NFPA 101 SAF-FIR PUBLIC COMMENTS
|
|
- Gladys Banks
- 7 years ago
- Views:
Transcription
1 Page 50 of ] Public Comment No. 82-NFPA [ New Section after * The fire resistance rating of an element or assembly determined by tests conducted in accordance with NFPA 251 or other approved test methods shall not be permitted to rely on an automatic fire protection system, unless evaluated as an equivalency in accordance with Section 1.4 or as part of a performance-based option in accordance with Chapter 5. Statement of Problem and Substantiation for Public Comment Page 1 of 14
2 Page 51 of 195 This proposal deals with the basics of fire resistance rated assemblies that become continuous systems when installed to the listed design. The inappropriate use of sprinkler technology in combination with construction elements to assign a fire resistance rating in accordance with ASTM E119, UL 263, or NFPA 251, creates a risk to life safety in buildings. Fire-resistance ratings represent the inherent fire resistance of an assembly or system (passive fire protection), independent of any active fire protection, (water washing). Some parties submit test reports to AHJs claiming non fire rated assemblies have fireresistance ratings that are derived from modified test standards using a flow of cooling water on the assembly surfaces during the fire test. Fire-resistance ratings are a property that is meant to represent the inherent resistance to fire of an assembly (passive fire protection), independent of any active fire protection. The code already allows the ability to reduce a fire rating once a sprinkler system and other elements are installed. This water washing of an assembly potentially doubles the trade off. Designers feel that because the atrium language permits sprinkler protection in lieu of the 1 -hour fire separation requirements that it is acceptable in other areas of buildings. ASTM E119, NFPA 251, and UL 263 make no provisions for testing such combinations to achieve fire-resistance ratings. NFPA 101provided two options that are acceptable for proving equivalency: 1. The equivalency provisions of Section Performance-based option in Chapter 5. Those are established processes that are scientific. There are several other elements to consider in addition to washing the element. Since the source of this concept for fire rating appears to be derived from the requirements for glazing used in atria, below is the the explanatory language that has existed in NFPA 101 as early as 1988 and remains in the 2012 edition: The intent of the requirement for closely spaced sprinklers to wet the atrium glass wall is to ensure that the surface of the glass is wet upon operation of the sprinklers The concept of wetting the glass that is exposed to a fire, without specifying a water application rate, is similar to boiling water in a Pyrex container over an open flame. As long as there is some water present to absorb the heat, the glass itself does not reach excessive temperatures that would cause failure [emphasis added]. Found 2012 edition of the 101 Handbook: To allow visual contact between the atrium and floors that have not been proven by engineering analysis to warrant openness, 8.6.7(1)(c) permits smoke-resisting separation consisting of glass walls, vision panels, and windows in lieu of 1-hour-rated fire barriers [emphasis added]. So the language found within the Handbook explains by use of example that the purpose of the sprinklers wetting the glazing is to prevent failure of the partition and newer language further explains that the TC is permitting a smoke-resisting separation in lieu of 1-hour. The language seems to indicate that the TC realizes that this will not be a 1-hour fire-resistance rated partition. There is just no scientific effort presented to this committee that sprinklers somehow provide and equivalent fire-resistance rating. In the last revision cycle, negative voters cited the fact that this provision, which existed in the 2009 edition of NFPA 5000 was removed. This was not done for technical reason, but rather, for consistency with NFPA 101 (NFPA 5000, Section ). The correct technical position is to include this provision in both Codes. Also, as a reminder, for the 2012 edition, the requirement passed committee, failed in the letter ballot, passed on the floor and then failed again in the letter ballot after the annual meeting. The last ballot for the 2015 edition (First Revision) failed by < 1% or 1 vote. Page 2 of 14
3 Page 52 of 195 Where the Code specifies the need for a 1-hour assembly, the intent in the development of that code provision would have clearly been to have an assembly that could survive a fire without being breached and without losing any load-bearing capabilities all by itself, without relying on an external water source of continued cooling. If sprinkler protection was also required for such occupancy, then the overall intent of the Code is to have these tow systems act independently, but in concert with each other. Submitter Information Verification Submitter Full Name: Catherine Stashak Organization: Office of the Illinois State Fire Marshal Submittal Date: Fri Apr 26 11:59:50 EDT 2013 Copyright Assignment I, Catherine Stashak, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Comment (including both the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any publication of the NFPA in which this Public Comment in this or another similar or derivative form is used. I hereby warrant that I am the author of this Public Comment and that I have full power and authority to enter into this copyright assignment. By checking this box I affirm that I am Catherine Stashak, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained therein. I understand and intend that, by checking this box, I am creating an electronic signature that will, upon my submission of this form, have the same legal force and effect as a handwritten signature Page 3 of 14
4 Page 53 of ] Public Comment No. 51-NFPA [ New Section after TITLE OF NEW CONTENT In existing installations, steel door frames without a label are permitted where approved by the AHJ. Statement of Problem and Substantiation for Public Comment The reference to "legible" labels was removed to address the comment from the committee that the initial proposed text would have permitted existing labels to be made illegible which is not the intent of the proposed code change. Steel door frames in good condition routinely recieve a labels during inspection from a testing lab at a cost to the building owner. The proposed change is consistent NFPA 5000 Section on building rehabilitation which requires door frames to be provided with a label OR be constructed of steel. Submitter Information Verification Submitter Full Name: LENNON PEAKE Organization: KOFFEL ASSOCIATES INC Submittal Date: Mon Apr 08 13:52:30 EDT 2013 Copyright Assignment I, LENNON PEAKE, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Comment (including both the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any publication of the NFPA in which this Public Comment in this or another similar or derivative form is used. I hereby warrant that I am the author of this Public Comment and that I have full power and authority to enter into this copyright assignment. By checking this box I affirm that I am LENNON PEAKE, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained therein. I understand and intend that, by checking this box, I am creating an electronic signature that will, upon my submission of this form, have the same legal force and effect as a handwritten signature Page 4 of 14
5 Page 54 of 195 Public Comment No. 71-NFPA [ New Section after ] (NEW) Penetrations in smoke barriers shall be protected by an approved through penetration firestop system tested in accordance with the requirements of UL 1479 for air leakage and installed to the listed system and manufacturers instructions. The L rating of the system measured at 0.30 inch (7.47 Pa) of water in both the ambient temperature and elevated temperature tests, shall not exceed: cfm per square foot (0.025 m 3 /s m 2 ) of penetration opening for each throughpenetration fire stop system; or 2. A total cumulative leakage of 50 cfm (0.024 m 3 /s) for any 100 square feet (9.3 m 2 ) of wall area, or floor area. Statement of Problem and Substantiation for Public Comment Page 5 of 14
6 Page 55 of 195 Currently, the Code requirements for smoke barriers lack quantitative guidance and performance requirements for the maximum leakage that is acceptable. Designers, contractors and AHJs have no way to determine acceptability of individual or a complete area of penetration or joint firestops. Simply put: How much leakage is too much before the barrier is no longer a smoke barrier? The Life Safety code already recognizes that there are instances in Chapters 11 through 43 where leakage rated doors and dampers are required. What is still lacking is identifying a performance level that is realistic and achievable for joints and penetrations in Smoke Barriers. This proposed Code change is intended to improve the Code regarding the requirements for smoke leakage through penetrations in smoke barriers. The proposal has been modified to only require leakage rated penetration for new construction as requested by the Committee. In these cases, this proposal would allow 5 cfm/ft2 for individual through penetrations as one option, and would also allow an alternative requirement for the cumulative total leakage of all through-penetrations in a given area of smoke barrier. NFPA 101 currently includes requirements for individual components, such as doors in corridors and smoke barriers, to be tested in accordance with a nationally recognized UL Standard (UL 1784) for the quantitative measurement of air leakage rates through door assemblies under prescribed conditions. To be consistent in Smoke Barrier code language, it is reasonable to require a total smoke barrier performance level per 100 ft2 (for example) in addition to dealing with individual items. Individual items are permitted to have maximum smoke leakage, but the sum of the total cannot exceed an identified criteria. This mehtod will permit flexibility with the individual penetrations, but more comprehensive on the smoke barrier leakage performance. The 50 cfm suggested here is the theoretical maximum of 10 through penetraions at maximum allowed 5 cfm/ft2 in 100 ft2 of wall or floor area. The Life Safety Code permits 1 sq. ft. of leakage are per 1,000 ft2 of wall space. Based on some fundamental assumptions about anticipated presure differentials during fires, the cumulative value of 50 cfm per 100 ft2 proposed also represents approximately 50% of that permitted leakage. Consequently, if installing a through-penetration firestop system that has an L-Rating of more than 5.0 cfm/ft2, such as might be the case for a cable tray where additional leakage can occur between the individual cables in a bundle, then the overall installation can still be compliant with the Code either by spacing out the penetrations sufficiently to maintain the average leakage of 50cfm/100ft2 or ensure that other through-penetrations within the same 100 ft2 control area have leakage rates that are low enough to compensate for one or more penetrations with higher L-Ratings. The addition of the UL 1479 Air Leakage rating will provide a nationally recognized UL Standard for the quantitative measurement of air leakage rates through a barrier containing penetrations under prescribed conditions. This would follow the same approach currently taken in NFPA 101 for the other elements within smoke barriers, and would be consistent with the current smoke barrier requirements in other model building codes. The UL and Intertek directories identify "L" ratings and contain thousands of penetration and joint designs that have an "L" rating. The knowledge required for firestop "L-Rated Systems" is the same as for systems selection of the firestop. Submitter Information Verification Page 6 of 14
7 Page 56 of 195 Submitter Full Name: Catherine Stashak Organization: Office of the Illinois State Fire Marshal Submittal Date: Thu Apr 25 13:16:58 EDT 2013 Copyright Assignment I, Catherine Stashak, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Comment (including both the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any publication of the NFPA in which this Public Comment in this or another similar or derivative form is used. I hereby warrant that I am the author of this Public Comment and that I have full power and authority to enter into this copyright assignment. By checking this box I affirm that I am Catherine Stashak, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained therein. I understand and intend that, by checking this box, I am creating an electronic signature that will, upon my submission of this form, have the same legal force and effect as a handwritten signature Page 7 of 14
8 Page 57 of 195 Public Comment No. 12-NFPA [ Section No ] Where permitted by Chapters 11 through 43, unenclosed vertical openings created by convenience stairways shall be permitted as follows: (1) The convenience stair openings shall not serve as required means of egress. (2) The building shall be protected throughout by an approved, supervised automatic sprinkler system in accordance with Section 9.7. (3) * The convenience stair openings shall be protected in accordance with the method detailed for the protection of vertical openings in NFPA 13, Standard for the Installation of Sprinkler Systems. (4) In new construction, the area of the floor opening shall not exceed twice the horizontal projected area of the stairway. (5) (5) For new construction, such openings shall not connect more than four contiguous stories unless otherwise permitted by chapter 11 through 43. Statement of Problem and Substantiation for Public Comment This comment is in relation ot CI 1. The issues associated with allowing such openings to connect several stories are related to fire behavior and other physical phenomena (i.e. stratification, stack effect, etc.) and are not occupancy specific. Submitter Information Verification Submitter Full Name: Bill Galloway Organization: Southern Regional Fire Code De Submittal Date: Tue Mar 12 13:43:18 EDT 2013 Copyright Assignment I, Bill Galloway, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Comment (including both the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any publication of the NFPA in which this Public Comment in this or another similar or derivative form is used. I hereby warrant that I am the author of this Public Comment and that I have full power and authority to enter into this copyright assignment. By checking this box I affirm that I am Bill Galloway, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained therein. I understand and intend that, by checking this box, I am creating an electronic signature that will, upon my submission of this form, have the same legal force and effect as a handwritten signature Page 8 of 14
9 Page 58 of 195 Public Comment No. 127-NFPA [ Section No ] Where permitted by Chapters 11 through 43, unenclosed vertical openings created by convenience stairways shall be permitted as follows: (1) The convenience stair openings shall not serve as required means of egress. (2) The building shall be protected throughout by an approved, supervised automatic sprinkler system in accordance with Section 9.7. (3) * The convenience stair openings shall be protected in accordance with the method detailed for the protection of vertical openings in NFPA 13, Standard for the Installation of Sprinkler Systems. (4) In new construction, the area of the floor opening shall not exceed twice the horizontal projected area of the stairway. (5) The convenience stair opening shall not connect more than two adjacent stories (one floor pierced only). Additional Proposed Changes File Name Description Approved 101_Original.pdf Orignal Comment Statement of Problem and Substantiation for Public Comment Page 9 of 14
10 Page 59 of 195 Related to PI 208 Problem: This new provision in the 2012 edition of NFPA 101 and NFPA 5000 for convenience stairs permits unenclosed vertical openings created by convenience stairs to potentially be installed in any occupancy, with no limitation on the maximum number of interconnected floors. It is not justifiable to extend the protection measures previously permitted for escalators to all convenience openings. This proposals restores the 2 storey limitation for convenience openings from the 2009 edition. Substantiation: This article introduces an unjustified level of risk to building occupants. This provision was added into the 2012 Life Safety Code and NFPA 5000 based on a proposal from the Detention and Care technical Committee. The item was information balloted to the BLD-FIR after their meeting had occurred. It was never justified Technically. One of the fundamental requirements of the Life Safety Code is that the design of buildings cannot rely solely on any one means of safeguarding occupants. This section relies exclusively on sprinkler performance. As we are all aware, sprinklers are an invaluable life safety and property protection technology. However, even the March 2012 edition of NFPA s Report on US Experience with Sprinklers states that the combined performance of operating effectiveness of sprinklers is 88% of reported fires where sprinklers were present in the fire area and fire was large enough to activate the sprinklers. One of the fundamental requirements of the Life Safety Code is that the design of buildings cannot rely solely on any one means of safeguarding occupants. This section relies exclusively on sprinkler performance. If sprinklers were to fail to operate, or fail to control a fire, this large multi-story hole in several floors could allow massive vertical spread of fire and products of combustion. As we are all aware, sprinklers are an invaluable life safety and property protection technology. However, even the March 2012 edition of NFPA s Report on US Experience with Sprinklers states that the combined performance of operating effectiveness of sprinklers is 88% of reported fires where sprinklers were present in the fire area and fire was large enough to activate the sprinklers. This further helps to justify the over-arching NFPA 101 philosophy that safety to life shall not depend on a single safeguard, Any permitted vertical opening should include consideration of what would happen if one protection measure failed, This new provision for convenience stairs is a major technical change to the philosophy of NFPA 101 in protection of vertical openings. It is not appropriate to extend the protection measures previously permitted for escalators to now permit other multi-story convenience openings. As stated in the substantiation provided on Log and Log b in the previous (2012 edition) cycle, Escalators represent a unique condition. The closelyspaced sprinkler form of protection has historically been permitted for escalators because it might be dangerous to enclose an escalator with walls and doors as an escalator will continue to run and deposit people at a floor even if the door on that floor becomes inoperative. Users of convenience stairs are not mechanically moved and deposited at a floor, so it is not necessary to make a special allowance removing the stairway enclosure needed for fire safety for such convenience stairs. The solution historically provided for escalators to be protected in accordance with the method detailed for the protection of vertical openings in NFPA13, Standard for the Installation of Sprinkler Systems, has been provided out of this necessity. Having this arrangement for escalator openings may not provide the same level of risk reduction and same level of smoke and fire containment as an enclosed stair shaft would, but it is a reasonable accommodation for unavoidable conditions, given that escalators are a building feature that will need to be accommodated. This sub-optimal but necessary solution should not be expanded without justification. In the 2012 edition of NFPA 101, Chapters 12 and 13 have already permitted the use of these new unlimited vertical openings for convenience stairs on the basis of their inclusion in These Chapters address multiple new and existing assembly occupancies, including dance halls and drinking establishments. The ability to utilize this provision is not restricted to any occupancy types. It is highly debatable if allowing these multi-story convenience openings for the first time ever is a reasonable relaxation of fire safety requirements, or if it potentially sacrifices the Page 10 of 14
11 Page 60 of 195 safety of occupants for some architectural freedom that was never needed or allocated before. Article of the Code requires that The design of every building or structure intended for human occupancy shall be such that reliance for safety to life does not depend solely on any single safeguard. An additional safeguard(s) shall be provided for life safety in case any single safeguard is ineffective due to inappropriate human actions or system failure. Further, under the fundamental requirements for Vertical Openings states Every vertical opening between the floors of a building shall be suitably enclosed or protected, as necessary, to afford reasonable safety to occupants while using the means of egress and to prevent the spread of fire, smoke, or fumes through vertical openings from floor to floor before occupants have entered exits. Sprinklers installed in accordance with the method detailed for the protection of vertical openings in NFPA13 should not be assumed as achieving this level of performance, because sprinklers will not prevent the development or spread of smoke or fumes through these multiple floors. This is particularly true in shielded fire scenarios. Of course, in the scenario where sprinklers fail to control a fire, which NFPA statistics indicate could be a 12% probability, then smoke and products of combustion would definitely not be minimized nor prevented from migrating to other floors, thus endangering egress on those upper floors. Submitter Information Verification Submitter Full Name: TONY CRIMI Organization: AC CONSLT SOLUTIONS INC Submittal Date: Mon May 06 13:36:10 EDT 2013 Copyright Assignment I, TONY CRIMI, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Comment (including both the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any publication of the NFPA in which this Public Comment in this or another similar or derivative form is used. I hereby warrant that I am the author of this Public Comment and that I have full power and authority to enter into this copyright assignment. By checking this box I affirm that I am TONY CRIMI, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained therein. I understand and intend that, by checking this box, I am creating an electronic signature that will, upon my submission of this form, have the same legal force and effect as a handwritten signature Page 11 of 14
12 Page 61 of 195 Public Comment No. 13-NFPA [ Section No ] Any escalators and moving walks not constituting an exit shall have their floor openings enclosed or protected as required for other vertical openings, unless otherwise permitted by one of the following: (1) The requirement of shall not apply to escalators in large open areas, such as atriums and enclosed shopping malls. (2) * In buildings protected throughout by an approved automatic sprinkler system in accordance with Section 9.7, escalator and moving walk openings shall be permitted to be protected in accordance with the method detailed in NFPA 13, Standard for the Installation of Sprinkler Systems, or in accordance with a method approved by the authority having jurisdiction. (3) In new buildings protected throughout by an approved automatic sprinkler system in accordance with Section 9.7, escalator and moving walk openings shall be permitted to be protected by rolling steel shutters appropriate for the fire resistance rating of the vertical opening and complying with all of the following in accordance with the method detailed in NFPA 13, Standard for the Installation of Sprinkler Systems, or in accordance with a method approved by the authority having jurisdiction, and the opening shall not connect more than four contiguous stories unless otherwise permitted by Chapter 11 through 43. : (a) (b) (c) The shutters shall close automatically and independently of each other upon smoke detection and sprinkler operation. A manual means of operating and testing the operation of the shutters shall be provided. The shutters shall be operated not less than once a week to ensure that they remain in proper operating condition. (d) The shutters shall operate at a speed not to exceed 30 ft/min (0.15 m/s) and shall be equipped with a sensitive leading edge. (e) The leading edge shall arrest the progress of a moving shutter and cause it to retract a distance of approximately 6 in. (150 mm) upon the application of a force not exceeding 20 lbf (90 N) applied to the surface of the leading edge. (f) The shutter, following the retraction specified in (3) (e), shall continue to close. (g) The operating mechanism for the rolling shutter shall be provided with standby power complying with the provisions of NFPA 70, National Electrical Code. Statement of Problem and Substantiation for Public Comment Page 12 of 14
13 Page 62 of 195 This comment is on CI 2.The issues associated with allowing such openings to connect several stories are related to fire behavior and other physical phenomena (i.e. stratification, stack effect, etc.) and are not occupancy specific. Submitter Information Verification Submitter Full Name: Bill Galloway Organization: Southern Regional Fire Code De Submittal Date: Tue Mar 12 13:47:02 EDT 2013 Copyright Assignment I, Bill Galloway, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Comment (including both the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any publication of the NFPA in which this Public Comment in this or another similar or derivative form is used. I hereby warrant that I am the author of this Public Comment and that I have full power and authority to enter into this copyright assignment. By checking this box I affirm that I am Bill Galloway, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained therein. I understand and intend that, by checking this box, I am creating an electronic signature that will, upon my submission of this form, have the same legal force and effect as a handwritten signature Page 13 of 14
14 Page 179 of 195 A ] Public Comment No. 83-NFPA [ New Section after A NFPA 251, ANSI/UL 263, and ASTM E119 are nationally recognized methods of determining fire resistance of building elements and assemblies. Assemblies tested in accordance with these fire-resistance test standards provide passive fire protection as a system. The test procedures set forth in these standards make no provision for testing fire resistance rated assemblies and systems washed with water from a n automatic fire suppression systems or water sprays in vertical or horizontal furnaces. As such, it is not possible to assign a fire resistance rating. Such evaluations can only be done via the Equivalency language in Section 1.4 or evaluation as a performance-based option in Chapter 5. Statement of Problem and Substantiation for Public Comment This is proposed annex language for the newly proposed Section Submitter Information Verification Submitter Full Name: Catherine Stashak Organization: Office of the Illinois State Fire Marshal Submittal Date: Fri Apr 26 12:27:32 EDT 2013 Copyright Assignment I, Catherine Stashak, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Comment (including both the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any publication of the NFPA in which this Public Comment in this or another similar or derivative form is used. I hereby warrant that I am the author of this Public Comment and that I have full power and authority to enter into this copyright assignment. By checking this box I affirm that I am Catherine Stashak, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained therein. I understand and intend that, by checking this box, I am creating an electronic signature that will, upon my submission of this form, have the same legal force and effect as a handwritten signature Page 14 of 14
A ROAD MAP FOR YOUR CODE, SMOKE BARRIER & SMOKE PARTITION REQUIREMENTS
A ROAD MAP FOR YOUR CODE, SMOKE BARRIER & SMOKE PARTITION REQUIREMENTS International Code Council National Fire Protection Association Underwriters Laboratories Inc. 5203 Leesburg Pike, Suite 600 1 Batterymarch
More informationCh. 58 DIVISION D-O 34 CHAPTER 58. DIVISION D-O ORDINARY COMMERCIAL, INDUSTRIAL, OFFICE OCCUPANCY GROUP CONSTRUCTION TYPE MAXIMUM STORY HEIGHT
Ch. 58 DIVISION D-O 34 CHAPTER 58. DIVISION D-O ORDINARY COMMERCIAL, INDUSTRIAL, OFFICE Sec. 58.1. Division D-O occupancies. 58.2. Separation and mixed occupancy. OCCUPANCY GROUP CONSTRUCTION TYPE MAXIMUM
More informationBuilding Code Clarifications - 7. Fire Resistance
Building Code Clarifications - 7. Fire Resistance 7.1 (15-12-030) Use of combustibles in Type III construction roof assemblies Code Section (15-12-030) Use of Combustibles was revised on May 17, 2000,
More informationFIRE-RESISTANCE-RATED CONSTRUCTION
CHAPTER 7 FIRE-RESISTANCE-RATED CONSTRUCTION SECTION 70 GENERAL 70. Scope. The provisions of this chapter shall govern the materials and assemblies used for structural fire resistance and fire-resistance-rated
More informationFIRE-RESISTANCE-RATED CONSTRUCTION
CHAPTER 7 FIRE-RESISTANCE-RATED CONSTRUCTION SECTION 70 GENERAL 70. Scope. The provisions of this chapter shall govern the materials and assemblies used for structural fire resistance and fire-resistance-rated
More informationBuilding Codes Update: The 2009 International Fire Code and the Apartment Industry
! Building Codes Update: The 2009 International Fire Code and the Apartment Industry Apartment operators and developers should be aware of organizational changes in the 2009 edition of the International
More informationFIRE AND SMOKE PROTECTION FEATURES
CHAPTER 7 FIRE AND SMOKE PROTECTION FEATURES SECTION 70 GENERAL 70. Scope. The provisions of this chapter shall govern the materials, systems and assemblies used for structural fire resistance and fire-resistance-rated
More informationCOMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES
COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES These guidelines are to be used for ALL commercial cooking hoods, ventilation systems and related fire suppression
More informationExcerpts from the Canadian National Building Code (NBC)
Excerpts from the Canadian National Building Code (NBC) Reproduced here with Permission of the Copyright Owner, the National Research Council of Canada, Institute for Research in Construction. For more
More informationCHAPTER 9 FIRE PROTECTION SYSTEMS
CHAPTER 9 FIRE PROTECTION SYSTEMS SECTION 901 GENERAL 901.1 Scope. Provisions of this chapter shall govern the application, design, installation, testing and maintenance of automatic sprinklers, standpipes
More informationFire Barriers & Fire Stopping
Presented by: Bill Lauzon, PE Lauzon Life Safety Consulting, LLC 262-945-4567 Lauzon.lsc@gmail.com Web: Lauzon-LSC.com Environmental Part 2 Life Safety Code Chapter 8 Fire Barriers & Fire Stopping 1 Fire
More informationFIRE AND SMOKE PROTECTION FEATURES
CHAPTER 7 FIRE AND SMOKE PROTECTION FEATURES SECTION 70 GENERAL 70. Scope. The provisions of this chapter shall govern the materials, systems and assemblies used for structural fire resistance and fire-resistance-rated
More informationHCD DSA OSHPD 1 2 1/AC AC SS SS/CC 1 2 3 4 2013 CALIFORNIA BUILDING CODE 199
CALIFORNIA BUILDING CODE MATRIX ADOPTION TABLE CHAPTER 7 FIRE AND SMOKE PROTECTION FEATURES (Matrix Adoption Tables are non-regulatory, intended only as an aid to the user. See Chapter for state agency
More informationTremco Fire Protection Systems Group Technical Bulletin
Compartmentalization products and design play a key role in protecting lives and property from fire. Understanding the tools and techniques available for firestopping is of utmost importance to designers,
More informationFrom Wired Glass to Clear Solutions: Designing with Fire Rated Glass Today
From Wired Glass to Clear Solutions: Designing with Fire Rated Glass Today Presented by SAFTI FIRST Fire Rated Glazing Solutions ABSTRACT: This white paper provides readers with a solid understanding of
More information5-8.1.4* Any required illumination shall be arranged so that the failure of any single lighting unit shall not leave any area in darkness.
NFPA 101 Life Safety Code Section 5-8 Illumination of Means of Egress 5-8.1 General. 5-8.1* Illumination of means of egress shall be provided in accordance with this section for every building and structure
More informationDesign Options (Tradeoffs) Allowed by the 2012 Building Codes for Properties with Sprinkler Systems. April 2013
Design Options (Tradeoffs) Allowed by the 2012 Building Codes for Properties with Sprinkler Systems April 2013 The National Multi Housing Council and the National Apartment Association (NMHC/NAA) have
More informationOntario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal
Ontario Fire Code SECTION 5.13 DIP TANKS Illustrated Commentary Office of the Ontario Fire Marshal Dip Tanks Illustrated Commentary 1 5.13.1. Location 5.13.1.1. Dip tank operations involving flammable
More informationHealthcare Engineering. Code Summary Report
American Society for Healthcare Engineering Code Summary Report CODE SUMMARY HEALTH CARE NEW BUILDINGS This code summary is based on the following codes: 2000 Edition NFPA 101, The Life Safety Code (LSC),
More informationTAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST
TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST In order to provide a comprehensive plan review in a timely manner, and to insure the design and installation of fire alarm systems
More informationLearn how all this can be achieved. architecture AND save money. exceptional. with the SALT LAKE CITY, UT PERMIT # US POSTAGE PAID FIRST CLASS
The ONLY horizontal sliding fire-door with these unique features: Spans unlimited widths, heights up to 23 feet Meets fire codes without being seen Approved for egress applications Automatic closing and
More information- 5 - Table1. Maximum Compartment Volumes
- 5 - Part II - SPECIFIC REQUIREMENTS 5. Compartmentation 5.1 Every building should be divided into compartments by walls and floors to inhibit the spread of fire. 5.2 Compartment walls, compartment floors,
More informationM E M O R A N D U M. To: Partnership for Safer Buildings Date: 21 March 2003
M E M O R A N D U M To: Partnership for Safer Buildings Date: 21 March 2003 From: Codes Assessment Subcommittee Walter Smittle III, Chairman Re: Building Code Fire Safety Concerns: NFPA 5000, Building
More informationThe 60 minute Fire Rated Application Explained
The 60 minute Fire Rated Application Explained One of the most confusing aspects of the code is the 60 minute fire rated application, and its easy to see why based on the questions that come up: Is 60
More informationLIFE SAFETY UPDATE. FULL SPRINKLERING OF ALL NURSING FACILITIES ADDITIONAL CLARIFICATIONS Prepared by Eric Rosenbaum, P.E. Hughes Associates, Inc.
LIFE SAFETY UPDATE FULL SPRINKLERING OF ALL NURSING FACILITIES ADDITIONAL CLARIFICATIONS Prepared by Eric Rosenbaum, P.E. Hughes Associates, Inc. The purpose of this update is as follows: Remind all state
More informationTerms and Definitions In Canada
Terms and Definitions In Canada Most of the following terms and definitions are taken directly from the National Building Code and referenced Test Methods. Learning these terms will provide an important
More informationIntroduction. CE marked construction products
Introduction This Technical Booklet has been prepared by the Department of Finance and Personnel and provides for certain methods and standards of building which, if followed, will satisfy the requirements
More informationIndiana Building Rehabilitation Standard
Rule 8. Indiana Building Rehabilitation Standard 675 IAC 12-8-1 Definitions Sec. 1. The following definitions apply throughout this rule: (1) "Building code" means the Indiana Building Code under 675 IAC
More informationHVAC Air Duct Leakage. Eli P. Howard, III Group Director Technical Resources SMACNA
HVAC Air Duct Leakage Eli P. Howard, III Group Director Technical Resources SMACNA Key Variables that Affect the Amount of Leakage Static Pressure Amount of Duct Openings in the Duct Surface Seams, Joints,
More informationArea of Rescue Assistance Communication System ADA Code Applicable excerpts:
Area of Rescue Assistance Communication System ADA Code Applicable excerpts: CONTENTS (Guidelines and Definitions) Page 1 Area of Rescue Assistance Requirements Page 2 Emergency Communication Equipment
More informationPROJECT SUMMARY. Scope of work details: (If phased construction, please see plan submittal guidelines.)
APPENDIX B BUILDING CODE SUMMARY FOR ALL COMMERCIAL FIRE RESTORATION PROJECTS (EXCEPT 1 AND 2-FAMILY DWELLINGS AND TOWNHOUSES) (Reproduce the following data on the building plans sheet 1 or 2) Name of
More informationOffice of the State Fire Marshal. Fire Rated Doors
Office of the State Fire Marshal Fire Rated Doors Fire Rated Doors These doors serve a purpose. They are manufactured in a way that is to help reduce the spread of fire and smoke. Fire rated doors allow
More informationBUILDING INSPECTORS INSPECTION FORM FOR CHILD CARE CENTERS
DCD-0304 Identification # Rev. 9/08 County Date of Inspection NAME OF OPERATION BUILDING INSPECTORS INSPECTION FORM FOR CHILD CARE CENTERS ADDRESS TELEPHONE: CITY STATE ZIP BUILDING INSPECTORS CERTIFICATE
More informationVAV Laboratory Room Airflow The Lowdown on Turndown
Technology Report March, 2003 VAV Laboratory The Lowdown on Turndown Turndown comparison of these two turndown ratios. Note the small actual airflow difference between them. control ranges are normally
More informationAVAILABLE TO DOWNLOAD ON THE APOLLO APP. Fire Alarm Systems Design. a guide to BS5839
AVAILABLE TO DOWNLOAD ON THE APOLLO APP a guide to Fire Alarm Systems Design BS5839 Part1:2013 The Regulatory Reform (Fire Safety) Order (FSO) became law on 1 October 2006 Legally you must comply! What
More informationHERNANDO COUNTY FIRE ALARM GUIDELINES
HERNANDO COUNTY FIRE ALARM GUIDELINES To be used for all commercial building fire alarm system plan review. The procedures set forth in this document are the minimum requirements necessary to ensure a
More informationFire-Rated Glass and Glazing START
Fire-Rated Glass and Glazing START www.pilkington.com/fire Fire-Rated Glass and Glazing Pilkington Fire Protection Glass North America 946 Kane Street, Suite A Toledo, OH 43612 Provider Number: J200 Course
More information2012 IBC & 2012 NFPA 101 Significant Means of Egress Changes. Questions. 1004.1 Design Occupant Load. 1005 - Means of Egress Capacity Determination
2012 IBC & 2012 NFPA 101 Significant Means of Egress Changes Clay Aler, P.E. Principal caler@koffel.com Andrew M. Schneider, P.E. Senior Fire Protection Engineer aschneider@koffel.com Questions Submit
More informationFIRE ALARM SYSTEM SUBMITTAL CHECKLIST AND APPLICATION
PERMITS AND INSPECTIONS FIRE ALARM SYSTEM SUBMITTAL CHECKLIST AND APPLICATION 911 Assigned PROJECT LOCATION Subdivision: Lot: Blk: Sec: PROJECT New Construction Addition/Remodel Demolition Other: Number
More informationThe Source of Firestop Expertise SM
The Source of Firestop Expertise SM Inspector Pocket Guide The following information is intended to provide construction and code enforcement professionals with basic checkpoints to ensure that the required
More informationFIRESTOPPING & SMOKE SEALS
SPECIFICATION SECTION 07 84 00 FIRESTOPPING & SMOKE SEALS 1 GENERAL 1.1 SECTION INCLUDES 1.1.1 Comply with Division 1, General Requirements and Documents referred to therein. 1.1.2 It is the intent of
More informationOriginal Document 10/16/07 Revised 01/30/09 2 nd Revision 01-23-12 3 rd Revision- 12/18/14
North Collier Fire Control & Rescue District Greater Naples Fire Rescue District Immokalee Fire Control & Rescue District 2800 North Horseshoe Drive Naples, Florida 34104 SYSTEM REHABILITATION PLAN CHECKLIST
More informationGeneral Fire Code Requirements Within Commercial Tenant Spaces
FIRE DEPARTMENT in cooperation with Scope: General Fire Code Requirements Within Commercial Tenant Spaces This handout is designed to assist owners, architects, contractors and others in understanding
More informationRESIDENTIAL PLUMBING ALTERATIONS PERMIT REQUIREMENTS
RESIDENTIAL PLUMBING ALTERATIONS PERMIT REQUIREMENTS The following guidelines are intended to assist with the permit acquisition process with regard to Plumbing Alterations. Not all information, or additional
More informationBasic Fire Door Requirements
TECHNICAL DATA SERIES S D I 118-01 Basic Fire Door Requirements 2001 Steel Door Institute STEEL DOOR INSTITUTE 30200 DETROIT ROAD - CLEVELAND, OHIO 44145 Technical Data Series SDI 118-2001 Basic Fire Door
More informationMINIMUM STANDARDS FOR HIGH-RISE BUILDINGS
CHAPTER 93 MINIMUM STANDARDS FOR HIGH-RISE BUILDINGS Note: Chapter 93 is entirely Seattle amendments to the International Fire Code and is not underlined. Point of Information The requirements of this
More informationMINNESOTA HEALTH CARE ENGINEERS IN ASSISTED LIVING FACILITIES
MINNESOTA HEALTH CARE ENGINEERS FIRE/LIFE SAFETY IN ASSISTED LIVING FACILITIES September 13, 2012 MINNESOTA HEALTH CARE ENGINEERS FIRE/LIFE SAFETY IN ASSISTED LIVING FACILITIES WELCOME Exits Restrooms
More informationCommercial Building Permit Application & Submittal Guidelines
Building Inspection Department 1625 13 th Street, Suite 106 Lubbock, Texas 79457 (806) 775-2087 (806) 775-2088 http://buildinsp.ci.lubbock.tx.us/ Commercial Building Permit Application & Submittal Guidelines
More informationSpray Booth Guideline
Department of Development Service 135 North D Street, Perris CA. 92570 Phone: (951) 443-1029 Fax: (951) 943-3293 PURPOSE The intent of this guideline is to provide the information necessary to ensure that
More informationHealth Chapter 420-5-22 ALABAMA STATE BOARD OF HEALTH ALABAMA DEPARTMENT OF PUBLIC HEALTH ADMINISTRATIVE CODE
Health Chapter 420-5-22 ALABAMA STATE BOARD OF HEALTH ALABAMA DEPARTMENT OF PUBLIC HEALTH ADMINISTRATIVE CODE CHAPTER 420-5-22 SUBMISSION OF PLANS AND SPECIFICATIONS FOR HEALTH CARE FACILITIES TABLE OF
More informationPage 4 of 17. Committee Input NFPA 101 Coordinate Smoke detector versus smoke alarm terminology.
Page 1 of 17 Page 2 of 17 Committee Input NFPA 101 Coordinate Smoke detector versus smoke alarm terminology. CODE PARAGRAPH WITH SUGGESTED CHANGES: 6.4.6.1.2 Residents should be rated as response probable
More informationCLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services
CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services 575 E. Flamingo Road, Las Vegas, NV 89119 (702) 455-7316 FAX (702) 455-7347 105.8a-6.1 TITLE: FIRE ALARM SYSTEM REQUIREMENTS SCOPE: This guideline
More informationGuidance on loft conversions in two-storey houses
Guidance on loft conversions in two-storey houses Technical guidance for building control surveyors, designers and installers 01 Guidance on loft conversions in two-storey houses Technical guidance for
More informationNC Rehab Code Case Study Cheerwine Building January 17, 2002; rev 4/12/02
NC Rehab Code Case Study Cheerwine Building January 17, 2002; rev 4/12/02 PART A: Project Data and Classification 1. Project name & location Renovation of the Cheerwine Building, 322 East Council St.,
More informationEducational. Educational-Existing 1/28/2014. OCCUPANT LOADS [no change] Application. Application
February 2014 Code Requirements and Inspections in Educational Occupancies Presented By: Barry W. Rickert Douglas M. Schanne Fire Marshal Training Program Supervisor Office of Education & Data Management
More informationCertification: Building Plans Examiner. Exam ID: B3
Certification: Building Plans Examiner Exam ID: B3 Scope: A Building Plans Examiner will be responsible for reviewing submitted plans to determine if they meet the requirements of the various Building
More informationWe hope these Frequently Asked Questions will be of use both to municipal officials and fire inspectors.
September 14, 2012 Dear AMM Member: Please see the attached Fire Code Frequently Asked Questions. This document was compiled by the Office of the Fire Commissioner at the AMM s request to help clarify
More informationPollution CO CO 2. Carbonaceo us soot H 2 S, NOX, SO2
Pollution CO CO 2 Carbonaceo us soot H 2 S, NOX, SO2 The National Building Code (NBC) contains set of minimum provisions, designed to protect the safety of the public with regard to structural sufficiency,
More informationWINDOW AND DOOR REPLACEMENT REQUIREMENTS
WINDOW AND DOOR REPLACEMENT REQUIREMENTS Should you have any questions after reading the following information, please call the Building Inspection Department at 651-439-4439 to discuss the topics of concern.
More informationFire Alarm System Plans Submittal Guidelines For New and Existing Systems
Fire Alarm System Plans Submittal Guidelines For New and Existing Systems SCOPE The Temecula Fire Prevention Bureau (TFPB) has established the following requirements for the submittal of all fire alarms,
More informationLife Safety Code Enabling References
SUPPLEMENT 4 Life Safety Code Enabling References Editor s Note: Supplement 4 provides users of NFPA 72, National Fire Alarm and Signaling Code, with a summary of requirements from NFPA 101, Life Safety
More informationSECTION 903 AUTOMATIC SPRINKLER SYSTEMS
Page 25 ABOUT CODE CORNER CCFS would like to remind you to check with your local Authority Having Jurisdiction (AHJ) for questions and opinions concerning your local Fire and Building Codes. The information
More informationThe Commonwealth of Massachusetts Executive Office of Public Safety Department of Fire Services
MITT ROMNEY GOVERNOR KERRY HEALEY LT. GOVERNOR EDWARD A. FLYNN SECRETARY The Commonwealth of Massachusetts Executive Office of Public Safety Department of Fire Services P.O. Box 1025 State Road Stow, Massachusetts
More informationPOSITION STATEMENT THE ENGINEER AND THE ENGINEERING TECHNICIAN DESIGNING FIRE PROTECTION SYSTEMS. July 28, 2008
SOCIETY OF FIRE PROTECTION ENGINEERS (SFPE) NATIONAL SOCIETY OF PROFESSIONAL ENGINEERS (NSPE) NATIONAL INSTITUTE FOR CERTIFICATION IN ENGINEERING TECHNOLOGIES (NICET) POSITION STATEMENT THE ENGINEER AND
More informationSingle Family Residential Basement Finish
How to Use This Guide Building Guide Pottawattamie County Planning & Development Department Building & Safety Division Single Family Residential Basement Finish Provide two (2) sets of plans and complete
More informationGeneral Safety & Health Standards Published by the Division of Building Safety In Cooperation with the Idaho Industrial Commission
General Safety & Health Standards Published by the Division of Building Safety In Cooperation with the Idaho Industrial Commission Local Fire Alarm 064. FIRE ALARM SYSTEMS 01. Scope 02. Definitions 03.
More information2010 edition. Handbook of. Fire-Rated Glass. for schools
Handbook of Fire-Rated Glass for schools 2010 edition The Rules have changed For decades, traditional wired glass has been the most common fire-rated glass product specified for schools in North America.
More information2007 ICC FINAL ACTION AGENDA
907.2.1.1 System initiation in Group A occupancies with an occupant load of 1,000 or more. Activation of the fire alarm in Group A occupancies with an occupant load of 1,000 or more shall initiate a signal
More informationFire Alarm Systems Requirements by Occupancy Type
WALT WHITE Fire Chief 5770 Freeport Blvd., Suite 200 Sacramento, CA 95822-3516 Ph: (916) 808-1300 Fax: (916) 808-1629 www.sacfire.org Fire Alarm Systems Requirements by Occupancy Type 2013 California Building
More informationOverview of Hotel Fire Safety Requirements
Overview of Hotel Fire Safety Requirements in the Fire Code Susan Clarke, P.Eng. Office of the Fire Marshal - January 10, 2012 1 Agenda Regulation History - Hotels Fire Code Overview (Parts 1 to 8) Defined
More informationMEANS OF EXIT / ESCAPE / EGRESS SELF INSPECTION CHECKLIST
OPTIONAL INFORMATION Name of School: Date of Inspection: Vocational Program/Course/Room: Signature of Inspector: MEANS OF EXIT / ESCAPE / EGRESS Guidelines: This checklist covers some of the regulations
More informationFire-Retardant-Treated (FRT) Plywood
T e c h n i c a l n o t e Fire-Retardant-Treated (FRT) Plywood Number K320 January 2009 Introduction Codes assure fire safety by controlling such things as size and design of the structure and flame-spread
More informationCode Requirements for Existing Buildings
Code Requirements for Existing Buildings Kevin S. Hastings, P.E., LEED AP R. W. Sullivan, Inc. 529 Main St., Suite 203 Charlestown, MA (617) 523-8227 www.rwsullivan.com R.W. Sullivan Engineering (RWS)
More informationOCFRD TENT STANDARD 6000. This Standard operates under the authority of Orange County, Florida Ordinance and State Statutes.
1. Authority Orange County Fire Rescue Department Tents & Membrane Structures Office of The Fire Marshall - 109 E. Church Street, Lower Level - Orlando, Florida 32801-3319 Phone: 407-836-0004 Fax: 407-836-8310
More informationRequired Certification Documentation. Contractor's installation certification for range hood fire suppression systems.
OFFICE OF UNIVERSIT BUILDING OFFICIAL PROJECT/CONSTRUCTION MAGER: Sample Manager Required Aboveground only Required Certification Documentation Contractor s material and test certifications for both above
More informationCHANGES IN NFPA 72 NATIONAL FIRE ALARM CODE 1999 2002
CHANGES IN NFPA 72 NATIONAL FIRE ALARM CODE 1999 2002 Three new chapters were added. What was chapter 1 in 1999 was reorganized into chapters 1 (Fundamentals), 2 (Referenced Publications), and 3 (Definitions).
More informationErrata NFPA 70. Proposed 2014 Edition
Errata NFPA 70 National Electrical Code (Report on Proposals) Reference: 12-109 (Log #1618) Panel Meeting Action Proposed 2014 Edition The National Electrical Code Technical Correlating Committee notes
More informationVestibule Case Study. Vestibule Requirement Intent [2003 IECC, 2006 IECC, 2003 IBC, 2006 IBC, 90.1-2001, 90.1-2004]
Vestibule Case Study [2003 IECC, 2006 IECC, 2003 IBC, 2006 IBC, 90.1-2001, 90.1-2004] Vestibule Requirement Intent Page 1 of 14 The primary intent behind the requirement for a vestibule is to reduce infiltration
More informationWinnipeg Fire Department Fire Prevention Branch
Winnipeg Fire Department Fire Prevention Branch Manitoba Fire Code Life-Safety Equipment Maintenance Requirements The Fire Prevention Branch of the Winnipeg Fire Department has prepared this document of
More informationRequirements for Fire Protection of Light Weight Floor Systems **Act 1 Revisited**
PHRC Webinar Series Tuesday, September 9, 2014 1:00 pm Requirements for Fire Protection of Light Weight Floor Systems **Act 1 Revisited** Presented by: Bryan Heitzmann Credit(s) earned on completion of
More informationSCHOOL FIRE AND LIFE SAFETY INSPECTION CHECKLIST
SCHOOL FIRE AND LIFE SAFETY INSPECTION CHECKLIST School Name: School Address: Town: Phone: Inspected By (Please Print): Inspection Organization Name: Inspector Phone: Date of Inspection: Building Name:
More informationAVAILABLE TO DOWNLOAD ON THE APOLLO APP. Pocket guide to. Fire Alarm Systems Design BS 5839-1. Standard
Pocket guide to Fire Alarm Systems Design BS 5839-1 Standard AVAILABLE TO DOWNLOAD ON THE APOLLO APP The Regulatory Reform (Fire Safety) Order (FSO) became law on 1 October 2006 Legally you must comply!
More informationClassroom Door Security & Locking Hardware
Classroom Door Security & Locking Hardware The ability to protect students and teachers while in the classroom is a high priority in all educational institutions. Many schools and school districts have
More informationINTERNATIONAL FIRE PROTECTION
An MDM PUBLICATION Issue 39 August 2009 www.mdmpublishing.com INTERNATIONAL FIRE PROTECTION THE GLOBAL VOICE FOR PASSIVE & ACTIVE FIRE PROTECTION Progress with fire-resistant glass Limiting risk, reducing
More informationrpsa FIRE PROTECTION ENGINEERS www.rpsa-fire.com
www.-fire.com R.P. SCHIFILITI ASSOCIATES, INC. P.O. Box 297 Reading, MA 01867-0497 USA 781.944.9300 Fax / Data 781.942.7500 Telephone Elevator Fire Safety: Elevator Recall and Elevator Power Shutdown Disclaimer:
More information#506 New Multi-Family Buildings & Additions Plan Intake Submittal Checklist
#506 New Multi-Family Buildings & Additions Plan Intake Submittal Checklist Case #: Date: Project Name: Site Address: Application Submittal Building permit applications and plans can be submitted to the
More information2006 IBC BUILDING CODE CHECKLIST FOR COMMERCIAL PROJECTS
2006 IBC BUILDING CODE CHECKLIST FOR COMMERCIAL PROJECTS IBC CODE DESIGN CHECKLIST (EXCEPT 1 AND 2-FAMILY DWELLINGS AND TOWNHOUSES) (Transfer the resulting data on the building plans Life Safety & Building
More informationFIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011
FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011 COLORADO SPRINGS FIRE DEPARTMENT Division of the Fire Marshal If you have any questions or comments regarding the
More informationThe following definitions apply with regard to requirements specified in this document:
GUIDELINES FOR INSTALLATION OF TEMPORARY AND PERMANENT ABOVEGROUND DIESEL FUEL TANKS FOR EMERGENCY AND STANDBY POWER SYSTEMS LOCATED OUTSIDE OF BUILDINGS For Use by Unidocs Member Agencies or where approved
More informationKITCHEN AND BATH REMODELING BUILDING PERMIT REQUIREMENTS
St. Louis County Department of Public Works Division of Code Enforcement KITCHEN AND BATH REMODELING BUILDING PERMIT REQUIREMENTS This guideline is intended to provide the homeowner/contractor with the
More informationALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS
ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS In this document are the fire safety equipment maintenance requirements that are found in Division B of the Alberta Fire Code (AFC 2006) for
More information4 Installation Requirements
4 Installation Requirements 9 4.1 Code Reference The authority having jurisdiction should be referenced to determine what law, ordinance or code shall apply in the use of flexible duct. Ducts conforming
More informationLOUISVILLE FIRE PROTECTION DISTRICT 895 West Via Appia, Louisville, Colorado 80027 303-666-8809
LOUISVILLE FIRE PROTECTION DISTRICT 895 West Via Appia, Louisville, Colorado 80027 303-666-8809 Contractor s Checklist and Installation Guide TABLE OF CONTENTS Fire Protection Narrative........... 3 Fire
More informationALVERNIA UNIVERSITY OSHA REGULATION: 29 CFR 1910.252 WELDING, CUTTING, AND BRAZING ( HOT WORK ) SECTION: 3600
OSHA REGULATION: 9 CFR 90.5 WELDING, CUTTING, AND BRAZING ( HOT WORK ) A. POLICY. This procedure follows requirements set forth in 9 CFR 90.5.. This policy applies to all Hot Work operations being done
More informationIn accordance with NFPA 30, these containers are not to store Class I flammable liquids.
In accordance with NFPA 30, these containers are not to store Class I flammable liquids. Zurich recommends storing these containers in dedicated liquid storage rooms, detached buildings, or in listed dispensing
More informationUL Fire Door Inspection Service. UL Fire Alarm Certification Program. A valuable but misunderstood resource for jurisdictions
2013 Issue 2 2 A Strong Foundation 3 Introducing UL Fire Door Inspection Service 6 Enhanced UL Marks Coming Your Way Soon UL Fire Alarm Certification Program A valuable but misunderstood resource for jurisdictions
More informationNFPA 101 2012 SELECT SIGNIFICANT CHANGES
NFPA 101 2012 SELECT SIGNIFICANT CHANGES William E. Koffel, P.E., FSFPE President Koffel Associates, Inc. www.koffel.com wkoffel@koffel.com Expertly Engineering Safety From Fire INTRODUCTION NFPA 101 is
More informationSPECIAL RESIDENCE (ASSISTED SELF-PRESERVATION) OCCUPANCIES (Adopted by the State of Oregon)
SPECIAL RESIDENCE (ASSISTED SELF-PRESERVATION) OCCUPANCIES (Adopted by the State of Oregon) SECTION SR101 GENERAL SR101.1 General. Group SR occupancies shall comply with the provisions of this appendix
More informationFLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL
FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL January, 2003 Environmental Health and Safety Florida Atlantic University 777 Glades Rd. Boca Raton, FL 33431 Phone: 561-297-3129 Fax:
More information