OPERATING FANS IN PARALLEL IN VIEW OF VARIABLE FLOW RATE OUTPUT
|
|
|
- Kelly Gordon
- 9 years ago
- Views:
Transcription
1 OPERATING FANS IN PARALLEL IN VIEW OF VARIABLE FLOW RATE OUTPUT Eddy J. Jacques & Pierre J. Wauters Department of Mechanical Engineering, Unité TERM, Université Catholique de Louvain, Belgium ABSTRACT Starting up a fan or modifying its setting point either by rotational speed variations or blade angle changes, obviously results in new ventilation conditions in the network, which is, of course, the object of the operation. However, since transient phenomena may then occur, particularly in complex networks, there may be a need to simulate these situations prior to any action. This is all the more true, if we are dealing with a multiple interactive fan system. Simulations with a transient model have shown that the flow in certain airways could be temporarily reversed due to the pressure variations that reach both its ends with a different time lag. This phenomenon may cause dangerous situations to occur in cases of fire or outburst of methane. It is also true that the air flow could be reversed in secondary and less powerful fans, while still rotating in the normal The study and the experimental investigation of the extension of the reverse flow characteristic is therefore justified from two points of view : a numerical simulation model for transient flow conditions must be capable of handling temporary reversed flows, and thus have appropriate fan characteristic curves available over the entire operating domain; while operating fans, reversed flows should be avoided or at least reduced. Therefore, the design of start-up procedures or real time control algorithms should take these phenomena into account. A particular interesting application is the operating of two fans in parallel. In order to investigate experimentally the characteristic curves of a fan under reversed flow conditions a small scale model was built. This facility was designed in such a manner that it was possible to carry out experiments concerning flow reversions and to try out sequential start-up procedures for two fans in parallel. INTRODUCTION As a rule, confined or nearly confined volumes where pollutants are produced, or where thermal problems could occur, need to be ventilated. However, in most of these cases, the volume flow demand of fresh air is variable in time. Therefore, the ventilation system must be designed to be flexible, i.e. to be capable of providing the necessary volume flow yet at minimum energy consumption. Fans with variable blade angles or variable rotational speeds are suitable for this job. Whether it would be more economical to work with variable rotational speeds rather than with variable blade angles, or maybe a combination of the two operating modes, is a question on its own and will be of no concern to what is being discussed in this paper. The easiest solution, if variable ventilation levels are expected, would be to cover the entire range with a single fan. But, in some cases a different solution may be preferred. Setting up two or more fans in parallel may be an attractive solution from the energy saving point of view. If for instance, during a significant part of the day, the fresh air demand fluctuates only around 5% or less of the peak ventilation capacity, it is obviously advantageous to use a pair of smaller fans connected in parallel. Also from the maintenance point of view, this solution could be justified. But, from the operational and regulating point of view it is not the easiest one. The more that, in a parallel connection scheme, each of these fans has to be fitted with a louver damper, which is, of course, an additional device to be operated. Mine networks and complex tunnel systems are often ventilated with several fans. One must be aware, though it is not always obvious at first sight, that one or more of these fans, installed at different locations in the network, could show a virtually in parallel operating scheme. How, in a general manner, a multiple fan system will react and have its impact on the flow distribution in the network is sometimes difficult to forecast, especially during transient situations due to the starting-up or stopping of certain fans. From this point of view, 1D-transient simulations could be a very helpful tool in determining the sequence of operating them. For a long time engineers knew the basic laws that rule fans in parallel and could draw the resulting characteristic curve (Osborne,1966). But, when it comes to operating them individually in order to obtain a global output volume flow that is gradually and smoothly changing from zero up to some maximum value, literature seems rather poor in giving an answer to the question stated in the next paragraph. PROBLEM STATEMENT Suppose a simple case where the volume flow rate Q needs to be adapted continuously between zero and Q max. Suppose also that for this application two identical fans are connected in parallel, each capable of a volume flow output : Q 1 = Q 2 =.5 Q max. The question then is how to operate this multiple fan
2 system. If one tries to draw, as a function of time, the output flow rate of this fan system that should be the response to a steady or stepwise increase of the volume flow demand, one would not know how to continue the plain curve once the flow rate exceeds significantly the value Q 1. Figure 1. Variable volume flow rate demand With a single fan, the dotted line in the diagram (see figure 1) would represent this further increase of the volume flow, but trying to achieve the same operation with a set of two parallel fans makes arise a few questions. They all concern the sequencing of the operations such as opening or closing dampers, starting-up or stopping a fan, changing blade angles or rotational speeds, and so on... Formulated in a more general manner, the question is how to operate successively n fans in parallel in order to obtain, at their common discharge point and without creating severe transient perturbations, m different volume flow rates ranging between zero, or Q min and Q max, Q max being the sum of the n flow rates Q n, and m being usually much larger than n. Simulations with a numerical model (Jacques,1995) show that in certain transient situations important reverse flows may occur. Without looking at the quantitative aspects of the obtained results, it is nevertheless obvious that this kind of calculations could not have been achieved if the numerical model did not include a combined characteristic in full of each fan, i.e. a characteristic that extends in the negative flow domain of a fan with its impeller still running in the normal Unfortunately, very little information exists on the dynamic behavior of a fan if its flow is forced to reverse. Some results with parallel connected fans have recently been made available (Schulze Dieckhoff, 1996). In the present state of the art, it is usually assumed (Douglas et al.,1995), and in analogy with pumps (Hanif Chaudry,1979), that the reverse flow part of the characteristic may be drawn as the mirror image with respect to the pressure axis, of a passive resistance characteristic to which the static pressure of the fan at zero volume flow rate is added. Of course, this assumption needed to be verified experimentally. FACILITY SET-UP Basically, the test facility has a modular design and has been built in such a manner that it could, on minor modifications, serve two purposes. These are, one, forcing the flow in a reverse direction through a fan, and, second, operating two fans in parallel. Figure 2. Reverse flow test facility Figure 2 shows the layout of the test facility in a first setup i.e., the reverse flow set-up. The essential elements are : Three airways, each connected to a chamber C. They form a network of three branches, B1, B2 and B3; Fan F1 which is the axial fan under study in reverse flow conditions. It is located in the first branch, B1, and its power is approximately 2 kw at 3 rpm; Regulator R in branch B2. Its main function is to control the volume flow in B1, but it acts also as a sort of security valve in case fan F1 starts to stall; Fan F3, a more powerful fan of around 5 kw at 3 rpm, is mounted in a larger duct. It has to be considered as an external fan, its only goal being to force a flow throughout the entire circuit in a reverse The different fan characteristics, and consequently also the flow rate variations, are obtained by changing the frequency of the motor of fan F1, and by using a Ward- Leonard group for moving fan F3. The entire test facility has been dimensioned in order to comply with the ISO requirements for measuring flows and pressures, at least when the air flows in what is considered to be the normal A slightly different layout of the same test facility is achieved in a second set-up, which is the parallel fan connection. Figure 3 shows the essential parts : Three airways forming the same basic network with three branches B1, B2 and B3. The latter one is a large, slightly divergent duct ending with a flow straightener and a short duct with an outlet orifice plate; Two similar, though not identical fans F1 and F2, are connected in parallel by means of two ducts of the same internal diameter. Each fan is equipped with a flow straightener, and further upstream, with in-duct orifice plates; Regulator R at the inlet side of fan F2. Figure 3. Test facility with fans in parallel MEASUREMENT INSTRUMENTATION The design of the test facility has primarily been guided by the concern to comply, when possible, with the standard procedures for measuring pressures and flow rates. When possible means : if the air flows in what is called the normal direction with regard to the fans. The volume flow rates are then measured by orifice plates. However, since the specific aim of the test facility is to determine the fan characteristic in reverse flow conditions, it is obvious that in parts of the circuit and during certain tests, the standards techniques would not be applicable. Therefore, Pitot tubes have been used with all the inconveniences thereof such as traversing problems, velocity profiles investigations, finding the right measurement locations, and so on... Static pressure is measured by a technique of averaging over four tappings, diagonally located. Direct measurements of the rotational speeds of the fans have been carried out with a revolution counter technique.
3 This information could also be checked by reading the frequency of the supply motor. 1 Pa 8 EXPERIMENTS AND RESULTS 3 rpm 6 Preliminary tests Since a great deal of the tests had to be conducted in non standard measurement conditions, it was believed that checking the balance of the three independendly measured flow rates at their junction, would give a good indication about the quality of the choosen measurement technique. This verification has been carried out for three different flow configurations. The results showed a closing error of the volume flows that did not exceed 4 % of the merging flow, and therefore, allowed us to consider that the tests could be carried out in a satisfactory manner and that the measurements would be valid. Reverse flow Submitting a fan to a forced reverse flow could lead to unfortunate consequences. In order to safeguard this as much as possible the fans, the tests have been conducted with a lot of care. The following figure 4 may show the sequence applied for gradually increasing the flow rate in the circuit, so realizing the reverse flow through fan F1. Figure 4. Sequence of the flow rate increase in the circuit Keeping the rotational speed of fan F1 as close as possible at 3 rpm, a first set of tests with different flow rates enabled one to plot the corresponding negative part of the characteristic of fan F1 (see figure 5). The same kind of tests were then repeated for two more rotational speeds which are 6 and 9 rpm respectively. These characteristics have also been drawn in figure 5. 6 rpm 9 rpm Figure 5. Fan characteristics in full at 3, 6 & 9 rpm At this point a few remarks need to be made : the experimental results around the origin of the axis are missing. The reason is that the volume flows close to zero could not be measured validly; the different duty points are obtained basically by changing the rotational speed of fan F3 and, in a few cases, by operating concurrently the regulator R. This operation causes the equivalent resistance of the entire circuit to be changed, which results in the rotational speed of fan F1 moving slightly away from its set value, in this case 3, 6 and 9 rpm. In order to obtain an homogeneous set of pressures and volume flow rates with respect to the same rotational speed of e.g. 3 rpm, the measured values have been corrected according to the similarity laws. The curve of 3 rpm shows clearly the quadratic law that rules the pressure as a function of the volume flow rate. This observation is maybe less obvious for the higher rotational speeds of fan F1 for which, due to power limitations of fan F3, the available volume flow measurement domain was less extended. Another interesting experimental result shows that the relationship between the rotational speed and the volume flow rate which is known to be linear, keeps more or less this linear behavior in the negative flow domain, notwithstanding the fact that the flow must be very turbulent. The closing error e on the flow rates at the three branch junction has been calculated for each test. The evaluation formula : e = (Q 2 + Q 3 - Q 1 ) / Q 1 applied on the eighteen test cases, yields an average value of around 1.9 %, a standard deviation of 1.6 % and a maximum value of 6.4 %. 4 2 Fans in parallel One of the problems in operating parallel fans is to determine the right time when the second fan needs to be started up because of an additional volume flow demand. As previously explained, this operation should be carried out in such a manner that the total output flow rate increases gradually, yet as fast as possible. Therefore the tests begin with fan F1 already running at its design speed, which is roughly 294 rpm at a motor frequency equal to 5 Hz. Three kind of tests are considered : Set 1. Since actions have to be taken concurrently on the
4 rotational speed of the fans and on the opening of the regulator, a first set of tests have been carried out to observe how the volume flow rates would evolve in branches B1, B2 and B3 if only the regulator is operated. These tests have then been repeated for several rotational speeds of fan F2. Figure 6 shows these parametric curves of the volume flow rate in branch B2 as a function of time. The total time that is necessary for the regulator to open, from a closed position to a full aperture, is approximately 9 s s rpm rpm 235 rpm 177 rpm 125 rpm 875 rpm 36 rpm Figure 6. Volume flow rate in branch B2 for seven rotational speeds of fan F2 Similar graphics showing the flow rate in branch B1 as well as the total output flow rate in branch B3 could also be drawn. In all these situations the resistance of the downstream part of the circuit was kept constant. For other values of this resistance, similar curves have been obtained. Set 2. The second set of the tests starts with the regulator closed and fan F2 stopped. The volume flow at the outlet of chamber C is thus the one produced by fan F1. At time equal to zero, fan F2 starts to run and reaches its maximum rotational speed after 1 s. The lower curve in figure 7 shows how the volume flow of fan F2 evolves, while the upper curve draws the total output volume flow of both fans. It is interesting to observe that nearly the total flow rate is already obtained after 4 s. Since there is an almost linear relationship between the opening time and the opening rate of the regulator, this lapse of time corresponds with the regulator half open. Further to this, one can see that it is impossible to avoid completely any flow reverse. However, this reverse volume flow moved through fan F2 is small, less than 4 % of its design capacity. The simulation also allows one to observe that the volume flow discharge of fan F2 becomes zero after 4 s. This point, defined as Z, corresponds in this case with an opening of the regulator that is roughly 5 % and a rotational speed of nearly 125 rpm. Within these 4 s, the total volume flow discharge seems not to suffer from any perturbation. The attention should nevertheless be drawn to the fact that the time span Z is dependent on the equivalent resistance of the circuit, and therefore has to be evaluated prior to the design of the actual operating procedure. Set 3. Operate both fans simultaneously in order to achieve the required flow rate Q 3 which is, of course, assumed to exceed significantly the maximum flow rate of a single fan. It is obvious that the resulting flow rate Q 3 can be obtained by several combinations of the flow rates of fans F1 and F2. Assuming that the exceeding demand is for example 5 % more, one of these combinations could be : 25 Q 3 = Q 1,max +.5 Q 2. However, it can be theorectically demonstrated that sharing the load equally over both the fans F1 and F2 is, from the energy point of view, preferable to any other workable combination. The results of tests with fan F2 moving at eight different rotational speeds and F1 at its design speed, are plotted in figure 8. They confirm experimentally the statement that it is always more efficient, and thus more economical, to have both fans running at the same rotational speed. Therefore, the control procedure should also include the setting of the motor frequencies of both fans at identical values. This operation means in this case that the rotational speeds of both fans should be changed in opposite directions, i.e. increasing one and decreasing the other, in order to reach as fast as possible the ultimate duty point where both fans run at the same rotational speed. W F1+F2 15 F1 at 294 rpm & F2 at variable rpm Z F2 5 F1 & F2 at same rpm s Z Figure 7. Discharge flow rates of fan F1 and of parallel fans F1+F Figure 8. Power consumption of two fans in parallel OPERATIONAL PROCEDURE
5 The results of the different aforementioned tests enables one to formulate an operational procedure that could be included in a local controller of a twin fan system. Once the point Z has been determined, the procedure would look as follows : 1. when the second fan needs to be put in operation, synchronize the opening rate of the louver damper with the increase of the rotational speed of the fan motor in order to reach as fast as possible the defined point Z. Then speed up the fan motor while going on with the opening of the louver damper till the required volume flow rate at the common discharge point is reached; 2. operate both fans simultaneously by changing their motor frequencies or their blade angle settings in an opposite direction in such a manner that the total flow rate remains constant. This step needs the time diagrams to be known, i.e. the variation rate of either the rotational speed or the blade angle as a function of time, because these curves might not be linear. Schulze Dieckhoff, B., Carolus, Th., 1996, Simulation of the dynamic Response of Aerodynamic Systems with Parallel Connected Axial Flow Fans, VDI Berichte 1249, p Of course, for maintenance reasons, the logic position of fans F1 and F2 can be switched, but if they are not really identical, the point Z may correspond to slightly different values for the angle setting of the louver damper and the rotational speed of the second fan. It must be emphasized that no thought has been given in this paper to the special case of combining fans with characteristics having points of contraflexure with the result that several flow rates are possible at a single value of the fan pressure. CONCLUSION The experimental work and the results described in this paper are twofold : they contribute to give experimental evidence of what had been assumed to be the fan characteristic in full, based so far only on analogies with pumps; they enable one to establish a few guide-lines for operating fans in parallel. Although the work has been carried out on a small scale model, there seems to be no reason a priori why these results could not be extended to larger fans. Nevertheless, the work could be completed by : more detailed investigations about the energy saving aspects with much larger fans; connecting parallel fans of which one is much smaller than the other. This aspect would certainly put the problem of energy saving in a different manner. REFERENCES Douglas, J.F.,Gasiorek,J.M.,Swaffield,J.A.,1995, Fluid Mechanics, Longman Scientific & Technical, England, ISBN ,p Hanif Chaudhry M., 1979, "Applied Hydraulic Transients", Van Nostrand Reinhold Company,New York, p Jacques, E., 1995, Transient Flows in Ventilation Networks, Proceedings, 7th US Ventilation Symposium, Lexington, KY, p Osborne, William C., 1966, Fans, Pergamon Press, p
PITOT-STATIC TUBE OR PITOT TUBE FOR MEASURING FLOW RATES?
XVII IMEKO World Congress Metrology in the 3rd Millennium June 22 27, 2003, Dubrovnik, Croatia PITOT-STATIC TUBE OR PITOT TUBE FOR MEASURING FLOW RATES? Eddy Jacques, Pierre Wauters Department of Mechanical
NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES
NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES 8.1 INTRODUCTION Testing, adjusting, and balancing of HVAC systems can best be accomplished by following a series of systematic procedures. The NEBB TAB
FAN PROTECTION AGAINST STALLING PHENOMENON
FAN PROTECTION AGAINST STALLING PHENOMENON Roberto Arias Álvarez 1 Javier Fernández López 2 2 1 ZITRON Technical Director [email protected] ZITRON Technical Pre Sales Management [email protected]
DESIGN CRITERIA AND OPERATIONAL LIMITS FOR AXIAL FLOW FANS OPERATED IN PARALLEL MODE
- 90 - DESIGN CRITERIA AND OPERATIONAL LIMITS FOR AXIAL FLOW FANS OPERATED IN PARALLEL MODE Dr.-Ing. Schiller, F. Howden Ventilatoren GmbH, Heidenheim ABSTRACT Axial Flow Fans are the preferred fan types
Chapter 3.5: Fans and Blowers
Part I: Objective type questions and answers Chapter 3.5: Fans and Blowers 1. The parameter used by ASME to define fans, blowers and compressors is a) Fan ration b) Specific ratio c) Blade ratio d) Twist
Centrifugal Fans and Pumps are sized to meet the maximum
Fans and Pumps are sized to meet the maximum flow rate required by the system. System conditions frequently require reducing the flow rate. Throttling and bypass devices dampers and valves are installed
ENGINEERING DATA. Fan Performance Troubleshooting Guide
Information and Recommendations for the Engineer ENGINEERING DATA Aerovent TC Ventco Fiber-Aire Twin City Fan & Blower TC Axial Clarage Fan Performance Troubleshooting Guide ED- Introduction Trying to
Chapter 8: Flow in Pipes
Objectives 1. Have a deeper understanding of laminar and turbulent flow in pipes and the analysis of fully developed flow 2. Calculate the major and minor losses associated with pipe flow in piping networks
Experiment # 3: Pipe Flow
ME 05 Mechanical Engineering Lab Page ME 05 Mechanical Engineering Laboratory Spring Quarter 00 Experiment # 3: Pipe Flow Objectives: a) Calibrate a pressure transducer and two different flowmeters (paddlewheel
FIXED DISPLACEMENT HYDRAULIC VANE PUMPS BQ SERIES
BQ FIXED DISPLACEMENT HYDRAULIC VANE PUMPS BQ SERIES Versatility, power, compactness and low running costs are the main characteristics of B&C vane pumps. All the components subject to wear are contained
Dampers. Inlet guide vane. Damper. Louvre damper. Handbook Radial Fans / Chapter 3 - Dampers REITZ List 2010 DO 1. Dampers
Inlet guide vane Damper ouvre damper Handbook Radial Fans / Chapter 3 - REITZ ist 2010 DO 1 Technical description rticle number and order code article number = component size DR D1 0 3-000 031-00 variant
Accurate Air Flow Measurement in Electronics Cooling
Accurate Air Flow Measurement in Electronics Cooling Joachim Preiss, Raouf Ismail Cambridge AccuSense, Inc. E-mail: [email protected] Air is the most commonly used medium to remove heat from electronics
Flow in data racks. 1 Aim/Motivation. 3 Data rack modification. 2 Current state. EPJ Web of Conferences 67, 02070 (2014)
EPJ Web of Conferences 67, 02070 (2014) DOI: 10.1051/ epjconf/20146702070 C Owned by the authors, published by EDP Sciences, 2014 Flow in data racks Lukáš Manoch 1,a, Jan Matěcha 1,b, Jan Novotný 1,c,JiříNožička
FIXED DISPLACEMENT HYDRAULIC VANE PUMPS BQ SERIES
BQ FIXED DISPLACEMENT HYDRAULIC VANE PUMPS BQ SERIES Versatility, power, compactness and low running costs are the main characteristics of B&C vane pumps. All the components subject to wear are contained
FIXED DISPLACEMENT HYDRAULIC VANE PUMPS BQ SERIES
BQ FIXED DISPLACEMENT HYDRAULIC VANE PUMPS BQ SERIES Versatility, power, compactness and low running costs are the main characteristics of B&C vane pumps. All the components subject to wear are contained
BASIC ELECTRONICS AC CIRCUIT ANALYSIS. December 2011
AM 5-202 BASIC ELECTRONICS AC CIRCUIT ANALYSIS December 2011 DISTRIBUTION RESTRICTION: Approved for Pubic Release. Distribution is unlimited. DEPARTMENT OF THE ARMY MILITARY AUXILIARY RADIO SYSTEM FORT
Averaging Pitot Tubes; Fact and Fiction
Averaging Pitot Tubes; Fact and Fiction Abstract An experimental investigation has been undertaken to elucidate effects of averaging stagnation pressures on estimated velocities for pressure averaging
Characteristics of Centrifugal Blower and Its Effective Use in High Static Pressure Area
Characteristics of Centrifugal Blower and Its Effective Use in High Static Pressure Area Masayuki TAKAHASHI With small fans, selecting the right fan that most fits the purpose is extremely important from
ECOCIAT. Domestic hot water heat recovery unit
Heat recovery unit Domestic hot water High energy efficiency with R410A Compact and quiet Scroll compressors Brazed-plate heat exchangers Heating Heat recovery ENVIRONMENTALLY HFC R410A PROTECTION DE FRIENDLY
ADVANCED CONTROL TECHNIQUE OF CENTRIFUGAL COMPRESSOR FOR COMPLEX GAS COMPRESSION PROCESSES
ADVANCED CONTROL TECHNIQUE OF CENTRIFUGAL COMPRESSOR FOR COMPLEX GAS COMPRESSION PROCESSES by Kazuhiro Takeda Research Manager, Research and Development Center and Kengo Hirano Instrument and Control Engineer,
Technical Support Bulletin Nr. 20 Special AC Functions
Technical Support Bulletin Nr. 20 Special AC Functions Summary! Introduction! Hot Start Control! Adaptive Control! Defrost Start Temperature Compensation Control! Anti-Sticking Control! Water Free Cooling
Surface Technology. Centrifugal Fan GMD
Centrifugal Fan ATEX classed adapted for paint shops Wide assortment broad area of application Service friendly low maintenance costs Headquarters: Centrifugal Fan Centrifugal Fan is a direct driven industrial
www.klmtechgroup.com TABLE OF CONTENT
Page : 1 of 26 Project Engineering Standard www.klmtechgroup.com KLM Technology #03-12 Block Aronia, Jalan Sri Perkasa 2 Taman Tampoi Utama 81200 Johor Bahru Malaysia TABLE OF CONTENT SCOPE 2 REFERENCES
3-PHASE LOW VOLTAGE NETWORK LOAD BALANCER : A COST EFFECTIVE SOLUTION TO LINE VOLTAGE VARIATIONS
3-PHASE LOW VOLTAGE NETWORK LOAD BALANCER : A COST EFFECTIVE SOLUTION TO LINE VOLTAGE VARIATIONS Pierre FRISTOT Olivier CONSTANT Catherine MONCET Omegawatt - France Omegawatt - France SDET - France [email protected]
SECTION 23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION
SECTION 23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION The purpose of this guide specification is to assist the specifier in correctly specifying Mechanical System Testing
Basic Electronics Prof. Dr. Chitralekha Mahanta Department of Electronics and Communication Engineering Indian Institute of Technology, Guwahati
Basic Electronics Prof. Dr. Chitralekha Mahanta Department of Electronics and Communication Engineering Indian Institute of Technology, Guwahati Module: 2 Bipolar Junction Transistors Lecture-2 Transistor
Experiment 3 Pipe Friction
EML 316L Experiment 3 Pipe Friction Laboratory Manual Mechanical and Materials Engineering Department College of Engineering FLORIDA INTERNATIONAL UNIVERSITY Nomenclature Symbol Description Unit A cross-sectional
Extremely compact in size to allow direct flange-mounting on vehicle engine or gearbox PTOs.
TXV - Presentation pumps with Load Sensing control variable displacement piston pumps ADVANTAGES pumps are variable displacement with pressure-flow control called Load Sensing. They self-regulate to give
VDI 2206 Prof. Dr. Magdy M. Abdelhameed
Course Code: MDP 454, Course Name:, Second Semester 2014 VDI 2206 Mechatronics System Design The mechatronic design methodology is based on a concurrent (instead of sequential) approach to discipline design,
8 Speed control of Induction Machines
8 Speed control of Induction Machines We have seen the speed torque characteristic of the machine. In the stable region of operation in the motoring mode, the curve is rather steep and goes from zero torque
Experimental Evaluation of the Discharge Coefficient of a Centre-Pivot Roof Window
Experimental Evaluation of the Discharge Coefficient of a Centre-Pivot Roof Window Ahsan Iqbal #1, Alireza Afshari #2, Per Heiselberg *3, Anders Høj **4 # Energy and Environment, Danish Building Research
SYNCHRONOUS MACHINES
SYNCHRONOUS MACHINES The geometry of a synchronous machine is quite similar to that of the induction machine. The stator core and windings of a three-phase synchronous machine are practically identical
FREQUENCY CONTROLLED AC MOTOR DRIVE
FREQUENCY CONTROLLED AC MOTOR DRIVE 1.0 Features of Standard AC Motors The squirrel cage induction motor is the electrical motor motor type most widely used in industry. This leading position results mainly
Practice Problems on Boundary Layers. Answer(s): D = 107 N D = 152 N. C. Wassgren, Purdue University Page 1 of 17 Last Updated: 2010 Nov 22
BL_01 A thin flat plate 55 by 110 cm is immersed in a 6 m/s stream of SAE 10 oil at 20 C. Compute the total skin friction drag if the stream is parallel to (a) the long side and (b) the short side. D =
Power Quality Paper #3
The Effect of Voltage Dips On Induction Motors by: M D McCulloch 1. INTRODUCTION Voltage depressions caused by faults on the system affect the performance of induction motors, in terms of the production
Unit 24: Applications of Pneumatics and Hydraulics
Unit 24: Applications of Pneumatics and Hydraulics Unit code: J/601/1496 QCF level: 4 Credit value: 15 OUTCOME 2 TUTORIAL 1 HYDRAULIC PUMPS The material needed for outcome 2 is very extensive so there
COUNTERBALANCE VALVES
COUNTERBALANCE VALVES Introduction They are modulating valves which allow free flow into the actuator and then block the reverse flow until they feel a pilot pressure inversely proportional to the load
Closed Loop Pressure Control for the Extrusion Process
Closed Loop Pressure Control for the Extrusion Process By John Pacini Updated by Douglas Joy Extrusion is a continuous process and successful economic production depends on maintaining stable output and
Resistors in Series and Parallel
Resistors in Series and Parallel Bởi: OpenStaxCollege Most circuits have more than one component, called a resistor that limits the flow of charge in the circuit. A measure of this limit on charge flow
Pure Efficiency. C.C.I.A.A.: N REA. 0195268 Cod. Fiscale e P. IVA: 00483230173 Capitale Sociale versato 100.000,00
Pure Efficiency. The need to significantly reduce the production costs to remain competitive on the global market and the requirement to control and lessen the environmental impact of all activities are
EXPERIMENTAL RESEARCH ON FLOW IN A 5-STAGE HIGH PRESSURE ROTOR OF 1000 MW STEAM TURBINE
Proceedings of 11 th European Conference on Turbomachinery Fluid dynamics & Thermodynamics ETC11, March 23-27, 2015, Madrid, Spain EXPERIMENTAL RESEARCH ON FLOW IN A 5-STAGE HIGH PRESSURE ROTOR OF 1000
PUTTING THE SPIN IN CFD
W H I T E PA P E R PUTTING THE SPIN IN CFD Overview Engineers who design equipment with rotating components need to analyze and understand the behavior of those components if they want to improve performance.
Lab 1a Wind Tunnel Testing Principles & Lift and Drag Coefficients on an Airfoil
Lab 1a Wind Tunnel Testing Principles & Lift and Drag Coefficients on an Airfoil OBJECTIVES - Calibrate the RPM/wind speed relation of the wind tunnel. - Measure the drag and lift coefficients of an airfoil
Energy Savings With Adjustable Frequency Drives. for Centrifugal Fans
Energy Savings With Adjustable Frequency Drives for Centrifugal Fans 2 Centrifugal Fans Centrifugal Fan Fans are designed to be capable of meeting the maximum demand of the system in which they are installed.
EDEXCEL NATIONAL CERTIFICATE/DIPLOMA UNIT 5 - ELECTRICAL AND ELECTRONIC PRINCIPLES NQF LEVEL 3 OUTCOME 4 - ALTERNATING CURRENT
EDEXCEL NATIONAL CERTIFICATE/DIPLOMA UNIT 5 - ELECTRICAL AND ELECTRONIC PRINCIPLES NQF LEVEL 3 OUTCOME 4 - ALTERNATING CURRENT 4 Understand single-phase alternating current (ac) theory Single phase AC
FULL DC INVERTER SYSTEMS
FULL DC INVERTER SYSTEMS INDIDUAL AND MODULAR DESIGN & FLEXIBLE COMBINATION commercial air conditioners SDV4 2011/2012 AIR CONDITIONING 1 WELCOME TO THE WORLD of SINCLAIR AIR CONDITIONERS Company operation
Power Supplies. 1.0 Power Supply Basics. www.learnabout-electronics.org. Module
Module 1 www.learnabout-electronics.org Power Supplies 1.0 Power Supply Basics What you ll learn in Module 1 Section 1.0 Power Supply Basics. Basic functions of a power supply. Safety aspects of working
UDSA - UDSBD unit heater
APPLICATIONS Heating >> FACTORIES >> WAREHOUSES >> HALLS >> SHOWROOMS >> GREENHOUSES >> RETAIL >>... UDSA - UDSBD unit heater www.reznor.eu V3 gas fired unit heater Reznor V3 unit heaters are one of the
Rules for Classification and Construction Additional Rules and Guidelines
VI Rules for Classification and Construction Additional Rules and Guidelines 5 Pumps 1 Guidelines for the Design, Construction and Testing of Pumps Edition 2007 The following Guidelines come into force
Unsteady Pressure Measurements
Quite often the measurements of pressures has to be conducted in unsteady conditions. Typical cases are those of -the measurement of time-varying pressure (with periodic oscillations or step changes) -the
Development and optimization of a hybrid passive/active liner for flow duct applications
Development and optimization of a hybrid passive/active liner for flow duct applications 1 INTRODUCTION Design of an acoustic liner effective throughout the entire frequency range inherent in aeronautic
Material taken from Fluid Power Circuits and Controls, John S. Cundiff, 2001
Pressure Control Chapter 3 Material taken from Fluid Power Circuits and Controls, John S. Cundiff, 2001 Introduction Pressure control is a key element in the design of any circuit. Used correctly, it can
Using CFD to improve the design of a circulating water channel
2-7 December 27 Using CFD to improve the design of a circulating water channel M.G. Pullinger and J.E. Sargison School of Engineering University of Tasmania, Hobart, TAS, 71 AUSTRALIA Abstract Computational
So far we have investigated combinational logic for which the output of the logic devices/circuits depends only on the present state of the inputs.
equential Logic o far we have investigated combinational logic for which the output of the logic devices/circuits depends only on the present state of the inputs. In sequential logic the output of the
Optimum fin spacing for fan-cooled heat sinks
Optimum fin spacing for fan-cooled heat sinks Keywords: optimum fin spacing fan-cooled heat sink heatsink optimal fin pitch parallel plate fin array optimization forced air cooling fan curve pressure drop
Keywords: CFD, heat turbomachinery, Compound Lean Nozzle, Controlled Flow Nozzle, efficiency.
CALCULATION OF FLOW CHARACTERISTICS IN HEAT TURBOMACHINERY TURBINE STAGE WITH DIFFERENT THREE DIMENSIONAL SHAPE OF THE STATOR BLADE WITH ANSYS CFX SOFTWARE A. Yangyozov *, R. Willinger ** * Department
Power Electronics. Prof. K. Gopakumar. Centre for Electronics Design and Technology. Indian Institute of Science, Bangalore.
Power Electronics Prof. K. Gopakumar Centre for Electronics Design and Technology Indian Institute of Science, Bangalore Lecture - 1 Electric Drive Today, we will start with the topic on industrial drive
HITACHI INVERTER SJ/L100/300 SERIES PID CONTROL USERS GUIDE
HITACHI INVERTER SJ/L1/3 SERIES PID CONTROL USERS GUIDE After reading this manual, keep it for future reference Hitachi America, Ltd. HAL1PID CONTENTS 1. OVERVIEW 3 2. PID CONTROL ON SJ1/L1 INVERTERS 3
Advance Electronic Load Controller for Micro Hydro Power Plant
Journal of Energy and Power Engineering 8 (2014) 1802-1810 D DAVID PUBLISHING Advance Electronic Load Controller for Micro Hydro Power Plant Dipesh Shrestha, Ankit Babu Rajbanshi, Kushal Shrestha and Indraman
Flow divider (flow distributor), type TQ
Flow divider (flow distributor), type TQ Pressure p max = 0 bar Flow Q CN max = 00 lpm Share ratio = :. General Task Flow dividers type TQ are self-regulating valves, which largely irrespective of the
DIRECT CURRENT GENERATORS
DIRECT CURRENT GENERATORS Revision 12:50 14 Nov 05 INTRODUCTION A generator is a machine that converts mechanical energy into electrical energy by using the principle of magnetic induction. This principle
Fan Basics and Selection Criteria (How to Use)
Feature: Understanding SANYO DENKI Products from Scratch Fan Basics and Selection Criteria (How to Use) Honami Osawa 1. Introduction In recent years, the importance of cooling technology has become even
1 DESCRIPTION OF THE APPLIANCE
1 DESCRIPTION OF THE APPLIANCE 1.1 INTRODUCTION The cast iron SF boilers are a valid solution for the present energetic problems, since they can run with solid fuels: wood and coal. These series of boilers
Water hammering in fire fighting installation
Water hammering in fire fighting installation Forward One of major problems raised in the fire fighting network installed at Pioneer company for pharmaceutical industry /Sulaymania was the high water hammering
EFFECT OF OBSTRUCTION NEAR FAN INLET ON FAN HEAT SINK PERFORMANCE
EFFECT OF OBSTRUCTION NEAR FAN INLET ON FAN HEAT SINK PERFORMANCE Vivek Khaire, Dr. Avijit Goswami Applied Thermal Technologies India 3rd Floor,C-Wing,Kapil Towers, Dr. Ambedkar Road, Pune- 411 1 Maharashtra,
VOLTAGE REGULATOR AND PARALLEL OPERATION
VOLTAGE REGULATOR AND PARALLEL OPERATION Generator sets are operated in parallel to improve fuel economy and reliability of the power supply. Economy is improved with multiple paralleled generators by
CFD STUDY OF TEMPERATURE AND SMOKE DISTRIBUTION IN A RAILWAY TUNNEL WITH NATURAL VENTILATION SYSTEM
CFD STUDY OF TEMPERATURE AND SMOKE DISTRIBUTION IN A RAILWAY TUNNEL WITH NATURAL VENTILATION SYSTEM J. Schabacker, M. Bettelini, Ch. Rudin HBI Haerter AG Thunstrasse 9, P.O. Box, 3000 Bern, Switzerland
HEAVY DUTY STORAGE GAS
Multi-Fin flue technology Flue damper saves energy Electronic controls HEAVY DUTY STORAGE GAS Dependability The Rheem heavy duty gas range is the work horse of the industry having proved itself over many
Energy, Work, and Power
Energy, Work, and Power This worksheet and all related files are licensed under the Creative Commons Attribution License, version 1.0. To view a copy of this license, visit http://creativecommons.org/licenses/by/1.0/,
Air Conditioning Clinic
Air Conditioning Clinic Air Conditioning Fans One of the Equipment Series February 2012 TRG-TRC013-EN Air Conditioning Fans One of the Equipment Series A publication of Trane Preface Air Conditioning
Minor losses include head losses through/past hydrants, couplers, valves,
Lecture 10 Minor Losses & Pressure Requirements I. Minor Losses Minor (or fitting, or local ) hydraulic losses along pipes can often be estimated as a function of the velocity head of the water within
Frequently Asked Questions
Frequently Asked Questions System and Valve Basics: 1. Q: What is good cooling coil performance? A: The temperature range is controlled within +/- 0.5 F (0.28 C) off the cooling coil at set point or below.
INDUCTION REGULATOR. Objective:
INDUCTION REGULATOR Objective: Using a wound rotor induction motor an Induction Regulator, study the effect of rotor position on the output voltage of the regulator. Also study its behaviour under load
Relationship between Sound Pressure and Sound Power Levels
Relationship between Sound Pressure and Sound Power Levels 4 W. T. W. CORY Chairman of the Eurovent WG 1 Fans If we wish to know the sound power transmitted through a fan and ducting system, it is preferable
Pushing the limits. Turbine simulation for next-generation turbochargers
Pushing the limits Turbine simulation for next-generation turbochargers KWOK-KAI SO, BENT PHILLIPSEN, MAGNUS FISCHER Computational fluid dynamics (CFD) has matured and is now an indispensable tool for
Equipment: Power Supply, DAI, Wound rotor induction motor (8231), Electrodynamometer (8960), timing belt.
Lab 13: Wound rotor induction motor. Objective: to examine the construction of a 3-phase wound rotor induction motor; to understand exciting current, synchronous speed and slip in this motor; to determine
Modeling and Analysis of DC Link Bus Capacitor and Inductor Heating Effect on AC Drives (Part I)
00-00-//$0.00 (c) IEEE IEEE Industry Application Society Annual Meeting New Orleans, Louisiana, October -, Modeling and Analysis of DC Link Bus Capacitor and Inductor Heating Effect on AC Drives (Part
Basic Technology Series
Basic Technology Series Fundamentals of Car Air Conditioning 2007 Air Conditioning #003 The Rear Cooler Construction Fan Fan Filter Figure A : Trunk Figure B : Overhead Dual Air-Conditioner In This Issue
Chapter 10. Control Design: Intuition or Analysis?
Chapter 10 Control Design: Intuition or Analysis? Dan P. Dumdie 10.1 Introduction In previous chapters, we discussed some of the many different types of control methods available and typically used in
PULSATION REDUCTION BY ACOUSTIC FILTERS FOR METERING APPLICATIONS. Robert J. McKee Ray G. Durke
PULSATION REDUCTION BY ACOUSTIC FILTERS FOR METERING APPLICATIONS Robert J. McKee Ray G. Durke Southwest Research Institute 6220 Culebra Road San Antonio, TX 78238 INTRODUCTION Because of the adverse effects
TEA1024/ TEA1124. Zero Voltage Switch with Fixed Ramp. Description. Features. Block Diagram
Zero Voltage Switch with Fixed Ramp TEA04/ TEA4 Description The monolithic integrated bipolar circuit, TEA04/ TEA4 is a zero voltage switch for triac control in domestic equipments. It offers not only
300 MW Variable Speed Drives for Pump-Storage Plant Application Goldisthal
May 24 MW Variable Speed Drives for Aurélie Bocquel APCG / 4BOC4 (MW-Goldisthal 1-5-24).PPT MW Variable Speed Drives for Content Major benefits of the cyclo-converter driven doubly-fed induction machines
FAN ENGINEERING. ( ) ρ N. Fan Performance Troubleshooting Guide
FN ENGINEERING Information and Recommendations for the Engineer FE- Fan Performance Troubleshooting Guide Introduction Trying to determine why a fan is not working the way you want it to can sometimes
The Secret of Hydraulic Schematics. BTPHydraulics www.iranfluidpower.com
The Secret of Hydraulic Schematics BTPHydraulics www.iranfluidpower.com www.iranfluidpower.com Table of Contents The Secret to Reading and Interpreting Hydraulic Schematics... 1 Hydraulic System Schematics...
Measuring Electric Phenomena: the Ammeter and Voltmeter
Measuring Electric Phenomena: the Ammeter and Voltmeter 1 Objectives 1. To understand the use and operation of the Ammeter and Voltmeter in a simple direct current circuit, and 2. To verify Ohm s Law for
PNEUMATIC CONTROLS Selection and Description
PNEUMATIC CONTROLS Selection and Description Carnes pneumatic controlled throttling units are suitable for a standard 20 psi control system and may be supplied with pressure dependent or pressure independent
Example. Fluid Power. Circuits
Example Fluid Power Circuits To Enhance Symbol Reading Skills To Work On Circuit Reading Skills With Answers HI LO Pump Circuit 18 A1 B1 17 16 15 13 Set 14 2,000 PSI PG2 Set 500 PSI 12 11 7 8 10 PG1 9
ENERGY SAVING OF OIL HYDRAULIC PUMP UNIT BY IDLING STOP METHOD USING AN ACCUMULATOR
ENERGY SAVING OF OIL HYDRAULIC PUMP UNIT BY IDLING STOP METHOD USING AN ACCUMULATOR Katsumasa Suzuki 1, Yoshitaka Niimura 1, Kazutoshi Akitani 1 and Ken Sugimura 2 ABSTRACT In recent years, energy saving
Enhancing the SNR of the Fiber Optic Rotation Sensor using the LMS Algorithm
1 Enhancing the SNR of the Fiber Optic Rotation Sensor using the LMS Algorithm Hani Mehrpouyan, Student Member, IEEE, Department of Electrical and Computer Engineering Queen s University, Kingston, Ontario,
BAFFLES AS A MEANS OF STATION PROTECTION FROM HIGH AIR VELOCITIES - COMPARISON OF ANALYTICAL AND FIELD MEASUREMENTS RESULTS
- 289 - BAFFLES AS A MEANS OF STATION PROTECTION FROM HIGH AIR VELOCITIES - COMPARISON OF ANALYTICAL AND FIELD MEASUREMENTS RESULTS Maevski Igor, PhD, PE Jacobs Engineering, USA ABSTRACT Draught relief
PUMP AND MOTOR DIVISION
INSTALLATION MANUAL SERIES P2 and P3 MOBILE PISTON PUMP 1 Check model code / compare with your paper work Nameplate of the pump Ordering / Sales Acknowledgement 2 Check rotation of the pump Clockwise rotation
SEPARATING DUST PARTICLES USING AN AERODYNAMIC DEDUSTER
SEPARATING DUST PARTICLES USING AN AERODYNAMIC DEDUSTER DEVELOPMENT OF AN AERODYNAMIC DEDUSTER FOR LIVESTOCK BUILDINGS G.A. Zhao, Y. Zhang Summary Dust is among the major pollutants that have a detrimental
KINETIC ENERGY RECOVERY SYSTEM BY MEANS OF FLYWHEEL ENERGY STORAGE
ADVANCED ENGINEERING 3(2009)1, ISSN 1846-5900 KINETIC ENERGY RECOVERY SYSTEM BY MEANS OF FLYWHEEL ENERGY STORAGE Cibulka, J. Abstract: This paper deals with the design of Kinetic Energy Recovery Systems
Laddomat 21-60 Charging unit
Laddomat 21-60 Charging unit User and installation instructions NOTE! Diagrams in this brochure only describe connection principles. Each installation must be measured and carried out according to the
Fan Performance By: Mark Stevens AMCA International Deputy Executive Director Technical Affairs
Fan Performance By: Mark Stevens AMCA International Deputy Executive Director Technical Affairs Fan Performance (Paper I.D. 021) Mark Stevens Air Movement and Control Association International Abstract
MULTI-ENGINE TURBO-PROP AEROPLANE ENDORSEMENT
MULTI-ENGINE TURBO-PROP AEROPLANE ENDORSEMENT ENGINEERING, DATA AND PERFORMANCE QUESTIONNAIRE FOR (Aeroplane make & model) Version 1 -August 1996 Name: ARN. Endorser: ARN: (Signature/Name) 1 The endorsement
With the background of fulfilling public commitments for ECONO-PILOT ENERGY-SAVING SYSTEM FOR WATER PUMPS
ECONO-PILOT ENERGY-SAVING SYSTEM FOR WATER PUMPS SAWAI Tsuneji *1 TAKAHASHI Hiroshi *1 INOUE Ken-ichi *2 We have developed the Econo-Pilot energy-saving system for water pumps, which reduces the power
ORC TURBOGENERATOR TYPE CHP - Organic Rankine Cycle Turbogenerator fed by thermal oil, for the combined production of electric energy and heat -
Doc. : 08C00031_e Date : 10.02.2009 Page : 1 / 9 ORC TURBOGENERATOR TYPE CHP - Organic Rankine Cycle Turbogenerator fed by thermal oil, for the combined production of electric - (Preliminary) Doc. : 08C00031_e
Degrees of Freedom In HVAC Controls Design BY JOHN VARLEY, P.E., HBDP, MEMBER ASHRAE
This article was published in ASHRAE Journal, June 05. Copyright 05 ASHRAE. Posted at www.ashrae.org. This article may not be copied and/or distributed electronically or in paper form without permission