1 On-Demand Ventilation Energy Saving in Industrial Applications Ales Litomisky, Ecogate, Inc. ABSTRACT The purpose of this paper is to describe innovative on-demand industrial ventilation. These on-demand systems are already being used in the chemical, metal, and woodworking industries, achieving average electricity savings of 68% over unregulated, classical systems. Industrial Ventilation Classical Design Classically designed industrial ventilation systems utilize a large central fan and a system of ducts connecting each workstation to the fan (Fig 2). The typical fan motor size is between 50 and 350 HP, based on the number of connected workstations and the length of the duct system (losses). Larger factories use multiple systems that operate continuously for the whole shift time. Industrial ventilation is used everywhere where dust, fumes, or mist is created, such as the woodworking, metal working, food processing, and pharmaceutical industries. Systems are designed in a way that enables ventilation from all installed machines at the same time. Correspondingly, the appropriate size of the fan motor is chosen. However, data from real factories show that, typically, less than 50 % of machinery is working at any given time; therefore, 50% of machinery is not producing dust (fume, mist); despite this fact, suction continues from all machines. The Fan Law shows why electricity savings can be high. This law of physics says that at 50% reduction of air-flow which is achieved by automatically closing gates on non-operating machinery, fan motor will consume only 12.5% of electricity (an 87.5% saving) of what is required when suction is running at all workstations. Figure 1: Fan Law Power [H.P. %] Air volume [CFM %] CFM = 50 % of blast gates are closed H.P. = 12.5 % of 100 % power Air volume [CFM %] Power [H.P. %] 6-91
2 If the air volume is reduced by 50 %, then the electricity consumption of the fan motor will be reduced to 12.5% of the original power - an 87.5% saving. The laws of physics are on our side this time. The basic idea is simple: Let s equip each workstation with a sensor that detects when ventilation is necessary, and let s use a motorized gate to close the ventilation duct when ventilation is not necessary. Then the RPM of the fan can be adjusted to achieve proper air volume in the ducting (Fig. 3). However, there is a problem with this simple idea: if dust or other material is to be transported through the ducting, then it is necessary to maintain a set minimum velocity in the ducting to prevent the material from settling in ducts; also, minimum negative pressure should be maintained to overcome pressure losses in the duct system 1. When gates at non-working workstations are closed, air volume and, subsequently, air velocity in the main duct will drop and dust could settle. An on-demand dust collecting system solves this problem by using a PLC (industrial computer) that calculates the necessary air volume and the necessary negative pressure based on information from the sensors. The PLC adjusts the RPM of the fan accordingly, and it also opens additional gates at non-working machinery if this is necessary for maintaining proper air velocity. Duct diameters are smaller because they are optimized for example for 70% of air volume. The Duct Optimizer software (for Windows PC) is available to simulate and optimize the duct system for any given application. How the On-Demand System Works Each workstation is equipped with a sensor that detects when ventilation is necessary (Fig. 3). A motor-operated gate closes the ventilation duct when suction is not needed at a particular outlet. Both the sensors and the gates are connected to a central computer (industrial PLC). As a result, the computer continually receives information from the sensors and uses a software model of the ducting and fan to calculate the proper RPM (speed) of the fan and to determine the number and position of additional gates to be open whenever necessary for maintaining proper air velocity and negative pressure in the duct system. A serial line is used to communicate with the variable speed drive to adjust fan speed. Additional information for the computer is provided by a negative pressure sensor installed in the main duct. Every five minutes, the computer records the following: consumption of the fan motor, times when each workstation was switched on or off, system warnings, and errors. This data can be downloaded to any computer by a modem or via an Internet connection. Data are collected in an SQL database from which many different reports can be generated. Energy saving reports can be used for financing the Pay-by-Electricity-Savings program. Customers pay for such a system in monthly payments that do not exceed the measured cost of saved electricity. 1 This minimum negative pressure is not a constant value; it is a variable dependent on the number and position of open gates. An extreme example is when just one gate next to the fan is open: in this case, the losses in ducting are minimal, and the necessary negative pressure must exceed just the losses in the dust collector and fan. On the other hand, when the open gate is located at the far end of a long duct system, the minimum necessary negative pressure is substantially higher because it has to overcome the additional losses in a long duct system. 6-92
3 Figure 2: Unregulated (Classical) Ventilation System with Duct System Connected to each Work-Station, Central Dust Collector, Fan and Fan AC Motor Figure 3: On-Demand Ventilation System Note: each workstation is equipped with a sensor and a gate to close the ventilation duct when necessary. Both the sensors and the gates are connected to a central computer (PLC) that calculates the proper RPM (speed) of the fan and determines the number and position of additional gates to be open whenever necessary for maintaining proper air velocity and negative pressure in the duct system. 6-93
4 Figure 4: Motorized Gates for Different Duct Diameters Are Used to Close Ventilation on Non-Working Machinery Table 1: Cost of the Fan Operation at 3 Shifts and Electricity Cost $0.07-$0.20 per kwh Cost of Fan Operation Per Year 3 Shifts (24 hr. day / 7 days per week), 100% fan load $ per kwh $0.07 $0.12 $0.14 $0.16 $0.18 $0.20 Sys. Size 50 HP $21,168 $36,288 $42,336 $48,384 $54,432 $60, HP $44,272 $75,895 $88,544 $101,194 $113,843 $126, HP $88,405 $151,551 $176,810 $202,068 $227,327 $252, HP $124,161 $212,847 $248,322 $283,796 $319,271 $354, HP $221,372 $379,495 $442,744 $505,993 $569,243 $632, HP $442,744 $758,990 $885,488 $1,011,987 $1,138,485 $1,264,984 By using an on-demand ventilation system, 50 to 80% of the fan operating cost can be saved. If air-conditioning or heating is used in a plant, then, in addition to the fan operation cost savings, additional savings are achieved because less air is ventilated outside the building, i.e. it is necessary to cool /heat less make-up air. Air conditioning/heating savings are typically two times higher than fan electricity savings (depending on geographical location, operating hours and energy cost). Figure 5: Savings by On-Demand Ventilation Systems Note: A. Fan operation electricity savings, B. air conditioning/heating savings (if used), and C. emission trading (where available). 6-94
5 Heating/air conditioning cost depends on geographic location and natural gas prices Typically, 2x higher savings (than fan operation cost savings) can be achieved by reducing make-up air volume Where Is Ventilation Used? Among industries using industrial ventilation are the automobile manufacturing, printing, food processing (flour, milk powder, salt, sugar, spices), chemical (solids, fumes), petrochemical & pharmaceutical industries, the woodworking industry, the metalworking industry, dental labs. Figure 6: Industries that Use Industrial Ventilation Example 1: Chemical Industry Battery Producer This example describes the system being used by a car/boat battery producer. This factory uses 24 workstations that produce lead battery grids. Production is planned in one-week intervals, based on the orders from dealers, seasonal changes, etc. Using this information, the factory makes a decision on how many workstations it will run during the different shifts of that one-week period. Any number out of those workstations (0-24) are then planned to be used during any particular shift. Each workstation uses supply-air as well as the ventilation system. Currently, both the supply-air and the ventilation system work for all workstations even if they are not in use. Implementing an on-demand air-supply and ventilation system could significantly reduce energy use. In our example, the factory was using 600 HP to operate the fan without the on-demand system. After installation of the on-demand system, only and average of 150 HP is required to run the fan, a 450 HP reduction. 6-95
6 Savings Over Current System Figure 7: Chemical Industry How Much kwh saved?* Heating / Air Conditioning Savings* 100 % $ 10 M 90 % 70 % 80 % 70 % 5 M kwh 10 M $ 1 M 60 % 1 M kwh 1 M $ 50,000 $ 100 K 50 % 50 % 40 % 100 K $ 10 K 30 % $ 5, % 10 K $ 1 K 10 % 0 % * represents per year savings Note: typical fan operation savings by on-demand systems compared to an unregulated design (left column), typical fan operation annual kwh savings (middle column) and how much can be saved on make-up air cost per year. (Heating/air conditioning is typically not used in the chemical industry.) Figure 8: Battery Producer Note: one large unregulated 600 HP system running 24/7/365 was used originally; the new system is divided into three sections that work on-demand (not all three sec-tions are working all the time; two sections and all workstations are equipped with gates; the fan is equipped with a variable speed drive. 6-96
7 Example 2: Dental Lab Dental labs use industrial ventilation to collect dust during stages of making dental crowns, bridges and dentures. The company in this example runs 72 operating workplaces in their facility. Each workplace is equipped with a motorized gate and a sensor; in this application the sensor senses current to the hand-held tool used by dental technicians. A variable speed drive controls the fan motor (40 HP). The ventilation system is open only for workstations that are in use. The ventilation system significantly reduced noise and the amount of air ventilated outside of the building. Because the whole building is air-conditioned and less air is ventilated outside of the building, air conditioning costs have been significantly reduced. Percent [%] of Filter Time Figure 9: Dental Lab with 72 Workstations Workstation Note: the chart shows activity time of individual work-stations as a percent of total shift time; workstation 44 is used max 55% of the shift time, several other workstations about 30% of the time, but the overall average is less than 10% of total shift time. Figure 10: Dental Labs Use Industrial Ventilation to Collect Dust Particles of Plaster, Metal Alloys, and Resins during Different Stages of Dental Production Note: the company in this example runs 72 operating workplaces in their facility. 6-97
8 Figure 11: Dental Lab Note: typical fan operation savings by on-demand systems over unregulated design (left column), typical fan operation annual kwh savings (middle column) and how much can be saved on heating/air conditioning annually. Example 3: Woodworking Industry Ventilation systems are commonly used in the woodworking industry (sawdust collecting). The amount of ventilated air is relatively high. For this example, a total of 900HP was required for the ventilating systems in one factory. It has a total of seven ventilation systems in the range from HP in fan size. Woodworking machines are not cutting material all the time. According to our measurements, cutting time represents less than 50 percent of the total shift time. Average electricity savings in this particular installation are 67% compared to an unregulated system, with annual savings of $250,000 (fan operation savings). Percent [%] of Filter Time Figure 12: Woodworking industry Workstation Note: 200 HP dust collecting system with a total of 40 work-stations; chart shows percentage of shift time each workstation is active; the overall average is about 10% - a substantial opportunity to save on fan operation by using an on-demand ventilation system. 6-98
9 Figure 13: Woodworking Industry Note: a typical fan operation saving by on-demand systems over unregulated design (left column); a typical fan operation annual kwh saving (middle column); how much can be saved on heating/ air conditioning when used (right column). Example 4: Exhaust Ventilation Systems in Car Manufacturing After analyzing the performance and effectiveness of industrial ventilation systems in automobile manufacturing plants, we have identified several areas where ventilation systems are running even without a car present (see Fig 15). To optimize the efficiency of ventilation, we propose that an on-demand systems be implemented (at Toe-In operation and Dynamic Vehicle Testing) to prevent exhaust fan activity in workplaces without a car present, and to ensure optimum ventilation. (Note: other opportunities to implement on-demand ventilation in car manufacturing are in foundries, paint spray repair booths, assembly line, care lines, etc.). 6-99
10 Figure 14: Automobile Manufacturing Note: typical fan operation savings by on-demand systems over unregulated systems (left column); typical fan operation annual kwh savings (middle column); how much can be saved on heating/air conditioning annually per one factory annually (right column). Heating/air conditioning savings represent majority of savings achieved. Figure 15: Toe-In Operation TOE IN OPERATION 65 CARS/HOUR PRODUCTION LINE 65 CARS/HOUR (55 sec per car) CAPACITY = 30 CARS/HOUR TOTAL CAPACITY = 4 x 30 = 120 CARS/HOUR VENTILATION = 100,000 CFM ABOUT 65/120 = 54% IS NECESSARY ABOUT 46% IS WASTED 50,000 CPM WASTED = $ 100,000 SAVINGS ON HEATING ANNUALLY AVERAGE FANS LOAD REDUCTION ABOUT 50 kw Note: Toe-In operation uses four workplaces in parallel with a total capacity of 120 cars per hour; production line runs at 65 cars per hour, i.e. 46% of the time a car cannot be present but ventilation still runs; A substantial opportunity for an on-demand system because more than 50% of the air volume is wasted. Let s assume for this example that there are 65 cars coming on the conveyor to the Toe-In per hour. The Toe-In adjustment takes approximately seconds (30-40 cars per hour; a conservative number of 30 cars per hour is used for the savings calculation at toe-in), so there must be several toe-in places working in parallel. Under ideal conditions, two working places 6-100
11 would be enough, but in real life there are four Toe-In working places for each plant (each conveyor) to compensate for possible equipment malfunction or various small delays. Nevertheless, it is obvious that the average use of these four working places is approximately 50%, and we therefore recommend that the on-demand ventilation system be implemented here because there is a substantial saving opportunity. Dynamic Vehicle Testing (DVT) Let s assume in this example that there are 65 cars coming to the DVT from the production line each hour. The DVT adjustment takes approximately seconds (24-30 cars per hour; conservative number of 24 cars per hour is used for the savings calculation at DVT), so there are several DVT places working in parallel. Optimally, 2-3 working places would be enough, but in real life there would be five workplaces here on each production line (conveyor) to compensate for possible disruptions or equipment malfunction. Nevertheless, it is obvious that the average use of these five working places is approximately 50%. We therefore recommend that the on-demand system be implemented here because there is a substantial saving opportunity. Figure 16: Block Diagram of the On-Demand Ventilation System for Toe-In and Dynamic Vehicle Testing On-demand ventilation system for Toe-in and DVT operations Inputs (car presence obtained from Toe-In or DVT control systems) and gates are connected to a central computer (industrial PLC) The computer also regulates the speed of the fan via a variable speed drive unit 6-101
12 Conclusion Based on our studies over 100 factories average workstation use is 30-50% of total shift time. Because workstation utilization is low ventilation can be designed 50-80% more efficiently if an on-demand system is implemented. Potential energy savings in the USA is 26 billion kwh per year with potential savings of electricity cost $ 1.8 billion per year; pollution offset $ 33 billion Lb CO 2 per year. References Industrial Ventilation Statistics by Ales Litomisky 2005, IETC 2006, New Orleans New Saving Opportunity: On-demand Industrial Ventilation; Ales Litomisky, Energy Engineering Vol. 103, No.3, 2006 Ecogate Q&A for industrial designers The United Sates review, International Energy Agency, 9 rue de la Federation, Paris, France The Energy Factor, Energy User News, September 2002, Special report for senior executives Energy Star Article: Finding the money for energy efficient projects, published in Energy User News Richard R. Vaillencourt, PE: The Correct Formula for Using the Affinity Laws, When There Is a Minimum Pressure Requirement Industrial Ventilation, A Manual of Recommended Practice, 24 th Edition, published by American Conference of Governmental Industrial Hygienists 6-102
Centrifugal Fans and Pumps are sized to meet the maximum
Fans and Pumps are sized to meet the maximum flow rate required by the system. System conditions frequently require reducing the flow rate. Throttling and bypass devices dampers and valves are installed
Energy Savings With Adjustable Frequency Drives. for Centrifugal Fans
Energy Savings With Adjustable Frequency Drives for Centrifugal Fans 2 Centrifugal Fans Centrifugal Fan Fans are designed to be capable of meeting the maximum demand of the system in which they are installed.
NFPA Combustible Dust Compliance and the Industrial Ventilation System
NFPA Combustible Dust Compliance and the Industrial Ventilation System Presented By: Tom Kroeger PE [email protected] Kirk & Blum, a CECO Environmental Company Marty Schloss PE [email protected]
NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES
NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES 8.1 INTRODUCTION Testing, adjusting, and balancing of HVAC systems can best be accomplished by following a series of systematic procedures. The NEBB TAB
Clearing the air A simple guide to buying and using local exhaust ventilation (LEV)
Clearing the air A simple guide to buying and using local exhaust ventilation (LEV) Clearing the air Health and Safety A simple guide to buying and using local exhaust ventilation (LEV) Every year, thousands
Demand Based Static Pressure Reset Control for Laboratories
LLC Demand Based Static Pressure Reset Control for Laboratories Laboratories are generally the largest users of energy in any facility. Whether in a pharmaceutical research facility, a university or a
Hybrid shunter locomotive
Hybrid shunter locomotive 1 Hervé GIRARD, Presenting Author, 2 Jolt Oostra, Coauthor, 3 Joerg Neubauer, Coauthor Alstom Transport, Paris, France 1 ; Alstom Transport, Ridderkerk, Netherlands 2 ; Alstom
vacon ac drives for mining & minerals
vacon ac drives for mining & minerals 1 strong experience in mining & minerals Vacon AC drives are robust to handle your most demanding requirements from simple ventilation to the most complex load sharing
Cooking at the Speed of light!
Cooking at the Infrared Cooking & Colouring Infrabaker is a modular infrared continuous cooking system developed by Infrabaker International. The machine is designed to cook and/or put colour on a wide
My Industrial Ventilation System Used to Work: The Role of System Documentation in Restoring System Performance
RMS AIHA Technical Conference September 17, 2015 My Industrial Ventilation System Used to Work: The Role of System Documentation in Restoring System Performance Keith D. Robinson, P.E. Presentation Outline
With the background of fulfilling public commitments for ECONO-PILOT ENERGY-SAVING SYSTEM FOR WATER PUMPS
ECONO-PILOT ENERGY-SAVING SYSTEM FOR WATER PUMPS SAWAI Tsuneji *1 TAKAHASHI Hiroshi *1 INOUE Ken-ichi *2 We have developed the Econo-Pilot energy-saving system for water pumps, which reduces the power
Drives and motors. A guide to using variable-speed drives and motors in car parks
Drives and motors A guide to using variable-speed drives and motors in car parks Helping car parks meet the energy and CO 2 reduction challenge In the UK, as population density increases and space becomes
HEATER, AIR CONDITIONING AND VENTILATION
55-1 GROUP 55 HEATER, AIR CONDITIONING AND VENTILATION CONTENTS GENERAL DESCRIPTION 55-2 HEATER AND AIR CONDITIONING SYSTEM 55-4 HEATER CONTROL 55-6 A/C-ECU 55-7 A/C COMPRESSOR 55-9 CONDENSER 55-9 DUCT
Case Studies: Infrared Heating in Industrial Applications
Case Studies: Infrared Heating in Industrial Applications Chao Chen, Puget Sound Energy ABSTRACT Puget Sound Energy (PSE) is a utility which serves more than one million electric customers and over 700,000
ENHANCED LABORATORY HVAC SYSTEM
ENHANCED LABORATORY HVAC SYSTEM INTRODUCTION Since the early 1980's the attention to more energy efficient laboratory designs has been on the rise due to the increase in energy cost and the emergence of
Fan Applications & System Guide
Fan Applications & System Guide Airflow for general ventilation can be calculated by; Area Method Air Change Method Occupancy Method Ventilation Calculation Methods Area Method Derives the ventilation
OPERATION MANUAL. Total Heat Exchanger HRV (Heat Reclaim Ventilation) (Ceiling mounted duct type)
OPERATION MANUAL (Ceiling mounted duct type) VAM50FB VAM500FB VAM650FB VAM800FB VAM000FB VAM500FB VAM000FB 8 7 6 9 5 7 5 0 6 8 6 9 0 5 5 7 7 6 7 A A B B 5 6 5 6 7 VAM50F VAM800F VAM500F VAM500F VAM000F
Electric Motor Brake Horsepower Calculations
Electric Motor Brake Horsepower Calculations By Norm Christopherson These motor calculations are contained here as they apply to the changing conditions of the blower motor when pulley adjustments are
WEEKLY SAFETY MEETING All Euramax Subsidiaries COMBUSTIBLE DUST. Safety Meeting Contents. Meeting Notice. Leaders Guide.
Safety Meeting Contents Meeting Notice Leaders Guide Employee Handout Employee Quiz Meeting Sign-In Sheet Employee Puzzle PRIOR TO THE WEEKLY MEETING: - Post the meeting notice by the timeclock - Read
Energy Benchmarking Report for Lafayette Elementary School Bound Brook, NJ
Energy Benchmarking Report for Lafayette Elementary School Bound Brook, NJ (for the period: March 2007 through February 2009) Prepared by: Background & Findings The New Jersey Clean Energy Program (NJCEP)
factor max Delivering Electrical Efficiency INFORMATION PACK factor max
INFORMATION PACK Delivering Electrical Efficiency Where innovation leads the way is a Canadian company that distributes efficient energy saving devices for commercial and industrial customers. The solutions
THE CASE FOR A REFRIGERATION PREVENTATIVE MAINTENACE PROGRAM
THE CASE FOR A REFRIGERATION PREVENTATIVE MAINTENACE PROGRAM Prepared and Presented By: Don Langston President & CEO, Aire Rite Air Conditioning & Refrigeration Inc Setting the Foundation The Refrigeration
Chapter 3.5: Fans and Blowers
Part I: Objective type questions and answers Chapter 3.5: Fans and Blowers 1. The parameter used by ASME to define fans, blowers and compressors is a) Fan ration b) Specific ratio c) Blade ratio d) Twist
Unico Inverter. Unique and efficient.
Unico Inverter. Unique and efficient. INTERNATIONAL PATENT PENDING The first fixed air conditioner without outdoor unit featuring DC Inverter technology. Great performance, reduced consumption. Designed
CITY OF LOS ANGELES PERSONNEL DEPARTMENT CAREER OPPORTUNITIES FOR MECHANICAL HELPER
CITY OF LOS ANGELES PERSONNEL DEPARTMENT CAREER OPPORTUNITIES FOR MECHANICAL HELPER This information is being given to you to describe potential opportunities as a Helper. The career ladders that Helpers
Programmable Logic Controllers
Programmable Logic Controllers PLC Basics Dr. D. J. Jackson Lecture 2-1 Operating systems and application programs A PLC contains a basic operating system that allows for: Downloading and executing user
VAV Laboratory Room Airflow The Lowdown on Turndown
Technology Report March, 2003 VAV Laboratory The Lowdown on Turndown Turndown comparison of these two turndown ratios. Note the small actual airflow difference between them. control ranges are normally
9/15/2011. Presented by: Jason Reason, CIH, CSP, CHMM Senior Industrial Hygienist Indiana Occupational Safety and Health Administration
OSHA Combustible Dust Inspections Presented by: Jason Reason, CIH, CSP, CHMM Senior Industrial Hygienist Indiana Occupational Safety and Health Administration Overview Background Information OSHA Combustible
Direct Fresh Air Free Cooling of Data Centres
White Paper Introduction There have been many different cooling systems deployed in Data Centres in the past to maintain an acceptable environment for the equipment and for Data Centre operatives. The
Type 1 dryers: Domestic dryers to be used primarily in a family living environment. Residences Individual apartments or condominiums
Dryer Exhaust Systems Types of Clothes Dryers Type 1 dryers: Domestic dryers to be used primarily in a family living environment. Residences Individual apartments or condominiums Type Sub 2 Title dryers:
Achieving ENERGY EFFICIENCY with Standard Air-Conditioning Units. Mike West, PhD, PE Advantek Consulting, Inc
Achieving ENERGY EFFICIENCY with Standard Air-Conditioning Units Mike West, PhD, PE Advantek Consulting, Inc Standard Air Conditioning Unit Packaged Unit Split System DX (not chilled water) Air-cooled
OSHA and Welding Exhaust
OSHA and Welding Exhaust The following has been taken directly from OSHA s General Industry Standards and Interpretations, Part 1910, Subpart Q Welding, Cutting, and Brazing. We have omitted irrelevant
Development of Ventilation Strategy in Diesel Engine Power Plant by Using CFD Modelling
Development of Ventilation Strategy in Diesel Engine Power Plant by Using CFD Modelling Panu Mustakallio and Risto Kosonen Halton Oy, Haltonintie 1-3, 47400 Kausala, Finland E-mail: [email protected]
Design Information. Designing Your Dust Collection System. Typical dust or fume collection system
Design Information Designing Your Dust Collection System There are five simple steps to designing an effective and efficient dust collection system. 1. Draw a floor plan of your shop Important Terms to
How To Save Energy On A Power Supply
Technical Note: Using EC Plug Fans to Improve Energy Efficiency of Chilled Water Cooling Systems in Large Data Centers A Technical Note from the Experts in Business-Critical Continuity Introduction A U.S.
Rainwater Harvesting
Rainwater Harvesting With climate change now a reality rather than a speculated possibility, the demand on water resources has gone up, whilst the amount of water available for supply has gone down. Forth
products 22 º C Ventilation Air Conditioning Refrigeration Energy & Cost Saving Products Inside PROVIDED BY HEINEN & HOPMAN
products > Energy & Cost Saving Products OUTSIDE 35 C HUMIDITY 90% 22 º C Inside PROVIDED BY HEINEN & HOPMAN Heating Ventilation Air Conditioning Refrigeration HVAC energy & COST SAVING POSSIBILITIES A
Airmanager Industrial HVAC retrofit results July 2013. Location Description:
Airmanager Industrial HVAC retrofit results July 2013 Location Description: Subject location is a waste composting facility in the UK that turns thousands of tons of kitchen and garden waste every year
Energy Audits Waste Water Treatment Plants
Energy Audits Waste Water Treatment Plants Ohio Water Environment Association Conference June 20, 2012 Presented by: Samuel J. Morgan, P.E., LEED AP CT Consultants, Inc. World Energy Trend US Total Energy
WHY AND HOW THE ENVIRONMENT HAS TO BE TAKEN INTO ACCOUNT AT THE WORLD SUMMIT ON THE INFORMATION SOCIETY, GENEVA 2003 TUNIS 2005
Document WSIS/PC-2/CONTR/43-E 18 December 2002 English only EPFL Working Group on the impact of ICT on the Environment WHY AND HOW THE ENVIRONMENT HAS TO BE TAKEN INTO ACCOUNT AT THE WORLD SUMMIT ON THE
Spray Booth Guideline
Department of Development Service 135 North D Street, Perris CA. 92570 Phone: (951) 443-1029 Fax: (951) 943-3293 PURPOSE The intent of this guideline is to provide the information necessary to ensure that
Understanding Operations Management The Open University (2011)
Understanding Operations Management The Open University (2011) 3 The transformation model 3.1 The transformation model The discussion above has highlighted the role of operations in creating and delivering
Conserve Insight Energy Use Monitor. User Guide
Conserve Insight Energy Use Monitor User Guide Find out how much energy your devices really use including watts, the cost of operation, and the amount of carbon dioxide (CO 2 ) produced in generating the
Glossary of Heating, Ventilation and Air Conditioning Terms
Glossary of Heating, Ventilation and Air Conditioning Terms Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment
HVAC Design Industrial Ventilation
HVAC Design Industrial Ventilation by Mike Ballew, P.E., LEED AP BD+C The Free Excel spreadsheets that accompany this course will be included with the final document that you receive when you purchase
Data Bulletin. Mounting Variable Frequency Drives in Electrical Enclosures Thermal Concerns OVERVIEW WHY VARIABLE FREQUENCY DRIVES THERMAL MANAGEMENT?
Data Bulletin April 2001 Raleigh, NC, USA Mounting Variable Frequency Drives in Electrical Enclosures Thermal Concerns OVERVIEW Variable frequency drives are available from manufacturers as enclosed engineered
Energy Saving Ideas for Your Box Plant
General Session Energy Saving Ideas for Your Box Plant Moderator: Jeff Pallini Fosber America, Inc. Program Overview: Immediate Ideas: Jim Simko of Simtek Systems, Inc. Mid-Term Ideas: John Donahue of
Solar air collectors for industry and larger halls S Ø. Efficient dehumidification and air heating for free...
Solar air collectors for industry and larger halls N S Ø Efficient dehumidification and air heating for free... This booklet contains information about SolarVenti Industrial air solar system. The system
ENERGY SAVING STUDY IN A HOTEL HVAC SYSTEM
ENERGY SAVING STUDY IN A HOTEL HVAC SYSTEM J.S. Hu, Philip C.W. Kwong, and Christopher Y.H. Chao Department of Mechanical Engineering, The Hong Kong University of Science and Technology Clear Water Bay,
CHAPTER 10: APPLIANCES AND LIGHTING
Chapter 10: Appliances and Lighting 151 CHAPTER 10: APPLIANCES AND LIGHTING According to the U.S. Environmental Protection Agency, appliances and home electronics account for 20% of energy bills in the
ENERGY AUDIT IN THE KACST BUILDING
ENERGY AUDIT IN THE KACST BUILDING S. M. Hasnain, S. H. Alawaji, A. M. Al-Ibrahim and S. M. Smiai Energy Research Institute (ERI) King Abdulaziz City for Science and Technology (KACST) P.O. Box 6086, Riyadh
Frequently Asked Questions Generators
Frequently Asked Questions Generators Fuel Related How much fuel do the generators use during normal operation? At exercise? The generator fuel consumption is given in each of the product knowledge books
Presented By: WALTER E. JOHNSTON, PE CEM, CEA, CLEP, CDSM, CPE <[email protected]
Presented By: WALTER E. JOHNSTON, PE CEM, CEA, CLEP, CDSM, CPE
Rules of Thumb Energy Efficiency in Buildings
Energy Efficiency in Buildings Energy Savings Cost Savings Increased Productivity Economic Development Other Standard lighting retrofits: $0.90-$1.20 per square foot. High-efficiency packaged and split
REFRIGERATED COMPRESSED AIR DRYERS
INNOVATIVE COMPRESSED AIR SOLUTIONS COMPRESSED AIR SOLUTIONS REFRIGERATED COMPRESSED AIR DRYERS WITH TRUE-CYCLING OPERATION 75 2,400 scfm Capacity Models STAINLESS STEEL HEAT EXCHANGERS www.zeks.com Compressed
Duct Design. Presented by Dave Janquart
Duct Design Presented by Dave Janquart Overview of Topics Duct design Duct insulation SMACNA Standards Factors Influencing Duct Design Equipment Losses Air Velocity Duct Material Duct Size & Shape Length
Basic Hydraulics and Pneumatics
Basic Hydraulics and Pneumatics Module 1: Introduction to Pneumatics PREPARED BY IAT Curriculum Unit March 2011 Institute of Applied Technology, 2011 ATM 1122 Basic Hydraulics and Pneumatics Module 1:
Pellet Process - Uses and Exposures
Pellet Process - Uses and Exposures 1 PROCESS - MANUFACTURING & USES 1 1.1 Manufacturing of pellets 2 Pellets are formed from the raw materials fine ores and additives of < 0.05 mm - into 9-16 mm spheres
HVAC Costs. Reducing Building. Building owners are caught between two powerful forces the need to lower energy costs. By Stephen J.
Reducing Building HVAC Costs of site rec By Stephen J. Pargeter Building owners are caught between two powerful forces the need to lower energy costs and the need to meet or exceed outdoor air ventilation
Do you remove fumes from robotic welding and laser cutting?
Do you remove fumes from robotic welding and laser cutting? Health and safety in the Automotive industry Do you offer a Safe and healthy Working environment? We do. To ensure a pleasant workplace for your
Information Technology Solutions
S AV E S M O N E Y Can reduce water consumption and waste disposal costs. Wastewater treatment with Vacuum Evaporation Systems Water treatment made easy! E NV IR O N ME NT F R IE N DLY Recycle water and
Fume Extraction: Guide to Safely Managing Solder Fumes in the Workplace
Fume Extraction: Guide to Safely Managing Solder Fumes in the Workplace Our thanks to OK International for allowing us to reprint the following. Why do we need fume extraction? Today s Electronics workplace
Printing and Publishing Energy Savings Guide
Printing and Publishing Energy Savings Guide Oregon printing and publishing plants face challenges of rising operating costs, environmental and other regulations, outdated equipment and customer demand
FPT FIAT POWERTRAIN TECHNOLOGIES PRESENTS ITS ENGINE RANGE FOR CONSTRUCTION APPLICATIONS AT INTERMAT 2009
FPT FIAT POWERTRAIN TECHNOLOGIES PRESENTS ITS ENGINE RANGE FOR CONSTRUCTION APPLICATIONS AT INTERMAT 2009 FPT Fiat Powertrain Technologies, is the Fiat Group Company dedicated to the research, development,
Half the cost Half the carbon
Half the cost Half the carbon the world s most efficient micro-chp What is BlueGEN? The most efficient small-scale electricity generator BlueGEN uses natural gas from the grid to generate electricity within
Environmental Benefits of Thin Computing A comparison of the environmental impacts of conventional desktop and thin computing
Environmental Benefits of Thin Computing A comparison of the environmental impacts of conventional desktop and thin computing This White Paper has been prepared for Wyse Technology Inc. March 2009 Overview
Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks
Presentation Outline Common Terms / Concepts HVAC Building Blocks Plant Level Building Blocks Description / Application Data Green opportunities Selection Criteria Air Distribution Building Blocks same
Example Retrocommissioning Measure: Opening Throttled Discharge Valves
Opening Throttled Discharge Valves This 21-story building, constructed in 1997, is located in Oregon and contains 589,000 gross square feet of mostly office occupancy. The HVAC system includes six large
PANDA SPRAY BOOTH FILTER INFORMATION
PANDA SPRAY BOOTH FILTER INFORMATION Our Spray Booth has been designed to reduce the risk of potential hazardous situations occurring. You must adhere to the specifications chart listed below when replacing
Resistors in Series and Parallel
Resistors in Series and Parallel Bởi: OpenStaxCollege Most circuits have more than one component, called a resistor that limits the flow of charge in the circuit. A measure of this limit on charge flow
USER S MANUAL HSC-24A
AIRREX AIR CONDITIONER USER S MANUAL HSC-24A Thank you for purchasing an AIRREX AIR CONDITIONER. BEFORE operation please read this user s manual carefully. Keep this manual readily available. It is ESSENTIAL
SENTRY AIR SYSTEMS, INC. PHARMACEUTICAL COMPOUNDING CONTAINMENT SYSTEMS SIMPLE SOLUTIONS FOR CLEANER AIR. www.sentryair.com 1.800.799.
SENTRY AIR SYSTEMS, INC. PHARMACEUTICAL COMPOUNDING CONTAINMENT SYSTEMS SIMPLE SOLUTIONS FOR CLEANER AIR 1.800.799.4609 www.sentryair.com Pharmaceutical Compounding Safety Solutions Sentry Air Systems
NewAir AC-14100E / AC-14100H Portable Air Conditioner Owner s Manual PLEASE READ AND SAVE THESE INSTRUCTIONS
NewAir AC-14100E / AC-14100H Portable Air Conditioner Owner s Manual PLEASE READ AND SAVE THESE INSTRUCTIONS PARTS LIST Front Back FIG.5 FIG.6 1. Control panel 2. Carrying handle 3. Water tank 4. Casters
Introduction. Motor Types
QwikSEER+ Theory of Operation and Retrofit Potential Mainstream Engineering Corporation Rockledge, FL 32955 http://www.qwik.com/products/qwikseer/index.jsp Prepared by Robert P. Scaringe and R. Paul Roth
Dry Ice Cleaning. New opportunities with FerroČrtalič d.o.o.
Dry Ice Cleaning New opportunities with FerroČrtalič d.o.o. Who is FerroČrtalič d.o.o. today? On the two sites of Novo mesto (1.000 m² covered) and Dolenjske Toplice (2.000 m² covered) now 25 people are
VendingMiser. A: VendingMiser uses three different technologies to intelligently manage the power to a vending machine.
Q: What is VendingMiser? VendingMiser Frequently Asked Ques ons A: VendingMiser is a member of the EnergyMiser family of the energy control products for vending machines which also includes the CoolerMiser,
Q. Why have we set up an energy centre and heat network in Bunhill?
FAQs: Bunhill energy centre and heat network Q. Why have we set up an energy centre and heat network in Bunhill? A. We set up a heat network in the Bunhill ward to provide cheaper, greener, locallyproduced
Remote Maintenance with Security Appliances FL MGuard RS2000 and RS4000. Economic and Reliable Service
Remote Maintenance with Security Appliances FL MGuard RS2000 and RS4000 Economic and Reliable Service Today, plants generally comprise of complex machines and systems with a high degree of automation.
MH 3M & 4M. High pressure washers with hot benefits
MH 3M & 4M High pressure washers with hot benefits The EcoPower boiler provides high efficiency and lowest equivalent fuel consumption as certified by EUnited. All key functions placed for optimal ease-of-use.
Steel Industry Systems with Integrated Mechanical and Electrical Control for High-quality Production and Energy Efficiency
Hitachi Review Vol. 59 (21), No. 4 159 Steel Industry Systems with Integrated Mechanical and Electrical Control for High-quality Production and Energy Efficiency Takenori Hatanaka Masahiro Kayama, Dr.
Integrating Computerized Maintenance Management System and Energy Efficiency Management System A Modified Approach
Integrating Computerized Maintenance Management System and Energy Efficiency Management System A Modified Approach Kifayah Abbood Alsaffar, University of Missouri, 3437 Thomas and Nell Lafferre Hall, University
Circulator Fan Performance Testing Standards BY CHRISTIAN TABER, BEMP, HBDP, MEMBER ASHRAE
This article was published in ASHRAE Journal, September 2015. Copyright 2015 ASHRAE. Posted at www.ashrae.org. This article may not be copied and/or distributed electronically or in paper form without
FAILURE MODES AND EFFECT ANALYSIS (FMEA)
FAILURE MODES AND EFFECT ANALYSIS (FMEA) INTRODUCTION While defining the functions and desired standards of performance of an asset, the objectives of maintenance with respect to that asset are defined.
Dual Maximum VAV Box Controls
ASHRAE Golden Gate Chapter November 13, 2014 Dual Maximum VAV Box Controls Steven T. Taylor, PE FASHRAE Taylor Engineering LLC staylor@taylor engineering.com Agenda VAV Box basics Sizing VAV Boxes How
SWIMMING POOL HEAT PUMP
SWIMMING POOL HEAT PUMP Installation & User Manual Model HP40B HP50B HP65B Hayward Pool Products Canada, Inc. T: 1-888-238-7665 www.haywardpool.ca CONTENT I. Application 4 II. Features 4 III. Technical
Heating your Building with Solar Energy
Heating your Building with Solar Energy Efficient, Simple and Cost Effective Natural Resources Canada Ressources naturelles Canada Solar Air Heating One of the inescapable realities of doing business
Types of Engineering Jobs
What Do Engineers Do? Engineers apply the theories and principles of science and mathematics to the economical solution of practical technical problems. I.e. To solve problems Often their work is the link
THE ELECTRIC HOOKUP. 1. Determine the wattage of various household appliances. 2. Calculate the number of kilowatt-hours used by appliances.
Objectives: The student will do the following: THE ELECTRIC HOOKUP 1. Determine the wattage of various household appliances. 2. Calculate the number of kilowatt-hours used by appliances. 3. Identify the
INDUSTRIAL AUTOMATION EQUIPMENT EDITION 2016. www.elipse-automation.eu
INDUSTRIAL AUTOMATION EQUIPMENT EDITION 2016 Your partner in an automated industry Our combination of technical know-how, product responsibility and on-time deliveries guarantees you the best WHY CHOOSE
Starting Current Reduction of Residential HVAC System and Peak-Load Impact of Power System: A Case Study
Starting Current Reduction of Residential HVAC System and Peak-Load Impact of Power System: A Case Study By Paul I-Hai Lin Professor of Electrical and Computer Engineering Technology P.E. (State of Indiana
imagine SOLAR AIR CONDITIONING MADE EASY
imagine SOLAR AIR CONDITIONING MADE EASY WHY SOLAR COOLING? Imagine...being able to fit a solar air conditioning system to your building that would result in dramatic reductions in electricity consumption
Construction Indoor Air Quality Management Plans for LEED. Matt Gregg, PE, LEED AP
Construction Indoor Air Quality Management Plans for LEED Matt Gregg, PE, LEED AP Agenda What is a Construction IAQ Management Plan? What are the LEED Requirements? What is the Mechanical Contractor s
Antonio Jose Cumbane (PhD) Maputo, 31 st May 2011
Environmental Health and Safety Aspects in the Cement Industry Antonio Jose Cumbane (PhD) Maputo, 31 st May 2011 Content The Mozambique Cement Industry Cement manufacturing Environmental Health and Safety
SIRIUX. SINGLE AND DOUBLE HIGH EFFICIENCY CIRCULATORS Heating Air-conditioning OPERATING LIMITS APPLICATIONS. 28 m 3 /h* Heads up to: Flows up to:
OPERATING LIMITS Flows up to: m /h* Heads up to: m C Max operating pressure: bars Temperature range: - à + C Max ambient temperature: + C ND of orifices: à * m /h: parallel operation SIRIUX SINGLE AND
Irrigation Pump Variable Frequency Drive (VFD) Energy Savings Calculation Methodology. Public Utility District No. 1 of Chelan County
Irrigation Pump Variable Frequency Drive (VFD) Energy Savings Calculation Methodology Public Utility District No. 1 of Chelan County This paper describes how to calculate energy saved by installing a variable
An overview of Euro VI for trucks over 3.5t. Brought to you by Mercedes-Benz
An overview of Euro VI for trucks over 3.5t Brought to you by Mercedes-Benz Contents What is Euro VI? What is Euro VI? 01 What s different about Euro VI? 02 When do you need to think about it? 03 How is