SPECIFICATION TECHNICAL AIR-CONDITIONING UNITS SINGLE AND SPLIT (DUCTED) (AIR COOLED PACKAGED UNIT)
|
|
- Bruno Norman
- 7 years ago
- Views:
Transcription
1 SPECIFICATION TECHNICAL AIR-CONDITIONING UNITS SINGLE AND SPLIT (DUCTED) (AIR COOLED PACKAGED UNIT) MAINTENANCE TYPE: STATUTORY 1.0 SCOPE OF SERVICES The Contractor shall provide maintenance Services for the Air Cooled Packaged Units including associated ductwork covered by this Contract. The Services shall be carried out at the intervals stated below unless otherwise stated in the Equipment and Pricing Schedule. 2.0 MINIMUM STANDARD The minimum standards for periodic inspection and servicing shall be as stated below and in accordance with the requirements of the current editions of: Fire and Rescue Service Act Building Act and Building Fire Safety Regulations BCA Building Code of Australia QDC MP 6.1 Maintenance of Fire Safety Installations AS 1851 Maintenance of Fire Protection Systems and Equipment AS/NZS 3788 Pressure equipment - In-service inspection AS 3873 Pressure equipment - Operation and maintenance AS/NZS Air-handling and water systems of buildings Microbial control Part 2: Operation and maintenance HB 40 The Australian Refrigeration and Air-conditioning Code of Good Practice 3.0 MINIMUM QUALIFICATIONS The Contractor shall ensure that it has the appropriate licences issued by the Queensland Building Services Authority to perform the services under the Contract and must provide evidence to the satisfaction of the Principal. The Contractor shall also ensure that persons who carry out required tests, services or make logbook entries are qualified in Refrigeration, Air Conditioning and Mechanical Services, with: a) Expertise in the servicing and repair of packaged air conditioning units b) Accreditation in the handling of Ozone Depleting Substances The Contractor shall hold valid licences issued under the Ozone Protection and Synthetic Greenhouse Gas Management Act 1989 as follows: National Refrigerant Trading Authorisation in the name of the company undertaking the work of the Contract. National Refrigerant Handling licence in the name of each employee of the company who is likely to handle refrigerants in undertaking the work of the Contract. The above licences shall be produced upon request by the Principal's Representative. 4.0 REFRIGERANT MANAGEMENT All maintenance and work practices are to be in accordance with The Australian Refrigeration and Air-conditioning Code of Good Practice (HB 40). All refrigerant usage is to be recorded. Whilst undertaking servicing, maintenance and repairs to equipment of this Contract, service personnel shall take all necessary precautions to ensure that no refrigerant is released to the atmosphere. All refrigerant is to be recovered using an approved recovery unit. It is the responsibility of the Contractor to provide a suitable recovery unit for the installations of the Contract. Document: TSW00010 Date Issued: Page 1 of 7
2 All clean recovered refrigerant may be re-used. The Contractor shall ensure that the re-use of recovered refrigerant does not cause any system malfunction due to unacceptable contamination. Recovered contaminated refrigerant shall not be re-used. 5.0 MAINTENANCE REQUIREMENTS AND FREQUENCY Perform all the service requirements as detailed below: 5.1 Refrigeration Compressors 1 Measure suction and discharge pressures. 2 Check all safeties and pressure gauges. 3 Ensure the unloading mechanism and controls are functioning correctly. 4 Inspect and record oil level and pressure including crankcase heater condition. 5 Inspect compressor motor coupling and / or pulleys and belts where applicable. 6 Test for and repair refrigerant and oil leakage. 7 Check for undue noise and vibration. 8 Measure and record motor amperage. Compare with nameplate rating. 9 Change sequence switch and ensure correct operation. 10 Clean compressor, base and motor casing. 11 For open compressors take an oil sample from each compressor and analyse for acid, moisture, etc. If an oil change is required, liaise with the principal's representative regarding approval. 12 Check compressor motor terminals for hot connections, undertake resistance test of windings and record readings. 13 Check operation efficiency of suction discharge valves. 5.2 Air Cooled Condensers 1 Check operation and condition of fans including fan cycling operation for head pressure modulating. 2 Check efficiency of condenser operation by reading compressor discharge pressure and report any abnormal function. 3 Clean condenser coils by hosing with water. 4 Report abnormal high noise level. Document: TSW00010 Date Issued: Page 2 of 7
3 5 Treat and paint corrosion as necessary. 6 Measure motor amperage and compare ratings. 7 Change lead-lag sequence on fan motors and calibrate head pressure modulating device. 8 Comb all condenser fins straight. 9 Supply and replace all belts on belt drive units. 10 Report on overall condition and indicate when replacement required. 5.3 Air Handling Unit and Air Filters 1 Clean and flush condensate trays and drains. Ensure drain is running free. Leave tray dry. 2 Inspect cooling and heating (if fitted) coils: Comb fins straight and clean coils as required, using biodegradable, non-toxic, water-based odour-free foaming detergent. Provide MSDS prior to the first service or on request. Rinse coils thoroughly with clean water after applying detergents. 3 Check air filters (dry media): Check integrity of filter seals to ensure there is no air bypass. Check that restraining brackets hold the filter frames securely and that the filter media is securely fastened. Repair filter handles and frames as required. Record pressure-drop across filters. If pressure-drop is excessive, report the circumstances to the principal s representative for further instructions. Note: supplying washable filter media and/or washing existing filter media are not acceptable. If removing dirty filter media from site, take care to avoid soiling floor coverings and other furnishings etc. Fans are to be turned off while filters are being inspected and/or changed. After completing the work, ensure the fans are turned on and operable. Remove filter debris from the chamber and leave clean and tidy. Document: TSW00010 Date Issued: Page 3 of 7
4 4 Check unit and seals for air leakage. 5 Check panels, doors and fastenings for security and air leaks. Repair any air leaks. 6 Check that insulation is clean and secure. Repair as required. 7 Check that all automatic volume control dampers and linkages are fully operable. Lubricate, using a dry lubricant, as required. 8 Check that all automatic volume control dampers seal tight when closed. 9 Check and record air on coil, air off coil, room, return air and outside air temperatures. 10 Check complete unit for corrosion or deterioration. 5.4 Fans and Motors Supply or Return Air used in Day-To-Day Operation Item 1 Obstructions Check there are no physical obstructions likely to impede performance. 2 Noise, Check motor and all bearings for noise, overheating and overheating and vibration excessive vibration. 3 Flexible Check flexible connections, where fitted, for leaks, tearing connections or fraying. 4 Fan belts (wear) Check fan belts for wear. 5 Guards and Check for satisfactory condition. other safety features 6 Bearings Check lubrication of bearings and lubricate as required. 7 Couplings Check couplings for tightness. 8 Fan belts Check for correct tension. (tension) 9 Fan blades Clean fan blades and scrolls. 10 Pulley wheels Check pulley wheels and couplings for alignment. and couplings 11 Casing guards Check casing, guards and impeller for corrosion. and impeller 12 Fan belts Supply and replace all drive belts. 13 Electrical Check electrical connections, isolators and terminal box. Document: TSW00010 Date Issued: Page 4 of 7
5 5.5 Ductwork 1 Check ductwork for air leakage. Repair minor leaks. 2 Check external insulation for retainment. Repair as required. 3 Check and clean all fresh air intakes, return air grilles, exhaust outlets and air relief transfer grilles. 4 Report severe deterioration of ductwork, insulation, dampers, heater banks and any build up of impurities. 5 Check integrity of flashing at external penetrations. 6 Check that all automatic terminal units are fully operable and that linkages are free to move. 7 Check that manual volume control dampers are correctly positioned and are freely adjustable. 8 Check and clean the following: Ductwork in the vicinity of moisture producing equipment. Drainage facilities associated with moisture producing equipment. Air terminal units, including air registers. Steam and spray humidifiers, including line strainers, valves, sparge pipes, spray nozzles and other components discharging moisture into the airstream. 5.6 Air conditioning controls Item no. Service item 1 Check for burnt wiring. 2 Check all fuses. 3 Check all meters for correct operation. 4 Check all contactors for correct operation. 5 Ensure all relays are secure. 6 Test all run and fault lights. Supply and replace faulty switchboard/panel lights. 7 Ensure all cable duct covers are in place and secure. 8 Ensure all control covers are in place and secure. 9 Clean inside of switchboard/control panel. 10 Check operation of air compressor and drain vessel where applicable. 11 Check staging controls for correct operation. Report short cycling to Principal s Representative. Document: TSW00010 Date Issued: Page 5 of 7
6 Item no. Service item 12 Check all temperatures and adjust if required. 13 Ensure all room thermostat covers are in place and secure. 14 Check set points of all controls for accuracy - recalibrate as required. 15 Ensure safety controls and devices are controlling at the recommended value. 16 Test all manual over-ride switches. 17 Test operation of all test switches. 5.7 System Shutdown (where applicable) Item 1 Full simulation Fully simulate a fire/smoke situation from any device such as a sprinkler, thermal or smoke detector, to effect shut-down of all air conditioning and mechanical ventilation systems not required to operate in fire mode (see clause of AS 1851). Check all systems required to shut down are not operating. 5.8 Pressure Vessels - Internal And External Inspection (where applicable) The minimum standards for periodic inspection and servicing shall be as stated below and in accordance with the current requirements of AS\NZS Inspections are required for vessels that contain either: 1) Group 1 refrigerants 1 when the vessel has pv > 200MPa.L 2 ; or 2) Any refrigerant from Group A2, A3 and B External Inspections 1 Inspect external surfaces of vessel for pitting. 2 Inspect external surfaces of vessel for cracks or splitting. 3 Inspect vessel for distortion or bulging. 4 Inspect vessel for corrosion. Repair as required. 1 Refer AS/NZS Group A1 refrigerants include R22, R123, R 134a and R4xx blends. Group B2 includes R717 (Ammonia) and Groups A2 and A3 contain the flammable refrigerants Propane, butane etc 2 Where p = design pressure of vessel in MPa (mega-pascals) and V=water volume of vessel in litres Document: TSW00010 Date Issued: Page 6 of 7
7 Remove all deposits and debris build-up from and around vessel. 6 Inspect condition of welds. 7 Inspect condition of all sockets, studs and flanges. 8 Inspect access panels for damage and sealing integrity. 9 Inspect vessel for leaks Internal Inspections 1 Inspect internal surfaces of vessel for pitting. 2 Inspect internal surfaces of vessel for cracks or splitting. 3 Inspect vessel for distortion or bulging. 4 Remove all deposits from vessel. 5 Inspect access panels for damage and sealing integrity. 6 Inspect vessel for leaks after reinstatement of access panels General 1 Supply a complete and concise report on each internal and external inspection. 2 Contact the Principal s Representative if further work is required. 3 On completion of inspection the Contractor shall fix an aluminium tag (business card size) to the equipment. The tag shall indicate the contractor s name, the Date Tested and the Next Test Date for both internal and external inspections. Document: TSW00010 Date Issued: Page 7 of 7
Evaluate, Clean, and Tune Guidance
Evaluate, Clean, and Tune Guidance The Evaluate, Clean and Tune (ECT) process serves three essential purposes in the Weatherization Assistance Program (WAP). The first is to evaluate the existing system
More informationPreventive Maintenance. State Energy Assessment Workshop By: DTE Energy Partnership & Services
Preventive Maintenance State Energy Assessment Workshop By: DTE Energy Partnership & Services Do you know? World wide research has shown that one of the reasons causing 80% of the accidents is deficient
More informationAttachment J-C18.1. HVAC Work Instructions
. RFP: Attachment J-C18.1 HVAC Work Instructions NNC13ZFD017J SOW Item No. Title Page C18-02 Control Air Systems Annual PM 2 C18-03 Split System AC Indoor Section Annual PM 3 C18-04 Condensing Unit Semi-Annual
More informationCOMMISSIONING OF HVAC SYSTEMS
FORM CL-01 SYSTEMS / EQUIPMENT INCLUDED : SYSTEM STARTUP CHECKLIST I - PRE - STARTUP INSPECTION EQUIPMENT MOUNTING & SETTING CONTROL, INTERLOCK & POWER WIRING ALIGNMENT OF MOTORS & DRIVES PIPING, CONNECTIONS
More informationAction Plan Template HVAC Page 1
Action Plan Template HVAC Page 1 Once Establish expected HVAC system efficiency - Write down the expected efficiency of HVAC systems to use as a baseline - Add this information to maintenance plan documentation
More informationSECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS
SECTION 15750 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for roof mounted, self-contained units, with electric cooling, and electric or reverse refrigeration cycle (heat pump) heating
More informationTable V. Troubleshooting Checklist for Refrigeration Systems. Air or non-condensable gas in system. Inlet water warm.
Table V Troubleshooting Checklist for Refrigeration Systems TROUBLE POSSIBLE CAUSE CORRECTIVE MEASURE High condensing pressure. Low condensing pressure. Air or non-condensable gas in system. Inlet water
More informationHVAC Design Requirements
Maintenance of HVAC HVAC Design Requirements Air Flow Diagram แบบ Recirculation Air Flow Diagram แบบ Once Through Definition Of Conditions As built At rest In operation air air air Maintenance GMP Requirements
More informationREQUEST FOR BIDS 2013-12 HVAC PREVENTATIVE MAINTENANCE AND SERVICE JANUARY 18, 2013. Issued by: NH Liquor Commission. PO Box 503, Concord, NH 03302
REQUEST FOR BIDS 2013-12 HVAC PREVENTATIVE MAINTENANCE AND SERVICE JANUARY 18, 2013 Issued by: NH Liquor Commission PO Box 503, Concord, NH 03302 This Page intentional left blank TABLE OF CONTENTS EXHIBITS...
More informationHVAC Checklist - Long Form
HVAC Checklist - Long Form Page 1 of 14 Appendix B discusses HVAC system components in relation to indoor air quality. utside Air Intake Location pen during occupied hours? Unobstructed? Standing water,
More informationConsortiwm Awdurdodau Lleol Cymru Consortium Local Authorities Wales
Consortiwm Awdurdodau Lleol Cymru Consortium Local Authorities Wales SPECIFICATION FOR LAUNDRY EQUIPMENT MAINTENANCE Maintenance Module 32 March 2011 issue This document has been compiled by the Engineering
More informationA Guide to Trouble-Free Cooling Towers
A Guide to Trouble-Free Cooling Towers A basic understanding of cooling tower operation and maintenance will help keep a cooling water system running in top condition, year after year By David M. Suptic
More informationTraining Syllabus to Instruct/Prepare for the ASE Transit Bus HVAC Test
APTA STANDARDS DEVELOPMENT PROGRAM RECOMMENDED PRACTICE American Public Transportation Association 1666 K Street, NW, Washington, DC, 20006-1215 APTA BTS-BMT-RP-001-10 Approved October, 2010 APTA Bus Maintenance
More informationNational Competency Based Skill Training Refrigeration and Air-conditioning Mechanic Logbook
National Competency Based Skill Training Refrigeration and Air-conditioning Mechanic Logbook Trainee:... Training Provider:... Year:... Trainee Contact no:... Competency Based Skill Training Logbook Introduction
More informationTrouble Shooting. Pump
Trouble Shooting Pump Trouble Possible Cause Remedy Oil leaking in the area of water pump crankshaft Worn crankshaft seal, bad bearing, grooved shaft, or failure of retainer o-ring. Excessive play on crankshaft
More informationBoiler and Burner Cleaning and Servicing Specifications
Boiler and Burner Cleaning and Servicing Specifications The Town of Groton of Public Works Department is requesting bids to provide manufacturers recommended maintenance, repairs and emergency service
More informationHVAC Preventative Maintenance Basics. Presented by Mike Crawley
HVAC Preventative Maintenance Basics Presented by Mike Crawley Air Handlers/Package Units: Coils have to be clean! The main purpose of any coil is to absorb or reject heat If coils are dirty; air flow
More informationTerms of Reference Air Handling Unit (HVAC System) Cleaning
Terms of Reference Air Handling Unit (HVAC System) Cleaning Introduction General cleaning of the air handling units is currently undertaken by the Mechanical Division staff composing of 3 personnel. Cleaning
More informationPreventive Maintenance. Learning Objectives: Howdy! Learning Objectives Cont:
Preventive Maintenance Fountain of Youth for HVAC Successful Learning Environment Bonus Strategies James D. McClure, P.E. Action Planning Guide As you listen to this presentation, use the chart in your
More informationFirst irst Co. Products
First irst Co. Products Recommended Maintenance Program PM1193 FIRST OPERATIONS,LP - P.O. Box 270969 - Dallas, Texas 75227 - www.firstco.com Table of Contents Introduction... 3 General Precautions... 3
More information3620 W 11th Streetб Houston, TX 77008 Telephone: 713-635-6291 Email: sales@kellogg-american.com Website: www.kellogg-american.com
Unpackaging & Handling Be sure to carefully inspect the unit before accepting the shipment. If any damage has occurred document it with the trucking company immediately. Contact your Kellogg Distributor
More informationCDS TROUBLESHOOTING SECTION I. VACUUM. 1.0. Weak vacuum at wand. Gauge reads normal (10hg to 14hg)
CDS TROUBLESHOOTING SECTION I. VACUUM 1.0. Weak vacuum at wand. Gauge reads normal (10hg to 14hg) 1.1. Clogged hoses or wand tube. Disconnect hoses and carefully check for an obstruction. 1.2. Excessive
More informationSECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM
SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop air conditioning unit (5 tons and smaller). 2. Roof curb. 1.2
More informationTHREE. Heating and Cooling
THREE Heating and Cooling 17 Condensation Drain Line The line that drains condensed moisture away from your heating and/or cooling unit needs periodic maintenance. If your unit is located in the attic,
More informationheating 3 & cooling heating and cooling 2010 PulteGroup, Inc. All Rights Reserved.
3 & cooling 17 heating 2010 PulteGroup, Inc. All Rights Reserved. condensation The line that drains condensed moisture away from your heating and/or cooling unit needs periodic maintenance. Air conditioning
More informationTable Z. Troubleshooting Chart for Air Conditioners. Cause
Troubleshooting Chart for Air Conditioners Type of Unit Complaint Cause With open-type compressor Electric motor will not start Power failure Check circuit for power source Compressor stuck Locate cause
More informationREFRIGERATION & AIR-CONDITIONING UNIT IIT KHARAGPUR
REFRIGERATION & AIR-CONDITIONING UNIT IIT KHARAGPUR Sub.: Day-to-Day operation contract & maintenance for 2 X 40 TR &1 X 20 TR DX type Central AC Plant of Netaji Auditorium of IIT Kharagpur Ref.: IIT/RAC/Netaji/OC
More informationUSER INSTRUCTIONS FOR 10 LITRE PORTABLE DEHUMIDIFIER MODEL NO. DHMD102
USER INSTRUCTIONS FOR 10 LITRE PORTABLE DEHUMIDIFIER MODEL NO. DHMD102 THANK YOU FOR CHOOSING YOUR NEW DEHUMIDIFIER. BEFORE USING THE UNIT READ THESE INSTRUCTIONS FULLY AND RETAIN THEM FOR FUTURE REFERENCE
More informationMINNESOTA WEST COMMUNITY & TECHNICAL COLLEGE COURSE OUTLINE
MINNESOTA WEST COMMUNITY & TECHNICAL COLLEGE COURSE OUTLINE Faculty are required to have the outline submitted to the Academic Affairs Office. The course outline is the form used for approval of new courses
More informationMaintenance for Energy Efficiency
Maintenance for Energy Efficiency Institute of Hospital Engineering, Australia (IHEA) Seminar Asset Management & Energy Efficiency Exclusive Trane distributor Australia/New Zealand. The TRANE trade mark
More informationSubpart 1. Installation. All plumbing systems must be. installed and tested according to this chapter and chapter 4715,
4658.4500 PLUMBING SYSTEMS; NEW CONSTRUCTION. Subpart 1. Installation. All plumbing systems must be installed and tested according to this chapter and chapter 4715, the Minnesota Plumbing Code. Subp. 2.
More informationHeating, Ventilation, Air Conditioning and Refrigeration (HVACR)
Heating, Ventilation, Air Conditioning and Refrigeration (HVACR) I. Demonstrate safety skills in typical HVACR work situations to NATE Core Installer Knowledge Areas for Technician Excellence for Safety
More informationFPS4 APPENDIX A (INTERIM) SPECIFICATION FOR THE INSPECTION AND TESTING OF AUTOMATIC FIRE SPRINKLER SYSTEMS
FPS4 APPENDIX A (INTERIM) SPECIFICATION FOR THE INSPECTION AND TESTING OF AUTOMATIC FIRE SPRINKLER SYSTEMS To be used in conjunction with the Fire Protection Association Australia FPS4-2000: Agreement
More informationB.C. Buildings Corporation. Mandatory Preventive Maintenance Standard. To Meet Section 4.78 of the WCB OH & S Regulation
B.C. Buildings Corporation Mandatory Preventive To Meet Section 4.78 of the WCB OH & S Regulation Prepared by: BCBC WCB-IAQ Steering Committee Mandatory Preventive TABLE OF CONTENTS Page no. INTRODUCTION...1
More informationSL280UHV SERIES GAS FURNACE WARNING
2010 Lennox Industries Inc. Dallas, Texas, USA 506677 01 11/2010 Supersedes 506409 01 SL280UHV SERIES GAS FURNACE Litho U.S.A. FIRE OR EXPLOSION HAZARD. Failure to follow safety warnings exactly could
More informationCARING FOR YOUR WATER HEATER
http://waterheatertimer.org/troubleshoot-rheem-tankless-water-heater.html Water Heater Inspections CARING FOR YOUR WATER HEATER Venting System (Direct Vent Only) The venting system should be inspected
More informationSECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT
SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT PART 1 - GENERAL 1.1 DESCRIPTION A. The Work specified in this Section consists of designing, furnishing and installing factory-assembled
More informationAir Conditioner Water Heater - A Product of HotSpot Energy LLC
Air Conditioner Water Heater - A Product of HotSpot Energy LLC PLEASE READ THIS BEFORE YOU INSTALL THE UNIT 1. This air conditioner must be installed and/or repaired by a qualified technician. If you perform
More informationASTACEA4 Inspect complex/central air conditioning systems
Overview This Unit covers the competences required to inspect complex/central air conditioning systems as defined by the CIBSE TM 44 Figure 1.1: Summary of system types and their component parts. The air
More informationSECTION 23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION
SECTION 23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION The purpose of this guide specification is to assist the specifier in correctly specifying Mechanical System Testing
More informationElements Elements describe the essential outcomes. 1. Prepare to diagnose and repair air conditioning and HVAC system
AURETU004 Application Competency Field Unit Sector Elements Elements describe the essential outcomes. 1. Prepare to diagnose and repair air conditioning and HVAC system 2. Diagnose air conditioning and
More informationADDENDUM NO. 1 TO THE BIDDING DOCUMENTS. HVAC SERVICE AND MAINTENANCE Saint Clair County MidAmerica Saint Louis Airport.
ADDENDUM NO. 1 TO THE BIDDING DOCUMENTS DATE: May 6, 2016 HVAC SERVICE AND MAINTENANCE Saint Clair County MidAmerica Saint Louis Airport BIDS CLOSE: May 12, 2016, at 2:30 p.m., Local Time TO ALL BIDDERS
More informationMIDLAND COLLEGE SYLLABUS DEMR 1323 AUTOMOTIVE HEATING AND AIR CONDITIONING 2-4
Course Description: Text, References and Supplies: Course Goals/Objectives: Theory of automotive air conditioning and heating systems. Emphasis on the basic refrigeration cycle and diagnosis and repair
More informationAIR CONDITIONING EFFICIENCY F8 Energy eco-efficiency opportunities in Queensland Foundries
AIR CONDITIONING EFFICIENCY F8 Energy eco-efficiency opportunities in Queensland Foundries Hot tips and cool ideas to save energy and money! Air conditioning units or systems are often used by foundries
More informationConsortiwm Awdurdodau Lleol Cymru Consortium Local Authorities Wales
Consortiwm Awdurdodau Lleol Cymru Consortium Local Authorities Wales SPECIFICATION FOR BOILER SERVICING MAINTENANCE Maintenance Module 11 March 2012 issue This document has been compiled by the Engineering
More informationBC & BCH SERIES INDOOR / OUTDOOR INSTALLATION
Air Conditioning Central Heating & Cooling BC & BCH SERIES INDOOR / OUTDOOR INSTALLATION INSTALLATION AND SERVICE MANUAL 2 PROJECT: ADDRESS: MODEL: SERIAL NUMBER: INSTALLER: ADDRESS: PHONE NUMBER: INSTALLATION
More informationHEATER, AIR CONDITIONING AND VENTILATION
55-1 GROUP 55 HEATER, AIR CONDITIONING AND VENTILATION CONTENTS GENERAL DESCRIPTION 55-2 HEATER AND AIR CONDITIONING SYSTEM 55-4 HEATER CONTROL 55-6 A/C-ECU 55-7 A/C COMPRESSOR 55-9 CONDENSER 55-9 DUCT
More informationhore PRODUCT CATALOGUE nd Offsh arine an ms for Ma & Refrig AUTONOMOUS AIR CONDITIONERS HV VAC &
hore nd Offsh arine an ms for Ma geration System & Refrig HV VAC & PRODUCT CATALOGUE AUTONOMOUS AIR CONDITIONERS O ! "# $ % & " ' (! ) * +,+( -../01..2 PRODUCT CATALOGUE 72-17 AUTONOMOUS AIR CONDITIONERS
More informationSECTION 15732 AIR CONDITIONING UNIT
SECTION 15732 AIR CONDITIONING UNIT PART 1 GENERAL 1.01 SUMMARY A. Section includes: 1. Packaged, split system air conditioning unit No. 1. 1.02 REFERENCES A. Air-Conditioning, Heating, and Refrigeration
More informationHeating Ventilation and Air Conditioning Diagnostics for Single Family Homes
Heating Ventilation and Air Conditioning Diagnostics for Single Family Homes Vincent Pedalino FSL Home Improvements Phoenix, AZ 1 HVAC Basics Ways to improve the performance of existing air conditioning
More informationSWIMMING POOL HEAT PUMP
SWIMMING POOL HEAT PUMP Installation & User Manual Model HP40B HP50B HP65B Hayward Pool Products Canada, Inc. T: 1-888-238-7665 www.haywardpool.ca CONTENT I. Application 4 II. Features 4 III. Technical
More informationPC1130 Electric Air Compressor
Senco Products Inc. 8485 Broadwell Road Cincinnati, Ohio 45244 PC1130 Electric Air Compressor Operating Instructions 2006 by Senco Products, Inc. Warnings for the safe use of this tool are included in
More informationSplit Air Conditioner
Split nditioner plit itsplit ir onditioner Split Split Split Split Split User s WNER'S 'S ER'S For s: AWI/AWO-21HPR1 Delta AWI/AWO-25HPR1 Delta AWI/AWO-32HPR1 Delta AWI/AWO-53HPR1 Delta AWI/AWO-65HPR1
More informationENGINE COOLING SYSTEM
ENGINE COOLING SYSTEM 1988 Toyota Celica 1987-88 TOYOTA Engine Cooling Systems Celica DESCRIPTION The basic liquid cooling system consists of a radiator, water pump, thermostat, cooling fan, pressure cap,
More informationFailure code manual. content
Failure code manual content 一 wall split AC series 2 二 floor standing AC series. 4 三 portable AC series.. 5 四 dehumidifer 6 五 DC inverter single split series...7 六 DC inverter multi-split series 10 1 一
More informationUSER S, MAINTENANCE and SERVICE INFORMATION MANUAL
CONTENTS SAFETY INFORMATION................ 2 FOR YOUR SAFETY....................... 2 SYSTEM OPERATION.................. 2 THERMOSTATS........................... 2 INTERMITTENT IGNITION DEVICE...........
More informationSTATEMENT OF WORK FOR MAINTENANCE OF AIR CONDITIONERS
STATEMENT OF WORK FOR MAINTENANCE OF AIR CONDITIONERS 1) SCOPE: The successful bidder (Contractor) is responsible to perform periodic routine preventive maintenance and repair of all accepted air conditioner
More informationCompetency Framework for Marine Engineer Class 6. Competency Framework for Marine Engineer Class 6
Table of Contents (MEC 6)... 1 Function: Operate Vessel Machinery and Systems... 1 Diesel engines.... 1 Operational procedures.... 3 Operate and monitor a vessel s engines and auxiliary equipment.... 4
More informationHeat Pump Water Heater IOM Manual
Heat Pump Water Heater IOM Manual Installation Operation & Maintenance This manual is intended as an aid to qualified service personnel for proper installation, operation and maintenance of the heat pump
More informationRESIDENTIAL HEATING OIL SERVICE CONTRACT ANNUAL COST $276.00
RESIDENTIAL HEATING OIL SERVICE CONTRACT This service contract covers all routine service and maintenance of your residential oil fired furnace or boiler. In addition this contract covers all service calls
More informationFOXAIR 60/50 ALL MODELS
FOXAIR 60/50 ALL MODELS OPERATION AND SERVICE MANUAL UNIT WEIGHT - ALL MODELS APPROX. 300 POUNDS FOXTRONICS, INC. 38 L x 28 W x 24 H Love Field-Dallas TX MADE IN THE USA 3448 West Mockingbird Lane Dallas,
More informationUSER INSTRUCTIONS FOR GET PORTABLE 12k BTU AIR CONDITIONER MODEL No. GPACU12HR
USER INSTRUCTIONS FOR GET PORTABLE 12k BTU AIR CONDITIONER MODEL No. GPACU12HR CONTENTS Introduction Safety Notes Identification of parts Installation instructions Operation instructions Maintenance Troubleshooting
More informationINSPECTION, TESTING AND MAINTENANCE OF FIRE PROTECTION SYSTEMS AND EQUIPMENT
CITY OF SPRING LAKE PARK Code Enforcement Department 1301 81 st Avenue NE Spring Lake Park MN 55432 Business Phone 763-784-6491 Fax 763-792-7257 INSPECTION, TESTING AND MAINTENANCE OF FIRE PROTECTION SYSTEMS
More information1.2 Refrigerant Equipment. General
Part 1 General 1.1 Summary.1 Unless otherwise indicated, follow the standards below when specifying heating, ventilation and air conditioning (HVAC) work. These standards are not intended to restrict or
More informationPC1131 Electric Air Compressor
Senco Products Inc. 8485 Broadwell Road Cincinnati, Ohio 45244 PC1131 Electric Air Compressor Operating Instructions 2006 by Senco Products, Inc. Warnings for the safe use of this tool are included in
More informationSix Monthly Servicing of Fire Extinguisher on Commercial Vessels.
Marine Safety Notice to Industry Number: 34 Date of Issue: 17 January 2012 Six Monthly Servicing of Fire Extinguisher on Commercial Vessels. This Notice to Industry is to clarify the requirements for the
More informationUSF St. Petersburg Operations & Maintenance of Facilities Preventative Maintenance Guide
USF St. Petersburg Operations & Maintenance of Facilities Preventative Maintenance Guide GUIDE EQUIPMENT TYPE & TASKS FREQUENCY A-1 Air Dryer 1. Lubricate valves and replace packing, if necessary 2. Check
More informationModel: 400E-2M. Bermad Electrically Controlled Deluge Valve with Easy Lock Manual Reset. Installation Operation Maintenance. Application Engineering
Model: 400E-2M Bermad Electrically Controlled Deluge Valve with Easy Lock Manual Reset Installation Operation Maintenance Application Engineering BERMAD 1. Safety First BERMAD believes that the safety
More informationHome Maintenance Checklist
Regular maintenance keeps your home functioning efficiently and safely and helps protect its value. We're happy to offer this checklist of ongoing and seasonal maintenance steps to help you safeguard your
More informationHow to Maintain an Air Conditioner
How to Maintain an Air Conditioner by Fix-It Club How to Troubleshoot a Central Air Conditioning System Publications International, Ltd. Central air conditioners are made up of two separate components:
More informationUHIR Series. Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater. Owner s Manual
UHIR Series Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater Owner s Manual This manual covers installation, maintenance and repair parts. Read carefully before attempting to
More informationOperating Instructions Split System Air Conditioner
Operating Instructions Split System Air Conditioner Model No. Indoor Unit Type Indoor Unit Type Nominal Capacity 26 36 F2 Low Silhouette Ducted S-26PF2U6 S-36PF2U6 Connectable outdoor unit lineup This
More informationBERMAD Fire Protection
Model: 400E-2M BERMAD Electrically Controlled Deluge Valve with Easy Lock Manual Reset Installation Operation Maintenance Safety First BERMAD believes that the safety of personnel working with and around
More informationESPD8-301R MODEL ESP-D FAN COIL UNIT TROUBLESHOOTING GUIDE
ESPD8-301R MODEL ESP-D FAN COIL UNIT TROUBLESHOOTING GUIDE Protected by one or more of the following U.S. Patents (3,507,354; 3,575,234; 3,596,936; 3,605,797; 3,685,329; 4,045,977; 4,698,982; 926,673 and
More informationElements Elements describe the essential outcomes.
AURETU005 Application Competency Field Unit Sector Elements Elements describe the essential outcomes. Retrofit and modify air conditioning and HVAC systems This unit describes the performance outcomes
More information10 tips for getting more reliability from your air-conditioning system [reliability]
10 tips for getting more reliability from your air-conditioning system [reliability] A guide for installers, specifiers, contractors and architects February 2010 10 tips for getting more reliability from
More informationBERMAD Fire Protection
400E-2M/700E-2M IOM Bermad Electrically Controlled Deluge Valve with EasyLock Manual Reset Model: 400E-2M/700E-2M INSTALLATION OPERATION MAINTENANCE Application Engineering BERMAD 400E-2M/700E-2M Bermad
More informationPreventative Maintenance Plan. Guide. The Simple, Smart Way To Properly Care For Home Systems And Appliances.
Preventative Maintenance Plan Guide The Simple, Smart Way To Properly Care For Home Systems And Appliances. Protect. Prevent. Preserve. Prolong. What AHS Preventative Maintenance Plans Can Do For Your
More informationSECTION 23 05 12 GENERAL PROVISIONS FOR HVAC WORK
SECTION 23 05 12 GENERAL PROVISIONS FOR HVAC WORK 1 GENERAL 1.1 GENERAL REQUIREMENTS A. This Section is coordinated with and complementary to the General Conditions and Supplementary General Conditions
More informationCircuit breaker panel. Power supply for condensing unit. Power supply for furnace. Air handler (Furnace)
UNIT OBJECTIVES Describe the concept of year-round air conditioning List three typical year-round air conditioning system types List the five ways to condition the air Determine airflow for a cooling system
More informationChapter 7 Hydraulic System Troubleshooting
Chapter 7 Hydraulic System Troubleshooting General The following troubleshooting information is provided as a general guide to identify, locate and correct problems that may be experienced with the hydraulic
More informationOil and Coolant Circulating Heating System. Model - OCSM
Oil and Coolant Circulating Heating System Model - OCSM Installation & Operation Manual 216280-000 REV 2 Identifying Your System The HOTSTART heating system is designed to heat fluids for use in marine
More informationImportant Ontario Fire Code Information for Building Owners in the City of Windsor
Important Ontario Fire Code Information for Building Owners in the City of Windsor This information is intended to be used a reference only. For a complete listing consult the Ontario Fire Code or contact
More informationHeater and Air Conditioner, Blend Air System, Troubleshooting 83.06
A/C Performance Diagnosis Problem Warm Airflow When the Air Conditioner is On, A/C Not Working, or Poor A/C Performance (dash outlet temperature is too high) Problem Warm Airflow When the Air Conditioner
More informationSELF-INSPECTION PROGRAM FOR FIRE PROTECTION EQUIPMENT
SELF-INSPECTION PROGRAM FOR FIRE PROTECTION EQUIPMENT INTRODUCTION No matter how reliable fire protection equipment may seem, periodic maintenance is needed to ensure proper operation. Fire protection
More informationAABC Specifications for Testing and Balancing HVAC Systems
AABC Specifications for Testing and Balancing HVAC Systems The Associated Air Balance Council (AABC) Total System Balancing Specifications for HVAC Testing, Balancing and Performance Verification TOTAL
More informationMAINTENANCE INSTRUCTIONS. Thermia Robust heat pump
MAINTENANCE INSTRUCTIONS Thermia Robust heat pump 9 6 8 0-5 4 7 4 5 0 0 1 R e v. 3 Table of contents 1 Important information.................. 2 1.1 Product description....................... 2 1.2 General................................
More informationSECTION 11 78 13 MORTUARY REFRIGERATORS
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 11 78 13 MORTUARY REFRIGERATORS SPEC WRITER NOTE: Delete between //---// if not applicable to project. Also delete any other item or paragraph not applicable in
More informationSYSTEM Inverter Air Conditioners
OPERATION MANUAL SYSTEM Inverter Air Conditioners MODEL Ceiling Suspended type FXHQ12MVJU FXHQ24MVJU FXHQ36MVJU Read these instructions carefully before installation. Keep this manual in a handy place
More informationUSER S MANUAL HSC-24A
AIRREX AIR CONDITIONER USER S MANUAL HSC-24A Thank you for purchasing an AIRREX AIR CONDITIONER. BEFORE operation please read this user s manual carefully. Keep this manual readily available. It is ESSENTIAL
More informationMP-4000 Alarm List (Software version 2.4.3 or later)
Service Bulletin SUBJECT: MP4000 Alarm s BULLETIN: C 100 DATE: June 19, 2013 ALARM LIST Where it is possible the alarm number is kept the same as for MP-3000. MP-3000 holds alarm number from 0 to 127.
More informationINVOICE. DATE: May 11, 2005. DESCRIPTION Inspection and report on a property located at OF SERVICES: Perfect Street, Sarasota, Fl.
INVOICE DATE: May 11, 2005 CLIENT: The Buyer DESCRIPTION Inspection and report on a property located at OF SERVICES: Perfect Street, Sarasota, Fl. TOTAL FEE: $ See Schedule Tom Villani Hallmark Inspection
More informationELECTRIC/DIESEL FIRE PUMP CHECK LIST
BUILDING NAME: DESIGNER: SCO REPRESENTATIVE: PUMP MANUF.: LOCATION: INSTALLER: DATE: OWNER NAME: INSTALLATION Certificate for flushing and hydrostatic test furnished Piping been hydrostatically tested
More informationNORSOK STANDARD H-001 Rev. 4, Nov. 2001. Heating, ventilation and air-conditioning
NORSOK STANDARD H-001 Rev. 4, Nov. 2001 Heating, ventilation and air-conditioning This NORSOK standard is developed by NTS with broad industry participation. Please note that whilst every effort has been
More informationPart 3 Ancillary technologies. Chapter 3.2. Mechanical ventilation with heat recovery
Part 3 Ancillary technologies Chapter CONTENTS SCOPE Clause Page DESIGN Design standards D1 1 Statutory requirements D2 1 System design D3 1 Building integration D4 2 Noise D5 2 Access and controls D6
More informationPump Maintenance - Repair
Pump Maintenance - Repair Brian Trombly Mo Droppers Cummins Bridgeway, Gaylord, Mi The basic centrifugal pump consists of two main elements: 1. The rotating element which includes an impeller and a shaft.
More informationTHERMO KING TRUCK & TRAILER UNIT ALARM CODES THIS DOCUMENT SHOWS ALL CURRENT ALARM CODES FOR THERMO KING TRUCK AND TRAILER UNITS.
THERMO KING TRUCK & TRAILER UNIT ALARM CODES THIS DOCUMENT SHOWS ALL CURRENT ALARM CODES FOR THERMO KING TRUCK AND TRAILER UNITS. NOT ALL CODES ARE POSSIBLE ON ANY INDIVIDUAL UNIT. IF THE ALARM APPLIES
More informationAustralian/New Zealand Standard
Australian/New Zealand Standard The use of ventilation and air conditioning in buildings - Part 1: Fire and smoke control in buildings UPDATED AS/NZS 1668.1:2015 What is the scope of this Standard? The
More informationAcumen Enterprises, Inc.
Hourly rates Discount w/o Rebate Electrician $78.00 10% $70.20 $70.73 HVAC Technician $78.00 10% $70.20 $70.73 Insulator $42.00 10% $37.80 $38.08 Sheet Metal Worker $74.00 10% $66.60 $67.10 Plumber/Pipefitter
More information