The HVAC Process: Changing the Properties of Air

Size: px
Start display at page:

Download "The HVAC Process: Changing the Properties of Air"

Transcription

1 The HVAC Process: Changing the Properties of Air Alexander Delli Paoli, Jr. ABSTRACT This discussion addresses the physical properties of air and water vapor mixtures. The components of the heating, ventilation, and air conditioning (HVAC) process that alter the moisture content of air to achieve desired levels in the facility or manufacturing process being served are described. Topics discussed can be thought of as the wet side of HVAC. The wet side includes all aspects of removing and adding moisture to air along with removing water condensed out of the airstream from the air handler. This paper continues a previous discussion describing HVAC systems (1). This and future discussions will provide a working knowledge of the HVAC process. A future paper will address the dry side of HVAC, which includes filters, fans, ductwork, controls, and safety components in the system. INTRODUCTION Psychrometrics is the study of air and water vapor mixtures. It is important to understand this topic and how those properties influence and affect the environment being controlled. A psychrometric chart is a graphic representation of all the possible conditions of air/water vapor mixtures (see Figure 1). Most psych charts are limited to certain areas of the total mixture spectrum. Practical limitations result in the creation of unique psych charts for sea level and differing elevations as well as charts portraying low, normal, and high temperature ranges. It is evident when a chart is not of the proper temperature range. It is unfortunately too easy to use a chart of the wrong elevation. The consequences of this error can result in HVAC equipment components that are not suited for the application. The moisture content levels portrayed by the process cycle on a psychrometric chart translate to desired humidity ranges in the controlled environment. Low moisture content in air is desirable when the concern is control of microbial or mold growth. However, low moisture content is not favorable if static electricity is a concern. Low humidity can also accelerate evaporation of ambient moisture, which can be good or bad for different process environments. Moisture content can also be an important factor for personnel in an environment. High moisture content in air also has positives and negatives, although there are usually more negatives with high moisture content: people feel muggy, microbes and molds flourish, and paper products become soft and perform inadequately in high moisture environments. Positive aspects of high moisture levels include the absence of static electricity and lower evaporation rates of ambient moisture. An optimally higher moisture level also minimizes drying of mucous membranes and could promote a healthier environment. THE PROPERTIES OF AIR AND WATER VAPOR MIXTURES The following discussion is expressed in English units. International (SI) units could also be utilized. Familiarity with the topic is achieved regardless of the units used. This section refers to Figures 1-3 to define the significant parameters presented on the psychrometric chart. Dry-Bulb Temperature Dry-bulb temperature is located on the abscissa of the chart (Figure 1, DB, Point 1). This is the temperature that indicates the addition and subtraction of heat in air. There is no connection to moisture levels when ABOUT THE AUTHOR Alexander Delli Paoli Jr., P.E., is managing director of Engineered Strategic Visions, Inc., Libertyville, IL, USA. Engineered Strategic Visions is an engineering consulting firm specializing in project planning and For more Author information, go to management, manufacturing support, asset and energy management plus several other areas of expertise. gxpandjvt.com/bios[ Alex may be reached at alex@engineervisions.com and at gxpandjv t. com Journal of Validation Technology [SPRING 2012] 75

2 Figure 1: Reading the psychrometric chart. is an important factor toward getting an accurate reading. Impurities in the water change the evaporation rate and the evaporation temperature, delivering erroneous results. Dew-Point Temperature The dew-point temperature parameter (Figure 1, DP, Point 3) is located on the ordinate scale at the right side of the chart. Dew-point temperature is exactly as the name suggests. It is the temperature at which air becomes saturated with moisture at a specific dry-bulb temperature and begins to create dew. Dew is the result of moisture condensing to water and coming out of the air/ moisture mixture. If this condensation is sufficiently rapid, fog forms. Dew point always occurs along the edge of the wet-bulb temperature line (Figure 1, Point 2) at the left side of the chart. presenting dry-bulb temperature. The real-feel or wind-chill temperature reported by network weather people is dependent on wind intensity. A stronger wind will strip the human skin s boundary layer, allowing more heat removal from skin and clothing. Moisture can also play a part, but is usually a small factor if skin is substantially covered by dry clothing. Wet-Bulb Temperature The wet-bulb temperature scale (Figure 1, WB, Point 2) is located on the curved part of the chart running from lower left to upper right. The terms wet bulb and dry bulb have historical origins based on the way the readings were taken with the technology available at the time. Mercury-in-glass thermometers were the instruments of greatest accuracy. Two thermometers were mounted on a sling to be manually spun together by a person. The bulb of one of the thermometers was covered with a fitted sock. The sock was wetted with the purest water available, hence the description wet-bulb temperature. The sling assembly was then spun to cause evaporative cooling on the wetted sock, cooling the covered thermometer bulb, and thus, indicating wetbulb temperature. Once both wet-bulb and dry-bulb temperatures were known, the state of the air/moisture mixture was known. Using the purest water available Specific Volume The specific volume parameter is represented diagonally across the chart (Figure 1, Point 4) running diagonally from upper left to lower right. Specific volume is doubly significant because the reciprocal of the number is the density of the air/moisture content. It is amusing to note that while a pound of dry air is equal to a pound of wet air, a cubic foot of wet air is lighter than a cubic foot of dry air. Enthalpy This property of the air/moisture mixture (Figure 1, Point 5) runs roughly parallel to the wet-bulb temperature scale. Enthalpy is a measure of the heat content of the mixture. It is used to determine equipment capacities for processing the HVAC cycle. Relative Humidity Relative humidity is the most popular way of expressing the moisture content of air. Relative humidity (Figure 1, RH, Point 6) is plotted on the chart running diagonally from lower left to upper right. RH is calculated as a ratio of the partial pressure of the water vapor in the current sample of the air/water vapor mixture to the partial pressure of water vapor at saturation in the current sample. 76 Journal of Validation Technology [SPRING 2012] ivthome.com

3 A l e x a n d e r D e l l i Pa o l i, J r. Absolute Humidity and Vapor Pressure Absolute humidity is not shown on the chart. This parameter is used to determine the actual amount of water that must be added or removed for sizing of HVAC processing equipment. The scale is typically located on a second ordinate scale on the right side of the chart. It is the ratio of the actual mass of water vapor in a sample to the mass of dry air in that same sample. Vapor pressure and other measures specific to the HVAC industry are also available on the chart, but these are of lesser value to understanding the HVAC process cycle. Figure 2: HVAC process cycle warm climate. CASE STUDIES The following case studies describe representative HVAC process cycles at different extremes (see Figures 2 and 3). Case Study One Warm Climate Case study one describes a facility in a warm and humid climate (see Figure 2). The key operating parameters are as follows: Desired process operating conditions: dry bulb temperature: 72ºF relative humidity: 50% RH Ambient (outside) conditions: dry bulb temperature: 100ºF wet bulb temperature: 80 F relative humidity: 45% RH. Note that the ambient relative humidity starts to lose relevance for most people at higher temperatures, so the wet-bulb temperature is provided. The wet-bulb temperature or absolute humidity readings are important for design engineers. The HVAC process cycle on the psychrometric chart will start at the desired operating point (Figure 2, Point 1) in the facility. This is the point representing 72 F/50% RH. Air from the facility is returned via ductwork to the air handler (Figure 4) where it is mixed with outside air at the conditions of Point 2. The two airstreams mix to conditions at Point 3. The total air then passes on to the cooling coils where conditions change from Point 3 to Point 4. At Point 4 within the cooling coil, the air/moisture mixture reaches its dew-point temperature. Moisture begins condensing and continues until the air reaches the temperature at Point 5. The air then leaves the cooling coil and is heated by the air handler or by heating coils in the ductwork to the temperature at Point 6. This additional heating is necessary because the air was cooled below the temperature needed to maintain facility equilibrium. This sub-cooling was necessary to achieve the desired moisture content offered at Point 5. The air then moves on into the controlled facility at Point 1 where it acquires heat being generated within the facility to maintain the desired environmental conditions. This completes the HVAC process cycle. Case Study Two Cool Climate This case study describes a facility in a cooler climate (see Figure 3) operating at the same process operating conditions as the facility in case study one. Comparison of Figure 2 to Figure 3 offers a clear graphic indication of the extremes to which the HVAC process equipment must perform to maintain the desired facility control conditions. The examples portray potential seasonal variations to the HVAC process cycle of a facility located in the Northern Hemisphere. Key operating parameters are as follows: desired process operating conditions: dry bulb temperature: 72 F relative humidity: 50% RH gxpandjv t. com Journal of Validation Technology [SPRING 2012] 77

4 Figure 3: HVAC process cycle cool climate. Outside air taken in: 50% of total volume being circulated by the air handler Ambient (outside) conditions: dry bulb temperature: 34 F relative humidity: 80% RH. The HVAC process cycle on the chart will again start at the desired operating point (Figure 3, Point 1) in the facility. This is the point representing 72 F /50% RH. Air from the facility is returned via ductwork to the air handler (see Figure 4) where it is eventually mixes with air coming from the outside. Notice in this example the mixing occurs only after the outside air at the conditions of Point 2 is heated through the preheat coil in the air handler to a safe temperature at Point 3 that will not expose the other components in the air handler to a freezing hazard. The two airstreams of equal volume then mix to conditions at Point 4. The total air has not been sub-cooled in this example, but it is cooler than is necessary to maintain the facility environmental conditions. The total air passes through a heating coil in the air handler where it is heated to a temperature at Point 5 appropriate to still remove the heat being generated in the controlled environment. Also note that the absolute humidity is increasing between Point 5 and Point 1. This suggests that humidification is occuring to prevent the air from becoming too dry for process conditions. The air then moves on into the controlled facility at Point 1 to maintain the desired environmental conditions. This completes the HVAC process cycle. COILS FOR COOLING AND HEATING This discussion explores the characteristics of coils used in HVAC systems. The name is somewhat of a misnomer; it suggests copper tubing on a bootlegger s distillation unit. That is most likely the origin of the term, but the coils used today must fit efficiently in rectangular air handlers and rectangular ductwork. For this reason, most coils are themselves put in a frame of a rectangular geometry. There is usually copper pipe inside the frame, typically with aluminum heat transfer plates called fins attached to the pipe (finned tubing). Row after row of copper is run back and forth across the airflow surface called the coil face. There are enough rows to cover the entire air stream in the air handler or ductwork. Even that is not enough to ensure complete treatment of the airstream passing through the coil. Several other important design details must be addressed for maximum coil efficiency. Face Velocity The velocity entering a coil is important for three primary reasons: heat transfer, pressure drop, and carry-over. Heat transfer. Heat transfer is best in a velocity range specified by the manufacturer of the coil. If the velocity is too high, air does not spend residence time in the coil to pick-up or give-up enough heat to be effective. If the velocity is too slow, the boundary layer on the fins of the coil get thicker and less turbulent causing less heat transfer. Pressure drop. Pressure drop through a coil is important to the total static pressure needed to drive air through the HVAC system. This is usually a decision made during the system design phase. The energy consumption, noise, and possibly lower heat transfer efficiency of the coil will endure through the life of the facility. Carry-over. Carry-over refers to the moisture being condensed on cooling coils after the air goes below dew-point temperature and is giving up the excess 78 Journal of Validation Technology [SPRING 2012] ivthome.com

5 A l e x a n d e r D e l l i Pa o l i, J r. Figure 4: Schematic of the HVAC system. water in the saturated air. If the velocity of the air is too great, the water droplets will be carried-over back into the airstream and downstream of the cooling coil. This usually means the water lands outside of the coil drain pan and impinges at another point in the air handler. This can cause floods as water accumulates, or higher humidity than desired if the water re-evaporates back into the airstream. Rare instances of fog entering the controlled facility have also been observed. Flooding in unexpected places is the most common occurrence. Number of Rows The entire face of a coil is covered by finned tubing. This is not enough by itself because a percentage of the air bypasses the fins and is not treated. There is also not enough contact time with one row of heat transfer surface. Additional rows are needed to assure the air has enough residence time in the coil to transfer heat or condense moisture. Typical heating and preheat coils range from one to six rows of depth (coil depth). Cooling coils typically range from four to ten rows deep with occasional needs for cooling coils of up to 16 rows of depth. The selection is the resolution of many design constraints by the design engineer. Fins per Length of Pipe Fins per length of pipe, like face velocity, is an important design consideration for the same reasons: heat transfer, pressure drop, and carry-over. Heat transfer is enhanced if fins are spaced close enough together to keep air from getting in between them without being treated. Fins too close together can lead to excessive pressure drop in the airstream. Close fins can be bridged by water droplets condensing in the coil, effectively blocking the unit. This blocking could cause water carry-over and decreased airflow to the controlled environment: another set of constraints for the design engineer and coil manufacturer. Drain Pans Drain pans should be placed under all water-bearing components in air handlers and ductwork. It is a small price to pay at installation to ensure a material failure gxpandjv t. com Journal of Validation Technology [SPRING 2012] 79

6 during the life of a facility does not cause a major flood in sensitive areas below the coils. Most facility personnel think of cooling coil pans as mandatory. Placing drain pans under other coils is a good practice if their rupture could cause undue hardship or business interruption. Cooling coils endure condensation from seasonal moisture in the northern climates. In warmer and more tropical climates, the cooling coils could be wet all four seasons. In either case, it is important to perform periodic cleaning and sanitization of coils and drains to minimize the possibility of microbial contamination. Traps A trap is a down-and-up loop in a drain to keep air from passing through the pipe. Traps are present in all sanitary sewer systems to prevent offensive sewer gases from migrating up through use point such as sinks in bathrooms and kitchens. In the case of a cooling coil trap, the trap is connected to the drain pan. The difference in this case is the fact that the air handler is under negative pressure at this location. This can cause two undesirable issues: air contamination within the air handler from an uncontrolled environment and flooding of the air handler by condensate overflow. Within the air handler (Figure 4) the fan section is pulling air through all the upstream components. This creates an increasing negative air pressure as the air is drawn across each component. By the time air has past the cooling coil, it has been drawn through return ductwork, prefilters, heating coils, and the cooling coil. This negative pressure can amount to multiple inches of water column. To prevent the trap from being blown, it must have an elevation difference outlet-to-inlet of typically six inches or more so the negative pressure can pull the water in the trap up toward the drain pan discharge without allowing the water in the bottom of the trap to pass air. Once the trap is blown-out, the negative pressure causes high velocity air to pass through the trap entraining air and conveying it back into the cooling coil drain pan. The drain eventually fills up and overflows inside the air handler. The leaks that ensue are disruptive to most facilities. Seasonal changes can cause trouble even after the trap has been primed (filled with liquid) initially. During a season when dehumidification is required, condensation flowing out the drain keeps the trap primed. Once a dryer climate occurs, cooling coil condensation stops and slow evaporation of the liquid in the trap begins. When the trap can no longer support the column of water created in it by the negative pressure inside the air handler, the trap blows-out and uncontrolled air starts flowing. This can continue throughout the dry season until condensation begins again, presenting the likelihood of flooding. This could be an undesirable annual event unless preventive measures are in place. Mechanical devices to prevent undesirable airflow exist, but they should be inspected periodically much like the rest of the HVAC system. It is just as simple to make an inspection of the traps part of the overall system preventive maintenance work orders and not introduce more contraptions on the trap. Traps can be filled with a fluid of low evaporation rate such as glycerin during the dry seasons to minimize the threat of a missed inspection. This fluid will be purged from the system when condensate begins flowing again. DEHUMIDIFICATION SOURCES Moisture is usually removed from air in one or more of three ways: cooling coils, desiccants, or compressed air. Cooling Coils Cooling coils are the most prevalent and cost effective method of dehumidification within typical temperature and humidity ranges found in controlled environments. Because temperature and relative humidity have an inverse relationship, it is difficult to quote exact numbers. An example of an operating point is 70 F at 50% relative humidity (RH). Cooling coils are limited to the freezing point of water because the condensation forming cannot be allowed to freeze in the coil and block the airflow. The fluid in the coil could be circulated colder than the freezing point of water with the use of antifreeze, but any temperature below 34 F is risking the freeze hazard. Using refrigerant directly in the cooling coil (direct expansion) is common on many smaller HVAC systems. This eliminates the risk of the fluid inside the coil freezing, but the concern for the condensate on the outer coil surfaces still exists. Control of the temperature leaving a direct expansion cooling coil is also less precise across the operating range of the coil. Desiccant Dehumidification Desiccant dehumidification is used when significantly lower humidity is needed in a facility. The size of the HVAC system is typically limited to serve just the facility requiring the lower humidity. Facilities using this type of system are likely to contain hygroscopic powders or other materials sensitive to moisture pick up. The dehumidification method can use either solid or liquid desiccant materials. Dry desiccants are usually in the shape of a porous wheel. The wheel is rotated between two ducts, each covering half of the wheel. The first half 80 Journal of Validation Technology [SPRING 2012] ivthome.com

7 A l e x a n d e r D e l l i Pa o l i, J r. of the rotation is in a duct performing the moisture removal for the air serving the controlled environment. The moisture-laden side of the wheel then rotates into the air stream of the second duct where the moisture is removed by warm air (wheel regeneration). The warm air then moves on for heat recovery or is exhausted to atmosphere. The wheel continues around again into the controlled air stream. The liquid desiccant system is similar in operation except that the liquid is exposed to the controlled environment airstream in a chamber to pick up moisture. The desiccant liquid is then circulated back to the dehumidification equipment where it is warmed to drive out the moisture. The liquid is then ready for reuse in the circulation loop. Compressed Air Air can be compressed to its saturation point and below to achieve low humidity in very small applications. The compressed air is usually cooled to further enhance moisture removal. When the air is later expanded the amount of moisture in the air can be low. While this is an effective way to remove moisture, it is not cost effective or energy efficient on a large scale. This method of dehumidification should not be ruled-out for small-scale, temporary, experimental, or emergency operations. The capacity of a facility s central compressed air system should be investigated before proceeding with this type of dehumidification system (i.e., tied into the source of compressed air). HUMIDIFICATION SOURCES Moisture is usually added to air in one or more of three ways: evaporation, steam humidifiers, or water humidifiers. Evaporation Evaporation from people and processes operating within a controlled environment contribute to the total moisture in a controlled environment. This can be considered an advantage in dryer seasons and part of the overall cooling load during the seasons of higher humidity. While evaporation is a contributing source in an operating facility, it is not considered a controllable parameter. Steam or water can be infused into air environment in a controllable, metered fashion. Steam Humidifiers Steam humidifiers disperse vapor in air handlers, ductwork, or in the controlled facility directly. Steam is already a vapor, so it poses a minor risk of wetting or flooding the inside of air handlers and ductwork. The steam is distributed to a piping grid typically located across the downstream face of the cooling coil in the air handler. In ductwork, steam humidifiers also consist of a piping grid distributed across the area of the duct. It is good practice to locate a humidity sensor downstream of any internal humidifier to detect saturated air. Condensation and eventual flooding would be the likely outcome of a failure of the primary humidification controls. This condition could occur with a control valve malfunction when the steam is not throttled or turned off adequately. The downstream humidity sensor could be designed to override the normal control sensor and generate an alarm to alert maintenance personnel. A safety concern with steam humidifiers is the hot pipes of the distribution grid. It is important that maintenance personnel are trained to be aware of this potential burn hazard Water Humidifiers Water humidifiers also disperse a mist through a distribution grid, which is evaporated as it is mixed with passing dry air in an air stream. The evaporation of this mist causes cooling of the airstream. Misting humidifiers can also be installed in the controlled facility directly, but they may cause cool spots in rooms due to the evaporative cooling effect of the water droplets. This type of humidifier requires greater attention to location in air handlers and ductwork. If the mist impinges on objects within the equipment, the liquid can build up and cause flooding. This could happen with the air never reaching its saturation point. A high humidity sensor and alarm are also recommended for the same reasons as with steam humidifiers. SUMMARY This paper initiated a more complete discussion of design constraints and details concerning the removal of moisture (wet side) from the air stream in a controlled environment. Topics addressed included psychrometrics and associated parameters including dry-bulb temperature, wet-bulb temperature, dew-point temperature, specific volume, enthalpy, and relative humidity. Case studies described HVAC processes conducted at different extremes. Coils for cooling and heating, and associated design details are described. Methods of dehumidification are discussed including cooling coils, desiccants, or compressed air. Humidification sources including evaporation, steam humidifiers, and water humidifiers are described. REFERENCE 1. Delli Paoli Jr., Alexander, The HVAC Process, Journal of Validation Technology, Volume 17, #4, Autumn 2011.JVT gxpandjv t. com Journal of Validation Technology [SPRING 2012] 81

Total Heat Versus Sensible Heat Evaporator Selection Methods & Application

Total Heat Versus Sensible Heat Evaporator Selection Methods & Application Total Heat Versus Sensible Heat Evaporator Selection Methods & Application Scope The purpose of this paper is to provide specifying engineers, purchasers and users of evaporators in industrial refrigeration

More information

Characteristics of Evaporators

Characteristics of Evaporators Characteristics of Evaporators Roger D. Holder, CM, MSME 10-28-2003 Heat or Energy In this paper, we will discuss the characteristics of an evaporator coil. The variance of the operational condenses of

More information

THE PSYCHROMETRIC CHART AND ITS USE

THE PSYCHROMETRIC CHART AND ITS USE Service Application Manual SAM Chapter 630-16 Section 3A THE PSYCHROMETRIC CHART AND ITS USE Psychrometry is an impressive word which is defined as the measurement of the moisture content of air. In broader

More information

Environmental Data Center Management and Monitoring

Environmental Data Center Management and Monitoring 2013 Raritan Inc. Table of Contents Introduction Page 3 Sensor Design Considerations Page 3 Temperature and Humidity Sensors Page 4 Airflow Sensor Page 6 Differential Air Pressure Sensor Page 6 Water Sensor

More information

Chilled Water HVAC Systems

Chilled Water HVAC Systems Chilled Water HVAC Systems By Ron Prager, Brinco Mechanical Services, Inc. Types of water based systems: There are three types of HVAC systems that utilize water as a heat transfer medium. The first system,

More information

How do I measure the amount of water vapor in the air?

How do I measure the amount of water vapor in the air? How do I measure the amount of water vapor in the air? Materials 2 Centigrade Thermometers Gauze Fan Rubber Band Tape Overview Water vapor is a very important gas in the atmosphere and can influence many

More information

Why is my air conditioner dripping on my customers?

Why is my air conditioner dripping on my customers? De-Mystifying HVAC Why is my air conditioner dripping on my customers? By Ron Prager One of the most frequent emergency service requests is a call for an air conditioner leaking water into the store. These

More information

How To Understand And Understand Psychrometrics

How To Understand And Understand Psychrometrics Air Conditioning Psychrometrics Course No: M05-005 Credit: 5 PDH A. Bhatia Continuing Education and Development, Inc. 9 Greyridge Farm Court Stony Point, NY 10980 P: (877) 322-5800 F: (877) 322-4774 info@cedengineering.com

More information

Controlling Wrap-Around Heat Pipes for Systems with Strict Space Humidity Requirements. By Michael O. Davis, PE, November 2015

Controlling Wrap-Around Heat Pipes for Systems with Strict Space Humidity Requirements. By Michael O. Davis, PE, November 2015 Controlling Wrap-Around Heat Pipes for Systems with Strict Space Humidity Requirements By Michael O. Davis, PE, November 2015 Advised by Heat Pipe Technology Background: HVAC systems are often designed

More information

Federal Wage System Job Grading Standards for Air Conditioning Equipment Operating, 5415. Table of Contents

Federal Wage System Job Grading Standards for Air Conditioning Equipment Operating, 5415. Table of Contents Federal Wage System Job Grading Standards for Air Conditioning Equipment Operating, 5415 Table of Contents WORK COVERED... 2 WORK NOT COVERED...2 TITLES... 2 GRADE LEVELS... 2 HELPER AND INTERMEDIATE JOBS...

More information

Green Building Handbook for South Africa Chapter: Heating, Ventilation and Cooling Luke Osburn CSIR Built Environment

Green Building Handbook for South Africa Chapter: Heating, Ventilation and Cooling Luke Osburn CSIR Built Environment Green Building Handbook for South Africa Chapter: Heating, Ventilation and Cooling Luke Osburn CSIR Built Environment The heating, ventilation and cooling loads of typical commercial office space can range

More information

Moisture Control. It s The Dew Point. Stupid! Its not the humidity.

Moisture Control. It s The Dew Point. Stupid! Its not the humidity. Moisture Control Its not the humidity. It s The Dew Point Stupid! Mike Schell EpiphanyTec Inc. Santa Barbara, CA mschell@epiphanytec.com 805 687-3175 Matching great technology to market need! Topics SHR

More information

Glossary of Heating, Ventilation and Air Conditioning Terms

Glossary of Heating, Ventilation and Air Conditioning Terms Glossary of Heating, Ventilation and Air Conditioning Terms Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment

More information

Dr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida

Dr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida Optimizing 100% Outside Air Systems with Heat Pipes Dr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida Introduction To meet increasingly rigorous building codes

More information

Data Centres. Special Working Group Spin I Relative Humidity in Data Centres

Data Centres. Special Working Group Spin I Relative Humidity in Data Centres Data Centres Special Working Group Spin I Table of Contents 1. Introduction 1 2. Data Centre Climate 1 2.1 Temperature 1 2.2 Particles and dust 2 2.3 Gases 3 2.4 Humidity 3 3. What is Humidity? 4 3.1 How

More information

Comparing Air Cooler Ratings Part 1: Not All Rating Methods are Created Equal

Comparing Air Cooler Ratings Part 1: Not All Rating Methods are Created Equal Technical Bulletin By Bruce I. Nelson, P.E., President, Colmac Coil Manufacturing, Inc. Comparing Air Cooler Ratings Part 1: Not All Rating Methods are Created Equal SUMMARY Refrigeration air coolers (evaporators)

More information

Molds and mildew are fungi that grow

Molds and mildew are fungi that grow Appendix C: Moisture, Mold and Mildew Molds and mildew are fungi that grow on the surfaces of objects, within pores, and in deteriorated materials. They can cause discoloration and odor problems, deteriorate

More information

Data Center Design Guide featuring Water-Side Economizer Solutions. with Dynamic Economizer Cooling

Data Center Design Guide featuring Water-Side Economizer Solutions. with Dynamic Economizer Cooling Data Center Design Guide featuring Water-Side Economizer Solutions with Dynamic Economizer Cooling Presenter: Jason Koo, P.Eng Sr. Field Applications Engineer STULZ Air Technology Systems jkoo@stulz ats.com

More information

Hospital Application Guide. Cost-effective climate control for hospitals

Hospital Application Guide. Cost-effective climate control for hospitals Hospital Application Guide Cost-effective climate control for hospitals Munters is the world leader in dehumidification Munters is the largest manufacturer of dehumidifiers in the world. Since developing

More information

Refrigeration Basics 101. By: Eric Nelson

Refrigeration Basics 101. By: Eric Nelson Refrigeration Basics 101 By: Eric Nelson Basics Refrigeration is the removal of heat from a material or space, so that it s temperature is lower than that of it s surroundings. When refrigerant absorbs

More information

SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS

SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS UNIT OBJECTIVES After studying this unit, the reader should be able to explain the purpose of the condenser in a refrigeration system. describe differences

More information

Chapter 14. At temperatures below the critical temperature, the gas GAS VAPOR MIXTURES AND AIR-CONDITIONING. Objectives

Chapter 14. At temperatures below the critical temperature, the gas GAS VAPOR MIXTURES AND AIR-CONDITIONING. Objectives Chapter 14 GAS VAPOR MIXTURES AND -CONDITIONING At temperatures below the critical temperature, the gas phase of a substance is frequently referred to as a vapor. The term vapor implies a gaseous state

More information

A discussion of condensate removal systems for clarifier and thickener drives for water and wastewater facilities.

A discussion of condensate removal systems for clarifier and thickener drives for water and wastewater facilities. A discussion of condensate removal systems for clarifier and thickener drives for water and wastewater facilities. Richard L. Dornfeld, BSME, P.E. Staff Engineer September 25, 2014 Moisture can be a problem

More information

Energy Efficient Building Design College of Architecture Illinois Institute of Technology, Chicago. Relative Humidities RH% 49.4. 0.

Energy Efficient Building Design College of Architecture Illinois Institute of Technology, Chicago. Relative Humidities RH% 49.4. 0. Psychrometrics Psychrometric Chart Relative Humidities RH% 49.4 100% 80% 0.030 Enthalpies 70% H btu/lb 46.5 0.028 85 Not to Scale 0.026 Humidity Numbers and Values 43.7 60% Ratios are approximate 0.024

More information

Dehumidification Frequently Asked Questions

Dehumidification Frequently Asked Questions Dehumidification Basics Why do you want to keep indoor Rh between 30-60%? ASHRAE recommends keeping the relative humidity in a home between 30-60% to limit the effects of many unwanted conditions and harmful

More information

HVAC Made Easy - Overview of Psychrometrics

HVAC Made Easy - Overview of Psychrometrics PDHonline Course M135 (4 PDH) HVAC Made Easy - Overview of Psychrometrics Instructor: A. Bhatia, B.E. 2012 PDH Online PDH Center 5272 Meadow Estates Drive Fairfax, VA 22030-6658 Phone & Fax: 703-988-0088

More information

New Trends in the Field of Automobile Air Conditioning

New Trends in the Field of Automobile Air Conditioning New Trends in the Field of Automobile Air Conditioning E. Janotkova and M. Pavelek Department of Thermomechanics and Environmental Engineering Brno University of Technology, 61669 Brno, Czech Republic

More information

Element D Services Heating, Ventilating, and Air Conditioning

Element D Services Heating, Ventilating, and Air Conditioning PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer

More information

How To Understand Evaporator

How To Understand Evaporator SECTION 5 COMMERCIAL REFRIGERATION UNIT 21 EVAPORATORS AND THE REFRIGERATION SYSTEM UNIT OBJECTIVES After studying this unit, the reader should be able to Define high-, medium-, and low-temperature refrigeration.

More information

By Tom Brooke PE, CEM

By Tom Brooke PE, CEM Air conditioning applications can be broadly categorized as either standard or critical. The former, often called comfort cooling, traditionally just controlled to maintain a zone setpoint dry bulb temperature

More information

Air Conditioning Clinic

Air Conditioning Clinic Air Conditioning Clinic Introduction to HVAC Systems One of the Systems Series February 2012 TRG-TRC018-EN Introduction to HVAC Systems One of the Systems Series A publication of Trane Preface Introduction

More information

Troubleshooting HVAC/R systems using refrigerant superheat and subcooling

Troubleshooting HVAC/R systems using refrigerant superheat and subcooling Troubleshooting HVAC/R systems using refrigerant superheat and subcooling Application Note Troubleshooting and servicing refrigeration and air conditioning systems can be a challenging process for both

More information

Troubleshooting an Air Conditioning system. R D Holder Eng. Roger D Holder MSME

Troubleshooting an Air Conditioning system. R D Holder Eng. Roger D Holder MSME Troubleshooting an Air Conditioning system R D Holder Eng. Roger D Holder MSME Troubleshooting of an air conditioning system is a step by step procedure. I have found that a 4 step procedure is the best

More information

The Different Types of Air Conditioning Equipment for IT Environments

The Different Types of Air Conditioning Equipment for IT Environments The Different Types of Air Conditioning Equipment for IT Environments By Tony Evans White Paper #59 Executive Summary Cooling equipment for an IT environment can be implemented in 10 basic configurations.

More information

Pool Dehumidification Basics

Pool Dehumidification Basics Copyright 2009 Wescor. All rights reserved. Permission granted to reproduce for personal and educational use only. When energy costs were low, many pool owners considered only first cost when choosing

More information

CPX/HT Series. REFRIGERATED AND HIGH TEMPERATURE DRYER 12 to 2400 CFM. High-performance products. Designed for you!

CPX/HT Series. REFRIGERATED AND HIGH TEMPERATURE DRYER 12 to 2400 CFM. High-performance products. Designed for you! CPX/HT Series REFRIGERATED AND HIGH TEMPERATURE DRYER 12 to 2400 CFM High-performance products. Designed for you! COMPRESSED AIR WATER CONTAMINATION Atmospheric air contains water in vapor form in different

More information

Subpart 1. Installation. All plumbing systems must be. installed and tested according to this chapter and chapter 4715,

Subpart 1. Installation. All plumbing systems must be. installed and tested according to this chapter and chapter 4715, 4658.4500 PLUMBING SYSTEMS; NEW CONSTRUCTION. Subpart 1. Installation. All plumbing systems must be installed and tested according to this chapter and chapter 4715, the Minnesota Plumbing Code. Subp. 2.

More information

HVAC Systems: Overview

HVAC Systems: Overview HVAC Systems: Overview Michael J. Brandemuehl, Ph.D, P.E. University of Colorado Boulder, CO, USA Overview System Description Secondary HVAC Systems Air distribution Room diffusers and air terminals Duct

More information

To provide good indoor air quality

To provide good indoor air quality Conditioning Ventilation Air for Improved Performance and Air Quality The practice of using a mixing chamber for mixing outdoor and return in a single system should be replaced by a technique with two

More information

How much do you know about HVAC? Try testing yourself with the following questions and then take a look at the answers on the following page.

How much do you know about HVAC? Try testing yourself with the following questions and then take a look at the answers on the following page. Demystifying HVAC Test Your HVAC Knowledge By Ron Prager How much do you know about HVAC? Try testing yourself with the following questions and then take a look at the answers on the following page. 1)

More information

THE HUMIDITY/MOISTURE HANDBOOK

THE HUMIDITY/MOISTURE HANDBOOK THE HUMIDITY/MOISTURE HANDBOOK Table of Contents Introduction... 3 Relative Humidity... 3 Partial Pressure... 4 Saturation Pressure (Ps)... 5 Other Absolute Moisture Scales... 8 % Moisture by Volume (%M

More information

APPLICATION GUIDE. Moisture Management in Waterborne Climate Systems

APPLICATION GUIDE. Moisture Management in Waterborne Climate Systems APPLICATION GUIDE Moisture Management in Waterborne Climate Systems Contents Introduction 3 WBCS Concept 3 Condensation 4 Moisture Sources in the Space 4 Impact of a High Moisture Load 5 Designing to Manage

More information

Humidification Strategies for Data Centers and Network Rooms

Humidification Strategies for Data Centers and Network Rooms Humidification Strategies for Data Centers and Network Rooms By Tony Evans White Paper #58 Revision 1 Executive Summary The control of humidity in Information Technology environments is essential to achieving

More information

AIR SYSTEMS ENERGY SERIES Energy Recovery Wheels

AIR SYSTEMS ENERGY SERIES Energy Recovery Wheels AIR SYSTEMS ENERGY SERIES Energy Recovery Wheels APPLICATION GUIDE Supercedes: Nothing Form 102.20-AG6 (305) INTRODUCTION As fossil fuel reserves are depleted, the cost of energy continues to rise. According

More information

How air conditioning works

How air conditioning works 1 How air conditioning works The essential ingredients in an air conditioning system are a fan to blow air around, a cold surface to cool and dehumidify the air, a warm surface and a source of water vapour.

More information

Lesson 36 Selection Of Air Conditioning Systems

Lesson 36 Selection Of Air Conditioning Systems Lesson 36 Selection Of Air Conditioning Systems Version 1 ME, IIT Kharagpur 1 The specific objectives of this chapter are to: 1. Introduction to thermal distribution systems and their functions (Section

More information

Causes of High Relative Humidity Inside Air Conditioned Buildings. Roger G.Morse AIA, Paul Haas CSP, CIH Morse Zehnter Associates

Causes of High Relative Humidity Inside Air Conditioned Buildings. Roger G.Morse AIA, Paul Haas CSP, CIH Morse Zehnter Associates Causes of High Relative Humidity Inside Air Conditioned Buildings Roger G.Morse AIA, Paul Haas CSP, CIH Morse Zehnter Associates S. FLORIDA AVE. AMBIENT 91 F db / 78 F wb 16,000 HOURS ANNUALLY THAT wb

More information

1932 Lexington Houston, Texas 77098-4220 (713) 524-4877. Recommendations for installation of cooling systems

1932 Lexington Houston, Texas 77098-4220 (713) 524-4877. Recommendations for installation of cooling systems 1932 Lexington Houston, Texas 77098-4220 (713) 524-4877 The purpose for this information is to provide a better understanding of the HVAC equipment, components, designs, and installations, of HVAC system

More information

Condensate Trapping: Don't Get Caught in a Trap of Your Own! - From the Trane Inc Website 1

Condensate Trapping: Don't Get Caught in a Trap of Your Own! - From the Trane Inc Website 1 Condensate Trapping: Don't Get Caught in a Trap of Your Own! - From the Trane Inc Website 1 Background: The past 10 years have seen a dramatic change in the design and function of air handlers, due in

More information

CONDENSATION IN REFRIDGERATED BUILDINGS

CONDENSATION IN REFRIDGERATED BUILDINGS CONDENSATION IN REFRIDGERATED BUILDINGS By: Steve Salisbury Nov. 10, 2010 (revised Nov. 14, 2013) Introduction The following discussion reviews the basic causes of condensation in refrigerated buildings

More information

Overview. Introduction Cooling Tower Basics Principles of Operation Types of Cooling Towers Common Applications Design Considerations

Overview. Introduction Cooling Tower Basics Principles of Operation Types of Cooling Towers Common Applications Design Considerations Stephen Lowe ASHRAE Hampton Roads Chapter Past President AECOM Design Mechanical Engineering Discipline Manager, Virginia Beach Division Professional Engineer Commonwealth of Virginia, NCEES BSME University

More information

Improving Data Center Energy Efficiency Through Environmental Optimization

Improving Data Center Energy Efficiency Through Environmental Optimization Improving Data Center Energy Efficiency Through Environmental Optimization How Fine-Tuning Humidity, Airflows, and Temperature Dramatically Cuts Cooling Costs William Seeber Stephen Seeber Mid Atlantic

More information

Evaluation Of Hybrid Air- Cooled Flash/Binary Power Cycle

Evaluation Of Hybrid Air- Cooled Flash/Binary Power Cycle INL/CON-05-00740 PREPRINT Evaluation Of Hybrid Air- Cooled Flash/Binary Power Cycle Geothermal Resources Council Annual Meeting Greg Mines October 2005 This is a preprint of a paper intended for publication

More information

COIL INPUT SCREENS. ITEM NUMBER: Always use a 1 through? In this field you might also use a dash and place quantity of coils here.

COIL INPUT SCREENS. ITEM NUMBER: Always use a 1 through? In this field you might also use a dash and place quantity of coils here. COIL INPUT SCREENS Example of a Water Coil Input Screen: (*please see the appendix for an example of an Evaporator, Steam or Condenser Coil input screen) PHYSICAL DATA ITEM NUMBER: Always use a 1 through?

More information

Measuring The Right Thing For Humidity Control It s the Dew Point Stupid!

Measuring The Right Thing For Humidity Control It s the Dew Point Stupid! Page 1 of 6 Measuring The Right Thing For Humidity Control It s the Dew Point Stupid! By Mike Schell, AirTest Technologies Corp. A version of this article appeared in the June 2004 edition of Indoor Air

More information

How To Design A Refrigeration System

How To Design A Refrigeration System AIRAH Refrigeration (in HVAC) Back to Basics For the First Time Terms of Reference What this session is NOT about Detailed Refrigeration Design Detailed analysis of various Refrigants properties Comparison

More information

Energy Recovery Ventilation Equipment

Energy Recovery Ventilation Equipment AHRI Standard 1060 (I-P) 2013 Standard for Performance Rating of Airto-Air Exchangers for Energy Recovery Ventilation Equipment IMPORTANT SAFETY DISCLAIMER AHRI does not set safety standards and does not

More information

Dew Point Tester. Instruction Manual. CVS Regular Chiller Model A-2. CVS Regular Chiller Model A-2

Dew Point Tester. Instruction Manual. CVS Regular Chiller Model A-2. CVS Regular Chiller Model A-2 Instruction Manual Dew Point Tester The CVS Dew Point Tester is a chilled mirror apparatus, which operates by attaining the conditions necessary by the definition of dew point. When a gas is cooled out

More information

KINGDOM OF SAUDI ARABIA SAUDI ARABIAN STANDARDS ORGANIZATION SASO. SAUDI STANDARD DRAFT No. 3457/2005

KINGDOM OF SAUDI ARABIA SAUDI ARABIAN STANDARDS ORGANIZATION SASO. SAUDI STANDARD DRAFT No. 3457/2005 KINGDOM OF SAUDI ARABIA SAUDI ARABIAN STANDARDS ORGANIZATION SASO SAUDI STANDARD DRAFT No. 3457/2005 NON-DUCTED AIR CONDITIONERS AND HEAT PUMPS TESTING AND RATING PERFORMANCE This standard is developed

More information

GEOTHERMAL HEATING AND COOLING INTRODUCTION

GEOTHERMAL HEATING AND COOLING INTRODUCTION GEOTHERMAL HEATING AND COOLING INTRODUCTION Geothermal Heating and Cooling Systems provide space conditioning -- heating, cooling, and humidity control. They may also provide water heating -- either to

More information

ES 106 Laboratory # 6 MOISTURE IN THE ATMOSPHERE

ES 106 Laboratory # 6 MOISTURE IN THE ATMOSPHERE ES 106 Laboratory # 6 MOISTURE IN THE ATMOSPHERE 6-1 Introduction By observing, recording, and analyzing weather conditions, meteorologists attempt to define the principles that control the complex interactions

More information

Wet Bulb Temperature and Its Impact on Building Performance

Wet Bulb Temperature and Its Impact on Building Performance Wet Bulb Temperature and Its Impact on Building Performance By: Kurmit Rockwell, PE, CEM, LEED AP and Justin Lee, PE, LEED, AP BD+C Energy Solution Services, AtSite, Inc. 1 What is Wet Bulb Temperature?

More information

Dedicated Outdoor Air-Dual Wheel System Control Requirements

Dedicated Outdoor Air-Dual Wheel System Control Requirements 4428 Dedicated Outdoor Air-Dual Wheel System Control Requirements Stanley A. Mumma, Ph.D., P.E. Fellow ASHRAE ABSTRACT The central thrust of this paper is to develop a clear understanding of the performance

More information

CONTAMINANT REMOVAL FROM CENTRIFUGAL SYSTEMS

CONTAMINANT REMOVAL FROM CENTRIFUGAL SYSTEMS CONTAMINANT REMOVAL FROM CENTRIFUGAL SYSTEMS BULLETIN 240-10-3 June 2004 Supersedes June 1983 Many centrifugal systems get little maintenance. As a result they operate with the refrigerant highly contaminated

More information

MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING

MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING V. Vakiloroaya*, J.G. Zhu, and Q.P. Ha School of Electrical, Mechanical and Mechatronic Systems,

More information

INSTRUCTIONS FOR HOW TO PROPERLY SELECT A FAN OR BLOWER

INSTRUCTIONS FOR HOW TO PROPERLY SELECT A FAN OR BLOWER INSTRUCTIONS FOR HOW TO PROPERLY SELECT A FAN OR BLOWER The instructions that follow are to assist you in completing the information required when making a fan or blower selection. If you need additional

More information

Federal Wage System Job Grading Standard for Air Conditioning Equipment Mechanic, 5306. Table of Contents

Federal Wage System Job Grading Standard for Air Conditioning Equipment Mechanic, 5306. Table of Contents Federal Wage System Job Grading Standard for Air Conditioning Equipment Mechanic, 5306 Table of Contents WORK COVERED... 2 WORK NOT COVERED...2 TITLES... 2 GRADE LEVELS... 2 HELPER AND INTERMEDIATE JOBS...

More information

UNIVERSITY OF MISSOURI 23 0000 - Heating Ventilating and Air-Conditioning (HVAC) March 2015.01

UNIVERSITY OF MISSOURI 23 0000 - Heating Ventilating and Air-Conditioning (HVAC) March 2015.01 GENERAL: This section provides general standards for overall sizing and design of Heating, Ventilating, and Air Conditioning (HVAC) systems. Other sections contain specific standards for each system per

More information

COMMERCIAL HVAC CHILLER EQUIPMENT. Air-Cooled Chillers

COMMERCIAL HVAC CHILLER EQUIPMENT. Air-Cooled Chillers COMMERCIAL HVAC CHILLER EQUIPMENT Air-Cooled Chillers Technical Development Programs (TDP) are modules of technical training on HVAC theory, system design, equipment selection and application topics. They

More information

International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS

International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS International Telecommunication Union ITU-T TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU Technical Paper (13 December 2013) SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES

More information

Example Retrocommissioning Measure: Opening Throttled Discharge Valves

Example Retrocommissioning Measure: Opening Throttled Discharge Valves Opening Throttled Discharge Valves This 21-story building, constructed in 1997, is located in Oregon and contains 589,000 gross square feet of mostly office occupancy. The HVAC system includes six large

More information

Air Conditioning 101. STN Presentation AC101

Air Conditioning 101. STN Presentation AC101 Air Conditioning 101 What is Refrigeration? Refrigeration is Cooling by the Removal of Heat Heat is Measured In BTU s A BTU is a British Thermal Unit It is the Amount of Heat to Raise One Pound of Water,

More information

Evaporative Cooling. Terminology. Date: February 28, 2012. Concepts

Evaporative Cooling. Terminology. Date: February 28, 2012. Concepts Evaporative Cooling Date: February 28, 2012 P R E S E N T E D B Y R O B E R T P A D G E T E 3 M S E N G I N E E R E D M E C H A N I C A L S Y S T E M S Concepts 1. Evaporation is a cooling process. Using

More information

Air Water Vapor Mixtures: Psychrometrics. Leon R. Glicksman c 1996, 2010

Air Water Vapor Mixtures: Psychrometrics. Leon R. Glicksman c 1996, 2010 Air Water Vapor Mixtures: Psychrometrics Leon R. Glicksman c 1996, 2010 Introduction To establish proper comfort conditions within a building space, the designer must consider the air temperature and the

More information

Economizer Fundamentals: Smart Approaches to Energy-Efficient Free-Cooling for Data Centers

Economizer Fundamentals: Smart Approaches to Energy-Efficient Free-Cooling for Data Centers A White Paper from the Experts in Business-Critical Continuity TM Economizer Fundamentals: Smart Approaches to Energy-Efficient Free-Cooling for Data Centers Executive Summary The strategic business importance

More information

2. The map below shows high-pressure and low-pressure weather systems in the United States.

2. The map below shows high-pressure and low-pressure weather systems in the United States. 1. Which weather instrument has most improved the accuracy of weather forecasts over the past 40 years? 1) thermometer 3) weather satellite 2) sling psychrometer 4) weather balloon 6. Wind velocity is

More information

Temperature and Humidity

Temperature and Humidity Temperature and Humidity Overview Water vapor is a very important gas in the atmosphere and can influence many things like condensation and the formation of clouds and rain, as well as how hot or cold

More information

HVAC Checklist - Long Form

HVAC Checklist - Long Form HVAC Checklist - Long Form Page 1 of 14 Appendix B discusses HVAC system components in relation to indoor air quality. utside Air Intake Location pen during occupied hours? Unobstructed? Standing water,

More information

APPLICATION GUIDE. Comparison of Latent Cooling Performance of Various HVAC systems in a Classroom Application

APPLICATION GUIDE. Comparison of Latent Cooling Performance of Various HVAC systems in a Classroom Application APPLICATION GUIDE Comparison of Latent Cooling Performance of Various HVAC systems in a Classroom Application Section Comparison of Latent Cooling Performance of Introduction Most commercial HVAC systems

More information

Table V. Troubleshooting Checklist for Refrigeration Systems. Air or non-condensable gas in system. Inlet water warm.

Table V. Troubleshooting Checklist for Refrigeration Systems. Air or non-condensable gas in system. Inlet water warm. Table V Troubleshooting Checklist for Refrigeration Systems TROUBLE POSSIBLE CAUSE CORRECTIVE MEASURE High condensing pressure. Low condensing pressure. Air or non-condensable gas in system. Inlet water

More information

Why and How we Use Capacity Control

Why and How we Use Capacity Control Why and How we Use Capacity Control On refrigeration and air conditioning applications where the load may vary over a wide range, due to lighting, occupancy, product loading, ambient weather variations,

More information

CONDENSATION. Section Break (Next Page)

CONDENSATION. Section Break (Next Page) CONDENSATION Elimination of condensation on or within walls and floors is as important as reducing the heat loss through the wall or floor. In addition to the moisture damage caused to buildings by condensation,

More information

Sustainable Preservation Practices for Managing Storage Environments Webinar: April 3, 2013

Sustainable Preservation Practices for Managing Storage Environments Webinar: April 3, 2013 The Fundamentals of HVAC: What Shapes the Storage Environment Sustainable Preservation Practices for Managing Storage Environments Webinar: April 3, 2013 Introduction Presenter Jeremy Linden, Preservation

More information

Precision Humidity Measurement for Pharmaceutical Fluid Bed Tablet Coating

Precision Humidity Measurement for Pharmaceutical Fluid Bed Tablet Coating Precision Humidity Measurement for Pharmaceutical Fluid Bed Tablet Coating are several reasons why tablet cores are coated, including: Alpharma/Purepac is one of the largest global generic pharmaceutical

More information

Creating the Ideal Environment for Accelerated Drying Times on Construction and Restoration Projects

Creating the Ideal Environment for Accelerated Drying Times on Construction and Restoration Projects 4.02.08 updated Creating the Ideal Environment for Accelerated Drying Times on Construction and Restoration Projects Moisture Removal Systems www.groundheaters.com www.wackerneuson.com Controlling moisture

More information

Engineering White Paper UTILIZING ECONOMIZERS EFFECTIVELY IN THE DATA CENTER

Engineering White Paper UTILIZING ECONOMIZERS EFFECTIVELY IN THE DATA CENTER Engineering White Paper UTILIZING ECONOMIZERS EFFECTIVELY IN THE DATA CENTER SUMMARY A proper balance of temperature and humidity control is essential for efficient data center operation, and integral

More information

Commissioning - Construction Documents (Page 1 of 6)

Commissioning - Construction Documents (Page 1 of 6) Commissioning - Construction Documents (Page 1 of 6) A. General Information Climate Zone: Building Type: Conditioned Area (sf): Reviewer's Name: Reviewer's Agency: Note: Design Review for each system/subsystem

More information

DOE FEMP First Thursday Seminar. Learner Guide. Core Competency Areas Addressed in the Training. Energy/Sustainability Managers and Facility Managers

DOE FEMP First Thursday Seminar. Learner Guide. Core Competency Areas Addressed in the Training. Energy/Sustainability Managers and Facility Managers DOE FEMP First Thursday Seminar Achieving Energy Efficient Data Centers with New ASHRAE Thermal Guidelines Learner Guide Core Competency Areas Addressed in the Training Energy/Sustainability Managers and

More information

White Paper #10. Energy Efficiency in Computer Data Centers

White Paper #10. Energy Efficiency in Computer Data Centers s.doty 06-2015 White Paper #10 Energy Efficiency in Computer Data Centers Computer Data Centers use a lot of electricity in a small space, commonly ten times or more energy per SF compared to a regular

More information

Humidity, Condensation, Clouds, and Fog. Water in the Atmosphere

Humidity, Condensation, Clouds, and Fog. Water in the Atmosphere Humidity, Condensation, Clouds, and Fog or Water in the Atmosphere The Hydrologic Cycle Where the Water Exists on Earth Evaporation From the Oceans and Land The Source of Water Vapor for the Atmosphere

More information

KU DESIGN GUIDELINES APPENDIX XVI RECOMMENDED BAS I/O CONTROL POINTS BY EQUIPMENT / SYSTEM

KU DESIGN GUIDELINES APPENDIX XVI RECOMMENDED BAS I/O CONTROL POINTS BY EQUIPMENT / SYSTEM KU DESIGN GUIDELINES APPENDIX XVI RECOMMENDED BAS I/O CONTROL POINTS BY EQUIPMENT / SYSTEM AIR HANDLING UNITS... 1 CHILLERS... 2 COOLING TOWERS... 2 CLOSED LOOP COOLERS... 2 MISCELLANEOUS SUPPLY FANS...

More information

Initial Experiments of a Novel Liquid Desiccant Dehumidifier for Industrial and Comfort Air Conditioning Systems

Initial Experiments of a Novel Liquid Desiccant Dehumidifier for Industrial and Comfort Air Conditioning Systems Abstract Initial Experiments of a Novel Liquid Desiccant Dehumidifier for Industrial and Comfort Air Conditioning Systems M. Jaradat, R. Heinzen, U. Jordan, K. Vajen Kassel University (Germany), Institute

More information

SECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS

SECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS SECTION 15750 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for roof mounted, self-contained units, with electric cooling, and electric or reverse refrigeration cycle (heat pump) heating

More information

HVAC Design Requirements

HVAC Design Requirements Maintenance of HVAC HVAC Design Requirements Air Flow Diagram แบบ Recirculation Air Flow Diagram แบบ Once Through Definition Of Conditions As built At rest In operation air air air Maintenance GMP Requirements

More information

Defining Quality. Building Comfort. Precision. Air Conditioning

Defining Quality. Building Comfort. Precision. Air Conditioning Defining Quality. Building Comfort. Precision Air Conditioning Today s technology rooms require precise, stable environments in order for sensitive electronics to operate optimally. Standard comfort air

More information

Condensate Treatment Solutions. CTS Series Eliminator II Oil-Water Separators

Condensate Treatment Solutions. CTS Series Eliminator II Oil-Water Separators Condensate Treatment Solutions CTS Series Eliminator II Oil-Water Separators 2 Condensate Treatment Solutions A Cleaner Environment & Reduced Disposal Costs Compressed air is compressed and discharged

More information

HEAT PUMP FREQUENTLY ASKED QUESTIONS HEAT PUMP OUTDOOR UNIT ICED-UP DURING COLD WEATHER:

HEAT PUMP FREQUENTLY ASKED QUESTIONS HEAT PUMP OUTDOOR UNIT ICED-UP DURING COLD WEATHER: HEAT PUMP FREQUENTLY ASKED QUESTIONS HEAT PUMP OUTDOOR UNIT ICED-UP DURING COLD WEATHER: It is normal for a heat pump to have a build up of white frost on the outside coil during cold damp weather. The

More information

Rusty Walker, Corporate Trainer Hill PHOENIX

Rusty Walker, Corporate Trainer Hill PHOENIX Refrigeration 101 Rusty Walker, Corporate Trainer Hill PHOENIX Compressor Basic Refrigeration Cycle Evaporator Condenser / Receiver Expansion Device Vapor Compression Cycle Cooling by the removal of heat

More information

Absolute and relative humidity Precise and comfort air-conditioning

Absolute and relative humidity Precise and comfort air-conditioning Absolute and relative humidity Precise and comfort air-conditioning Trends and best practices in data centers Compiled by: CONTEG Date: 30. 3. 2010 Version: 1.11 EN 2013 CONTEG. All rights reserved. No

More information

Energy Efficient Server Room and Data Centre Cooling. Computer Room Evaporative Cooler. EcoCooling

Energy Efficient Server Room and Data Centre Cooling. Computer Room Evaporative Cooler. EcoCooling Energy Efficient Server Room and Data Centre Cooling Computer Room Evaporative Cooler EcoCooling EcoCooling CREC Computer Room Evaporative Cooler Reduce your cooling costs by over 90% Did you know? An

More information