Contents. APA Construction Details. Full fill cavity walls Partial fill cavity walls Solid externally insulated walls 26-37

Size: px
Start display at page:

Download "Contents. APA Construction Details. Full fill cavity walls 2-13. Partial fill cavity walls 14-25. Solid externally insulated walls 26-37"

Transcription

1 Contents Pages Full fill cavity walls 2-13 Partial fill cavity walls Solid externally insulated walls Appendix (BRE confirmation of Ψ and y-values) Page 1 of 40 APA Construction Details

2 Full fill cavity walls Applicable range of U-values Walls W/m²K Floors W/m²K Roofs W/m²K The following indicative guidance illustrates good practice for the design and construction of interfaces only in respect to ensuring thermal performance. For detailing ensuring continuity of air barrier, reference should be made to Accredited Details. This guidance must be implemented with due regard to all the other requirements imposed by the Building Regulations. The following y-value can be used in SAP 2005 calculations provided all the junction details of the particular dwelling to which SAP 2005 is being applied, conform these APA Full fill cavity wall details and, where appropriate, the relevant Accredited Details. y = 0.04 Page 2 of 40 APA Detail Numbers: FF - -

3 Full fill cavity walls Ground bearing floor - Insulation below slab Aircrete inner leaf above and below DPC Install perimeter insulation with a minimum R-value of 0.80m²K/W (eg 20mm of insulation with a conductivity of 0.025W/mK) Floor insulation to tightly abut blockwork wall Wall insulation to be continued at least 150mm below top of floor insulation At least one course of aircrete foundation blocks The wall insulation installed below the wall DPC must be fit for purpose with regards to water absorption. be made to Accredited Detail Number: MEI-GF W/mK 0.051W/mK 0.058W/mK Page 3 of 40 APA Detail Number: FF - GF - 01

4 Full fill cavity walls Beam and block floor. Insulation above slab Aircrete inner leaf above and below DPC Install perimeter insulation with a minimum R-value of 0.80m²K/W (eg 20mm of insulation with a conductivity of 0.025W/mK) Floor insulation to tightly abut blockwork wall Wall insulation to be continued at least 150mm below top of floor insulation Beam and aircrete infill block floor At least one course of aircrete foundation blocks The wall insulation installed below the wall DPC must be fit for purpose with regards to water absorption. be made to Accredited Detail Number: MEI-GF-02. Floor span Average value onto wall parallel to wall 0.047W/mK 0.040W/mK 0.044W/mK (Aircrete wall block conductivity = 0.11W/mK) 0.053W/mK 0.048W/mK 0.051W/mK (Aircrete wall block conductivity = 0.15W/mK) 0.059W/mK 0.052W/mK 0.056W/mK (Aircrete wall block conductivity = 0.19W/mK) Page 4 of 40 APA Detail Number: FF - GF - 02

5 Full fill cavity walls Timber intermediate floor Aircrete inner leaf above and below timber floor Continue cavity wall insulation across floor abutment zone. Aircrete infill between joists Suspended timber floors may be laid in joist hangers rather than built in. For timber engineered joists, proprietary filler pieces must be fitted on both sides of the web between the top and bottom flanges (see manufacturers details). be made to Accredited Detail Number: MCI-IF W/mK 0.000W/mK 0.001W/mK Page 5 of 40 APA Detail Number: FF - IF - 01

6 Full fill cavity walls Roof / gable wall. Insulation at ceiling level Aircrete inner leaf above and below ceiling level Ensure that the full depth of insulation between and over joists extends to the inner edge of the wall. Continue cavity wall insulation to top of gable OR 270mm above bottom of ceiling tie and insert cavity tray Pack compressible insulation between last joist and gable wall. The use of over joist insulation is considered best practice as it eliminates the cold bridge caused by the joist. be made to Accredited Detail Number: MCI-RG W/mK 0.054W/mK 0.062W/mK Page 6 of 40 APA Detail Number: FF - RG - 01

7 Full fill cavity walls Roof / eaves. Insulation at ceiling level Ensure the gap between the wall plate and the proprietary eaves ventilator is completely filled with insulation having a minimum R-value across the insulation of 1.2m²K/W. Ensure that the full depth of insulation between and over joists abuts the eaves insulation. Aircrete inner leaf Ensure continuity of the insulation throughout the junction. The use of over joist insulation is considered best practice as it eliminates the cold bridge caused by the joist. Use a proprietary eaves ventilator to ensure ventilation in accordance with BS5250, installed so as not to prevent free water drainage below tiling battens. be made to Accredited Detail Number: MCI-RE W/mK 0.070W/mK 0.071W/mK Page 7 of 40 APA Detail Number: FF - RE - 01

8 Full fill cavity walls Aircrete separating wall / external wall abutment Continue cavity wall insulation across abutment zone. Aircrete inner leaf Aircrete inner leaf Aircrete separating wall Refer to Approved Document B for fire safety requirements and Approved Document E for sound insulation requirements be made to Accredited Detail Number: MCI-IW W/mK 0.065W/mK 0.066W/mK Page 8 of 40 APA Detail Number: FF - IW - 01

9 Full fill cavity walls Dense block separating wall / external wall abutment Continue cavity wall insulation across abutment zone. Aircrete inner leaf Aircrete inner leaf Dense block separating wall Refer to Approved Document B for fire safety requirements and Approved Document E for sound insulation requirements be made to Accredited Detail Number: MCI-IW W/mK 0.075W/mK 0.076W/mK Page 9 of 40 APA Detail Number: FF - IW - 02

10 Full fill cavity walls Windows and doors. Lintels (insulated base plate) Aircrete inner leaf Minimum frame overlap to be 30mm. Ensure insulation having a minimum R-value of 0.6m²W/K overlaps the window frame and lintel base plate. (eg 15mm of insulation with a conductivity of 0.025W/mK). Ensure that all gaps around and between lintels are filled with tightly packed insulation material. be made to Accredited Detail Number: MCI-WD W/mK 0.214W/mK 0.222W/mK Page 10 of 40 APA Detail Number: FF - WD - 01

11 Full fill cavity walls Windows and doors. Lintels (not continuous base plate) Aircrete inner leaf Minimum frame overlap to be 30mm. Lintel to be fully insulated and must not have a continuous base plate. Ensure that all gaps around and between lintels are filled with tightly packed insulation material. be made to Accredited Detail Number: MCI-WD W/mK 0.219W/mK 0.223W/mK Page 11 of 40 APA Detail Number: FF - WD - 02

12 Full fill cavity walls Windows and doors. Sills Install a proprietary cavity closer or block of insulation having a minimum thermal resistance path through the closer of not less than 0.45m²K/W (manufacturers certified data). Minimum frame overlap to be 30mm. Aircrete inner leaf be made to Accredited Detail Number: MCI-WD W/mK 0.017W/mK 0.017W/mK Page 12 of 40 APA Detail Number: FF - WD - 03

13 Full fill cavity walls Windows and doors. Jambs Minimum frame overlap to be 30mm. Aircrete inner leaf Install a proprietary cavity closer or block of insulation having a minimum thermal resistance path through the closer of not less than 0.45m²K/W (manufacturers certified data). be made to Accredited Detail Number: MCI-WD W/mK 0.017W/mK 0.017W/mK Page 13 of 40 APA Detail Number: FF - WD - 04

14 Partial fill cavity walls Applicable range of U-values Walls W/m²K Floors W/m²K Roofs W/m²K The following indicative guidance illustrates good practice for the design and construction of interfaces only in respect to ensuring thermal performance. For detailing ensuring continuity of air barrier, reference should be made to Accredited Details. This guidance must be implemented with due regard to all the other requirements imposed by the Building Regulations. The following y-value can be used in SAP 2005 calculations provided all the junction details of the particular dwelling to which SAP 2005 is being applied, conform to these APA Partial fill cavity wall details and, where appropriate, the relevant Accredited Details. y = 0.04 Page 14 of 40 APA Detail Numbers: PF - -

15 Partial fill cavity walls Ground bearing floor - Insulation below slab Partial fill insulation to be secured firmly against the inner leaf of the cavity wall Aircrete inner leaf above and below DPC Install perimeter insulation with a minimum R-value of 0.80m²K/W (eg 20mm of insulation with a conductivity of 0.025W/mK) Floor insulation to tightly abut blockwork wall Wall insulation to be continued at least 150mm below top of floor insulation At least one course of aircrete foundation blocks The wall insulation installed below the wall DPC must be fit for purpose with regards to water absorption. be made to Accredited Detail Number: MCI-GF W/mK 0.055W/mK 0.061W/mK Page 15 of 40 APA Detail Number: PF - GF - 01

16 Partial fill cavity walls Beam and block floor. Insulation above slab Partial fill insulation to be secured firmly against the inner leaf of the cavity wall Aircrete inner leaf above and below DPC Install perimeter insulation with a minimum R-value of 0.80m²K/W (eg 20mm of insulation with a conductivity of 0.025W/mK) Floor insulation to tightly abut blockwork wall Wall insulation to be continued at least 150mm below top of floor insulation Beam and aircrete infill block floor At least one course of aircrete foundation blocks The wall insulation installed below the wall DPC must be fit for purpose with regards to water absorption. be made to Accredited Detail Number: MEI-GF-02. Floor span Average value onto wall parallel to wall 0.040W/mK 0.040W/mK 0.040W/mK (Aircrete wall block conductivity = 0.11W/mK) 0.045W/mK 0.047W/mK 0.046W/mK (Aircrete wall block conductivity = 0.15W/mK) 0.056W/mK 0.052W/mK 0.054W/mK (Aircrete wall block conductivity = 0.19W/mK) Page 16 of 40 APA Detail Number: PF - GF - 02

17 Aircrete inner leaf above and below timber floor Partial fill cavity walls Timber intermediate floor Partial fill insulation to be secured firmly against the inner leaf of the cavity wall Continue cavity wall insulation across floor abutment zone. Aircrete infill between joists Suspended timber floors may be laid in joist hangers rather than built in. For timber engineered joists, proprietary filler pieces must be fitted on both sides of the web between the top and bottom flanges (see manufacturers details). be made to Accredited Detail Number: MCI-IF W/mK 0.001W/mK 0.001W/mK Page 17 of 40 APA Detail Number: PF - IF - 01

18 Partial fill cavity walls Roof / gable wall. Insulation at ceiling level Aircrete inner leaf above and below ceiling level Ensure that the full depth of insulation between and over joists extends to the inner edge of the wall. Continue cavity wall insulation to top of gable OR 270mm above bottom of ceiling tie and insert cavity tray Partial fill insulation to be secured firmly against the inner leaf of the cavity wall Pack compressible insulation between last joist and gable wall. The use of over joist insulation is considered best practice as it eliminates the cold bridge caused by the joist. be made to Accredited Detail Number: MCI-RG W/mK 0.055W/mK 0.062W/mK Page 18 of 40 APA Detail Number: PF - RG - 01

19 Partial fill cavity walls Roof / eaves. Insulation at ceiling level Ensure the gap between the wall plate and the proprietary eaves ventilator is completely filled with insulation having a minimum R-value across the insulation of 1.2m²K/W. Ensure that the full depth of insulation between and over joists abuts the eaves insulation. Partial fill insulation to be secured firmly against the inner leaf of the cavity wall Aircrete inner leaf Ensure continuity of the insulation throughout the junction. The use of over joist insulation is considered best practice as it eliminates the cold bridge caused by the joist. Use a proprietary eaves ventilator to ensure ventilation in accordance with BS5250, installed so as not to prevent free water drainage below tiling battens. be made to Accredited Detail Number: MCI-RE W/mK 0.070W/mK 0.071W/mK Page 19 of 40 APA Detail Number: PF - RE - 01

20 Partial fill cavity walls Aircrete separating wall / external wall abutment Partial fill insulation to be secured firmly against the inner leaf of the cavity wall Insulation across abutment zone. Aircrete inner leaf Aircrete inner leaf Aircrete separating wall Refer to Approved Document B for fire safety requirements and Approved Document E for sound insulation requirements be made to Accredited Detail Number: MCI-IW W/mK 0.078W/mK 0.078W/mK Page 20 of 40 APA Detail Number: PF - IW - 01

21 Partial fill cavity walls Dense block separating wall / external wall abutment Partial fill insulation to be secured firmly against the inner leaf of the cavity wall Insulation across abutment zone. Aircrete inner leaf Aircrete inner leaf Dense block separating wall Refer to Approved Document B for fire safety requirements and Approved Document E for sound insulation requirements be made to Accredited Detail Number: MCI-IW W/mK 0.092W/mK 0.091W/mK Page 21 of 40 APA Detail Number: PF - IW - 02

22 Partial fill cavity walls Windows and doors. Lintels (insulated base plate) Partial fill insulation to be secured firmly against the inner leaf of the cavity wall Aircrete inner leaf Minimum frame overlap to be 30mm. Ensure insulation having a minimum R-value of 0.6m²W/K overlaps the window frame and lintel base plate. (eg 15mm of insulation with a conductivity of 0.025W/mK). Ensure that all gaps around and between lintels are filled with tightly packed insulation material. be made to Accredited Detail Number: MCI-WD W/mK 0.208W/mK 0.218W/mK Page 22 of 40 APA Detail Number: PF - WD - 01

23 Partial fill cavity walls Windows and doors. Lintels (not continuous base plate) Partial fill insulation to be secured firmly against the inner leaf of the cavity wall Aircrete inner leaf Lintel to be fully insulated and must not have a continuous base plate. Minimum frame overlap to be 30mm. Ensure that all gaps around and between lintels are filled with tightly packed insulation material. be made to Accredited Detail Number: MCI-WD W/mK 0.234W/mK 0.239W/mK Page 23 of 40 APA Detail Number: PF - WD - 02

24 Partial fill cavity walls Windows and doors. Sills Install a proprietary cavity closer or block of insulation having a minimum thermal resistance path through the closer of not less than 0.45m²K/W (manufacturers certified data). Minimum frame overlap to be 30mm. Partial fill insulation to be secured firmly against the inner leaf of the cavity wall Aircrete inner leaf be made to Accredited Detail Number: MCI-WD W/mK 0.017W/mK 0.017W/mK Page 24 of 40 APA Detail Number: PF - WD - 03

25 Partial fill cavity walls Windows and doors. Jambs Partial fill insulation to be secured firmly against the inner leaf of the cavity wall Minimum frame overlap to be 30mm. Aircrete inner leaf Install a proprietary cavity closer or block of insulation having a minimum thermal resistance path through the closer of not less than 0.45m²K/W (manufacturers certified data). be made to Accredited Detail Number: MCI-WD W/mK 0.017W/mK 0.017W/mK Page 25 of 40 APA Detail Number: PF - WD - 04

26 Solid externally insulated walls Applicable range of U-values Walls W/m²K Floors W/m²K Roofs W/m²K The following indicative guidance illustrates good practice for the design and construction of interfaces only in respect to ensuring thermal performance. For detailing ensuring continuity of air barrier, reference should be made to Accredited Details. This guidance must be implemented with due regard to all the other requirements imposed by the Building Regulations. The following y-value can be used in SAP 2005 calculations provided all the junction details of the particular dwelling to which SAP 2005 is being applied, conform to these APA Solid externally insulated wall details and, where appropriate, the relevant Accredited Details. Page 26 of 40 y = 0.02 y = 0.03 (for aircrete blocks with a thermal conductivity of 0.11W/mK) (all other aircrete blocks) APA Detail Numbers: EI - -

27 Solid externally insulated walls Ground bearing floor - Insulation below slab Solid aircrete wall above and below DPC Install perimeter insulation with a minimum R-value of 0.80m²K/W (eg 20mm of insulation with a conductivity of 0.025W/mK) Wall insulation below DPC to have a minimum R-value of 2.11m²K/W Floor insulation to tightly abut blockwork wall Wall insulation below DPC to be continued at least 200mm below top of floor insulation At least one course of aircrete foundation blocks The wall insulation installed below the wall DPC must be fit for purpose with regards to water absorption. be made to Accredited Detail Number: MEI-GF W/mK 0.061W/mK 0.070W/mK Page 27 of 40 APA Detail Number: EI - GF - 01

28 Solid externally insulated walls Beam and block floor. Insulation above slab Solid aircrete wall above and below DPC Install perimeter insulation with a minimum R-value of 0.80m²K/W (eg 20mm of insulation with a conductivity of 0.025W/mK) Wall insulation below DPC to have a minimum R-value of 2.11m²K/W Floor insulation to tightly abut blockwork wall Wall insulation below DPC to be continued at least 200mm below top of floor insulation Beam and aircrete infill block floor At least one course of aircrete foundation blocks The wall insulation installed below the wall DPC must be fit for purpose with regards to water absorption. be made to Accredited Detail Number: MEI-GF-02. Floor span Average value onto wall parallel to wall 0.050W/mK 0.044W/mK 0.047W/mK (Aircrete wall block conductivity = 0.11W/mK) 0.062W/mK 0.054W/mK 0.058W/mK (Aircrete wall block conductivity = 0.15W/mK) 0.075W/mK 0.062W/mK 0.069W/mK (Aircrete wall block conductivity = 0.19W/mK) Page 28 of 40 APA Detail Number: EI - GF - 02

29 Solid externally insulated walls Timber intermediate floor Solid aircrete wall above and below timber floor Aircrete infill between joists Continue wall insulation across floor abutment zone. Aircrete infill across joists where joists do not bear on full width of wall Suspended timber floors may be laid in joist hangers rather than built in. For timber engineered joists, proprietary filler pieces must be fitted on both sides of the web between the top and bottom flanges (see manufacturers details). be made to Accredited Detail Number: MEI-IF W/mK 0.001W/mK 0.000W/mK Page 29 of 40 APA Detail Number: EI - IF - 01

30 Solid externally insulated walls Roof / gable wall. Insulation at ceiling level Solid aircrete wall above and below ceiling Ensure that the full depth of insulation between and over joists extends to the inner edge of the wall. Continue wall insulation to top of gable Pack compressible insulation between last joist and gable wall. The use of over joist insulation is considered best practice as it eliminates the cold bridge caused by the joist. be made to Accredited Detail Number: MEI-RG W/mK 0.065W/mK 0.076W/mK Page 30 of 40 APA Detail Number: EI - RG - 01

31 Solid externally insulated walls Roof / eaves. Insulation at ceiling level Ensure the gap between the wall plate and the proprietary eaves ventilator is completely filled with insulation having a minimum R-value across the insulation of 1.2m²K/W. Ensure that the full depth of insulation between and over joists abuts the eaves insulation. Solid aircrete wall Ensure continuity of the insulation throughout the junction. The use of over joist insulation is considered best practice as it eliminates the cold bridge caused by the joist. Use a proprietary eaves ventilator to ensure ventilation in accordance with BS5250, installed so as not to prevent free water drainage below tiling battens. be made to Accredited Detail Number: MEI-RE W/mK 0.070W/mK 0.071W/mK Page 31 of 40 APA Detail Number: EI - RE - 01

32 Solid externally insulated walls Aircrete separating wall / external wall abutment Continue wall insulation across abutment zone. Proprietary cavity sock (conductivity not more than 004W/m²K) Solid aircrete external wall Solid aircrete external wall Aircrete separating wall Refer to Approved Document B for fire safety requirements and Approved Document E for sound insulation requirements be made to Accredited Detail Number: MCI-IW W/mK 0.059W/mK 0.059W/mK (External wall block conductivity = 0.11W/mK) (External wall block conductivity = 0.15W/mK) (External wall block conductivity = 0.19W/mK) Page 32 of 40 APA Detail Number: EI - IW - 01

33 Solid externally insulated walls Dense block separating wall / external wall abutment Continue wall insulation across abutment zone. Proprietary cavity sock (conductivity not more than 004W/m²K) Solid aircrete external wall Solid aircrete external wall Dense block separating wall Refer to Approved Document B for fire safety requirements and Approved Document E for sound insulation requirements be made to Accredited Detail Number: MCI-IW W/mK 0.078W/mK 0.077W/mK (External wall block conductivity = 0.11W/mK) (External wall block conductivity = 0.15W/mK) (External wall block conductivity = 0.19W/mK) Page 33 of 40 APA Detail Number: EI - IW - 02

34 Solid externally insulated walls Windows and doors. Lintels (insulated base plate) Solid aircrete wall Ensure insulation having a minimum R-value of 0.6m²W/K overlaps the window frame/packing piece and lintel base plate. (eg 15mm of insulation with a conductivity of 0.025W/mK). be made to Accredited Detail Number: MEI-WD W/mK 0.028W/mK 0.027W/mK Page 34 of 40 APA Detail Number: EI - WD - 01

35 Solid externally insulated walls Windows and doors. Lintels be made to Accredited Detail Number: MEI-WD W/mK 0.000W/mK 0.000W/mK Page 35 of 40 APA Detail Number: EI - WD - 02

36 Solid externally insulated walls Windows and doors. Sills Wall insulation carried up to underside of sill member. Solid aircrete wall be made to Accredited Detail Number: MEI-WD W/mK 0.012W/mK 0.013W/mK Page 36 of 40 APA Detail Number: EI - WD - 03

37 Solid externally insulated walls Windows and doors. Jambs Ensure insulation having a minimum R-value of 0.6m²W/K overlaps the window frame/packing piece and lintel base plate. (eg 15mm of insulation with a conductivity of 0.025W/mK). Solid aircrete wall be made to Accredited Detail Number: MEI-WD W/mK 0.033W/mK 0.037W/mK Page 37 of 40 APA Detail Number: EI - WD - 04

38 Appendix BRE confirmation of Ψ and y-values Page 38 of 40 BRE Letter: HCT002/247482

39 Appendix BRE confirmation of Ψ and y-values Table 1 Page 39 of 40

40 Appendix BRE confirmation of Ψ and y-values Table 2 Page 40 of 40

Module 3.7. Thermal bridging

Module 3.7. Thermal bridging Module 3.7 Thermal bridging Learning Outcomes On successful completion of this module learners will be able to - Describe construction details which influence thermal bridging. 2 Introduction to thermal

More information

Introduction & Principles Issued in support of Junction Details, Parts 1 to 5

Introduction & Principles Issued in support of Junction Details, Parts 1 to 5 Accredited Construction Details (Scotland) 2010 For the limitation of thermal bridging and air infiltration in low and medium rise domestic buildings Introduction & Principles Issued in support of Junction

More information

Rockwool Flexi Insulation Application Guide

Rockwool Flexi Insulation Application Guide Pitched roof Rafters InterMediate floors INTERNAL partitions external Framed walls separating floors Separating Walls Rockwool Flexi Insulation Application Guide Ground floor The perfect fit for any framed

More information

Good Craftsmanship Guide. Carpentry and Joinery- Carcassing

Good Craftsmanship Guide. Carpentry and Joinery- Carcassing Good Craftsmanship Guide Carpentry and Joinery- Carcassing Introduction This Good Craftsmanship Guide highlights key problems with the major elements of Carpentry and Joinery - Carcassing, and gives guidance

More information

Multi-layer Insulation Blanket for Roofs

Multi-layer Insulation Blanket for Roofs Multilayer Insulation Blanket for Roofs Thermal Insulation in a 40mm thin, flexible, multilayer membrane Meets requirements of L1A, L1B 2010 In accordance with BR443 NHBC Acceptance Pitched & Flat roof

More information

Section 3.1.2. Timber Frame Walls. Single layer between studs. Single layer between studs with service void. Between studs with insulated lining

Section 3.1.2. Timber Frame Walls. Single layer between studs. Single layer between studs with service void. Between studs with insulated lining Section Timber Frame Walls Single layer between studs Product: Earthwool FrameTherm Rolls and Slabs Tf01 Single layer between studs with service void Product: Earthwool FrameTherm Rolls and Slabs Tf02

More information

Section 5.0. Basements. Wall insulated externally. Wall insulated internally. Ba02. Product: Polyfoam ECO Floorboard Ba01.

Section 5.0. Basements. Wall insulated externally. Wall insulated internally. Ba02. Product: Polyfoam ECO Floorboard Ba01. Section 5.0 Basements Wall insulated externally Product: Polyfoam ECO Ba01 Wall insulated internally Product: Polyfoam ECO Ba02 Basements Basements Basement design Waterproofing BS 8102: 2009 Code of practice

More information

Rochdale Building Control Guide. Approved Document C. Site preparation and resistance to contaminants and moisture

Rochdale Building Control Guide. Approved Document C. Site preparation and resistance to contaminants and moisture Rochdale Building Control Guide Approved Document C Site preparation and resistance to contaminants and moisture Dampness is often misdiagnosed within buildings, the approved document deals with prevention

More information

BER Assessors Dwellings Technical Bulletin

BER Assessors Dwellings Technical Bulletin BER Assessors Dwellings Technical Bulletin Issue No. 2/12 April 2012 Contents: 1. SUPPLEMENTARY ELECTRIC WATER HEATING IN SUMMER... 2 2. PITCHED ROOF U-VALUE CALCULATIONS... 8 2.1. PITCHED ROOF, INSULATED

More information

GUIDANCE SHEET FOR CONSERVATORIES, SUNROOMS AND EXTENSIONS TO DWELLINGS.

GUIDANCE SHEET FOR CONSERVATORIES, SUNROOMS AND EXTENSIONS TO DWELLINGS. GUIDANCE SHEET FOR CONSERVATORIES, SUNROOMS AND EXTENSIONS TO DWELLINGS. This leaflet provides guidance on how to attain compliance with The Building (Amendment) Regulations (Northern Ireland) 2006, Part

More information

Fire 2This Technical Bulletin has been commissioned by the UK SIP Association in

Fire 2This Technical Bulletin has been commissioned by the UK SIP Association in REV 1-12.12.11/TB002 Technical Bulletin Fire 2This Technical Bulletin has been commissioned by the UK SIP Association in conjunction with TRADA Technology and is intended to provide the reader with introductory

More information

NRG 75 CRF NRG GREENBOARD WALL SYSTEM

NRG 75 CRF NRG GREENBOARD WALL SYSTEM NRG GREENBOARD WALL SYSTEM NRG Energy Efficient Building Systems is pleased to announce a revolution in lightweight cladding systems. NRG Building Systems is the first and only company to achieve CodeMark

More information

Rev 1-12.2013. Code of Practice. SIP Technology. www.uksips.org

Rev 1-12.2013. Code of Practice. SIP Technology. www.uksips.org Rev 1-12.2013 Code of Practice SIP Technology www.uksips.org What are Structural Insulated Panels (SIPS)? SIPS are prefabricated, high performance, lightweight, building panels that can be used in floors,

More information

Innovation - High performance roof, wall and floor insulation board. delivering better performance

Innovation - High performance roof, wall and floor insulation board. delivering better performance 2010 VERSION 1 IRL High performance roof, wall and floor insulation board Innovation - delivering better performance PRODUCT SPECIFICATION INSTALLATION GUIDE I ve worked with Xtratherm for years, they

More information

STRUCTURAL CONCEPT FOR LIGHT GAUGE STEEL FRAME SYSTEM

STRUCTURAL CONCEPT FOR LIGHT GAUGE STEEL FRAME SYSTEM Chapter 9 STRUCTURAL CONCEPT FOR LIGHT GAUGE STEEL FRAME SYSTEM 9.1 BACKGROUND Steel is widely used in the construction of multi-storey buildings. However, steel construction is seldom used and is traditionally

More information

This seminar covers the principles, design and installation of ground bearing and suspended insulated floors. You will discover

This seminar covers the principles, design and installation of ground bearing and suspended insulated floors. You will discover Dow Construction Products Thermal Insulation of Floors This seminar covers the principles, design and installation of ground bearing and suspended insulated floors. You will discover Why a floor should

More information

BUILDING CONTROL GUIDANCE SHEET REPLACEMENT WINDOWS AND DOORS Last updated 16/11/2010

BUILDING CONTROL GUIDANCE SHEET REPLACEMENT WINDOWS AND DOORS Last updated 16/11/2010 Building Control Charnwood Borough Council Southfield Road Loughborough LE11 2TN BUILDING CONTROL GUIDANCE SHEET REPLACEMENT WINDOWS AND DOORS Last updated 16/11/2010 Page 1 of 6 PURPOSE: This Guidance

More information

DESIGNERS GUIDE TO DOMESTIC CONSERVATORIES

DESIGNERS GUIDE TO DOMESTIC CONSERVATORIES WBCA 403 DESIGNERS GUIDE TO DOMESTIC CONSERVATORIES A guide to assist those intending to install or who are involved in installing conservatories. Includes information about: conservatory and component

More information

CI/SfB (31.9) BETTER BY DESIGN PRODUCT GUIDE COMPLETE GUIDE TO THE IG PRODUCT RANGE. www.iglintels.com

CI/SfB (31.9) BETTER BY DESIGN PRODUCT GUIDE COMPLETE GUIDE TO THE IG PRODUCT RANGE. www.iglintels.com CI/SfB (31.9) Hh2 BETTER BY DESIGN PRODUCT GUIDE COMPLETE GUIDE TO THE IG PRODUCT RANGE www.iglintels.com BETTER BY DESIGN IG produce the UK s largest range of steel lintels backed by industry leading

More information

TGD L 2011. Limiting Thermal Bridging and Air Infiltration. Acceptable Construction Details. Introduction

TGD L 2011. Limiting Thermal Bridging and Air Infiltration. Acceptable Construction Details. Introduction TGD L 2011 Limiting Thermal Bridging and Air Infiltration Acceptable Construction Details Introduction Government of Ireland 2015 1 INTRODUCTION This guide to Acceptable Construction Details (ACDs) is

More information

Linea Weatherboard DIRECT FIX CONCRETE SLAB AND SOFFIT FIGURE 1

Linea Weatherboard DIRECT FIX CONCRETE SLAB AND SOFFIT FIGURE 1 Top plate Stud Soffit lining 45mm min nog Fix scotia bead Building underlay/james Hardie rigid air barrier Soffit Detail Building underlay/james Hardie rigid air barrier Bottom plate 25mm wide cant strip.

More information

Thermal Performance of Steel Beam Junctions using Different Connection Methods

Thermal Performance of Steel Beam Junctions using Different Connection Methods Modern methods of construction and prefabrication Sustainable building design Construction and life cycle costing Steel, concrete, timber, masonry and glass construction Construction design guidance and

More information

PRESTRESSED CONCRETE FLOORING BEAMS

PRESTRESSED CONCRETE FLOORING BEAMS PRESTRESSED CONCRETE FLOORING BEAMS TRIED & TRUSTED Introduction Established in 2001 TT Concrete Products Limited has become a prominent manufacturer of prestressed concrete flooring beams throughout the

More information

Energy Company Obligation (ECO): Technical Monitoring Questions

Energy Company Obligation (ECO): Technical Monitoring Questions Energy Company Obligation (ECO) Technical Monitoring Questions v1 30/05/2013 Energy Company Obligation (ECO): Technical Monitoring Questions Under ECO suppliers are required to instruct suitably qualified

More information

The Pocket Guide To Insulation August 2013

The Pocket Guide To Insulation August 2013 The Pocket Guide To Insulation August 2013 Introduction Knauf Insulation is the UK s leading manufacturer of insulation products, including: Earthwool glass and rock mineral wool Polyfoam ECO extruded

More information

ONLINE VERSION. The Building Regulations 2010 The Building (Approved Inspectors etc) Regulations 2010 ONLINE VERSION

ONLINE VERSION. The Building Regulations 2010 The Building (Approved Inspectors etc) Regulations 2010 ONLINE VERSION The Building Regulations 2010 The Building (Approved Inspectors etc) Regulations 2010 E1 E2 E3 E4 E Protection against sound from other parts of the building and adjoining buildings Protection against

More information

IRISH BUILDING CONTROL INSTITUTE HOTEL COURT HOTEL BALLYCONNELL CO CAVAN. 26 th MARCH 2009 TIMBER FRAME CONSTRUCTION

IRISH BUILDING CONTROL INSTITUTE HOTEL COURT HOTEL BALLYCONNELL CO CAVAN. 26 th MARCH 2009 TIMBER FRAME CONSTRUCTION IRISH BUILDING CONTROL INSTITUTE HOTEL COURT HOTEL BALLYCONNELL CO CAVAN 26 th MARCH 2009 TIMBER FRAME CONSTRUCTION Bill Robinson BSc. C. Eng. M. I. Struct. E. Timber Design Services 1 IS440 Timber frame

More information

!!!!!! !!! Decra Plus DPSW010 DPSTW011 DPSW012 DPSW013 DPSW014 DPSW015 DPSW016 DPSW020 DPSW021 DPSW024 DPSW030 DPSW031 DPSW035 DPSW030 DPSW031 DPSW035

!!!!!! !!! Decra Plus DPSW010 DPSTW011 DPSW012 DPSW013 DPSW014 DPSW015 DPSW016 DPSW020 DPSW021 DPSW024 DPSW030 DPSW031 DPSW035 DPSW030 DPSW031 DPSW035 Decra Plus Drawing no DPSW010 DPSTW011 DPSW012 DPSW013 DPSW014 DPSW015 Description Shown In Decra Brochure Most Commonly Used Detail t~êã=oççñ=b~îéë=aéí~áä=b~îéë=lîéêü~åö=táíü=fåëìä~íéç=c~ëåá~=~åç=pçññáí

More information

2014 British Columbia Building Code Changes

2014 British Columbia Building Code Changes District of Houston 250-845-2238 2014 British Columbia Building Code Changes A District of Houston interpretation of the 2014 Building Code Changes for 9.36 & 9.32 The following changes reflect the most

More information

Building Control Guidance Note

Building Control Guidance Note Issued 01/01/13 Rev Page 1 of 5 If you intend to convert an existing loft space into additional rooms you will need to apply for Building Regulation Approval. You may also need Planning Permission if you

More information

The Scottish Building Standards TECHNICAL HANDBOOK CONSERVATORIES

The Scottish Building Standards TECHNICAL HANDBOOK CONSERVATORIES The Scottish Building Standards TECHNICAL HANDBOOK CONSERVATORIES The Scottish Building Standards TECHNICAL HANDBOOK CONSERVATORIES Crown copyright 2006 Cover designed and produced by Astron Text pages

More information

Fig. 2 WALL-TO-WALL PANEL CONNECTIONS CORNER WALL CONNECTION

Fig. 2 WALL-TO-WALL PANEL CONNECTIONS CORNER WALL CONNECTION SIPS SCREWS WITH MINIMUM 1" PENETRATION IN WOOD MEMBER IN SIP WALL PANEL CONNECTED TO @ 24" O.C. MAXIMUM OUTSIDE SKIN EACH SIDE OF FRAMING TYP. AS RECOMMENDED BY FOAM CORE AS EACH SIDE OF FRAMING TYP.

More information

Building Regulations for the Conservation of Fuel and Power

Building Regulations for the Conservation of Fuel and Power Insulation CI/SfB Rn7 M2 First Issue April 2014 Building Regulations for the Conservation of Fuel and Power ENGLAND EXISTING DWELLINGS 2013 EDITION Low Energy Low Carbon Buildings Contents Page Introduction

More information

INSULATED PITCHED ROOFING

INSULATED PITCHED ROOFING DOW CONSTRUCTION PRODUCTS (a division of the Dow Chemical Company Ltd) INSULATED PITCHED ROOFING Welcome to this RIBA approved CPD self tutorial. First some information about the Dow Chemical Company itself:

More information

The WANZ Guide to Window Installation

The WANZ Guide to Window Installation The WANZ Guide to Window Installation as described in E2/AS1 Amendment 5 2 of 60 Contents Overview 5 Objective 5 Scope 5 Opening Preparation 7 Step P1 Preliminary Check 8 Step P2 Cut the Underlay 9 Step

More information

The WANZ Guide to Window Installation

The WANZ Guide to Window Installation The WANZ Guide to Window Installation as described in E2/AS1 Amendment 5 Ver. 1.1 Page 2 of 74 Contents Overview Page 5 Objective Page 5 Scope Page 5 Opening Preparation Page 7 Step P1 Preliminary Check

More information

BUILDING CONTROL GUIDANCE SHEET USE OF BREATHABLE ROOFING FELTS.

BUILDING CONTROL GUIDANCE SHEET USE OF BREATHABLE ROOFING FELTS. Building Control Charnwood Borough Council Southfield Road Loughborough LE11 2TN BUILDING CONTROL GUIDANCE SHEET USE OF BREATHABLE ROOFING FELTS. Last updated 16/11/2010 Page 1 of 6 PURPOSE: This Guidance

More information

Residential Refurbishment. September 2012. ThermoShell Internal Wall Insulation System Design Guide

Residential Refurbishment. September 2012. ThermoShell Internal Wall Insulation System Design Guide Residential Refurbishment September 2012 ThermoShell Internal Wall Insulation System Design Guide The importance of wall insulation in houses Buildings account for 40% of our energy consumption and in

More information

Residential Inspection Guidelines

Residential Inspection Guidelines Residential Inspection Guidelines 201 Pre-Pour Foundation Dimensions Building Location Certificate - if required in the building consent Construction and Advice Notes Check the building dimensions against

More information

fire separating walls #2

fire separating walls #2 210108 fire separating walls #2 ISSUE BSA has identified a number of instances of defective fire separating walls in duplexes, town houses and multi-residential complexes. The system of fire separating

More information

CI/SfB 2- Rj7 December 2010

CI/SfB 2- Rj7 December 2010 Engineered Timber Systems CI/SfB 2- Rj7 December 2010 STANDARD DETAILS Contents Wall Details W1 Typical wall section. W2 a Sectional elevation through soleplate fixing detail. Ground bearing slab. W2 b

More information

The Kingspan Insulation Price List 1 st January 2013

The Kingspan Insulation Price List 1 st January 2013 Insulation The Kingspan Insulation Price List 1 st January 2013 FOR BUILDING FABRIC INSULATION, CAVITY CLOSERS AND MEMBRANES Visit our website: www.kingspaninsulation.co.uk Low Energy - Low Carbon Buildings

More information

Building Construction. Lightweight construction. Conventional Construction

Building Construction. Lightweight construction. Conventional Construction Ventilation 53 Building Construction The firefighter s ability to safely and efficiently ventilate a building through its roof will depend to some degree on the firefighter s understanding of roof construction.

More information

Envelope INSULATION BATT (2) Avoid Using Batt Insulation With Metal Framing. Pressure or Friction Fit

Envelope INSULATION BATT (2) Avoid Using Batt Insulation With Metal Framing. Pressure or Friction Fit R-H-DI1 INSULATION BATT NR-E-IB1 Avoid Using Batt Insulation With Metal Framing Batt insulation should not be used with metal framing systems. Although it is common to see fiberglass batt insulation installed

More information

Lintel Product Selector

Lintel Product Selector Uniclass L325:P4142 Cl/Sfb October 2014 EPIC F631:X442 (31.9) Hh2 www.catnic.com Lintel Product Selector October 2014 Care has been taken to ensure that the contents of this publication are accurate, but

More information

CERTIFICATE NAME OF PRODUCT MANUFACTURER PRODUCT DESCRIPTION CERTIFICATION PROCEDURE. No VTT C-6044-10 Date of issue 11.10.2010, Updated July 1, 2011

CERTIFICATE NAME OF PRODUCT MANUFACTURER PRODUCT DESCRIPTION CERTIFICATION PROCEDURE. No VTT C-6044-10 Date of issue 11.10.2010, Updated July 1, 2011 CERTIFICATE NAME OF PRODUCT No VTT C-6044-10 Date of issue 11.10.2010, Updated July 1, 2011 H-CONTROL REFLEX+ reflective insulating vapour control layer for roof and wall applications MANUFACTURER ACTIS

More information

The Scottish Building Standards TECHNICAL HANDBOOK CONSERVATORIES 2 ND EDITION

The Scottish Building Standards TECHNICAL HANDBOOK CONSERVATORIES 2 ND EDITION The Scottish Building Standards TECHNICAL HANDBOOK CONSERVATORIES 2 ND EDITION CONTENTS Page 1 STATUS OF THIS DOCUMENT 3 2 WHEN YOU CAN USE THIS DOCUMENT 4 3 INTRODUCTION 5 4 SUBSOIL CONDITIONS 6 5 FOUNDATIONS

More information

Section 4.3. Separating Floors. Timber frame floor with I-Beams. Upgrading existing timber floor with new ceiling. Timber frame floor with

Section 4.3. Separating Floors. Timber frame floor with I-Beams. Upgrading existing timber floor with new ceiling. Timber frame floor with Section Separating Floors Timber frame floor with I-Beams Product: Earthwool Acoustic Roll and Floorfoam Easy Edge Strip Timber frame floor with solid timber joists Product: Earthwool Acoustic Roll and

More information

Glass partitions SFB 3074

Glass partitions SFB 3074 Glass partitions SFB 3074 Our facade system SFB 3074 is innovative in its design. We have made a great effort to obtain an energy effective system. The future requirements regarding the economical use

More information

BUILDING CONTROL GUIDANCE FOR DOMESTIC LOFT CONVERSIONS

BUILDING CONTROL GUIDANCE FOR DOMESTIC LOFT CONVERSIONS BUILDING CONTROL GUIDANCE FOR DOMESTIC LOFT CONVERSIONS OCTOBER 2010 EDITION 4-1 - Introduction This document intends to provide education and guidance on how some of the technical design and construction

More information

domestic structure SBSG 2007 ANNEX C

domestic structure SBSG 2007 ANNEX C domestic structure SBSG 2007 ANNEX C Small buildings structural guidance 1.A General 1.B Stability 1.C Foundations 1.D Masonry walls 1.E Timber frame walls 1.F Timber floor and roof members contents domestic

More information

Installation Window Building In Details

Installation Window Building In Details Installation Window Building In Details INSTALLATION Photo courtesy of Rowe Aluminium DATE: NOVEMBER 2009 REPLACES: AUGUST 2003 INSTALLATION Installation Replaces: Scale: NOT TO SCALE Vantage snap-on couplers

More information

Ecojoist. Practical benefits of Ecojoist. www.eleco.com/gang-nail

Ecojoist. Practical benefits of Ecojoist. www.eleco.com/gang-nail Ecojoist Practical benefits of Ecojoist. www.eleco.com/gang-nail Gang-Nail Systems, an Eleco plc company, offer integrated solutions f the timber engineering industry which assist in reducing design, production

More information

FOREST OF DEAN DISTRICT COUNCIL BUILDING CONTROL SERVICES. Building Control Guidance for. Loft Conversions

FOREST OF DEAN DISTRICT COUNCIL BUILDING CONTROL SERVICES. Building Control Guidance for. Loft Conversions FOREST OF DEAN DISTRICT COUNCIL BUILDING CONTROL SERVICES Building Control Guidance for Loft Conversions 1ST EDITION - AUGUST 2008 About this document This document intends to provide education and guidance

More information

RULING OF THE MINISTER OF MUNICIPAL AFFAIRS AND HOUSING

RULING OF THE MINISTER OF MUNICIPAL AFFAIRS AND HOUSING BUILDING CODEACT, 1992 RULING OF THE MINISTER OF MUNICIPAL AFFAIRS AND HOUSING Pursuant to clause 29(l)(b) of the Building Code Act, 1992. as amended, the Director of the Building and Development Branch

More information

Domestic Extensions. Monmouthshire County Council. Building control guidance document

Domestic Extensions. Monmouthshire County Council. Building control guidance document Monmouthshire County Council Building control guidance document Domestic Extensions Building Regulations 2010 (with 2013 amendments) For use in Wales May 2013 Edition Guidance produced for Monmouthshire

More information

SOUND INSULATION FOR EXTERIOR WALLS AND FACADE SYSTEMS

SOUND INSULATION FOR EXTERIOR WALLS AND FACADE SYSTEMS NOISE TECHNICAL FACT SHEET FACT SHEET 5 SOUND INSULATION FOR EXTERIOR WALLS AND FACADE SYSTEMS The sound insulation of exterior walls and roof-ceiling systems refers to their ability to reduce external

More information

Development Services City of Lawrence, KS

Development Services City of Lawrence, KS Development Services City of Lawrence, KS Building Planning Table R301.2 (1) Climatic & Geographic Design Criteria Building Planning The design criteria for wind speed increased from 90 MPH to 115 MPH.

More information

EXTRA. NHBC s technical newsletter April 2002 Issue 23. This edition includes:

EXTRA. NHBC s technical newsletter April 2002 Issue 23. This edition includes: NHBC s technical newsletter April 2002 Issue 23 This edition includes: 2 3 4 5 6 Major changes to NHBC glazing Standards Glazing requirements amended to improve the durability of insulating glass units.

More information

Section 2.4. Built-up Metal Roofs. Rail and bracket system. Standing seam system. Bu02. Product: Earthwool FactoryClad range Bu01

Section 2.4. Built-up Metal Roofs. Rail and bracket system. Standing seam system. Bu02. Product: Earthwool FactoryClad range Bu01 Section Built-up Metal Roofs Rail and bracket system Product: Earthwool FactoryClad range Bu01 Standing seam system Product: Earthwool FactoryClad range and Earthwool Universal Slab Bu02 Built-up Metal

More information

Extension. for. Pretend Customer 123 A Road HA7 9BP. at: 123 A Road HA7 9BP

Extension. for. Pretend Customer 123 A Road HA7 9BP. at: 123 A Road HA7 9BP for Pretend Customer at: Pretend Customer Site address: Monday, 23 November 2015 Dear Pretend Customer, Subject: Thank you for your valued enquiry and instructions to quote for the above project. We are

More information

Conventions for U-value calculations

Conventions for U-value calculations Conventions for U-value calculations 2006 edition Brian Anderson BRE Scotland BRE is committed to providing impartial and authoritative information on all aspects of the built environment for clients,

More information

NEW AUSTRALIAN STANDARDS FOR MASONRY IN SMALL STRUCTURES S.J. LAWRENCE

NEW AUSTRALIAN STANDARDS FOR MASONRY IN SMALL STRUCTURES S.J. LAWRENCE NEW AUSTRALIAN STANDARDS FOR MASONRY IN SMALL STRUCTURES S.J. LAWRENCE Conjoint Professor Centre for Infrastructure Performance and Reliability The University of Newcastle Callaghan, NSW, Australia A.W.

More information

Agrément Certificate 06/4300 Product Sheet 1

Agrément Certificate 06/4300 Product Sheet 1 Domestic and General Insulation Ltd Energy House Magnis Works Roman Road Hereford HR4 9QR Tel: 0844 543 0043 Fax: 01432 268680 e-mail: headoffice@dgi.org.uk website: www.dgi.org.uk APPROVAL INSPECTION

More information

Low Energy Low Carbon Buildings

Low Energy Low Carbon Buildings I n s u l a t i o n CI/Sfb (27.9) Rn7 M2 Eighth Issue March 2011 TR27 LPC/FM INSULATION FOR FLAT ROOFS WATERPROOFED WITH FULLY ADHERED SINGLE PLY, PARTIALLY BONDED BUILT UP FELT, MASTIC ASPHALT AND COLD

More information

Residential Foundations and Basements

Residential Foundations and Basements Residential Foundations and Basements Disclaimer All of the following information is based on the 2006 International Residential Code with Kentucky Amendments. As some information is paraphrased, article

More information

CITY OF VAUGHAN SCHEDULE O LOT GRADING DESIGN FOR RESIDENTIAL DEVELOPMENT

CITY OF VAUGHAN SCHEDULE O LOT GRADING DESIGN FOR RESIDENTIAL DEVELOPMENT Page 1 CITY OF VAUGHAN SCHEDULE O LOT GRADING DESIGN FOR RESIDENTIAL DEVELOPMENT CIVIC CENTRE 2141 MAJOR MACKENZIE DRIVE MAPLE ONTARIO L6A 1T1 905-832-2281 Page 2 SECTION 1 - GENERAL OBJECTIVES To provide

More information

STEP-BY-STEP. construction guide. Delivering better priced Conservatories, Sun Lounges and Garden Rooms via the Internet.

STEP-BY-STEP. construction guide. Delivering better priced Conservatories, Sun Lounges and Garden Rooms via the Internet. STEP-BY-STEP construction guide Delivering better priced Conservatories, Sun Lounges and Garden Rooms via the Internet. Welcome to our CONSERVATORY AND SUNROOM CONSTRUCTION GUIDE What is the specification

More information

8/18/14. Introduction to. Framing. Terminology and Concepts

8/18/14. Introduction to. Framing. Terminology and Concepts 8/18/14 Introduction to Framing Terminology and Concepts Terminology: Framing Level Two points on exactly the same horizontal plane. Square Intersecting lines or faces that form an exact 90 angle. Plumb

More information

Foundations and Substructures

Foundations and Substructures Ground workers handbook Foundations and Substructures Introduction The Ground Workers Handbook gives guidance to site managers and site staff on any particular issues on your site for traditional forms

More information

EAST LYME HIGH SCHOOL

EAST LYME HIGH SCHOOL Overview: 1971 N 1966 GYM 1966 CLASSROOM WING 1966 AUD. 1971 GYM 1998 1998 POOL EAST LYME HIGH SCHOOL Original 1966 Building: The original East Lyme High School was constructed in 1966 and was composed

More information

House building is changing fast NHBC unveils new Standards Chapters on curtain walling and cladding, and light steel framed walls and floors

House building is changing fast NHBC unveils new Standards Chapters on curtain walling and cladding, and light steel framed walls and floors W42_Stand_Extra_32 15/3/05 9:17 am Page 2 NHBC s technical newsletter April 2005 Issue 32 This edition includes: 2 House building is changing fast NHBC unveils new Standards Chapters on curtain walling

More information

CHAPTER 6 CONSTRUCTION TYPES

CHAPTER 6 CONSTRUCTION TYPES CHAPTER 6 CONSTRUCTION TYPES SECTION 601 GENERAL 601.1 Scope. Provisions of this chapter shall govern the classification of construction type by materials and fire resistance of its elements and the use

More information

RESIDENTIAL PLUMBING ALTERATIONS PERMIT REQUIREMENTS

RESIDENTIAL PLUMBING ALTERATIONS PERMIT REQUIREMENTS RESIDENTIAL PLUMBING ALTERATIONS PERMIT REQUIREMENTS The following guidelines are intended to assist with the permit acquisition process with regard to Plumbing Alterations. Not all information, or additional

More information

ABOUT CWB CERTIFICATION/ QUALIFICATION The work CWB does on behalf of our clients can be divided into five main categories:

ABOUT CWB CERTIFICATION/ QUALIFICATION The work CWB does on behalf of our clients can be divided into five main categories: CWB CERTIFICATION/ CWB CERTIFICATION/ QUALIFICATION QUALIFICATION SERVICES SERVICES CANADIAN WELDING CERTIFICATION AN OVERVIEW Canada, like many countries around the world, has specific rules and regulations

More information

Installation Details. D1 General D2 Walls D3 Ceilings D4 Reference. D Installation Details

Installation Details. D1 General D2 Walls D3 Ceilings D4 Reference. D Installation Details D Installation Details D1 General D2 Walls D3 Ceilings D4 Reference D Installation Details D Contents D1 General Installation and Fastening Sequence for Steel Studs D1.1 Fastener Selection D1.3 D2 Walls

More information

BuildDesk U 3.4. Manual

BuildDesk U 3.4. Manual BuildDesk U 3.4 Manual June 2010 Page 1 /102 Contents 1 Foreword...4 1.1 BuildDesk U 3.4...4 1.2 Help functions...4 1.2.1 Quickstart in 8 steps...4 1.2.2 BuildDesk Helpdesk...5 2 Introduction...6 2.1 Short

More information

The better way to build TM. Installation Manual. FOUNDATION SIPs & FROST WALLS SIPs

The better way to build TM. Installation Manual. FOUNDATION SIPs & FROST WALLS SIPs The better way to build TM Installation Manual FOUNDATION SIPs & FROST WALLS SIPs February 2016 PWF FOUNDATION & FROST WALL SIPs Installation Manual Table of Contents Topics General Requirements...................................

More information

Chapter 2: Foundations

Chapter 2: Foundations Chapter 2: Foundations Crawlspace [V502.1.2] Vents. Vents in the crawlspace help keep floor insulation and floor framing dry. Crawlspace vents also reduce the potential for radon buildup under the floor.

More information

Design guide. Part 1: Structural Design

Design guide. Part 1: Structural Design Design guide Part 1: Structural Design Design guide Part 1: Structural Design Advantages: Fast Economical Strong Insulating Environmentally friendly Versatile Modernist house supplied by SIPBuild Vernacular

More information

Guide to the safe installation of downlighters in dwellings

Guide to the safe installation of downlighters in dwellings Guide to the safe installation of downlighters in dwellings Technical guidance for designers and installers 01 Guide to the safe installation of downlighters in dwellings Technical guidance for designers

More information

Chapter 5.4. Waterproofing of basements and other below ground structures

Chapter 5.4. Waterproofing of basements and other below ground structures Chapter Waterproofing of basements and other below ground structures Waterproofing of basements and other below ground structures CONTENTS SCOPE DESIGN Clause Page D1 Design standards D1 2 D2 Statutory

More information

If stepping is required, step at 180mm as seen in this picture.

If stepping is required, step at 180mm as seen in this picture. Cast Foundations to standard building regulations requirements. Foundations must be cast completely level, 600mm wide by 230mm deep for single storey, double storey is not allowed by NHBRC. If stepping

More information

technology UICK progressive sustainable any design, any shape, any colour, anywhere you like!

technology UICK progressive sustainable any design, any shape, any colour, anywhere you like! uality using advanced building technology UICK uality innovative progressive sustainable any design, any shape, any colour, anywhere you like! 2 NicheQ is an award winning progressive and innovative builder

More information

WARMFILL CAVITY WALL INSULATION WARMFILL CAVITY WALL INSULATION FOR MASONRY CAVITY WALLS

WARMFILL CAVITY WALL INSULATION WARMFILL CAVITY WALL INSULATION FOR MASONRY CAVITY WALLS Warmfill Limited Unit 5, Port of Larne Business Park Redlands Road Larne BT40 1AX Tel: 028 9042 8260 Fax: 028 9042 7641 e-mail: sales@warmfill.com website: www.warmfill.com APPROVAL INSPECTION TESTING

More information

How To Certify The Scottsdale Construction System

How To Certify The Scottsdale Construction System BRE CERTIFICATION LIMITED PRODUCT SCOTTSDALE CONSTRUCTION SYSTEM CERTIFICATE NUMBER 129/07 DATE OF ISSUE December 2007 SUPPLIED BY Scottsdale Construction System Ltd SUMMARY The Scottsdale Construction

More information

0331 Brick and block construction

0331 Brick and block construction 0331 BRICK AND BLOCK CONSTRUCTION This worksection has been written for Class 1 and 10a buildings that fully conform to the scope of AS 4773.1. If the works include isolated structures, (totally separate

More information

Internal wall insulation in existing housing

Internal wall insulation in existing housing Energy Efficiency Best Practice in Housing Internal wall insulation in existing housing A guide for specifiers and contractors Cost-effective External wall appearance maintained Easier to install and maintain

More information

PASSIVE FIRE PROTECTION SYSTEMS Application & Technical Manual: Ceilings & Floors

PASSIVE FIRE PROTECTION SYSTEMS Application & Technical Manual: Ceilings & Floors PASSIVE FIRE PROTECTION SYSTEMS Application & Technical Manual: Ceilings & Floors For distribution in Asia Pacific PASSIVE FIRE PROTECTION SYSTEMS Application & Technical Manual: Ceilings & Floors Contents

More information

Fire safety in timber buildings

Fire safety in timber buildings Fire safety in timber buildings Introduction Fire spread in buildings is a risk to life safety for which the Building Regulations (for England and Wales 1,2, Scotland 3 and Northern Ireland 4 ) aims to

More information

Timber Frame Walls Rethinking Construction

Timber Frame Walls Rethinking Construction Insulation Fifth Issue November 2007 Timber Frame Walls Rethinking Construction INSULATION BEST PRACTICE FOR THE 21ST CENTURY Summary 9 mm OSB sheathing 3 mm skim coated 15 mm plasterboard Rock or glass

More information

2009 IECC Update. Scope. Content. International Energy Conservation Code

2009 IECC Update. Scope. Content. International Energy Conservation Code 2009 IECC Update International Energy Conservation Code Scope The code applies to both residential and commercial buildings. In the code, the United States is divided into eight climate zones which are

More information

The formation of roof waterproofing details calls for

The formation of roof waterproofing details calls for 3.5 BUILT-UP ROOFING DETAIL DESIGN INTRODUCTION The formation of roof details calls for a combination of the skills of the designer and the roofer. There are many different approaches to detail design

More information

CI/SfB (31.9) BETTER BY DESIGN LINTEL GUIDE SPECIFIER S GUIDE TO OUR RANGE OF LINTELS. www.iglintels.com

CI/SfB (31.9) BETTER BY DESIGN LINTEL GUIDE SPECIFIER S GUIDE TO OUR RANGE OF LINTELS. www.iglintels.com CI/SfB (31.9) Hh2 BETTER BY DESIGN LINTEL GUIDE SPECIFIER S GUIDE TO OUR RANGE OF LINTELS www.iglintels.com BETTER BY DESIGN IG produce the UK s largest range of steel lintels backed by industry leading

More information

TR21. I n s u l a t i o n. Low Energy Low Carbon Buildings

TR21. I n s u l a t i o n. Low Energy Low Carbon Buildings I n s u l a t i o n CI/Sfb (27.9) Rn7 M2 Fourth Issue March 2011 TR21 INSULATION FOR FLAT ROOFS WATERPROOFED WITH PARTIALLY BONDED BUILT UP FELT AND MASTIC ASPHALT High performance rigid thermoset insulation

More information

Cavity Drain R20 is manufactured from1.0mm thick black high density polyethylene with studs approximately 20mm high.

Cavity Drain R20 is manufactured from1.0mm thick black high density polyethylene with studs approximately 20mm high. CI/SfB Tn6 L6813 September 2013 RIW CAVITY DRAIN R20 R20 is manufactured from1.0mm thick black high density polyethylene with studs approximately 20mm high. Other systems are available for specific uses,

More information

MUNICODE SERVICES LTD.

MUNICODE SERVICES LTD. The Preserved Wood Foundation Guide MUNICODE SERVICES LTD. Prepared by MuniCode Services Ltd. Outline and Restrictions of this Guide The following information required for the construction of Preserved

More information

KINGSPAN INSULATION KINGSPAN KOOLTHERM K12 FRAMING BOARD INSULATION

KINGSPAN INSULATION KINGSPAN KOOLTHERM K12 FRAMING BOARD INSULATION Kingspan Insulation Limited Pembridge Leominster Herefordshire HR6 9LA Tel: 01544 388601 Fax: 01544 388888 e-mail: general.enquiries@kil.kingspan.co.uk APPROVAL INSPECTION TESTING CERTIFICATION TECHNICAL

More information

SG Series 65mm Frame Windows (Fixed Lite Window Illustrated)

SG Series 65mm Frame Windows (Fixed Lite Window Illustrated) (Fixed Lite Window Illustrated) SINGLE LEAF CLADDING / CORRUGATED STEEL (Awning Window Illustrated) SINGLE LEAF CLADDING / FOAM BOARD (Casement Window Illustrated) BRICK VENEER CONSTRUCTION (Horizontal

More information