.com WTS Disaster Recovery Planning Guide Page 1 Introduction This guide will provide
Calculating Space and Power Density Requirements for Data Centers
Calculating Space and Power Density Requirements for Data Centers White Paper 155 Revision 0 by Neil Rasmussen Executive summary The historic method of specifying data center power density using a single
Data Centers, Information Technology and Low Current Services
Data Centers, Information Technology and Low Current Services 1 Data Centers and Low Current Services SDT offers a wide-ranging variety of professional services to Data Centres and Low Current operators.
Data Center Knowledge, Vision Control
Data Center Knowledge, Vision Control Objective Overview of the progressive trends in Data Centers, driven by Intelligent Infrastructure Solutions Data Center Layout Secured Storage Back up Core Backbone
Managing Cooling Capacity & Redundancy In Data Centers Today
Managing Cooling Capacity & Redundancy In Data Centers Today About AdaptivCOOL 15+ Years Thermal & Airflow Expertise Global Presence U.S., India, Japan, China Standards & Compliances: ISO 9001:2008 RoHS
Ten Errors to Avoid When Commissioning a Data Center
Ten Errors to Avoid When Commissioning a Data Center By Paul Marcoux White Paper # 149 Executive Summary Data center commissioning can deliver an unbiased evaluation of whether a newly constructed data
Data Center Management. Didik Partono Rudiarto CDCP, ITIL-F, COBIT5, CITM
Data Center Management Didik Partono Rudiarto CDCP, ITIL-F, COBIT5, CITM A physical place that houses a computer network's most critical systems, including back-up power supplies, air conditioning, and
Guideline for Water and Energy Considerations During Federal Data Center Consolidations
Guideline for Water and Energy Considerations During Federal Data Center Consolidations Prepared for the U.S. Department of Energy Federal Energy Management Program By Lawrence Berkeley National Laboratory
in other campus buildings and at remote campus locations. This outage would include Internet access at the main campus.
DATA CENTER The current Campus Data Center is located within historic Founders Hall which is in a less-than ideal location for a variety of reasons, but is typical of an existing campus IT infrastructure
X-tier Data Facility. Prepared by X-tier SAE Corporation
X-tier Data Facility Company Profile X-tier Corporation X-tier is based in Leawood, Kansas. X-tier provides business agnostic, security hardened, custom and turnkey Cloudbased software systems, services,
Maximizing Uptime in Mission- Critical Facilities
Maximizing Uptime in Mission- Critical Facilities White Paper 7 Revision 0 by Joe Soroka > Executive summary As technology reaches into every corner of our world, the importance of, and reliance on, your
Creating Order from Chaos in Data Centers and Server Rooms
Creating from in Data Centers and Server Rooms White Paper 119 Revision 1 by Dennis Bouley > Executive summary Data center professionals can rid themselves of messy racks, sub-standard under floor air
7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America
7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer
Power backup in data centers. Something going on. 24 I MTU Report 03/10
Power backup in data centers Something going on 24 I MTU Report 03/10 Energy All over the world, Internet commerce is growing at an incredibly rapid rate as more and more people become accustomed to banking,
Data center management suite. Providing optimal control and efficiency to data center management. www.siemens.com/datacenters
Data center management suite Providing optimal control and efficiency to data center management www.siemens.com/datacenters Streamline operations with Siemens suite of integrated management tools You work
IBM Twin Data Center Complex Ehningen Peter John IBM BS [email protected]. 2011 IBM Corporation
IBM Twin Data Center Complex Ehningen Peter John IBM BS [email protected] Overview Profile IBM owned facility 6447 m² IT-Space Infrastructure concurrent maintainable (Tier Level 3) Feed-ins of Power
LEVEL 3 DATA CENTER SERVICES IN OMAHA, NEBRASKA HIGH AVAILABILITY ENTERPRISE COMPUTING BUSINESS DEMANDS IT. LEVEL 3 DELIVERS IT.
LEVEL 3 DATA CENTER SERVICES IN OMAHA, NEBRASKA HIGH AVAILABILITY ENTERPRISE COMPUTING BUSINESS DEMANDS IT. LEVEL 3 DELIVERS IT. THE SCALE TO SUPPORT GLOBAL ENTERPRISE IT Designed and equipped to meet