SECTION 3 ONM & J STRUCTURAL ANALYSIS
|
|
|
- Kathleen Houston
- 10 years ago
- Views:
Transcription
1 Historic Boynton Beach High School Existing Building Assessment City of Boynton Beach February 10, 2011 SECTION 3 ONM & J STRUCTURAL ANALYSIS
2 STRUCTURAL ENGINEERS SPECIAL INSPECTORS STRUCTURAL CONDITION ASSESSMENT & STRUCTURAL FEASIBILITY STUDY OLD BOYNTON BEACH HIGH SCHOOL Boynton Beach, Florida Project No.: February 7, LA Kirksey Street Suite 200 West Palm Beach, FL Phone: (561) Fax (561)
3 TABLE OF CONTENTS Page Number I. Scope 1 II. Project Description 2 III. Executive Summary 3 4 IV. General Observations 5 8 A. Exterior 1. North Elevation 2. East Elevation 3. South Elevation 4. West Elevation 5. Roof B. Interior 1. Roof Framing 2. Second Floor Framing 3. Ground Floor Framing 4. Exterior / Interior Bearing Walls 5. Foundation V. Feasibility Study 9 12 A. Codes and Standards B. Design Loads C. Foundation System D. Wall Framing System 1. Exterior 2. Interior E. Floor Framing System 1. Ground / Second Floor Classroom Wing 2. Second Floor Auditorium / Gymnasium Wing F. Roof Framing System 1. Classroom Wing 2. Auditorium / Gymnasium Wing VI. General Notes 13 VII. Exhibits A. Photographs B. Typical Reinforcement Details C. Photo Key Plan
4 SCOPE Pursuant to your request, we performed a visual site visit review and a cursory design analysis on the Old Boynton Beach High School located on Ocean Avenue, Boynton Beach, Florida. The purpose of the investigation was to perform a Structural Condition Assessment of the two-story building and to provide a schematic narrative out-lining the general structural improvements (exterior walls, roof / floor framing systems, foundations, etc. to resist gravity / wind loads) required for the current Florida Building Code. The inspection methods used to formulate our conclusions were based on a visual review of the exterior / interior of the building. In addition, a cursory design analysis was performed to determine what general repairs / modifications will be required to bring the overall structure up to current code (The Florida Building Code, 2007 Edition) for gravity / wind loads. This cursory design analysis will provide us with additional information to make a determination as to the feasibility of upgrading the existing building structure. The cursory design analysis used to formulate our conclusions was based on a plan review of the original building drawings, dated July 15, 1927 and information provided by REG Architects, Inc. Various areas of the exterior / interior were available to expose the framing of the roof / floor structure. No destructive testing of materials / components was undertaken. Our evaluation is based only on visual examination of the areas, which were opened on the date of our visits. 1
5 PROJECT DESCRIPTION The building consists of a two-story terracotta / wood frame structure of approximately 28,500 square feet designed as a high school in a Mediterranean revival style. The facility was originally constructed in the late 1920 s. The exterior envelope of the building consists of painted textured stucco cladding, cast stone trim, arches, aluminum / glass windows and two main entries on the South (front) elevation. The roof is clad with a built-up roofing membrane system with sections of barrel tile roofing in the mansard areas. The structural roof framing system in the classroom wing consists of stick built wood trusses, wood rafters, wood plank sheathing and a built-up membrane roof cladding system. In the auditorium / gymnasium wing the structural roof framing system consists of structural steel riveted bow trusses, heavy timber purlins with wood plank sheathing. Steel I beams, wood rafters and wood plank decking are present over the stage area of the auditorium / gymnasium. The classroom wing second floor structural framing system consists of wood floor beams, diagonal wood plank sheathing and finished tongue and groove hard wood flooring. The structural floor system in the auditorium / gymnasium wing consists of concrete slab / joist system supported on concrete beams and columns. The ground floor consists of a 4 reinforced concrete slab-on-grade with some sections framed with wood floor beams, diagonal wood plank sheathing supported on reinforced concrete foundation walls. The foundation system of the building consists of reinforced concrete walls, continuous and isolated spread footings. The building is equipped with sanitary sewer, storm water drainage, domestic water, electrical and phone services. Parking is provided on the West and North elevations of the building. 2
6 EXECUTIVE SUMMARY The Old Boynton Beach High School building is in fair structural condition, albeit, having areas of noted deterioration / damage requiring repair and / or replacement. The building envelope walls, consisting of painted light-textured stucco cladding on hollow terracotta tile masonry, aluminum / single-glazed glass windows, were observed to be in fair condition with no structural deficiencies apparent. The painted stucco cladding was also noted to be flaking. The roof cladding (consisting of a built-up membrane system and a clay tile barrel roof system in the mansard areas) was not observed during our site visit. We recommend that a roofing specialist be consulted to review in detail the condition of the roof claddings. The structural roof framing system in the classroom wing of the building, consisting of stick built wood trusses, wood roof rafters, wood plank sheathing, supported on the terracotta tile masonry / wood-framed stud bearing walls, was observed to be in good condition with some isolated areas of damage / deterioration from severe, long-term water / moisture intrusion and exposure. These isolated areas of damage / deterioration will require repair, removal and / or replacement. In the auditorium / gymnasium wing of the building, the roof framing system, consisting of structural steel riveted bow trusses, heavy timber purlins and wood plank sheathing, was noted to be in good condition with no apparent structural defects observed. Steel I beams, wood rafters and wood plank decking over the stage area of the auditorium / gymnasium require further investigation due to being inaccessible. The classroom wing, second floor framing system, consisting of wood floor beams, diagonal wood plank floor deck and finished tongue and groove hardwood flooring, was observed to be in good condition with no structural defects apparent, albeit, in the isolated observed areas of long-term water / moisture damage / deterioration / rot. These isolated areas of structural damage / deterioration will require removal, repair and / or replacement. The ground floor structural framing system in the auditorium / gymnasium wing, consisting of a reinforced concrete slab / joist system was observed to be in good condition with no structural defects apparent. The framed portion of the ground floor in the classroom wing, consisting of wood floor joists, diagonal wood plank floor sheathing, was observed to be in good condition where 3
7 accessible. Further investigation of the framed portions of the ground floor is recommended, which was not accessible during the site visits. If the building is to be used for future occupancy, structural repairs will be required as follows: Damage to the exterior terracotta wall. Open joints / cracks in the exterior cast stone trim band. Water damage to the classroom wing wood roof framing. Water damage to the wood 2 nd floor framing. Water damage / cracks to the interior plaster / wood lath on the exterior / interior terracotta / wood-framed walls. The cursory design investigation revealed that the building structure will require repairs / replacements and modifications for upgrading the structure to the current building code (2007 Edition). These upgrades are as follows: Reinforcement to the exterior terracotta wall panels. Reinforcement to all door and window openings (jamb / sills). Connections between the bearing ends of all wood joist / truss and terracotta walls on the roof / floor levels. Additional fasteners to the roof wood planks. In addition, the building will also require architectural and M.E.P. repairs / improvements per the requirements of this current code. All windows / doors / louvers, etc. will also require replacement to comply with the current code. 4
8 GENERAL OBSERVATIONS A. Exterior 1. North Elevation (exhibit 12). a. The painted stucco cladding of the exterior wall was noted to be in good condition with no cracks / deficiencies observed. Flaking / peeling paint is present throughout the entire North exterior elevation. b. The aluminum single-glazed glass windows were in fair / poor condition reflecting the results of age with some broken glazing apparent. c. The louvers above the lower level windows were observed to be in poor condition. d. The two exterior doors of the elevation were noted to be in poor condition. 2. East Elevation containing exit door from the auditorium / gymnasium wing (exhibits 8 11). a. The exterior paint on the stucco cladding was noted to be in poor condition with extensive peeling / flaking of the paint observed. b. The textured stucco cladding was in good condition with no cracking or deterioration observed. c. The cast stone bands / window sills were observed to be in good condition with no defects noted. Roof overflow pipes present on the South section of the elevation. d. The single-glazed glass / aluminum windows were in fair / poor condition due to aging with some glazing missing / boarded-up (exhibits 9, 10). e. The painted metal facia at the auditorium / gymnasium section of the elevation was noted to be in good condition with the exception of some minor damages observed at the Northeast corner. f. Doors and some lower level windows at the North end of the elevation were boarded up. The protective boarding was observed to be deteriorating. g. Damage to the stucco cladding and terracotta block wall was observed at the Southeast corner of the elevation. We were advised that his damage may have been the result of a lightning strike some time ago (exhibit 7). 3. South Elevation building front containing the building entrances (West and East) (exhibits 1 6). 5
9 a. The painted stucco cladding on the exterior terracotta masonry walls was observed to be in good condition with a few minor stucco cracks apparent. The painting in some areas was observed to be flaking / peeling. b. The aluminum / single-glazed glass windows were observed to be in fair to poor condition with the results of aging evident. c. The cast stone trim at the window sills and the arch window columns was observed to be in good condition with no structural defects apparent. d. The East and West entrances with the stucco clad columns and cast stone trim were noted to be in good to fair condition with some minor cracking observed. The exterior jambs (exhibit 5) were in poor condition, deteriorated / rotted. Entry doors were in poor condition and partially boarded up. e. The concrete entry platforms / steps were noted to be in fair condition, worn from aging, with no structural cracks / defects observed. 4. West Elevation containing the exit from the auditorium / gymnasium wing (exhibits 13 19). a. The stucco cladding on the exterior terracotta masonry walls of this elevation was observed to be in good overall condition with some minor cracking noted in a few isolated areas (exhibits 13, 15, 16). The painted surface was noted to be peeling / flaking in many areas throughout the entire West elevation. b. The cast stone trim band, cast stone sills and column trim at the arch window areas of the elevation were observed to be in fair condition with some opening of the joints noted (exhibits 14, 15). c. The wood-framed / single-glazed windows observed in the arch window area (North section of the elevation) were observed to be in poor condition. The aluminum frame single-glazed arched windows occurring at the South portion of the elevation were noted to be in fair condition (exhibit 17). d. The aluminum frame / single-glazed windows throughout the remaining overall West elevation were observed to be in poor condition, many with boarded-up glazed panes (exhibit 13). e. The exit doors observed on this elevation were in poor condition with signs of age and deterioration (exhibit 13). 5. Roof investigation of the roof cladding is not included in this report. 6
10 B. Interior 1. Roof Framing a. Auditorium / gymnasium wing (exhibits 24, 30, 32, 33): The structural roof framing system, consisting of riveted steel bow -type long span trusses, heavy timber purlins and wood plank decking, was observed to be in good condition with no structural defects apparent. Structural steel I beams with wood rafters and wood decking were observed to be in good condition with no visual structural defects noted and are present over the stage area of the auditorium / gymnasium. b. Classroom wing (exhibits 29, 34 39): The roof framing structural system, consisting of wood roof rafters stick framed wood trusses and wood plank roof decking, observed to be in good condition with no structural deficiencies apparent, albeit, in the observed isolated areas of severe water / moisture damage and long-term deterioration (exhibit 29). 2. Second Floor Framing (exhibits 22, 27): The structural framing system of the second floor classroom wing, consisting of wood floor beams, diagonal wood plank floor decking and finished hardwood tongue and groove flooring, observed to be in generally good structural condition with no apparent structural defects observed, except in the few isolated areas of severe long-term water / moisture damage (exhibit 40). It is to be noted that additional areas of damage to the finished hardwood flooring were noted in numerous areas of the classroom wing. 3. Ground Floor Framing (exhibits 20, 21): The ground floor framed area under the auditorium / gymnasium floor, consisting of a reinforced concrete slab / joist system with reinforced concrete beams and columns, was noted to be in good condition with no structural defects observed. The ground floor framing system located under a portion of the classroom wing, consisting of wood floor joists, diagonal wood plank decking with finished hardwood tongue and groove flooring, was observed in limited areas to be in good condition with no structural defects apparent (exhibit 20). 4. Exterior / Interior Bearing Walls (exhibits 25, 26, 31, 35, 36). a. The exterior bearing walls of the building consist of cement plaster, wood lath on stucco clad terracotta clay masonry units in running bond. The condition of the terracotta masonry units was observed to be in good condition with no structural deficiencies apparent. The interior plaster was observed to be cracked and moisture damaged. Wood lath was observed to be in fair to good condition, except in areas of moisture damage. 7
11 b. The interior bearing walls (exhibits 25, 37, 39), consisting of cement plaster, wood lath on terracotta clay masonry units or cement plaster on wood lath and wood stud partitions, were noted to be in good overall condition with some areas of isolated damage observed. Water / moisture damage was observed on the plaster surfaces in various areas throughout the building. 5. Foundation A review of the original construction documents indicates that the foundation of the building consists of a 4 reinforced concrete slab-on-grade, reinforced concrete walls, continuous footings and spread footings. Field observations of the foundation system were not performed due to being inaccessible. 8
12 FEASIBILITY STUDY A. Codes and Standards Florida Building Code, 2007 Edition with 2009 Supplements Design wind speed is 140 mph, exposure C, Importance Factor is 1.15 Existing Reinforcing Steel Fy = 18 ksi Structural Steel Fy = 24 ksi B. Design Loads Wind loads per ASCE 7-05 Roof live loads 20 PSF Floor live loads 50 PSF classrooms, 100 PSF corridors, 80 PSF auditorium / gymnasium. C. Foundation System 1. The original drawings indicate that the foundation system consists of isolated and continuous spread footings. 2. The existing footings were not accessible in the field of our review. The original drawings do indicate footing sizes and rebar. The isolated spread footings for the interior columns with rebar are shown in footing schedule. 3. No information on the allowable soil bearing pressure was indicated on the contract drawings available for our review. For our preliminary analysis, we are using 3,000 PSF as a safe soil bearing pressure. Our design analysis indicated that the existing isolated spread footing is structurally adequate to support the required gravity loads. 4. The existing continuous footings at the interior demising walls and exterior building perimeter walls are specified on the original drawings. The perimeter walls and some interior walls will be utilized as shearwalls (to resist hurricane wind loads per the current code). 5. These footings are sufficient to resist the gravity / hurricane wind loads per the current code. D. Wall Framing System 1. Exterior: a. Ground Floor Description: 12 stucco clad terracotta block unreinforced walls present on all elevations. 9
13 Comments: a.1: 12 terracotta block masonry unreinforced wall panels are not adequate to resist the present Florida Building Code wind loads. a.2: The walls are adequate to support the proposed superimposed gravity loads. a.3 The existing windows / doors / jambs / sills are in poor condition, not adequate to resist current Florida Building Code wind loads. Repairs: a.1 See repair details, Exterior Wall Reinforcement. a.2: None. a.3: Remove and replace with new doors / windows conforming to the present Florida Wind Code. In addition, the window / door jambs, head and sills must be reinforced to properly support the windows / doors (see Typical Window / Door Reinforcement Detail). b. Second Floor Description: 8 stucco clad terracotta block unreinforced walls present on all elevations. Comments: b.1: 8 terracotta block unreinforced wall panels are not adequate to resist the present Florida Building Code wind loads. b.2: The walls are adequate to support the proposed superimposed gravity loads. b.3: The existing windows / doors / jambs / sills are in poor condition, not adequate to resist current Florida Building Code wind loads. Repairs: b.1: See repair details, Exterior Wall Reinforcement. b.2: None. b.3: Remove and replace with new doors / windows conforming to the present Florida Wind Code. In addition, the window / door jambs, head and sills must be reinforced to properly support the windows / doors (see Typical Window / Door Reinforcement Detail). 2. Interior (Bearing Walls) Ground Floor & Second Floor: Description: 8 plaster clad terracotta block unreinforced walls. Comments: 1: 8 plaster clad terracotta masonry walls are adequate to resist gravity loads. 10
14 2: Wood joists have no connection to the exterior / interior terracotta walls for proper floor diaphragm and lateral bracing. Repair: 1. None. 2. See repair details Typical Hurricane Tie-Down Details. E. Floor Framing System 1. Ground / Second Floor Classroom Wing Description: 3 x12 / 2 x12 wood floor joists at 16 on center with 1 x6 diagonal wood plank decking. Comments: The existing 3 x12 / 2 x12 wood floor joists at 16 on center with 1 x6 diagonal wood plank decking is sufficient for the present gravity loading in the areas where there is no damage. Wood joists have no connection to the exterior / interior terracotta walls for proper floor diaphragm and lateral bracing Repair: All floor-framing in areas of damage are to be repaired as shown / noted in the floor joist repair details (see Wood Framing Repair Detail ). For joist bearing connections, see Typical Hurricane Tie- Down Details. 2. Second Floor Auditorium / Gymnasium Wing Description: Reinforced concrete / joist system with reinforced concrete beams / columns. Drawings do not indicate any reinforcing. Comments: Auditorium / gymnasium wing floor framing system is sufficient to support the present gravity loading using minimum reinforcing steel requirement. Repair: See Typical Concrete Repair Details for repair of minor spalls, cracks, exposed rebar. F. Roof Framing System 1. Classroom Wing Description: 3 x12 / 2 x12 wood rafters at 16 on center with 1 x6 wood plank decking and 2 x8 stick wood trusses at 16 on center with 1 x6 wood plank decking. Comments: The roof framing is sufficient to support the present gravity loads. Tie downs / straps for resisting wind uplift / lateral loads are not present. The 1 x6 wood planks will also require additional fasteners to resist wind uplift loads. 11
15 Repairs: Hurricane wind tie-down straps / tie-downs are required to resist the uplift / lateral wind loads of the present Florida Building Code (see Typical Hurricane Tie-Down Details ). 2. Auditorium / Gymnasium Wing Description: Structural steel riveted bow trusses, heavy timber roof purlins, with wood plank decking. Steel I beams with wood rafters and wood plank decking over the stage area. Design information was not found on the roof steel / wood framing over the stage area; this area was also inaccessible. Comments: Auditorium / gymnasium roof framing is sufficient to support the present gravity loading. No tie-downs /straps to resist wind uplift loading are present. Repairs: Hurricane wind tie-down straps are required to resist the uplift wind loads of the present Florida Building Code (see Hurricane Tie- Down Details ). 12
16 GENERAL NOTES The information is this report is based on information transmitted by your office. We were commissioned to make a limited visual review of the structure and provide general methods of repair. This report is based upon clearly, visible, open and unobstructed areas of the premises on the date of our site visits. No opinion is rendered with regard to structural elements, which are concealed. Our report attempts to establish the areas and the amount of repair that is necessary. This limited review does not guarantee the structural integrity of the premises under its current use nor any proposed alterations. If you have any questions, please feel free to contact our office. O DONNELL, NACCARATO, MIGNOGNA & JACKSON, INC. Joseph F. Mincuzzi, P.E. Vice President John W. Dawson, BSCE Project Manager STATE OF FLORIDA Registered Professional Engineer No Registered Professional Special Inspector No Registered Building Inspector No. BN
17 PHOTOGRAPHS Exhibit 1 Exhibit 2
18 Exhibit 3 Exhibit 4
19 Exhibit 5 Exhibit 6
20 Exhibit 7 Exhibit 8
21 Exhibit 9 Exhibit 10
22 Exhibit 11 Exhibit 12
23 Exhibit 13 Exhibit 14
24 Exhibit 15 Exhibit 16
25 Exhibit 17 Exhibit 18
26 Exhibit 19 Exhibit 20
27 Exhibit 21 Exhibit 22
28 Exhibit 23 Exhibit 24
29 Exhibit 25 Exhibit 26
30 Exhibit 27 Exhibit 28
31 Exhibit 29 Exhibit 30
32 Exhibit 31 Exhibit 32
33 Exhibit 33 Exhibit 34
34 Exhibit 35 Exhibit 36
35 Exhibit 37 Exhibit 38
36 Exhibit 39 Exhibit 40
37
38
39
40
41
42
43
44
45
46
47
48
Page & Turnbull imagining change in historic environments through design, research, and technology
DCI+SDE STRUCTURAL EVALUATIONS OFFICE BUILDING, TOOL SHED & WATER TANK, AND BLACKSMITH & MACHINE SHOP BUILDINGS SAN FRANCISCO, CALIFORNIA [14290] PRIMARY PROJECT CONTACT: H. Ruth Todd, FAIA, AICP, LEED
Building Condition Assessment: 109-111 North Howard Street Baltimore, Maryland
KPA The Joint Venture of EBA Engineering, Inc. and Kennedy Porter & Associates, Inc. 4813 Seton Drive, Baltimore, MD 21215 Phone: (410-358-7171) Fax: (410)358-7213 Building Condition Assessment: Baltimore,
Building Condition Assessment: 215-219 West Lexington Street Baltimore, Maryland
KPA The Joint Venture of EBA Engineering, Inc. and Kennedy Porter & Associates, Inc. 4813 Seton Drive, Baltimore, MD 21215 Phone: (410-358-7171) Fax: (410)358-7213 Building Condition Assessment: Baltimore,
STRUCTURAL ASSESSMENT REPORT BOLINAS MARINE STATION - BOLINAS, CALIFORNIA
STRUCTURAL ASSESSMENT REPORT BOLINAS MARINE STATION - BOLINAS, CALIFORNIA College of Marin c/o Swinerton Management & Consulting P.O. Box 144003 835 College Avenue, Building MS-3 Kentfield, California
EAST LYME HIGH SCHOOL
Overview: 1971 N 1966 GYM 1966 CLASSROOM WING 1966 AUD. 1971 GYM 1998 1998 POOL EAST LYME HIGH SCHOOL Original 1966 Building: The original East Lyme High School was constructed in 1966 and was composed
14 September 2015. Sarah Zorn Planning and Economic Development 25 West Fourth Street, Ste. 1100 St. Paul, MN 55102
Sarah Zorn Planning and Economic Development 25 West Fourth Street, Ste. 1100 St. Paul, MN 55102 Project No.: 15538.00 Re: Structural Condition Review of the building at 700 4 th St. E. Dear Sarah: We
Mark Cramer Inspection Services, Inc.
Mark Cramer Inspection Services, Inc. 492 Twentieth Avenue, Indian Rocks Beach, FL 34635-2970 (727) 595-4211 Fax (727) 596-7583 Certified Member #12085 American Society of Home Inspectors Construction
PELHAM MEMORIAL HIGH SCHOOL STONE FAÇADE REPORT. November 2007
PELHAM MEMORIAL HIGH SCHOOL STONE FAÇADE REPORT November 2007 PURPOSE OF INVESTIGATION Determine possible locations of moisture intrusion into and through facade. Determine cause of horizontal and vertical
CLIENT. Inspection Report. 271 Front St. Alert Bay, B.C. Island Building Inspections V ANCOUVER I SLAND B. C.
CLIENT Inspection Report 271 Front St. Alert Bay, B.C. Island Building Inspections 2013 V ANCOUVER I SLAND B. C. Elevation Photos For the Property at 271 Front Street Alert Bay, BC ELEVATION PICTURES Front
STRUCTURAL ASSESSMENT
STRUCTURAL ASSESSMENT Project: 1432-1434 East Commerce St. Job. No: 122200 Location: San Antonio, TX Date: Dec. 10, 2012 Weather: Sunny, Windy,60 deg Performed by: Jeff Haughton and Frank Lamas, Alpha
A0 SHEET 1 OF 5 400 LOCUST STREET FRANKFORT, KANSAS 66427 FRANKFORT, KANSAS 66427 ROOF REPAIR OF THE 400 LOCUST STREET
POYNTZ AVENUE, STE 9 MANHATTAN, KS 0..0..9 FAX WEST th STREET JUNCTION CITY, KS.... FAX 0, Bruce McMillan AIA, Architects, P.A. HERITAGE TRUST FUND GRANT PROJECT NO. 0-0 ROOF REPAIR OF THE 00 LOCUST STREET
Building Condition Assessment Report
C2 - Nurses Resident (aka Administration) Building Condition Assessment Report Asset Address Address Construction Year Size (Gross Floor Area) Asset Type Floors Above Ground Inspection Date C2 - Nurses
Structural Assessment Report
Report Dallas Township Elementary School Dallas, Pennsylvania (JBCI Project No. 144911) 1655 Suburban Station Building 1617 John F. Kennedy Boulevard Philadelphia PA 19103 215 665 0497 5 Sandwood Drive
STRUCTURAL ASSESSMENT. Full Metal Jacket Building 0 Prince Street, Alexandria, VA
STRUCTURAL ASSESSMENT FOR Full Metal Jacket Building 0 Prince Street, Prepared by: ALPHA CORPORATION (Alpha) 1850 S. Loudoun Street, Suite 200 Winchester, VA 22601 540-723-0704 September 22, 2010 J. Michael
Building Condition Assessment Report
Building Condition Assessment Report Asset C3c - Oak Terrace Cottage 121 Address Riverview Lands, 2601 Lougheed Highway, Coquitlam, BC. V5C 4J2 Construction Year Size (Gross Floor Area) 1920. 2,553 Sq.Ft.
Prepared For San Francisco Community College District 33 Gough Street San Francisco, California 94103. Prepared By
Project Structural Conditions Survey and Seismic Vulnerability Assessment For SFCC Civic Center Campus 750 Eddy Street San Francisco, California 94109 Prepared For San Francisco Community College District
October 30, 2014. Mr. & Mrs. Daniel Vick 101 Southwind Cove Benton, AR. Report of Findings, Structural Investigation, Benton, Arkansas, Dear Mr.
117 S. Market St. Benton, AR 72015 * 501-315-2626 * Fax 501-315-0024 October 30, 2014 Mr. & Mrs. Daniel Vick 101 Southwind Cove Benton, AR Re: Report of Findings,, Benton, Arkansas, Dear Mr. Vick: This
201 WATER STREET FORWARDERS MUSEUM AND VISITORS INFORMATION CENTRE
STRUCTURAL INSPECTION REPORT DRAFT 201 WATER STREET FORWARDERS MUSEUM AND VISITORS INFORMATION CENTRE TOWN OF PRESCOTT Date: November 2013 GENIVAR No.: 131-20617-00 2611 Queensview Drive, Suite 300, Ottawa,
48. AQUARIUM. Aquarium. Classification: Cluster: Location: Close to junction of Inselrhue and Loiter Way, Belle Isle. Total Area: No.
Classification: Cluster: Location: Total Area: No. of Stories Aquarium Acreage Owned: Acquired: 1904 Most Recent Improvements: THE AQUARIUM Close to junction of Inselrhue and Loiter Way, Belle Isle Two
Vision Home Inspection
Vision Home Inspection 324 Rams Run Shepherdsville KY 40165-7877 Inspector: James McFadden Property Inspection Report Client(s): Property address: Inspection date: View report summary This report is the
CZAR Engineering, L.L.C.
CZAR Engineering, L.L.C. Lamont H. Czar, P.E. Phone: (609) 653-9445 5014 Fernwood Avenue Fax:(609)653-2015 Egg Harbor Township, New Jersey 08234 www.czarengineering.com May 3, 2013 Craig Dothe, Architect
Photos showing the change in condition from 2006 to 2012 are located in Appendix A.
January 27, 2012 Ms. Theresa Gallavan Economic Development Director City of Lompoc 100 Civic Center Plaza Lompoc, California 93436 RE: Lompoc Theater Limited Visual Condition Assessment Dear Theresa: Representatives
17,280 square feet Overview:
CENTRAL OFFICE Located at 167 Boston Post Road, East Lyme, Connecticut, the Central Office was built in 1916 as the original Flanders Elementary School and remains connected to the current school. The
POST AND FRAME STRUCTURES (Pole Barns)
POST AND FRAME STRUCTURES (Pole Barns) Post and frame structures. The following requirements serve as minimum standards for post and frame structures within all of the following structural limitations:
SODA SPRINGS JOINT SCHOOL DISTRICT NO. 150 RECOMMENDED REPAIRS, REPLACEMENT, AND ADDITIONS OPINIONS OF PROBABLE COST
SODA SPRINGS JOINT SCHOOL DISTRICT NO. 150 RECOMMENDED REPAIRS, REPLACEMENT, AND ADDITIONS OPINIONS OF PROBABLE COST SODA SPRINGS HIGH SCHOOL REPAIRS AND UPGRADES SITE Construction Estimate = $100,000
Memorandum. July 16, 2008. To: Plan Commission City of Madison
Memorandum July 16, 2008 To: Plan Commission City of Madison From: Marc Schellpfeffer Engberg Anderson Re: Structural/Architectural Assessment of Homes for Proposed Demolition Findorff Yards Office Lofts
PRESERVATION PLANNING ASSOCIATES 519 Fig Avenue, Santa Barbara, CA 93101 Telephone (805) 450-6658 Email: [email protected]
PRESERVATION PLANNING ASSOCIATES 519 Fig Avenue, Santa Barbara, CA 93101 Telephone (805) 450-6658 Email: [email protected] June 17, 2015 Ms. Kimberley Heaton McCarthy Supervising Planner Building and Safety
Engineers, Civil Structural Survey
Engineers, Civil Structural Survey 317 STREET 0 6 3 6 0 886-1966 886-9165 FAX. September 1 1 Mr. Alan Bergren City Manager City of Norwich Broadway, Floor Norwich, 06360 Re: Limited Structural Condition
HEDDERMAN ENGINEERING, INC. www.heddermanengineering.com Office 281-355-9911, Fax 281-355-9903 [email protected]
HEDDERMAN ENGINEERING, INC. www.heddermanengineering.com Office 281-355-9911, Fax 281-355-9903 [email protected], 2011 TO: Mr. REF: CONDITION OF PROPERTY SURVEY Dear Mr. : At your request,
D Sample Notices to Property Owners, Sample Affidavits, and Other Material
D Sample Notices to Property Owners, Sample Affidavits, and Other Material These samples are offered to illustrate specific points in the Desk Reference. States and communities should examine them carefully
Inspecting to a higher standard.
Inspecting to a higher standard. Rob Hopkin Silver Spring, MD 20902 Monday, June 2, 2014 ProTec Inspection Services Inc. 19736 Selby Ave Poolesville, MD 20837 301-972-8531 www.protec-inspections.com [email protected]
TAX APPRAISAL DISTRICT OF BELL COUNTY STORES & COMMERCIAL IMPROVEMENT CLASSIFICATION GUIDE
TAX APPRAISAL DISTRICT OF BELL COUNTY STORES & COMMERCIAL IMPROVEMENT CLASSIFICATION GUIDE 1/22/2008 1 STORES & COMMERCIAL BUILDINGS 1. General Construction Class Descriptions 2. Types a. Class A - Fireproofed
CITIZENS PROPERTY INSURANCE CORPORATION. STREET ADDRESS: 14300 Gulf Blvd, Maderia Beach, FL 33708 6 Six story masonry residence
CITIZENS PROPERTY INSURANCE CORPORATION BUILDING TYPE II AND III MITIGATION VERIFICATION AFFIDAVIT This affidavit must be completed to capture mitigation features applicable to a Type II (4 to 6 story)
SCHEMATIC AND PROJECT BUDGET APPROVAL EAST CAMPUS NURSING EDUCATION AND CLASSROOM
Shepherd University Board of Governors June 9, 2005 Agenda Item No. 9 SCHEMATIC AND PROJECT BUDGET APPROVAL EAST CAMPUS NURSING EDUCATION AND CLASSROOM In 1994 construction began on the Byrd Science and
Project Report. Structural Investigations Hotel del Sol Yuma, Arizona
Project Report Structural Investigations Yuma, Arizona Prepared by: 2619 Spruce Street Boulder, CO 80302 303-444-3620 Prepared for: Principle Engineering Group, Inc. 833 East Plaza Circle, Suite 100 Yuma,
Facility Assessment for. 11801 East Main Street, Huntley, IL
Facility Assessment for 11801 East Main Street, Huntley, IL July 12, 2012 Prepared by: Dewberry Architects Inc. 25 S. Grove Avenue, Suite 500 Elgin, IL 60120 (847) 695-5840 The Village of Huntley requested
MEMORANDUM. General: Foundation:
MEMORANDUM State of Alaska Department of Transportation and Public Facilities Central Region - Division of Construction and Operations Public Facilities Branch TO: Jennifer Murrel DATE: August 19, 2010
Historic Preservation Certification Application Part 2 343-345 Main Street West South Haven, Vermont NPS Project No. 12345
Exterior Features 1 site and drainage 2 foundation 3 wood siding and trim 4 exterior doors 5 windows / storm windows 6 porches front and rear 7 chimneys 8 roofing Interior Features 9 frame 10 basement
Certification: Building Plans Examiner. Exam ID: B3
Certification: Building Plans Examiner Exam ID: B3 Scope: A Building Plans Examiner will be responsible for reviewing submitted plans to determine if they meet the requirements of the various Building
Expected Performance Rating System
Expected Performance Rating System In researching seismic rating systems to determine how to best classify the facilities within the Portland Public School system, we searched out what was used by other
HURRICANE MITIGATION RETROFITS FOR EXISTING SITE-BUILT SINGLE FAMILY RESIDENTIAL STRUCTURES
HURRICANE MITIGATION RETROFITS FOR EXISTING SITE-BUILT SINGLE FAMILY RESIDENTIAL STRUCTURES 101 Retrofits Required. Pursuant to Section 553.844 553.884, Florida Statutes, strengthening of existing site-built,
HOOVER TREATED WOOD PRODUCTS, INC. TECHNICAL NOTE FOR ADDITIONAL INFORMATION: 1-800-TEC-WOOD (832-9663)
HOOVER TREATED WOOD PRODUCTS, INC. TECHNICAL NOTE FOR ADDITIONAL INFORMATION: 1-800-TEC-WOOD (832-9663) Fire-Retardant-Treated Wood Framed Wall Assemblies GENERAL INFORMATION Fire-resistant construction
CHAPTER 6 CONSTRUCTION TYPES
CHAPTER 6 CONSTRUCTION TYPES SECTION 601 GENERAL 601.1 Scope. Provisions of this chapter shall govern the classification of construction type by materials and fire resistance of its elements and the use
COMMONLY USED RESIDENTIAL BUILDING CODES
COMMONLY USED RESIDENTIAL BUILDING CODES INTERNATIONAL RESIDENTIAL CODE (2009) form revised 5/10 FOUNDATION 1. DESIGN OF FORMWORK. Section 1906.1 IBC 2009, Section R404.1.2.3.6 IRC 2009, ACI 318 Section
www.citiesinspection.com October 5, 2015 Dear Client,
www.citiesinspection.com October 5, 2015 Dear Client, On 9/14/2015, Cities Inspection Service, Inc. completed a building inspection of the property located at 123 Oak Street, Someplace, Minnesota for you.
Foundation Experts, LLC Specializes in Foundation Repair and Waterproofing
1 Most basements show some signs of leaking and cracking. Through the years, problems with water, poor soils, grading, drainage and possible settling affect the integrity of a basement. Being able to recognize
ISO Types 1-6: Construction Code Descriptions
ISO 1 Frame (combustible walls and/or roof) Class 1B Buildings where the exterior walls are wood or other combustible materials, including construction where the combustible materials are combined with
Walls. Add Strength and Water Resistance When Repairing Your. Replace damaged framing members when walls are open
Add Strength and Water Resistance When Repairing Your Walls Any home repair or remodeling work you do presents an opportunity to make your home fare better in the next storm. Whether you are just replacing
STRUCTURAL CONCEPT FOR LIGHT GAUGE STEEL FRAME SYSTEM
Chapter 9 STRUCTURAL CONCEPT FOR LIGHT GAUGE STEEL FRAME SYSTEM 9.1 BACKGROUND Steel is widely used in the construction of multi-storey buildings. However, steel construction is seldom used and is traditionally
WEBSTER ELEMENTARY SCHOOL New Rochelle, New York Evaluation of Collapsed Ceiling Room 204
WEBSTER ELEMENTARY SCHOOL New Rochelle, New York Evaluation of Collapsed Ceiling Room 204 Structural Inspection Report Client: CSArch Architecture Engineering Construction Management 19 Front Street, Newburgh,
Building Construction. Structural Systems 1. Load-bearing wall construction 2. Skeleton framing 3. Combination of the two
Structural Systems 1. Load-bearing wall construction 2. Skeleton framing 3. Combination of the two Factors governing type selection Economics not necessarily the one that requires the least structural
Facility Summary. Facility Condition Summary. Seattle School District David T. Denny International Infrastructure. Facility Components
Infrastructure Facility Condition Summary Weighted Avg Condition Score Facility Components Systems Surveyor/ Date Done Comments G Sitework.9 Site Improvements Parking Pedestrian Paving Site Development
CONSERVATION MAINTENANCE WORKSHEET Universal Checklist
3.1 SITE 1 Concrete curbs Check for cracks, spalling, growth from joints X 2 Stone curbs Check for cracks, spalling, growth from joints X 3 Concrete walkways Look for uneven surfaces, ponding, growth from
Date: March 7, 2006 Report for [removed]
Date: March 7, 2006 Report for [removed] The Preservation Resource Center Of New Orleans, in conjunction the National Trust for Historic Preservation, has conducted a condition survey of your property.
Seattle Public Schools Building Excellence IV Projects Under Construction
Seattle Public Schools Building Excellence IV Projects Under Construction Project Slide Number Arbor Heights Elementary School 2 Cascadia Elementary School & Robert Eagle Staff Middle School 13 Genesee
4. ANCHOR BOLTS AND STRAPS a. ½" anchor bolts shall be embedded 7" into concrete a maximum of 6' on center and 12" from corners and ends of plates.
GENERAL CODE REQUIREMENTS (BASEMENTS) 1. FOOTINGS a. Footings shall be below frost line depth (42"). b. For an 8" foundation wall, footings shall be no less than 8" deep and 16" wide. c. Steel reinforcement
Claim No.: DOCUMENT TYPE: INVEST ENGINEERING REPORT Date of Loss: October 29, 2012. 384 Ocean Avenue Long Branch, NJ
January 9, 2013 Mr. Richard Swink National General Adjuster York SLA 5501 LBJ Freeway, Suite 375 Dallas, Texas 75240 Email: [email protected] Tel: 214/673-4148 (M) RE: Claim No.: TBD DOCUMENT TYPE:
How To Prevent Water Damage To A Home
Having inspected about 800 homes in the last four years, I have seen a lot of problems with many homes. Most of these problems are minor; however, there are some problems that are quite serious. One of
423 NORTH HOWARD ST. VISUAL STRUCTURAL ASSESSMENT
Urgent Needs II City of Baltimore No. 1099 423 NORTH HOWARD ST. 423 North Howard Street (circa 1880) is a multi-story building constructed second in row south of Franklin Street and between the vacant
Property Condition Assessment
Property Condition Assessment Business, Wisconsin Inspection Date: 8/2009 Prepared For: Business Owner Report Number: TD999909 Prepared By: Shamrock Building Inspection Consultants LLC N29 W29951 Shel-Mar
Roof Inspection. Summary Report
www.real-estate-inspections.com Roof Inspection Summary Report Subject Property Prepared for: File Number: Client in Detroit 05-15-RF-004 Inspector: Craig Milliken, PE # 32779 CPM Real Estate Inspections,
Inspection Item COMMENTS
APPENDIX 9 AFFORDABLE HOUSING PROGRAM INSPECTION CHECKLIST Participating Jurisdiction: Homeowner Name: Assisted Property Address: Date of Physical Inspection of Property: Total Square Footage of Property:
Exterior Elevated Elements Inspection Guidelines
Exterior Elevated Elements Inspection Guidelines Planning and Development 1. Guideline Purpose These guidelines are intended to assist practicing professionals in complying with Berkeley Municipal Code
Residential Inspection Guidelines
Residential Inspection Guidelines 201 Pre-Pour Foundation Dimensions Building Location Certificate - if required in the building consent Construction and Advice Notes Check the building dimensions against
Building Foundation and Structure
Building Foundation and Structure Overview The construction of the Hall of Waters building began in 1936, and was constructed over the original site of the Siloam and Sulpho-Saline Springs. The original
Residential Deck Safety, Construction, and Repair
Juneau Permit Center, 4 th Floor Marine View Center, (907)586-0770 This handout is designed to help you build your deck to comply with the 2006 International Residential Building code as modified by the
RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000
RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000 SECTION R905 REQUIREMENTS FOR ROOF COVERINGS R905.1 Roof covering application. Roof coverings
Foundation Evaluation Report for PROPERTY ADDRESS Houston, Texas 77089. August 30, 2012. Prepared for:
A Full Service Real Estate Inspection & Engineering Firm for Houston, Texas 77089 August 30, 2012 Prepared for: CLIENT S NAME MAILING ADDRESS Houston, Texas 77089 Prepared by: Charles J. Jenkins, P.E.
LAYING BLOCK AND BRICK
LAYING BLOCK AND BRICK Products highlighted in this section: SAKRETE Type N Mortar Mix SAKRETE Type S Mortar Mix Brick And Block Laying Basics The first step in building a brick or block wall is to construct
Reference: BRM-00220488-A0 July 18 th, 2014. Cursory Visual Review of Various Below Grade Spaces and Exposed Foundation Walls
Reference: BRM-00220488-A0 July 18 th, 2014 Toronto Catholic District School Board 80 Sheppard Avenue East Toronto, Ontario M2N 6E8 Re: 1.0 Introduction Exp Services Inc. (exp) was retained by the Toronto
Structural Failures Cost Lives and Time
Structural Failures Cost Lives and Time Recent failures of storage bins, silos and other structures highlight the need to increase awareness of hazards associated with these structures. Since 2010, one
Rehab Inspection Report Page 1
Rehab Inspection Report Page 1 Home Address: Construction Style: Number of bedrooms Square footage: Value of offer: Estimated rehab cost: Value of resale: Orientation of house: N S E W Note: orientation
Steve Brinkman Alain Pinel Realtors 167 S San Antonio Road Los Altos, CA 94022 RE: Foundation Inspection for 162 Del Monte Ave. Los Altos, CA 94022
M G C O N S T R U C T O R S & E N G I N E E R S, I N C. I N S P E C T O R S E N G I N E E R S B U I L D E R S C A L I F O R N I A E N G I N E E R I N G A N D B U I L D I N G L I C E N S E A / B 6 4 2 0
OSHA GUIDANCE DOCUMENT FALL PROTECTION IN RESIDENTIAL CONSTRUCTION
OSHA GUIDANCE DOCUMENT FALL PROTECTION IN RESIDENTIAL CONSTRUCTION OSHA GUIDANCE DOCUMENT FALL PROTECTION IN RESIDENTIAL CONSTRUCTION Table of Contents Executive Summary... 1 Introduction... 1 Installing
The Florida Building Code
The Florida Building Code Florida s Response to Hurricane Risk Rick Dixon Florida Building Commission Florida Building Commission Architect Structural Engineer Mechanical Engineer Fire Protection Engineer
Home Inspection Report
Home Inspection Report Report Number: 144 For The Property Located On: 123 Any Street 27587 Prepared For Exclusive Use By: Mr. Sample N/A,,, Report Prepared By: Edward Carapezza; License No.: 3447 Inspector
Repairs, Remodeling, Additions, and Retrofitting
Repairs, Remodeling, Additions, and Retrofitting HOME BUILDER S GUIDE TO COASTAL CONSTRUCTION FEMA 499/August 2005 Technical Fact Sheet No. 30 Purpose: To outline National Flood Insurance Program (NFIP)
6 RETROFITTING POST & PIER HOUSES
Retrofitting Post & Pier Houses 71 6 RETROFITTING POST & PIER HOUSES by James E. Russell, P.E. 72 Retrofitting Post & Pier Houses Retrofitting Post & Pier Houses 73 RETROFITTING POST AND PIER HOUSES This
llc ~X IIB,_j I 3 September 10, 2012 Red Carpet Inn 3955 W. Colonial Drive Orlando Florida 32808 Fire Damage Structural Assessment Gentlemen:
- llc ENG I NEERING FOR ARCH ITECTUR E Red Carpet Inn 3955 W. Colonial Drive Orlando Florida 32808 Re: Red Carpet Inn Fire Damage Structural Assessment Gentlemen: In accordance with your request, on September
Common Problems with Walls
Common Problems with Walls Common Problems with Walls There are problems and concerns that are shared by all walls and siding installations. In this article, we will learn about the following commonly
Report on Sanctuary/Chancel Crawl Space Inspection. St. John in The Wilderness, 2896 Old Lakeshore Road Bright s Grove. Project No.
Report on Sanctuary/Chancel Crawl Space Inspection St. John in The Wilderness, 2896 Old Lakeshore Road Bright s Grove Project No. E112056 1. Background St. John in the Wilderness (SJITW) is considering
What is Seismic Retrofitting?
What is Seismic Retrofitting? SEISMIC RETROFITTING A Seismic Retrofit provides existing structures with more resistance to seismic activity due to earthquakes. In buildings, this process typically includes
REQUIREMENTS FOR SUBMITTING PLANS FOR NEW CONSTRUCTION
RESIDENTIAL: REQUIREMENTS FOR SUBMITTING PLANS FOR NEW CONSTRUCTION 2 COMPLETE SETS OF PRINTS WITH ENGINEERS STAMP ON FOUNDATION PLAN INCLUDING ELECTRICAL, PLUMBING, ETC. SITE PLAN SHOWING HOUSE LOCATION
Melbourne balcony Assessments
Balcony Assessment Melbourne balcony Assessments Address: SAMPLE Date: Assessor: Luke O Neill Registered Builder DBL-C 31305 Assessment Guidelines This is an assessment of balcony and elements as presented
NCMA TEK CONCRETE MASONRY FOUNDATION WALL DETAILS. TEK 5-3A Details (2003)
NCMA TEK National Concrete Masonry Association an information series from the national authority on concrete masonry technology CONCRETE MASONRY FOUNDATION WALL DETAILS TEK 5-3A Details (2003) Keywords:
Timber Frame Construction
Timber Frame Construction Introduction Design and Detailing What is timber? Failure modes History of timber frame construction Forms of timber frame construction Live and dead loads Wind loads Roof construction
Block Lofts Condominiums
Block Lofts Condominiums Building Envelope Condition Assessment 747 Ralph McGill Boulevard Atlanta, Georgia Presented to: Block Lofts Condominium Home Owners Association C/o Heritage Property Management
March 14, 2007. Installation of Bay, Bow and Garden Windows
March 14, 2007 Re: Installation of Bay, Bow and Garden Windows Attached are the Atrium Companies, Inc recommendation for the installation of bay, bow and garden windows. These instructions were developed
PROFESSIONAL ENGINEERING INSPECTIONS, INC.
PROFESSIONAL ENGINEERING INSPECTIONS, INC. P. O. BOX 271492 HOUSTON, TEXAS 77277 Registered Engineering Firm #1503 http://www.profengineering.com (713) 664-1264 July 8, 2004 Mr. Simple Samson 2831 Octoberfest
Architectural Inspection Site Structures
0141 Freestanding Shelters Open air shelters not attached to the building. Bike rack shelter with bike racks: This 8'x30' structure is located on the north east side of the building on the wooded landscape
Leaky Homes Financial Assistance Package (FAP) Repair plan example
LEAKY HOMES FINANCIAL ASSISTANCE PACKAGE FACT SHEET Repair Plan Example - June 2014 Page 1 Leaky Homes Financial Assistance Package (FAP) Repair plan example Introduction This repair plan example is intended
SINGLE FAMILY RESIDENCE HURRICANE MITIGATION APPLICATION
SINGLE FAMILY RESIDENCE HURRICANE MITIGATION APPLICATION As of October 1, 2007, this mitigation form must be submitted as part of the roofing permit application package. Secondary water barrier (if applicable)
[TECHNICAL REPORT I:]
[Helios Plaza] Houston, Texas Structural Option Adviser: Dr. Linda Hanagan [TECHNICAL REPORT I:] Structural Concepts & Existing Conditions Table of Contents Executive Summary... 2 Introduction... 3 Structural
REQUEST FOR QUALIFICATIONS FROM FOUNDATION REPAIR CONTRACTORS BROOMFIELD DEPOT FOUNDATION REHABILITATION PROJECT
Project Description and Scope The City and County of Broomfield, Colorado (Broomfield) hereby solicits this Request for Qualifications (RFQ) to prequalify and shortlist up to five (5) foundation repair
Slavic Village Building Condition Review
Slavic Village Building Condition Review Slavic Village Development May 8, 2015 Page 1 EXECUTIVE SUMMARY City Architecture was commissioned by Slavic Village Development to review five existing facilities
29 Broadway- 14 th Fl Tel: 212.888.8334 New York NY 10006 Fax: 212.419.1939. Due Diligence Report. New York, New York
Due Diligence Report New York, New York Prepared for Mr. On February 8, 2010 P a g e 1 Table of Contents PAGE 3.. GENERAL INFORMATION PAGE 4 FILINGS PERMITS AND ENCUMBRANCES PAGE 6. CORE AND SHELL PAGE
BROWNSVILLE STRUCTURES STUDY. July 2012. Prepared by. LDA ARCHITECTS 33 Terminal Way, Suite 317 Pittsburgh, Pennsylvania 15219 1208
BROWNSVILLE STRUCTURES STUDY July 2012 Prepared by LDA ARCHITECTS 33 Terminal Way, Suite 317 Pittsburgh, Pennsylvania 15219 1208 TABLE OF CONTENTS I. SUMMARY OF BUILDING ANALYSIS.. 1 II. INDIVIDUAL BUILDING
Protecting Your Home from Wind Damage
Protecting Your Home from Wind Damage During severe thunderstorms or hurricanes, homes may be damaged or destroyed by high winds. Debris flying through the air can break windows and doors, allowing high
