Block Lofts Condominiums
|
|
- Allen Payne
- 8 years ago
- Views:
Transcription
1 Block Lofts Condominiums Building Envelope Condition Assessment 747 Ralph McGill Boulevard Atlanta, Georgia Presented to: Block Lofts Condominium Home Owners Association C/o Heritage Property Management Services, Inc. 500 Sugar Mill Road, Suite 200B Atlanta, Georgia Attention: Ms. Iraci de Queiroz, Division Manager
2 Table of Contents Block Lofts Condominiums Building Envelope Condition Assessment Block Lofts Report... Page 1 Appendix A Moisture Probes... Page 26 Appendix B Infrared Scan... Page 36 IR Scan... Page 47 Appendix C Exploratory Openings... Page 68 Appendix D Repair Options... Page 107
3 May 2, 2013 MH Ref.: Block Lofts Condominium Home Owners Association c/o Ms. Iraci de Queiroz, Division Manager Heritage Property Management Services, Inc. 500 Sugar Mill Road, Suite 200B Atlanta, Georgia Re: Building Envelope Condition Assessment for Block Lofts Condominiums Dear Ms. Queiroz: This letter report documents the results of Morrison Hershfield s building envelope condition assessment work for the Block Lofts Condominium project. The scope of work completed by Morrison Hershfield included an occupant survey, a visual review, infrared imaging, moisture probes and exploratory openings. The purpose of this condition assessment was to determine the probable extent of water infiltration problems and to develop a draft scope for repair for cost estimating purposes. Deficiencies reported herein are based on our visual observations and exploratory openings performed through a representative sampling of the stucco cladding assembly. They do not represent a total inventory of all locations with deficiencies nor do they imply that all similar locations or items to be deficient. A photographic record of observations was made using digital photos. Selected representative photographs and infrared images are included throughout the report. All photographic information taken during this assessment has been provided on a flash drive. Building Description The Block Loft Condominium community consists of three similar four-story, plus a mezzanine level, wood-framed structures constructed over concrete foundations. The cladding is cement plaster and scored face cement block veneer. The windows are aluminum framed, flange mounted units. Wood-framed swing doors provide access to the front entries, balconies, and waterproof decks of the residential units. Overhead doors provide car access into the garages. The roofs are clad with an EPDM roofing material. The roofs drain to scuppers, into conductor heads, and down rainwater leaders, where we assume they drain into the city storm water systems. The roof structures are wood framed. Morrison Hershfield Corporation 1455 Lincoln Parkway, Suite 500 Atlanta, Georgia
4 - 2 - Refer to photos 100-1, 200-1, and for general views of the buildings. The following documents were provided to MH by the Homeowners Association: Description Document Date Architectural, Civil, MEP, and Structural Drawings September 22, 2003 DRC Forensic Inspection Report November 20, 2012 DRC Scope Of Repairs November 20, 2012 Exterior Assemblies The exterior building enclosure assemblies (as shown on the architectural drawings) are as follows: 1. Exterior Walls Assemblies (components listed from exterior to interior) a. Stucco Wall over wood frame: i. Cement Plaster on Metal Lath ii. One Layer of Building Felt iii. OSB Sheathing iv. Wood Stud Framing and Batt Insulation b. Concrete Block Walls i. Scored Face Concrete Block c. Flange Mounted Aluminum Window Assemblies 2. Roof Assemblies a. Low-slope roof i. EPDM Roof Membrane ii. Insulation iii. TJI Joist System b. Metal Coping Cap
5 - 3 - Occupant Survey An occupant survey was conducted to gather information relative to water intrusion and other moisture related issues. A total of 41 owners responded to the questionnaire. The following table summarizes the key findings of the occupant questionnaire Issue % of Owners reporting issues Number of Owners Water Leak 34% 14 Wall Leaks 17% 7 Window Leaks 10% 4 Ceiling Leaks 15% 6 Floor Leaks 17% 7 Door Leaks 5% 2 Balcony Deterioration 15% 6 Balcony Standing Water 10% 4 Interior Damage 22% 9 Field Review Work The following field work was completed by Morrison Hershfield: Description MH Staff Date(s) Document Review Visual Review Moisture Probes Infrared Imaging Exploratory Openings Ed Lehman Ed Lehman Ed Lehman, Chris Norris Shawn Sheehan Chris Norris, Joe Sumpter
6 - 4 - Observations Visual Review The following photographs document observations from our field work: Building Overall view of Building View of all cladding types Crack in the stucco at a pilaster
7 Crack in stucco at soffit condition Balcony saddle condition Building Overall view of Building 200
8 Field view of Building Dryer vent through stucco system noting moisture around vent Field view of end condition
9 Efflorescence at scored face block Building Overall view of Building 300
10 Field view of Building Balcony saddle condition Field view of end condition
11 Efflorescence at scored face block Typical Typical Condition: Head flashing is sealed and thus there is no way for this area to weep. Typical Typical Condition: Deteriorated polyurethane sealant typical at all sealant joints
12 Observations Moisture Probes Moisture content measurements were taken using Delmhorst BD-10 and Delmhorst BD-2100 meters. The moisture probe locations are noted in Appendix A. The following are general guidelines for interpretation of moisture content measurements in wood materials: Moisture Content (MC) <20% 20% to 30% >30% Interpretation the wood has not been recently exposed to liquid water and the MC is below that required for wood decay fungi to propagate Probable exposure to liquid water, and represent a MC at which fungal growth can be sustained. We interpret this as a Caution reading. Conditions under which fungi can flourish and decay can progress quickly. We interpret this as a Danger reading. The following table summarizes the moisture probe readings. Detailed information showing individual moisture probe locations and readings can be found in Appendix A. Moisture Probe Range No. Readings % of Readings < 20% 2 12% 20% to 30% 5 29% > 30% 10 59% Total Readings %
13 Observations Infrared Imaging Infrared imaging of the exterior building walls and a roof sample was completed. The infrared images of the walls showed several thermal anomalies within the stucco clad wall areas, which may be indicative of potential moisture accumulation. The thermal images of the roof sample showed one thermal anomaly indicative of potential moisture accumulation. The thermal imaging anomalies and the IR Report can be found in Appendix B. The following photographs document key observations from our field work: IR100-1 Building 100 Southwest Elevation Shaded areas note areas of concern based on IR scan IR100-2 Building 100 West Elevation Shaded areas note areas of concern based on IR scan
14 IR200-1 Building 200 South Elevation Shaded areas note areas of concern based on IR scan IR200-2 Building 200 Northwest Elevation Shaded areas note areas of concern based on IR scan
15 IR200-3 Building 200 East Elevation Shaded areas note areas of concern based on IR scan IR300-1 Building 300 Southwest Elevation Shaded areas note areas of concern based on IR scan
16 IR300-2 Building 300 Southeast Elevation Shaded areas note areas of concern based on IR scan IR300- Roof Building 300 Roof Scan notes an isolated damaged area of the roof at the northeast corner. Observations Exploratory Openings Nineteen (19) exploratory openings were made in the exterior wall assemblies to confirm the construction and condition of the building envelope components. The opening locations are identified in the elevation drawings contained in Appendix C. The following table summarizes the results.
17 Exploratory Opening Summary Table Extent of Damage Found Openings in Exposed Walls 13% of Openings No damage, no evidence of moisture Evidence of moisture but sheathing intact (staining) Deteriorated sheathing, but framing intact Sheathing and framing deteriorated 3 16% 11 58% 5 26% 0 0% Total Openings % The following photographs document key observations from our exploratory openings: 01 Exploratory Opening 1: Building 100 North Elevation Balcony Saddle Opening at Control Joint Moisture Reading: >40% Deteriorated Sheathing
18 Exploratory Opening 2: Building 100 North Elevation Balcony Saddle Opening at Control Joint Moisture Reading: >40% Deteriorated Sheathing 03 Exploratory Opening 3: Building 200 South Elevation Field Opening Moisture Reading: 8.7% 04 Exploratory Opening 4: Building 100 South Elevation Field Opening at Control Joint Moisture Reading: >40% Deteriorated Sheathing
19 Exploratory Opening 5: Building 100 South Elevation Window Sill Moisture Reading: 22% 06 Exploratory Opening 6: Building 100 south Elevation Window Head Moisture Reading: 9%
20 Exploratory Opening 7: Building 200 North Elevation Balcony Saddle at Control Joint Moisture Reading: 38.9% Deteriorated Sheathing 08 Exploratory Opening 8: Building 200 North Elevation Balcony Saddle Opening at Control Joint Moisture Reading: 34.3% Deteriorated Sheathing 09 Exploratory Opening 9: Building 200 North Elevation Field Opening below openings 7 & 8 Moisture Reading: 36.7% Deteriorated Sheathing
21 Exploratory Opening 10: Building 200 South Elevation Soffit Condition Moisture Reading: >40% 11 Exploratory Opening 11: Building 200 South Elevation Field Moisture Reading: 20%
22 Exploratory Opening 12: Building 200 East Elevation at Dryer Vent Moisture Reading: >40% Deteriorated Sheathing 13 Exploratory Opening 13: Building 100 West Elevation Window Head Opening at Control Joint Moisture Reading: 24.8% Deteriorated Sheathing
23 Exploratory Opening 14: Building 300 East Elevation Field Opening Below the Window Sill at Control Joint Intersection Moisture Reading: >40% Deteriorated Sheathing 15 Exploratory Opening 15: Building 300 East Elevation Window Head Moisture Reading: 12% 16 Exploratory Opening 15: Building 300 East Elevation at Walkway Column Moisture Reading: >40%
24 Exploratory Opening 17: Building 300 West Elevation at Balcony Moisture Reading: 20% 18 Exploratory Opening 18: Building 300 West South Elevation Above Masonry Moisture Reading: 25% 19 Exploratory Opening 19: Building 300 South Elevation Field Opening at Control Joint Moisture Reading: 26%
25 Discussion The stucco clad wood-framed wall assemblies are clad in what is commonly referred to as a concealed-barrier system. Concealed-barrier stucco systems incorporate a water-resistant material (typically two layers consisting of building paper or housewrap and in this case a single layer of paper) behind the exterior cladding system. Small gaps between the building paper and the backside of the stucco provide limited ability for drainage or drying of incidental moisture from the wall assembly. The stucco assembly on this project is not provided with weeps or any other means for the drainage of incidental moisture. Water is able to enter behind the stucco at control joints, at interfaces such as dryer vents and balcony saddles, and at any cracks in the stucco itself. The stucco assembly does not provide the ability to drain this water back to the exterior, which is resulting in saturation of the building paper, elevated moisture content of the OSB sheathing, and resultant deterioration of the building paper and sheathing. Based on the exploratory work conducted for this assessment it appears that the damage at the present time is largely limited to the sheathing, although some framing damage has also occurred particularly at soffit conditions. The stucco assembly installed at the Block Lofts condominiums is not an appropriate assembly for the Atlanta climate, and without remedial work continued deterioration should be expected. At the time of this assessment the extent of damage does not present a risk for structural failure, however, if deterioration is allowed to progress framing damage and structural failure may eventually result. Recommendations The roofing is currently in good to fair condition and does not require any significant remedial work with the exception of the isolated area identified at Building 300. With an appropriate maintenance program a remaining service life of 5-10 years should be achievable for the roof membrane. The stucco clad wall assembly is not appropriate for the Atlanta climate and remediation will be required for the stucco wall assemblies. Removal of stucco will be required to implement effective repairs. We have provided two options for repair of the stucco walls as follows: Option 1: Replace all stucco in weather exposed areas (See Appendix D for Area of Repair) This option includes the following scope of repair: 1. Remove and dispose of all stucco, accessories, and building paper 2. Replace moisture damaged OSB sheathing (estimated at 10% of exposed wall area) 3. Replace damaged wood framing. Framing replacement is anticipated primarily at soffit conditions. 4. Remove and re-flash all windows in work area. 5. Install new dryer vent covers complete w/ flashing 6. Install new drainable stucco system (Sto Powerwall NeXT) a. Fluid applied air/water barrier (StoGuard)
26 b. New drainage mat (Sto Drainscreen) c. Flashing w/ end dams above all windows d. Through wall flashing at floor lines e. Three coat cement plaster stucco (Sto Powerwall) f. Acrylic finish (Sto Acryl) 7. Caulk penetrations in stucco with silicone caulking. Tremco Spectrem 1 or Dow 790 This repair option will allow review and repair of all damage OSB and sheathing. The completed repair will be a drainable stucco system, which will provide the Owners with a durable, low maintenance wall assembly. Option 2: Targeted Repairs (See Appendix D for Area of Repair) This option includes the following scope of repair: 1. Targeted stucco removal as follows in weather exposed locations: a. Remove 1' above and 2' below all horizontal control joints b. Remove 1' either side of all vertical control joints c. Remove 1' below all windows, extending 1'horizontally beyond windows d. Remove 1' above all windows, extending 1' horizontally beyond windows e. Remove 1' above, 2' below and 1' to horizontally beyond all dryer vents f. 2' above and wrapping bottom of all soffit conditions g. Full height of all pilasters h. Remove building paper in all areas of stucco removal i. Inspect OSB sheathing, extend stucco removal in any locations where damage extends beyond the removed stucco or within 6" of the edges of removed area. 2. Remove and re-flash all windows, provide weeps to exterior below each window sill flange. 3. Remove and replace all damaged OSB sheathing and framing 4. Install two layers of air/water barrier (Tyvek Stucco Wrap over Tyvek Commercial Wrap) 5. Install new three coat stucco complete w/ accessories 6. Caulk all control joints and all penetrations through stucco with Dow 790 sealant 7. Coat entire stucco wall assembly with Dow Allguard silicone coating The above option may reduce the overall extent of stucco removal to some extent, however, the construction cost savings of this option will be limited due to the additional coordination required and the possibility that further removal could be required if damage is found to extend beyond the extent of initial stucco removal. The completed stucco repair will be a face sealed system, meaning that it relies on preventing water intrusion at the exterior face of the building. Maintenance of sealants and of the Dow Allguard coating will be critical to the long term durability of this repair. Dow Allguard will require re-coating on a year cycle, and can only be re-coated with either Dow Allguard or a compatible silicone coating. The Dow Allguard will also give the building a slight sheen and a slightly "rubbery" texture.
27 Isolated Roof Repair-Building 300 Roof We recommend taking a roof core sample at the identified area to confirm if indeed the area is wet. If the area is found to be wet, we recommend removing the wet material and making the necessary repairs, replace and patch back the roof in this area. Repair Option Comparison Removal and re-flashing of windows is recommended in both repair options. Re-flashing the windows will allow installation of drained sill pans beneath the windows. Sill pans will redirect any water leaking through the window frames into the rough opening back to the exterior without damage to the wall assembly. In the experience of MH, aluminum framed residential grade windows are often prone to leaks at the corners, which can result in trapped water within the wall assembly and resultant damage. Windows that are known to leak can also be replaced as part of the repair work. Given the extent of damage and the limitations of the Option 2 targeted repairs, Morrison Hershfield recommends implementing the Option 1 repair scope. Regardless of the repair option selected, complete construction documents including material specifications, building elevations showing the extent of the work, assembly and interface details, and bid forms should be prepared. Proper documentation will be critical to control the cost and quality of the repair work. The repair work should be bid to a limited group of selected pre-qualified bidders with experience with this type of work, or by a negotiated contract with a single qualified contractor. Yours truly, Morrison Hershfield Corporation Edward Lehman, Assoc. AIA, CEI, RRO Building Science Consultant Chris Norris, PE, LEED AP, CEI Principal / Building Science Specialist Joe Sumpter, CEI Building Science Consultant Shawn Sheehan, RA, NCARB, CEI, RRO Building Science Consultant P:\PROJECTS\613 SERIES\ BLOCK LOFTS EIFS EVALUATION\00\07 - REPORTING\BLOCK LOFTS REPORT DRAFT.DOC
28 APPENDIX A Moisture Probes
29 Building 100
30 Building 100 Moisture Probe Locations
31 Building 100 Moisture Probe Locations
32 Building 200
33 Building 200 Moisture Probe Locations
34 Building 200 Moisture Probe Locations
35 Building 300
36 Building 300 Moisture Probe Locations
37 Building 300 Moisture Probe Locations
38 APPENDIX B Infrared Scan
39 Building 100
40 Building 100 Infrared Scan Anomalies
41 Building 100 Infrared Scan Anomalies
42 Building 200
43 Building 200 Infrared Scan Anomalies
44 Building 200 Infrared Scan Anomalies
45 Building 300
46 Building 300 Infrared Scan Anomalies
47 Building 300 Infrared Scan Anomalies
48 Infrared Scan Report
49 51.1 F Sp2 0 Sp Image 7:33:55 Image Camera FLIR Location: Building 100, South Elevation Other remarks: Object 25 Reflected Apparent 62.0 Atmospheric 46.0 Sp Sp Comment: Thermal anomalies were observed and are consistent with water patterns behind the surface of stucco. Recommendation: Inspected by : Shawn Sheehan Signature:... date: Morrison Hershfield 1455 Lincoln Parkway, Suite 500 Atlanta, GA Phone: ,
50 52.4 F Sp Sp1 Sp Image 7:34:04 Image Camera FLIR Location: Building 100, South Elevation Other remarks: Object 7.8 Reflected Apparent 62.0 Atmospheric 46.0 Sp Sp Sp Comment: Thermal anomalies were observed and are consistent with water patterns behind the surface of stucco. Recommendation: Inspected by : Shawn Sheehan Signature:... date: Morrison Hershfield 1455 Lincoln Parkway, Suite 500 Atlanta, GA Phone: ,
51 Sp F Sp Image 7:38:17 Image Camera FLIR Location: Building 100, South Elevation Other remarks: Object 7.8 Reflected Apparent 62.0 Atmospheric 46.0 Sp Sp Comment: Thermal anomalies were observed and are consistent with water patterns behind the surface of stucco. Recommendation: Inspected by : Shawn Sheehan Signature:... date: Morrison Hershfield 1455 Lincoln Parkway, Suite 500 Atlanta, GA Phone: ,
52 53.7 F 40 Sp Sp Image 7:38:34 Image Camera FLIR Location: Building 100, South Elevation Other remarks: Object 7.8 Reflected Apparent 62.0 Atmospheric 46.0 Sp Sp Comment: Thermal anomalies were observed and are consistent with water patterns behind the surface of stucco. Recommendation: Inspected by : Shawn Sheehan Signature:... date: Morrison Hershfield 1455 Lincoln Parkway, Suite 500 Atlanta, GA Phone: ,
53 49.2 F 40 Sp Sp Image 7:40:15 Image Camera FLIR Location: Building 100, East Elevation Other remarks: Object 7.8 Reflected Apparent 62.0 Atmospheric 46.0 Sp Sp Comment: Thermal anomalies were observed and are consistent with water patterns behind the surface of stucco. Recommendation: Inspected by : Shawn Sheehan Signature:... date: Morrison Hershfield 1455 Lincoln Parkway, Suite 500 Atlanta, GA Phone: ,
54 47.1 F Sp Sp Image 7:40:23 Image Camera FLIR Location: Building 100, East Elevation Other remarks: Object 7.8 Reflected Apparent 62.0 Atmospheric 46.0 Sp Sp Comment: Thermal anomalies were observed and are consistent with water patterns behind the surface of stucco. Recommendation: Inspected by : Shawn Sheehan Signature:... date: Morrison Hershfield 1455 Lincoln Parkway, Suite 500 Atlanta, GA Phone: ,
55 48.7 F Sp Sp Image 7:49:06 Image Camera FLIR Location: Building 300, Southeast Elevation Other remarks: Object 7.8 Reflected Apparent 62.0 Atmospheric 46.0 Sp Sp Comment: Thermal anomalies were observed and are consistent with water patterns behind the surface of stucco. Recommendation: Inspected by : Shawn Sheehan Signature:... date: Morrison Hershfield 1455 Lincoln Parkway, Suite 500 Atlanta, GA Phone: ,
56 Sp2 Sp F Image 7:49:22 Image Camera FLIR Location: Building 300, Southeast Elevation Other remarks: Object 7.8 Reflected Apparent 62.0 Atmospheric 46.0 Sp Sp Comment: Thermal anomalies were observed and are consistent with water patterns behind the surface of stucco. Recommendation: Inspected by : Shawn Sheehan Signature:... date: Morrison Hershfield 1455 Lincoln Parkway, Suite 500 Atlanta, GA Phone: ,
57 53.2 F 40 Sp Sp Image 8:00:26 Image Camera FLIR Location: Building 100, West Elevation Other remarks: Object 7.8 Reflected Apparent 62.0 Atmospheric 46.0 Sp Sp Comment: Thermal anomalies were observed and are consistent with water patterns behind the surface of stucco. Recommendation: Inspected by : Shawn Sheehan Signature:... date: Morrison Hershfield 1455 Lincoln Parkway, Suite 500 Atlanta, GA Phone: ,
58 52.0 F 40 Sp Sp Image 8:00:40 Image Camera FLIR Location: Building 100, West Elevation Other remarks: Object 7.8 Reflected Apparent 62.0 Atmospheric 46.0 Sp Sp Comment: Thermal anomalies were observed and are consistent with water patterns behind the surface of stucco. Recommendation: Inspected by : Shawn Sheehan Signature:... date: Morrison Hershfield 1455 Lincoln Parkway, Suite 500 Atlanta, GA Phone: ,
59 51.7 F Sp1 40 Sp Image 8:00:47 Image Camera FLIR Location: Building 100, West Elevation Other remarks: Object 7.8 Reflected Apparent 62.0 Atmospheric 46.0 Sp Sp Comment: Thermal anomalies were observed and are consistent with water patterns behind the surface of stucco. Recommendation: Inspected by : Shawn Sheehan Signature:... date: Morrison Hershfield 1455 Lincoln Parkway, Suite 500 Atlanta, GA Phone: ,
60 Sp F Sp Image 8:10:34 Image Camera FLIR Location: Building 200, North Elevation Other remarks: Object 7.8 Reflected Apparent 62.0 Atmospheric 46.0 Sp Sp Comment: Thermal anomalies were observed and are consistent with water patterns behind the surface of stucco. Recommendation: Inspected by : Shawn Sheehan Signature:... date: Morrison Hershfield 1455 Lincoln Parkway, Suite 500 Atlanta, GA Phone: ,
61 44.7 F Sp Sp Image 8:10:40 Image Camera FLIR Location: Building 200, North Elevation Other remarks: Object 50 Reflected Apparent 62.0 Atmospheric 46.0 Sp Sp Comment: Thermal anomalies were observed and are consistent with water patterns behind the surface of stucco. Recommendation: Inspected by : Shawn Sheehan Signature:... date: Morrison Hershfield 1455 Lincoln Parkway, Suite 500 Atlanta, GA Phone: ,
62 55.0 F 40 Sp Sp Image 8:18:23 Image Camera FLIR Location: Building 300, Northwest corner Other remarks: Object 7.8 Reflected Apparent 62.0 Atmospheric 46.0 Sp Sp Comment: Thermal anomalies were observed and are consistent with water patterns behind the surface of stucco. Recommendation: Inspected by : Shawn Sheehan Signature:... date: Morrison Hershfield 1455 Lincoln Parkway, Suite 500 Atlanta, GA Phone: ,
63 65.7 F Sp Sp Image 8:18:32 Image Camera FLIR Location: Building 300, Northwest corner Other remarks: Object 7.8 Reflected Apparent 62.0 Atmospheric 46.0 Sp Sp Comment: Thermal anomalies were observed and are consistent with water patterns behind the surface of stucco. Recommendation: Inspected by : Shawn Sheehan Signature:... date: Morrison Hershfield 1455 Lincoln Parkway, Suite 500 Atlanta, GA Phone: ,
64 65.6 F Sp Sp Image 8:18:39 Image Camera FLIR Location: Building 300, Northwest corner. Other remarks: Object 7.8 Reflected Apparent 62.0 Atmospheric 46.0 Sp Sp Comment: Thermal anomalies were observed and are consistent with water patterns behind the surface of stucco. Recommendation: Inspected by : Shawn Sheehan Signature:... date: Morrison Hershfield 1455 Lincoln Parkway, Suite 500 Atlanta, GA Phone: ,
65 52.2 F Sp Sp Image 8:20:49 Image Camera FLIR Location: Building 300, West Elevation Other remarks: Object 7.8 Reflected Apparent 62.0 Atmospheric 46.0 Sp Sp Comment: Thermal anomalies were observed and are consistent with water patterns behind the surface of stucco. Recommendation: Inspected by : Shawn Sheehan Signature:... date: Morrison Hershfield 1455 Lincoln Parkway, Suite 500 Atlanta, GA Phone: ,
66 Sp F 60 Sp Image 8:21:05 Image Camera FLIR Location: Building 300, West Elevation Other remarks: Object 7.8 Reflected Apparent 62.0 Atmospheric 46.0 Sp Sp Comment: Thermal anomalies were observed and are consistent with water patterns behind the surface of stucco. Recommendation: Inspected by : Shawn Sheehan Signature:... date: Morrison Hershfield 1455 Lincoln Parkway, Suite 500 Atlanta, GA Phone: ,
67 43.5 F 40 Sp Sp Image 8:21:37 Image Camera FLIR Location: Building 300, South Elevation Other remarks: Object 7.8 Reflected Apparent 62.0 Atmospheric 46.0 Sp Sp Comment: Thermal anomalies were observed and are consistent with water patterns behind the surface of stucco. Recommendation: Inspected by : Shawn Sheehan Signature:... date: Morrison Hershfield 1455 Lincoln Parkway, Suite 500 Atlanta, GA Phone: ,
68 46.4 F Sp Sp Image 8:22:33 Image Camera FLIR Location: Building 300, South Elevation Other remarks: Object 50 Reflected Apparent 62.0 Atmospheric 46.0 Sp Sp Comment: Thermal anomalies were observed and are consistent with water patterns behind the surface of stucco. Recommendation: Inspected by : Shawn Sheehan Signature:... date: Morrison Hershfield 1455 Lincoln Parkway, Suite 500 Atlanta, GA Phone: ,
69 Sp1 Sp F Image 7:52:27 Image Camera FLIR Object 7.8 Reflected Apparent 62.0 Atmospheric 75.0 Sp Sp Location: Building 300, northwest corner of the roof. Other remarks: Comment: Thermal anomaly was observed and is consistent with water patterns behind membrane roofing. Puncture was observed in roof membrane. Recommendation: Inspected by : Shawn Sheehan Signature:... date: Morrison Hershfield 1455 Lincoln Parkway, Suite 500 Atlanta, GA Phone: ,
70 APPENDIX C Exploratory Openings
71 Building 100
72 Photo 100-A Building North Elevation Photo 100-B Building South Elevation Photo 100-C Building East Elevation
73 Building 100 Exploratory Openings
74 Building 100 Exploratory Openings
75 Exploratory Opening 1: Building 100 North Elevation Photo 1a: Opening at a right side balcony saddle condition Photo 1b: Opening with a layer of felt shingle lapping approximately 6
76 Photo 1c: Line of control joint with noted water infiltration Moisture reading of >40% with deteriorating sheathing due to moisture infiltrating at the control joint Photo 1d: Moisture reading of >40% with deteriorating sheathing due to moisture infiltrating at the control joint Exploratory Opening 2: Building 100 North Elevation Photo 2a: Opening at a left side balcony saddle condition
77 Photo 2b: Opening with a layer of felt shingle lapping approximately 6 Photo 2c: Line of control joint with noted water infiltration. Moisture reading of >40% with deteriorating sheathing due to moisture infiltrating at the control joint. Photo 2d: Moisture reading of >40% with deteriorating sheathing due to moisture infiltrating at the control joint.
78 Exploratory Opening 4: Building 100 South Elevation Photo 4a: Line of control joint with noted water infiltration. Moisture reading of >40% with deteriorating sheathing due to moisture infiltrating at the control joint Photo 4b: Excessive moisture reading at sheathing below control joint.
79 Exploratory Opening 5: Building 100 South Elevation Photo 5a: Right Window Sill noting the felt paper with some deterioration. Photo 5b: Self-adhered membrane flashing at sill. Note that the opening does not appear to be wrapped with weather barrier. Area of water infiltration with due to deteriorating sealant at the window to stucco joint Photo 5c: Moisture reading at the base of the sill opening with a reading of 22%.
80 Exploratory Opening 6: Building 100 South Elevation Photo 6a Right window head with felt paper intact. Photo 6b: Window head with felt paper removed noting dry condition.
81 Photo 6c: Moisture reading for this area of 9% Exploratory Opening 13: Building 100 West Elevation Photo 13a: Opening taken at the window head on the west elevation.
82 Photo 13b: Opening with building felt over self-adhered flashing. Building felt was saturated when the opening was performed. Photo 13c: Opening with the building felt removed. The sealant joint at the window head is preventing the stucco system from weeping out and forcing the moisture back into the building. Photo 13d: Moisture reading for this area of 24.8% at the side of the window.
83 Building 200
84 Photo 200-A: Building 200- North Elevation Photo 200-B: Building 200-South Elevation Photo 200-C: Building 200-East Elevation
85 Building 200 Exploratory Openings
86 Building 200 Exploratory Openings
87 Exploratory Opening 3: Building 200 North Elevation Photo 3a: Opening taken in the field of a pilaster. Photo 3b: Opening with a single layer of building felt. Photo 3c: Opening with the building felt removed. Sheathing appears to be dry.
88 Photo 3d: Moisture reading of 8.7% Exploratory Opening 7: Building 200 North Elevation Photo 7a: Opening taken at the right balcony saddle through a control joint. Photo 7b: Opening with felt removed noting deteriorated sheathing.
89 Photo 7c: Moisture reading of 38.9%. Exploratory Opening 8: Building 200 North Elevation Photo 8a: Opening taken at the left balcony saddle through a control joint. Photo 8b: Opening with a single layer of building felt shingle lapped at the control joint with approximately 6: overlap.
90 Photo 8c: Opening with building felt removed noting deteriorated sheathing below the control joint. Photo 8d: Moisture reading of 34.3% Exploratory Opening 9: Building 200 North Elevation Photo 9a: Opening taken in the field centered below openings 7 & 8.
91 Photo 9b: Single layer of building felt and sheathing. Photo 9c: Moisture reading of 36.7% at left edge of opening
92 Exploratory Opening 10: Building 200 South Elevation Photo 10a: Opening taken at the face of soffit condition at walkway. Photo 10b: Moisture reading of >40% at the base of the face where the soffit turns back. Photo 10c: Moist and deteriorating sheathing was noted at this location.
93 Exploratory Opening 11: Building 200 South Elevation Photo 11a: Opening in the field area of the stucco on the southeast corner. Felt paper intact. Photo 11b: Moisture reading of 20% at lower corner of the opening. The readings at the lower portion of the opening ranged from 15-20% and at the upper portion of the opening the range was 7-9%
94 Exploratory Opening 12: Building 200 East Elevation Photo 12a Opening was taken at a dryer vent penetration. The felt paper has deteriorated in this area. Photo 12b: The sheathing is moist in the area surrounding the dryer. The vent penetration does not appear to have been flashed to the weather barrier at the penetration.
95 Photo 12c: Sheathing is moist and delaminating at this area below the dryer vent. Photo 12d: Moisture reading at this location 35%
96 Building 300
97 Photo 300-A: Building 300-West Elevation Photo 300-B: Building 300- East Elevation Photo 300-C: Building 300-South Elevation
98 Building 300 Exploratory Openings
99 Building 300 Exploratory Openings
100 Exploratory Opening 14: Building 300 East Elevation Photo 14a: Opening taken below a window sill at the vertical to horizontal control join intersection. Photo 14b: Opening with building felt exposed. Photo 14c: Opening with building felt removed noting deteriorating sheathing.
101 Photo 14d: Moisture reading >40%.
102 Exploratory Opening 15: Building 300 East Elevation Photo 15a: Opening at the right head of the window. Building felt appears to be dry. Photo 15b: Head opening with felt removed noting the self-adhered flashing at the window flanges. Photo 15c: Moisture reading at side of opening is 12%. Head condition appears to be dry.
103 Exploratory Opening 16: Building 300 East Elevation Photo 16a: Opening taken at column area of the walkway. Felt paper appears to be deteriorating at the right side. Photo 16b: Opening after felt paper has been removed. Water infiltration noted at the right side of the opening as it turns back. Photo 16c: Moisture reading of >40%
104 Exploratory Opening 17: Building 300 West Elevation Photo 17a: Opening between balconies at a control joint. Photo 17b: Opening with felt paper removed noting some water infiltration along the control joint area. Photo 17c: Moisture reading of 20% along the control joint
105 Exploratory Opening 18: Building 300 South Elevation Photo 18a: Opening at the base of stucco at masonry to stucco area. Building felt appear to be dry. Photo 18b: Opening with building felt removed. Opening occurs below a window beside a vertical control joint.
106 Photo 18c: Moisture reading of 25% at the right side of the opening along the vertical control joint.
107 Exploratory Opening 19: Building 300 South Elevation Photo 19a: Opening was taken in the field area of the stucco along a horizontal control joint. Photo 19b: Moisture reading below the control joint of 26% Photo 19c: Moisture reading above the control joint of 12%.
108
109 APPENDIX D Repair Options
110 Repair Option 1
111 Repair Option 1: Front and Rear Elevations
112 Repair Option 1: End Elevation
113 Repair Option 2
114 Repair Option 2: Front and Rear Elevations
115 Repair Option 2: End Elevation
PETERSONS WATERFRONT CONDOMINIUMS
CONSULT DESIGN CONSTRUCT PETERSONS WATERFRONT CONDOMINIUMS 103 Park Street Chelan, Washington Findings Summary Report Prepared for: Petersons Waterfront Condominium Association March 21, 2014 J2 Project
More informationRDH Building Sciences Inc.
MAK LTR 2007 03 26 Proposal for Building Enclosure Consulting Services RDH Building Sciences Inc. 509 FAIRVIEW AVENUE N SEATTLE WA 98109-5507 TEL 206 324 2272 FAX 206 324 6339 SEA@RDHBE.COM WWW.RDHBE.COM
More informationExterior Elevated Elements Inspection Guidelines
Exterior Elevated Elements Inspection Guidelines Planning and Development 1. Guideline Purpose These guidelines are intended to assist practicing professionals in complying with Berkeley Municipal Code
More informationWater Damage & Repair
Water Damage & Repair Chinatown Preservation Talks 2015 James Engler, P.A Glenn Mason, AIA Mason Architects Program Outline Terminology & Waterproofing Basics Discussion of why this is important Below
More informationFinegan Inspection Services, Inc.
Finegan Inspection Services, Inc. Report Prepared For: Phone 513-683-0733 Fa 513-697-0163 Owners Property Address City, State, ZIP Phone FAX Owners Realtor Realty Company Phone FAX OWNER INFORMATION PROPERTY
More informationWilliamson and Associates, Inc. Report of Building Exterior Condition Evaluation, dated January 2 nd, 2013. (68 pages)
INNOVATIVE BUILDING AND ARCHITECTURE CONSULTANTS Mr. Bud Hall Senior Vice President of construction Turnberry Associates 19501 Biscayne Boulevard, Suite 400 Aventura, FL 33180 Subject: The Nashville Hilton
More informationStucco Moisture Inspection Report
Stucco Moisture Inspection Report For the Property Located At: Sample Inspection St. Report Prepared Ecusively For: Potential Buyer Pace FL. 32571 >< 850.393.6106 >< ofc- 850-941-8600 > Email: pat@moistureconsultantsinc.com
More informationBuilding Condition Assessment: 109-111 North Howard Street Baltimore, Maryland
KPA The Joint Venture of EBA Engineering, Inc. and Kennedy Porter & Associates, Inc. 4813 Seton Drive, Baltimore, MD 21215 Phone: (410-358-7171) Fax: (410)358-7213 Building Condition Assessment: Baltimore,
More information3.1 Water Intrusion Problems Related to Unsealed Stucco Penetrations
3.1 Water Intrusion Problems Related to Unsealed Stucco Penetrations Any penetration through the stucco that is left unsealed will allow entry of moisture. Even an average size home can have an extreme
More informationInspecting to a higher standard.
Inspecting to a higher standard. Rob Hopkin Silver Spring, MD 20902 Monday, June 2, 2014 ProTec Inspection Services Inc. 19736 Selby Ave Poolesville, MD 20837 301-972-8531 www.protec-inspections.com rob@protec-inspections.com
More informationSTRUCTURAL ASSESSMENT
STRUCTURAL ASSESSMENT Project: 1432-1434 East Commerce St. Job. No: 122200 Location: San Antonio, TX Date: Dec. 10, 2012 Weather: Sunny, Windy,60 deg Performed by: Jeff Haughton and Frank Lamas, Alpha
More information10DBMC International Conference On Durability of Building Materials and Components LYON [France] 17 20 April 2005
10DBMC International Conference On Durability of Building Materials and Components Wall Cladding System Durability Lessons Learned from the Premature Deterioration of Wood-Framed Construction Clad with
More informationNon Invasive Roof Leak Detection Using Infrared Thermography
Non Invasive Roof Leak Detection Using Infrared Thermography Scott Wood Four Star Cleaning and Restoration, Inc. ABSTRACT Residential roofs without attics are typically inspected for leaks by installing
More informationDecember 24, 2008. twalker@sedaconstruction.com. SEDA Construction Attn: Ted Walker 2120 Corporate Square Boulevard Jacksonville, Florida 32216
December 24, 2008 twalker@sedaconstruction.com SEDA Construction Attn: Ted Walker 2120 Corporate Square Boulevard Jacksonville, Florida 32216 RE: Georgetown Community 2C - Revised Assessment Date: October
More informationWhen dealing with a potential moisture problem, time is of the essence. Taking a proactive approach will save you money and headaches down the road.
If you own a house clad in something known as exterior insulated finish systems (EIFS), also known as synthetic stucco, you are probably trying to cope with a small but growing feeling of anxiety. You
More informationWindow Sill Details for Effective Drainage of Water
Construction Technology Update No. 76 Window Sill Details for Effective Drainage of Water By M.A. Lacasse and M.M. Armstrong Satisfactory window performance demands a good product and proper installation.
More informationUniversity of California - Santa Barbara West Campus Point Faculty Housing
University of California - Santa Barbara West Campus Point Faculty Housing Reconstruction Guidelines and Considerations to Correct Exterior Building Envelope Weatherproofing Defects and Recommended Upgrades
More informationWeather Resistive Barriers: Building Science Makes a Case for Two Layers by Dave Olson Technical Services Manager, Fortifiber Building Systems Group
Weather Resistive Barriers: Building Science Makes a Case for Two Layers by Dave Olson Technical Services Manager, Fortifiber Building Systems Group Since water intrusion is among the most damaging problems
More information201 WATER STREET FORWARDERS MUSEUM AND VISITORS INFORMATION CENTRE
STRUCTURAL INSPECTION REPORT DRAFT 201 WATER STREET FORWARDERS MUSEUM AND VISITORS INFORMATION CENTRE TOWN OF PRESCOTT Date: November 2013 GENIVAR No.: 131-20617-00 2611 Queensview Drive, Suite 300, Ottawa,
More informationHow To Repair A Boat Landing Deck With A Boat Bed
RESIDENTIAL INSULATED SHEATHING INSTALLATION GUIDE Residential Insulated Sheathing Installation Guide ROXUL COMFORTBOARD IS Table of Contents Slab-on-grade-to Above Grade Wall...1 Foundation Wall at Footing
More informationSECTION 3 ONM & J STRUCTURAL ANALYSIS
Historic Boynton Beach High School Existing Building Assessment City of Boynton Beach February 10, 2011 SECTION 3 ONM & J STRUCTURAL ANALYSIS STRUCTURAL ENGINEERS SPECIAL INSPECTORS STRUCTURAL CONDITION
More informationAsphalt Shingle Application Requirements
Alberta Allied Roofing Association Asphalt Shingle Application Requirements Section 1 Roof Decks 1.1 General Asphalt Shingles are not permitted to be installed directly over rigid insulation. When Asphalt
More informationPage & Turnbull imagining change in historic environments through design, research, and technology
DCI+SDE STRUCTURAL EVALUATIONS OFFICE BUILDING, TOOL SHED & WATER TANK, AND BLACKSMITH & MACHINE SHOP BUILDINGS SAN FRANCISCO, CALIFORNIA [14290] PRIMARY PROJECT CONTACT: H. Ruth Todd, FAIA, AICP, LEED
More informationComment Form on Proposed Gut Rehabilitation Alternatives
Comment Form on Gut Rehabilitation Alternatives Name: Organization: Email: Instructions Submission: Please submit this form to energystarhomes@energystar.gov by October 10 th, 2012 with the subject line
More informationStuccoSpec Moisture Testing Inspection
e-mail - stuccospec@juno.com StuccoSpec Moisture Testing Inspection Property Located At: 265 Elm Street, Anywhere, USA 01/27/02 Ordered by: Mr. & Mrs. John Doe #2 Song Sparrow Place, The Woodlands, T 77381281-364-0012
More informationCommon Problems with Walls
Common Problems with Walls Common Problems with Walls There are problems and concerns that are shared by all walls and siding installations. In this article, we will learn about the following commonly
More informationSeptember 3, 2009. Ric Boyd, Public Works Director Ketchikan Gateway Borough 344 Front St. Ketchikan, AK 99901
September 3, 2009 Ric Boyd, Public Works Director Ketchikan Gateway Borough 344 Front St. Ketchikan, AK 99901 RE: Ketchikan Gateway Borough Gateway Recreation Center Roof Observations and Intrusive Inspections
More informationCLIENT. Inspection Report. 271 Front St. Alert Bay, B.C. Island Building Inspections V ANCOUVER I SLAND B. C.
CLIENT Inspection Report 271 Front St. Alert Bay, B.C. Island Building Inspections 2013 V ANCOUVER I SLAND B. C. Elevation Photos For the Property at 271 Front Street Alert Bay, BC ELEVATION PICTURES Front
More informationHEDDERMAN ENGINEERING, INC. www.heddermanengineering.com Office 281-355-9911, Fax 281-355-9903 office@heddermanengineering.com
HEDDERMAN ENGINEERING, INC. www.heddermanengineering.com Office 281-355-9911, Fax 281-355-9903 office@heddermanengineering.com, 2011 TO: Mr. REF: CONDITION OF PROPERTY SURVEY Dear Mr. : At your request,
More informationReference: BRM-00220488-A0 July 18 th, 2014. Cursory Visual Review of Various Below Grade Spaces and Exposed Foundation Walls
Reference: BRM-00220488-A0 July 18 th, 2014 Toronto Catholic District School Board 80 Sheppard Avenue East Toronto, Ontario M2N 6E8 Re: 1.0 Introduction Exp Services Inc. (exp) was retained by the Toronto
More informationGreenGuard Housewrap Installation Guide
000768PACBPHW_Flashing Bro 5/23/03 2:52 PM Page 1 For the most current product information, go to www.green-guard.com. Pactiv Building Products believes the information and recommendations herein to be
More informationFigure 1 The GENERAL CONTRACTOR blames the applicator (if available) for improper installation and
BACKGROUND History The Exterior Insulation and Finish System (EIFS) was originally developed in West Germany in the 1960s. The original market for EIFS was providing an insulation layer to existing masonry
More informationOctober 30, 2014. Mr. & Mrs. Daniel Vick 101 Southwind Cove Benton, AR. Report of Findings, Structural Investigation, Benton, Arkansas, Dear Mr.
117 S. Market St. Benton, AR 72015 * 501-315-2626 * Fax 501-315-0024 October 30, 2014 Mr. & Mrs. Daniel Vick 101 Southwind Cove Benton, AR Re: Report of Findings,, Benton, Arkansas, Dear Mr. Vick: This
More informationMost of my work is in exterior remediation, both as a builder. Adhered Concrete Masonry Veneer To avoid water damage, treat faux stone like stucco
Best Practices Stone Veneer Adhered Concrete Masonry Veneer To avoid water damage, treat faux stone like stucco by mark parlee Photos: Mark Parlee Most of my work is in exterior remediation, both as a
More informationAssessing Curtain Walls
Assessing Curtain Walls Considerations and Best Practices Paul E Beers GCI Consultants, LLC pbeers@gciconsultants.com What is a Curtain Wall System? A curtain wall system is an outer covering of a building
More informationRoof Inspection. Summary Report
www.real-estate-inspections.com Roof Inspection Summary Report Subject Property Prepared for: File Number: Client in Detroit 05-15-RF-004 Inspector: Craig Milliken, PE # 32779 CPM Real Estate Inspections,
More informationENERGY STAR Qualified New Homes Thermal Enclosure Checklist. Water Management Checklist. Eli Caudill
ENERGY STAR Qualified New Homes Thermal Enclosure Checklist & Water Management Checklist Eli Caudill ENERGY STAR Version 3 Tighter Standards Whole Home Approach Better, More Sustainable Construction Surpasses
More informationReport on Sanctuary/Chancel Crawl Space Inspection. St. John in The Wilderness, 2896 Old Lakeshore Road Bright s Grove. Project No.
Report on Sanctuary/Chancel Crawl Space Inspection St. John in The Wilderness, 2896 Old Lakeshore Road Bright s Grove Project No. E112056 1. Background St. John in the Wilderness (SJITW) is considering
More informationBuilding Condition Assessment: 215-219 West Lexington Street Baltimore, Maryland
KPA The Joint Venture of EBA Engineering, Inc. and Kennedy Porter & Associates, Inc. 4813 Seton Drive, Baltimore, MD 21215 Phone: (410-358-7171) Fax: (410)358-7213 Building Condition Assessment: Baltimore,
More informationVer. 2. Guide to. Inspecting Residential Brick Veneer
Ver. 2 Guide to Inspecting Residential Brick Veneer 1. A guide created by industry professionals. The knowledgeable staff at MASONPRO together with technical support from the Masonry Institute of Michigan
More informationPhotos showing the change in condition from 2006 to 2012 are located in Appendix A.
January 27, 2012 Ms. Theresa Gallavan Economic Development Director City of Lompoc 100 Civic Center Plaza Lompoc, California 93436 RE: Lompoc Theater Limited Visual Condition Assessment Dear Theresa: Representatives
More informationCase Studies of the Cause and Origin of Fungal Growth in Residential and Commercial Structures
Case Studies of the Cause and Origin of Fungal Growth in Residential and Commercial Structures Stewart M. Verhulst, M.S., P.E. 1 Erik L. Nelson, Ph.D., P.E., M.ASCE 2 Deepak Ahuja, M.S., P.E.,M.ASCE 3
More informationMeasure Guideline: Water Management at Tub and Shower Assemblies
Measure Guideline: Water Management at Tub and Shower Assemblies Bruce Dickson IBACOS, Inc. December 2011 NOTICE This report was prepared as an account of work sponsored by an agency of the United States
More informationCITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN 55110 Fax: 651-429-8503. Re-Roofing: Asphalt Shingles
CITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN 55110 Fax: 651-429-8503 Re-Roofing: Asphalt Shingles This is a summary of the standard requirements based on the
More informationEAST LYME HIGH SCHOOL
Overview: 1971 N 1966 GYM 1966 CLASSROOM WING 1966 AUD. 1971 GYM 1998 1998 POOL EAST LYME HIGH SCHOOL Original 1966 Building: The original East Lyme High School was constructed in 1966 and was composed
More informationAAMA 2400-10. Standard Practice for Installation of Windows with a Mounting Flange in Open Stud Frame Construction for Low Wind/Water Exposure
A M E R I C A N A R C H I T E C T U R A L AAMA 2400-10 Standard Practice for Installation of Windows with a Mounting Flange in Open Stud Frame Construction for Low Wind/Water Exposure M A N U F A C T U
More informationHousewrap Errors. By Steve Easley
Housewrap Errors By Steve Easley There Are Seven Common Mistakes Contractors Make When Installing Housewraps Green building and remodeling programs, the U.S. Environmental Protection Agency s IAQ Plus
More informationPre-Drywall Inspection Report
SM MEDALLION INSPECTIONS helping people make informed decisions Pre-Drywall Inspection Report 5657 Garden Valley Place Milton, Georgia 30024 Prepared for Betsy and Paul Dougherty January12, 2015 Medallion
More informationVision Home Inspection
Vision Home Inspection 324 Rams Run Shepherdsville KY 40165-7877 Inspector: James McFadden Property Inspection Report Client(s): Property address: Inspection date: View report summary This report is the
More informationStructural Assessment Report
Report Dallas Township Elementary School Dallas, Pennsylvania (JBCI Project No. 144911) 1655 Suburban Station Building 1617 John F. Kennedy Boulevard Philadelphia PA 19103 215 665 0497 5 Sandwood Drive
More informationRepair of Spalling and Leaking Clay Brick Building Walls
B etter buildings Repair of Spalling and Leaking Clay Brick Building Walls Overview A few years after being built in Waterloo in 1980, a condominium of three, six-storey buildings showed severe spalling
More informationMemorandum. July 16, 2008. To: Plan Commission City of Madison
Memorandum July 16, 2008 To: Plan Commission City of Madison From: Marc Schellpfeffer Engberg Anderson Re: Structural/Architectural Assessment of Homes for Proposed Demolition Findorff Yards Office Lofts
More informationClad Direct Glaze Window Installation Instructions
Clad Direct Glaze Window Installation Instructions Sill flashing and sealing: 2. An overview of the proper flashing sequence is shown in figure 1. Please read entire installation instructions carefully
More informationLeaky Homes Financial Assistance Package (FAP) Repair plan example
LEAKY HOMES FINANCIAL ASSISTANCE PACKAGE FACT SHEET Repair Plan Example - June 2014 Page 1 Leaky Homes Financial Assistance Package (FAP) Repair plan example Introduction This repair plan example is intended
More informationEnvelope INSULATION BATT (2) Avoid Using Batt Insulation With Metal Framing. Pressure or Friction Fit
R-H-DI1 INSULATION BATT NR-E-IB1 Avoid Using Batt Insulation With Metal Framing Batt insulation should not be used with metal framing systems. Although it is common to see fiberglass batt insulation installed
More informationA0 SHEET 1 OF 5 400 LOCUST STREET FRANKFORT, KANSAS 66427 FRANKFORT, KANSAS 66427 ROOF REPAIR OF THE 400 LOCUST STREET
POYNTZ AVENUE, STE 9 MANHATTAN, KS 0..0..9 FAX WEST th STREET JUNCTION CITY, KS.... FAX 0, Bruce McMillan AIA, Architects, P.A. HERITAGE TRUST FUND GRANT PROJECT NO. 0-0 ROOF REPAIR OF THE 00 LOCUST STREET
More informationWater Management & Damage Prevention:
Water Management & Damage Prevention: A Guide for Homeowners This article provides homeowners with basic information to make these decisions and take the appropriate actions to keep their homes dry and
More informationInstallation Instructions Double-Hung, Single-Hung, Casement, Awning, Sliding, Picture & Shapes Non-Impact & Impact Resistant Nailing Fin Windows
Installation Instructions Double-Hung, Single-Hung, Casement, Awning, Sliding, Picture & Shapes Non-Impact & Impact Resistant Nailing Fin Windows americancraftsmanwindows.com Project Requirements: Read
More informationbout your HOUSE before you start Repairing And Replacing Materials Exterior Walls
A bout your HOUSE before you start Repairing And Replacing Materials Exterior Walls CE 28 h Exterior finish materials are expected to protect the house from the elements while providing an attractive appearance.
More informationFinal inspections are completed by site visit only. Access to fenced yards shall be planned.
ROOFING RESIDENTIAL BUILDING INSPECTIONS DEPARTMENT www.ci.blaine.mn.us This handout is intended only as a guide and is based in part on the 2015 Minnesota State Building Code, Blaine City ordinances,
More informationStructure Survey Findings:
Structure Survey Findings: Visible portions of the following were observed: foundations; structure to walls, columns, floors, roofs, overhang posts, and columns; attached or firmly abutting decks, balconies,
More informationInfrared Moisture Detection
What it can do for you... what it can t and why 1. Infrared camera basics 2. Examples Lew Harriman MoistureDM.com 3. Summary - The 4 most important facts about infrared moisture detection 1 of 19 Infrared
More informationPreventing Ice Dams on Roofs
Preventing Ice Dams on Roofs Facility Manager November/December 2005 When a roof leaks, facility managers inevitably receive complaints from building occupants. If it is winter, ice dams are often the
More informationwww.citiesinspection.com October 5, 2015 Dear Client,
www.citiesinspection.com October 5, 2015 Dear Client, On 9/14/2015, Cities Inspection Service, Inc. completed a building inspection of the property located at 123 Oak Street, Someplace, Minnesota for you.
More informationRECOATING AND RENEWING SPF ROOFING SYSTEMS
RECOATING AND RENEWING SPF ROOFING SYSTEMS Procedures, Regional Differences and type of coating systems Bruce Schenke Premium Spray Products REASONS TO RECOAT/RENEW Add a new coating layer to renew the
More informationBuilding Foundation and Structure
Building Foundation and Structure Overview The construction of the Hall of Waters building began in 1936, and was constructed over the original site of the Siloam and Sulpho-Saline Springs. The original
More informationRoof Repair Project Report. Fairbank Complex 40 Fairbank Road Sudbury, Massachusetts. February 14, 2014. RBA Project No. 2014007.00.
Report Fairbank Complex 40 Fairbank Road RBA Project No. 2014007.00 Prepared by: 33 Center Street, 2 nd Floor Burlington, MA Tel: 781-273-1537 Fax: 781-273-1695 TABLE OF CONTENTS Roof Repair Project Report...
More informationMelbourne balcony Assessments
Balcony Assessment Melbourne balcony Assessments Address: SAMPLE Date: Assessor: Luke O Neill Registered Builder DBL-C 31305 Assessment Guidelines This is an assessment of balcony and elements as presented
More informationINSTALLATION INSTRUCTIONS for Vinyl Windows with Integral Nailing Fin (JII001)
Thank you for selecting JELD-WEN products. Attached are JELD-WEN s recommended installation instructions for Vinyl windows with an integral nailing fin. While the use of these installation instructions
More informationMarch 19, 2014. Ms. Jean McDonald CAP Management 910 16th Street, Suite 1010 Denver, Colorado 80202
Ms. Jean McDonald CAP Management 910 16th Street, Suite 1010 Denver, Colorado 80202 Re: Prospector s Point Walkway/Façade Repairs Martin/Martin, Inc Project No.: 13.0358.S.02 Ms. McDonald: Per your request
More informationNatatorium Building Enclosure Deterioration Due to Moisture Migration
Buildings 2012, 2, 534-541; doi:10.3390/buildings2040534 OPEN ACCESS buildings ISSN 2075-5309 www.mdpi.com/journal/buildings/ Case Study Natatorium Building Enclosure Deterioration Due to Moisture Migration
More informationWhat s Wrong with this Project? Report
NAHB RESEARCH CENTER INDUSTRY PARTNERSHIP FOR HIGH PERFORMING HOMES Task Order Agreement KNDJ-0-40335-01 Deliverable Task 11.3 What s Wrong with this Project? Report Prepared For: Alliance for Sustainable
More informationTITLE: MASONRY PARAPET WALLS AND FLAT ROOF REQUIREMENTS 11/1/09
TITLE: MASONRY PARAPET WALLS AND FLAT ROOF REQUIREMENTS 11/1/09 PMT GUIDE # 10 Book of Order Section G-10.0102o: "The session is responsible for the mission and government of the particular church. It
More informationbout your HOUSE before you start Renovating Your Basement Moisture Problems
A bout your HOUSE before you start Renovating Your Basement Moisture Problems CE 28 c Condensation of cold surfaces, efflorescence Water leak in corner on floor Mold and decay on floor joists and sill
More informationHome Inspection Report
Home Inspection Report Report Number: 144 For The Property Located On: 123 Any Street 27587 Prepared For Exclusive Use By: Mr. Sample N/A,,, Report Prepared By: Edward Carapezza; License No.: 3447 Inspector
More informationResidential Roofing Guide
Residential Roofing Guide TABLE OF CONTENTS Building Detail and Accessories...... 1 Panel Introduction and Handling...... 2 Cutting and Trimming.... 3 Roof Preparation..... 3 Roof Slope..... 3 Re-roofing...
More informationWATER INTRUSION SIDING. 1 Damage in Residential Walls from Construction Defects and Water 2 TYPES OF CONSTRUCTION DEFECTS
1 Damage in Residential Walls from Construction Defects and Water Intrusion: Old and New Issues George Tsongas, Ph.D., P.E. Consulting Engineer and Building Scientist Professor Emeritus of Mechanical Engineering
More informationROOFS - Guidance for Repair, Maintenance and Replacement
ROOFS - Guidance for Repair, Maintenance and Replacement Guilford Association Architectural Committee ROOFING Slate and tile roofs are a critical design feature of Guilford homes. The homes were designed
More informationMarch 14, 2007. Installation of Bay, Bow and Garden Windows
March 14, 2007 Re: Installation of Bay, Bow and Garden Windows Attached are the Atrium Companies, Inc recommendation for the installation of bay, bow and garden windows. These instructions were developed
More informationMark Cramer Inspection Services, Inc.
Mark Cramer Inspection Services, Inc. 492 Twentieth Avenue, Indian Rocks Beach, FL 34635-2970 (727) 595-4211 Fax (727) 596-7583 Certified Member #12085 American Society of Home Inspectors Construction
More informationPROFESSIONAL ENGINEERING INSPECTIONS, INC.
PROFESSIONAL ENGINEERING INSPECTIONS, INC. P. O. BOX 271492 HOUSTON, TEXAS 77277 Registered Engineering Firm #1503 http://www.profengineering.com (713) 664-1264 July 8, 2004 Mr. Simple Samson 2831 Octoberfest
More informationRESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000
RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000 SECTION R905 REQUIREMENTS FOR ROOF COVERINGS R905.1 Roof covering application. Roof coverings
More informationVA25014B0516 VA CINCINNATI PROJECT NO. 539-328 INPATIENT BED TOWER ADDITION (4 TH AND 5 TH FLOORS) SECTION 09 29 00 GYPSUM BOARD
SECTION 09 29 00 GYPSUM BOARD PART 1 - GENERAL 1.1 DESCRIPTION This section specifies installation and finishing of gypsum board, vapor retarder and air and moisture barrrier. 1.2 RELATED WORK A. Installation
More informationBituminous Sheet Flat Roofs: Their repair and maintenance
Bituminous Sheet Flat Roofs: Their repair and maintenance Flat roof covered in sheets of bituminous felt Introduction Whilst flat roofs are often regarded as inferior to their pitched counterparts and
More informationClear Fork Valley Local School District. Roofing Repairs Spring/Summer 2015
Clear Fork Valley Local School District Roofing Repairs Spring/Summer 2015 Instructions to Bidders: Public Notice To Bidders (ORC 3313.46) Notice is hereby given that sealed bids will be received at the
More information423 NORTH HOWARD ST. VISUAL STRUCTURAL ASSESSMENT
Urgent Needs II City of Baltimore No. 1099 423 NORTH HOWARD ST. 423 North Howard Street (circa 1880) is a multi-story building constructed second in row south of Franklin Street and between the vacant
More informationFIELD TESTING SERVICES
FIELD TESTING SERVICES Chris Leach Director of Testing Baton Rouge, Louisiana Destin, Florida Scott Leach David Nichols Field Testing Representative Field Testing Representative 17485 Opportunity Avenue
More informationFoundation Evaluation Report for PROPERTY ADDRESS Houston, Texas 77089. August 30, 2012. Prepared for:
A Full Service Real Estate Inspection & Engineering Firm for Houston, Texas 77089 August 30, 2012 Prepared for: CLIENT S NAME MAILING ADDRESS Houston, Texas 77089 Prepared by: Charles J. Jenkins, P.E.
More informationELIGIBLE REPAIR PROJECT PARAMETERS
THE DISTRICT MUNICIPALITY OF MUSKOKA ONTARIO RENOVATES PROGRAM FOR HOMEOWNERS ELIGIBLE REPAIR PROJECT PARAMETERS 1. To have your project considered and payment processed, all projects requiring a Building
More informationAir-Conditioning, Heating, and Refrigeration Institute. Sheet Metal and Air-Conditioning Contractors National Association
Air-Conditioning, Heating, and Refrigeration Institute Sheet Metal and Air-Conditioning Contractors National Association GUIDELINE B-1997 ACKNOWLEDGEMENT These guidelines for Roof Mounted Outdoor Air-
More informationExterior Repair Project. By: Kami Farahmandpour, PE, RRC, RWC, CCS, CCCA Alex Szatanek. Building Technology Consultants, PC BTC
Exterior Repair Project Glen Ellyn Public Library By: Kami Farahmandpour, PE, RRC, RWC, CCS, CCCA Alex Szatanek Outline 2010 and 2011 Roof Replacement and Facade Repair Project Review Primary Reasons for
More informationbout your house before you start Renovating Your Basement Moisture Problems
A bout your house CE 28c before you start Renovating Your Basement Moisture Problems Mold and decay on floor joists and sill plates Stuffy air, high humidity, poor air circulation Water draining in from
More informationINSTALLATION INSPECTION GUIDE FOR 3RD PARTY INSPECTORS FOR PAREX USA EXTERIOR INSULATION AND FINISH SYSTEMS
INSTALLATION INSPECTION GUIDE FOR 3RD PARTY INSPECTORS FOR PAREX USA EXTERIOR INSULATION AND FINISH SYSTEMS Introduction This inspection guide is organized to follow the EIF System's Installation Guide.
More informationClaim No.: DOCUMENT TYPE: INVEST ENGINEERING REPORT Date of Loss: October 29, 2012. 384 Ocean Avenue Long Branch, NJ
January 9, 2013 Mr. Richard Swink National General Adjuster York SLA 5501 LBJ Freeway, Suite 375 Dallas, Texas 75240 Email: rswink@swinkinsurance.com Tel: 214/673-4148 (M) RE: Claim No.: TBD DOCUMENT TYPE:
More informationCHAPTER 7: Building Systems ROOFING SYSTEMS
ROOFING SYSTEMS Purpose Examples 1. Shingle roof system 2. Metal roof with blanket insulation 3. Metal roof with rigid insulation 4. Built-up asphalt roof system 5. Single-ply roof system 6. Modified Bitumen
More informationCrescent Valley High School Roof Investigation
Crescent Valley High School Roof Investigation Project: Corvallis School District Crescent Valley High School Roof Date: July 26, 2011 Report By: Rowell Brokaw Architects: Mark Young, AIA, Chris Andrejko
More informationThermographic Inspection of Building and Roof Water Intrusion in the State of Florida
Thermographic Inspection of Building and Roof Water Intrusion in the State of Florida By: James Brady Level III Certified Infrared Thermographer Brady Infrared Inspections, Inc. 935 Pine Castle Court Stuart,
More informationWarranty Information TABLE OF CONTENTS PROCEDURES FOR WARRANTY 2
Warranty Information TABLE OF CONTENTS PROCEDURES FOR WARRANTY 2 PROTECTING YOUR DURO-LAST ROOFING 3 Safety Measures 3 Inspection 3 Maintenance Program 4 Sealants 4 Drainage 4 Parapets Walls 4 Building
More informationWalls. Add Strength and Water Resistance When Repairing Your. Replace damaged framing members when walls are open
Add Strength and Water Resistance When Repairing Your Walls Any home repair or remodeling work you do presents an opportunity to make your home fare better in the next storm. Whether you are just replacing
More informationPELHAM MEMORIAL HIGH SCHOOL STONE FAÇADE REPORT. November 2007
PELHAM MEMORIAL HIGH SCHOOL STONE FAÇADE REPORT November 2007 PURPOSE OF INVESTIGATION Determine possible locations of moisture intrusion into and through facade. Determine cause of horizontal and vertical
More information