1 FAN PROTECTION AGAINST STALLING PHENOMENON Roberto Arias Álvarez 1 Javier Fernández López ZITRON Technical Director [email protected] ZITRON Technical Pre Sales Management [email protected] STALLING ON AXIAL FANS One of the main problems that could be suffered by the fans installed in the definitive ventilation systems is stalling, this being one of the major causes of concern for the operation contractors in charge of the ventilation systems of tunnels. Stalling in axial fans is a phenomenon that can be compared with the situation experienced by aircraft wings where, as the angle of incidence of the airflow is increased, the lift force increases first, but falls abruptly when a certain critical angle is exceeded. Figures 1 and 2 show both flow conditions. Figure 1 - blade operating in ideal conditions Figure 2 - blade operating in stall 1

2 In the case of the fan blades, severe separation of the flow lines along the profile of the blade occurs, and this induces a strong decrease in the increasing pressure given by the fan, impacting negatively on fan efficiency and radiated noise. The fan stalling is a situation that should always be avoided. Below there is a list of some of the main problems created by fan stalling: - Potential risk of serious damage due to blade fatigue - Fan does not develop the design performance, air flow and pressure (Lower safety level of the system). - Efficiency is lower and hence power consumption is higher. - Dramatic increase in noise. - Higher vibration levels than at normal operation. In some severe cases, stall operation for any prolonged time may result in fan blade rupture due to metal fatigue, and consequently in the damage of the major parts of the fan. Figure 3 - progressive stall starting at blade tips Concerning the noise, when the fan is operating at or near the stall region, the noise generated by the fan will be increased. In some cases, this phenomenon, known as hammering, could generate a sound as if the blades were being hit by a solid object. 2

3 On the other hand, we should be aware that ideal situations are not always the reality, and therefore we should take into account in our designs that fans could face this problem during their operational life. The air flow delivered by the fan will be determined by the intersection of the fan performance curve with the system resistance curve. In order to know the maximum system resistance that the fan will be able to deal with, a real test at full power and nominal speed prior to the fan installation on site is totally necessary. The factory acceptance test in a proper test bench then becomes one of the first steps to avoid further stall problems on site. By testing the stalling point in the factory the real margins to the fan stall limit will be known. One fan performance curve will be obtained for each impeller pitch angle, and as shown in figure 4, as the system curve increases the fan air flow delivered by the fan will decrease. Figure 4 System resistance Vs fan performance curve It would be nice if system calculations were always accurate, but sometimes wrong calculations or unexpected changes in the system resistance could make the fan operate in the stall zone. 3

4 FIGHTING AGAINST FAN STALLING As explained above, stalling is a phenomenon that should be always avoided in the fans. In order to do that, below we present a table showing the main steps for an effective fight against fan stalling. FIVE EFFECTIVE STEPS AGAINST FAN STALLING 1 st Realistic system calculation of system pressure loss 2 nd Factory fan performance test at nominal speed 3 rd Fan stall detection system 4 th System evaluation for additional pressure loss sources removal 5 th Installation of anti-stall devices in the fan 1 st step: Realistic system calculation of system pressure loss The most frequent reason of fan stalling is the wrong system pressure drop calculation. As shown above (figure 4), when the real system resistance curve is higher than the calculated one, the fan will deliver lower air flow than originally expected, and if this error is big enough, the fan will operate in stall. The tunnel safety demands are being improved every day, and hence the proposed ventilation systems are more complex, making use of dampers or roof openings necessary to comply with the tunnel ventilation demands during normal and emergency conditions. Extreme care should be taken when determining the total pressure drop value for the design volume flow, and all the system pressure drop sources should be designed to create the lowest pressure drop possible. The most standardised method to calculate the system pressure drop is the coefficient method. This methodology calculates the required pressure drop by multiplying the dynamic pressure by the experimental factors published in different literature such as Idelchik or ASHRAE. Although the coefficient method takes into account important parameters such as flow regime, turbulent or laminar, it is sometimes difficult to get accurate results and additional CFD simulations may be required. ZITRON uses FLUENT software to confirm the fan selection in those cases where traditional numerical calculations are not providing reliable results. In the following images (figure 5) it can be observed how the flow lines across different elements are not occupying all the available section, so velocity and hence dynamic pressure may not be the ones expected from the numerical calculations. 4

5 90º bend after mine collar shaft Diffuser flow discharge before splitter silencers Flow discharge to tunnel after saccardo nozzle Figure 5 CFD simulations The main advantage of using CFD simulation is that real accuracy of the air flow performance in the system can be determined, and therefore the most suitable fan with enough margin to the stall region can be selected. 5

6 Although the CFD tool is very useful for the ventilation designers, care should be taken when using this software, the right choice of the input parameters and boundary conditions being of critical importance. The validation of the CFD simulation then becomes necessary to improve the accuracy of the results obtained. In this sense, ZITRON is the company with the largest number of validated CFD simulations ; all the CFD simulations carried out by ZITRON are later validated during the ventilation system commissioning, adjusting the software theoretical values to the real ones obtained in the tunnels. 2 st step: Factory fan performance test at nominal speed Once the fan is selected, designed and manufactured, a real test at full power and nominal speed should be carried out prior to site delivery. During the test, the fan performance curve and the exact stalling region are determined, and therefore the real fan limits are known. In order to find out the maximum pressure drop that the fan will be able to generate before stalling, the test should be carried out in a proper laboratory which is able to run the fan at full power. The ZITRON test bench is an AMCA accredited laboratory (see Figure 6 certificate), and is ready for the testing of fans of up to 4 m diameter and 1600 Kw motor rated power. The test is carried out by generating several system resistance curves and then by measuring the air flow and pressure delivered by the fan all over the selected impeller pitch angle curve. In addition to the air flow and pressure, the motor power consumption is also measured, so real fan efficiency for each operation point is obtained. Figure 6 ZITRON AMCA laboratory certificate In order to get real performance curves for fans running at full power and speed, the ZITRON test bench (figure 7) is an underground tunnel of almost 100 m long, with a cross section of 52 m2. By means of an auxiliary fan with a 2800 mm impeller diameter and a circular closing 6

7 damper with continuous adjustable blade angle, all kinds of possible circuit resistances are generated, and all the fan performance curve points are tested. When the damper is closed enough, the tested fan will start to operate in stall, making it possible to record the real performance delivered under this situation, such as air flow, pressure, efficiency, vibrations, noise With the ZITRON test bench it is possible to analyse in detail the fan stall behaviour before delivering the fans to site, knowing in advance the real risks and possible solutions. Figure 7 ZITRON Test Bench As shown in the below image (figure 8), the complete fan performance curve is obtained and the real margin from the design duty point up to the stall limit can be observed. The example on the next page is for a ZITRON 100% reversible fan, where both directions of impeller rotation are tested, forward (blue line) and reverse (red line). 7

8 Figure 8 100% reversible axial fan test 8

9 3 rd step: Fan stall detection system It is important to note that the stall may not always be apparent. A fan operating in stall will show increase in normal fan noise or excessive increase in power consumption, but without an effective warning device, it may be difficult to detect that the fan is really operating in stall. Even devices designed for anti-stall purposes, such as anti-stall rings, are not designed for stall operation warning. Anti-stall rings are used to minimise the fan stall effects but not to detect stalling itself. The most effective, simple and cost-effective system for stall detection is offered by ZITRON and consists in installing a Petermann probe on the fans (see figure 9). Figure 9 - ZITRON fan stall detection system, Petermann probe 9

10 The pressure variations occurring in the stalling zone express themselves by creating one or more zones in which the airflow through the vane channels is blocked or goes in the opposite direction. The Petermann probe uses the above phenomenon to detect the stall condition of an axial flow fan by measuring the pressure difference between the total air pressure acting in a direction opposite to the direction of rotation of the fan impeller (with of a hook-shaped tubular measuring probe) and a reference pressure corresponding substantially to the static pressure at the wall of the air duct in the same radial measuring plane immediately in front of the fan blades, upstream. This pressure difference will be approximately zero in the stable working range of the fan, but increases considerably at a point corresponding to the inflection of the pressure difference characteristic when the fan enters in stall condition. Thus, by means of a simple differential pressure transmitter it is possible to know when the fan is in the stall condition. Figure 10 represents the pressure difference between both pressure probes depending on the air flow delivered by the fan. In this curve it is possible to see the characteristic change at the junction between the stable working range and the unstable range in the fan characteristic. Figure 10 - point of inflection The Petermann probe system is used for stall-detecting purposes, warning the ventilation system operators when the fan is operating at stall and making a signal which can be treated as trip or alarm. 10

11 4 th step: System evaluation for additional pressure loss sources removal Once the stall is detected, the circuit where the fan is installed must be analysed looking for the reason of such stall operation. Although numerical calculations can be used to determine the reason of the stall problem, again CFD simulations can be very useful to detect the problem as well as to solve it. The major part of the pressure drop in the ventilation system occurs in the sudden changes of flow velocity. Figure 11 shows a real example of how it was possible to decrease by almost 40% the pressure drop generated by a 90º elbow, by installing guide vanes. Figure 11 different 90º elbow configurations Before using any system for safe fan operation in stall (i.e. anti-stall rings), it is strongly recommended to analyse in detail the complete ventilation circuit, looking for any possible modification in its original design which helps to bring the fan out of the stall region. 11

12 5 th step: Installation of anti-stall devices in the fan Anti-stall rings There are different methods to keep the fan operating in stall mitigating the risk of blade rupture, and one of those is the anti-stall ring. The Anti-stall ring consists in a chamber located around the impeller. This chamber is fitted with internal guide vanes that catch the turbulent flow generated at the blade tips during the stall. The turbulent flow is stabilised and returned to the main volume flow which is circulating through the impeller. This system could seem advantageous, but once it is analysed in detail, some disadvantages are found. The Anti-stall ring system reduces drastically the fan efficiency, and therefore the power consumption all along the fan design life will be higher than really required to deliver the design duty point. In addition, if the fans operates in stall it will not deliver the design air flow, and hence the safety level of the ventilation system will be much lower than originally expected. Figure 12 fan stall region Now that the patent has expired, this system is being offered by different fan manufacturers, but it should be noticed that fan stall will be avoided assuming a continuous efficiency loss. Depending on the type of axial fan, the anti-stall ring negative impact in efficiency could be between 4 % and 8 % during stable fan operation, but reaching values around 40% when the fan is working on its unstable part of the curve. 12

13 Figure 13 - anti-stall ring For some applications, other anti-stall systems could be used to bring the fan out of the unstable region. As it occurs with anti-stall rings, delivered air flow will be lower than originally specified, but without negative impact on efficiency. By means of pitch angle variation, which could be also carried out without stopping the fan, even for system resistance higher than expected, the fan could continue working without risk of damage. Figure 14 - blade adjustment for fan bring out of stall As shown in the above figure (14), in case the fan adjusted to pitch angle nº4 is operating in stall, pitch angle nº 3 could be set to bring the fan out of the stall region. We should note that this system avoids the risk of fan damage and without the typical stalling decrease of the fan efficiency. 13

14 CONCLUSIONS Stall is one the main problems that the fans could suffer. In order to avoid this kind of problem, there are five main steps that should be taken into account: - 1 st : Realistic system calculation of system pressure loss - 2 nd : Factory fan performance test at nominal speed - 3 rd : Fan stall detection system - 4 th : System evaluation for additional pressure loss sources removal - 5 th : Installation of anti-stall devices in the fan The most frequent reason for fan stall is the underestimation of the system pressure drop; CFD tools are very helpful to calculate the real system pressure drop. Stall problems due to wrong pressure drop calculations or any unexpected change of the circuit geometry should always be investigated and solved. It should be noticed that anti-stall rings does reduce the risk of blade rupture due to fatigue, but does not eliminate the risk. Even if the fan is not suffering from rupture problems, a fan operating in stall by means of anti-stall rings is never the best solution. When the fan is in stall, the air flow delivered is lower than originally specified and this means that the safety level of the system is lower than required. One of the risks of the use of anti-stall rings is that the stall may not be detected, and hence the fan will remain working on its unstable region for long periods of time without looking for the solution to the reason that has induced the stall. In addition to the reduced air flow delivered by the fans, it should be noted that the fan power requirements are directly related to the fan efficiency, and anti-stall rings will produce a negative impact on fan efficiency. An alternative method such as automatic blade pitch angle adjustment, which is reliable and energy-friendly, should always be considered before choosing poor efficiency anti-stall systems. It could be said that nobody would drive their car continuously with the handbrake on, because it would be necessary to stop at some point, and that s really what is occurring when energy is continuously wasted with anti-stall rings. REFERENCES EUROVENT 1/11, published

Development of Ventilation Strategy in Diesel Engine Power Plant by Using CFD Modelling

Development of Ventilation Strategy in Diesel Engine Power Plant by Using CFD Modelling Development of Ventilation Strategy in Diesel Engine Power Plant by Using CFD Modelling Panu Mustakallio and Risto Kosonen Halton Oy, Haltonintie 1-3, 47400 Kausala, Finland E-mail: [email protected]

More information

Chapter 3.5: Fans and Blowers

Chapter 3.5: Fans and Blowers Part I: Objective type questions and answers Chapter 3.5: Fans and Blowers 1. The parameter used by ASME to define fans, blowers and compressors is a) Fan ration b) Specific ratio c) Blade ratio d) Twist

More information

Head Loss in Pipe Flow ME 123: Mechanical Engineering Laboratory II: Fluids

Head Loss in Pipe Flow ME 123: Mechanical Engineering Laboratory II: Fluids Head Loss in Pipe Flow ME 123: Mechanical Engineering Laboratory II: Fluids Dr. J. M. Meyers Dr. D. G. Fletcher Dr. Y. Dubief 1. Introduction Last lab you investigated flow loss in a pipe due to the roughness

More information

OPERATING FANS IN PARALLEL IN VIEW OF VARIABLE FLOW RATE OUTPUT

OPERATING FANS IN PARALLEL IN VIEW OF VARIABLE FLOW RATE OUTPUT OPERATING FANS IN PARALLEL IN VIEW OF VARIABLE FLOW RATE OUTPUT Eddy J. Jacques & Pierre J. Wauters Department of Mechanical Engineering, Unité TERM, Université Catholique de Louvain, Belgium ABSTRACT

More information

Dampers. Inlet guide vane. Damper. Louvre damper. Handbook Radial Fans / Chapter 3 - Dampers REITZ List 2010 DO 1. Dampers

Dampers. Inlet guide vane. Damper. Louvre damper. Handbook Radial Fans / Chapter 3 - Dampers REITZ List 2010 DO 1. Dampers Inlet guide vane Damper ouvre damper Handbook Radial Fans / Chapter 3 - REITZ ist 2010 DO 1 Technical description rticle number and order code article number = component size DR D1 0 3-000 031-00 variant

More information

Air Conditioning Clinic

Air Conditioning Clinic Air Conditioning Clinic Air Conditioning Fans One of the Equipment Series February 2012 TRG-TRC013-EN Air Conditioning Fans One of the Equipment Series A publication of Trane Preface Air Conditioning

More information

Practice Problems on Boundary Layers. Answer(s): D = 107 N D = 152 N. C. Wassgren, Purdue University Page 1 of 17 Last Updated: 2010 Nov 22

Practice Problems on Boundary Layers. Answer(s): D = 107 N D = 152 N. C. Wassgren, Purdue University Page 1 of 17 Last Updated: 2010 Nov 22 BL_01 A thin flat plate 55 by 110 cm is immersed in a 6 m/s stream of SAE 10 oil at 20 C. Compute the total skin friction drag if the stream is parallel to (a) the long side and (b) the short side. D =

More information

Fan Performance By: Mark Stevens AMCA International Deputy Executive Director Technical Affairs

Fan Performance By: Mark Stevens AMCA International Deputy Executive Director Technical Affairs Fan Performance By: Mark Stevens AMCA International Deputy Executive Director Technical Affairs Fan Performance (Paper I.D. 021) Mark Stevens Air Movement and Control Association International Abstract

More information

Using CFD to improve the design of a circulating water channel

Using CFD to improve the design of a circulating water channel 2-7 December 27 Using CFD to improve the design of a circulating water channel M.G. Pullinger and J.E. Sargison School of Engineering University of Tasmania, Hobart, TAS, 71 AUSTRALIA Abstract Computational

More information

NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES

NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES 8.1 INTRODUCTION Testing, adjusting, and balancing of HVAC systems can best be accomplished by following a series of systematic procedures. The NEBB TAB

More information

Characteristics of Centrifugal Blower and Its Effective Use in High Static Pressure Area

Characteristics of Centrifugal Blower and Its Effective Use in High Static Pressure Area Characteristics of Centrifugal Blower and Its Effective Use in High Static Pressure Area Masayuki TAKAHASHI With small fans, selecting the right fan that most fits the purpose is extremely important from

More information

www.klmtechgroup.com TABLE OF CONTENT

www.klmtechgroup.com TABLE OF CONTENT Page : 1 of 26 Project Engineering Standard www.klmtechgroup.com KLM Technology #03-12 Block Aronia, Jalan Sri Perkasa 2 Taman Tampoi Utama 81200 Johor Bahru Malaysia TABLE OF CONTENT SCOPE 2 REFERENCES

More information

Basic Selection & Proper Application of Overhead Air Distribution Devices

Basic Selection & Proper Application of Overhead Air Distribution Devices Basic Selection & Proper Application of Overhead Air Distribution Devices GRD Selection & Application Terms Selection Throw Sound Installation Variations affect Performance Inlet Effects Basics Return

More information

DESIGN CRITERIA AND OPERATIONAL LIMITS FOR AXIAL FLOW FANS OPERATED IN PARALLEL MODE

DESIGN CRITERIA AND OPERATIONAL LIMITS FOR AXIAL FLOW FANS OPERATED IN PARALLEL MODE - 90 - DESIGN CRITERIA AND OPERATIONAL LIMITS FOR AXIAL FLOW FANS OPERATED IN PARALLEL MODE Dr.-Ing. Schiller, F. Howden Ventilatoren GmbH, Heidenheim ABSTRACT Axial Flow Fans are the preferred fan types

More information

Tubular Casing Pumps. The Driving Force in Your Cooling Water System

Tubular Casing Pumps. The Driving Force in Your Cooling Water System Tubular Casing Pumps The Driving Force in Your Cooling Water System KSB know-how,experience and service... More than 120 years tradition in the design and construction of pumps, valves and relevant systems

More information

Performance prediction of a centrifugal pump working in direct and reverse mode using Computational Fluid Dynamics

Performance prediction of a centrifugal pump working in direct and reverse mode using Computational Fluid Dynamics European Association for the Development of Renewable Energies, Environment and Power Quality (EA4EPQ) International Conference on Renewable Energies and Power Quality (ICREPQ 10) Granada (Spain), 23rd

More information

Pushing the limits. Turbine simulation for next-generation turbochargers

Pushing the limits. Turbine simulation for next-generation turbochargers Pushing the limits Turbine simulation for next-generation turbochargers KWOK-KAI SO, BENT PHILLIPSEN, MAGNUS FISCHER Computational fluid dynamics (CFD) has matured and is now an indispensable tool for

More information

Accurate Air Flow Measurement in Electronics Cooling

Accurate Air Flow Measurement in Electronics Cooling Accurate Air Flow Measurement in Electronics Cooling Joachim Preiss, Raouf Ismail Cambridge AccuSense, Inc. E-mail: [email protected] Air is the most commonly used medium to remove heat from electronics

More information

VOLU-probe/SS. Stainless Steel Pitot Airflow Traverse Probes. Accurate airflow measurement for demanding applications

VOLU-probe/SS. Stainless Steel Pitot Airflow Traverse Probes. Accurate airflow measurement for demanding applications VOLU-probe/SS Stainless Steel Pitot Airflow Traverse Probes Accurate airflow measurement for demanding applications VOLU-probe/SS The VOLU-probe/SS Stainless Steel Pitot Airflow Traverse Probe is ideally

More information

Engineering & Expertise Designing Pump Sumps

Engineering & Expertise Designing Pump Sumps Engineering & Expertise Designing Pump Sumps Formed Suction Intake Engineering & Expertise Total solution engineering increases operational efficiency Introduction The primary function of a propeller pump

More information

ENGINEERING DATA. Fan Performance Troubleshooting Guide

ENGINEERING DATA. Fan Performance Troubleshooting Guide Information and Recommendations for the Engineer ENGINEERING DATA Aerovent TC Ventco Fiber-Aire Twin City Fan & Blower TC Axial Clarage Fan Performance Troubleshooting Guide ED- Introduction Trying to

More information

Centrifugal Fans and Pumps are sized to meet the maximum

Centrifugal Fans and Pumps are sized to meet the maximum Fans and Pumps are sized to meet the maximum flow rate required by the system. System conditions frequently require reducing the flow rate. Throttling and bypass devices dampers and valves are installed

More information

product application guide

product application guide Understanding Fan System Effects Fan Application FA/101-99 product application guide A technical bulletin for engineers, contractors and students in the air movement and control industry. The air moving

More information

CFD MODELLING FOR SWIRL DIFFUSER AND ITS IMPLICATIONS ON AIR CHANGE EFFECTIVENESS ASSESSMENT TO GREEN STAR'S IEQ-2

CFD MODELLING FOR SWIRL DIFFUSER AND ITS IMPLICATIONS ON AIR CHANGE EFFECTIVENESS ASSESSMENT TO GREEN STAR'S IEQ-2 CFD MODELLING FOR SWIRL DIFFUSER AND ITS IMPLICATIONS ON AIR CHANGE EFFECTIVENESS ASSESSMENT TO GREEN STAR'S IEQ-2 Eddy Rusly 1 and Mirek Piechowski 2 1,2 Meinhardt (VIC), Melbourne, Australia ABSTRACT

More information

Experiment 3 Pipe Friction

Experiment 3 Pipe Friction EML 316L Experiment 3 Pipe Friction Laboratory Manual Mechanical and Materials Engineering Department College of Engineering FLORIDA INTERNATIONAL UNIVERSITY Nomenclature Symbol Description Unit A cross-sectional

More information

PFT Two stage axial fan The high pressure fan for modern boiler plants

PFT Two stage axial fan The high pressure fan for modern boiler plants PFT Two stage axial fan The high pressure fan for modern boiler plants Modern boilers equipped with complete flue-gas cleaning systems demand fans for high pressure that can be controlled quickly and accurately

More information

EFFECT OF OBSTRUCTION NEAR FAN INLET ON FAN HEAT SINK PERFORMANCE

EFFECT OF OBSTRUCTION NEAR FAN INLET ON FAN HEAT SINK PERFORMANCE EFFECT OF OBSTRUCTION NEAR FAN INLET ON FAN HEAT SINK PERFORMANCE Vivek Khaire, Dr. Avijit Goswami Applied Thermal Technologies India 3rd Floor,C-Wing,Kapil Towers, Dr. Ambedkar Road, Pune- 411 1 Maharashtra,

More information

O-I DUBI PLANT FANS Quotation Spec Data & Specifications

O-I DUBI PLANT FANS Quotation Spec Data & Specifications TECHNICAL DATA O-I DUBI PLANT FANS Quotation Spec Data & Specifications 1 page for the global informations + 12 pages for the fans data Revision 2 end april Global informations: These fans are a replacement

More information

Methodology for Liquid Ultrasonic Flow Measurement within the Laminar to Turbulent Transitional Zone

Methodology for Liquid Ultrasonic Flow Measurement within the Laminar to Turbulent Transitional Zone Methodology for Liquid Ultrasonic Flow Measurement within the Laminar to Turbulent Transitional Zone Dave Seiler Daniel Measurement and Control March 25, 2014 Heavy Oil Definition!!!!the API classifies

More information

Fundamentals of Acoustics & Practical HVAC Design Considerations. Demir Doken Acoustic Engineer

Fundamentals of Acoustics & Practical HVAC Design Considerations. Demir Doken Acoustic Engineer Fundamentals of Acoustics & Practical HVAC Design Considerations Demir Doken Acoustic Engineer What is sound? Sound is a mechanical wave that is an oscillation of pressure transmitted through some medium

More information

NUMERICAL ANALYSIS OF WELLS TURBINE FOR WAVE POWER CONVERSION

NUMERICAL ANALYSIS OF WELLS TURBINE FOR WAVE POWER CONVERSION Engineering Review Vol. 32, Issue 3, 141-146, 2012. 141 NUMERICAL ANALYSIS OF WELLS TURBINE FOR WAVE POWER CONVERSION Z. 1* L. 1 V. 2 M. 1 1 Department of Fluid Mechanics and Computational Engineering,

More information

2013 Code_Saturne User Group Meeting. EDF R&D Chatou, France. 9 th April 2013

2013 Code_Saturne User Group Meeting. EDF R&D Chatou, France. 9 th April 2013 2013 Code_Saturne User Group Meeting EDF R&D Chatou, France 9 th April 2013 Thermal Comfort in Train Passenger Cars Contact For further information please contact: Brian ANGEL Director RENUDA France [email protected]

More information

Fans and Air Handling Units. Will Rea and Paul Pilutti February 16 th, 2011

Fans and Air Handling Units. Will Rea and Paul Pilutti February 16 th, 2011 Fans and Air Handling Units Will Rea and Paul Pilutti February 16 th, 2011 HTS Lunch and Learns Available Online Visit www.htseng.com Engineering Tools Resource Center Contents Fans Fan Curves Fan Laws

More information

5.14 COMPUTATIONAL MODELLING OF AIRFLOW IN URBAN STREET CANYON AND COMPARISON WITH MEASUREMENTS

5.14 COMPUTATIONAL MODELLING OF AIRFLOW IN URBAN STREET CANYON AND COMPARISON WITH MEASUREMENTS 5.14 COMPUTATIONAL MODELLING OF AIRFLOW IN URBAN STREET CANYON AND COMPARISON WITH MEASUREMENTS J. Pospisil 1,M. Jicha 1, A. Niachou 2 and M. Santamouris 2 1 Brno University of Technology, Faculty of Mechanical

More information

CENTRIFUGAL PUMP OVERVIEW Presented by Matt Prosoli Of Pumps Plus Inc.

CENTRIFUGAL PUMP OVERVIEW Presented by Matt Prosoli Of Pumps Plus Inc. CENTRIFUGAL PUMP OVERVIEW Presented by Matt Prosoli Of Pumps Plus Inc. 1 Centrifugal Pump- Definition Centrifugal Pump can be defined as a mechanical device used to transfer liquid of various types. As

More information

UCCS PES/ENSC 2500: Renewable Energy Spring 2014 Test 3 name:

UCCS PES/ENSC 2500: Renewable Energy Spring 2014 Test 3 name: UCCS PES/ENSC 2500: Renewable Energy Spring 2014 Test 3 name: 1. When a wind turbine is positioned between radio, television or microwave transmitter and receiver it can sometime reflect some of the in

More information

Averaging Pitot Tubes; Fact and Fiction

Averaging Pitot Tubes; Fact and Fiction Averaging Pitot Tubes; Fact and Fiction Abstract An experimental investigation has been undertaken to elucidate effects of averaging stagnation pressures on estimated velocities for pressure averaging

More information

SUMMARY of PRODUCTS. HVAC Systems Control Airflow, Space, & Building Pressurization. Accurate airflow measurement for demanding applications

SUMMARY of PRODUCTS. HVAC Systems Control Airflow, Space, & Building Pressurization. Accurate airflow measurement for demanding applications SUMMARY of PRODUCTS HVAC Systems Control Airflow, Space, & Building Pressurization Accurate airflow measurement for demanding applications Airflow Measuring Stations FAN-E AIRFLOW MEASURING STATION. The

More information

Minor losses include head losses through/past hydrants, couplers, valves,

Minor losses include head losses through/past hydrants, couplers, valves, Lecture 10 Minor Losses & Pressure Requirements I. Minor Losses Minor (or fitting, or local ) hydraulic losses along pipes can often be estimated as a function of the velocity head of the water within

More information

GEOMETRIC, THERMODYNAMIC AND CFD ANALYSES OF A REAL SCROLL EXPANDER FOR MICRO ORC APPLICATIONS

GEOMETRIC, THERMODYNAMIC AND CFD ANALYSES OF A REAL SCROLL EXPANDER FOR MICRO ORC APPLICATIONS 2 nd International Seminar on ORC Power Systems October 7 th & 8 th, 213 De Doelen, Rotterdam, NL GEOMETRIC, THERMODYNAMIC AND CFD ANALYSES OF A REAL SCROLL EXPANDER FOR MICRO ORC APPLICATIONS M. Morini,

More information

XFlow CFD results for the 1st AIAA High Lift Prediction Workshop

XFlow CFD results for the 1st AIAA High Lift Prediction Workshop XFlow CFD results for the 1st AIAA High Lift Prediction Workshop David M. Holman, Dr. Monica Mier-Torrecilla, Ruddy Brionnaud Next Limit Technologies, Spain THEME Computational Fluid Dynamics KEYWORDS

More information

FLUID FLOW STREAMLINE LAMINAR FLOW TURBULENT FLOW REYNOLDS NUMBER

FLUID FLOW STREAMLINE LAMINAR FLOW TURBULENT FLOW REYNOLDS NUMBER VISUAL PHYSICS School of Physics University of Sydney Australia FLUID FLOW STREAMLINE LAMINAR FLOW TURBULENT FLOW REYNOLDS NUMBER? What type of fluid flow is observed? The above pictures show how the effect

More information

SEPARATING DUST PARTICLES USING AN AERODYNAMIC DEDUSTER

SEPARATING DUST PARTICLES USING AN AERODYNAMIC DEDUSTER SEPARATING DUST PARTICLES USING AN AERODYNAMIC DEDUSTER DEVELOPMENT OF AN AERODYNAMIC DEDUSTER FOR LIVESTOCK BUILDINGS G.A. Zhao, Y. Zhang Summary Dust is among the major pollutants that have a detrimental

More information

Energy savings in commercial refrigeration. Low pressure control

Energy savings in commercial refrigeration. Low pressure control Energy savings in commercial refrigeration equipment : Low pressure control August 2011/White paper by Christophe Borlein AFF and l IIF-IIR member Make the most of your energy Summary Executive summary

More information

SPECIAL APPLICATIONS

SPECIAL APPLICATIONS Page 1 SPECIAL APPLICATIONS The protection of microelectronics clean rooms using aspirating smoke detection systems requires special consideration. The physical configuration of the room(s) and the direction

More information

Mixing in the process industry: Chemicals Food Pharmaceuticals Paper Polymers Minerals Environmental. Chemical Industry:

Mixing in the process industry: Chemicals Food Pharmaceuticals Paper Polymers Minerals Environmental. Chemical Industry: Mixing Notes: Chapter 19 Robert P. Hesketh Mixing in the process industry: Chemicals Food Pharmaceuticals Paper Polymers Minerals Environmental Chemical Industry: Paints and Coatings Synthetic Rubbers

More information

Once you know the volume of air and the static pressure of the system to be cooled, you can determine the fan specifications for your product.

Once you know the volume of air and the static pressure of the system to be cooled, you can determine the fan specifications for your product. COOLING FAN REQUIREMENTS CALCULATIONS Determining System Impedance Determining the actual airflow produced by a fan mounted in an enclosure is much more difficult than calculating the airflow required.

More information

DSRQ - DSRSQ - DSRSQ-THERM

DSRQ - DSRSQ - DSRSQ-THERM DSRQ - DSRSQ - DSRSQ-THERM Specification item: Variable geometry diffuser on 597x597 mm panel developed for rooms with high ceilings where a long throw and a high induction ratio are required. Made up

More information

INSTRUCTIONS FOR HOW TO PROPERLY SELECT A FAN OR BLOWER

INSTRUCTIONS FOR HOW TO PROPERLY SELECT A FAN OR BLOWER INSTRUCTIONS FOR HOW TO PROPERLY SELECT A FAN OR BLOWER The instructions that follow are to assist you in completing the information required when making a fan or blower selection. If you need additional

More information

Lecture 6 - Boundary Conditions. Applied Computational Fluid Dynamics

Lecture 6 - Boundary Conditions. Applied Computational Fluid Dynamics Lecture 6 - Boundary Conditions Applied Computational Fluid Dynamics Instructor: André Bakker http://www.bakker.org André Bakker (2002-2006) Fluent Inc. (2002) 1 Outline Overview. Inlet and outlet boundaries.

More information

Comparing Energy Savings of Different VAV Systems

Comparing Energy Savings of Different VAV Systems Comparing Energy Savings of Different VAV Systems Prepared By: Martyn Dodd [email protected] EnergySoft LLC 1025 5th Street, Suite A Novato, CA 94945 415-897-6400 www.energysoft.com Last Modified: March

More information

UDSA - UDSBD unit heater

UDSA - UDSBD unit heater APPLICATIONS Heating >> FACTORIES >> WAREHOUSES >> HALLS >> SHOWROOMS >> GREENHOUSES >> RETAIL >>... UDSA - UDSBD unit heater www.reznor.eu V3 gas fired unit heater Reznor V3 unit heaters are one of the

More information

Relevance of Modern Optimization Methods in Turbo Machinery Applications

Relevance of Modern Optimization Methods in Turbo Machinery Applications Relevance of Modern Optimization Methods in Turbo Machinery Applications - From Analytical Models via Three Dimensional Multidisciplinary Approaches to the Optimization of a Wind Turbine - Prof. Dr. Ing.

More information

CFD Analysis of Swept and Leaned Transonic Compressor Rotor

CFD Analysis of Swept and Leaned Transonic Compressor Rotor CFD Analysis of Swept and Leaned Transonic Compressor Nivin Francis #1, J. Bruce Ralphin Rose *2 #1 Student, Department of Aeronautical Engineering& Regional Centre of Anna University Tirunelveli India

More information

Surface Technology. Centrifugal Fan GMD

Surface Technology. Centrifugal Fan GMD Centrifugal Fan ATEX classed adapted for paint shops Wide assortment broad area of application Service friendly low maintenance costs Headquarters: Centrifugal Fan Centrifugal Fan is a direct driven industrial

More information

SARTRE: SAfe Road TRains for the Environment

SARTRE: SAfe Road TRains for the Environment SARTRE: SAfe Road TRains for the Environment Arturo Dávila Mario Nombela IDIADA Automotive Technology SA London Heathrow, September 21, 2010. The research leading to these results has received funding

More information

Application of CFD Simulation in the Design of a Parabolic Winglet on NACA 2412

Application of CFD Simulation in the Design of a Parabolic Winglet on NACA 2412 , July 2-4, 2014, London, U.K. Application of CFD Simulation in the Design of a Parabolic Winglet on NACA 2412 Arvind Prabhakar, Ayush Ohri Abstract Winglets are angled extensions or vertical projections

More information

- White Paper - Data Centre Cooling. Best Practice

- White Paper - Data Centre Cooling. Best Practice - White Paper - Data Centre Cooling Best Practice Release 2, April 2008 Contents INTRODUCTION... 3 1. AIR FLOW LEAKAGE... 3 2. PERFORATED TILES: NUMBER AND OPENING FACTOR... 4 3. PERFORATED TILES: WITH

More information

Lab 8: DC generators: shunt, series, and compounded.

Lab 8: DC generators: shunt, series, and compounded. Lab 8: DC generators: shunt, series, and compounded. Objective: to study the properties of DC generators under no-load and full-load conditions; to learn how to connect these generators; to obtain their

More information

Vertical selfpriming Side-Channel Pumps Type WPV

Vertical selfpriming Side-Channel Pumps Type WPV Vertical selfpriming Side-Channel Pumps Type WPV FIELD OF APPLICATION The side-channel pumps are selfpriming and operate more economically (better efficiency) than normal centrifugal pumps when handling

More information

Data centers have been cooled for many years by delivering

Data centers have been cooled for many years by delivering The Increasing Challenge of Data Center Design and Management: Is CFD a Must? Mark Seymour, Christopher Aldham, Matthew Warner, Hassan Moezzi Future Facilities, San Jose, California, USA Mark Seymour,

More information

THE USE OF A CORIOLIS FLOW METER FOR MEASURING MOLASSES PRODUCTION IN A SUGAR MILL. ABSTRACT

THE USE OF A CORIOLIS FLOW METER FOR MEASURING MOLASSES PRODUCTION IN A SUGAR MILL. ABSTRACT THE USE OF A CORIOLIS FLOW METER FOR MEASURING MOLASSES PRODUCTION IN A SUGAR MILL. P. W. Rein 1, D. J. Muzzell 2, and N. Dolan 2 1 Audubon Sugar Institute, LSU AgCenter, St. Gabriel, LA, 2 Raceland Raw

More information

Mechanical Heating Ventilation and Air Conditioning Ductwork and Duct Accessories

Mechanical Heating Ventilation and Air Conditioning Ductwork and Duct Accessories Basis of Design This section applies to the design and installation of ductwork, air terminal boxes, air outlets and inlets, volume dampers, pressure relief dampers, smoke/fire dampers, and smoke/fire

More information

MacroFlo Opening Types User Guide <Virtual Environment> 6.0

MacroFlo Opening Types User Guide <Virtual Environment> 6.0 MacroFlo Opening Types User Guide 6.0 Page 1 of 18 Contents 1. Introduction...4 2. What Are Opening Types?...5 3. MacroFlo Opening Types Manager Interface...5 3.1. Add... 5 3.2. Reference

More information

CETA Application Guide for the Exhaust System Requirements of Class II, Type B Biosafety Cabinets CAG-007-2010 March 24, 2010

CETA Application Guide for the Exhaust System Requirements of Class II, Type B Biosafety Cabinets CAG-007-2010 March 24, 2010 CETA Application Guide for the Exhaust System Requirements of Class II, Type B Biosafety Cabinets CAG-007-2010 March 24, 2010 1. Background Class II Type B Biosafety Cabinets (BSCs) are unique laboratory

More information

Performance Comparison of a Vertical Axis Wind Turbine using Commercial and Open Source Computational Fluid Dynamics based Codes

Performance Comparison of a Vertical Axis Wind Turbine using Commercial and Open Source Computational Fluid Dynamics based Codes Performance Comparison of a Vertical Axis Wind Turbine using Commercial and Open Source Computational Fluid Dynamics based Codes Taimoor Asim 1, Rakesh Mishra 1, Sree Nirjhor Kaysthagir 1, Ghada Aboufares

More information

Experiment (13): Flow channel

Experiment (13): Flow channel Introduction: An open channel is a duct in which the liquid flows with a free surface exposed to atmospheric pressure. Along the length of the duct, the pressure at the surface is therefore constant and

More information

Demand Based Static Pressure Reset Control for Laboratories

Demand Based Static Pressure Reset Control for Laboratories LLC Demand Based Static Pressure Reset Control for Laboratories Laboratories are generally the largest users of energy in any facility. Whether in a pharmaceutical research facility, a university or a

More information

Design recommendations FOR PUMP STATIONS WITH LARGE CENTRIFUGAL FLYGT WASTEWATER PUMPS

Design recommendations FOR PUMP STATIONS WITH LARGE CENTRIFUGAL FLYGT WASTEWATER PUMPS Design recommendations FOR PUMP STATIONS WITH LARGE CENTRIFUGAL FLYGT WASTEWATER PUMPS 2 Contents Flygt large centrifugal pumps introduction...................................................... 4 General

More information

Numerical Analysis of Independent Wire Strand Core (IWSC) Wire Rope

Numerical Analysis of Independent Wire Strand Core (IWSC) Wire Rope Numerical Analysis of Independent Wire Strand Core (IWSC) Wire Rope Rakesh Sidharthan 1 Gnanavel B K 2 Assistant professor Mechanical, Department Professor, Mechanical Department, Gojan engineering college,

More information

FIRE DAMPER APPLICATION GUIDE

FIRE DAMPER APPLICATION GUIDE FIRE AND CEILING RADIATION DAMPERS FIRE DAMPER APPLICATION GUIDE Use this application guide to help determine what type of fire damper best suits the application. Below are listed the ten Metal-Fab fire

More information

INFLUENCE OF VARIATION IN CPU UTILIZATION ON THE RACK LEVEL FAN CONFIGURATION AS A COOLING TECHNIQUE FOR HIGH END SERVERS SHREYAS NAGARAJ

INFLUENCE OF VARIATION IN CPU UTILIZATION ON THE RACK LEVEL FAN CONFIGURATION AS A COOLING TECHNIQUE FOR HIGH END SERVERS SHREYAS NAGARAJ INFLUENCE OF VARIATION IN CPU UTILIZATION ON THE RACK LEVEL FAN CONFIGURATION AS A COOLING TECHNIQUE FOR HIGH END SERVERS by SHREYAS NAGARAJ Presented to the Faculty of the Graduate School of The University

More information

EXPERIMENTAL AND NUMERICAL ANALYSIS OF THE COLLAR PRODUCTION ON THE PIERCED FLAT SHEET METAL USING LASER FORMING PROCESS

EXPERIMENTAL AND NUMERICAL ANALYSIS OF THE COLLAR PRODUCTION ON THE PIERCED FLAT SHEET METAL USING LASER FORMING PROCESS JOURNAL OF CURRENT RESEARCH IN SCIENCE (ISSN 2322-5009) CODEN (USA): JCRSDJ 2014, Vol. 2, No. 2, pp:277-284 Available at www.jcrs010.com ORIGINAL ARTICLE EXPERIMENTAL AND NUMERICAL ANALYSIS OF THE COLLAR

More information

EXPERIMENTAL RESEARCH ON CHARACTERISTICS OF CENTRIFUGAL PUMP NOISE IN WATER PIPE SYS- TEM

EXPERIMENTAL RESEARCH ON CHARACTERISTICS OF CENTRIFUGAL PUMP NOISE IN WATER PIPE SYS- TEM The 21 st International Congress on Sound and Vibration 13-17 July, 2014, Beijing/China EXPERIMENTAL RESEARCH ON CHARACTERISTICS OF CENTRIFUGAL PUMP NOISE IN WATER PIPE SYS- TEM Muze Huang, Hongling Sun,

More information

A. Hyll and V. Horák * Department of Mechanical Engineering, Faculty of Military Technology, University of Defence, Brno, Czech Republic

A. Hyll and V. Horák * Department of Mechanical Engineering, Faculty of Military Technology, University of Defence, Brno, Czech Republic AiMT Advances in Military Technology Vol. 8, No. 1, June 2013 Aerodynamic Characteristics of Multi-Element Iced Airfoil CFD Simulation A. Hyll and V. Horák * Department of Mechanical Engineering, Faculty

More information

Chapter 8: Flow in Pipes

Chapter 8: Flow in Pipes Objectives 1. Have a deeper understanding of laminar and turbulent flow in pipes and the analysis of fully developed flow 2. Calculate the major and minor losses associated with pipe flow in piping networks

More information

The INSEAN E779a Propeller Test Case: a Database For CFD Validation

The INSEAN E779a Propeller Test Case: a Database For CFD Validation The INSEAN E779a Propeller Test Case: a Database For CFD Validation G.Calcagno,F. Di Felice, M. Felli,S. Franchi, F.Pereira, F.Salvatore INSEAN (Italian Ship Model Basin), via di Vallerano 139, 00128 Rome,

More information

Michael Montgomery Marketing Product Manager Rosemount Inc. Russ Evans Manager of Engineering and Design Rosemount Inc.

Michael Montgomery Marketing Product Manager Rosemount Inc. Russ Evans Manager of Engineering and Design Rosemount Inc. ASGMT / Averaging Pitot Tube Flow Measurement Michael Montgomery Marketing Product Manager Rosemount Inc. Russ Evans Manager of Engineering and Design Rosemount Inc. Averaging Pitot Tube Meters Introduction

More information

FATIGUE CONSIDERATION IN DESIGN

FATIGUE CONSIDERATION IN DESIGN FATIGUE CONSIDERATION IN DESIGN OBJECTIVES AND SCOPE In this module we will be discussing on design aspects related to fatigue failure, an important mode of failure in engineering components. Fatigue failure

More information

The Design & Analysis of a Low NPSH Centrifugal Pump Featuring a Radial Inlet and Axial Inducer Using STAR-CCM+

The Design & Analysis of a Low NPSH Centrifugal Pump Featuring a Radial Inlet and Axial Inducer Using STAR-CCM+ The Design & Analysis of a Low NPSH Centrifugal Pump Featuring a Radial Inlet and Axial Inducer Using STAR-CCM+ Edward M Bennett Travis A Jonas Mechanical Solutions 11 Apollo Drive Whippany, NJ 07981 March

More information

TOP 10 NOISE CONTROL TECHNIQUES

TOP 10 NOISE CONTROL TECHNIQUES TOP 10 NOISE CONTROL TECHNIQUES The following are 10 simple noise control techniques that have wide application across the whole of industry. In many cases, they will produce substantial noise reductions

More information

Aerodynamic Analysis. Estimation of aerodynamic performance from constant speed and coast down testing

Aerodynamic Analysis. Estimation of aerodynamic performance from constant speed and coast down testing Aerodynamic Analysis Estimation of aerodynamic performance from constant speed and coast down testing Introduction This report will focus on the aerodynamic performance of the vehicle using data collected

More information

CFturbo Modern turbomachinery design software

CFturbo Modern turbomachinery design software COMPRESSOR Tech Magazine CFturbo Modern turbomachinery design software Designing new compressors from scratch and compressor redesign By Ralph-Peter Mueller & Gero Kreuzfeld Ralph-Peter Mueller and Gero

More information

ME 239: Rocket Propulsion. Over- and Under-expanded Nozzles and Nozzle Configurations. J. M. Meyers, PhD

ME 239: Rocket Propulsion. Over- and Under-expanded Nozzles and Nozzle Configurations. J. M. Meyers, PhD ME 239: Rocket Propulsion Over- and Under-expanded Nozzles and Nozzle Configurations J. M. Meyers, PhD 1 Over- and Underexpanded Nozzles Underexpanded Nozzle Discharges fluid at an exit pressure greater

More information

Eco Pelmet Modelling and Assessment. CFD Based Study. Report Number 610.14351-R1D1. 13 January 2015

Eco Pelmet Modelling and Assessment. CFD Based Study. Report Number 610.14351-R1D1. 13 January 2015 EcoPelmet Pty Ltd c/- Geoff Hesford Engineering 45 Market Street FREMANTLE WA 6160 Version: Page 2 PREPARED BY: ABN 29 001 584 612 2 Lincoln Street Lane Cove NSW 2066 Australia (PO Box 176 Lane Cove NSW

More information

Aerodynamic Department Institute of Aviation. Adam Dziubiński CFD group FLUENT

Aerodynamic Department Institute of Aviation. Adam Dziubiński CFD group FLUENT Adam Dziubiński CFD group IoA FLUENT Content Fluent CFD software 1. Short description of main features of Fluent 2. Examples of usage in CESAR Analysis of flow around an airfoil with a flap: VZLU + ILL4xx

More information

Introduction to the Smith Chart for the MSA Sam Wetterlin 10/12/09 Z +

Introduction to the Smith Chart for the MSA Sam Wetterlin 10/12/09 Z + Introduction to the Smith Chart for the MSA Sam Wetterlin 10/12/09 Quick Review of Reflection Coefficient The Smith chart is a method of graphing reflection coefficients and impedance, and is often useful

More information

OPERATING MANUAL CONTRACTOR STYLE AXIAL FANS

OPERATING MANUAL CONTRACTOR STYLE AXIAL FANS Manual No. BLWR043 Rev. 4 September 2012 OPERATING MANUAL CONTRACTOR STYLE AXIAL FANS CVF-8AC CVF-8AC50 CVF-6ACAN CVF-15ACAN CVF-25ACAN CVF-8A15KIT CVF-8A25KIT MODELS: CVF-8DC CVF-6DCAN CVF-15DCAN CVF-25DCAN

More information

CENTRIFUGAL PUMP SELECTION, SIZING, AND INTERPRETATION OF PERFORMANCE CURVES

CENTRIFUGAL PUMP SELECTION, SIZING, AND INTERPRETATION OF PERFORMANCE CURVES CENTRIFUGAL PUMP SELECTION, SIZING, AND INTERPRETATION OF PERFORMANCE CURVES 4.0 PUMP CLASSES Pumps may be classified in two general types, dynamic and positive displacement. Positive displacement pumps

More information

University Turbine Systems Research 2012 Fellowship Program Final Report. Prepared for: General Electric Company

University Turbine Systems Research 2012 Fellowship Program Final Report. Prepared for: General Electric Company University Turbine Systems Research 2012 Fellowship Program Final Report Prepared for: General Electric Company Gas Turbine Aerodynamics Marion Building 300 Garlington Rd Greenville, SC 29615, USA Prepared

More information

A Simplified 3d Model Approach in Constructing the Plain Vane Profile of A Radial Type Submersible Pump Impeller

A Simplified 3d Model Approach in Constructing the Plain Vane Profile of A Radial Type Submersible Pump Impeller Research Journal of Engineering Sciences ISSN 2278 9472 A Simplified 3d Model Approach in Constructing the Plain Vane Profile of A Radial Type Submersible Pump Impeller Abstract Gundale V.A. 1, Joshi G.R.

More information

Aeronautical Testing Service, Inc. 18820 59th DR NE Arlington, WA 98223 USA. CFD and Wind Tunnel Testing: Complimentary Methods for Aircraft Design

Aeronautical Testing Service, Inc. 18820 59th DR NE Arlington, WA 98223 USA. CFD and Wind Tunnel Testing: Complimentary Methods for Aircraft Design Aeronautical Testing Service, Inc. 18820 59th DR NE Arlington, WA 98223 USA CFD and Wind Tunnel Testing: Complimentary Methods for Aircraft Design Background Introduction ATS Company Background New and

More information

FAN ENGINEERING. ( ) ρ N. Fan Performance Troubleshooting Guide

FAN ENGINEERING. ( ) ρ N. Fan Performance Troubleshooting Guide FN ENGINEERING Information and Recommendations for the Engineer FE- Fan Performance Troubleshooting Guide Introduction Trying to determine why a fan is not working the way you want it to can sometimes

More information

Numerical Investigation of Angle and Geometric of L-Shape Groin on the Flow and Erosion Regime at River Bends

Numerical Investigation of Angle and Geometric of L-Shape Groin on the Flow and Erosion Regime at River Bends World Applied Sciences Journal 15 (2): 279-284, 2011 ISSN 1818-4952 IDOSI Publications, 2011 Numerical Investigation of Angle and Geometric of L-Shape Groin on the Flow and Erosion Regime at River Bends

More information

Pump Maintenance - Repair

Pump Maintenance - Repair Pump Maintenance - Repair Brian Trombly Mo Droppers Cummins Bridgeway, Gaylord, Mi The basic centrifugal pump consists of two main elements: 1. The rotating element which includes an impeller and a shaft.

More information

Duct Design. Presented by Dave Janquart

Duct Design. Presented by Dave Janquart Duct Design Presented by Dave Janquart Overview of Topics Duct design Duct insulation SMACNA Standards Factors Influencing Duct Design Equipment Losses Air Velocity Duct Material Duct Size & Shape Length

More information