Fan Applications. Major Considerations Defined. Fan Application. Major Application Considerations. A. Fan Types FA/126-06
|
|
|
- Harold McKinney
- 9 years ago
- Views:
Transcription
1 Fan Application FA/ A technical bulletin for engineers, contractors and students in the air movement and control industry. Fan Applications There are many different types of fans and many applications in which they can be used. For an application to be successful and work as intended, the fan and system must be compatible both structurally as well as from a performance standpoint. This section outlines several generic fan applications and the major considerations relating to fan type, rating parameters and fan design. Please use this information as a part of the fan selection process. Major Application Considerations All of the previous applications can be reduced to a few generic application characteristics such as clean or dirty air, normal or high temperature, fume or gas control, low or high erosion, etc. The enclosed matrix provides guidance for those elements that should receive special attention during the selection process. These characteristics are not all inclusive, however, they do present a good starting point for a successful application. Major Considerations Defined A. Fan Types 1. Propeller fan: Propeller fans may have many different blade shapes and number of blades. They generally have relatively small hubs. They may or may not have a housing. Housings are in the form of a panel with an orifice in it. The panel is mounted in a wall so that air does not re-circulate from the discharge back to the inlet. Pressures are normally less than one inch of static pressure with very high flow rate. These fans are best suited for circulating air, supplying and exhausting clean ambient air from/to large spaces. 2. Centrifugal Airfoil, Backward Inclined, Backward Curved: These fans are the most efficient of the centrifugal designs. Static efficiencies peak at around 80 percent and occur around 60 percent of free delivery. Their performance characteristic curve is stable over a wide range. The fan horsepower curve is non-overloading. The fan design is suitable for all forms of control methods. It is primarily suited for clean air applications but P.O. Box 410 Schofield, WI Fax Copyright 2006 Greenheck Fan Corp.
2 non-sticky dust like particles can be handled. Due to stress considerations, this design is best suited for moderate speeds through class III (up to 13.5 inches w.g.) and moderate temperatures through 800 F. 3. Forward curved centrifugal: This fan is generally wider with shallow scooped blades making it well suited for handling high flow rates at low pressures. The design is limited primarily to lower speeds and temperatures due to stress levels. Some designs incorporate internal struts for added stiffness during starts and stops. The performance curve is stable from free delivery to peak pressure, but there is a dip to the left of peak pressure. The horsepower curve rises constantly and relatively sharply from shut-off to free delivery. Its efficiency is relatively low but this is not typically critical because most applications are relatively low in horsepower. Control is by dampers, speed change and sometimes by inlet guide vanes. 4. Vane axial: These fans are well suited for high flow rates at low to moderate pressures up to six inches of water. There are several blade variations as to shape, numbers and whether they are fixed, adjustable or controllable blade pitch. The fans are characterized with large hubs and straightening vanes. The airflow is straight through, saving space. The performance curve is stable from free delivery to peak pressure, however, there is a stall area just behind peak pressure where it should not be operated. Sound levels have a higher frequency characteristic which makes it easier to attenuate if need be. 5. Mixed flow inline: The wheel design is a combination of axial and centrifugal components. It operates most efficiently in the range between a vane axial and a centrifugal satisfying applications for moderate flow rates and moderate pressures. The housing is similar to a vane axial incorporating guide vanes and straight through flow thus saving space. The fan s main advantages are its lower sound levels and high operating efficiencies. 6. Radial, radial tipped: These fans have efficiencies in the 60 to 75 percent range and have a higher pressure characteristic than most fans. The horsepower curve rises constantly from shut-off to free delivery. Due to turbulence and the blade shape, these fans can handle contaminants in the air stream. Wheels often incorporate wear protection for longer life. These fans can be modified or designed to accommodate high temperatures. 7. Paddle wheel: This design is used primarily for conveying material. It is normally very rugged in design in order to accommodate impact forces and limit fatigue cracks. Shafts and bearings are typically oversized for durability. Density calculations should not only reflect the air but the material passing through the fan for horsepower predictions to be accurate. Efficiencies are relatively low. 8. Plenum: This design incorporates an AF, BI, BC wheel without a housing. The primary purpose is to pressurize a compartment or plenum forcing a uniform flow of air downstream from a higher to a lower pressure region. It is less efficient than a housed unit but is well suited for saving space and minimizing ductwork configurations. 9. Inline fans: Inline fans may utilize a centrifugal, mixed flow or axial type wheel in a round tube or square shaped housing. When supplied with a centrifugal wheel and guide vanes within the tube, the term tubular centrifugal is normally used. When supplied with a mixed flow type wheel, the term mixed flow is normally used. When supplied with an axial type wheel without guide vanes, the term tube axial is normally used. Inline fans are typically used in space saving applications in which the pressures are relatively low (2-3 inches of static pressure) at moderate flow rates, but can handle pressures up to 8 inches w.g. B. Ratings 1. Efficiency: Efficiency is an important factor considering the relatively high cost of energy. The operating point location on the fan curve must be considered when controls are to be used to modulate the fan over a wide flow range. Various controls must be evaluated for effectiveness and their impact upon fan efficiency at lower flow rates. 2
3 2 Single or parallel operation: There are many different reasons for using multiple fans in a single system. They may be in series or parallel and one fan will have an impact upon the other fans during control or start-ups or shut downs. Stability is very important and the operating point location on the fan curve must be evaluated during all changes. (Refer to FA/115-02) 3. Method of control: When selecting fans it is most important to know the control method and its characteristics ahead of time. The operating point location on the fan curve should be evaluated for each duty cycle as well as sound requirements. 4. Special air density: Many applications operate close to the standard density corresponding to 70 F sea level and a specific gravity of one. However changes in altitude, temperature, specific gravity, materials in the air stream and suction pressure can all affect the fan air density which has a great impact upon the fan s performance. (Refer to FA/101-99) 5. Sound: Fans make sound as a by-product of handling air. Sound can be minimized by using the right fan type, selecting the operating point near peak efficiency and using a larger fan at a slower speed. Fan location is critical in some applications and should not be located near sensitive office areas, conference rooms, etc. The control method will also have an impact upon the fan noise. (Refer to FA/121-03, FA/122-03, FA/123-03)) 6. Non-surge, stability: The operating point location on the fan curve determines the fan/system stability. Some fans have stall areas, discontinuities and flat portions of their curves where hunting can occur. The slope of the fan curve is important when applying fan controls. 7. Capture & Entrainment Velocities: Fans and systems that convey materials must be sized so that the airstream can pick up or capture the material and then keep it suspended in the airstream (entrainment) so that it will not settle out at some location in the system. C. Design 1. Location: Knowing where a fan is to be located can make or break an application. Different considerations apply whether a fan is indoors, outdoors, mounted on a concrete slab or several stories up in a structure. Fans should not be located near sensitive offices or conference rooms. High speed fans should not be near property lines. Maintenance and the ability to install and/or remove components is important. Proper distances must be maintained between fans and walls, other fans, etc. so that system effects are minimized. 2. Orientation: Proper fan orientation and connection to the system are critical factors in applying a fan properly. Connections should not disturb the air entering the fan or additional losses known as system effects will occur. (Refer to FA/119-03) 3. Vibration: Vibration is important not only to the life of the fan but to the acceptability of the application. Fans must be installed and mounted upon proper bases that are flat and level. Vibration isolation may be necessary to limit the transmission of vibration and structure-borne noise into a building. Vibration isolation may require flex connections, rubber mats, neoprene isolators, springs, snubbers etc. An isolation base may be required for high speed applications. (Refer to FA/108-00) 4. Leakage and sealing: Many applications require contaminants in the airstream to not leak out through connections, shaft openings, accessories or seams in housings. Toxic gasses may require completely air tight construction for safety of personnel. At times, special tests are specified to determine leakage rates. 5. Spark resistant construction: Fans are typically made using various grades of carbon steel that can cause a spark if components strike each other. AMCA documents specify different levels of spark resistance to minimize the possibility of sparks occurring which can result in an explosion. (Refer to FA/116-08) 3
4 6. Special materials: Fans can be made from special materials to minimize corrosion, erosion, extremes in hot or cold temperatures, food service etc. Materials such as aluminum, stainless steel, plastic or fiberglass can be used to satisfy special requirements. 7. Temperature and rate of temperature change: The operating temperature, design temperature and the rate of change in temperature are important design parameters. The rate of temperature change affects the internal stresses created inside hubs and the thermal expansion present in various parts. If parts become loose because of differences in their expansion rate, violent vibration can result destroying the fan. (Refer to FA/109-01) 8. Durability and reliability: This is the degree of ruggedness that takes into account a fan s design to insure long life. 9. Bearing design, cooling, lube: In order to maintain expected L-10 life, bearings must be maintained within certain speed limits, load limits, temperature limits and vibration limits. Special seals may be necessary to keep dirt and contamination out of the lubricant. Lubrication intervals are typically specified as well. (Refer to FA/103-00) 10. Thermal expansion: Materials expand and contract with temperature. Sufficient clearances must be designed into the fan so that components do not interfere or seize. Special mountings may be necessary to allow growth of the housing and not distort shaft or bearing seals. Drive component alignment must be maintained. 11. Erosion: Contaminants in the airstream can cause wear. Wear weakens fan parts. These parts must be replaced at intervals or protected by some sacrificial material. Sometimes harder materials are used to resist wear. 12. Corrosion: Contaminants can eat away or corrode a material resulting in failure. Special materials such as stainless steel, Everdur, aluminum, and fiberglass may be employed to resist corrosion. Many coatings can be applied to protect the base material. 13. Build-up: Build-up occurs when contaminants in the airstream stick to fan parts and build-up over time. This increases the weight, stress levels and can cause severe unbalance when chunks fly off rotating wheel components. 14. Special codes and regulations: The construction of fans is often covered by local or national codes. These may apply to snow loads, wind loads, seismic loads, fire and smoke etc. (Refer to CS/100-99, CS/101-00) 15 Start/Stops: Many start/stops can result in low cycle fatigue causing cracks in the materials of construction. 16. Flow reversal fan: Emergency tunnel ventilation and fire/smoke applications may require the fan produce equal performance in forward as well as reverse direction. 17. Special coatings: Corrosion can be minimized by using base materials inert to the contaminant. Special coatings can be used for protection of the base material as long as no wear exists. (Refer to FA/110-04R) 18. Toxic gases: This condition requires airtight construction so that there is no leakage in or out of the fan. 19. Insulation: Insulation on a fan housing can keep heat or cold within the fan or protect the fan from the environment. Insulation can also reduce radiated sound. 20. Motors: Selecting the right motor for a given application is critical. Greenheck s Product Application Guide FA/ will provide information to help select the appropriate motor. Summary This article emphasizes the major considerations pertinent to fan selection and application. It is not all inclusive since there are many other considerations not listed. It is always best to take a step back and use common sense as the final criteria. Another source of useful product application criteria can be found in FA/
5 Common Applications for Fans General Ventilation Air handling fan: A fan that moves large volumes of air or overcomes high pressures. This fan typically moves air through coils. Agricultural fans: A propeller fan in an enclosure with screens that circulates air over poultry or exhausts air from barns. Attic ventilation fan: A propeller fan that circulates attic air to remove hot air and draw in cooler outside air. Bathroom fan: A fan that exhausts moist air and odors to the outside. Cabinet fan: Fan that is mounted inside a cabinet or box that is used in a ducted application. Used to locate fans away form noise sensitive areas. Ceiling exhaust fan: Fan that exhausts air from utility rooms, bathrooms, meeting rooms, conference rooms to the outside. Mounted in the ceiling. Central (whole) house Ceiling Exhaust Fans fan: A propeller fan mounted in the ceiling that exhausts air to an attic while drawing in fresh cooler air through windows of a house. Combustible fan: Fans that can exhaust air that is combustible, these fans typically have non-ferrous components to prevent sparking. Cross flow fan: A very wide forward curved wheel in which air enters and leaves at ninety degrees to its axis of rotation. This fan is used in window heating and cooling units and fireplace ventilators. Energy recovery ventilator: A unit that uses an energy recovery device (wheel or plate) to transfer energy from air being exhausted to fresh outside air entering a building Exhaust fan: Normally a fan mounted in a plenum or large space that exhausts air to the outside of a building. Fan terminal unit: A relatively small unit containing a fan with or without reheat coils located in an under the floor or in ceiling plenums to direct air through grills into an occupied space. Hooded roof fan: a fan that is roof mounted and has a hood that prevents the elements from entering the building. Horticultural fan: A propeller fan mounted in an enclosure containing screens and a damper that exhausts air from greenhouses. Kitchen exhaust fan: A fan used to exhaust grease laden air collected by a hood to the exterior of the building. Typically a centrifugal fan. Make-up air unit: A ventilating unit that contains fans, filters, coils, etc. to condition air being supplied to a space to replace air that has been exhausted. Recirculating fan: Fan that moves the air around within the same space. Return air fan: Removes air from an occupied space and delivers the air to a mixing box, where the air is recirculated into or discharged out of a building. Sidewall propeller fan: Fan located in the wall of a building that uses an axial propeller to exhaust high volumes of air with no ductwork. Smoke exhaust fan: A standby fan that removes smoke from a building in case of a fire. The fan must meet rigid structural and performance requirements. Spun aluminum fan: Fan that is made mainly of aluminum, exhausts air and is roof mounted. Spun Aluminum Fans An upblast version is commonly used for kitchen exhaust applications. The downblast is for relatively clean air. 5
6 Supply fan: A fan that supplies outside air to an occupied space. Air may be heated, cooled, humidified, or dehumidified during the process. Tamper resistant fan: Fan that has provisions so it can not be tampered with without internal access. Upblast fan: A fan that exhausts air up and away from the mounting surface, typically a roof. Unit heater: A propeller fan and tempering coil unit that heats or cools small spaces to maintain personnel comfort. Utility fan: A multipurpose scroll house fan that can be configured for many applications, typically has many outlet positions available. Industrial Applications Utility Fan Bag house fan: A fan that draws dirty air through bag filters in an air cleaning unit similar to a vacuum cleaner but on a much larger scale. Basic oxygen fan: A fan that supplies a burst of air (oxygen) to a furnace used to make steel. The fan idles for long periods of time and suddenly upon demand supplies the flow of air required. Bifurcator fan: An inline fan for handling hot or contaminated air where the direct connected motor is separated from the air by means of a compartment or tunnel. Brake fan: A fan wheel typically running backwards that absorbs power. Cement or lime kiln exhaust fan: Exhausts air from a kiln drying cement. One of the most severe corrosive and high temperature applications to be found. Exhaust fan: Removes clean air or contaminated air from an occupied or industrial space. Forced draft fan: Supplies combustion air to a furnace or burner. Fume hood exhaust fan: A fan that exhausts air from a hood over pickling, plating or other process and discharges it at a high velocity to the outside. High pressure blower: A high speed fan that provides a low volume of air at high pressures for processes, cooling, aeration, flotation, etc. Impulse or jet fan: An axial fan with a high velocity discharge that induces air flow in a long underground tunnel without ductwork. Incinerator fan: A fan that exhausts fumes, ashes, dust, etc. from an incinerator. These are high temperature and very corrosive applications. Induced draft fan: A fan that removes flue gas from a furnace or burner and discharges it to the outside or into an air cleaning unit. Industrial exhaust fan: A heavy duty fan that exhausts air from grinding, buffing, pickling tanks, textiles, etc. At times, these fans may handle solids such as wood chips. Material conveying fan: A fan that handles air containing small solids or entrained dust. Mine fan: A fan that supplies air to a mine shaft for ventilation. These fans may exhaust air that contains small solids from the mining process. Paper fan: A fan with sharpened blades that chops strips of paper and discharges them into a bin or truck for recycling. Pelletizing or sintering fan: A fan that handles very hot and dirty air from a steel making process that enriches the iron ore charge through coagulation. Cooling tower fan: A very large diameter axial/ propeller impeller that runs relatively slow while drawing air through or over a liquid to cool it. 6
7 Plug Fan Plug fan: A fan that is mounted in the wall of a dryer or oven. The fan mixes and recirculates the air to maintain a uniform temperature. Scarfing fan: A fan that blows slag off of red hot steel billets. Scrubber fan: A fan that provides air at high pressure to clean, aerate and evaporate contaminants. Spray booth fan: A fan that exhausts air from a paint spray booth to the outside or to an air cleaning process. The air is laden with wet paint that requires a very intensive maintenance program for cleaning the fan. Supply fan: A fan that provides clean air for ventilation, cooling etc. into a building. Fluidized bed boiler fan: Provides air that floats a bed of coal. Forced draft fan: Supplies air to a boiler for complete combustion. This fan may be required to overcomes losses from the fan to the balance draft point in the boiler. Gas recirculation fan: Redirects boiler gases increasing mass flow through various parts of the furnace such as superheaters, reheaters and economizers. Tempers hot gases in the boiler to 1900 F. The fan must be sized to overcome losses through the boiler passages and recirculating ductwork. Indirect reheat fan: Adds clean heated air to the system. Induced draft fan: Exhaust products of combustion and provides the necessary draft at the fire and to compensate for additional losses to the end of the system. Overfire air fan: Delivers air over the fire to improve combustion and reduce smoke generation. This fan reduces forced draft requirements, overcomes piping losses and provides turbulent mixing action. Supply Fans Traction motor fan: A fan that supplies air for cooling locomotive traction motors. This is a very demanding application due to frequent start-stops and reliability concerns. Power Plant or Mechanical Draft Cyclone burner fan: Provides combustion air and produces cyclonic action in the burner and furnace. This increases combustion efficiency. Flue gas desulfurization booster fan: A fan placed in series with the induced draft fan providing added pressure capability to overcome air pollution devices in retrofit applications. Tube Axial Fan Primary Air Fan: Transports powdered fuel from the pulverizer to the burner. Provides additional combustion air that makes up for leakage out of the boiler. Seal air fan: Provides clean air to the chamber surrounding the furnace. Creates a pressure large enough to prevent the escape of dirty gas from the furnace. Secondary air fan: Provides additional combustion air. Waste energy fan: Removes hot gases from a waste heat boiler. 7
8 Greenheck Product Application Guide HVAC Ventilation Categories and Applications Major Consideration General Applications A. Fan types 1. Propeller 2. Centrifugal AF, BI, BC 3 Forward Curved 4. Vane Axial 5. Mixed Flow 6. Radial, Radial Tipped 7 Paddle Wheel 8. Plenum 9. Inline B. Rating 1. High Efficiency 2. Single or Parallel Operation 3. Method of Control - Dampers - Inlet Vanes - Blade Changes - Speed 4. Special Air Density 5. Sound 6. Non surge-stability 7. Capture and Entrainment Velocity C. Design 1. Location 2. Orientation 3. Vibration 4. Leakage and Sealing 5. Spark Resistant, Explosive 6. Special Materials 7. Temp & Rate of Temp Change 8. Durability & Reliability 9. Bearing design, cooling, lube 10. Thermal Expansion 11. Erosion (wear) 12. Corrosion 13. Build-up 14. Special Codes & Regulations 15. Start/Stops 16. Flow reversal fan 17. Special Coatings 18. Toxic Gas 19. Insulation General Ventilation Kitchen Ventilation Food & Textile High Temperature Fans General Exhaust Fume, Gas or Odor Conveying Materials Air Cleaning Palletizing, Scintering Mining & Tunnel Explosive Gases (Combustible) Incineration High Pressure Blowers 8
INSTRUCTIONS FOR HOW TO PROPERLY SELECT A FAN OR BLOWER
INSTRUCTIONS FOR HOW TO PROPERLY SELECT A FAN OR BLOWER The instructions that follow are to assist you in completing the information required when making a fan or blower selection. If you need additional
Chapter 3.5: Fans and Blowers
Part I: Objective type questions and answers Chapter 3.5: Fans and Blowers 1. The parameter used by ASME to define fans, blowers and compressors is a) Fan ration b) Specific ratio c) Blade ratio d) Twist
A Guide to Trouble-Free Cooling Towers
A Guide to Trouble-Free Cooling Towers A basic understanding of cooling tower operation and maintenance will help keep a cooling water system running in top condition, year after year By David M. Suptic
Subpart 1. Installation. All plumbing systems must be. installed and tested according to this chapter and chapter 4715,
4658.4500 PLUMBING SYSTEMS; NEW CONSTRUCTION. Subpart 1. Installation. All plumbing systems must be installed and tested according to this chapter and chapter 4715, the Minnesota Plumbing Code. Subp. 2.
Evaluate, Clean, and Tune Guidance
Evaluate, Clean, and Tune Guidance The Evaluate, Clean and Tune (ECT) process serves three essential purposes in the Weatherization Assistance Program (WAP). The first is to evaluate the existing system
SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM
SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop air conditioning unit (5 tons and smaller). 2. Roof curb. 1.2
Fans and Air Handling Units. Will Rea and Paul Pilutti February 16 th, 2011
Fans and Air Handling Units Will Rea and Paul Pilutti February 16 th, 2011 HTS Lunch and Learns Available Online Visit www.htseng.com Engineering Tools Resource Center Contents Fans Fan Curves Fan Laws
Multi-Cyclone Dust Collectors
Multi-Cyclone Dust Collectors Clarage Half a Century of Design and Experience Designed and Fabricated to Meet Customer Needs Clarage Multi-Cyclone Mechanical CollectorS Experience makes the difference.
HVAC Systems: Overview
HVAC Systems: Overview Michael J. Brandemuehl, Ph.D, P.E. University of Colorado Boulder, CO, USA Overview System Description Secondary HVAC Systems Air distribution Room diffusers and air terminals Duct
2014 British Columbia Building Code Changes
District of Houston 250-845-2238 2014 British Columbia Building Code Changes A District of Houston interpretation of the 2014 Building Code Changes for 9.36 & 9.32 The following changes reflect the most
USER S, MAINTENANCE and SERVICE INFORMATION MANUAL
CONTENTS SAFETY INFORMATION................ 2 FOR YOUR SAFETY....................... 2 SYSTEM OPERATION.................. 2 THERMOSTATS........................... 2 INTERMITTENT IGNITION DEVICE...........
product application guide
Understanding Fan System Effects Fan Application FA/101-99 product application guide A technical bulletin for engineers, contractors and students in the air movement and control industry. The air moving
Basics of HVAC Cleaning
Basics of HVAC Cleaning Seminar Outline Residential 1. Types of systems used and why 2. Types of air distribution systems 3. System components 4. Determining the need for cleaning (ACR2002) 5. Project
Ventilation Solutions Kitchens. fantech
Ventilation Solutions Kitchens 2 Kitchens Today s kitchens have become much more than a place for cooking and food preparation. The kitchen is the heart of the home. It s the center of activity for the
Chapter 12 Industrial Ventilation
Chapter 1 Industrial Ventilation Introduction Industrial Ventilation is an important method for reducing employee exposures to airborne contaminants. Ventilation is used to reduce or remove contaminates
Drives and motors. A guide to using variable-speed drives and motors in retail environments
Drives and motors A guide to using variable-speed drives and motors in retail environments Improving energy efficiency and lowering the carbon footprint Retailers across the UK take their corporate responsibility
RPV - RP - RA air handling units
APPLICATIONS Heating, ventilation, cooling >> FACTORIES >> WAREHOUSES >> HALLS >> DISTRIBUTION CENTRES >> COMMERCIAL PREMISES >> PLACES OF WORSHIP RPV - RP - RA air handling units www.reznor.eu RPV - RP
B.C. Buildings Corporation. Mandatory Preventive Maintenance Standard. To Meet Section 4.78 of the WCB OH & S Regulation
B.C. Buildings Corporation Mandatory Preventive To Meet Section 4.78 of the WCB OH & S Regulation Prepared by: BCBC WCB-IAQ Steering Committee Mandatory Preventive TABLE OF CONTENTS Page no. INTRODUCTION...1
Efficiency on a large scale CFB Steam Boilers
Efficiency on a large scale CFB Steam Boilers Circulating Fluidized Bed Steam Boiler The Circulating Fluidized Bed Steam Boiler is an offering from Bosch Thermotechnology a member of the worldwide Bosch
COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES
COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES These guidelines are to be used for ALL commercial cooking hoods, ventilation systems and related fire suppression
Pulverized Coal Pipe Testing and Balancing
Pulverized Coal Pipe Testing and Balancing By Richard F. (Dick) Storm, PE The first step in optimizing combustion system performance is balancing the air and fuel flowing through each of the plant's coal
Mechanical Rooftop Custom Capabilities
Mechanical Rooftop Custom Capabilities Mechanical Construction Capabilities Price manufactures a wide range of custom gas heat and DX cooled units to meet your new construction and retrofit needs. In addition
Element D Services Heating, Ventilating, and Air Conditioning
PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer
Recirculating Roof Fans Models ESRMD, ESRMDF and ERD
Recirculating Roof Fans Models ESRMD, ESRMDF and ERD Four-Way Fan Exhaust Supply Mix Recirculate BUILDING VALUE IN AIR. October 2005 Recirculating Roof Fans Exhaust/Supply/Recirculation/Mix Model ESRMD
AIR CONDITIONING EFFICIENCY F8 Energy eco-efficiency opportunities in Queensland Foundries
AIR CONDITIONING EFFICIENCY F8 Energy eco-efficiency opportunities in Queensland Foundries Hot tips and cool ideas to save energy and money! Air conditioning units or systems are often used by foundries
THREE. Heating and Cooling
THREE Heating and Cooling 17 Condensation Drain Line The line that drains condensed moisture away from your heating and/or cooling unit needs periodic maintenance. If your unit is located in the attic,
Building and Grounds Maintenance Checklist
Building and Grounds Maintenance Checklist Name: School: Room or Area: Date Completed: Signature: Instructions 1. Read the IAQ Backgrounder and the Background Information for this checklist. 2. Keep the
Sulfur Tail Gas Thermal Oxidizer Systems By Peter Pickard
Sulfur Tail Gas Thermal Oxidizer Systems By Peter Pickard Introduction SRU s (Sulfur Recovery Units) are critical pieces of equipment in refineries and gas plants. SRUs remove sulfur compounds from certain
Energy Efficiency in Industrial HVAC Systems
Energy Efficiency in Industrial HVAC Systems Heating, ventilation and air conditioning (HVAC) constitutes up to 35 percent of energy used in manufacturing facilities. This fact sheet is geared towards
SECTION 23 34 13. A. Horsepower: Do not increase or decrease fan motor horsepower without written approval from Engineer.
PART 1 GENERAL SECTION 23 34 13 HVAC FANS 1.01 SUMMARY A. Section Includes: 1. Exhaust fans. 2. Transfer fans. B. Related Documents: 1. Drawings and general provisions of the Contract, including General
HEAT RECOVERY OPTIONS FOR DRYERS AND OXIDIZERS
HEAT RECOVERY OPTIONS FOR DRYERS AND OXIDIZERS William K. Scullion, Application Engineering Leader, MEGTEC Systems, De Pere, WI Introduction Competitive pressures continuously motivate us to examine our
AABC Specifications for Testing and Balancing HVAC Systems
AABC Specifications for Testing and Balancing HVAC Systems The Associated Air Balance Council (AABC) Total System Balancing Specifications for HVAC Testing, Balancing and Performance Verification TOTAL
Condensing Boiler Efficiency
Condensing Boiler Efficiency Date: July 17, 2012 PRES E NT ED BY DO N L E O NA RDI LE O N A RD I I NC. HV AC T RAI N I N G & C ON SU LT IN G Concepts 1 The current state of evolution in boiler design 2
Phoenix Process Engineering, Inc. Project Experience Helping Clients Achieve MACT Compliance
Phoenix Process Engineering, Inc. Project Experience Helping Clients Achieve MACT Compliance The Boiler MACT, 40 CFR 63, Subpart DDDDD, was vacated in 2007 by the U.S Court of Appeals and the 2004 rule
heating 3 & cooling heating and cooling 2010 PulteGroup, Inc. All Rights Reserved.
3 & cooling 17 heating 2010 PulteGroup, Inc. All Rights Reserved. condensation The line that drains condensed moisture away from your heating and/or cooling unit needs periodic maintenance. Air conditioning
CORROSION RESISTANT FRP FANS & BLOWERS
CORPORATION CORROSION RESISTANT FRP FANS & BLOWERS Superior Quality High Efficiency Low Noise Level Competitive Pricing Fans in Stock Dedicated to detail, precision and quality control Welcome to M.K.
Attachment J-C18.1. HVAC Work Instructions
. RFP: Attachment J-C18.1 HVAC Work Instructions NNC13ZFD017J SOW Item No. Title Page C18-02 Control Air Systems Annual PM 2 C18-03 Split System AC Indoor Section Annual PM 3 C18-04 Condensing Unit Semi-Annual
During Various Aluminum Fabricating Operations
Guidelines for Handling Aluminum Fines Generated During Various Aluminum Fabricating Operations F-1 Guidelines for Handling Aluminum Fines Generated During Various Aluminum Fabricating Operations SCOPE
HVAC Checklist - Long Form
HVAC Checklist - Long Form Page 1 of 14 Appendix B discusses HVAC system components in relation to indoor air quality. utside Air Intake Location pen during occupied hours? Unobstructed? Standing water,
Specific Volume of Liquid (Column 7). The volume per unit of mass in cubic feet per pound.
Steam Tables What They Are How to Use Them The heat quantities and temperature/ pressure relationships referred to in this Handbook are taken from the Properties of Saturated Steam table. Definitions of
Answers to Your Questions from the Webinar
2008 Desert Aire and USA Swimming. Used by permission. Desert Aire & USA Swimming - Aquatics Webinar - Answers to Your Questions Answers to Your Questions from the Webinar Thank you for your interest in
A GUIDE TO SELECTING YOUR INDUSTRIAL OVEN
A GUIDE TO SELECTING YOUR INDUSTRIAL OVEN Application 1 The first step in selecting an industrial oven is defining the required heat application that your oven will be used for. Heat processing is extensively
Glossary of HVAC Terms
Glossary of HVAC Terms Heating, Ventilation and Air Conditioning (HVAC) is a major sub- discipline of mechanical engineering. The goal of HVAC design is to balance indoor environmental comfort with other
How much do you know about HVAC? Try testing yourself with the following questions and then take a look at the answers on the following page.
Demystifying HVAC Test Your HVAC Knowledge By Ron Prager How much do you know about HVAC? Try testing yourself with the following questions and then take a look at the answers on the following page. 1)
5. State the function of pulveriser. The pulverisers are the equipments which are used to powdered coal.
413 POWER PLANT ENGINEERING PART-A 1. Define Power. Power is the rate at which energy is used (or) Energy/time. 2. What are the types of fuels? Solid fuel Liquid fuel Gaseous fuel (Any one among the above
SECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS
SECTION 15750 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for roof mounted, self-contained units, with electric cooling, and electric or reverse refrigeration cycle (heat pump) heating
Home Energy Evaluation Report for Fritz Kreiss and Catherine McQueen
Home Energy Evaluation Report for Fritz Kreiss and Catherine McQueen May 2008 Wisconsin Area PO BOX 115 Lake Geneva, WI 53147 CELL (414) 550-4765 Home Performance with ENERGY STAR Evaluation Report Customer
Mechanical Heating Ventilation and Air Conditioning Ductwork and Duct Accessories
Basis of Design This section applies to the design and installation of ductwork, air terminal boxes, air outlets and inlets, volume dampers, pressure relief dampers, smoke/fire dampers, and smoke/fire
ROOF TOP MOUNTED Air Handler Specification
ROOF TOP MOUNTED Air Handler Specification PART 1: GENERAL (Model RT) Mechanical Specification 1.01 WORK INCLUDED A. Provide complete air handling unit(s) suitable for outdoor installation. Contractor
Air Conditioning Clinic
Air Conditioning Clinic Air Conditioning Fans One of the Equipment Series February 2012 TRG-TRC013-EN Air Conditioning Fans One of the Equipment Series A publication of Trane Preface Air Conditioning
Product Data Bulletin
Product Data Bulletin Adjustable Frequency Drives and HVAC Systems An Application Guide September, 1994 Raleigh, NC, U.S.A. INTRODUCTION All buildings pose the same problem: how to heat or cool the air
NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES
NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES 8.1 INTRODUCTION Testing, adjusting, and balancing of HVAC systems can best be accomplished by following a series of systematic procedures. The NEBB TAB
PFT Two stage axial fan The high pressure fan for modern boiler plants
PFT Two stage axial fan The high pressure fan for modern boiler plants Modern boilers equipped with complete flue-gas cleaning systems demand fans for high pressure that can be controlled quickly and accurately
SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT
SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT PART 1 - GENERAL 1.1 DESCRIPTION A. The Work specified in this Section consists of designing, furnishing and installing factory-assembled
Hot Water Boilers and Controls Why Condensing Boilers are Different. Presented Oct. 14, 2008 Long Island Chapter, ASHRAE
Hot Water Boilers and Controls Why Condensing Boilers are Different Presented Oct. 14, 2008 Long Island Chapter, ASHRAE H.W. Boilers and Controls Major types of boilers Advantages and disadvantages Resistance
BPC Green Builders. Green building for new and existing homes. Health Comfort Energy
BPC Green Builders Green building for new and existing homes Health Comfort Energy Mechanical Systems Installed HVAC Systems Primary energy source large, roof mounted, solar thermal array (AET flat plate)
HVAC Processes. Lecture 7
HVAC Processes Lecture 7 Targets of Lecture General understanding about HVAC systems: Typical HVAC processes Air handling units, fan coil units, exhaust fans Typical plumbing systems Transfer pumps, sump
SPECIFICATION TECHNICAL AIR-CONDITIONING UNITS SINGLE AND SPLIT (DUCTED) (AIR COOLED PACKAGED UNIT)
SPECIFICATION TECHNICAL AIR-CONDITIONING UNITS SINGLE AND SPLIT (DUCTED) (AIR COOLED PACKAGED UNIT) MAINTENANCE TYPE: STATUTORY 1.0 SCOPE OF SERVICES The Contractor shall provide maintenance Services for
Tube Axial Roof Upblast Model TAUB with Fabricated Steel Propeller
Tube Axial Roof Upblast Model TAUB with Fabricated Steel Propeller Belt Drive Low and High Pressure October 009 Features Page Header Tube Axial Roof Upblast Fans Greenheck belt drive tube axial upblast
Heating Ventilation and Air Conditioning Diagnostics for Single Family Homes
Heating Ventilation and Air Conditioning Diagnostics for Single Family Homes Vincent Pedalino FSL Home Improvements Phoenix, AZ 1 HVAC Basics Ways to improve the performance of existing air conditioning
Guidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems
Guidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems If you're a designer or a BCA, this guidance on the energy efficiency of HVAC systems in commercial buildings may
Diagnostics for Mobile Homes: HVAC
Diagnostics for Mobile Homes: HVAC Adam Harris NYSWDA Wade Thompson - IWTC Objectives Identify different types of HVAC used in mobile homes Provide an overview of duct systems Demonstrate various tests
WATER HEATERS. If your water heater tank is leaking, then your course is clear: buy a new unit. But if it isn t, your answer is less obvious.
HOME ENERGY GUIDE TECHNIQUES TACTICS & TIPS WATER HEATERS Minnesota Department of Commerce Energy Information Center Water heating is often the second largest energy expense in the Minnesota home, and
123 street Salt Lake City, Utah 84092
Salt Lake City, Utah 84092 Prepared for: Sample AC inspection Prepared by: Page 1 of 8 Table of Contents Definitions 2 General Information 2 Air Conditioning 3 Heating System 6 Summary 8 Page 2 of 8 Definitions
Preventive Maintenance. State Energy Assessment Workshop By: DTE Energy Partnership & Services
Preventive Maintenance State Energy Assessment Workshop By: DTE Energy Partnership & Services Do you know? World wide research has shown that one of the reasons causing 80% of the accidents is deficient
ENGINE COOLING SYSTEM
ENGINE COOLING SYSTEM 1988 Toyota Celica 1987-88 TOYOTA Engine Cooling Systems Celica DESCRIPTION The basic liquid cooling system consists of a radiator, water pump, thermostat, cooling fan, pressure cap,
Spray Booth Guideline
Department of Development Service 135 North D Street, Perris CA. 92570 Phone: (951) 443-1029 Fax: (951) 943-3293 PURPOSE The intent of this guideline is to provide the information necessary to ensure that
ENGINEERING DATA. Fan Performance Troubleshooting Guide
Information and Recommendations for the Engineer ENGINEERING DATA Aerovent TC Ventco Fiber-Aire Twin City Fan & Blower TC Axial Clarage Fan Performance Troubleshooting Guide ED- Introduction Trying to
1.2 Refrigerant Equipment. General
Part 1 General 1.1 Summary.1 Unless otherwise indicated, follow the standards below when specifying heating, ventilation and air conditioning (HVAC) work. These standards are not intended to restrict or
Glossary of Heating, Ventilation and Air Conditioning Terms
Glossary of Heating, Ventilation and Air Conditioning Terms Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment
Gas-Fired, Residential Storage Type Water Heaters
Consulting, Resource, Education, Training, and Support Services for Home Inspectors A candle loses no light when it lights another candle. Gas-Fired, Residential Storage Type Water Heaters Most inspectors
Center for Energy Education Laboratory
Paper ID #7072 Center for Energy Education Laboratory Dr. Robert Gilbert, Sinclair Community College Robert B. Gilbert, Ph.D., LEED AP, BA, is an Associate Professor of Energy Management Technology, and
1 DESCRIPTION OF THE APPLIANCE
1 DESCRIPTION OF THE APPLIANCE 1.1 INTRODUCTION The cast iron SF boilers are a valid solution for the present energetic problems, since they can run with solid fuels: wood and coal. These series of boilers
Building Energy Systems. - HVAC: Heating, Distribution -
* Some of the images used in these slides are taken from the internet for instructional purposes only Building Energy Systems - HVAC: Heating, Distribution - Bryan Eisenhower Associate Director Center
Pool Dehumidification Basics
Copyright 2009 Wescor. All rights reserved. Permission granted to reproduce for personal and educational use only. When energy costs were low, many pool owners considered only first cost when choosing
INTERNATIONAL FIRE TRAINING CENTRE FIREFIGHTER INITIAL PUMPS AND PRIMERS. Throughout this note he means he/she and his means his/hers.
INTERNATIONAL FIRE TRAINING CENTRE FIREFIGHTER INITIAL PUMPS AND PRIMERS Throughout this note he means he/she and his means his/hers. Areas of bold type are considered to be of prime importance. INTRODUCTION
NFPA Combustible Dust Compliance and the Industrial Ventilation System
NFPA Combustible Dust Compliance and the Industrial Ventilation System Presented By: Tom Kroeger PE [email protected] Kirk & Blum, a CECO Environmental Company Marty Schloss PE [email protected]
Combustible dust. How to use this guide. Combustible Dust
INDUSTRIAL HYGIENE Combustible dust How to use this guide The purpose of this guide is to provide an overview of the dangers of combustible dust explosions along with tools and resources to recognize,
Roof Curbs, Extensions and Equipment Supports
Roof s, Extensions and Equipment Supports December 2012 Roof Page s, Header Extensions and Equipment Supports Table of Contents Model GPI Standard and Optional Construction Features... 3 Model Number Code....
Commercial Gas Furnace Upflow
Commercial Gas Furnace Upflow Model G24-200 80% A.F.U.E. 200,000 Btuh Input Heating Cap. 7.5 or 10 Tons Nominal Add-On Cooling GUK FEATURES Certified by A.G.A./C.G.A. Laboratories. Heavy gauge painted
- White Paper - Data Centre Cooling. Best Practice
- White Paper - Data Centre Cooling Best Practice Release 2, April 2008 Contents INTRODUCTION... 3 1. AIR FLOW LEAKAGE... 3 2. PERFORATED TILES: NUMBER AND OPENING FACTOR... 4 3. PERFORATED TILES: WITH
Boiler and Burner Cleaning and Servicing Specifications
Boiler and Burner Cleaning and Servicing Specifications The Town of Groton of Public Works Department is requesting bids to provide manufacturers recommended maintenance, repairs and emergency service
TYPICAL FIRE SAFETY INSPECTION VIOLATIONS
TYPICAL FIRE SAFETY INSPECTION VIOLATIONS The following is a list of typical violations often found by inspectors and a generic solution. You can use this list to improve the safety of your facility, to
Decree of the Ministry of the Environment on fire safety of ventilation systems
THE NATIONAL BUILDING CODE OF FINLAND MINISTRY OF THE ENVIRONMENT Housing and Building Department Decree of the Ministry of the Environment on fire safety of ventilation systems Adopted in Helsinki, 18
Design Information. Designing Your Dust Collection System. Typical dust or fume collection system
Design Information Designing Your Dust Collection System There are five simple steps to designing an effective and efficient dust collection system. 1. Draw a floor plan of your shop Important Terms to
Johnson Air-Rotation Systems
AR Series TM Johnson Air-Rotation Systems Solution TM D Series TM FF Series TM 80/20 PR Series TM Johnson Air-Rotation systems announces a major addition to its product line, completing its line of high
SL280UHV SERIES GAS FURNACE WARNING
2010 Lennox Industries Inc. Dallas, Texas, USA 506677 01 11/2010 Supersedes 506409 01 SL280UHV SERIES GAS FURNACE Litho U.S.A. FIRE OR EXPLOSION HAZARD. Failure to follow safety warnings exactly could
Home Maintenance Checklist
Regular maintenance keeps your home functioning efficiently and safely and helps protect its value. We're happy to offer this checklist of ongoing and seasonal maintenance steps to help you safeguard your
Printing and Publishing Energy Savings Guide
Printing and Publishing Energy Savings Guide Oregon printing and publishing plants face challenges of rising operating costs, environmental and other regulations, outdated equipment and customer demand
UPBLAST & HOODED PROPELLER ROOF VENTILATORS
The Industrial Choice. Model D53 / B53 Model HD53 / HB53 UPBLAST & HOODED ELLER ROOF VENTILATORS Direct Drive & Belt Driven Model D53 / B53 Upblast Exhaust Fans Model HD53 / HB53 Hooded Supply & Exhaust
CENTRIFUGAL PUMP OVERVIEW Presented by Matt Prosoli Of Pumps Plus Inc.
CENTRIFUGAL PUMP OVERVIEW Presented by Matt Prosoli Of Pumps Plus Inc. 1 Centrifugal Pump- Definition Centrifugal Pump can be defined as a mechanical device used to transfer liquid of various types. As
Heating, Ventilation, Air Conditioning and Refrigeration (HVACR)
Heating, Ventilation, Air Conditioning and Refrigeration (HVACR) I. Demonstrate safety skills in typical HVACR work situations to NATE Core Installer Knowledge Areas for Technician Excellence for Safety
READ AND SAVE THESE INSTRUCTIONS
AUTOMATIC WITH To register this product visit: www.broan.com MODELS MD6T MD8T MD10T READ AND SAVE THESE INSTRUCTIONS FOR RESIDENTIAL USE ONLY Page 1 WARNING TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK,
THE USE OF STEEL BUILDING PANELS FOR ANIMAL CONFINEMENT
BACKGROUND Technical TSB 4.1 Bulletin Construction THE USE OF STEEL BUILDING PANELS FOR ANIMAL CONFINEMENT BACKGROUND TBP 2005.2 This Technical Bulletin is intended to assist users in the design and maintenance
By K.K.Parthiban / Boiler specialist / Venus Energy Audit System
FINE TUNING EXPERIENCE OF A CFBC BOILER By K.K.Parthiban / Boiler specialist / Venus Energy Audit System Introduction The Industrial boilers have been seeing a growth in capacity in the recent years. Current
EASY$ TIP SHEETS. Energy Advice Saving Yukoners Money
EASY$ TIP SHEETS Energy Advice Saving Yukoners Money Quick Links How to check for leaks Draftproofing products Sealants Draft proofing your home Draftproofing can be a cost-effective measure you take to
Basic Selection & Proper Application of Overhead Air Distribution Devices
Basic Selection & Proper Application of Overhead Air Distribution Devices GRD Selection & Application Terms Selection Throw Sound Installation Variations affect Performance Inlet Effects Basics Return
Integrated Solar Radiant Systems
Integrated Solar Radiant Systems William Shady PE President Topics Radiant heating Indoor air quality Radiant Cooling Project Photos Questions and answers The goal for our clients Healthy Comfort Why Radiant
Bring the fresh in. Dedicated Outside Air Systems
Bring the fresh in. Dedicated Outside Air Systems The inside story on outside air. On average, we breathe in 3,400 gallons of air each day. Ambient indoor air pollution is a major problem, affecting health