1 DOW CONSTRUCTION PRODUCTS (a division of the Dow Chemical Company Ltd) INSULATED PITCHED ROOFING Welcome to this RIBA approved CPD self tutorial. First some information about the Dow Chemical Company itself: US origin, 100 years old. 2nd largest chemical company in the world Produces: chemicals, plastics, agrochemicals. Annual sales: 18 billion. Employs: 45,000 globally (Europe 8,000) Dow in the UK STYROFOAM* production since 1969 : polystyrene produced at Barry, Wales; extruded foam insulation produced in Kings Lynn. Dow Construction Products offers the STYROFOAM range of blue extruded polystyrene foam insulation: Floors - Floormate* 200,350,500 and 700 Cavity Walls Walls internally Structures below ground Pitched Roofs Inverted Flat Roofs Conventional Flat Roofs - Wallmate* CW - Styrofoam* IB - Perimate* DI - Roofmate* PR, RL - Roofmate* SL, LG - Deckmate* CM, FF * Trademarks of the Dow Chemical Company

2 Dow Construction Products Insulated Pitched Roofing This self-tutorial seminar covers all aspects of the so called Warm Roof Concept at rafter level pitched roof insulation. You will discover The insulation options The advantages of the warm versus the cold roof How a warm roof is constructed The general design considerations, relevant codes of practice and applicable standards to adhere to The role and selection of the various components with particular emphasis on the insulation, the underlay, fasteners and methods of securement The relevance and importance of the building physics issues, thermal insulation, condensation and ventilation The ins and outs of detail design: eaves, ridge, valley, hip and roof penetrations How the warm roof concept has been put to the test in the field

3 INSULATED PITCHED ROOFING INTRODUCTION: It is estimated that today around 10% of new pitched roofs are insulated at rafter level and that this figure is increasing. Various insulation solutions are available which are dependent on the type of insulation used and its location ( ie above, between or below the rafters or a combination of these ), and the type of underlay used. Although the insulation of pitched roofs cannot be considered a new application it is now the subject of much debate both in the technical press and within the industry itself - indeed the BRE, NFRC and BSI are all actively involved. The aim of this seminar is to review the application from an insulant manufacturer s point of view.

4 CONTENT Insulation options Advantages of an insulated roof structure The Warm roof concept Design considerations Roof build-up: the components Building Regulations: requirements Case study Detailing Conclusions

5 Roof structure: uninsulated attic/loft space insulation at ceiling level insulation at ceiling / joist level - mineral / glass fibre normally used attic / loft space ventilated (vents provided at eaves and at ridge) Note: Could adequate ventilation be provided by a water vapour permeable (breather) underlay and thus do away with providing vents at eaves and ridge level?

6 Roof structure: insulated insulation at rafter level room in the roof Insulation can be a) above, b) between c) below the rafters or a combination of these Warm roof insulation above rafters sometimes referred to as sarking insulation (see BRE Thermal insulation: avoiding risks BR262 Hybrid roof : insulation between and/or under rafters. Note: Focus of this seminar will be on the warm pitched roof as this is the optimum ( and perhaps the most challenging ) of the insulation options.

7 ADVANTAGES : INSULATED VS UNINSULATED ROOF STRUCTURE Increased living /working space for same footprint Additional space at lower cost Added value Allows room to grow Cost of providing additional space in the attic can be less than 50% of the standard floor cost. plus with a warm roof: - reduced risk of condensation on structural membranes. - thermal movement of roof structure reduced. - roof structure kept dry - no need for timber preservative treatment.

8 THE WARM PITCHED ROOF - roof build up Counterbatten Tiling batten Tiles Vapour permeable underlay Insulation Rafter Insulation shown above and between rafters Vapour permeable underlay (breather type) can be laid either in direct contact with the insulation ( as shown ) or over the counterbattens Suitable for new build or where the roof covering is to be replaced ( note increase in roof height! ) and where it would be difficult to provide eaves ventilation Note: Need for a vapour control layer (VCL)? YES for areas exposed to high humidity levels e.g swimming pools, kitchens, changing rooms. Use plasterboard (13 mm) to cover exposed XPS insulation.

9 THE WARM PITCHED ROOF CONCEPT rigid insulation over (and between) rafters plus a water vapour permeable (breather) underlay Note: Where proprietary products are to be specified, manufacturers recommendations should be followed. Designers should satisfy themselves that the performance of these products and the given recommendations have been proven by relevant experience in use or by test data based on the conditions and methods of application in equivalent and appropriate internal and external climatic conditions.

10 THE WARM PITCHED ROOF First thatched roofing! Developed from Scottish sarking - early 80 s Agrément certification - mid 80 s Thousands roofs, millions sq metres installed Includes all insulation types Minimal condensation problems No securement problems Note: Thatched roof - really is a breathing warm roof Sarking - originated in Germany / Scandinavia refers to a sheet or underskirt of boarding. - traditionally in Scotland 25mm thick close timber boarding at underslating level. - helps reduce effect of wind uplift on slates.

11 Design considerations! BS 5268 : Part 7 : 1990 Roof construction - rafters & purlins (Approved Document A : 1994 )! BS 5534 : Part 1 : 1997 Slating & tiling! BS 6399 : Part 1 : 1984 Dead loading! BS 6399 : Part 2 : 1995 Wind loading! BS 6399 : Part 3 : 1988 Imposed & snow loading

12 ROOF BUILD-UP - THE COMPONENTS Rafters Vapour Control Layer Insulation Underlay Battens Fasteners

13 RAFTERS Consider: Roof slope Cut vs trussed Dimensions (and tolerances) Spacing Bracing Note: Must assume that insulation does not contribute to the racking strength of roof structure.

14 VAPOUR CONTROL LAYER (VCL) Usually a membrane (eg 500 gauge polyethylene sheet) Substantially reduces transfer of water vapour Installed on warm side of insulation A VCL reduces water vapour transfer through any building component in which it is incorporated. (BRE document BR 262: Thermal insulation - avoiding risks specifies a minimum water vapour resistance of 200 MNs/g. BS 5250 refers to the use of 500 gauge polyethylene with a range of 200 to 350 MNs/g, typically 250 MNs/g.) The VCL should be installed on the warm side of the insulation. ( Note that a VCL at ceiling level will require increased ventilation below it during the wet trade phases of construction.) Performance of a VCL also is dependant on workmanship and build ability - see Clause 9.2 of BS It is essential that it is adequately lapped and sealed so as to maintain its integrity. Particular care should be given to detail design and installation around penetrations through the VCL (e.g services, compartment walls) and to the sealing of punctures caused by fasteners.

15 INSULATION Location - above / between / below (or any combination) Selection - thermal performance - water vapour permeability - water resistance (absorption) - user friendliness Thickness Installation - thermal integrity - convection tight Location: (a) over the rafters (b) between the rafters (c) under the rafters or any combination of these Note : Option (a) is sometimes referred to as a warm roof construction or as sarking insulation. All options can be used for new roof constructions or where the roof is to be replaced from rafter level up. Only options (b) and (c) can be used in situations where the roof covering cannot be removed or replaced. Selection: Rigid, semi-rigid and flexible insulants can be used. Each has its own specific physical characteristics as regards performance and installation requirements - the manufacturers recommendations should be followed. cont ->

16 Thickness: The thickness of the insulation will be determined by the required thermal performance as well as by the roof construction (see Approved Document L). It is important to ensure the continuity of the thermal insulation. If this is broken eg by the rafters and /or penetrations through the roof, the resulting thermal bridges can increase the risk of localised condensation and pattern staining of ceilings at rafter line. Note: Building Regulations require the effect of thermal bridging to be taken into account when calculating the thermal performance (U-value) of the roof. Refer to BS 5250 Section 9.6 and BRE Document 262: Thermal insulation - avoiding risks. Installation: Thermal integrity is essential. The roof void should be completely insulated. For example gable end walls will need to be insulated to their full height. The designer should take care to ensure that there are no gaps or breaks in the insulation envelope. The insulation should be installed to fit tightly at ridges, at eaves and around penetrations. Seal if necessary with flexible (polyethylene) or PU foam. Insulation boards should fit tightly together with no gaps around them. Rigid board joints should be correctly positioned so as to shed any likely incoming external water. Some types of board will require their joints to be sealed with tape - refer to the manufacturers instructions. Special care needs to be taken with rebated boards designed for over and between rafter installation e.g Roofmate PR to ensure that the rafter spacing is accurately set out so as to avoid gaps or unnecessary cutting of boards. Convection tight/airtight: A roof system in which the free movement of air through any section of the construction is prevented by use of airtight joints and seals is said to be convection tight or airtight.

17 INSULATION - typical physical properties XPS EPS PUR MF Thermal conductivity W/mK Water vapour resistance (relative to MF) Water vapour resistivity MNs/gm Water absorption % vol ? Compressive strength kpa max 175 max 120 max Density kg/m XPS EPS PUR MF - extruded foamed polystyrene - expanded foamed polystyrene (bead board) - polyurethane/polyisocyanurate - mineral fibre Thermal conductivity XPS, EPS measured at 90 days (after equilibrium reached) - long term value. PUR measured immediately after production ie before equilibrium reached - short term value. Water vapour resistance Determined relative to MF(air) for equivalent U-value thicknesses (XPS=50mm) Water absorption Be sure to take into account likely effect on thermal conductivity!

18 ROOFMATE* RL, PR - physical characteristics PR RL Density kg/m Thermal conductivity W/mK Compressive strength kn/m Water absorption % vol Water vapour resistivity MNs/gm Board size mm 2500 x x 600 Thickness mm 80, 90, , 50 Edge profile - rebated tongue & groove Roofmate RL Tongue and groove on all sides. Board should be laid so the tongues in horizontal joints face up the slope. Roofmate PR Available with edge flanged to suit 38 and 50mm rafters - type 38 and 50 respectively. Boards should be laid so that horizontal lap joints (i.e top and bottom of boards) point down the slope so that boards higher up the roof overlap those further down (boards are marked so as to facilitate this e.g with an arrow pointing up the slope of the roof).

19 UNDERLAYS- REQUIREMENTS - TRADITIONAL Keep water (snow, dust) out Air tight Adequate strength - WATER VAPOUR PERMEABLE (Breather) As Traditional plus water vapour permeability Keep water etc. out - secondary defense against wind driven rain, snow and dust. Air tight - to reduce wind load on primary roof covering. Adequate strength - tensile, tear strength (for nails), extensibility (reduce movement under wind pressure). Working temp. range - 20 to + 80 deg C. Water vapour permeability - Traditional underlay e.g BS747 Type IF felt These are defined (BS5250) as having a water vapour resistance in excess of 50MNs/g - Water vapour permeable (breather) underlay BS 4016 : 1995 Flexible building membranes (breather type) - max. water vapour resistance 0.6MNs/g BRE Thermal Insulation : Avoiding risks - specifies MNs/g.

20 UNDERLAYS WATER VAPOUR RESISTANCE Traditional Breather MNs/g BS 747 Type IF felt Monarfil* Permo* 0.20 Tyvek* HD - Soft 0.24 Tyvek* Pro 0.16 Roofshield* 0.08 Monarperm* Insulation XPS - 90mm 85 PUR - 80mm 46 MF mm 0.6 * Tradenames Monarfil reinforced polyethylene (0.25mm) Permo Tyvek Soft Tyvek Pro Roofshield - laminated spunbond polypropylene - spunbond polyethylene (0.19mm) - spunbond polyethylene / polypropylene laminate (0.42mm) - spunbond polypropylene laminate (0.60mm) Monarperm spunbond polypropylene (0.45mm)

21 BREATHER UNDERLAYS Performance criteria should reflect real life roof conditions Water vapour permeability + water resistance - working conditions - compatibility - tenting - blinding Installation Roof conditions : - 20 to C, 0 to 100% RH, seasonal, daily, hourly changes Compatibility Tenting - specifically with timber preservatives - water ( surfactants ) vs solvent based ( swelling ) cause loss of performance. - a problem with the early materials. Underlay leaks when touching surface below. Blinding - by dust, ice (?) Installation or - laid direct on insulation (common practice in North) - can cause noise (ie wind flutter )? - supported on counterbattens(common practice in South) - userfriendliness => slipperiness underfoot for roofer!

22 BATTENS Tiling, counter Dimensions Location of underlay Securement When the insulation is installed over the rafters, counter-battens will be required to secure the insulation to the rafters and to provide drainage under the tile battens - refer to BS 5534 Part 1 Section Care should be taken to ensure that the construction techniques employed provide for adequate and accurate location of the fixings used to secure the battens and counterbattens to the rafters. Width determined by diameter of fasteners (10-11 x diameter) Thickness determined by method of securement Underlay can be in direct contact with surface of insulation or located above the counter battens Who installs what? Carpenter - up to and including counterbattens (rafters, insulation) Roofer - above counterbattens (underlay, tile battens, tiles) or from the rafters up (insulation, battens, underlay,tiles)

23 SECUREMENT - need to secure tiles/slates, underlay and insulation against dead wind and imposed loads Insulation consider: - thickness (over rafters), physical properties Fasteners eg BS 1202 nails, Helifix Inskew, Proctor PR nails consider: - penetration, pull-out strength, deflection under load - ease and accuracy of installation Refer to manufacturers for advice

24 SECUREMENT cont When the insulation is installed over the rafters the fasteners securing the counter battens or battens through to the rafters must be of sufficient strength and length and correctly spaced so as to resist dead, wind and imposed loads. The following should be considered: Site locality - the assessment and determination of wind and imposed loads Roof Construction - roof pitch, rafter spacing, depth and width, insulation thickness; batten/counter batten length, width and depth; fastener diameter, length and spacing. Materials and related properties - slate/tile weight; rafter and battens/.counter battens: timber specification; fasteners: pull-out and pullthrough strengths, shear strength and deformation under load characteristics. Consideration should also be given to the deflection and possible overloading of the fasteners under load down the slope of the roof. It is recommended that the deflection should not exceed 3mm. A fastener must be capable of withstanding the dead and imposed loads vectored down the slope of the roof i.e its maximum allowable bending stress must not be exceeded - refer to the fastener and insulation manufacturers for advice. It may be necessary to provide stronger and larger diameter fasteners (with a corresponding increase in batten and rafter dimensions) or a reduced spacing and/or stop battens (i.e parallel to the eaves/ridge) Note : The trend towards increased thickness of insulation with reduced U values (June 2000 proposals to change Approved Document L).

25 Securement cont! BS 6399 : Part 1 : 1996 Deadloads! BS 6399 : Part 2 : 1995 Wind uplift! BS 6399 : Part 3 : 1988 Imposed Loads! BS 5268 : Part 2 : 1996! BS 5534 : Part 1 : 1997! BS 1202 : Part 1 : 1994 use above to determine fastener size and density ( per m 2 ) Note: Designers must take into account the two loading conditions for the fasteners: Wind uplift on the roof. Resistance to slip (deflection of the fastener) down the slope - dependant on the pitch of the roof and the dead and imposed loading. Insulation should not be considered to be a structural material. Refer to manufacturer s literature for the specialist fasteners.

26 Fasteners - method of securement Counter battens nailed to rafters through insulation Tile battens nailed to counter battens Tiles Rafter thickness Figure above shows a method of securement for insulation laid over and between the rafters, in this case Roofmate PR. Counterbattens 32 mm thick secured with galvanised slab nails 100mm long x 3.35 mm dia spaced at 200 and 150 mm centres for duo and mono pitched roofs respectively - refer to BS 5268 : Part 2 : Tiling battens are secured with galvanised slab nails at the required gauge - refer to BS 5534 : Part 1: 1997.

27 BUILDING REGULATIONS Building Regulations 1991, amended Requirement LI : Conservation of Fuel and Power Reasonable provision shall be made for the conservation of fuel and power in buildings by limiting the heat loss through the fabric of the building

28 BUILDING REGULATIONS Approved Document L Maximum U-values (W/m2K) DWELLINGS Approved Document L : 1995 U- values OTHER BUILDINGS SAP </= 60 >60 Cold roof Warm roof Cold roof 0.25 Warm roof - residential others 0.45 If roof slope is greater than 70 o then max U = 0.45 W/m 2 K For building classification see Approved Document B Building Regulations specify maximum allowable U-values - the optimum cost effective U-values are in fact lower eg: W/m 2 K Floors 0.35 Roofs Walls

29 BUILDING REGULATIONS CONDENSATION Approved Document F:1995 Adequate provision shall be made to prevent excessive condensation in a roof but. Is based on traditional underlay experience therefore.. refer to: BRE Thermal insulation : avoiding risks see Section Sarking insulation BS see Clauses 9.1, 9.2 and 9.3

30 CONDENSATION - it s prevention Short, long term concerns Insulation Underlay - continuity, convection tight, performance - choice, performance Roof covering (tiles/slates) - air permeability (?) Ventilation YES - between underlay/roof covering YES - between insulation/traditional underlay NO - between insulation/breather underlay Control of condensation is of particular concern for those roof systems where a breather underlay is used without a ventilated airspace between it and the insulation. It is recommended that a condensation risk analysis is undertaken - refer to to BS Use of the criteria for condensation build-up within the roof system as detailed in BS 6229 : 1982 (Section A ) is recommended. The roof system below a breather underlay should be designed and installed so as to be convection tight as is possible throughout its design life. Consideration should be given to installing a VCL on the warm side of insulation if the insulation has a low water vapour resistance - refer to the insulation manufacturer for advice. cont ->

31 For buildings with high internal temperatures and humidities it is recommended that a VCL be installed and for exceptional conditions, as may be experienced in say swimming pools, laundries, that the advice of a design specialist be sought. Ventilation - defined as the controlled movement of air There are two air spaces to be considered: Between the underlay and the insulation For traditional underlays ventilation should be provided in accordance with the recommendations given in BS 5250 and Approved Document F2 (1990). For breather underlays ventilation is not normally required. Between the roof covering and underlay Where a traditional underlay is used it is not normally necessary to provide ventilation. Where a breather underlay is used without ventilation between the underlay and insulation it will be necessary to ensure that there is adequate ventilation. This may be provided through the slate/tile assembly. Apertures for ventilation can be provided at the eaves, ridge or incorporated into the slate/tile assembly - refer to BS 5250 for ventilation aperture sizes. NOTE: Ventilation through the slate/tile joints may not be sufficient due to the close fitting of the slates/tiles. There may also be a risk that the joints become blocked by vegetation or dust over the lifespan of the roof. Additional ventilation inlets or outlets may, therefore, be required. Particular attention should be given to long span roofs to ensure that adequate ventilation is provided.

32 BUILDING REGULATIONS FIRE APPROVED DOCUMENT B : 1992 EXTERNAL FIRE SPREAD - B4 BS 476 : Part 3 : 1958 AA (best) rating - tile/slate roofs - unaffected by insulation INTERNAL FIRE SPREAD - B2 BS476 : Part 7 : 1971 Class O rating - 13mm plasterboard BS476 : Part 7 External fire exposure roof tests BS476 : Part 1 Surface spread of flame test - lists Classes 1 (highest) to 4; XPS is unclassifiable Class O is not identified in BS476. However, it can be achieved by materials of limited combustibility e.g plasterboard or a Class 1 material which has a fire propagation index (I) < 12 and a sub-index (I,) < 6. For useful information on aspects of XPS in building applications see BS 6203 : 1989

33 INSULATED PITCHED ROOFING In summary: Warm roof concept 15 + years proven track record minimal condensation problems secure Design for the total system Pay attention to the design of details* Take care in installation The issues: Insulation - location, selection, installation Underlay - selection, performance, installation Condensation - its prevention Securement * see end of tutorial for typical details

34 Case study - Hospital Extension m 2 insulated pitched roof Architects: Watkins, Gray International Main contractor: J Longley & Co. Insulation installer: NH Etheridge Ltd Roofer: Cobsen, Davies Location: Conquest Hospital, Hastings, East Sussex Project: BUPA extension - completed 1998

35 Case study - Hospital! Insulation: Roofmate* PR Type 50 (90mm)! Roof space for services - heating, ventilation

36 Case study - Hospital! Underlayer: Tyvek 2001-B Pro! Securement:! Tiles: (over counterbattens) Helifix Inscrew 600 fasteners - 110mm long Marley Modern

37 Case study - Hospital U-value calculations Tiles Vented airspace Tyvek 2001-B Pro Unvented airspace Roofmate PR Plasterboard U-value = 0.25 W/m 2 K Thickness Thermal Resistance (mm) (m2k/w) Outside surface resistance Concrete tiles Vented airspace (between tiles and sarking) Tyvek 2001-BPro - - Unvented airspace Roofmate PR Unvented airspace Plasterboard Inside surface resistance

38 Case study - Hospital Condensation risk analysis U-value: 0.25 W/m 2 K Condensation build up winter 0 g/m 2 summer 0 g/m 2 annual 0 g/m 2 Red : Actual temperature profile Blue : dew point temperature Temperature ºC Condensation occurs where red and blue lines touch or cross Notes: Element: Pitched roof, ceiling at rafter line, warm pitched roof Exposure: exposed Internal surface emissivity: high External surface emissivity: high Building use: hospital Environmental conditions Summer Winter Internal temp ºC External temp ºC 18 5 Internal humidity % External humidity % Construction Thickness (mm) Vapour Resistance (MNs/g) Outside surface resistance - - Concrete tiles Vented airspace - - (between tiles and sarking) Tyvek 2001-BPro Unvented airspace - - Roofmate PR Roofmate PR Umvented airspace - - Plasterboard Inside surface resistance - -

39 Warm pitched roof construction - detailing

40 Warm pitched roof construction Type A - insulation over and between rafters - Roofmate PR Counter battens Tiling battens Tiles Vapour permeable membrane Roofmate PR Insulation Rafter

41 A1- Eaves detail Ensure continuity of insulation Set rebated edges of insulation over rafters

42 A2 - Hip detail Cut insulation to line of hip and set over support battens Hip rafter

43 A3 - Roof window detail Roof window Cut insulation to fit tight against roof window trimmers and seal with gap filler Counter batten

44 A4 - Valley detail Discontinuous edge batten to allow drainage and ventilation Gutter lining on separating layer Cut insulation boards to line of valley. Form rebate to set over valley boards Set valley boards between rafters

45 A5 - Ridge detail Nail tiles to battens Nail tiling battens to counterbattens Nail counter battens to rafters Cut insulation to fit tight at ridge and seal with gap filler

46 A6 - Abutment detail Fix batten in gap between insulation and wall Insulation over and between rafters Underlay

47 A7 - Verge detail Insulation set over and between rafters Flying rafter Bargeboard

48 Warm pitched roof construction Type B - insulation over rafters Roofmate RL Counterbattens Tiling battens Tiles Vapour permeable membrane Roofmate RL Insulation Rafter

49 B1 - Eaves detail Ensure continuity of insulation

50 B2 - Hip detail Cut insulation to line of hip and set onto support battens Support battens Hip rafter

51 B3 - Roof window detail Roof window Cut insulation to fit tight against roof window trimmers and seal with gap filler Counter batten

52 B4 - Valley detail Cut insulation boards to line of valley and set over valley boards Discontinuous edge batten to allow drainage and ventilation Gutter lining on separating layer Valley rafter Set valley boards between rafters

53 B5 - Ridge detail Nail counterbattens to rafters Nail tiles to battens Nail tiling battens to counterbattens Cut insulation to fit tight at ridge and seal with gap filler

54 B6 - Abutment detail Nail counter battens to rafters Nail battens to counter battens Plasterboard ceiling Lay insulation boards over rafters

55 B7 - Verge detail Plasterboard ceiling Bargeboard Make up piece of insulation set over gable wall

56 INSULATED PITCHED ROOFING Summarising : Issues : Warm Roof: 15 years proven experience! minimal condensation, securement problems Design for total system Attention to detail design Care in installation Insulation selection, performance, installation Underlay selection, performance, installation Condensation: it s prevention Securement

57 If the following questionnaire is successfully completed and sent to Dow Construction Products, 2 Heathrow Boulevard, 284 Bath Road, West Drayton, Middx UB7 0DQ Fax Number a CPD certificate will be forwarded to you. 1. In the warm roof concept the insulation is placed above the rafters between the rafters above and between the rafters between the rafters 2. If a pitched roof is insulated at rafter level (and the loft space is to be utilised) What are the maximum allowable U-values Domestic Buildings (SAP>60) Non-Domestic - Old Peoples Home - Office 3. What is the difference between a traditional and breather underlay Water tight Air tight Tear Strength (nails) Tensile properties Water Vapour permeable 4. Where would you provide ventilation in a pitched roof construction insulated at rafter level if a) a traditional or b) a breather underlay is used? (a) (b) Below rafters Below insulation Between insulation and underlay Between underlay and tiles/slates

58 5. Which properties are of particular importance for breather underlays? Water resistance Water vapour resistance Compatibility with timber preservatives Tear strength Tearing resistance Slipperiness Blinding resistance Colour Air tightness 6. In designing a pitched roof which standards should you refer to for General design - slating/tiling Wind loads Design - timber structure Dead loads Imposed loads 1 = BS 6399 : Part 1 2 = BS 6399 : Part 2 3 = BS 6399 : Part 3 4 = BS 5534 : Part 1 5 = BS 5268 : Part 2

59 7. Where would you go for advice on how to avoid condensation in a pitched roof? BS 5250 Approved Document L Approved Document F BRE 262 Thermal Insulation : avoiding risks BS 5534 Insulation manufacturers 8. In a warm roof construction what issues did you need to consider to avoid/reduce the risk of condensation.? Use of a vapour control layer Water vapour permeability of insulation Convection tightness of insulation layer Type of underlay Location of underlay Where to ventilate Air permeability of primary roof covering Drying our of building structure Attention to details e.g. at eaves Securement of underlay 9. What factors must be considered when selecting and specifying fasteners? Length Diameter Pull-out strength (from timber) Bending stress Ease and accuracy of installation Deflection under load Width of battens, rafters

60 10. Which of these should be considered when selection of insulation for installation or rafter level? Location Compressive strength Rigidity Water vapour permeability Water resistance Thermal conductivity Ease of installation Fire resistance Nail ability Name Company Name Address Telephone Number

Including. Rubershield-Pro. Breather Membrane

Including. Rubershield-Pro. Breather Membrane Including RubershieldPro Breather Membrane 2 Ruberoid produces a wide range of underslating membranes, primarily to be installed below tiles, slates or metal roofing providing a secondary barrier against

More information

Multi-layer Insulation Blanket for Roofs

Multi-layer Insulation Blanket for Roofs Multilayer Insulation Blanket for Roofs Thermal Insulation in a 40mm thin, flexible, multilayer membrane Meets requirements of L1A, L1B 2010 In accordance with BR443 NHBC Acceptance Pitched & Flat roof

More information

Roofers Guide to Underslating Membranes

Roofers Guide to Underslating Membranes Roofers Guide to Underslating Membranes IKO is a worldwide enterprise, with more than 3000 employees, and manufacturing plants in Canada, the United States, United Kingdom, Belgium, Holland, France and

More information

ROOFERS CHOICE BREATHER MEMBRANES FOR USE IN COLD NON-VENTILATED ROOFS

ROOFERS CHOICE BREATHER MEMBRANES FOR USE IN COLD NON-VENTILATED ROOFS Mercury Building Products Ltd 114 Eckington Road Coal Aston Dronfield Sheffield S18 3AY Tel: 01246 292816 Fax: 01246 292867 e-mail: sales@vaprfree.co.uk danny@vaprfree.co.uk website: www.mercurybuildingproducts.com

More information

BUILDING CONTROL GUIDANCE SHEET USE OF BREATHABLE ROOFING FELTS.

BUILDING CONTROL GUIDANCE SHEET USE OF BREATHABLE ROOFING FELTS. Building Control Charnwood Borough Council Southfield Road Loughborough LE11 2TN BUILDING CONTROL GUIDANCE SHEET USE OF BREATHABLE ROOFING FELTS. Last updated 16/11/2010 Page 1 of 6 PURPOSE: This Guidance

More information

Contents. APA Construction Details. Full fill cavity walls 2-13. Partial fill cavity walls 14-25. Solid externally insulated walls 26-37

Contents. APA Construction Details. Full fill cavity walls 2-13. Partial fill cavity walls 14-25. Solid externally insulated walls 26-37 Contents Pages Full fill cavity walls 2-13 Partial fill cavity walls 14-25 Solid externally insulated walls 26-37 Appendix (BRE confirmation of Ψ and y-values) 38-40 Page 1 of 40 APA Construction Details

More information

This seminar covers the principles, design and installation of ground bearing and suspended insulated floors. You will discover

This seminar covers the principles, design and installation of ground bearing and suspended insulated floors. You will discover Dow Construction Products Thermal Insulation of Floors This seminar covers the principles, design and installation of ground bearing and suspended insulated floors. You will discover Why a floor should

More information

CERTIFICATE NAME OF PRODUCT MANUFACTURER PRODUCT DESCRIPTION CERTIFICATION PROCEDURE. No VTT C-6044-10 Date of issue 11.10.2010, Updated July 1, 2011

CERTIFICATE NAME OF PRODUCT MANUFACTURER PRODUCT DESCRIPTION CERTIFICATION PROCEDURE. No VTT C-6044-10 Date of issue 11.10.2010, Updated July 1, 2011 CERTIFICATE NAME OF PRODUCT No VTT C-6044-10 Date of issue 11.10.2010, Updated July 1, 2011 H-CONTROL REFLEX+ reflective insulating vapour control layer for roof and wall applications MANUFACTURER ACTIS

More information

CHESTERFLEX ROOF WATERPROOFING MEMBRANES

CHESTERFLEX ROOF WATERPROOFING MEMBRANES CI/SfB (47) Ln2 Chesterfelt Ltd CHESTERFLEX ROOF WATERPROOFING MEMBRANES Certificate No 94/3062 DETAIL SHEET 2 Product THIS DETAIL SHEET RELATES TO CHESTERFLEX ROOF WATERPROOFING MEMBRANES, POLYESTER REINFORCED

More information

Asphalt Shingle Application Requirements

Asphalt Shingle Application Requirements Alberta Allied Roofing Association Asphalt Shingle Application Requirements Section 1 Roof Decks 1.1 General Asphalt Shingles are not permitted to be installed directly over rigid insulation. When Asphalt

More information

MONARPERM 600, MONARPERM PLUS AND MONARPERM TOP (COLD VENTILATED AND WARM NON-VENTILATED)

MONARPERM 600, MONARPERM PLUS AND MONARPERM TOP (COLD VENTILATED AND WARM NON-VENTILATED) Icopal Limited Barton Dock Road Stretford Manchester M32 0YL Tel: 0161 865 4444 Fax: 0161 866 9859 e-mail: info.uk@icopal.com website: www.icopal.com APPROVAL INSPECTION TESTING CERTIFICATION TECHNICAL

More information

Section 5.0. Basements. Wall insulated externally. Wall insulated internally. Ba02. Product: Polyfoam ECO Floorboard Ba01.

Section 5.0. Basements. Wall insulated externally. Wall insulated internally. Ba02. Product: Polyfoam ECO Floorboard Ba01. Section 5.0 Basements Wall insulated externally Product: Polyfoam ECO Ba01 Wall insulated internally Product: Polyfoam ECO Ba02 Basements Basements Basement design Waterproofing BS 8102: 2009 Code of practice

More information

Cupa Natural Slate Roofing design and fixing guide

Cupa Natural Slate Roofing design and fixing guide Cupa Natural Slate Roofing design and fixing guide Cupa Natural Slate synonymous with quality Currently the Spanish slate industry is the undisputed market leader in natural slate production, with 90%

More information

SANS 1 0 1 7 7-9. www.spunchem.com FIRE PERFORMANCE SANS 428 ENERGY SAVER REFLECTIVE TIASA A MEMBER OF 2009/366 2009/367 2009/369 2008/341

SANS 1 0 1 7 7-9. www.spunchem.com FIRE PERFORMANCE SANS 428 ENERGY SAVER REFLECTIVE TIASA A MEMBER OF 2009/366 2009/367 2009/369 2008/341 REFLECTIVE ENERGY SAVER FIRE PERFORMANCE SANS 428 SANS 1 0 1 7 7-9 SANS 10177-10 SANS 10177-11 www.spunchem.com A MEMBER OF TIASA Thermal Insulation Association of Southern Africa 2009/66 2009/67 2009/69

More information

!!!!!! !!! Decra Plus DPSW010 DPSTW011 DPSW012 DPSW013 DPSW014 DPSW015 DPSW016 DPSW020 DPSW021 DPSW024 DPSW030 DPSW031 DPSW035 DPSW030 DPSW031 DPSW035

!!!!!! !!! Decra Plus DPSW010 DPSTW011 DPSW012 DPSW013 DPSW014 DPSW015 DPSW016 DPSW020 DPSW021 DPSW024 DPSW030 DPSW031 DPSW035 DPSW030 DPSW031 DPSW035 Decra Plus Drawing no DPSW010 DPSTW011 DPSW012 DPSW013 DPSW014 DPSW015 Description Shown In Decra Brochure Most Commonly Used Detail t~êã=oççñ=b~îéë=aéí~áä=b~îéë=lîéêü~åö=táíü=fåëìä~íéç=c~ëåá~=~åç=pçññáí

More information

RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000

RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000 RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000 SECTION R905 REQUIREMENTS FOR ROOF COVERINGS R905.1 Roof covering application. Roof coverings

More information

Fire 2This Technical Bulletin has been commissioned by the UK SIP Association in

Fire 2This Technical Bulletin has been commissioned by the UK SIP Association in REV 1-12.12.11/TB002 Technical Bulletin Fire 2This Technical Bulletin has been commissioned by the UK SIP Association in conjunction with TRADA Technology and is intended to provide the reader with introductory

More information

Bituminous Sheet Flat Roofs: Their repair and maintenance

Bituminous Sheet Flat Roofs: Their repair and maintenance Bituminous Sheet Flat Roofs: Their repair and maintenance Flat roof covered in sheets of bituminous felt Introduction Whilst flat roofs are often regarded as inferior to their pitched counterparts and

More information

AND MEMBRANES ROOFING UNDERLAYS. www.fakro.com

AND MEMBRANES ROOFING UNDERLAYS. www.fakro.com AND MEMBRANES 010 ROOFING UNDERLAYS 1 HO DOES YOUR ROOF BREATHe? MEMBRANES THE WAY to A WARM AND DRY ROOF HO HO HO HO HO HO WATERTIGHTNESS The FAKRO Company offers a wide range of membranes and underlays

More information

Section 2.4. Built-up Metal Roofs. Rail and bracket system. Standing seam system. Bu02. Product: Earthwool FactoryClad range Bu01

Section 2.4. Built-up Metal Roofs. Rail and bracket system. Standing seam system. Bu02. Product: Earthwool FactoryClad range Bu01 Section Built-up Metal Roofs Rail and bracket system Product: Earthwool FactoryClad range Bu01 Standing seam system Product: Earthwool FactoryClad range and Earthwool Universal Slab Bu02 Built-up Metal

More information

Section 2.3. Flat Roofs. Warm deck single ply membrane. Warm deck single ply membrane. Warm deck built-up felt/ mastic asphalt. Protected membrane

Section 2.3. Flat Roofs. Warm deck single ply membrane. Warm deck single ply membrane. Warm deck built-up felt/ mastic asphalt. Protected membrane Section Flat Roofs Warm deck single ply membrane Product: Rocksilk Krimpact Flat Roof Slab Fl01 Warm deck single ply membrane Product: Polyfoam ECO Roofboard Fl02 Warm deck built-up felt/ mastic asphalt

More information

CITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN 55110 Fax: 651-429-8503. Re-Roofing: Asphalt Shingles

CITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN 55110 Fax: 651-429-8503. Re-Roofing: Asphalt Shingles CITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN 55110 Fax: 651-429-8503 Re-Roofing: Asphalt Shingles This is a summary of the standard requirements based on the

More information

Section 3.1.2. Timber Frame Walls. Single layer between studs. Single layer between studs with service void. Between studs with insulated lining

Section 3.1.2. Timber Frame Walls. Single layer between studs. Single layer between studs with service void. Between studs with insulated lining Section Timber Frame Walls Single layer between studs Product: Earthwool FrameTherm Rolls and Slabs Tf01 Single layer between studs with service void Product: Earthwool FrameTherm Rolls and Slabs Tf02

More information

GUIDANCE SHEET FOR CONSERVATORIES, SUNROOMS AND EXTENSIONS TO DWELLINGS.

GUIDANCE SHEET FOR CONSERVATORIES, SUNROOMS AND EXTENSIONS TO DWELLINGS. GUIDANCE SHEET FOR CONSERVATORIES, SUNROOMS AND EXTENSIONS TO DWELLINGS. This leaflet provides guidance on how to attain compliance with The Building (Amendment) Regulations (Northern Ireland) 2006, Part

More information

PROVIDING PROTECTION IN CONSTRUCTION Technical guide: roofs. www.tyvek.co.uk www.construction.tyvek.com

PROVIDING PROTECTION IN CONSTRUCTION Technical guide: roofs. www.tyvek.co.uk www.construction.tyvek.com PROVIDING PROTECTION IN CONSTRUCTION Technical guide: roofs www.tyvek.co.uk www.construction.tyvek.com DuPont TM membranes Providing protection Contents Page Introduction............................................................................................................................

More information

Built-up roofing solutions with rigid insulation boards on concrete decks for new-build and refurbishment E-a5

Built-up roofing solutions with rigid insulation boards on concrete decks for new-build and refurbishment E-a5 Cl Sfb (27-9) Rn7 M2 December 2004 Built-up roofing solutions with rigid insulation boards on concrete decks for new-build and refurbishment E-a5 Fesco, Fesco S, Retrofit, Retrofit S, Fesco Fillet, PF,

More information

Part 3 Ancillary technologies. Chapter 3.2. Mechanical ventilation with heat recovery

Part 3 Ancillary technologies. Chapter 3.2. Mechanical ventilation with heat recovery Part 3 Ancillary technologies Chapter CONTENTS SCOPE Clause Page DESIGN Design standards D1 1 Statutory requirements D2 1 System design D3 1 Building integration D4 2 Noise D5 2 Access and controls D6

More information

I n s u l a t i o n. Low Energy Low Carbon Buildings

I n s u l a t i o n. Low Energy Low Carbon Buildings I n s u l a t i o n CI/Sfb (47) Ln6 Sixth Issue March 2011 BREATHABLE MEMBRANE FOR UNVENTILATED PITCHED ROOFS AND TIMBER FRAME WALLS Waterproof can be used as a temporary roof covering Non tenting Airtight

More information

Building Construction. Lightweight construction. Conventional Construction

Building Construction. Lightweight construction. Conventional Construction Ventilation 53 Building Construction The firefighter s ability to safely and efficiently ventilate a building through its roof will depend to some degree on the firefighter s understanding of roof construction.

More information

TR21. I n s u l a t i o n. Low Energy Low Carbon Buildings

TR21. I n s u l a t i o n. Low Energy Low Carbon Buildings I n s u l a t i o n CI/Sfb (27.9) Rn7 M2 Fourth Issue March 2011 TR21 INSULATION FOR FLAT ROOFS WATERPROOFED WITH PARTIALLY BONDED BUILT UP FELT AND MASTIC ASPHALT High performance rigid thermoset insulation

More information

Energy Company Obligation (ECO): Technical Monitoring Questions

Energy Company Obligation (ECO): Technical Monitoring Questions Energy Company Obligation (ECO) Technical Monitoring Questions v1 30/05/2013 Energy Company Obligation (ECO): Technical Monitoring Questions Under ECO suppliers are required to instruct suitably qualified

More information

STEEL BUILDINGS IN EUROPE. Single-Storey Steel Buildings Part 8: Building Envelope

STEEL BUILDINGS IN EUROPE. Single-Storey Steel Buildings Part 8: Building Envelope STEEL BUILDINGS IN EUROPE Single-Storey Steel Buildings Part 8: Building Envelope Single-Storey Steel Buildings Part 8: Building Envelope 2 - ii Part 8: Building Envelope emissions

More information

Introduction & Principles Issued in support of Junction Details, Parts 1 to 5

Introduction & Principles Issued in support of Junction Details, Parts 1 to 5 Accredited Construction Details (Scotland) 2010 For the limitation of thermal bridging and air infiltration in low and medium rise domestic buildings Introduction & Principles Issued in support of Junction

More information

CI SfB. (4-) Nn2. Onduline. Mini Profile. Onduline Garden Roof Range. Onduline Building Products Ltd

CI SfB. (4-) Nn2. Onduline. Mini Profile. Onduline Garden Roof Range. Onduline Building Products Ltd CI SfB (4-) Nn2 Onduline Mini Profile Onduline Garden Roof Range Onduline Building Products Ltd Onduline Garden Roof Range Onduline Mini Profile The new Onduline Mini Profile sheets have been designed

More information

Building Regulations for the Conservation of Fuel and Power

Building Regulations for the Conservation of Fuel and Power Insulation CI/SfB Rn7 M2 First Issue April 2014 Building Regulations for the Conservation of Fuel and Power ENGLAND EXISTING DWELLINGS 2013 EDITION Low Energy Low Carbon Buildings Contents Page Introduction

More information

BER Assessors Dwellings Technical Bulletin

BER Assessors Dwellings Technical Bulletin BER Assessors Dwellings Technical Bulletin Issue No. 2/12 April 2012 Contents: 1. SUPPLEMENTARY ELECTRIC WATER HEATING IN SUMMER... 2 2. PITCHED ROOF U-VALUE CALCULATIONS... 8 2.1. PITCHED ROOF, INSULATED

More information

Rockwool Flexi Insulation Application Guide

Rockwool Flexi Insulation Application Guide Pitched roof Rafters InterMediate floors INTERNAL partitions external Framed walls separating floors Separating Walls Rockwool Flexi Insulation Application Guide Ground floor The perfect fit for any framed

More information

PREMIUM LAMINATED ASPHALT SHINGLES Dallas, TX Tuscaloosa, AL Phillipsburg, KS

PREMIUM LAMINATED ASPHALT SHINGLES Dallas, TX Tuscaloosa, AL Phillipsburg, KS Application Instructions for THESE ARE THE MANUFACTURER S APPLICATION INSTRUCTIONS FOR THE ROOFING CONDITIONS DESCRIBED. TAMKO BUILDING PRODUCTS, INC. ASSUMES NO RESPONSIBILITY FOR LEAKS OR OTHER ROOFING

More information

Cl/SfB (13.9) a comprehensive. technical guide. to the specification of. vapour control layers. www.proctorgroup.com GROUP LTD

Cl/SfB (13.9) a comprehensive. technical guide. to the specification of. vapour control layers. www.proctorgroup.com GROUP LTD Cl/SfB (13.9) Ln6 a comprehensive technical guide to the specification of vapour control layers..the knowledge to produce solutions GROUP LTD www.proctorgroup.com Partnerships in action THE PROBLEM GROUP

More information

Rochdale Building Control Guide. Approved Document C. Site preparation and resistance to contaminants and moisture

Rochdale Building Control Guide. Approved Document C. Site preparation and resistance to contaminants and moisture Rochdale Building Control Guide Approved Document C Site preparation and resistance to contaminants and moisture Dampness is often misdiagnosed within buildings, the approved document deals with prevention

More information

Good Craftsmanship Guide. Carpentry and Joinery- Carcassing

Good Craftsmanship Guide. Carpentry and Joinery- Carcassing Good Craftsmanship Guide Carpentry and Joinery- Carcassing Introduction This Good Craftsmanship Guide highlights key problems with the major elements of Carpentry and Joinery - Carcassing, and gives guidance

More information

Signs of insulation problems In the winter. In the summer. conditioning system

Signs of insulation problems In the winter. In the summer. conditioning system about your house CE 19 While previous generations may have been content to live in drafty houses, most people now want comfortable warm houses. A healthy house today is well sealed, well insulated and

More information

FLAT ROOF INSULATION INSULATION ROOFING FLAT. Quick Guide. Quick Guide. Insulation. EcoTherm Insulation UK Sales Team. Insulation

FLAT ROOF INSULATION INSULATION ROOFING FLAT. Quick Guide. Quick Guide. Insulation. EcoTherm Insulation UK Sales Team. Insulation Insulation Insulation Scotland & North England 07824 412579 North West & North Wales 07931 342948 South Wales & West Midlands 07940 546247 Yorkshire & East Midlands 07825 570100 FLAT ROOF INSULATION EcoTherm

More information

Innovation - High performance roof, wall and floor insulation board. delivering better performance

Innovation - High performance roof, wall and floor insulation board. delivering better performance 2010 VERSION 1 IRL High performance roof, wall and floor insulation board Innovation - delivering better performance PRODUCT SPECIFICATION INSTALLATION GUIDE I ve worked with Xtratherm for years, they

More information

Conservatory Roof Structural Information Guide

Conservatory Roof Structural Information Guide Conservatory Roof Structural Information Guide Effective from ugust 8 Useful Information This guide displays data on the permissible roof member spans and for different roof loadings; it should be used

More information

Rev 1-12.2013. Code of Practice. SIP Technology. www.uksips.org

Rev 1-12.2013. Code of Practice. SIP Technology. www.uksips.org Rev 1-12.2013 Code of Practice SIP Technology www.uksips.org What are Structural Insulated Panels (SIPS)? SIPS are prefabricated, high performance, lightweight, building panels that can be used in floors,

More information

Providing protection in construction

Providing protection in construction Providing protection in construction VOLUME 2: WALLS AND FLOORS Contact Information UK office address: DuPont Tyvek Hither Green Trading Estate Clevedon, North Somerset BS21 6XU Tel: 01275 879770 Fax (sales):

More information

Part 7 Roofs. Chapter 7.2. Pitched roofs. Effective from 1 January 2012

Part 7 Roofs. Chapter 7.2. Pitched roofs. Effective from 1 January 2012 Part 7 Roofs Chapter Effective from 1 January 2012 CONTENTS SCOPE DESIGN Clause Page Design standards D1 1 Statutory requirements D2 1 Loadbearing structure D3-D4 1 Trussed rafter roofs D5 1 Traditional

More information

Multi-Foil reflective insulation SPACE SAVING U-VALUE AS LOW AS 0.16W/m 2 K LIGHTWEIGHT EASY TO FIX

Multi-Foil reflective insulation SPACE SAVING U-VALUE AS LOW AS 0.16W/m 2 K LIGHTWEIGHT EASY TO FIX Multi-Foil reflective insulation SPACE SAVING U-VALUE AS LOW AS 0.16W/m 2 K LIGHTWEIGHT EASY TO FIX TECHNICAL CHARACTERISTICS Multi-Foil Reflective Insulation Xfoil Range of insulation is designed to achieve

More information

FIRE PERFORMANCE OF STRUCTURAL INSULATED PANEL SYSTEMS

FIRE PERFORMANCE OF STRUCTURAL INSULATED PANEL SYSTEMS INFORMATION PAPER IP 21/10 FIRE PERFORMANCE OF STRUCTURAL INSULATED PANEL SYSTEMS Tom Lennon and Danny Hopkin The use of Structural Insulated Panel (SIP) systems in construction in the UK has increased

More information

Roofing Systems. There are many different systems, each with it's own special requirements and benefits. Browse through all the options below.

Roofing Systems. There are many different systems, each with it's own special requirements and benefits. Browse through all the options below. Roofing Systems There are many different systems, each with it's own special requirements and benefits. Browse through all the options below. BUR (Built-Up Roofing) Built-Up-Roofing, BUR is a roof that

More information

Guide to the safe installation of downlighters in dwellings

Guide to the safe installation of downlighters in dwellings Guide to the safe installation of downlighters in dwellings Technical guidance for designers and installers 01 Guide to the safe installation of downlighters in dwellings Technical guidance for designers

More information

Abstract. 2. Cold Pitched Roofs

Abstract. 2. Cold Pitched Roofs Heat and moisture transport between houses and cold lofts - a combination of convection and diffusion Emannuel Essah and Chris Sanders Glasgow Caledonian University Abstract About 80% of domestic pitched

More information

The Pleasance, Edinburgh

The Pleasance, Edinburgh Refurbishment Case Study 5 DRAFT The Pleasance, Edinburgh Insulation of coom ceiling, attic space & lightwell 2 nd edition The views expressed in commissioned case studies are those of the authors and

More information

Low Energy Low Carbon Buildings

Low Energy Low Carbon Buildings I n s u l a t i o n CI/Sfb (27.9) Rn7 M2 Eighth Issue March 2011 TR27 LPC/FM INSULATION FOR FLAT ROOFS WATERPROOFED WITH FULLY ADHERED SINGLE PLY, PARTIALLY BONDED BUILT UP FELT, MASTIC ASPHALT AND COLD

More information

Construction. SikaProof A-08 Edge, A-12 Edge. Fully bonded FPO sheet membrane in L-shape for the SikaProof A waterproofing system. Product Description

Construction. SikaProof A-08 Edge, A-12 Edge. Fully bonded FPO sheet membrane in L-shape for the SikaProof A waterproofing system. Product Description Product Data Sheet Edition 15/10/2014 Identification no: 02 07 04 10 300 0 000002 SikaProof A Edge SikaProof A-08 Edge, A-12 Edge Fully bonded FPO sheet membrane in L-shape for the SikaProof A waterproofing

More information

PROFILED METAL ROOFING DESIGN GUIDE

PROFILED METAL ROOFING DESIGN GUIDE MCRMA Technical Paper No. 6 CI/SfB (23) Nh2 JUNE 2004 PROFILED METAL ROOFING DESIGN GUIDE THE METAL CLADDING & ROOFING MANUFACTURERS ASSOCIATION LIMITED Contents Page 1.0 Typical construction and assemblies

More information

Sika Membran System For Sealing and Waterproofing Construction Gaps in Building Façades

Sika Membran System For Sealing and Waterproofing Construction Gaps in Building Façades Construction Sika For Sealing and Waterproofing Construction Gaps in Building Façades Waterproof and Airtight Flexible Seal Controlled Vapour Diffusion Bonds to any Building Substrate Prevents Interstitial

More information

Interior Walls below and above ground OLDROYD THE ULTIMATE WATERPROOF MEMBRANE SYSTEM

Interior Walls below and above ground OLDROYD THE ULTIMATE WATERPROOF MEMBRANE SYSTEM P r o d u c t a p p l i c a t i o n s a n d t e c h n i c a l i n f o r m a t i o n 2 below and above ground V OLDROYD THE ULTIMATE WATERPROOF MEMBRANE SYSTEM V The flexible, fast and cost-effective answer

More information

2014 British Columbia Building Code Changes

2014 British Columbia Building Code Changes District of Houston 250-845-2238 2014 British Columbia Building Code Changes A District of Houston interpretation of the 2014 Building Code Changes for 9.36 & 9.32 The following changes reflect the most

More information

Western Red Cedar Shingles Product Guide

Western Red Cedar Shingles Product Guide Western Red Cedar Shingles Product Guide Western Red Cedar Shingles & Shakes from John Brash are a truly renewable and sustainable roofing and cladding material; with one of the lowest carbon footprints

More information

STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM

STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM Installed in Pre-engineered Steel Buildings Provides Lowest Cost Construction Method for CORROSIVE AND WET Environments PREFERRED SOLUTIONS, INC.

More information

The Pocket Guide To Insulation August 2013

The Pocket Guide To Insulation August 2013 The Pocket Guide To Insulation August 2013 Introduction Knauf Insulation is the UK s leading manufacturer of insulation products, including: Earthwool glass and rock mineral wool Polyfoam ECO extruded

More information

Section 4.3. Separating Floors. Timber frame floor with I-Beams. Upgrading existing timber floor with new ceiling. Timber frame floor with

Section 4.3. Separating Floors. Timber frame floor with I-Beams. Upgrading existing timber floor with new ceiling. Timber frame floor with Section Separating Floors Timber frame floor with I-Beams Product: Earthwool Acoustic Roll and Floorfoam Easy Edge Strip Timber frame floor with solid timber joists Product: Earthwool Acoustic Roll and

More information

Building Control Guidance Note

Building Control Guidance Note Elements Renovation / Replacement. Issued 25/01/13 Rev a Page 1 of 9 (Applies to both Domestic and Non-Domestic Premises) Works relating to thermal elements can arise in building an extension, a material

More information

0845 0098 980 www.nicholsonsts.com

0845 0098 980 www.nicholsonsts.com 0845 0098 980 www.nicholsonsts.com ROOFTRAK The IFP is revolutionising the way we fix things to roofs. Technical Director of a leading UK roofing system manufacturer The ROOFTRAK-IFP A revolutionary solution

More information

TP10. Insulation RAFTER LEVEL INSULATION FOR TILED OR SLATED PITCHED WARM ROOF SPACES BBA BRITISH

TP10. Insulation RAFTER LEVEL INSULATION FOR TILED OR SLATED PITCHED WARM ROOF SPACES BBA BRITISH Insulation CI/Sfb (27.9) Rn7 M2 Fifth Issue May 2007 TP10 RAFTER LEVEL INSULATION FOR TILED OR SLATED PITCHED WARM ROOF SPACES High performance rigid urethane insulation thermal conductivity 0.023 W/m.K

More information

Renovating Your Basement

Renovating Your Basement building science.com 2006 Building Science Press All rights of reproduction in any form reserved. Renovating Your Building America Report - 0309 2003 (revised 2007) Building Science Corporation Abstract:

More information

Timber Frame Walls Rethinking Construction

Timber Frame Walls Rethinking Construction Insulation Fifth Issue November 2007 Timber Frame Walls Rethinking Construction INSULATION BEST PRACTICE FOR THE 21ST CENTURY Summary 9 mm OSB sheathing 3 mm skim coated 15 mm plasterboard Rock or glass

More information

Cavity Drain R20 is manufactured from1.0mm thick black high density polyethylene with studs approximately 20mm high.

Cavity Drain R20 is manufactured from1.0mm thick black high density polyethylene with studs approximately 20mm high. CI/SfB Tn6 L6813 September 2013 RIW CAVITY DRAIN R20 R20 is manufactured from1.0mm thick black high density polyethylene with studs approximately 20mm high. Other systems are available for specific uses,

More information

WATERPROOFING OF REINFORCED CONCRETE FLAT ROOF 12

WATERPROOFING OF REINFORCED CONCRETE FLAT ROOF 12 WATERPROOFING OF REINFORCED CONCRETE FLAT ROOF 12 87 88 GOOD INDUSTRY PRACTICES 12 WATERPROOFING OF REINFORCED CONCRETE FLAT ROOF 12.1 BACKGROUND Most roofs in Singapore are constructed using reinforced

More information

September 3, 2009. Ric Boyd, Public Works Director Ketchikan Gateway Borough 344 Front St. Ketchikan, AK 99901

September 3, 2009. Ric Boyd, Public Works Director Ketchikan Gateway Borough 344 Front St. Ketchikan, AK 99901 September 3, 2009 Ric Boyd, Public Works Director Ketchikan Gateway Borough 344 Front St. Ketchikan, AK 99901 RE: Ketchikan Gateway Borough Gateway Recreation Center Roof Observations and Intrusive Inspections

More information

Repairing storm damaged roofs

Repairing storm damaged roofs Repairing storm damaged roofs Tie-down designs for tile and sheet roofs Conforms to wind classifications of up to category N3 (previously W41N) designed to withstand a maximum gust wind speeds of 50 metres

More information

System 5000 FLAME-FREE, FELT SYSTEM, INSTALLED USING HOT AIR, TOTALLY ELIMINATING FIRE RISK AND PROVIDING A BITUMEN ALTERNATIVE TO SINGLE PLY

System 5000 FLAME-FREE, FELT SYSTEM, INSTALLED USING HOT AIR, TOTALLY ELIMINATING FIRE RISK AND PROVIDING A BITUMEN ALTERNATIVE TO SINGLE PLY CI/SfB Oct 12 (47) Ln Uniclass L524 FLAME-FREE, FELT SYSTEM, INSTALLED USING HOT AIR, TOTALLY ELIMINATING FIRE RISK AND PROVIDING A BITUMEN ALTERNATIVE TO SINGLE PLY Bailey Flame-free felt roofing Bailey

More information

Preventing Ice Dams on Roofs

Preventing Ice Dams on Roofs Preventing Ice Dams on Roofs Facility Manager November/December 2005 When a roof leaks, facility managers inevitably receive complaints from building occupants. If it is winter, ice dams are often the

More information

How To Test A Wrap N Drain X Dampproofing System

How To Test A Wrap N Drain X Dampproofing System National Research Council Canada Institute for Research in Construction Conseil national de recherches Canada Institut de recherche en construction CCMC 13094-R &&0& EVALUATION DIVISION 07111 REPORT Issued

More information

ICOPAL POUR AND ROLL ROOF WATERPROOFING ICOPAL POWER ELASTOMERIC ROOF WATERPROOFING SYSTEM

ICOPAL POUR AND ROLL ROOF WATERPROOFING ICOPAL POWER ELASTOMERIC ROOF WATERPROOFING SYSTEM Icopal Limited Barton Dock Road Stretford Manchester M32 0YL Tel: 0161-865 4444 Fax: 0161-864 8433 e-mail: market.uk@icopal.com website: www.icopal.co.uk APPROVAL INSPECTION TESTING CERTIFICATION TECHNICAL

More information

Residential Roofing Guide

Residential Roofing Guide Residential Roofing Guide TABLE OF CONTENTS Building Detail and Accessories...... 1 Panel Introduction and Handling...... 2 Cutting and Trimming.... 3 Roof Preparation..... 3 Roof Slope..... 3 Re-roofing...

More information

CHAPTER 7: Building Systems ROOFING SYSTEMS

CHAPTER 7: Building Systems ROOFING SYSTEMS ROOFING SYSTEMS Purpose Examples 1. Shingle roof system 2. Metal roof with blanket insulation 3. Metal roof with rigid insulation 4. Built-up asphalt roof system 5. Single-ply roof system 6. Modified Bitumen

More information

STRUCTURAL CONCEPT FOR LIGHT GAUGE STEEL FRAME SYSTEM

STRUCTURAL CONCEPT FOR LIGHT GAUGE STEEL FRAME SYSTEM Chapter 9 STRUCTURAL CONCEPT FOR LIGHT GAUGE STEEL FRAME SYSTEM 9.1 BACKGROUND Steel is widely used in the construction of multi-storey buildings. However, steel construction is seldom used and is traditionally

More information

ABSeam Panel Overview and Installation Instructions

ABSeam Panel Overview and Installation Instructions 82 Garden Spot Road Ephrata, PA 17522 717-445-6885 35 Ridge Road Newville, PA 17241 717-776-5951 ABSeam Panel Overview and Installation Instructions Applications: The ABSeam panel is an architectural panel

More information

HERITAGE WOODGATE LAMINATED ASPHALT SHINGLES Dallas, TX

HERITAGE WOODGATE LAMINATED ASPHALT SHINGLES Dallas, TX Application Instructions for THESE ARE THE MANUFACTURER S APPLICATION INSTRUCTIONS FOR THE ROOFING CONDITIONS DESCRIBED. TAMKO BUILDING PRODUCTS, INC. ASSUMES NO RESPONSIBILITY FOR LEAKS OR OTHER ROOFING

More information

Chapter 6 ROOF-CEILING SYSTEMS

Chapter 6 ROOF-CEILING SYSTEMS Chapter 6 ROOF-CEILING SYSTEMS Woodframe roof-ceiling systems are the focus of this chapter. Cold-formed steel framing for a roof-ceiling system also is permitted by the IRC but will not be discussed;

More information

Module 3.7. Thermal bridging

Module 3.7. Thermal bridging Module 3.7 Thermal bridging Learning Outcomes On successful completion of this module learners will be able to - Describe construction details which influence thermal bridging. 2 Introduction to thermal

More information

COMMERCIAL BUILDING APPLICATIONS

COMMERCIAL BUILDING APPLICATIONS EXPANDED POLYSTYRENE FOR COMMERCIAL BUILDING APPLICATIONS www.falconfoam.com Commercial Building Ap Expanded Polystyrene Insulation Falcon Foam leads the commercial building industry with products that

More information

*Trademark of The Dow Chemical Company A business unit of The Dow Chemical Company and its subsidiaries Copyright 2003 The Dow Chemical Company.

*Trademark of The Dow Chemical Company A business unit of The Dow Chemical Company and its subsidiaries Copyright 2003 The Dow Chemical Company. Dow Chemical is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned on completion of this program will be reported to CES Records for AIA members.

More information

ROOF CONSTRUCTION Roof Styles Gable Roof Hip Roof Gambrel Roof

ROOF CONSTRUCTION Roof Styles Gable Roof Hip Roof Gambrel Roof ROOF CONSTRUCTION The overall appearance of a building is greatly affected by the roof lines and the roofing materials. The designer has many standard designs to choose from and should be able to find

More information

The Kingspan Insulation Price List 1 st January 2013

The Kingspan Insulation Price List 1 st January 2013 Insulation The Kingspan Insulation Price List 1 st January 2013 FOR BUILDING FABRIC INSULATION, CAVITY CLOSERS AND MEMBRANES Visit our website: www.kingspaninsulation.co.uk Low Energy - Low Carbon Buildings

More information

After reading this lesson you will be able to: 12.3 IMPORTANCE OF ROOF 12.4 TYPES OF ROOF IN A HOUSE

After reading this lesson you will be able to: 12.3 IMPORTANCE OF ROOF 12.4 TYPES OF ROOF IN A HOUSE 86 :: Certificate in Construction Supervision (CIVIL) 12 ROOF 12.1 INTRODUCTION The structure provided to cover the house surface (floor) is known as roof. For different situation and requirement, it is

More information

CONDENSATION IN REFRIDGERATED BUILDINGS

CONDENSATION IN REFRIDGERATED BUILDINGS CONDENSATION IN REFRIDGERATED BUILDINGS By: Steve Salisbury Nov. 10, 2010 (revised Nov. 14, 2013) Introduction The following discussion reviews the basic causes of condensation in refrigerated buildings

More information

Final inspections are completed by site visit only. Access to fenced yards shall be planned.

Final inspections are completed by site visit only. Access to fenced yards shall be planned. ROOFING RESIDENTIAL BUILDING INSPECTIONS DEPARTMENT www.ci.blaine.mn.us This handout is intended only as a guide and is based in part on the 2015 Minnesota State Building Code, Blaine City ordinances,

More information

Shingle Roofing: What s below the surface is important

Shingle Roofing: What s below the surface is important What s below the surface is important The roof is leaking, the shingles look old, and the downspouts are dripping. It must be time to replace the roof or is it? Shingle roofs may seem simple, but a roof

More information

Mold Preventing I nterior System

Mold Preventing I nterior System interior insulation and renovation boards A system of components that have been designed to work perfectly together to repair damage caused by mold. The system consists of boards, insulation wedges, reveal

More information

SHINGLE APPLICATION GUIDE

SHINGLE APPLICATION GUIDE SHINGLE APPLICATION GUIDE CONTENTS 01. General conditions 01. Material requirements 02. Terms 07. Estimating shingle requirements 08. Roof preparation 10.Shingle application E version 2006 GENERAL CONDITIONS

More information

CONTENTS. General conditions 2. Material requirements 3. Terms 4. Estimating shingle requirements 4. Roof preparation 6. Shingle application 9 - 1 -

CONTENTS. General conditions 2. Material requirements 3. Terms 4. Estimating shingle requirements 4. Roof preparation 6. Shingle application 9 - 1 - CONTENTS General conditions Material requirements 3 Terms 4 Estimating shingle requirements 4 Roof preparation 6 Shingle application 9 Shingle Shingle application application guide guide - - b a 3a 3b

More information

Fire safety in timber buildings

Fire safety in timber buildings Fire safety in timber buildings Introduction Fire spread in buildings is a risk to life safety for which the Building Regulations (for England and Wales 1,2, Scotland 3 and Northern Ireland 4 ) aims to

More information

RACKING AND ATTACHMENT CRITERIA FOR EFFECTIVE MEMBRANE ROOF SYSTEM INTEGRATION Public Version 1: July 9, 2012

RACKING AND ATTACHMENT CRITERIA FOR EFFECTIVE MEMBRANE ROOF SYSTEM INTEGRATION Public Version 1: July 9, 2012 RACKING AND ATTACHMENT CRITERIA FOR EFFECTIVE MEMBRANE ROOF SYSTEM INTEGRATION Public Version 1: July 9, 2012 Commercial rooftops represent the most available, sustainable and secure real estate for new

More information

The Case for Cross Laminated Timber: Part 2

The Case for Cross Laminated Timber: Part 2 Learning Objectives The Case for Cross Laminated Timber: Part 2 Opportunities and Challenges for a New Class of Timber Product 1. Review answers to common questions regarding the design and construction

More information

Ubiflex. Non-lead flashing system

Ubiflex. Non-lead flashing system Ubiflex Non-lead flashing system Ubiflex non-lead flashing Ubiflex is a non-lead waterproof flashing material which can be used in most applications where lead is traditionally used to provide a weatherproof

More information

TR31. I n s u l a t i o n. Low Energy Low Carbon Buildings

TR31. I n s u l a t i o n. Low Energy Low Carbon Buildings I n s u l a t i o n CI/Sfb (27.9) Rn7 M2 Sixth Issue March 2011 TR31 STRUCTURAL INSULATION / FSC CERTIFIED PLYWOOD COMPOSITE FOR FLAT ROOFS WATERPROOFED WITH PARTIALLY BONDED BUILT UP FELT High performance

More information