M E M O R A N D U M. Diane Matthews, Administrator, Technical Projects. NFPA 5000 First Draft Letter Ballot (A2014)
|
|
- Anthony Harrison
- 7 years ago
- Views:
Transcription
1 National Fire Protection Association 1 Batterymarch Park, Quincy, MA Phone: Fax: M E M O R A N D U M TO: FROM: NFPA Technical Committee on Fire Protection Features (BLD-FIR) Diane Matthews, Administrator, Technical Projects DATE: September 11, 2012 SUBJECT: NFPA 5000 First Draft Letter Ballot (A2014) Attached please find the First Revisions for NFPA The ballot is for formally voting on whether or not you concur with the committee s First Revisions. Reasons must accompany all negative and abstaining votes. Please do not vote negatively because of editorial errors. However, please bring such errors to my attention for action. Please complete and return your ballot as soon as possible but no later than Friday, September 28, As noted on the ballot form, please return the ballot to Diane Matthews, Administrator, Technical Projects, either via to bld-fir@nfpa.org or via fax to You may also mail your ballot to the attention of Diane Matthews at NFPA, 1 Batterymarch Park, Quincy, MA The return of ballots is required by the Regulations Governing the Development of NFPA Standards. Attachments
2 5000 FR400 BLD-FIR Final Action: (8.1.3) Recommendation: The fire resistance rating of an element or assembly as determined by an approved test method shall not be permitted to rely on an automatic sprinkler system or any other fire suppression system FR412 BLD-FIR Final Action: ( ) The fire resistance ratings of structural elements and building assemblies shall be determined in accordance with the prescriptive requirements of based on the test procedures set forth in ASTM E 119, Standard Test Methods for Fire Tests of Building Construction and Materials, or UL 263, Standard for Fire Tests of Building Construction and Materials, or other approved test methods or analytical methods in accordance with End-jointed lumber used in such an assembly shall have the designation Heat Resistant Adhesive or HRA included in its grade mark FR411 BLD-FIR Final Action: ( (New) ) Recommendation: Insert new Section to read as follows: End-jointed lumber used in such an assembly shall have the designation heat resistant adhesive or HRA included in its grade mark FR433 BLD-FIR Final Action: ( ) Recommendation: Add new section to read as follows: Ceiling Plenum Tested Assembly. Where the plenum is a part of a floor/ceiling or roof/ceiling assembly that has been tested or investigated and assigned a fire resistance rating of 1 hour or more, and the assembly contains air ducts and openings for air ducts, all the materials and the construction of the assembly, including the air duct materials and the size and protection of the openings, shall conform with the design of the fire resistance rated assembly, as tested in accordance with ASTM E 119, Standard Test Methods for Fire Tests of Building Construction and Materials; or UL 263, Standard for Fire Tests of Building Construction and Materials FR434 BLD-FIR Final Action: ( ) Fire dampers shall be installed and maintained in accordance with NFPA 90A80, Standard for the Installation of Air-Conditioning and Ventilating SystemsFire Doors and Other Opening Protectives. [221:5.10.1] 1
3 5000 FR404 BLD-FIR Final Action: ( (4)) Recommendation: Add new text to read as follows: Where walls or partitions are required to have a fire resistance rating of not less than 1 hour, recessed fixtures shall be installed in the wall or partition in such a manner that the required fire resistance is not reduced, unless one of the following criteria is met: (1) Any steel electrical box not exceeding 16 in.2 (10,300 mm2) in area shall be permitted where the aggregate area of the openings provided for the boxes does not exceed 100 in.2 (64,520 mm2) in any 100 ft2 (9.3 m2) of wall area, and, where outlet boxes are installed on opposite sides of the wall, the boxes shall be separated by one of the following means: (a) By a horizontal distance of not less than 24 in. (610 mm) (b) By a horizontal distance of not less than the depth of the wall cavity where the wall cavity is filled with cellulose loose-fill, rock wool, or slag wool insulation (c) By solid fireblocking in accordance with (d) By other listed materials and methods (2) Membrane penetrations for any listed electrical outlet box made of any material shall be permitted, provided that such boxes have been tested for use in fire resistance rated assemblies and are installed in accordance with the instructions included in the listing. (3) The annular space created by the membrane penetration of a fire sprinkler shall be permitted, provided that the space is covered by a metal escutcheon plate. (4) Membrane penetrations by electrical boxes of any size or type, which have been listed as part of a wall opening protective material system for use in fire-resistance-rated assemblies and are installed in accordance with the instructions included in the listing shall be permitted FR414 BLD-FIR Final Action: (8.10.2) Requirements Continuity. Smoke partitions shall comply with one of the following 5000 FR415 BLD-FIR Final Action: ( ) Recommendation: Where a fire protection resistance rating is specified for a smoke partition elsewhere in this Code, openings shall be protected as follows: (1) Door opening protectives shall have a fire protection rating of not less than 20 minutes where tested in accordance with NFPA 252, Standard Methods of Fire Tests of Door Assemblies, without hose stream test, unless otherwise specified by Chapters 15 through 31 and 33 through 34. (2) Fire windows shall comply with Section 8.7. (3) Glazing used in sidelights and transoms adjacent to 20-minute doors in 1 2-hour fire resistance rated smoke partitions shall be tested in accordance with and shall attain a minimum 20-minute fire protection rating, including hose stream. 2
4 5000 FR417 BLD-FIR Final Action: ( ) Where a smoke barrier is also constructed as a fire barrier, the penetrations shall be protected in accordance with the requirements of Section 8.8 to limit the spread of fire for a time period equal to the fire resistance rating of the assembly, as required by , to restrict the transfer of smoke, unless the requirements of are met FR416 BLD-FIR Final Action: ( ) Recommendation: Smoke Barriers Dampers FR418 BLD-FIR Final Action: ( ) Every floor that separates stories in a building shall be constructed as a smoke barrier and shall meet one of the following: shall meet the following criteria: (1) Openings shall restrict the passage of smoke as specified by (1) It shall be constructed as a smoke barrier in accordance with Section (2) The requirement of (1) shall not apply where otherwise specified It shall be permitted to have openings as described by , , , or Chapters 15 through 31 and 33 through FR420 BLD-FIR Final Action: ( ) The requirements of shall not apply where otherwise specified by any of the following: (1) Enclosure shall not be required where otherwise specified by , , , , or Chapters 15 through 31 and 33 through 34. (2)* Enclosure shall not be required for expansion or seismic joints designed to prevent the penetration of fire and shown to have a fire resistance rating of not less than the required fire resistance rating of the floor when tested in accordance with ANSI/UL (3) Enclosure shall not be required for penetrations for cables, cable trays, conduits, pipes, tubes, combustion vents and exhaust vents, wires, or pneumatic tube conveyors protected in accordance with and (4) Enclosure shall not be required where escalators and moving walks are protected in accordance with
5 5000 FR432 BLD-FIR Final Action: ( ) Recommendation: Shafts that do not extend to the bottom or the top of the building or structure shall comply with either , , or Shafts shall be enclosed at the lowest or highest level of the shaft, respectively, with construction in accordance with and Section Shafts shall be permitted to terminate in a room or space having a use related to the purpose of the shaft, provided that the room or space is separated from the remainder of the building by construction having a fire resistance rating and opening protectives in accordance with and Section Shafts that do not extend to the bottom or top of the building or structure shall be permitted to be protected by approved fire dampers installed in accordance with their listing at the lowest or highest floor level, as applicable, within the shaft enclosure Shafts. Shafts that do not extend from the bottom to the top of the building or structure shall comply with either , , or , as modified by or Shafts that do not extend to the top of the building or structure shall be enclosed at the highest level of the shaft with construction in accordance with Shafts that do not extend to the bottom of the building or structure shall be enclosed at the lowest level of the shaft with construction in accordance with Shafts that do not extend to the bottom and to the top of the building or structure shall be enclosed at the lowest and highest level of the shaft with construction in accordance with In lieu of any enclosure required at lowest or highest level of a shaft by through , shafts shall be permitted to terminate in a room or space having a use related to the purpose of the shaft, provided that the room or space is separated from the remainder of the building by construction having a fire resistance rating and opening protectives in accordance with and Section Any enclosure required at the lowest or highest level of a shaft by through shall be permitted to be protected by approved fire dampers installed in accordance with their listing FR421 BLD-FIR Final Action: (8.12.2) Recommendation: Communicating Space. Unless prohibited by Chapters 15 through 31 and 33 through 34, unenclosed floor openings forming a communicating space between floor levels shall be permitted, provided that the following conditions are met: (1) The communicating space does not connect more than three contiguous stories. (2) The lowest or next to lowest story within the communicating space is a street floor. (3) The entire floor area of the communicating space is open and unobstructed, such that a fire in any part of the space will be readily obvious to the occupants of the space prior to the time it becomes an occupant hazard. (4) The communicating space is separated from the remainder of the building by fire barriers with not less than a 1-hour fire resistance rating, unless one of the following is met: (a) In buildings protected throughout by an approved automatic sprinkler system in accordance with NFPA13 or NFPA 13R Section 55.3, a smoke barrier in accordance with Section 8.11 shall be permitted to serve as the separation required by (4). (5) The communicating space has ordinary hazard contents protected throughout by an approved automatic sprinkler system in accordance with NFPA13 or NFPA13R Section 55.3 or has only low hazard contents. (See Chapter 6.) 4
6 5000 FR422 BLD-FIR Final Action: (8.12.3) * Atrium. Unless prohibited by Chapters 15 through 31 and 33 through 34, an atrium shall be permitted, provided that all of the following conditions are met: (1) The atrium is separated from the adjacent spaces by fire barriers with not less than a 1-hour fire resistance rating with opening protectives for corridor walls, unless one of the following criteria is met: (a) Any number of levels of the building shall be permitted to open directly to the atrium without enclosure based on the results of the engineering analysis required in (5). (b)* Glass walls and inoperable windows shall be permitted in lieu of the fire barriers where all of the following criteria are met: i. Automatic sprinklers supplied are spaced along both sides of the glass wall, and the inoperable windows at intervals not to exceed 6 ft (1830 mm). ii. The automatic sprinklers specified in (1)(b) (i) are located at a distance from the glass wall not to exceed 12 in. (305 mm) and arranged so that the entire surface of the glass is wet upon operation of the sprinklers. iii. The glass wall is of tempered, wired, or laminated glass held in place by a gasket system that allows the glass framing system to deflect without breaking (loading) the glass before the sprinklers operate. iv. The automatic sprinklers specified in (1)(b) (i) are not required on the atrium side of the glass wall and the inoperable window where there is no walkway or other floor area on the atrium side above the main floor level. v. Doors in the glass walls are of glass or other material that resists the passage of smoke. vi. Doors in the glass walls are self-closing or automatic-closing upon detection of smoke. vii. The glass is continuous vertically, without horizontal mullions, window treatments, or other obstructions that would interfere with the wetting of the entire glass surface. (2) Access to exits is permitted to be within the atrium, and exit discharge in accordance with is permitted to be within the atrium. (3) The occupancy within the space meets the specifications for classification as low or ordinary hazard contents. (See Chapter 6.) (4) The entire building is protected throughout by an approved, supervised automatic sprinkler system in accordance with NFPA 13 or NFPA 13R and Section (5)* An engineering analysis is performed that demonstrates that the building is designed to keep the smoke layer interface above the highest unprotected opening to adjoining spaces, or 6 ft (1830 mm) above the highest floor level of exit access open to the atrium, for a period equal to 1½ times the calculated egress time or 20 minutes, whichever is greater. (6)* An engineered smoke control system is installed to meet the requirements of (5) and is independently activated by each of the following: (a) Upon actuation of the required automatic sprinkler system within the atrium or areas open to the atrium (b) Manual controls that are readily accessible to the fire department 5
7 5000 FR424 BLD-FIR Final Action: (8.12.5) Recommendation: Convenience Openings Where permitted by Chapters 15 through 31, and 33 through 34, unenclosed vertical openings not concealed within the building construction shall be permitted as follows: (1) Such openings shall connect not more than two adjacent stories (one floor pierced only). (2) Such openings shall be separated from unprotected vertical openings serving other floors by a barrier complying with (3) Such openings shall be separated from corridors. (4)*Such openings shall be separated from other fire or smoke compartments on the same floor. (5) In new construction, the convenience Such openings shall be separated from the corridor referenced in (3) by a smoke partition, unless Chapters 15 through 31, and 33 through 34 require the corridor to have a fire resistance rating. (6)*Such openings shall not serve as a required means of egress FR409 BLD-FIR Final Action: ( ) Recommendation: Where permitted by Chapters 15 through 31, and 33 through 34, unenclosed vertical openings created by convenience stairways shall be permitted as follows: (1) The convenience stair openings shall not serve as required means of egress. (2) The building shall be protected throughout by an approved, supervised automatic sprinkler system in accordance with Section (3) The convenience stair openings shall be protected in accordance with the method detailed for the protection of vertical openings in NFPA 13, Standard for the Installation of Sprinkler Systems. (4) The area of the floor opening shall not exceed twice the horizontal projected area of the stairway FR425 BLD-FIR Final Action: ( ) Service openings for conveyors, elevators, and dumbwaiters, where required to be open on more than one story at the same time for purposes of operation, shall be provided with closing devices in accordance with
8 5000 FR426 BLD-FIR Final Action: ( ) Any concealed combustible space in which building materials having a flame spread index greater than Class A are exposed shall be draftstopped as follows: (1) Every exterior and interior wall and partition shall be firestopped at each floor level, at the top story ceiling level, and at the level of support for roofs. (12) Every unoccupied attic space shall be subdivided by draftstops into areas not to exceed 3000 ft2 (280 m2). (23) Any concealed space between the ceiling and the floor or roof above shall be draftstopped for the full depth of the space along the line of support for the floor or roof structural members and, if necessary, at other locations to form areas not to exceed 1000 ft2 (93 m2) for any space between the ceiling and floor and 3000 ft2 (280 m2) for any space between the ceiling and roof FR427 BLD-FIR Final Action: ( ) Recommendation: The requirements of shall not apply if either of the following conditions is met where any of the following conditions are met: (1) The requirements shall not apply where the concealed space is protected throughout by an approved automatic sprinkler system in accordance with NFPA 13. Where the space is protected throughout by an approved automatic sprinkler system in accordance with NFPA 13 (2)* The requirements shall not apply to concealed spaces serving as plenums. Where concealed spaces serve as plenums 5000 FR429 BLD-FIR Final Action: ( ) Draftstopping materials shall be not less than 1/2 in. (13 mm) gypsum board, 15/32 in. (12 mm) wood structural panel, or other approved materials that are adequately supported FR430 BLD-FIR Final Action: (8.15.2(1)) Where protection is provided with automatic extinguishing systems without fire resistance rated separation, the space protected shall be enclosed with smoke partitions in accordance with Section 8.10, unless otherwise permitted by one of the following: (1) This requirement shall not apply to mercantile occupancy general storage areas and stockrooms protected by automatic sprinklers in accordance with NFPA 13 Section
9 5000 FR405 BLD-FIR Final Action: (8.15.4) Recommendation: * Alcohol-Based Hand-Rub Dispensers. Where permitted by Chapters 15 through 31, and 33 through 34, alcohol-based hand-rub dispensers shall be permitted provided they meet all of the following criteria: (1) The maximum individual dispenser fluid capacity shall be as follows: (a) 0.32 gal (1.2 L) for dispensers in corridors and areas open to corridors. (b) 0.53 gal (2.0 L) for dispensers in rooms or suites of rooms separated from corridors. (2) Where aerosol containers are used, the maximum capacity of the aerosol dispenser shall be 18 oz. (0.51 kg) and shall be limited to Level 1 aerosols as defined in NFPA 30B, Code for the Manufacture and Storage of Aerosol Products (3) Dispensers shall be separated from each other by horizontal spacing of not less than 48 in. (1220 mm). (4) Not more than an aggregate 10 gal (37.8 L) of alcohol-based hand-rub solution or 1135 oz (32.2 kg) of Level 1 aerosols, or a combination of liquids and Level 1 aerosols not to exceed, in total, the equivalent of 10 gal (37.8 L) or 1135 oz (32.2 kg,) shall be in use outside of a storage cabinet in a single smoke compartment, or fire compartment or story whichever is less in area. One dispenser complying with (1) per room and located in that room shall not be included in the aggregated quantity (5) Storage of quantities greater than 5 gal (18.9 L) in a single smoke compartment or fire compartment or story, whichever is less in area, shall meet the requirements of NFPA 30, Flammable and Combustible Liquids Code. (6) Dispensers shall not be installed in the following locations: (a) Above an ignition source for a horizontal distance of 1 in. (25 mm) to each side of the ignition source (b) To the side of an ignition source within a 1 in. (25 mm) horizontal distance from the ignition source (c) Beneath an ignition source within a 1 in. (25 mm) vertical distance from the ignition source (7) Dispensers installed directly over carpeted floors shall be permitted only in sprinklered areas of the building. (8) The alcohol-based hand-rub solution shall not exceed 95 percent alcohol content by volume. (9) Operation of the dispenser shall comply with the following criteria: (a) The dispenser shall not release its contents except when the dispenser is activated, either manually or automatically by touch-free activation. (b) Any activation of the dispenser shall only occur when an object is placed within 4 in. (100 mm) of the sensing device. (c) An object placed within the activation zone and left in place shall not cause more than one activation. (d) The dispenser shall not dispense more solution than the amount required for hand hygiene consistent with label instructions (e) The dispenser shall be designed, constructed and operated in a manner that ensures accidental or malicious activation of the dispensing device is minimized. (f) The dispenser shall be tested in accordance with the manufacturer s care and use instructions each time a new refill 8
10 is installed FR431 BLD-FIR Final Action: ( (New) ) Recommendation: Add new section to read as follows: * Explosion Protection. Where hazardous processes or storage is of such a character as to introduce an explosion potential, an explosion venting system or an explosion suppression system specifically designed for the hazard involved shall be provided FR403 BLD-FIR Final Action: (8.17) 8.17 Rubbish Waste Chutes and Laundry Linen Chutes Openings through floors for rubbish waste chutes and laundry linen chutes shall be separately enclosed by fire barrier walls constructed in accordance with the provisions of Section 8.4 and having a fire resistance rating in accordance with the provisions of Section Inlet openings serving waste and linen chutes shall be protected in accordance with Section Doors of rubbish waste chutes and laundry linen chutes shall open only to a room that is designed and used exclusively for accessing the chute opening, except as modified by Rubbish waste chutes and laundry linen chutes shall be permitted to open into rooms not exceeding 400 ft 2 (37.2 m 2 ) in area used for storage, provided that the room is protected by automatic sprinklers FR401 BLD-FIR Final Action: (A.8.1.3) Recommendation: A The test procedures set forth in fire test methods referenced in make no provision for testing automatic fire suppression systems or water sprays in conjunction with structural members or assemblies tested in vertical or horizontal fire resistance furnaces FR410 BLD-FIR Final Action: (A ) A.8.2 A NFPA 251, Standard Methods of Tests of Fire Resistance of Building Construction and Materials, ANSI/UL 263, Standard for Fire Tests of Building Construction and Materials, and ASTM E 119, Standard Test Methods for Fire Tests of Building Construction and Materials, are considered nationally recognized methods of determining fire resistance ratings and have been found to yield equivalent test results. (Note to editor: Remove asterisk from 8.2 and relocate to ) 9
11 5000 FR413 BLD-FIR Final Action: (A ) A The intent of this provision is to permit the provisions of either ASCE/SFPE 29, Standard Calculation Methods for Structural Fire Protection, or ACI 216.1/TMS , Standard Method for Determining Fire Resistance of Concrete and Masonry Code Requirements for Determining Fire Resistance of Concrete and Masonry Construction Assemblies, to be used for the calculation of fire resistance of concrete or masonry elements or assemblies 5000 FR435 BLD-FIR Final Action: (A (New) ) Recommendation: Add new text to read as follows: A Where the construction meets the provisions of (1), (2) or (2), the required exterior wall fire resistance rating is for fire exposure from the inside only. [221, A.6.9.2] 5000 FR407 BLD-FIR Final Action: (A.8.8.2) Recommendation: Add new text to read as follows: A Firestop materials become systems when installed to the listed firestop system design from an accredited testing laboratory. Installation of firestop materials to the listed system should meet all limitations of the system. FM 4991, Standard for the Approval of Firestop Contractors and the UL Qualified Firestop Contractor Program both provide a quantified qualification of the firestop installer who understands the detailed installation requirements. Where the configuration of a penetrating item or group of items is such that a listed system is determined to be nonexistent and reconfiguration of the penetrations or fire resistance rated assembly is determined to be impractical or impossible, alternative methods for maintaining the integrity of the required fire resistance rating of the assembly should be permitted to be established using an engineering analysis based on a comparison of listed systems prepared by a manufacturer s technical representative of the systems specified, by the laboratory that conducted the original test, or by a professional engineer. ASTM E 2174, Standard Practice for On-Site Inspection of Installed Fire Stops, provides guidance for the inspection of through-penetration fire stop systems tested in accordance with ASTM E 814, Standard Test Method for Fire Tests of Through-Penetration Fire Stops, and ANSI/UL 1479, Standard for Fire Tests of Through-Penetration Firestops. 10
12 5000 FR408 BLD-FIR Final Action: (A ) Recommendation: A Materials used to protect joints become systems when installed to the listed joint system design from an accredited testing laboratory. Installation of joint materials to the listed system should meet all limitations of the system. FM 4991, Standard for the Approval of Firestop Contractors and the UL Qualified Firestop Contractor Program both provide a quantified qualification of the joint system installer who understands the detailed installation requirements. Where the configuration of a joint is such that a listed system is determined to be nonexistent and reconfiguration of the joint or fire resistance rated assembly is determined to be impractical or impossible, alternative methods for maintaining the integrity of the required fire resistance rating of the assembly should be permitted to be established using an engineering analysis based on a comparison of listed systems prepared by a manufacturer s technical representative of the systems specified, prepared by the laboratory that conducted the original test, or by a professional engineer. On-site inspection of firestopping is important in maintaining the integrity of any vertical or horizontal fire barrier. Two standard practice documents were developed with the ASTM process to allow inspections of through-penetration firestops, joints, and perimeter fire barrier systems. ASTM E 2393, Standard Practice for On-Site Inspection of Installed Fire Resistive Joint Systems and Perimeter Fire Barriers, provides guidance for the inspection of fire-resistive joints and perimeter fire barrier joint systems tested in accordance with the requirements of ASTM E 1966, Standard Test Method for Fire-Resistive Joint Systems, or with ANSI/UL 2079, Standard for Tests for Fire Resistance of Building Joint Systems. ASTM E 2393 contains a standardized report format, which would lead to greater consistency for inspections 5000 FR419 BLD-FIR Final Action: (A ) Recommendation: A Openings might include items such as stairways, hoistways for elevators, dumbwaiters, and inclined and vertical conveyors; and shaftways used for light, ventilation, or building services. A Openings might include items such as stairways; hoistways for elevators, dumbwaiters, and inclined and vertical conveyors; shaftways used for light, ventilation, or building services; or expansion joints and seismic joints used to allow structural movements FR423 BLD-FIR Final Action: (A ) Recommendation: A Where atriums are used, there is an added degree of safety to occupants because of the large volume of space into which smoke can be dissipated. However, there is a need to ensure that dangerous concentrations of smoke are promptly removed from the atrium, and the exhaust system needs careful design. For information about systems that can be used to provide smoke protection in these spaces, see the following: (1) NFPA 92, Standard for Smoke Control Systems (2) Design of Smoke Management Systems by J.H. Klote and J.A.Milke (2) Principles of Smoke Management 11
13 5000 FR402 BLD-FIR Final Action: (A (3)) Recommendation: Add text to read as follows: A (3) Draftstops defined in the requirements of NFPA 13, Standard for the Installation of Sprinkler Systems, are curtain style descending from the ceiling surface or ceiling plane 5000 FR428 BLD-FIR Final Action: (A (2)) Recommendation: Add new annex language as follows: A (2) See NFPA 90A, Standard for the Installation of Air-Conditioning and Ventilating Systems FR406 BLD-FIR Final Action: (A and A ) Recommendation: Add a new section to read: A The total quantities of flammable liquids in any area should comply with the provisions of other recognized codes, including NFPA 1, Fire Code, and NFPA 30, Flammable and Combustible Liquids Code. In addition, special consideration should be given to the following: (1) Obstructions created by the installation of hand-rub solution dispensers (2) Location of dispensers with regard to adjacent combustible materials and potential sources of ignition, especially where dispensers are mounted on walls of combustible construction (3) Requirements for other fire protection features, including complete automatic sprinkler protection, to be installed throughout the compartment (4) Amount and location of the flammable solutions, both in use and in storage, particularly with respect to potential for leakage or failure of the dispenser 5000 FR436 BLD-FIR Final Action: (A ) Recommendation: Add new text to read as follows: A For details, see NFPA 68, Standard on Explosion Protection by Deflagration Venting. 12
FIRE-RESISTANCE-RATED CONSTRUCTION
CHAPTER 7 FIRE-RESISTANCE-RATED CONSTRUCTION SECTION 70 GENERAL 70. Scope. The provisions of this chapter shall govern the materials and assemblies used for structural fire resistance and fire-resistance-rated
More informationFIRE-RESISTANCE-RATED CONSTRUCTION
CHAPTER 7 FIRE-RESISTANCE-RATED CONSTRUCTION SECTION 70 GENERAL 70. Scope. The provisions of this chapter shall govern the materials and assemblies used for structural fire resistance and fire-resistance-rated
More informationExcerpts from the Canadian National Building Code (NBC)
Excerpts from the Canadian National Building Code (NBC) Reproduced here with Permission of the Copyright Owner, the National Research Council of Canada, Institute for Research in Construction. For more
More informationFIRE AND SMOKE PROTECTION FEATURES
CHAPTER 7 FIRE AND SMOKE PROTECTION FEATURES SECTION 70 GENERAL 70. Scope. The provisions of this chapter shall govern the materials, systems and assemblies used for structural fire resistance and fire-resistance-rated
More informationFIRE AND SMOKE PROTECTION FEATURES
CHAPTER 7 FIRE AND SMOKE PROTECTION FEATURES SECTION 70 GENERAL 70. Scope. The provisions of this chapter shall govern the materials, systems and assemblies used for structural fire resistance and fire-resistance-rated
More informationFebruary 2014 Alberta Fire Code 4.2.6.3. Page 1 of 5. Fire Safety and Hand Hygiene in Healthcare Facilities
FIRE CODE VARIANCE February 2014 Alberta Fire Code 4.2.6.3. Page 1 of 5 ISSUE: Fire Safety and Hand Hygiene in Healthcare Facilities This Variance covers alcohol based hand hygiene products used in healthcare
More informationA ROAD MAP FOR YOUR CODE, SMOKE BARRIER & SMOKE PARTITION REQUIREMENTS
A ROAD MAP FOR YOUR CODE, SMOKE BARRIER & SMOKE PARTITION REQUIREMENTS International Code Council National Fire Protection Association Underwriters Laboratories Inc. 5203 Leesburg Pike, Suite 600 1 Batterymarch
More informationBuilding Code Clarifications - 7. Fire Resistance
Building Code Clarifications - 7. Fire Resistance 7.1 (15-12-030) Use of combustibles in Type III construction roof assemblies Code Section (15-12-030) Use of Combustibles was revised on May 17, 2000,
More informationHCD DSA OSHPD 1 2 1/AC AC SS SS/CC 1 2 3 4 2013 CALIFORNIA BUILDING CODE 199
CALIFORNIA BUILDING CODE MATRIX ADOPTION TABLE CHAPTER 7 FIRE AND SMOKE PROTECTION FEATURES (Matrix Adoption Tables are non-regulatory, intended only as an aid to the user. See Chapter for state agency
More information- 5 - Table1. Maximum Compartment Volumes
- 5 - Part II - SPECIFIC REQUIREMENTS 5. Compartmentation 5.1 Every building should be divided into compartments by walls and floors to inhibit the spread of fire. 5.2 Compartment walls, compartment floors,
More informationNFPA 101 SAF-FIR PUBLIC COMMENTS
Page 50 of 195 8.2.3.1.2 ] Public Comment No. 82-NFPA 101-2013 [ New Section after 8.2.3.1.3* The fire resistance rating of an element or assembly determined by tests conducted in accordance with NFPA
More informationCertification: Building Plans Examiner. Exam ID: B3
Certification: Building Plans Examiner Exam ID: B3 Scope: A Building Plans Examiner will be responsible for reviewing submitted plans to determine if they meet the requirements of the various Building
More informationHealthcare Engineering. Code Summary Report
American Society for Healthcare Engineering Code Summary Report CODE SUMMARY HEALTH CARE NEW BUILDINGS This code summary is based on the following codes: 2000 Edition NFPA 101, The Life Safety Code (LSC),
More informationFIRESTOPPING & SMOKE SEALS
SPECIFICATION SECTION 07 84 00 FIRESTOPPING & SMOKE SEALS 1 GENERAL 1.1 SECTION INCLUDES 1.1.1 Comply with Division 1, General Requirements and Documents referred to therein. 1.1.2 It is the intent of
More informationNew Ambulatory Health Care Occupancies
NFPA 101 Substantiation: The changes proposed to NFPA 101 Chapter 20, New Ambulatory Health Care Occupancies, make the chapter a stand-alone set of requirements that do not reference the use of the provisions
More informationOntario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal
Ontario Fire Code SECTION 5.13 DIP TANKS Illustrated Commentary Office of the Ontario Fire Marshal Dip Tanks Illustrated Commentary 1 5.13.1. Location 5.13.1.1. Dip tank operations involving flammable
More informationNew Ontario Building Code Requirements for Mid-rise Wood Frame Buildings
New Ontario Building Code Requirements for Mid-rise Wood Frame Buildings Note: This information addresses complex issues in a summary fashion. Consideration should be given to the official version of the
More informationGeneral Fire Code Requirements Within Commercial Tenant Spaces
FIRE DEPARTMENT in cooperation with Scope: General Fire Code Requirements Within Commercial Tenant Spaces This handout is designed to assist owners, architects, contractors and others in understanding
More informationThis handout is a guide only and does not contain all of the requirements of the Minnesota State Building Code or city ordinances.
Basement Finishing Guide Community Development Department Building Inspections Division 5200 85 th Avenue North / Brooklyn Park, MN 55443 Phone: (763) 488-6379 / Fax: (763) 493-8171 6/15 www.brooklynpark.org
More informationRESIDENTIAL PLUMBING ALTERATIONS PERMIT REQUIREMENTS
RESIDENTIAL PLUMBING ALTERATIONS PERMIT REQUIREMENTS The following guidelines are intended to assist with the permit acquisition process with regard to Plumbing Alterations. Not all information, or additional
More informationErrata has been identified as follows:
2009 IFC Performing Commercial Fire Inspections Inventory Number: 1424S09 Second Printing; July 2014 Changes HAVE been made- Third Printing: September 2014 Errata has been identified as follows: 1. Page
More informationThe Accord on Fire and Building Safety in Bangladesh Building Standard
The Accord on Fire and Building Safety in Bangladesh Building Standard December 30, 2013 TABLE OF CONTENTS 1 Part 1 Scope and Definitions... 1 2 Part 2 Administration and Enforcement... 5 3 Part 3 General
More informationLIFE SAFETY UPDATE. FULL SPRINKLERING OF ALL NURSING FACILITIES ADDITIONAL CLARIFICATIONS Prepared by Eric Rosenbaum, P.E. Hughes Associates, Inc.
LIFE SAFETY UPDATE FULL SPRINKLERING OF ALL NURSING FACILITIES ADDITIONAL CLARIFICATIONS Prepared by Eric Rosenbaum, P.E. Hughes Associates, Inc. The purpose of this update is as follows: Remind all state
More informationStandards Revisions Related to the Centers for Medicare & Medicaid Services CoPs
Standards Revisions Related to the Centers for Medicare & Medicaid Services CoPs EC.003.01 The hospital manages fire risks. 9. 10. Elements of Performance for EC.003.01 The hospital minimizes the potential
More informationTerms and Definitions In Canada
Terms and Definitions In Canada Most of the following terms and definitions are taken directly from the National Building Code and referenced Test Methods. Learning these terms will provide an important
More informationCOMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES
COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES These guidelines are to be used for ALL commercial cooking hoods, ventilation systems and related fire suppression
More informationBuilding Codes Update: The 2009 International Fire Code and the Apartment Industry
! Building Codes Update: The 2009 International Fire Code and the Apartment Industry Apartment operators and developers should be aware of organizational changes in the 2009 edition of the International
More informationSpray Booth Guideline
Department of Development Service 135 North D Street, Perris CA. 92570 Phone: (951) 443-1029 Fax: (951) 943-3293 PURPOSE The intent of this guideline is to provide the information necessary to ensure that
More informationFire Barriers & Fire Stopping
Presented by: Bill Lauzon, PE Lauzon Life Safety Consulting, LLC 262-945-4567 Lauzon.lsc@gmail.com Web: Lauzon-LSC.com Environmental Part 2 Life Safety Code Chapter 8 Fire Barriers & Fire Stopping 1 Fire
More informationA Code Review for Emergency Generators and Indoor Use of Portable Generators
A Code Review for Emergency Generators and Indoor Use of Portable Generators By: the Fire and Life-Safety Group (FLS) Fire Code requires that emergency generators be stationary generators. Therefore, a
More informationTremco Fire Protection Systems Group Technical Bulletin
Compartmentalization products and design play a key role in protecting lives and property from fire. Understanding the tools and techniques available for firestopping is of utmost importance to designers,
More informationDesign Options (Tradeoffs) Allowed by the 2012 Building Codes for Properties with Sprinkler Systems. April 2013
Design Options (Tradeoffs) Allowed by the 2012 Building Codes for Properties with Sprinkler Systems April 2013 The National Multi Housing Council and the National Apartment Association (NMHC/NAA) have
More informationPage 4 of 17. Committee Input NFPA 101 Coordinate Smoke detector versus smoke alarm terminology.
Page 1 of 17 Page 2 of 17 Committee Input NFPA 101 Coordinate Smoke detector versus smoke alarm terminology. CODE PARAGRAPH WITH SUGGESTED CHANGES: 6.4.6.1.2 Residents should be rated as response probable
More informationCode Requirements for Existing Buildings
Code Requirements for Existing Buildings Kevin S. Hastings, P.E., LEED AP R. W. Sullivan, Inc. 529 Main St., Suite 203 Charlestown, MA (617) 523-8227 www.rwsullivan.com R.W. Sullivan Engineering (RWS)
More informationEducational. Educational-Existing 1/28/2014. OCCUPANT LOADS [no change] Application. Application
February 2014 Code Requirements and Inspections in Educational Occupancies Presented By: Barry W. Rickert Douglas M. Schanne Fire Marshal Training Program Supervisor Office of Education & Data Management
More informationThe Source of Firestop Expertise SM
The Source of Firestop Expertise SM Inspector Pocket Guide The following information is intended to provide construction and code enforcement professionals with basic checkpoints to ensure that the required
More informationWe hope these Frequently Asked Questions will be of use both to municipal officials and fire inspectors.
September 14, 2012 Dear AMM Member: Please see the attached Fire Code Frequently Asked Questions. This document was compiled by the Office of the Fire Commissioner at the AMM s request to help clarify
More informationGeneral Safety & Health Standards Published by the Division of Building Safety In Cooperation with the Idaho Industrial Commission
General Safety & Health Standards Published by the Division of Building Safety In Cooperation with the Idaho Industrial Commission Local Fire Alarm 064. FIRE ALARM SYSTEMS 01. Scope 02. Definitions 03.
More informationOverview of Hotel Fire Safety Requirements
Overview of Hotel Fire Safety Requirements in the Fire Code Susan Clarke, P.Eng. Office of the Fire Marshal - January 10, 2012 1 Agenda Regulation History - Hotels Fire Code Overview (Parts 1 to 8) Defined
More informationCHAPTER 6 CONSTRUCTION TYPES
CHAPTER 6 CONSTRUCTION TYPES SECTION 601 GENERAL 601.1 Scope. Provisions of this chapter shall govern the classification of construction type by materials and fire resistance of its elements and the use
More informationCh. 58 DIVISION D-O 34 CHAPTER 58. DIVISION D-O ORDINARY COMMERCIAL, INDUSTRIAL, OFFICE OCCUPANCY GROUP CONSTRUCTION TYPE MAXIMUM STORY HEIGHT
Ch. 58 DIVISION D-O 34 CHAPTER 58. DIVISION D-O ORDINARY COMMERCIAL, INDUSTRIAL, OFFICE Sec. 58.1. Division D-O occupancies. 58.2. Separation and mixed occupancy. OCCUPANCY GROUP CONSTRUCTION TYPE MAXIMUM
More informationIndiana Building Rehabilitation Standard
Rule 8. Indiana Building Rehabilitation Standard 675 IAC 12-8-1 Definitions Sec. 1. The following definitions apply throughout this rule: (1) "Building code" means the Indiana Building Code under 675 IAC
More informationREVEWED BY: Ross Rogien B.O/P.R. ADDITIONAL REVIEW(S) REQ.-FIRE DEPT Y/N
PLAN REVIEW FOR: PROJECT NAME: OWNER: ARCH/DESIGNER: ADDRESS: Ph/Fx: Plans Dated: E-mail: Sealed By: Estimated Project Cost - $ REVEWED BY: Ross Rogien B.O/P.R. ADDITIONAL REVIEW(S) REQ.-FIRE DEPT Y/N
More informationCurrent as of 11/10/08 1 of 1
BEST PRACTICES STANDARDS FOR SCHOOLS UNDER CONSTRUCTION OR BEING PLANNED FOR CONSTRUCTION I. Site Layout A. School buildings shall be provided with a securable perimeter. A securable perimeter means that
More informationRequirements for Hydrogen Storage and Use
Requirements for Hydrogen Storage and Use I. INTRODUCTION Fire and Life-Safety Group (FLS) The following is a summary of the fire and building code requirements for the storage and use of hydrogen. These
More informationCHAPTER 6 DUCT SYSTEMS
CHAPTER 6 DUCT SYSTEMS SECTION MC 601 GENERAL 601.1 Scope. Duct systems used for the movement of air in air-conditioning, heating, ventilating and exhaust systems shall conform to the provisions of this
More informationADMINISTRATIVE SERVICES MANUAL
Purpose Responsibilities Proper Storage and use of flammable liquids can significantly reduce the possibility of accidental fires and injuries. To minimize risk to life and properly, the requirements of
More informationVestibule Case Study. Vestibule Requirement Intent [2003 IECC, 2006 IECC, 2003 IBC, 2006 IBC, 90.1-2001, 90.1-2004]
Vestibule Case Study [2003 IECC, 2006 IECC, 2003 IBC, 2006 IBC, 90.1-2001, 90.1-2004] Vestibule Requirement Intent Page 1 of 14 The primary intent behind the requirement for a vestibule is to reduce infiltration
More informationHow To Make A House Safe
1 RESIDENTIAL Screen Enclosures Orange County Residential Code Compliance Alternative design method for screen enclosures R301.2.1.1.3 PLAN REVIEW Engineered plans must state that the Alternative Design
More informationTYPICAL FIRE SAFETY INSPECTION VIOLATIONS
TYPICAL FIRE SAFETY INSPECTION VIOLATIONS The following is a list of typical violations often found by inspectors and a generic solution. You can use this list to improve the safety of your facility, to
More informationAustralian/New Zealand Standard
Australian/New Zealand Standard The use of ventilation and air conditioning in buildings - Part 1: Fire and smoke control in buildings UPDATED AS/NZS 1668.1:2015 What is the scope of this Standard? The
More informationCHAPTER 9 FIRE PROTECTION SYSTEMS
CHAPTER 9 FIRE PROTECTION SYSTEMS SECTION 901 GENERAL 901.1 Scope. Provisions of this chapter shall govern the application, design, installation, testing and maintenance of automatic sprinklers, standpipes
More informationDUCT SYSTEMS CHAPTER 6
CHAPTER 6 DUCT SYSTEMS SECTION 601 GENERAL 601.1 Scope. Duct systems used for the movement of air in air-conditioning, heating, ventilating and exhaust systems shall conform to the provisions of this chapter
More informationFlorida Building Code 2004 SECTION 1009 STAIRWAYS AND HANDRAILS
Florida Building Code 2004 SECTION 1009 STAIRWAYS AND HANDRAILS 1009.1 Stairway width. The width of stairways shall be determined as specified in Section 1005.1, but such width shall not be less than 44
More informationFIRE SAFETY SELF-INSPECTION FORM FOR CULTURAL INSTITUTIONS. 1. All Floors (inspect from top floor to basement): Yes No
General Inspection FIRE SAFETY SELF-INSPECTION FORM FOR CULTURAL INSTITUTIONS 1. All Floors (inspect from top floor to basement): Yes are fire exits and directional signs properly illuminated? is the emergency
More informationFIRE SAFETY SELF-INSPECTION FORM FOR CULTURAL INSTITUTIONS
FIRE SAFETY SELF-INSPECTION FORM FOR CULTURAL INSTITUTIONS The attached self-inspection form is intended for staff use at regular, frequent intervals. It should not take the place of two other vital measures
More informationNFPA 101 2012 SELECT SIGNIFICANT CHANGES
NFPA 101 2012 SELECT SIGNIFICANT CHANGES William E. Koffel, P.E., FSFPE President Koffel Associates, Inc. www.koffel.com wkoffel@koffel.com Expertly Engineering Safety From Fire INTRODUCTION NFPA 101 is
More informationRequired Certification Documentation. Contractor's installation certification for range hood fire suppression systems.
OFFICE OF UNIVERSIT BUILDING OFFICIAL PROJECT/CONSTRUCTION MAGER: Sample Manager Required Aboveground only Required Certification Documentation Contractor s material and test certifications for both above
More informationFIRE SAFETY SURVEY REPORT 2000 CODE - HEALTH CARE Medicare Medicaid
DEPARTMENT OF HEALTH AND HUMAN SERVICES CENTERS FOR MEDICARE & MEDICA SERVICES FIRE SAFETY SURVEY REPORT - HEALTH CARE Medicare Medicaid 1. (A) PROVER NUMBER K1 K2 PART I Life Safety Code, New and Existing
More informationREFERENCE STANDARD RS 13 MECHANICAL VENTILATION, AIR CONDITIONING, AND REFRIGERATION SYSTEMS * LIST OF REFERENCED NATIONAL STANDARDS
REFERENCE STANDARD RS 13 MECHANICAL VENTILATION, AIR CONDITIONING, AND REFRIGERATION SYSTEMS * LIST OF REFERENCED NATIONAL STANDARDS **NFiPA 90A Standard for the Installation of Air Conditioning and Ventilating
More informationNotes. Material 1. Appropriate Flammable Liquids
29 CFR 1910.106 Flammable Materials Flammable Liquids Preparation 1. Read Applicable Background information and related Company Policy Chapter. 2. Make Copies of this Lesson Plan for Personnel 3. Make
More informationIn accordance with NFPA 30, these containers are not to store Class I flammable liquids.
In accordance with NFPA 30, these containers are not to store Class I flammable liquids. Zurich recommends storing these containers in dedicated liquid storage rooms, detached buildings, or in listed dispensing
More informationExit Routes, Emergency Action Plans, Fire Prevention Plans, and Fire Protection. OSHA Office of Training and Education 1
Exit Routes, Emergency Action Plans, Fire Prevention Plans, and Fire Protection OSHA Office of Training and Education 1 Introduction Fires and explosions kill more than 200 and injure more than 5,000 workers
More informationCHILD CARE CENTER INFORMATION SHEET
CHILD CARE CENTER INFORMATION SHEET SECTION 1 INTRODUCTION This fire safety information sheet is based on the 2007 Minnesota State Fire Code (MSFC) and the 2007 Minnesota State Building Code (MSBC). It
More informationArea of Rescue Assistance Communication System ADA Code Applicable excerpts:
Area of Rescue Assistance Communication System ADA Code Applicable excerpts: CONTENTS (Guidelines and Definitions) Page 1 Area of Rescue Assistance Requirements Page 2 Emergency Communication Equipment
More informationMINIMUM STANDARDS FOR HIGH-RISE BUILDINGS
CHAPTER 93 MINIMUM STANDARDS FOR HIGH-RISE BUILDINGS Note: Chapter 93 is entirely Seattle amendments to the International Fire Code and is not underlined. Point of Information The requirements of this
More informationDecree of the Ministry of the Environment on fire safety of ventilation systems
THE NATIONAL BUILDING CODE OF FINLAND MINISTRY OF THE ENVIRONMENT Housing and Building Department Decree of the Ministry of the Environment on fire safety of ventilation systems Adopted in Helsinki, 18
More information2010 FLORIDA BUILDNG CODE, FIRE AND LIFE SAFETY i
2010 FLORIDA BUILDNG CODE, FIRE AND LIFE SAFETY i Changes between the 2006 and 2009 Editions of the International Codes account for the vast majority of changes to the 2010 Florida Building Code. In many
More informationSingle Family Residential Basement Finish
How to Use This Guide Building Guide Pottawattamie County Planning & Development Department Building & Safety Division Single Family Residential Basement Finish Provide two (2) sets of plans and complete
More information2014 British Columbia Building Code Changes
District of Houston 250-845-2238 2014 British Columbia Building Code Changes A District of Houston interpretation of the 2014 Building Code Changes for 9.36 & 9.32 The following changes reflect the most
More informationSample Written Program. For. Flammable Liquids
Sample Written Program For Flammable Liquids 1 Flammable Liquids. (YOUR COMPANY NAME) Purpose Proper Storage and use of flammable liquids can significantly reduce the possibility of accidental fires and
More informationPollution CO CO 2. Carbonaceo us soot H 2 S, NOX, SO2
Pollution CO CO 2 Carbonaceo us soot H 2 S, NOX, SO2 The National Building Code (NBC) contains set of minimum provisions, designed to protect the safety of the public with regard to structural sufficiency,
More information2012 CODES SIGNIFICANT CHANGES 2012 IBC
2012 CODES SIGNIFICANT CHANGES 2012 IBC 1. Section 303.4 added language that includes commercial kitchens which are associated with restaurants, cafeterias, and similar dining facilities to be classified
More information2007 ICC FINAL ACTION AGENDA
907.2.1.1 System initiation in Group A occupancies with an occupant load of 1,000 or more. Activation of the fire alarm in Group A occupancies with an occupant load of 1,000 or more shall initiate a signal
More informationFire-Rated Glass and Glazing START
Fire-Rated Glass and Glazing START www.pilkington.com/fire Fire-Rated Glass and Glazing Pilkington Fire Protection Glass North America 946 Kane Street, Suite A Toledo, OH 43612 Provider Number: J200 Course
More informationHealthandSafetyOntario.ca. Introduction. Storage Containers. Storing Flammable Liquids
Flammable Liquids Storage Introduction This guideline is designed to help you store flammable liquids safely. It is based on the requirements of the Ontario Fire Code, Part 4, and of the Regulations for
More informationLIQUEFIED PETROLEUM GASES
CHAPTER 38 LIQUEFIED PETROLEUM GASES SECTION 3801 GENERAL 3801.1 Scope. Storage, handling and transportation of liquefied petroleum gas (LP-gas) and the installation of LP-gas equipment pertinent to systems
More informationHealth Care Facilities
Health Care Facilities CHAPTER 25 Joseph M. Jardin A large Illinois hospital undergoing a sprinkler retrofit quickly discovered the benefits of upgrading its system when sprinklers confined a fire caused
More informationSPACE TYPE: LABORATORY (WET) FOR CHEMISTRY AND BIOLOGY
SPACE TYPE: LABORATORY (WET) FOR CHEMISTRY AND BIOLOGY Construction Criteria The unit costs for (Wet) space types are based on the construction quality and design features in the following table. This
More informationFirestopping & Fireblocking:
Firestopping & Fireblocking: By Vickie J. Lovell A discussion of the definitions of firestopping and fireblocking will help fire protection engineers clarify existing code language and sort out prevailing
More informationArapahoe County Residential Water Heater Installation and Inspection Guide
Arapahoe County Residential Water Heater Installation and Inspection Guide The attached handout is designed to be a general permit submittal and inspection guide covering most installation instances, however
More informationThe following definitions apply with regard to requirements specified in this document:
GUIDELINES FOR INSTALLATION OF TEMPORARY AND PERMANENT ABOVEGROUND DIESEL FUEL TANKS FOR EMERGENCY AND STANDBY POWER SYSTEMS LOCATED OUTSIDE OF BUILDINGS For Use by Unidocs Member Agencies or where approved
More informationRetardants Inc. The Decision You Make May Save A Life! 123 Columbia Court North Suite 201 Chaska, MN 55318
Fire Barrier Moldable Putty+ Pads 123 Columbia Court North Suite 201 Chaska, MN 55318 952-448-7377 FAX:952-448-2613 e-mail: info@fireretardantsinc.com Visit Our Web Site at www.fireretardantsinc.com Protecting
More informationGENERAL FIRE SAFETY TERMS & DEFINITIONS
UCL Fire Technical Note - TN006 Fire Safety Technical Guide GENERAL FIRE SAFETY TERMS & DEFINITIONS Reference: BS4422-2005 Fire Safety Vocabulary - for further information and definitions BS EN ISO 13943-2000:
More informationBasic Fire Door Requirements
TECHNICAL DATA SERIES S D I 118-01 Basic Fire Door Requirements 2001 Steel Door Institute STEEL DOOR INSTITUTE 30200 DETROIT ROAD - CLEVELAND, OHIO 44145 Technical Data Series SDI 118-2001 Basic Fire Door
More informationHow to Install Modular Wiring, Cabling and Air Distribution Devices beneath a Access Floor without a Fire Suppression System
How to Install Modular Wiring, Cabling and Air Distribution Devices beneath a Access Floor without a Fire Suppression System July 28, 2003 We are pleased to provide the following joint statement by CII,
More informationSafe Operating Procedure
Safe Operating Procedure (Revised 07/09) HOT WORK PERMIT OPERATIONS (For assistance, please contact EHS at (402) 472-4925, or visit our web site at http://ehs.unl.edu/) Authority In recognition of the
More informationMINNESOTA STATE DEPARTMENT OF PUBLIC SAFETY
MINNESOTA STATE DEPARTMENT OF PUBLIC SAFETY State Fire Marshal Division 444 Cedar Street, Suite 145, St. Paul, Minnesota 55101-5145 Phone: 651/201-7200 FAX: 651/215-0525 TTY: 651/282/6555 Internet: http://www.fire.state.mn.us
More informationEthanol Vehicle and Infrastructure Codes and Standards Citations
Ethanol Vehicle and Infrastructure Codes and Standards Citations This document lists codes and standards typically used for U.S. ethanol vehicle and infrastructure projects. To determine which codes and
More informationOREGON FIRE CODE Interpretations and Technical Advisories
OREGON FIRE CODE Interpretations and Technical Advisories A collaborative service by local and state fire professionals, along with our stakeholders and customers, to provide consistent and concise application
More informationMAJOR 2015 MN RESIDENTIAL CODE CHANGES Effective Date: January 24 th, 2015
MAJOR 2015 MN RESIDENTIAL CODE CHANGES Effective Date: January 24 th, 2015 **Disclaimer: This document is to serve as informational purposes only. This is not a code book or a final interpretation of the
More informationNC Rehab Code Case Study Cheerwine Building January 17, 2002; rev 4/12/02
NC Rehab Code Case Study Cheerwine Building January 17, 2002; rev 4/12/02 PART A: Project Data and Classification 1. Project name & location Renovation of the Cheerwine Building, 322 East Council St.,
More informationSECTION FC 2706 NON-PRODUCTION CHEMICAL LABORATORIES
New York City Administrative Code - Title 29 New York City Fire Code SECTION FC 2706 NON-PRODUCTION CHEMICAL LABORATORIES 2706.1 Scope. This section shall govern the storage, handling and use of laboratory
More informationKITCHEN AND BATH REMODELING BUILDING PERMIT REQUIREMENTS
St. Louis County Department of Public Works Division of Code Enforcement KITCHEN AND BATH REMODELING BUILDING PERMIT REQUIREMENTS This guideline is intended to provide the homeowner/contractor with the
More informationFIRE PROTECTION IN THE 2008 NEW YORK CITY BUILDING CODE
FIRE PROTECTION IN THE 2008 NEW YORK CITY BUILDING CODE New York Society of Architects 24 January 2008 Presented by Joseph Razza, PE Rolf Jensen & Associates, Inc. John Lee, RA NYC Department of Buildings
More information2012 IBC & 2012 NFPA 101 Significant Means of Egress Changes. Questions. 1004.1 Design Occupant Load. 1005 - Means of Egress Capacity Determination
2012 IBC & 2012 NFPA 101 Significant Means of Egress Changes Clay Aler, P.E. Principal caler@koffel.com Andrew M. Schneider, P.E. Senior Fire Protection Engineer aschneider@koffel.com Questions Submit
More informationFIRE AND LIFE SAFETY REQUIREMENTS FOR EXISTING BUILDINGS
CHAPTER 46 FIRE AND LIFE SAFETY REQUIREMENTS FOR EXISTING BUILDINGS SECTION 4601 GENERAL 4601.1 Scope. The provisions of this chapter shall apply to existing buildings constructed prior to a state building
More informationServices Enclosures and Protected Shafts - Maintaining Compartmentation
Introduction When a fire resisting element is used to provide fire compartmentation, every opening that allows services to pass through the element must be adequately protected by sealing, or fire stopping
More informationFIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011
FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011 COLORADO SPRINGS FIRE DEPARTMENT Division of the Fire Marshal If you have any questions or comments regarding the
More information