Role of the PI System in Georgia Tech Data Center Laboratory

Size: px
Start display at page:

Download "Role of the PI System in Research @ Georgia Tech Data Center Laboratory"

Transcription

1 Role of the PI System in Georgia Tech Data Center Laboratory Presented by Vaibhav K. Arghode Prepared by Vikneshan Sundaralingam

2 Outline Data center laboratory general information Current use of PI System Future use of PI System Copyri g h t 2012 OSIso f t, LLC. i

3 3 Data Center Georgia Tech A Platform for Transformative Research on Green Data Centers Director: Dr. Yogendra Joshi yogendra.joshi@me.gatech.edu

4 4 8.75m Power distribution unit D O O R Downflow CRAC APC In row cooler HP rack HP rack IBM rack Center rack Mixed HP/ IBM rack CEETHERM Data Center Layout Upflow CRAC APC In row cooler Mixed HP/ IBM rack HP rack IBM rack Center rack Server Simulator Downflow CRAC Upflow CRAC Dell Power edge 64 Node Rack 640 node rack Storage Center Center Center Center Storage Downflow CRAC Spare Center Center Center Center Center Center Network Downflow CRAC 6.4m 6.4m Experimental zone Computational a zone Center Details: 10 Racks 6 Servers / Rack 14 Blades / Server 4 Cores/ Blade Total: 3360 Cores Power distribution unit Power distribution unit Data Center Layout D O O R Equipment Donations courtesy: Data Acquisition: OSIsoft Building Management System: McKenney s Racks: APC Fan assist Chimney Racks: Wrightline Servers: Intel, Yahoo and OIT CRAC unit: Liebert Server Simulator: APC Branch circuit power metering: PDI corp Remote KVM switch: Minicom and Digi In row coolers: APC

5 CRAC (Down flow) CRAC (Down flow) CRAC (Up flow) CRAC (Up flow) CRAC (Down flow) CRAC (Down flow) 5 Dampers 6 inch thick Insulated collapsible partition Data Center- Air Distribution Cold air inlets Hot air exhaust Contained hot air roof return 2 ft. ducted supply Plenum 2 ft. ducted supply Plenum 3 ft Raised floor plenum Over head supply Under floor supply 2 ft. ducted supply Plenum 2 ft. ducted supply Plenum Economizer

6 6 Particle Image Velocimetry System (PIV) Fan speed and Heat setting dials PIV system One of the first PIV systems for rack level air flow mapping. 22 kw Server Simulator with adjustable fan speed and heater power settings to simulate a variety of air flow and heat loads. Server Simulator Perforated floor tiles with dampers

7 7 Particle Image Velocimetry Pulsed Laser t Cylindrical lens Measurement area and plane (0.60x1.9) m 2 Light Sheet Image map 1 pulse 1 Interrogation area Image map 2 pulse 2 Cross correlation function Vector map Data Analysis Velocity Stream lines Vorticity Turbulence CCD camera Flow seeded with particles x, y ( Particle Displacement) Noise filtering and random vector elimination x y u Velocity vectors Δx u Δt v Δy v Δt Vector Statistics Camera 2 (Image map B) Camera 1 (Image map A) Light Sheet Y X Perforated floor tile Rack (server simulator)

8 Height of the server simulator measured from the perforated floor tile (mm) 8 Tile/Rack Air Flow Studies using PIV Cold aisle Distance measured from the centre of cold aisle (mm) 5.5 kw/rack (625 CFM) Rack air inlet 625 CFM Velocity (m/s) Perforated tile 625 CFM Entrainment Cold aisle By-Pass Rack air inlet 2500 CFM 22 kw/rack (2500 CFM) Recirculation Perforated tile 2500 CFM [ref] Kumar, P., Joshi, Y., Experimental Investigations on the Effect of Perforated Tile Air Jet Velocity on Server Air Distribution in a High Density Data Center, Intersociety Conference on Thermal Phenomena (ITHERM), Jun 2-5, 2010, Las Vegas, USA.

9 Aisle center Rack Aisle center Rack Aisle center Rack Aisle center Rack 9 Pressure outlet Pressure inlet (K=10) Pressure inlet 22 kw/rack (2500 CFM) Aisle top Numerical Modeling Aisle top Aisle top Aisle top Grill Tile Gap Fan Mass flow inlet Pressure inlet Symmetry Body force 4.2million cells Velocity (m/s) Tile PIV (Experiments) Tile Geometrical Resolution Tile Modified Body Force (Developed) Modified body force with momentum source region of 22 width and 6 height suggests closer comparison with geometrical resolution and PIV results Tile Porous Jump (Generally Used) [mbf] Arghode, V. K., Kumar, P., Joshi, Y., Weiss, T., Meyer, G., Rack Level Modeling of Air Flow Through Perforated Tile in a Data Center, International Mechanical Engineering Congress and Exposition (IMECE), Nov 9-15, 2012, Houston, USA.

10 10 Grid Based Temperature Measurements T type thermocouples (wire gauge 28, mm) 252 thermocouples (width = 4ft, depth = 2ft, height = 6ft 6inch) 3D mapping of the cold aisle 6 planes along the height, 5 planes along the depth and 10 planes along the width

11 11 Rack Air Flow and Heat Load Measurement Air Inlet Air Outlet T in RACK Rack Load Tester T out Thermistor (T) Thermal Anemometer (V) Array (15 3) of temperature (thermistor) and velocity (thermal anemometer) sensors Mass flow rate calculated based on the measured velocity Rack heat load calculated based on mass weighted outlet temperature and inlet temperatures and the mass flow rate Air mass flow Heat load m= A V Measured Velocity Flow Area Air density Q=m C p (T out -T in ) Air specific heat Measured Temperatures

12 12 Containment System with Active Fan Tiles Top Curtain Fan Assisted Tiles

13 Outline Data center laboratory general information Current use of PI System Future use of PI system Copyri g h t 2012 OSIso f t, LLC. ii

14 14 Temperature Thermal diodes (CPU temperatures) Sensor Types Resistance temperature detectors, thermistors, and thermocouples (air temperature) Power Branch Circuit Monitoring System (at Power Distribution PDU level) Power Outlet Power Sensing (at Power Strips) Water Velocity/Flow : Dual turbine flow meter (Rear Door Heat Exchanger) Magnetic flow meter (Computer Room Air Conditioning) Air Velocity/Flow: Constant temperature hotwire anemometer (point velocity measurement) Particle image velocimetry (PIV) (velocity field) Flow hood (tile flow rate) Pressure Sensors Humidity Sensors

15 15 Interfaces MODBUS TCP/IP Communication protocol published by Modicon in 1979 for use with its programmable logic controllers (PLCs). Currently used as the interface with the building management system. SNMP (Simple Network Management Protocol) Internet-standard protocol for managing devices on IP networks. Used in facility to communicate with power strips and blade centers. IPMI (Intelligent Platform Management Interface) Used by system administrators to manage computers and gather data for monitoring purposes. Used in facility to communicate with server to collect server health data

16 16 Data Acquisition and Archiving Building Management User Machine 1 (e. g. CRAC) MODBUS Web Server Machine 2 (e. g. Power Strip) PI Server Software: Analyze and Visualize (e.g. Matlab, Labview) Machine 3 (e. g. Server) IPMI Headnode with Linux Platform

17 17 Rack Level Monitoring Example (SNMP)

18 18 Control System Design and Implementation Building management system (BMS) uses Niagra by Tridium to regulate cooling MATLAB script or code communicates with PI System using PI OLEDB, which sends commands through output tags to BMS. MATLAB built-in functions and tools used (e.g. SIMULINK) to design and implement controller. Benefits: A comprehensive library of tools in MATLAB for control system design No need for actual controller board Fail safe: no changes made to existing controllers in data center Suited for research purposes because of its flexibility and fast turnaround times PI Server MATLAB Building Management System

19 19 Controller Implementation Example Regulating maximum CPU temperatures for a rack by varying CRAC supply air temperature CPU Max Temp. Setpoint Idle to full load Integral action controller as an add-on to existing CRAC controls. Sampling period : 2 minutes Only one rack turned active in experimental zone (preliminary testing) Test case: Step increase in compute load [ref] Sundaralingam, V., Joshi, Y, Controller to regulate maximum server CPU temperatures in a rack by varying CRAC supply air temperatures, International Mechanical Engineering Congress and Exposition (IMECE), Nov 9-15, 2012, Houston, USA.

20 Outline Data center laboratory general information Current use of PI system Future use of PI system Copyri g h t 2012 OSIso f t, LLC. iii

21 21 Future Work Webserver Development Integrate Sharepoint Server with the PI System tools: PI WebParts, PI ProcessBook and etc. Webserver function Facilitate data extraction Visualize data Disseminate live and archived data to the public (login credentials will be provided for approved requests Tentative beta site availability (April 2013) Development of logic/physics based controllers for air cooled data center Contained aisles Active fan tiles Advanced air delivery systems

22 Brought to you by Copyri g h t 2012 OSIso f t, LLC.

The CEETHERM Data Center Laboratory

The CEETHERM Data Center Laboratory The CEETHERM Data Center Laboratory A Platform for Transformative Research on Green Data Centers Yogendra Joshi and Pramod Kumar G.W. Woodruff School of Mechanical Engineering Georgia Institute of Technology

More information

Effect of Rack Server Population on Temperatures in Data Centers

Effect of Rack Server Population on Temperatures in Data Centers Effect of Rack Server Population on Temperatures in Data Centers Rajat Ghosh, Vikneshan Sundaralingam, Yogendra Joshi G.W. Woodruff School of Mechanical Engineering Georgia Institute of Technology, Atlanta,

More information

TRANSIENT AIR TEMPERATURE MEASUREMENTS IN A DATA CENTER

TRANSIENT AIR TEMPERATURE MEASUREMENTS IN A DATA CENTER Proceedings of the 21st National & 10TH ISHMT-ASME Heat and Mass Transfer Conference December 27-30, 2011, IIT Madras, India Paper ID: ISHMT_USA_013 TRANSIENT AIR TEMPERATURE MEASUREMENTS IN A DATA CENTER

More information

Liquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED.

Liquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED. Liquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED. Presentation Goals & Outline Power Density Where we have been- where we are now - where we are going Limitations of Air Cooling

More information

EXPERIMENTAL CHARACTERIZATION OF TRANSIENT TEMPERATURE EVOLUTION IN A DATA CENTER FACILITY

EXPERIMENTAL CHARACTERIZATION OF TRANSIENT TEMPERATURE EVOLUTION IN A DATA CENTER FACILITY EXPERIMENTAL CHARACTERIZATION OF TRANSIENT TEMPERATURE EVOLUTION IN A DATA CENTER FACILITY Rajat Ghosh, Pramod Kumar Vikneshan Sundaralingam Yogendra Joshi yogendra.joshi@me.gatech.edu G.W. Woodruff School

More information

Benefits of. Air Flow Management. Data Center

Benefits of. Air Flow Management. Data Center Benefits of Passive Air Flow Management in the Data Center Learning Objectives At the end of this program, participants will be able to: Readily identify if opportunities i where networking equipment

More information

Impacts of Perforated Tile Open Areas on Airflow Uniformity and Air Management Performance in a Modular Data Center

Impacts of Perforated Tile Open Areas on Airflow Uniformity and Air Management Performance in a Modular Data Center Impacts of Perforated Tile Open Areas on Airflow Uniformity and Air Management Performance in a Modular Data Center Sang-Woo Ham 1, Hye-Won Dong 1, Jae-Weon Jeong 1,* 1 Division of Architectural Engineering,

More information

Optimum Climate Control For Datacenter - Case Study. T. Prabu March 17 th 2009

Optimum Climate Control For Datacenter - Case Study. T. Prabu March 17 th 2009 Optimum Climate Control For Datacenter - Case Study T. Prabu March 17 th 2009 Agenda 2 About EDEC (Emerson) Facility Data Center Details Design Considerations & Challenges Layout Design CFD Analysis Of

More information

Air, Fluid Flow, and Thermal Simulation of Data Centers with Autodesk Revit 2013 and Autodesk BIM 360

Air, Fluid Flow, and Thermal Simulation of Data Centers with Autodesk Revit 2013 and Autodesk BIM 360 Autodesk Revit 2013 Autodesk BIM 360 Air, Fluid Flow, and Thermal Simulation of Data Centers with Autodesk Revit 2013 and Autodesk BIM 360 Data centers consume approximately 200 terawatt hours of energy

More information

Benefits of Cold Aisle Containment During Cooling Failure

Benefits of Cold Aisle Containment During Cooling Failure Benefits of Cold Aisle Containment During Cooling Failure Introduction Data centers are mission-critical facilities that require constant operation because they are at the core of the customer-business

More information

Energy Efficiency Opportunities in Federal High Performance Computing Data Centers

Energy Efficiency Opportunities in Federal High Performance Computing Data Centers Energy Efficiency Opportunities in Federal High Performance Computing Data Centers Prepared for the U.S. Department of Energy Federal Energy Management Program By Lawrence Berkeley National Laboratory

More information

Data Center Components Overview

Data Center Components Overview Data Center Components Overview Power Power Outside Transformer Takes grid power and transforms it from 113KV to 480V Utility (grid) power Supply of high voltage power to the Data Center Electrical Room

More information

Fundamentals of CFD and Data Center Cooling Amir Radmehr, Ph.D. Innovative Research, Inc. radmehr@inres.com

Fundamentals of CFD and Data Center Cooling Amir Radmehr, Ph.D. Innovative Research, Inc. radmehr@inres.com Minneapolis Symposium September 30 th, 2015 Fundamentals of CFD and Data Center Cooling Amir Radmehr, Ph.D. Innovative Research, Inc. radmehr@inres.com Learning Objectives 1. Gain familiarity with Computational

More information

Optimizing Network Performance through PASSIVE AIR FLOW MANAGEMENT IN THE DATA CENTER

Optimizing Network Performance through PASSIVE AIR FLOW MANAGEMENT IN THE DATA CENTER Optimizing Network Performance through PASSIVE AIR FLOW MANAGEMENT IN THE DATA CENTER Lylette Macdonald, RCDD Legrand Ortronics BICSI Baltimore 2011 Agenda: Discuss passive thermal management at the Rack

More information

APC APPLICATION NOTE #92

APC APPLICATION NOTE #92 #92 Best Practices for Designing Data Centers with the InfraStruXure InRow RC By John Niemann Abstract The InfraStruXure InRow RC is designed to provide cooling at the row and rack level of a data center

More information

The New Data Center Cooling Paradigm The Tiered Approach

The New Data Center Cooling Paradigm The Tiered Approach Product Footprint - Heat Density Trends The New Data Center Cooling Paradigm The Tiered Approach Lennart Ståhl Amdahl, Cisco, Compaq, Cray, Dell, EMC, HP, IBM, Intel, Lucent, Motorola, Nokia, Nortel, Sun,

More information

How To Improve Energy Efficiency Through Raising Inlet Temperatures

How To Improve Energy Efficiency Through Raising Inlet Temperatures Data Center Operating Cost Savings Realized by Air Flow Management and Increased Rack Inlet Temperatures William Seeber Stephen Seeber Mid Atlantic Infrared Services, Inc. 5309 Mohican Road Bethesda, MD

More information

Managing Cooling Capacity & Redundancy In Data Centers Today

Managing Cooling Capacity & Redundancy In Data Centers Today Managing Cooling Capacity & Redundancy In Data Centers Today About AdaptivCOOL 15+ Years Thermal & Airflow Expertise Global Presence U.S., India, Japan, China Standards & Compliances: ISO 9001:2008 RoHS

More information

Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009

Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009 Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009 Agenda Overview - Network Critical Physical Infrastructure Cooling issues in the Server Room

More information

Managing Data Centre Heat Issues

Managing Data Centre Heat Issues Managing Data Centre Heat Issues Victor Banuelos Field Applications Engineer Chatsworth Products, Inc. 2010 Managing Data Centre Heat Issues Thermal trends in the data centre Hot Aisle / Cold Aisle design

More information

Analysis of the UNH Data Center Using CFD Modeling

Analysis of the UNH Data Center Using CFD Modeling Applied Math Modeling White Paper Analysis of the UNH Data Center Using CFD Modeling By Jamie Bemis, Dana Etherington, and Mike Osienski, Department of Mechanical Engineering, University of New Hampshire,

More information

Computational Fluid Dynamic Investigation of Liquid Rack Cooling in Data Centres

Computational Fluid Dynamic Investigation of Liquid Rack Cooling in Data Centres School of something School of Mechanical Engineering FACULTY OF OTHER ENGINEERING Computational Fluid Dynamic Investigation of Liquid Rack Cooling in Data Centres A. Almoli 1, A. Thompson 1, N. Kapur 1,

More information

Using Computational Fluid Dynamics (CFD) for improving cooling system efficiency for Data centers

Using Computational Fluid Dynamics (CFD) for improving cooling system efficiency for Data centers Data Centre Best Practises Workshop Using Computational Fluid Dynamics (CFD) for improving cooling system efficiency for Data centers Shishir Gupta 17 th March 2009 You are Here Introduction to CFD Data

More information

Cooling Audit for Identifying Potential Cooling Problems in Data Centers

Cooling Audit for Identifying Potential Cooling Problems in Data Centers Cooling Audit for Identifying Potential Cooling Problems in Data Centers By Kevin Dunlap White Paper #40 Revision 2 Executive Summary The compaction of information technology equipment and simultaneous

More information

Power and Cooling for Ultra-High Density Racks and Blade Servers

Power and Cooling for Ultra-High Density Racks and Blade Servers Power and Cooling for Ultra-High Density Racks and Blade Servers White Paper #46 Introduction The Problem Average rack in a typical data center is under 2 kw Dense deployment of blade servers (10-20 kw

More information

RAISED-FLOOR DATA CENTER: PERFORATED TILE FLOW RATES FOR VARIOUS TILE LAYOUTS

RAISED-FLOOR DATA CENTER: PERFORATED TILE FLOW RATES FOR VARIOUS TILE LAYOUTS Paper Presented at ITHERM 2004 Ninth Intersociety Conference on Thermal and Thermomechanical Phenomena in Electronic Systems June 1-4, Las Vegas, NV RAISED-FLOOR DATA CENTER: PERFORATED TILE FLOW RATES

More information

Data Center Power Consumption

Data Center Power Consumption Data Center Power Consumption A new look at a growing problem Fact - Data center power density up 10x in the last 10 years 2.1 kw/rack (1992); 14 kw/rack (2007) Racks are not fully populated due to power/cooling

More information

2006 APC corporation. Cooling Solutions and Selling Strategies for Wiring Closets and Small IT Rooms

2006 APC corporation. Cooling Solutions and Selling Strategies for Wiring Closets and Small IT Rooms Cooling Solutions and Selling Strategies for Wiring Closets and Small IT Rooms Agenda Review of cooling challenge and strategies Solutions to deal with wiring closet cooling Opportunity and value Power

More information

Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001

Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001 Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001 Presented by: Liberty Engineering, LLP 1609 Connecticut Avenue

More information

Data Centers: How Does It Affect My Building s Energy Use and What Can I Do?

Data Centers: How Does It Affect My Building s Energy Use and What Can I Do? Data Centers: How Does It Affect My Building s Energy Use and What Can I Do? 1 Thank you for attending today s session! Please let us know your name and/or location when you sign in We ask everyone to

More information

Title: Design of a Shared Tier III+ Data Center: A Case Study with Design Alternatives and Selection Criteria

Title: Design of a Shared Tier III+ Data Center: A Case Study with Design Alternatives and Selection Criteria Tier 3+ 1 Title: Design of a Shared Tier III+ Data Center: A Case Study with Design Alternatives and Selection Criteria Abstract: Schoolcraft College is constructing a High Availability (HA) Data Center

More information

COMPARATIVE ANALYSIS OF WIDELY USED AIR CONTAINMENT SYSTEMS IN COMMERCIAL DATA CENTERS FOR MAXIMUM COOLING PERFORMANCE KASTURI RANGAN RAJAGOPALAN

COMPARATIVE ANALYSIS OF WIDELY USED AIR CONTAINMENT SYSTEMS IN COMMERCIAL DATA CENTERS FOR MAXIMUM COOLING PERFORMANCE KASTURI RANGAN RAJAGOPALAN COMPARATIVE ANALYSIS OF WIDELY USED AIR CONTAINMENT SYSTEMS IN COMMERCIAL DATA CENTERS FOR MAXIMUM COOLING PERFORMANCE by KASTURI RANGAN RAJAGOPALAN Presented to the Faculty of the Graduate School of The

More information

GUIDE TO ICT SERVER ROOM ENERGY EFFICIENCY. Public Sector ICT Special Working Group

GUIDE TO ICT SERVER ROOM ENERGY EFFICIENCY. Public Sector ICT Special Working Group GUIDE TO ICT SERVER ROOM ENERGY EFFICIENCY Public Sector ICT Special Working Group SERVER ROOM ENERGY EFFICIENCY This guide is one of a suite of documents that aims to provide guidance on ICT energy efficiency.

More information

Element D Services Heating, Ventilating, and Air Conditioning

Element D Services Heating, Ventilating, and Air Conditioning PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer

More information

IPACK2005-73273 DISTRIBUTED LEAKAGE FLOW IN RAISED-FLOOR DATA CENTERS

IPACK2005-73273 DISTRIBUTED LEAKAGE FLOW IN RAISED-FLOOR DATA CENTERS Proceedings of IPACK5 ASME InterPACK '5 July 17-, San Francisco, California, USA IPACK5-7373 DISTRIBUTED LEAKAGE FLOW IN RAISED-FLOOR DATA CENTERS Amir Radmehr Innovative Research, Inc. Plymouth, MN, USA

More information

High Density Data Centers Fraught with Peril. Richard A. Greco, Principal EYP Mission Critical Facilities, Inc.

High Density Data Centers Fraught with Peril. Richard A. Greco, Principal EYP Mission Critical Facilities, Inc. High Density Data Centers Fraught with Peril Richard A. Greco, Principal EYP Mission Critical Facilities, Inc. Microprocessors Trends Reprinted with the permission of The Uptime Institute from a white

More information

Great Lakes Data Room Case Study

Great Lakes Data Room Case Study Great Lakes Data Room Case Study WeRackYourWorld.com Problem: During a warm summer period in 2008, Great Lakes experienced a network outage due to a switch failure in the network enclosure. After an equipment

More information

Containment Solutions

Containment Solutions Containment Solutions Improve cooling efficiency Separate hot and cold air streams Configured to meet density requirements Suitable for commercial and SCEC endorsed cabinets Available for retrofit to SRA

More information

Choosing Close-Coupled IT Cooling Solutions

Choosing Close-Coupled IT Cooling Solutions W H I T E P A P E R Choosing Close-Coupled IT Cooling Solutions Smart Strategies for Small to Mid-Size Data Centers Executive Summary As high-density IT equipment becomes the new normal, the amount of

More information

11 Top Tips for Energy-Efficient Data Center Design and Operation

11 Top Tips for Energy-Efficient Data Center Design and Operation 11 Top Tips for Energy-Efficient Data Center Design and Operation A High-Level How To Guide M e c h a n i c a l a n a l y s i s W h i t e P a p e r w w w. m e n t o r. c o m When is Data Center Thermal

More information

AEGIS DATA CENTER SERVICES POWER AND COOLING ANALYSIS SERVICE SUMMARY

AEGIS DATA CENTER SERVICES POWER AND COOLING ANALYSIS SERVICE SUMMARY AEGIS DATA CENTER SERVICES POWER AND COOLING ANALYSIS SERVICE SUMMARY The Aegis Services Power and Assessment Service provides an assessment and analysis of your data center facility and critical physical

More information

Elements of Energy Efficiency in Data Centre Cooling Architecture

Elements of Energy Efficiency in Data Centre Cooling Architecture Elements of Energy Efficiency in Data Centre Cooling Architecture Energy Efficient Data Center Cooling 1 STULZ Group of Companies Turnover 2006 Plastics Technology 400 Mio A/C Technology 200 Mio Total

More information

Doc Ref: 2015.06.01.002. 602.783.1112 baselayer.com 2015 BASELAYER TECHNOLOGY, LLC

Doc Ref: 2015.06.01.002. 602.783.1112 baselayer.com 2015 BASELAYER TECHNOLOGY, LLC TM 602.783.1112 baselayer.com 2015 BASELAYER TECHNOLOGY, LLC TM D400E Data Module (60Hz) The EDGE D400E is designed to meet high power density requirements for both the HPC and Web Scale environments while

More information

Validation of Modeling Tools for Detection Design in High Airflow Environments

Validation of Modeling Tools for Detection Design in High Airflow Environments Validation of Modeling Tools for Detection Design in High Airflow Environments Joshua B. Dinaburg Dr. Jason Floyd, Ph.D. Dr. Sai Thumuluru, Ph.D FM Global MODELING DETECTION RESPONSE Establish validated

More information

How Row-based Data Center Cooling Works

How Row-based Data Center Cooling Works How Row-based Data Center Cooling Works White Paper 208 Revision 0 by Paul Lin and Victor Avelar Executive summary Row-based data center cooling is normally regarded as a cold air supply architecture that

More information

A Comparative Study of Various High Density Data Center Cooling Technologies. A Thesis Presented. Kwok Wu. The Graduate School

A Comparative Study of Various High Density Data Center Cooling Technologies. A Thesis Presented. Kwok Wu. The Graduate School A Comparative Study of Various High Density Data Center Cooling Technologies A Thesis Presented by Kwok Wu to The Graduate School in Partial Fulfillment of the Requirements for the Degree of Master of

More information

Liebert Hiross HPW The High Performance Wallmount Cooling Solutions for Telecom Mobile Remote Access Nodes

Liebert Hiross HPW The High Performance Wallmount Cooling Solutions for Telecom Mobile Remote Access Nodes Precision Cooling for Business-Critical Continuity Liebert Hiross HPW The High Performance Wallmount Cooling Solutions for Telecom Mobile Remote Access Nodes We re Emerson Network Power, backed by Emerson,

More information

I-STUTE Project - WP2.3 Data Centre Cooling. Project Review Meeting 8, Loughborough University, 29 th June 2015

I-STUTE Project - WP2.3 Data Centre Cooling. Project Review Meeting 8, Loughborough University, 29 th June 2015 I-STUTE Project - WP2.3 Data Centre Cooling Project Review Meeting 8, Loughborough University, 29 th June 2015 Topics to be considered 1. Progress on project tasks 2. Development of data centre test facility

More information

Dealing with Thermal Issues in Data Center Universal Aisle Containment

Dealing with Thermal Issues in Data Center Universal Aisle Containment Dealing with Thermal Issues in Data Center Universal Aisle Containment Daniele Tordin BICSI RCDD Technical System Engineer - Panduit Europe Daniele.Tordin@Panduit.com AGENDA Business Drivers Challenges

More information

Statement Of Work. Data Center Power and Cooling Assessment. Service. Professional Services. Table of Contents. 1.0 Executive Summary

Statement Of Work. Data Center Power and Cooling Assessment. Service. Professional Services. Table of Contents. 1.0 Executive Summary Statement Of Work Professional Services Data Center Power and Cooling Assessment Data Center Power and Cooling Assessment Service 1.0 Executive Summary Table of Contents 1.0 Executive Summary 2.0 Features

More information

Control Strategies for Plenum Optimization in Raised Floor Data Centers

Control Strategies for Plenum Optimization in Raised Floor Data Centers Control Strategies for Plenum Optimization in aised Floor Data Centers Keke Chen, Clifford C. Federspiel, David M. Auslander, Cullen E. Bash, Chandrakant D. Patel Enterprise Software and Systems Laboratory

More information

Energy Efficiency and Availability Management in Consolidated Data Centers

Energy Efficiency and Availability Management in Consolidated Data Centers Energy Efficiency and Availability Management in Consolidated Data Centers Abstract The Federal Data Center Consolidation Initiative (FDCCI) was driven by the recognition that growth in the number of Federal

More information

Enclosure and Airflow Management Solution

Enclosure and Airflow Management Solution Enclosure and Airflow Management Solution CFD Analysis Report Des Plaines, Illinois December 22, 2013 Matt Koukl- DECP Mission Critical Systems Affiliated Engineers, Inc. Contents Executive Summary...

More information

Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency

Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency A White Paper from the Experts in Business-Critical Continuity TM Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency Executive Summary Energy efficiency

More information

Re Engineering to a "Green" Data Center, with Measurable ROI

Re Engineering to a Green Data Center, with Measurable ROI Re Engineering to a "Green" Data Center, with Measurable ROI Alan Mamane CEO and Founder Agenda Data Center Energy Trends Benchmarking Efficiency Systematic Approach to Improve Energy Efficiency Best Practices

More information

Challenges In Intelligent Management Of Power And Cooling Towards Sustainable Data Centre

Challenges In Intelligent Management Of Power And Cooling Towards Sustainable Data Centre Challenges In Intelligent Management Of Power And Cooling Towards Sustainable Data Centre S. Luong 1*, K. Liu 2, James Robey 3 1 Technologies for Sustainable Built Environments, University of Reading,

More information

Driving Data Center Efficiency Through the Adoption of Best Practices

Driving Data Center Efficiency Through the Adoption of Best Practices Data Center Solutions 2008 Driving Data Center Efficiency Through the Adoption of Best Practices Data Center Solutions Driving Data Center Efficiency Through the Adoption of Best Practices Executive Summary

More information

INFRASTRUCTURE FOR DATACENTERS

INFRASTRUCTURE FOR DATACENTERS INFRASTRUCTURE FOR DATACENTERS 02 ENERGY EFFICIENCY IN DATACENTERS The energy efficiency is one of the biggest challenges that datacenter infrastructures are facing today. The datacenters need to have

More information

Local Temperature Control in Data Center Cooling: Part I, Correlation Matrix

Local Temperature Control in Data Center Cooling: Part I, Correlation Matrix Local Temperature Control in Data Center Cooling: Part I, Correlation Matrix Keke Chen, David M. Auslander, Cullen E. Bash, Chandrakant D. Patel Enterprise Software and Systems Laboratory HP Laboratories

More information

Improving Rack Cooling Performance Using Airflow Management Blanking Panels

Improving Rack Cooling Performance Using Airflow Management Blanking Panels Improving Rack Cooling Performance Using Airflow Management Blanking Panels White Paper 44 Revision 4 by Neil Rasmussen > Executive summary Unused vertical space in open frame racks and rack enclosures

More information

LEVEL 3 DATA CENTER ASSESSMENT

LEVEL 3 DATA CENTER ASSESSMENT Nationwide Services Corporate Headquarters 410 Forest Street Marlborough, MA 01752 USA Tel: 800-342-5332 Fax: 508-303-0579 www.eecnet.com LEVEL 3 DATA CENTER ASSESSMENT Submitted by: Electronic Environments

More information

Statement Of Work Professional Services

Statement Of Work Professional Services Statement Of Work Professional Services Data Center Cooling Analysis using CFD Data Center Cooling Analysis Using Computational Fluid Dynamics Service 1.0 Executive Summary Table of Contents 1.0 Executive

More information

DEVELOPMENT OF AN EXPERIMENTALLY-VALIDATED COMPACT MODEL OF A SERVER RACK

DEVELOPMENT OF AN EXPERIMENTALLY-VALIDATED COMPACT MODEL OF A SERVER RACK DEVELOPMENT OF AN EXPERIMENTALLY-VALIDATED COMPACT MODEL OF A SERVER RACK A Thesis Presented to The Academic Faculty by Graham Nelson In Partial Fulfillment of the Requirements for the Degree Master of

More information

Energy Efficient Server Room and Data Centre Cooling. Computer Room Evaporative Cooler. EcoCooling

Energy Efficient Server Room and Data Centre Cooling. Computer Room Evaporative Cooler. EcoCooling Energy Efficient Server Room and Data Centre Cooling Computer Room Evaporative Cooler EcoCooling EcoCooling CREC Computer Room Evaporative Cooler Reduce your cooling costs by over 90% Did you know? An

More information

HPPR Data Center Improvements Projects Towards Energy Efficiency (CFD Analysis, Monitoring, etc.)

HPPR Data Center Improvements Projects Towards Energy Efficiency (CFD Analysis, Monitoring, etc.) HPPR Data Center Improvements Projects Towards Energy Efficiency (CFD Analysis, Monitoring, etc.) Felipe Visbal / March 27, 2013 HPPR Data Center Technologies Team Services Data Centers: Thermal Assessments

More information

Energy Efficient Data Centre at Imperial College. M. Okan Kibaroglu IT Production Services Manager Imperial College London.

Energy Efficient Data Centre at Imperial College. M. Okan Kibaroglu IT Production Services Manager Imperial College London. Energy Efficient Data Centre at Imperial College M. Okan Kibaroglu IT Production Services Manager Imperial College London 3 March 2009 Contents Recognising the Wider Issue Role of IT / Actions at Imperial

More information

APC APPLICATION NOTE #112

APC APPLICATION NOTE #112 #112 Best Practices for Deploying the InfraStruXure InRow SC By David Roden Abstract The InfraStruXure InRow SC (ACSC100 and ACSC101) is a self-contained air conditioner for server rooms and wiring closets.

More information

Modeling Rack and Server Heat Capacity in a Physics Based Dynamic CFD Model of Data Centers. Sami Alkharabsheh, Bahgat Sammakia 10/28/2013

Modeling Rack and Server Heat Capacity in a Physics Based Dynamic CFD Model of Data Centers. Sami Alkharabsheh, Bahgat Sammakia 10/28/2013 Modeling Rack and Server Heat Capacity in a Physics Based Dynamic CFD Model of Data Centers Sami Alkharabsheh, Bahgat Sammakia 1/28/213 2 ES2 Vision To create electronic systems that are self sensing and

More information

Center Thermal Management Can Live Together

Center Thermal Management Can Live Together Network Management age e and Data Center Thermal Management Can Live Together Ian Seaton Chatsworth Products, Inc. Benefits of Hot Air Isolation 1. Eliminates reliance on thermostat 2. Eliminates hot spots

More information

Energy Performance Optimization of Server Room HVAC System

Energy Performance Optimization of Server Room HVAC System International Journal of Thermal Technologies E-ISSN 2277 4114 2 INPRESSCO, All Rights Reserved Available at http://inpressco.com/category/ijtt/ Research Article Manoj Jadhav * and Pramod Chaudhari Department

More information

CoolTop. A unique water cooled air-conditioning unit for server room cooling from the top AC-TOPx-CW-240/60

CoolTop. A unique water cooled air-conditioning unit for server room cooling from the top AC-TOPx-CW-240/60 CoolTop A unique water cooled air-conditioning unit for server room cooling from the top AC-TOPx-CW-240/60 Application CoolTop is a new, unique air conditioning unit especially designed for datacenters.

More information

Case Study: Opportunities to Improve Energy Efficiency in Three Federal Data Centers

Case Study: Opportunities to Improve Energy Efficiency in Three Federal Data Centers Case Study: Opportunities to Improve Energy Efficiency in Three Federal Data Centers Prepared for the U.S. Department of Energy s Federal Energy Management Program Prepared By Lawrence Berkeley National

More information

Improving Rack Cooling Performance Using Airflow Management Blanking Panels

Improving Rack Cooling Performance Using Airflow Management Blanking Panels Improving Rack Cooling Performance Using Airflow Management Blanking Panels By Neil Rasmussen White Paper #44 Revision 3 Executive Summary Unused vertical space in open frame racks and rack enclosures

More information

Best Practices for Wire-free Environmental Monitoring in the Data Center

Best Practices for Wire-free Environmental Monitoring in the Data Center White Paper 11800 Ridge Parkway Broomfiled, CO 80021 1-800-638-2638 http://www.42u.com sales@42u.com Best Practices for Wire-free Environmental Monitoring in the Data Center Introduction Monitoring for

More information

Unified Physical Infrastructure (UPI) Strategies for Thermal Management

Unified Physical Infrastructure (UPI) Strategies for Thermal Management Unified Physical Infrastructure (UPI) Strategies for Thermal Management The Importance of Air Sealing Grommets to Improving Smart www.panduit.com WP-04 August 2008 Introduction One of the core issues affecting

More information

Introducing Computational Fluid Dynamics Virtual Facility 6SigmaDC

Introducing Computational Fluid Dynamics Virtual Facility 6SigmaDC IT Infrastructure Services Ltd Holborn Gate, 330 High Holborn, London, WC1V 7QT Telephone: +44 (0)20 7849 6848 Fax: +44 (0)20 7203 6701 Email: info@itisltd.co.uk www.itisltd.com Introducing Computational

More information

Unified Physical Infrastructure SM (UPI) Strategies for Smart Data Centers

Unified Physical Infrastructure SM (UPI) Strategies for Smart Data Centers Unified Physical Infrastructure SM (UPI) Strategies for Smart Data Centers Deploying a Vertical Exhaust System www.panduit.com WP-09 September 2009 Introduction Business management applications and rich

More information

EHDC. Cooling system for Data Center and server cabinets.

EHDC. Cooling system for Data Center and server cabinets. EHDC Cooling system for Data Center and server cabinets. EHDC PEN LP EHDC L is a High Density Cooling module for an pen Loop configuration. It is ideally installed with Enoc Systems cold corridor containment

More information

The Benefits of Supply Air Temperature Control in the Data Centre

The Benefits of Supply Air Temperature Control in the Data Centre Executive Summary: Controlling the temperature in a data centre is critical to achieving maximum uptime and efficiency, but is it being controlled in the correct place? Whilst data centre layouts have

More information

Cooling a hot issue? MINKELS COLD CORRIDOR TM SOLUTION

Cooling a hot issue? MINKELS COLD CORRIDOR TM SOLUTION Cooling a hot issue? MINKELS COLD CORRIDOR TM SOLUTION The heat load in data centers is increasing rapidly, the adaptation of a cooling strategy is often necessary. Many data centers and server rooms use

More information

Liebert CRV Row-Based Cooling Intelligent Precision Cooling For Data Center Equipment. Precision Cooling For Business-Critical Continuity

Liebert CRV Row-Based Cooling Intelligent Precision Cooling For Data Center Equipment. Precision Cooling For Business-Critical Continuity Liebert Row-Based Cooling Intelligent Precision Cooling For Data Center Equipment Precision Cooling For Business-Critical Continuity The Intelligent Data Center Cooling Solution: Liebert Trust the industry

More information

Agenda. Who we are What we do How we serve the BPO Industry

Agenda. Who we are What we do How we serve the BPO Industry Achieving Energy Efficiency in Data Centres Agenda Who we are What we do How we serve the BPO Industry Energy Efficiency for Data Centres Jardine Matheson Founded as a trading company in China in 1832,

More information

Ten Steps to Solving Cooling Problems Caused by High- Density Server Deployment

Ten Steps to Solving Cooling Problems Caused by High- Density Server Deployment Ten Steps to Solving Cooling Problems Caused by High- Density Server Deployment By Peter Hannaford White Paper #42 Revision 1 Executive Summary High-density servers present a significant cooling challenge.

More information

Application of CFD modelling to the Design of Modern Data Centres

Application of CFD modelling to the Design of Modern Data Centres Application of CFD modelling to the Design of Modern Data Centres White Paper March 2012 By Sam Wicks BEng CFD Applications Engineer Sudlows March 14, 2012 Application of CFD modelling to the Design of

More information

Unique Airflow Visualization Techniques for the Design and Validation of Above-Plenum Data Center CFD Models

Unique Airflow Visualization Techniques for the Design and Validation of Above-Plenum Data Center CFD Models Unique Airflow Visualization Techniques for the Design and Validation of Above-Plenum Data Center CFD Models The MIT Faculty has made this article openly available. Please share how this access benefits

More information

MAXIMIZING YOUR DATA CENTER INFRASTRUCTURE: CENTRALIZED MANAGEMENT AND WIRE-FREE ENVIRONMENTAL MONITORING

MAXIMIZING YOUR DATA CENTER INFRASTRUCTURE: CENTRALIZED MANAGEMENT AND WIRE-FREE ENVIRONMENTAL MONITORING MAXIMIZING YOUR DATA CENTER INFRASTRUCTURE: CENTRALIZED MANAGEMENT AND WIRE-FREE Chris C. Gaskins Vice President of Product Development RF Code, Inc. AUGUST 2010 Shawn Griggs Director of Product Management

More information

Measuring Power in your Data Center: The Roadmap to your PUE and Carbon Footprint

Measuring Power in your Data Center: The Roadmap to your PUE and Carbon Footprint Measuring Power in your Data Center: The Roadmap to your PUE and Carbon Footprint Energy usage in the data center Electricity Transformer/ UPS Air 10% Movement 12% Cooling 25% Lighting, etc. 3% IT Equipment

More information

Boosting the Energy efficiency of a Server Room: experimental + virtual approach.

Boosting the Energy efficiency of a Server Room: experimental + virtual approach. Boosting the Energy efficiency of a Server Room: experimental + virtual approach. Nowadays, the increase in computing power allows the successful applications of the CFD simulation methods in civil environments.

More information

Small Data / Telecommunications Room on Slab Floor

Small Data / Telecommunications Room on Slab Floor Small Data / Telecommunications Room on Slab Floor Small Data / Telecommunications Room on Slab Floor During a warm summer period in 2008, Great Lakes experienced a network outage due to a switch failure

More information

DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no significant differences

DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no significant differences DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no significant differences November 2011 Powered by DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no

More information

Our data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management.

Our data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management. AIMS is Malaysia and South East Asia s leading carrier neutral data centre operator and managed services provider. We provide international class data storage and ancillary services, augmented by an unrivaled

More information

High Density Rack Configurations and their Associated Cooling Issues

High Density Rack Configurations and their Associated Cooling Issues High Density Configurations and their Associated Cooling Issues From IXEurope High Density Server Configurations The Fact High-density server configurations represent the cutting edge of server management.

More information

University of St Andrews. Energy Efficient Data Centre Cooling

University of St Andrews. Energy Efficient Data Centre Cooling Energy Efficient Data Centre Cooling St. Andrews and Elsewhere Richard Lumb Consultant Engineer Future-Tech Energy Efficient Data Centre Cooling There is no one single best cooling solution for all Data

More information

Green Data Centre: Is There Such A Thing? Dr. T. C. Tan Distinguished Member, CommScope Labs

Green Data Centre: Is There Such A Thing? Dr. T. C. Tan Distinguished Member, CommScope Labs Green Data Centre: Is There Such A Thing? Dr. T. C. Tan Distinguished Member, CommScope Labs Topics The Why? The How? Conclusion The Why? Drivers for Green IT According to Forrester Research, IT accounts

More information

Best Practices in HVAC Design/Retrofit

Best Practices in HVAC Design/Retrofit Best Practices in HVAC Design/Retrofit Little Server Room BIG $AVINGS Justin Lewis, P.E., LEED AP, DCEP Sr Energy Project Manager C:530.400.6042 O:530.754.4870 jlewis@ucdavis.edu 1 What s the problem here?

More information

Prediction Is Better Than Cure CFD Simulation For Data Center Operation.

Prediction Is Better Than Cure CFD Simulation For Data Center Operation. Prediction Is Better Than Cure CFD Simulation For Data Center Operation. This paper was written to support/reflect a seminar presented at ASHRAE Winter meeting 2014, January 21 st, by, Future Facilities.

More information

CFD-Based Operational Thermal Efficiency Improvement of a Production Data Center

CFD-Based Operational Thermal Efficiency Improvement of a Production Data Center CFD-Based Operational Thermal Efficiency Improvement of a Production Data Center Umesh Singh, Amarendra K Singh, Parvez S and Anand Sivasubramaniam Tata Consultancy Services Ltd., India ABSTRACT Effective

More information

- White Paper - Data Centre Cooling. Best Practice

- White Paper - Data Centre Cooling. Best Practice - White Paper - Data Centre Cooling Best Practice Release 2, April 2008 Contents INTRODUCTION... 3 1. AIR FLOW LEAKAGE... 3 2. PERFORATED TILES: NUMBER AND OPENING FACTOR... 4 3. PERFORATED TILES: WITH

More information

Data Center Cooling & Air Flow Management. Arnold Murphy, CDCEP, CDCAP March 3, 2015

Data Center Cooling & Air Flow Management. Arnold Murphy, CDCEP, CDCAP March 3, 2015 Data Center Cooling & Air Flow Management Arnold Murphy, CDCEP, CDCAP March 3, 2015 Strategic Clean Technology Inc Focus on improving cooling and air flow management to achieve energy cost savings and

More information

How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions

How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions Intel Intelligent Power Management Intel How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions Power and cooling savings through the use of Intel

More information