1 Minimizing Fan Energy Costs Parts 1 and 2 Robert C. Monroe Hudson Products Corporation, Houston, Texas Of five ways for reducing the energy cost of operating axial fans, two are discussed in Part1: Improving the fan and the drive system. The three other methods will be taken up in Part 2. Reprinted from Chemical Engineering Cost File, 1993
2 Part 1 Minimizing Fan Energy Costs The causes of fan system inefficiency are sometimes obvious, but usually not. For instance, blade design itself is critical. Axial-fan blades are usually made of extruded aluminum or molded fiberglass. The former are always of uniform chord width, whereas the latter can have an irregular shape (Fig. 1). A basic design criterion is that a blade should produce uniform flow over the entire plane of the fan. An aerodynamic principle involved says that the work done at any radius along the blade is a function of blade width, angle of attack, and tangential velocity squared. Angle of attack in airfoil design dictates the amount of blade twist at any radius along the blade. At points along a blade from the tip to the hub, tangential velocity decreases sharply. To compensate for this, so as to produce uniform flow, the blade must be wider and its twist greater, closer to the hub. If it cannot be made wider, its twist must be correspondingly greater. In the case of the extruded blade, twist is created by mechanical bending. Of course, limits of elasticity prescribe the maximum twist. In the case of the molded blade, however, there is no such limitation to chord width or twist, so it can be made closer to the ideal shape. The point being made is that blade design itself can cause poor flow distribution and inefficiency. Also an inherent problem with the axial fan is swirl-the tangential deflection of exit-flow caused by the effect of torque. Air vectors at the extreme inboard section of a blade actually reverse direction, diminishing the net flow. Swirl can be prevented with an inexpensive hub component, which usually covers the inner 25-35% of the fan diameter. Checking Fan Efficiency Basic efficiency can be checked by means of the fan's performance curve. For the fan's operating point, the following must be known: fan diameter (ft), air flow (ft 3 /min), total pressure (in. water), air density, design horsepower, and fan speed (rpm). Total pressure is the sum of static pressure and velocity pressure. Actual static pressure (referred to actual density) is the total of all the pressure drops through the tower fill, or tube bundle, plus that caused by the tower or air cooler. Velocity pressure is the force needed to simply move the desired volume of air. Most fan curves show velocity pressure as a function of airflow for a fan. With the foregoing known, total efficiency can be calculated: Total efficiency = [(actual total pressure)(actual ft 3 /min)] / [(6,356)(actual horsepower)]. Total pressure and horsepower must be based on the same density, either actual or for the standard condition of lb/ft 3. Check that operating speed is as specified for the fan curve. If in doubt, calculate the fan's efficiency from published performance data, keeping in mind that these data were probably collected under conditions as perfect as possible, and so will not reflect actual air-cooler or tower conditions. Although actual efficiencies will be less than curve efficiencies, fan curves can, and should, be the common denominator for comparing fan performance. System efficiency will be discussed later. Hudson Products Corporation Page2of9
3 Total efficiencies of aerodynamically well-designed fans can range between 0.75 and However, actual efficiencies rarely exceed 0.75 not because of the fans, but because system efficiencies tend to be lower. This is why critical judgment must be exercised in evaluating horsepower requirements from ideal "curve" conditions. In some cases, it may be prudent to actually perform scale-model tests on a new tower configuration in a wind tunnel so as to define the "system resistance" line. As a rule of thumb, fewer blades translate into higher axial-fan efficiency. A crowded inboard area creates hub turbulence, which lessens efficiency. Fixed vs. Variable Pitch Whether the pitch of fan blades is fixed or variable also affects energy consumption. Consider what happens when airflow is changed across a resistance (e.g., tower fill or tube bundle). Assume flow can be throttled, as by mechanically actuated louvers. Take, for example, a 14-ft-dia. fan with 14-deg pitched blades operating at its design Point 1 (Fig. 2). The system resistance line (dashed line) is the locus of points obtained by summing static and velocity pressure losses vs. flows through the bundle. The pitch angle of 14 deg represents the delivery characteristic of the fan. Assume density remains constant and lower air flow results from decreased duty. The louver throttles the airflow to control its outlet temperature. In Fig. 2, the points shown as 1, 2', 3' and 4' represent the total pressure output, and the horsepower consumed by the fixed-pitch fan. If the airflow were being controlled by means of a variable-pitch fan, instead of via throttling, the total pressure output would exactly match the system requirements, as shown by points 2, 3 and 4. This would significantly reduce horsepower requirements. In this case, the variable-pitch fan saves 26%, 51% and 73% of the horsepower required by the fixed fan at points 2', 3' and 4'. A variable-pitch fan typically is controlled by a 3-15 psi instrument signal. In the event of signal failure, it automatically moves to full design pitch, functioning very much like a diaphragm-operated, spring-return valve operator. Its airflow usually ranges from design to zero, although it can provide up to 60% of its upflow in a negative, or down, direction. Fig. 3 shows the decrease in flow and power for a set of 45-deg travel. Note how horsepower falls to a minimum "no load" motor condition, then increases as work is being done in the negative airflow mode. (No-load losses are a function of iron and magnetic losses in the motor.) Operating Cooling-Tower Fans to Save Energy A study by the predecessor to the U.S. Dept. of Energy of a typical cooling tower in Houston, Tex., operating with 100 million Btu/h heat load and a 110 F-to-95 F cooling water range, revealed the following relative power consumptions: No control, full speed Single-speed, automatic on/off Two-speed, automatic on/off Automatic variable-pitch fan 100% (base) 65% of base 59% of base 50% of base The tower was equipped with four fans, each run by a 25-hp motor. The results typify the power savings possible in Houston, where annual dry-bulb temperatures vary from 30 F to over 100 F. Hudson Products Corporation Page3of9
4 If airflow were controlled with a fixed-pitch fan and a variable-speed drive, rather than by a variable-pitch fan, the results would be similar. Speed changing saves power because horsepower consumption is a cubic function of airflow i.e., hp 2 =hp 1 (cfm 2 /cfm 1 ) 3. There is a slight advantage in controlling flow by varying speed rather than adjusting blade pitch angle, because the operating-point efficiency is maintained at all lower speeds. The efficiency of a variable-pitch fan declines with decreasing pitch angle. Because, in both cases, power consumption drops off dramatically, the actual savings would have to be carefully evaluated. However, power savings of 50%/yr, or greater, can be realized by replacing a fixed-pitch, continuously operating fan with one whose blade pitch or speed is automatically varied. Improving the Drive System Cooling-tower fans are generally gear-driven. The efficiencies of such drives fall between 96% and 98%. Not much can be done to improve these efficiencies, which depend on the type and class of gear. Efficiencies of smaller fans driven by V-belts range between 92% and 95%, because of slippage. Newer synchronous drives can eliminate slippage and improve efficiency by 3-4%. Besides saving energy, these drives reduce the costs of periodically tightening drive belts and replacing worn sheaves. Lower tension also lessens motor-bearing wear. J. Matley, Editor Author Robert C. Monroe is Manager of Fan Engineering for Hudson Products Corporation, Houston. He has 23 years of experience as fan engineer and two years experience as Manager R&D. He was engaged in the design of oilfield tools for 17 years. He holds a B.S.M.E. from the University of Houston. Formerly President of the Cooling Tower Institute and a member of its Board of Directors, he is a member of ASME and the Texas Society for Professional Engineers. Hudson Products Corporation Page4of9
5 Figure 1 Extruded blades are uniform in shape; molded ones are irregular Figure 2 Flow control by varying blade pitch consumes less energy Figure 3 Signal controls blade pitch, changing air flow and hp Hudson Products Corporation Page5of9
6 Part 2 Minimizing Fan Energy Costs The configuration of a cooling tower or air cooler can contribute to fan inefficiency. Fan efficiency can be undermined by too much tip clearance, poor inlet conditions, and excessive approach and discharge velocities. Too much tip clearance allows discharge air to circulate back around blade tips and into the fan inlet. In Fig. 1, losses in efficiency and total discharge pressure are related to tip clearance for a small fan at one flowrate. The data are from tests with a 5-ft-dia. fan having an initial clearance of in., which is increased to in. (A clearance of 0.27 in. with a 5-ft-dia. fan is equivalent to 0.75 in. with a 14-ft-dia. fan; a clearance of 0.18 in. with a 5-ft-dia. fan is equivalent to 1 in. with a 28-ft-dia. fan.) Inlet conditions are especially critical with forced-draft coolers. A total pressure loss of 26% and an efficiency drop of 18%, at a velocity pressure of 0.2 in. water, were revealed by tests on fans not equipped with an inlet bell on the fan ring. These losses, which are a function of velocity pressure, increase with higher air flows. Excessive approach velocity can occur if the air-cooler fan inlet is too close to grade or the cooler is crowded by adjacent structures. Estimate approach velocity from the cylinder projected from the fan ring i.e., the projected area. Therefore, approach velocity = (ft 3 /min)/πdh. With an air cooler, the approach velocity should not exceed 50% of the discharge velocity. Discharge velocity = (ft 3 /min)/(0.785d 2 ). Cooling-tower approach velocity is measured at the inlet louvers. For counterflow towers, the tendency is to allow 800-1,200 ft/min through the louvers. For crossflow towers, the range is typically ft/min. Excessive discharge velocity wastes horsepower. This loss is gauged by fan velocity pressure. For fans of 6-40 ft dia., typical velocity pressures range from in. water. If the velocity pressure approaches in., a velocity-regain stack should be considered. The excessive velocity pressure recovered by a stack is used to lower pressure, and thus horsepower consumption. Typical horsepower savings are shown in Fig. 2. Cooling-tower fans of 16-ft dia. and larger are usually equipped with such stacks. Fan Operating Point The point where the system resistance line meets the fan performance line at the desired air flow defines a fan's operating point. At this point, the fan's output exactly meets the air-flow and pressure-drop requirements. Such a point will be represented by a specific blade pitch angle, actual ft 3 /min and total pressure air output, and fan rpm. Fan rpm is usually set by noise restrictions, available gear or belt ratios, or the manufacturer's standard practice. Most large fans operate at a tip speed of about 11,000 ft/min. The most obvious thing to check pertaining to operating point is whether the fan is "stalled." A stalled fan is like a cavitating pump: it consumes a lot of energy but produces no work. If a poorly operating fan is suspected of stall, try lowering blade pitch and see if the static pressure (measured with a water manometer) in the plenum changes. If the pressure does not change, the fan may be stalled. A stalled fan draws more horsepower with increasing pitch, but air flow and static pressure may actually decrease. Because efficiency varies along pitch lines and with air flow, power can be saved and noise and vibration reduced by simply fine-tuning a fan's operating point. Hudson Products Corporation Page6of9
7 At various speeds, calculate operating points using speed factors, and check efficiencies at these points on the fan curve. Speed factor = curve speed/actual speed. If, for example, the curve tip-speed was 12,000 ft/min, and the new speed is 10,000 ft/min, the speed factor = 12,000/10,000 = 1.2. (This can also be calculated in rpm. Tip speed = (rpm)(π)(fan dia.), or rpm = tip speed/πd.) After calculating the speed factor, find the fan's new operating point: (ft 3 /min) 2 = (ft 3 /min) 1 (speed factor), or (total pressure) 2 = (total pressure) 1 (speed factor) 2. Using the speed factor, the fan speed can be changed at will. Each new speed and pitch angle will improve or worsen the efficiency of the original starting point. Plot total pressure vs. ft 3 /min air flow for various pitch angles on the appropriate fan curve to obtain the horsepower requirement. Note that the pressure and flow work are the same at all the operating points, at which pitch angles differ. Many manufacturers refine cooling-tower design by such an optimization procedure before selecting an optimum gear ratio. Variable Pitch vs. Variable Speed The choice between automatically-varied fan pitch and variable fan speed depends on such factors as: (1) initial costs and payback period, (2) the availability of suitable fans, and (3) the number of fans performing the same duty. Automatically-variable-pitch systems are simple and low-cost compared with variable-speed drive systems. A typical variable-pitch fan hub costs an additional $2,000 to $4,000 per fan. This includes the cost of a valve positioner for controlling pitch precisely. A typical variable-frequency type of variable-speed drive for a 40-hp motor can cost upwards of $10,000 per fan. The advantage of the latter drive is that any fan system can be retrofitted with it, normally without fan or gearbox modifications. Payback period is calculated from power savings, which depend on the "degree days" at the site, power cost, required air flow vs. ambient temperature, and installation cost. The $/hp cost of a variable-speed drive drops significantly the larger the unit. For example, a 50-hp variable-speed drive may cost $12,500 (or $250/hp), but a 400-hp one may cost $46,000 (or $115/hp). Since, for heat-transfer purposes, an even air flow across a bundle is desirable, the maximum number of fans should be operated by a single large controller, rather than by several smaller ones. A variable-speed drive can handle multiple motors, up to its rated capacity. Variable-pitch fans range up to 20 ft dia. The limiting factor is the pneumatic power available for controlling blade pitch. Variable-speed drives can exceed 1,000 hp. First cost for an automatically-variable-pitch fan including optional hub and valve positioner, and control-signal and air lines is typically $4,000. First cost for a variable-speed unit including reversing magnetic starter, signal conditioner and wiring is typically $4,500/fan, plus the drive cost. A reversing magnetic starter is required because a variable-speed fan must be operated in reverse to overcome the natural draft of an air cooler and attain "zero" air flow. The results of a study comparing costs and energy savings from automatically-variable-pitch and variable-speed fans are shown in Fig. 3. (Fig. 3 assumptions are: all fan motors are 30-hp, three-phase; power costs Hudson Products Corporation Page7of9
8 $0.05/kWh; cost of variable-pitch fan includes controls and piping; and cost of variable-speed fan includes starter and signal controller.) Note that the "break-over point" at which variable-speed fans offer more savings than variable-pitch fans is between 4 and 5 two-fan bays. This indicates that, with fewer than 8 fans, variable-pitch fans would be more cost-effective. Fig. 3 also shows that, with larger numbers of units, the variable-speed fan becomes more economical. In terms of horsepower, at less than about 300 total hp, the variable-pitch fan is the likely choice; at greater than 300 hp, the variable-speed fan should be selected. With either variable-pitch or variable-speed fans, power savings of 50%, or more, can be realized. J. Matley, Editor Hudson Products Corporation Page8of9
9 Figure 2 Velocity-recovery stacks save horsepower Figure 1 Efficiency declines with larger tip clearance Figure 3 Costs and savings are compared for 50%-automatically-variable-pitch fans and 100%-variable-speed fans Hudson Products Corporation Page9of9
Centrifugal Fans and Pumps are sized to meet the maximum
Fans and Pumps are sized to meet the maximum flow rate required by the system. System conditions frequently require reducing the flow rate. Throttling and bypass devices dampers and valves are installed
Air Conditioning Clinic
Air Conditioning Clinic Air Conditioning Fans One of the Equipment Series February 2012 TRG-TRC013-EN Air Conditioning Fans One of the Equipment Series A publication of Trane Preface Air Conditioning
Chapter 3.5: Fans and Blowers
Part I: Objective type questions and answers Chapter 3.5: Fans and Blowers 1. The parameter used by ASME to define fans, blowers and compressors is a) Fan ration b) Specific ratio c) Blade ratio d) Twist
Introduction. Motor Types
QwikSEER+ Theory of Operation and Retrofit Potential Mainstream Engineering Corporation Rockledge, FL 32955 http://www.qwik.com/products/qwikseer/index.jsp Prepared by Robert P. Scaringe and R. Paul Roth
COOLING TECHNOLOGY INSTITUTE
PAPER NO: TP04-13 CATEGORY: DRY COOLING COOLING TECHNOLOGY INSTITUTE PERFORMANCE IMPROVEMENT TO EXISTING AIR-COOLED HEAT EXCHANGERS ROBERT GIAMMARUTI HUDSON PRODUCTS CORPORATION The studies and conclusions
Electric Motors and Drives
EML 2322L MAE Design and Manufacturing Laboratory Electric Motors and Drives To calculate the peak power and torque produced by an electric motor, you will need to know the following: Motor supply voltage,
CENTRIFUGAL PUMP SELECTION, SIZING, AND INTERPRETATION OF PERFORMANCE CURVES
CENTRIFUGAL PUMP SELECTION, SIZING, AND INTERPRETATION OF PERFORMANCE CURVES 4.0 PUMP CLASSES Pumps may be classified in two general types, dynamic and positive displacement. Positive displacement pumps
Optimization of Water - Cooled Chiller Cooling Tower Combinations
Optimization of Water - Cooled Chiller Cooling Tower Combinations by: James W. Furlong & Frank T. Morrison Baltimore Aircoil Company The warm water leaving the chilled water coils is pumped to the evaporator
NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES
NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES 8.1 INTRODUCTION Testing, adjusting, and balancing of HVAC systems can best be accomplished by following a series of systematic procedures. The NEBB TAB
Energy Savings With Adjustable Frequency Drives. for Centrifugal Fans
Energy Savings With Adjustable Frequency Drives for Centrifugal Fans 2 Centrifugal Fans Centrifugal Fan Fans are designed to be capable of meeting the maximum demand of the system in which they are installed.
We will discuss common industrial applications with guides for the proper use of electric motors on these.
INTRODUCTION: Baldor Electric Company has prepared this Specifiers Guide to help you cover all the bases when you are specifying electric motors. It will cover in a generic way most of the subjects which
product application guide
Understanding Fan System Effects Fan Application FA/101-99 product application guide A technical bulletin for engineers, contractors and students in the air movement and control industry. The air moving
FAN PROTECTION AGAINST STALLING PHENOMENON
FAN PROTECTION AGAINST STALLING PHENOMENON Roberto Arias Álvarez 1 Javier Fernández López 2 2 1 ZITRON Technical Director [email protected] ZITRON Technical Pre Sales Management [email protected]
Documenting Results to Validate Energy Savings Projects: Case Study of Direct Drive Cooling Tower Installations: Before and After
Documenting Results to Validate Energy Savings Projects: Case Study of Direct Drive Cooling Tower Installations: Before and After Roman Wajda, Baldor Electric Company ABSTRACT Documenting the actual energy
DESIGN CRITERIA AND OPERATIONAL LIMITS FOR AXIAL FLOW FANS OPERATED IN PARALLEL MODE
- 90 - DESIGN CRITERIA AND OPERATIONAL LIMITS FOR AXIAL FLOW FANS OPERATED IN PARALLEL MODE Dr.-Ing. Schiller, F. Howden Ventilatoren GmbH, Heidenheim ABSTRACT Axial Flow Fans are the preferred fan types
Field Service and Replacement Parts for Air Cooled Heat Exchangers
Field Service and Replacement Parts for Air Cooled Heat Exchangers qüéêã~ä=båöáåééêáåö= GEA Rainey Corporation ROMO=tÉëí=`Ü~ååÉä=oç~ÇI=`~íççë~I=lâä~Üçã~=TQMNR= qéäk=evnuf=ossjpmsmi=ëéêîáåéé~êíë]öé~ê~áåéókåçã=
AIR CONDITIONING TECHNOLOGY
AIR CONDITIONING TECHNOLOGY PART 9 Water Cooled Condensers & Cooling Towers IN LAST month s article we looked at how Air Cooled Condensers are used to transfer the total heat of rejection from the air
Minor losses include head losses through/past hydrants, couplers, valves,
Lecture 10 Minor Losses & Pressure Requirements I. Minor Losses Minor (or fitting, or local ) hydraulic losses along pipes can often be estimated as a function of the velocity head of the water within
Product Data Bulletin
Product Data Bulletin Adjustable Frequency Drives and HVAC Systems An Application Guide September, 1994 Raleigh, NC, U.S.A. INTRODUCTION All buildings pose the same problem: how to heat or cool the air
WINDER SYSTEMS GE Industrial Control Systems
WINDER SYSTEMS Systems Concepts Terminology GE Industrial Control Systems APPLICATION TECHNIQUES With a smooth metal surface material, a paper liner is sometimes wound with a coil. The paper is lightweight
ENERGY LOSS AND EFFICIENCY OF POWER TRANSMISSION BELTS
www.carlislebelts.com [email protected] Reprinted by Permission from: Third World Energy Engineering Congress The Association of Energy Engineers, Atlanta, Georgia ENERGY LOSS AND EFFICIENCY OF POWER
INSTRUCTIONS FOR HOW TO PROPERLY SELECT A FAN OR BLOWER
INSTRUCTIONS FOR HOW TO PROPERLY SELECT A FAN OR BLOWER The instructions that follow are to assist you in completing the information required when making a fan or blower selection. If you need additional
ENGINEERING DATA. Fan Performance Troubleshooting Guide
Information and Recommendations for the Engineer ENGINEERING DATA Aerovent TC Ventco Fiber-Aire Twin City Fan & Blower TC Axial Clarage Fan Performance Troubleshooting Guide ED- Introduction Trying to
Agricultural Pumping Efficiency Improvements
APPLICATION NOTE An In-Depth Examination of an Energy Efficiency Technology Agricultural Pumping Efficiency Improvements Summary...1 How This Technology Saves Energy...2 Types of Energy Efficiency Measures...4
Drives and motors. A guide to using variable-speed drives and motors in retail environments
Drives and motors A guide to using variable-speed drives and motors in retail environments Improving energy efficiency and lowering the carbon footprint Retailers across the UK take their corporate responsibility
Once you know the volume of air and the static pressure of the system to be cooled, you can determine the fan specifications for your product.
COOLING FAN REQUIREMENTS CALCULATIONS Determining System Impedance Determining the actual airflow produced by a fan mounted in an enclosure is much more difficult than calculating the airflow required.
Frequently Asked Questions
Frequently Asked Questions System and Valve Basics: 1. Q: What is good cooling coil performance? A: The temperature range is controlled within +/- 0.5 F (0.28 C) off the cooling coil at set point or below.
Fan Basics and Selection Criteria (How to Use)
Feature: Understanding SANYO DENKI Products from Scratch Fan Basics and Selection Criteria (How to Use) Honami Osawa 1. Introduction In recent years, the importance of cooling technology has become even
5. FANS AND BLOWERS. 5.1 Introduction. 5.2 Fan Types
5. FANS AND BLOWERS 5. Fans and Blowers Syllabus Fans and blowers: Types, Performance evaluation, Efficient system operation, Flow control strategies and energy conservation opportunities 5.1 Introduction
VAV Laboratory Room Airflow The Lowdown on Turndown
Technology Report March, 2003 VAV Laboratory The Lowdown on Turndown Turndown comparison of these two turndown ratios. Note the small actual airflow difference between them. control ranges are normally
Demand Based Static Pressure Reset Control for Laboratories
LLC Demand Based Static Pressure Reset Control for Laboratories Laboratories are generally the largest users of energy in any facility. Whether in a pharmaceutical research facility, a university or a
Data Center. Ultra-Efficient chilled water system optimization. White paper. File No: 9.236 Date: december 03, 2015 Supersedes: new Date: new
Data Center Ultra-Efficient chilled water system optimization White paper File No: 9.236 Date: december 03, 2015 Supersedes: new Date: new Data Center - Ultra-Efficient white paper 3 abstract The primary
Mobile field balancing reduces vibrations in energy and power plants. Published in VGB PowerTech 07/2012
Mobile field balancing reduces vibrations in energy and power plants Published in VGB PowerTech 07/2012 Dr. Edwin Becker PRÜFTECHNIK Condition Monitoring PRÜFTECHNIK Condition Monitoring GmbH 85737 Ismaning
The Effect of Forced Air Cooling on Heat Sink Thermal Ratings
zpero 1 The Effect of Forced Air Cooling on Heat Sink Thermal Ratings By Paul Bachman, Fellow Engineer & Ronnie Haiduk, Applications Engineer, Crydom, Inc. ABSTRACT A heat sink s ability to dissipate thermal
/ Marley NC Class Cooling Tower /
/ Marley NC Class Cooling Tower / Q u i e t B y D e s i g n Four-cell NC Class cooling tower serving a municipal power plant. T h e R e s u l t o f S o u n d E n g i n e e r i n g The NC Class not only
UNDERSTANDING REFRIGERANT TABLES
Refrigeration Service Engineers Society 1666 Rand Road Des Plaines, Illinois 60016 UNDERSTANDING REFRIGERANT TABLES INTRODUCTION A Mollier diagram is a graphical representation of the properties of a refrigerant,
The Pressure Velocity (PV) Relationship for Lead Screws
The Pressure Velocity (PV) Relationship for Lead Screws Robert Lipsett, Engineering Manager Thomson Industries, Inc. Wood Dale, IL 540-633-3549 www.thomsonlinear.com The Pressure Velocity (PV) factor is
www.klmtechgroup.com TABLE OF CONTENT
Page : 1 of 26 Project Engineering Standard www.klmtechgroup.com KLM Technology #03-12 Block Aronia, Jalan Sri Perkasa 2 Taman Tampoi Utama 81200 Johor Bahru Malaysia TABLE OF CONTENT SCOPE 2 REFERENCES
How To Save Energy On A Power Supply
Technical Note: Using EC Plug Fans to Improve Energy Efficiency of Chilled Water Cooling Systems in Large Data Centers A Technical Note from the Experts in Business-Critical Continuity Introduction A U.S.
Application Information
Moog Components Group manufactures a comprehensive line of brush-type and brushless motors, as well as brushless controllers. The purpose of this document is to provide a guide for the selection and application
Fan Performance By: Mark Stevens AMCA International Deputy Executive Director Technical Affairs
Fan Performance By: Mark Stevens AMCA International Deputy Executive Director Technical Affairs Fan Performance (Paper I.D. 021) Mark Stevens Air Movement and Control Association International Abstract
Sam E. Chapple, P. Eng. Chief Technical / Business Development Officer
Hudson Products Corporation 1307 Soldiers Field Dr. Sugar Land, Texas, USA 77479-4072 Phone: (281) 275-8125 or (780) 438-3267 Telecopier: (281) 275-8211 or (780) 437-4655 Email: [email protected]
Permanent Magnet Technology within Direct Drive Cooling Tower Motors Creates System Energy Savings
Permanent Magnet Technology within Direct Drive Cooling Tower Motors Creates System Energy Savings Roman Wajda, Robbie McElveen, Bill Martin, and Steve Evon, Baldor Electric Company ABSTRACT At a time
OPERATING FANS IN PARALLEL IN VIEW OF VARIABLE FLOW RATE OUTPUT
OPERATING FANS IN PARALLEL IN VIEW OF VARIABLE FLOW RATE OUTPUT Eddy J. Jacques & Pierre J. Wauters Department of Mechanical Engineering, Unité TERM, Université Catholique de Louvain, Belgium ABSTRACT
Electric Motor Brake Horsepower Calculations
Electric Motor Brake Horsepower Calculations By Norm Christopherson These motor calculations are contained here as they apply to the changing conditions of the blower motor when pulley adjustments are
Equipment: Power Supply, DAI, Wound rotor induction motor (8231), Electrodynamometer (8960), timing belt.
Lab 13: Wound rotor induction motor. Objective: to examine the construction of a 3-phase wound rotor induction motor; to understand exciting current, synchronous speed and slip in this motor; to determine
GEAROLOGY 2-1 SPUR GEARS SPUR GEARS
GEAROLOGY 2-1 2 2-2 GEAROLOGY COMMON APPLICATIONS: Spur gears are used to Now that you ve been introduced to both Boston Gear and some of the basics of our Gearology course which we like to call Power
NUMERICAL ANALYSIS OF WELLS TURBINE FOR WAVE POWER CONVERSION
Engineering Review Vol. 32, Issue 3, 141-146, 2012. 141 NUMERICAL ANALYSIS OF WELLS TURBINE FOR WAVE POWER CONVERSION Z. 1* L. 1 V. 2 M. 1 1 Department of Fluid Mechanics and Computational Engineering,
ENERGY AUDIT REPORT MINIMUM REQUIREMENTS
ENERGY AUDIT REPORT MINIMUM REQUIREMENTS Energy Audit Reports must contain the following: 1) Eligibility Criteria: a) Evidence demonstrating that the Eligibility Criteria were met. 2) Participant Information:
AABC Specifications for Testing and Balancing HVAC Systems
AABC Specifications for Testing and Balancing HVAC Systems The Associated Air Balance Council (AABC) Total System Balancing Specifications for HVAC Testing, Balancing and Performance Verification TOTAL
Why and How we Use Capacity Control
Why and How we Use Capacity Control On refrigeration and air conditioning applications where the load may vary over a wide range, due to lighting, occupancy, product loading, ambient weather variations,
Fans and Air Handling Units. Will Rea and Paul Pilutti February 16 th, 2011
Fans and Air Handling Units Will Rea and Paul Pilutti February 16 th, 2011 HTS Lunch and Learns Available Online Visit www.htseng.com Engineering Tools Resource Center Contents Fans Fan Curves Fan Laws
Introduction of Duplex Pump HPD71+71 and Short-Stroke Pump HPV112+112
Shin-ichi Kamimura Komatsu has come up with a high-pressure, large-capacity, duplex swash plate pump, HPD71+71, as the main pump for PC160-7 and a short-length, tandem swash plate pump (short-stroke pump),
A Guide to Trouble-Free Cooling Towers
A Guide to Trouble-Free Cooling Towers A basic understanding of cooling tower operation and maintenance will help keep a cooling water system running in top condition, year after year By David M. Suptic
ENGINEERING BULLETIN No. EB 039 Product: Cooling Towers, Closed Circuit Coolers & Evaporative Condensers Date: June 2003
For Distribution ENGINEERING BULLETIN No. EB 039 Product: Cooling Towers, Closed Circuit Coolers & Evaporative Condensers Date: June 2003 Purpose: Variable Frequency Drives The purpose of this Engineering
Accurate Air Flow Measurement in Electronics Cooling
Accurate Air Flow Measurement in Electronics Cooling Joachim Preiss, Raouf Ismail Cambridge AccuSense, Inc. E-mail: [email protected] Air is the most commonly used medium to remove heat from electronics
FANS & BLOWERS. Energy Efficiency Reference Guide. Airflow Volume. Ducted Propeller
Total Pressure FANS & BLOWERS Energy Efficiency Reference Guide Radial-Blade Centrifugal Tubeaxial Backward-inclined Airfoil Centrifugal Forward-curved Centrifugal Ducted Propeller Airflow Volume DISCLAIMER:
CENTRIFUGAL PUMP OVERVIEW Presented by Matt Prosoli Of Pumps Plus Inc.
CENTRIFUGAL PUMP OVERVIEW Presented by Matt Prosoli Of Pumps Plus Inc. 1 Centrifugal Pump- Definition Centrifugal Pump can be defined as a mechanical device used to transfer liquid of various types. As
New Deluxe Wall Mounted Heat Pump Series EXTERIOS
New Deluxe Wall Mounted Heat Pump Series EXTERIOS May 2013 New Deluxe Wall Mounted Heat Pump Series Panasonic Adding New Air Conditioner Lineup Setting Another Mile Stone in the US Ductless Split History
Duct Design. Presented by Dave Janquart
Duct Design Presented by Dave Janquart Overview of Topics Duct design Duct insulation SMACNA Standards Factors Influencing Duct Design Equipment Losses Air Velocity Duct Material Duct Size & Shape Length
INSTALLATION AND MAINTENANCE INSTRUCTIONS FOR THREE PHASE INDUCTION MOTORS
INSTALLATION AND MAINTENANCE INSTRUCTIONS FOR THREE PHASE INDUCTION MOTORS Frames 143T - 449TZ 5100 North IH 35 Round Rock, Texas 78681 Phone: 800-451-8798 512-255-4141 Fax: 512-244-5512 RECEIVING 1. Check
Characteristics of Centrifugal Blower and Its Effective Use in High Static Pressure Area
Characteristics of Centrifugal Blower and Its Effective Use in High Static Pressure Area Masayuki TAKAHASHI With small fans, selecting the right fan that most fits the purpose is extremely important from
GEAROLOGY 4-1 WORMS AND WORM GEARS WORMS AND WORM GEARS
GEAROLOGY 4-1 4 4-2 GEAROLOGY COMMON APPLICATIONS: Worm and worm gear sets are used in many, everyday products including: electrical mixers, hubometers, right Now that you have an understanding of two
Applying Pressure Independent Control Valves in H.V.A.C. Systems. A Presentation to: Orange Empire ASHRAE Santa Ana Nov. 17, 2009
Applying Pressure Independent Control Valves in H.V.A.C. Systems A Presentation to: Orange Empire ASHRAE Santa Ana Nov. 17, 2009 1 Introduction I know, as building design consultants, so much of your effort
Optimum fin spacing for fan-cooled heat sinks
Optimum fin spacing for fan-cooled heat sinks Keywords: optimum fin spacing fan-cooled heat sink heatsink optimal fin pitch parallel plate fin array optimization forced air cooling fan curve pressure drop
Chapter 4.5: Electric Motors, Variable Speed Drives
Short type questions Chapter 4.5: Electric Motors, Variable Speed Drives 1. The resistance of a motor stator winding at 30 C is 0.264 ohms per phase. What will be the resistance of the stator winding per
Pumps: Convert mechanical energy (often developed from electrical source) into hydraulic energy (position, pressure and kinetic energy).
HYDRAULIC MACHINES Used to convert between hydraulic and mechanical energies. Pumps: Convert mechanical energy (often developed from electrical source) into hydraulic energy (position, pressure and kinetic
The Secret of Hydraulic Schematics. BTPHydraulics www.iranfluidpower.com
The Secret of Hydraulic Schematics BTPHydraulics www.iranfluidpower.com www.iranfluidpower.com Table of Contents The Secret to Reading and Interpreting Hydraulic Schematics... 1 Hydraulic System Schematics...
Example. Fluid Power. Circuits
Example Fluid Power Circuits To Enhance Symbol Reading Skills To Work On Circuit Reading Skills With Answers HI LO Pump Circuit 18 A1 B1 17 16 15 13 Set 14 2,000 PSI PG2 Set 500 PSI 12 11 7 8 10 PG1 9
FIXED DISPLACEMENT HYDRAULIC VANE PUMPS BQ SERIES
BQ FIXED DISPLACEMENT HYDRAULIC VANE PUMPS BQ SERIES Versatility, power, compactness and low running costs are the main characteristics of B&C vane pumps. All the components subject to wear are contained
Evaporative Cooling System for Aquacultural Production 1
Fact Sheet EES-100 March 1993 Evaporative Cooling System for Aquacultural Production 1 C. D. Baird, R. A. Bucklin, C. A. Watson and F. A. Chapman 2 INTRODUCTION Florida aquaculture sales totaled $54 million
Unidrive M Energy Savings
Unidrive M Energy Savings Why is this important? Some Data: Money, Lots of Money >13.5m electric motors 1Hp or greater installed in US industrial process operations. Industry spends >$33b annually on electricity
TECHNICAL INFORMATION Bulletin
Peerless Pump Company 2005 Dr. M.L. King Jr. Street, P.O. Box 7026, Indianapolis, IN 46207-7026, USA Telephone: (317) 925-9661 Fax: (317) 924-7338 www.peerlesspump.com www.epumpdoctor.com TECHNICAL INFORMATION
SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS
SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS UNIT OBJECTIVES After studying this unit, the reader should be able to Describe the different types of open single-phase motors used to drive
COOLING TECHNOLOGY INSTITUTE
PAPER NO: CATEGORY: TP09-18 FANS COOLING TECHNOLOGY INSTITUTE RECENT DEVELOPMENTS IN MOTOR TECHNOLOGY ALLOW DIRECT DRIVE OF LOW SPEED COOLING TOWER FANS ROBBIE MCELVEEN BILL MARTIN RYAN SMITH BALDOR ELECTRIC
Basic Selection & Proper Application of Overhead Air Distribution Devices
Basic Selection & Proper Application of Overhead Air Distribution Devices GRD Selection & Application Terms Selection Throw Sound Installation Variations affect Performance Inlet Effects Basics Return
Compressed air systems. How to plan, install and operate. Best Practices for Maintenance Management
electronically REPRINTED FROM APRIL 2013 Best Practices for Maintenance Management If a shop builds and operates its compressed air system to avoid common problems including inadequate flow, leaks and
DIRECT CURRENT GENERATORS
DIRECT CURRENT GENERATORS Revision 12:50 14 Nov 05 INTRODUCTION A generator is a machine that converts mechanical energy into electrical energy by using the principle of magnetic induction. This principle
ENGINE COOLING SYSTEM
ENGINE COOLING SYSTEM 1988 Toyota Celica 1987-88 TOYOTA Engine Cooling Systems Celica DESCRIPTION The basic liquid cooling system consists of a radiator, water pump, thermostat, cooling fan, pressure cap,
Variable-Speed Fan Retrofits for Computer-Room Air Conditioners
Variable-Speed Fan Retrofits for Computer-Room Air Conditioners Prepared for the U.S. Department of Energy Federal Energy Management Program Technology Case Study Bulletin By Lawrence Berkeley National
NO LOAD & BLOCK ROTOR TEST ON THREE PHASE INDUCTION MOTOR
INDEX NO. : M-142 TECHNICAL MANUAL FOR NO LOAD & BLOCK ROTOR TEST ON THREE PHASE INDUCTION MOTOR Manufactured by : PREMIER TRADING CORPORATION (An ISO 9001:2000 Certified Company) 212/1, Mansarover Civil
AKRON EDUCTORS TROUBLESHOOTING GUIDE OPERATION & THEORY OF EDUCTORS GENERAL OPERATING AND MAINTENANCE INSTRUCTIONS
AKRON EDUCTORS TROUBLESHOOTING GUIDE OPERATION & THEORY OF EDUCTORS GENERAL OPERATING AND MAINTENANCE INSTRUCTIONS Products Include: 60 gpm eductors Style 3060, 3061, 3062 & 3070 95 gpm eductors Style
On-Demand Ventilation Energy Saving in Industrial Applications
On-Demand Ventilation Energy Saving in Industrial Applications Ales Litomisky, Ecogate, Inc. ABSTRACT The purpose of this paper is to describe innovative on-demand industrial ventilation. These on-demand
HVAC SYSTEM (HEATER, VENTILATOR, AND A/C)
HVAC SYSTEM (HEATER, VENTILATOR, AND A/C) HEATER SYSTEM 1. Heater System A: GENERAL A semi-center type integrated air conditioning unit is used, where a high performance heater core and an evaporator core
EFFECT OF OBSTRUCTION NEAR FAN INLET ON FAN HEAT SINK PERFORMANCE
EFFECT OF OBSTRUCTION NEAR FAN INLET ON FAN HEAT SINK PERFORMANCE Vivek Khaire, Dr. Avijit Goswami Applied Thermal Technologies India 3rd Floor,C-Wing,Kapil Towers, Dr. Ambedkar Road, Pune- 411 1 Maharashtra,
Vapor Chambers. Figure 1: Example of vapor chamber. Benefits of Using Vapor Chambers
Vapor Chambers A vapor chamber is a high-end thermal management device that can evenly dissipate heat from a small source to a large platform of area (see Figure 1). It has a similar construction and mechanism
Equipment: Power Supply, DAI, Universal motor (8254), Electrodynamometer (8960), timing belt.
Lab 12: The universal motor. Objective: to examine the construction of the universal motor; to determine its no-load and full-load characteristics while operating on AC; to determine its no-load and full-load
Propeller Efficiency. Rule of Thumb. David F. Rogers, PhD, ATP
Propeller Efficiency Rule of Thumb David F. Rogers, PhD, ATP Theoretically the most efficient propeller is a large diameter, slowly turning single blade propeller. Here, think the Osprey or helicopters.
Evaluation Of Hybrid Air- Cooled Flash/Binary Power Cycle
INL/CON-05-00740 PREPRINT Evaluation Of Hybrid Air- Cooled Flash/Binary Power Cycle Geothermal Resources Council Annual Meeting Greg Mines October 2005 This is a preprint of a paper intended for publication
High Altitude HVAC. Silvertip Integrated Engineering Consultants [email protected] www.silvertipconsultants.com
Presentation to: Rocky Mountain ASHRAE 2013 Tech Conference April 19, 2013 High Altitude HVAC Design Considerations by: Michael D. Haughey, PE, HBDP, CEM, LEED TM AP 2013 Silvertip Integrated Engineering
FIXED DISPLACEMENT HYDRAULIC VANE PUMPS BQ SERIES
BQ FIXED DISPLACEMENT HYDRAULIC VANE PUMPS BQ SERIES Versatility, power, compactness and low running costs are the main characteristics of B&C vane pumps. All the components subject to wear are contained
Walnut Drying Design and Operation. Selecting Dryer Type. Tray Drying Before 1920. Don Osias Jim Thompson
Walnut Drying Design and Operation Don Osias Jim Thompson Selecting Dryer Type Tray Drying Before 1920 1 Stack Dryer Energy efficient High capital cost Pothole For small lots High labor cost Hopper-bottom
DIRECT STEAM INJECTION HOT WATER SYSTEMS FOR JACKETED HEATING
By Philip Sutter Pick Heaters, Inc. DIRECT STEAM INJECTION HOT WATER SYSTEMS FOR JACKETED HEATING INTRODUCTION Many process plants currently use steam or hot water to heat jacketed devices such as tanks,
FIXED DISPLACEMENT HYDRAULIC VANE PUMPS BQ SERIES
BQ FIXED DISPLACEMENT HYDRAULIC VANE PUMPS BQ SERIES Versatility, power, compactness and low running costs are the main characteristics of B&C vane pumps. All the components subject to wear are contained
Dampers. Inlet guide vane. Damper. Louvre damper. Handbook Radial Fans / Chapter 3 - Dampers REITZ List 2010 DO 1. Dampers
Inlet guide vane Damper ouvre damper Handbook Radial Fans / Chapter 3 - REITZ ist 2010 DO 1 Technical description rticle number and order code article number = component size DR D1 0 3-000 031-00 variant
Pump Maintenance - Repair
Pump Maintenance - Repair Brian Trombly Mo Droppers Cummins Bridgeway, Gaylord, Mi The basic centrifugal pump consists of two main elements: 1. The rotating element which includes an impeller and a shaft.
Application of CFD modelling to the Design of Modern Data Centres
Application of CFD modelling to the Design of Modern Data Centres White Paper March 2012 By Sam Wicks BEng CFD Applications Engineer Sudlows March 14, 2012 Application of CFD modelling to the Design of
Motors and Inverters for Environmentally Friendly Industrial Equipment
Motors and Inverters for Environmentally Friendly Industrial Equipment 238 Motors and Inverters for Environmentally Friendly Industrial Equipment Takatoshi Sakai Hideharu Tanaka Yuji Tanaka Katsuyuki Utatsu
Hydraulic Control Technology for Wind Turbine Generators
Industrial Hydraulics Electric Drives and Controls Linear Motion and Assembly Technologies Pneumatics Service Automation Mobile Hydraulics Hydraulic Control Technology for Wind Turbine Generators Extra
QSV Series Vacuums an EnPro Industries company QUINCY QSV SERIES ROTARY SCREW VACUUM PUMPS 7.5 HP TO 200 HP
QSV Series Vacuums an EnPro Industries company QUINCY QSV SERIES ROTARY SCREW VACUUM PUMPS 7.5 HP TO 200 HP QSV ROTARY SCREW VACUUM PUMPS QUINCY COMPRESSOR: THE LEADER IN INDUSTRIAL VACUUM TECHNOLOGY Pioneers