B4-102 CROSS SOUND CABLE PROJECT SECOND GENERATION VSC TECHNOLOGY FOR HVDC

Size: px
Start display at page:

Download "B4-102 CROSS SOUND CABLE PROJECT SECOND GENERATION VSC TECHNOLOGY FOR HVDC"

Transcription

1 21, rue d'artois, F Paris B4-102 Session 2004 CIGRÉ CROSS SOUND CABLE PROJECT SECOND GENERATION VSC TECHNOLOGY FOR HVDC B. D. RAILING G. MOREAU L. RONSTRÖM* J. J. MILLER P. BARD J. LINDBERG P. STECKLEY TransÉnergieUS Hydro-Québec ABB Power Technologies (USA) (Canada) (Sweden) 1 INTRODUCTION The Cross Sound Cable Project (CSC) is a HVDC transmission system that interconnects the electricity market regions of New England and New York as illustrated in Figure 1. TransÉnergieUS Ltd. developed the CSC project, the first merchant transmission project in operation in the USA. CSC is a bi-directional 330 MW transmission system consisting of two voltage source AC/DC converter (VSC) stations connected by a pair of 40-kilometer DC submarine cables. Transmission capacity over the CSC project was offered to market participants through an open season process and a firm capacity purchase agreement was executed with the successful bidder. A key feature of the HVDC technology in CSC is the ability to precisely control power transfers in accordance with scheduled transactions by those who have purchased rights to its capacity. Additional benefits of the selected HVDC technology include: Figure 1 Geographical location of Cross Sound Cable Reactive power/ac voltage control at each converter to support the connected AC networks Converter stations have a compact layout with the majority of equipment housed within a typical warehouse-style building Use of DC cables with solid dielectric insulation (contains no oil) Power transfer is continuously controllable from 0 MW to 330 MW delivered in both directions without the need for equipment switching Modular design allows for comprehensive factory testing which leads to a short field-testing and commissioning program This paper describes the second-generation VSC technology employed in the CSC project, presents the main circuit one-line diagram and control system features, and discusses the commissioning and operational experience. *leif.ronstrom@se.abb.com

2 2 GENERAL SYSTEM DESCRIPTION 2.1 AC Networks As depicted in Figures 1 and 2, CSC links the AC networks of Connecticut and Long Island, New York. These AC networks are contained within two separately operated control regions in the northeast United States with independent energy and capacity markets. In Connecticut, CSC s northern converter station interconnects with the AC transmission grid via a short tap to the existing 345 kv overhead transmission line that extends from the nearby 115 kv East Shore to the 345 kv Scovill Rock substation. At East Shore a pair of autotransformers step the 115 kv voltage up to 345 kv. The Scovill Rock substation facilities include two additional 345 kv network circuits and a generator connection. This interconnection location was selected for CSC as it offers access to the 345 kv bulk transmission network in Connecticut and provides for a short HVDC cable section to the submarine cable landfall in New Haven Harbor. The CSC converter station on Long Island connects to the 138 kv bulk AC transmission system at the Shoreham substation. Four 138 kv transmission lines emanate from the Shoreham substation providing adequate transmission capacity to support rated power transfer over CSC. Again, this location was selected as it provides easy access to both the existing AC network and the HVDC submarine cable landfall. No new AC transmission beyond the short direct connection ties were required to interconnect CSC to the existing AC networks. Detail of the VSC interconnection breaker arrangement can be found in Figure 5. Power generation plants are located in close proximity to both converter stations. In Connecticut, a single generation unit rated at 511 MVA connects into the 115 kv substation at East Figure 2 Cross Sound Cable Interconnections Shore and a unit rated 461 MVA is connected into the Scovill Rock 345 kv substation. On Long Island, three 99 MVA generators are connected at the Wading River 138 kv substation, which is a short distance from Shoreham. Two GT units of 56 MVA and 17.5 MVA also supply the Shoreham 69 kv substation. 2.2 DC Transmission System Converter Equipment The first commercial HVDC transmission projects using VSC were rated up to 60 MW. They used two-level bridges and solid dielectric DC cables designed for ±80 kv DC [1,6]. For CSC, a single three-phase VSC, capable of 346 MVA was chosen. The converter is a 3-level bridge, using IGBT positions in place of diodes for the neutral-point clamping. The IGBT positions are based on a new generation IGBT and diode pack, divided into sub-modules to enable different current ratings using the same physical dimensions. The Figure 3 The Shoreham Converter Station converter DC voltage has been raised to ±150 kv, but the

3 selected PWM (Pulse Width Modulation) pattern switches the valves on and off only between + or 150 kv and 0 V, thus keeping the well-proven switching amplitude (+80 to 80 kv) and the number of IGBT positions in a valve from the previous 2-level VSC-based transmission projects. The switching frequency is 1260 Hz (21 st harmonic), which is half the frequency of the previous 2-level VSC projects. The selection of these parameters gives only half of the losses of an equally large two-level converter, and still no increase of harmonics. Each converter station can operate in any point within the PQ diagram shown in Figure 4, since active and reactive power are controlled completely independent. The IGBT valves are cooled with a glycol/water mixture and installed in modular valve housings. One phase is built up of four housings, containing valves and high-density DC capacitors. The full three-phase bridge uses twelve housings. The IGBT valve assembly has been modified so that opening of the cooling water circuit at replacement of an individual IGBT is no longer necessary. Separate housings for the control equipment and for the cooling water treatment and pumps complete the converter, entirely located inside the building seen in Figure 3. Air core, water cooled phase reactors (L4) connect the converter to the 200 kv AC filter bus, where three shunt filters, tuned to the 21 st, 41 st, and 25 th harmonics are connected via breakers, equipped with synchronous closing functionality. The power line carrier (PLC) filtering equipment (components L1, L2, L3, C1, C2 C3 and C4) is installed on the secondary side of the converter transformer. Figure 4 Steady-state PQ diagram Three standard single-phase AC transformers are used to match the AC network voltages to the converter AC voltage. A spare unit is provided at each converter station. The incoming breaker has associated pre-insertion resistors to minimize the transients at converter energisation. A 3 rd harmonic filter is installed on the DC side to remove the component due to the 3 rd harmonic modulation technique implemented in the controls (more information in the section below). 345 or 138 kv Shoreham only UDC_P1 IDC_P kv Q1 U_PCC U_AC I_VSC 3 x 120 MVA Q2 L1 L2 L3 200 kv L4 C1 C2 C3 C4 Auxiliary power rd 3 harmonic filter -150 kv Converter Building st th Mvar st Enclosure UDC_P2 IDC_P2 Figure 5 Converter Station Single-line Diagram Control and Protection The control and protection system is built up in the same way as in the DirectLink HVDC project. See the description in reference [1]. In CSC, telecommunication is added between the stations to enable fast runback for specific network disturbances. To ensure reliability, the control system is duplicated with one control system active and the other in standby. Each control system consists of pole control and protection, and valve control units (VCU).

4 The latter receives the on/off switching signals from the pole control and executes the switching orders to the valves. The main objective of the control system is to control the transferred active and reactive power independently. The ability to control reactive power may be used either to keep the reactive power exchange or the AC voltage constant at the point of common coupling (PCC), independent of the DC voltage or active power control modes. By using PWM the resulting converter voltage at the converter terminals is achieved by switching the valves according to a modulation scheme determined by several factors, such as calculated reference voltage, available DC voltage, harmonic generation and currents in the valves. The pole control consists of a state feedback controller for the converter current control. The active and reactive currents are controlled independently. The controller is synchronized to the fundamental network voltage using a phase-locked loop (PLL). The DC voltage, active power, reactive power and AC voltage controls calculate the reference currents to the converter current control. In steady state, one converter must operate in DC voltage control and the other in active power control. u dc+ X i v X t i t PCC DC Filter u f B u pcc VCU p ref q ref u ac ref u dcu dc y ref Pole Control converter ac current control APC, RPC & ACVC DCVC PLL i v u f i t u pcc Figure 6 Converter together with the pole controller; the latter consists of the converter AC current control, DC voltage control (DCVC), active power control (APC), reactive power control (RPC) and the AC voltage control (ACVC). The control is synchronized to the network fundamental voltage using a phase locked loop, PLL. The converter protections are integrated in the same duplicated main computer system, but operate independently of the control systems. All primary measuring units, cabling and computer boards are separated between control and protection, thereby ensuring that a fault in one control measurement device does not affect the protection system. Third-harmonic modulation. A zero sequence third-harmonic component is added to the sinusoidal reference voltage to reduce the peak AC converter voltage in order that, with the same DC voltage, an approximately 15 % increased AC-side fundamental-frequency voltage is available from the VSC. DC voltage balance control. The three-level converter is mid-point grounded and balancing of the DC pole voltages is needed to prevent any ground current circulation. Certain space vectors are used in the modulation to balance the bridge. Low order harmonic suppression. Minor non-linearities in the valve switching create low-order harmonics. To prevent their amplification, a special controller was designed to act on the PWM pattern in order to minimize the low order (5 th and 7 th ) harmonic currents at the PCC. The end result is that the PCC voltage levels at these harmonics are hardly affected by converter operation and there is very little contribution from these frequencies to the IT product.

5 AC voltage control. This control feature includes a slope (droop), similar to the voltage regulators on generators. The reactive power capability is dependent on the active power transfer, as shown in Figure 4. A strong network may limit the possibility of reaching the AC voltage set point due to the reactive power limit. The use of a slope mitigates this issue and has the additional advantage of avoiding hunting between the converter AC voltage control and similar controls on nearby generators. Sub-synchronous damping control. To ensure that sub-synchronous oscillations are not amplified by the converter control, a sub-synchronous damping controller (SSDC) is used. The angular frequency deviation given by a PLL is band-pass filtered to extract the sensitive frequency range. This signal is used in the SSDC and the limited output signal is added to the current orders. The SSDC is an integral part of the control system and cannot be turned off. It is active in the entire sensitive frequency range DC transmission cables, installation and rating A pair of 40 km long, DC transmission cables rated ±150 kv and 1200 ADC steady state, were designed [3] for both land and submarine installation. These cables are solid dielectric with a 1300 mm 2 copper conductor. The submarine cable uses a lead alloy metal sheath, PE protective sheath, galvanized steel armor wires, and an outer protective layer of polypropylene yarn bonded with bitumen. A specialized ship for submarine cable installation was used to transport and install the pair of DC transmission cables and a 192-core fiber optic cable. Installation of the submarine cable system was performed using a hydraulic jet plow during the last two weeks of May The submarine cable system was buried to a minimum depth of approximately 2.0 m below the seabed. Approximately 600 m of the cable system was installed in a horizontal direct drill (HDD) pipe below shellfish beds. A small water-cooling system is used to cool the cable system in the HDD. 3 COMMISSIONING Installation of the converter stations was completed during July The commissioning program was modified to achieve reliable transmission to support the Long Island and New England utilities during the remainder of the summer 2002 peak period. Additional commissioning personnel were assigned by the manufacturer and owner to complete the critical terminal and transmission testing as soon as possible. It was decided to defer a portion of the performance tests until after the summer 2002 period with the understanding that the converter stations would be staffed with commissioning personnel, and data acquisition equipment would be used to constantly monitor the critical AC and DC side parameters. The critical terminal and transmission commissioning tests were completed by August 8, Additional testing periods were scheduled as needed between Aug 2002 and Sept 2003 to complete the performance measurements. 4 STEADY STATE AND TRANSIENT PERFORMANCE 4.1 AC Side Harmonics For both converter stations, a maximum increase of 1% was allowed for individual voltage harmonics between the 2 nd and the 85 th. Total harmonic distortion (THD) was limited to 2% in New Haven and 3% in Shoreham. Finally a limit was set at 35 for the telephone interference factor (TIF) in New Haven and at 12 ka rms for the IT product in Shoreham. The limits for individual harmonic distortion and THD were easily met at both stations. As seen in the top curve of Figure 7, only low order harmonics are present in the voltage spectrum. However, they are not caused by converter operation, as they are also present when the converters are blocked. Recorded TIF stayed around 20 at New Haven with the converters in operation. The requirements for the IT product were harder to meet at Shoreham because of the presence of important voltage components at the 5 th and 7 th harmonics resulting in an IT between 14 and 20 ka rms. Low-order harmonic controller settings were subsequently optimized through numerous field tests to finally reach an IT product of 9.5 to 10 ka rms. The 5 th and 7 th harmonic currents are now kept below 2 A rms as seen in the second curve of Figure 7.

6 4.2 DC Side Harmonics With the land portion of the DC cables being very short, there is little exposure for telephone interference and therefore no strict limits were imposed on the DC side harmonics. For information purposes, they were nevertheless measured during commissioning. The HV conductor current (IDC_P1 and P2) was made available for recording via AC/DC current transducers while the total DC cable current information came from Rogowski coils installed around the cables. It can be appreciated from the top curve of Figure 8 that the converter DC side current has a major component at the 2 nd harmonic with other important odd and even triplen components up to the 21 st. The bottom curve with a log scale indicates that the components are greatly reduced due to the shielding provided by the DC cable screen. 4.3 Conducted and Radiated Noise Conducted noise is controlled by the PLC filtering equipment installed on the secondary side of the power transformer. Between 50 and 300 khz, the maximum level for the voltage on the primary side of the transformer was specified at 8.9 mv rms in a 1 khz bandwidth. The level was lowered by 6 db between 300 and 500 khz. These levels were not exceeded at either converter station. The specification asked for a maximum radiated noise level of 100 µv/m between 500 khz and 1 GHz at a distance of 460 m from any energized equipment. This level was not exceeded at either converter station. 4.4 Audible Sound The station design was done with careful attention to audible noise requirements. Both sites are located within industrial areas (70 dba limit at property line), but the audible noise impact was to be kept lower in certain directions. The stations were arranged with respect to those directions. The station building has been used as an acoustical screen for sound from the cooling fans, PLC filters and power transformers. The AC and DC CSC - Original Estim ated vs. Actual Loss Curve filters, IGBT valves and cooling 24 pumps are located inside the station Estimated Losses 20 building. Hence, the acoustical Actual Losses impact from the converter stations 16 has been minimized and the local 12 noise limits have not been exceeded. 4.5 Losses Actual CSC transmission system losses were measured during commissioning of the project. All converter station auxiliary power was supplied by the CSC power Losses (MW) Inve rt er Output Powe r (M W) Figure 9 Total Transmission System Losses, including station and cable losses

7 transformer tertiary windings during measurements. The cooling systems for the IGBT valves, phase reactors, building areas and power transformers were operated at maximum to simulate cooling load at 40ºC dry-bulb air temperature. The actual loss curve shown in Figure 9 was created using the actual MW values from the 345 kv and 138 kv utility revenue meters at the PCC at each converter. As seen in Figure 9, actual measured losses were found to be lower than the initially estimated losses, especially at high MW power transfer. The three-level bridge valve design, higher currents and lower switching frequency used in CSC offered superior power loss performance than anticipated as compared to the two-level bridge design used in earlier VSC projects such as DirectLink [1]. 4.6 Behavior during transients and faults Special care has been taken to minimize the transients for the two frequent converter operations consisting in converter energization and converter deblocking. This was achieved via pre-insertion resistors associated to the incoming breaker, AC filter circuit breakers equipped with a synchronous closing function and a staggered sequence for the converter deblocking. For more information, the reader can consult Sections 5.1 and 5.2 of reference [4], which is related to a similar project in Australia, the Murraylink project. The CSC converters are continuously operated in AC voltage control and this is quite appreciated by the neighboring utilities. CSC now takes care easily of the steady state voltage regulation at the connecting stations. It is also improving the dynamic stability as seen in Figures 10 and 11. Figure 10 corresponds to multiple AC faults during a severe thunderstorm on Long Island. The converter did not only exhibit its robustness in riding through the disturbances but also supported the voltage up to its reactive power limit of 125 Mvar while keeping the active power fairly constant. A similar behavior is observed in Figure 11 for an AC fault in Connecticut. 5 OPERATIONAL EXPERIENCE 5.1 Restoration after the August blackout Following the blackout of the northeastern portion of North America on August 14, 2003, CSC was instrumental in restoring electric power to customers on Long Island. CSC was the first transmission link to Long Island that was put into service after the blackout. The link transported 330 MW to the island, enough power to restore electric service to over 330,000 homes. Furthermore, CSC s AC voltage control feature proved valuable by stabilizing AC system voltage in Connecticut and on Long Island during and subsequent to the network restoration (refer to example presented in Figure 10). 5.2 Sub-synchronous torsional interaction Sub-synchronous torsional interaction (SSTI) may be described as interaction of the active control systems of transmission equipment such as a FACTs device or HVDC exciting the torsional modes of

8 a turbine generator shaft. There is a potential of SSTI risk only if the AC network results in a high degree of coupling between the HVDC converter and generator. The frequency range of concern for the torsional modes is about 7 Hz to 30 Hz. To prevent adverse interaction, even for situations with a high degree of unit coupling, the pole control at the HVDC converters includes a sub-synchronous damping controller (SSDC) [5]. The manufacturer s experience from delivered HVDC installations demonstrates that adverse SSTI can be avoided by proper design practices. A method of screening for units that may have a high potential for coupling or interaction with the HVDC facility is assessment of a Unit Interaction Factor (UIF) [2]. UIF screening of generation near the HVDC converters was performed for various AC network configurations to determine if any units may be considered a high SSTI risk. To ensure proper control system design, suspect units were then subject to more detailed analysis which modeled the actual HVDC control system and SSDC under various modes of HVDC converter operation and determined the small-signal electrical damping torque of the turbine rotor. Studies demonstrated that all HVDC control modes would contribute positive damping over the frequency range of concern. However, with consideration for CSC being the first application of VSC based technology in North America, some local generation owners elected to have torsional stress monitoring and relay systems installed as back-up protection. There has been no occurrence of any SSTI phenomenon in the operational experience to date. 5.3 Availability The Cross Sound Cable availability was approximately 97.5% for the period ending December 31, Punch list and final adjustment work was completed during this time period. The most serious forced outage lasted for 14.6 hours due to a fault in the IGBT valve control at the Shoreham converter station. 6 CONCLUSION New design concepts were used to expand the existing VSC technology from the 60 MW, 2-level, ±80 kv range to the 330 MW, 3-level, ±150 kv range. This was made possible by the use of enhanced control and protection systems, larger power electronic components and new arrangements of the modular converter design. DC transmission cables using solid dielectric insulation were developed for the ±150 kv range for both land and submarine cable applications. Installation and commissioning of the converter stations and DC transmission cables was completed approximately 24 months after contract signing. All performance criteria for power quality, transfer capability, audible sound and losses were met. 7 REFERENCES [1] B. D. Railing, J. J. Miller, G. Moreau, J. Wasborg, Y. Jiang-Häfner, D. Stanley, The DirectLink VSC-based HVDC Project and its Commissioning, [CIGRÉ 2002, Paper no ]. [2] High-Voltage Direct Current Handbook, First Edition, Electric Power Research Institute, TR s, [3] A. Ericsson, M. Jeroense, J. Miller, L. Palmqvist, B. Railing, P. Riffon: HVDC Light Cable Systems The Latest Projects, [Nordic Insulation Symposium, Tampere, Finland, 2003]. [4] I. Mattsson, A. Ericsson, B. D. Railing, J. J. Miller, B. Williams, G. Moreau, C. D. Clarke, Murraylink, the Longest Underground HVDC Cable in the World, [CIGRÉ Paris August 2004]. [5] Y. Jiang-Häfner, H. Duchen, K. Linden, M.Hyttinen, P. F. de Toledo, T. Tulkiewicz, A. K. Skytt, H. Björklund, Improvement of subsynchronous torsional damping using VSC HVDC, [PowerCon 2002 Conference, Kunming, China 2002]. [6] U. Axelsson, A. Holm, C. Liljegren, K. Eriksson, L. Weimers, Gotland HVDC Light Transmission Worlds First Commercial Small Scale DC Transmission, [CIRED Conference, Nice, France, 1999].

HVDC Light, a tool for electric power transmission to distant loads

HVDC Light, a tool for electric power transmission to distant loads Presented at VI Sepope Conference, Salvador, Brazil, May 1998 HVDC Light, a tool for electric power transmission to distant loads by Gunnar Asplund Kjell Eriksson* Ove Tollerz ABB Power Systems AB ABB

More information

HVDC Light and development of Voltage Source Converters

HVDC Light and development of Voltage Source Converters 1 HVDC Light and development of Voltage Source Converters K. Eriksson, ABB Utilities Abstract- On March 10, 1997 was transmitted on the 3 MW HVDC Light transmission between Hellsjön and Grängesberg in

More information

DC TRANSMISSION BASED ON VOLTAGE SOURCE CONVERTERS

DC TRANSMISSION BASED ON VOLTAGE SOURCE CONVERTERS DC TRANSMISSION BASED ON VOLTAGE SOURCE CONVERTERS by Gunnar Asplund, Kjell Eriksson, Hongbo Jiang, Johan Lindberg, Rolf Pålsson, Kjell Svensson ABB Power Systems AB Sweden SUMMARY Voltage Source Converters

More information

2012 San Francisco Colloquium

2012 San Francisco Colloquium 2012 San Francisco Colloquium http : //www.cigre.org HVDC and Power Electronic Systems for Overhead Line and Insulated Cable Applications B4-8 Trans Bay Cable A Breakthrough of VSC Multilevel Converters

More information

CO-ORDINATION OF PARALLEL AC-DC SYSTEMS FOR OPTIMUM PERFORMANCE

CO-ORDINATION OF PARALLEL AC-DC SYSTEMS FOR OPTIMUM PERFORMANCE CO-ORDINATION OF PARALLEL AC-DC SYSTEMS FOR OPTIMUM PERFORMANCE Ana Diez Castro & Rickard Ellström Ying Jiang Häfner Christer Liljegren Vattenfall Utveckling AB ABB Power Systems Gotlands Energiverk AB

More information

Introduction. Harmonics and IEEE 519 Page 1 of 19

Introduction. Harmonics and IEEE 519 Page 1 of 19 Introduction In an ideal power system, the voltage supplied to customer equipment, and the resulting load current are perfect sine waves. In practice, however, conditions are never ideal, so these waveforms

More information

Harmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies

Harmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies Soonwook Hong, Ph. D. Michael Zuercher Martinson Harmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies 1. Introduction PV inverters use semiconductor devices to transform the

More information

Introduction to The Trans Bay Cable Project

Introduction to The Trans Bay Cable Project Introduction to The Trans Bay Cable Project We ve come a long way 1 But thanks to the advances of two men and 2 The Battle of Currents 3 Utilities are able to choose the most effective and efficient means

More information

Topics. HVDC Fundamentals

Topics. HVDC Fundamentals Topics HVDC Fundamentals Conventional Converters Capacitor Commutated Converters Voltage Source Converters Reactive Power Requirements System Configurations Tapping Control basics High Power Transmission

More information

Product Data Bulletin

Product Data Bulletin Product Data Bulletin Power System Harmonics Causes and Effects of Variable Frequency Drives Relative to the IEEE 519-1992 Standard Raleigh, NC, U.S.A. INTRODUCTION This document describes power system

More information

EMTP STUDIES PERFORMED TO INSERT LONG AC CABLES IN THE FRENCH GRID

EMTP STUDIES PERFORMED TO INSERT LONG AC CABLES IN THE FRENCH GRID Tension (kv) Impedance (Ohms) EMTP STUDIES PERFORMED TO INSERT LONG AC CABLES IN THE FRENCH GRID frequency (Hz) Simon DESCHANVRES Yannick VERNAY RTE, CNER, Substations Department t (ms) EMTP-RV Users Group

More information

Electrical Considerations for HVDC Transmission Lines. Joe Mooney, PE

Electrical Considerations for HVDC Transmission Lines. Joe Mooney, PE Electrical Considerations for HVDC Transmission Lines Joe Mooney, PE POWER Engineers has met the standards and requirements of the Registered Continuing Education Program. Credit earned on completion of

More information

Smart Grid and Renewable Energy Grid Integration. Jian Sun, Professor and Director Department of ECSE & Center for Future Energy Systems

Smart Grid and Renewable Energy Grid Integration. Jian Sun, Professor and Director Department of ECSE & Center for Future Energy Systems Smart Grid and Renewable Energy Grid Integration Jian Sun, Professor and Director Department of ECSE & Center for Future Energy Systems 1 How Smart Can We Make This Grid? 2 Smart Grid Drivers Need to Use

More information

AMSC s Superconductor Cable Technologies for Electric Utilities

AMSC s Superconductor Cable Technologies for Electric Utilities International Workshop 2014 AMSC s Superconductor Cable Technologies for Electric Utilities Michael Ross, P.E. Managing Director of Superconductor Power Systems AMSC Corporate Facts Headquartered in MA,

More information

Brochure Introducing HVDC

Brochure Introducing HVDC Brochure Introducing HVDC ABB and HVDC The world s first commercial high-voltage direct current (HVDC) link, situated between the Swedish mainland and the island Gotland, was delivered by ABB already in

More information

HVDC Light Cables. Submarine and land power cables

HVDC Light Cables. Submarine and land power cables HV Light Cables Submarine and land s The HV Light s to offshore platform The light and robust HV Light s can be laid with very cost effecient methods HV Light System HV Light is a transmission system in

More information

Variable Frequency Drives - a Comparison of VSI versus LCI Systems

Variable Frequency Drives - a Comparison of VSI versus LCI Systems Variable Frequency Drives - a Comparison of VSI versus LCI Systems Introduction TMEIC is a leader in the innovative design and manufacture of large ac variable f requency drive systems. TMEIC has been

More information

HV Submarine Cable Systems Design, Testing and Installation

HV Submarine Cable Systems Design, Testing and Installation HV Submarine Cable Systems Design, Testing and Installation CIGRE Ireland Technical Seminar 6 th October 2010 Robert Donaghy Senior Consultant Engineer, ESB International Presentation Overview Applications

More information

POWER TRANSMISSION FROM OFFSHORE WIND FARMS

POWER TRANSMISSION FROM OFFSHORE WIND FARMS POWER TRNSMISSION FROM OFFSHORE WIND FRMS Thorsten Völker University of pplied Sciences Bremerhaven Germany BSTRCT The future for wind power generation in Germany is offshore wind energy. The preferred

More information

Magnus Callavik, ABB Power Systems, HVDC, 721 64 Västerås, Sweden Phone: +46(0)21323226. e-mail: magnus.callavik@se.abb.com

Magnus Callavik, ABB Power Systems, HVDC, 721 64 Västerås, Sweden Phone: +46(0)21323226. e-mail: magnus.callavik@se.abb.com HVDC GRIDS FOR OFFSHORE AND ONSHORE TRANSMISSION Magnus Callavik, ABB Power Systems, HVDC, 721 64 Västerås, Sweden Phone: +46(0)21323226. e-mail: magnus.callavik@se.abb.com SUMMARY The objective with this

More information

300 MW Variable Speed Drives for Pump-Storage Plant Application Goldisthal

300 MW Variable Speed Drives for Pump-Storage Plant Application Goldisthal May 24 MW Variable Speed Drives for Aurélie Bocquel APCG / 4BOC4 (MW-Goldisthal 1-5-24).PPT MW Variable Speed Drives for Content Major benefits of the cyclo-converter driven doubly-fed induction machines

More information

HVDC Technology for Large Scale Offshore Wind Connections

HVDC Technology for Large Scale Offshore Wind Connections HVDC Technology for Large Scale Offshore Wind Connections Nandan Mahimkar, Gunnar Persson,Claes Westerlind, ABB AB, SE-771 80, Ludvika, Sweden, nandan.mahimkar@in.abb.com, gunnar.persson@se.abb.com,claes.westerlind@se.abb.com,

More information

HVDC 2000 a new generation of high-voltage DC converter stations

HVDC 2000 a new generation of high-voltage DC converter stations HVDC 2000 a new generation of high-voltage DC converter stations Improved performance and robustness, shorter lead times and faster delivery, plus reduced maintenance needs, were the development goals

More information

Knowing the FACTS. FACTS that enhance power quality in rail feeder systems

Knowing the FACTS. FACTS that enhance power quality in rail feeder systems Knowing the FACTS FACTS that enhance power quality in rail feeder systems ROLF GRÜNBAUM, PER HALVARSSON, BJÖRN THORVALDSSON The increase in traffic on existing tracks combined with new high-speed rail

More information

HVDC-VSC: transmission technology of the future

HVDC-VSC: transmission technology of the future A bi-pole ± 285 kv HVDC line sandwiched between 3-phase 400 kv HVAC lines. HVDC-VSC: transmission technology of the future A new hybrid HVDC circuit technology using voltage source converters is only half

More information

Offshore Platform Powered With New Electrical Motor Drive System

Offshore Platform Powered With New Electrical Motor Drive System Offshore Platform Powered With New Electrical Motor Drive System Authors: Jan O. Lamell, M.Sc E.E. ABB Automation Technologies Presenters: Thomas Johansson, M.Sc E.E. ABB Automation Technologies Timothy

More information

Control Development and Modeling for Flexible DC Grids in Modelica

Control Development and Modeling for Flexible DC Grids in Modelica Control Development and Modeling for Flexible DC Grids in Modelica Andreas Olenmark 1 Jens Sloth 2 Anna Johnsson 3 Carl Wilhelmsson 3 Jörgen Svensson 4 1 One Nordic AB, Sweden, andreas.olenmark@one-nordic.se.

More information

Analysis of AC-DC Converter Based on Power Factor and THD

Analysis of AC-DC Converter Based on Power Factor and THD Website: www.ijetae.com (SSN 50-459, SO 900:008 Certified Journal, Volume 3, ssue, February 03) Analysis of AC-DC Converter Based on Power Factor and THD Shiney.S.Varghese, Sincy George Department of Electrical

More information

Updated SYSTEM IMPACT STUDY OF NEW ENGLAND AREA

Updated SYSTEM IMPACT STUDY OF NEW ENGLAND AREA CROSS SOUND CABLE PROJECT 330MW HVdc INTERCONNECTION BETWEEN NEW HAVEN, CONNECTICUT AND SHOREHAM, NY Updated SYSTEM IMPACT STUDY OF NEW ENGLAND AREA Subordinate Status Removal and Amendment of Approved

More information

factsheet High Voltage Direct Current electricity technical information

factsheet High Voltage Direct Current electricity technical information factsheet High Voltage Direct Current electricity technical information Introduction High voltage direct current (HVDC) technology is one of the technical options National Grid can consider for the future

More information

Voltage Source HVDC Overview Mike Barnes Tony Beddard

Voltage Source HVDC Overview Mike Barnes Tony Beddard Voltage Source HVDC Overview Mike Barnes Tony Beddard Note: This is a version with images removed which have copyrighted other than from the University of Manchester, for web publication. Should a conference

More information

Principles of Adjustable Frequency Drives

Principles of Adjustable Frequency Drives What is an Adjustable Frequency Drive? An adjustable frequency drive is a system for controlling the speed of an AC motor by controlling the frequency of the power supplied to the motor. A basic adjustable

More information

The design and performance of Static Var Compensators for particle accelerators

The design and performance of Static Var Compensators for particle accelerators CERN-ACC-2015-0104 Karsten.Kahle@cern.ch The design and performance of Static Var Compensators for particle accelerators Karsten Kahle, Francisco R. Blánquez, Charles-Mathieu Genton CERN, Geneva, Switzerland,

More information

Holly STATCOM FACTS to replace critical generation, operational experience

Holly STATCOM FACTS to replace critical generation, operational experience Holly STATCOM FACTS to replace critical generation, operational experience A. Oskoui, B. Mathew, Member, IEEE, J.-P. Hasler, M. Oliveira, Member, IEEE, T. Larsson, Member, IEEE, Å. Petersson, E. John,

More information

SVC LIGHT: A POWERFUL MEANS FOR DYNAMIC VOLTAGE AND POWER QUALITY CONTROL IN INDUSTRY AND DISTRIBUTION.

SVC LIGHT: A POWERFUL MEANS FOR DYNAMIC VOLTAGE AND POWER QUALITY CONTROL IN INDUSTRY AND DISTRIBUTION. SVC LIGHT: A POWERFUL MEANS FOR DYNAMIC VOLTAGE AND POWER QUALITY CONTROL IN INDUSTRY AND DISTRIBUTION. R. Grünbaum ABB Power Systems AB, AC Systems Division, Sweden. INTRODUCTION Modern society relies

More information

Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager

Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager Introduction There is a growing trend in the UPS industry to create a highly efficient, more lightweight and smaller UPS

More information

Specifying a Variable Frequency Drive s

Specifying a Variable Frequency Drive s Specifying a Variable Frequency Drive s Put on by Bruce Reeves and Jeremy Gonzales Dykman Electrical Covering the Western US For all of your VFD and Soft Start and Motor Needs How To Specify a Variable

More information

Cable Solutions for Servo and Variable Frequency Drives (VFD)

Cable Solutions for Servo and Variable Frequency Drives (VFD) Cable Solutions for Servo and Variable Frequency Drives (VFD) Electric drive systems with continuous torque and speed control are widespread today. They allow an optimal adjustment of the drive with respect

More information

AC/DC Power Supply Reference Design. Advanced SMPS Applications using the dspic DSC SMPS Family

AC/DC Power Supply Reference Design. Advanced SMPS Applications using the dspic DSC SMPS Family AC/DC Power Supply Reference Design Advanced SMPS Applications using the dspic DSC SMPS Family dspic30f SMPS Family Excellent for Digital Power Conversion Internal hi-res PWM Internal high speed ADC Internal

More information

INTERNATIONAL JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY (IJEET)

INTERNATIONAL JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY (IJEET) INTERNATIONAL JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY (IJEET) International Journal of Electrical Engineering and Technology (IJEET), ISSN 0976 ISSN 0976 6545(Print) ISSN 0976 6553(Online) Volume

More information

Renewable Energy Grid Integration

Renewable Energy Grid Integration Renewable Energy Grid Integration Jian Sun Professor and Director Grid Integration Issues Cost, Reliability & Efficiency of Grid Interface Grid Congestion, Weak Grids Variability of Renewable Production

More information

STATCOM Application at VELCO Essex Substation

STATCOM Application at VELCO Essex Substation STATCOM Application at VELCO Essex Substation Gregory Reed John Paserba Terrence Croasdaile Mitsubishi Electric Power Products, Inc. Warrendale, Pennsylvania, USA Masatoshi Takeda Naoki Morishima Yoshi

More information

HVDC. A firewall against disturbances in high-voltage grids. Lennart Carlsson

HVDC. A firewall against disturbances in high-voltage grids. Lennart Carlsson A firewall against disturbances in high-voltage grids Lennart Carlsson Interconnections between grids are desirable because they not only permit economies through the sharing of reserves, but they also

More information

Submarine Power Cables. State-of-the-art production facility, more than 100 years of experience and reference installations around the world.

Submarine Power Cables. State-of-the-art production facility, more than 100 years of experience and reference installations around the world. Submarine Power Cables State-of-the-art production facility, more than 100 years of experience and reference installations around the world. Reliable submarine power cables ABB is one of the world s most

More information

Requirements for Offshore Grid Connections. in the. Grid of TenneT TSO GmbH

Requirements for Offshore Grid Connections. in the. Grid of TenneT TSO GmbH Requirements for Offshore Grid Connections in the Grid of TenneT TSO GmbH Bernecker Straße 70, 95448 Bayreuth Updated: 21 December 2012 1/10 Requirements for Offshore Grid Connections in the Grid of TenneT

More information

Recent Siemens HVDC Activities Yuriy Kazachkov Siemens PTI

Recent Siemens HVDC Activities Yuriy Kazachkov Siemens PTI IEEE PES 2008 HVDC & FACTS Subcommittee Recent Siemens HVDC Activities Yuriy Kazachkov Siemens PTI 660MW 500kV in operation since July 2007 Commercial Operation Neptune RTS Costumer Project Name Location

More information

Electric Power Systems An Overview. Y. Baghzouz Professor of Electrical Engineering University of Nevada, Las Vegas

Electric Power Systems An Overview. Y. Baghzouz Professor of Electrical Engineering University of Nevada, Las Vegas Electric Power Systems An Overview Y. Baghzouz Professor of Electrical Engineering University of Nevada, Las Vegas Overview Power Generation Conventional power generation Power generation from renewables

More information

Power Plant Electrical Distribution Systems

Power Plant Electrical Distribution Systems PDH Course E184 Power Plant Electrical Distribution Systems Gary W Castleberry, PE 2008 PDH Center 2410 Dakota Lakes Drive Herndon, VA 20171-2995 Phone: 703-478-6833 Fax: 703-481-9535 www.pdhcenter.com

More information

Transmissão em Corrente Contínua

Transmissão em Corrente Contínua Transmissão em Corrente Contínua Panorama Atual e Perspectivas Futuras no Brasil Multi-Terminal HVDC Classic Some Considerations Brazilian SC B4 Paulo Fischer de Toledo, ABB Basic considerations Traditional

More information

Respecting the environment

Respecting the environment MAIN FEATURE CHAPTER I RESEARCH WITH AN EYE ON THE FUTURE Respecting the environment Low power losses and a lesser visual impact on the landscape make Gas-Insulated Lines (GIL) a very environmentally friendly

More information

MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS

MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS Meher Capacitors offers reliable and innovative products and solutions in the fields of Reactive Power Compensation, Power Quality and Energy

More information

2012 San Francisco Colloquium

2012 San Francisco Colloquium 2012 San Francisco Colloquium http : //www.cigre.org Advances in voltage source converter (VSC) technologies B4-6 500 kv VSC Transmission System for lines and cables B. JACOBSON, B. WESTMAN, M. P. BAHRMAN*

More information

HVDC Light & SVC Light Reference list

HVDC Light & SVC Light Reference list & Reference list ABB & Projects Worldwide 37 1 Hällsjön 2 Hagfors 3 Gotland 4 Directlink 5 Tjæreborg 6 Eagle Pass 7 Trierer Stahlwerk 8 Cross Sound Cable 9 Murraylink 10 Outokumpu Stainless 11 Evron 12

More information

Summary of Electric Transmission Assessment Report

Summary of Electric Transmission Assessment Report Summary of Electric Transmission Assessment Report January 2010 Assessment and Analysis of the State-Of-the-Art High-Voltage Electric Transmission Systems with Specific Focus on High-Voltage Direct Current

More information

Kit 106. 50 Watt Audio Amplifier

Kit 106. 50 Watt Audio Amplifier Kit 106 50 Watt Audio Amplifier T his kit is based on an amazing IC amplifier module from ST Electronics, the TDA7294 It is intended for use as a high quality audio class AB amplifier in hi-fi applications

More information

Hyperlinks are Inactive

Hyperlinks are Inactive Prepared by: NIB/EOB PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES 05503 Department: Electric T&D Section: T&D Engineering and Technical Support Approved by: G.O. Duru (GOD)

More information

ANCILLARY EQUIPMENT AND ELECTRICAL EQUIPMENT Power Supply Systems and Electrical Equipment for Desalination Plants - Y.M. Hamud and A.H.

ANCILLARY EQUIPMENT AND ELECTRICAL EQUIPMENT Power Supply Systems and Electrical Equipment for Desalination Plants - Y.M. Hamud and A.H. POWER SUPPLY SYSTEMS AND ELECTRICAL EQUIPMENT FOR DESALINATION PLANTS Y.M. Hamud and A.H. Anwar Abu Dhabi Water and Electricity Authority, Abu Dhabi, UAE Keywords : Electrical System, Network for Desalination,

More information

Dynamic Reactive Compensation MV STATCOM

Dynamic Reactive Compensation MV STATCOM PCS 6000 Leaflet Dynamic Reactive Compensation MV STATCOM Providing stability, security, and reliability to the grid. Installing a STATCOM at one or more suitable points on the network is a powerful and

More information

Three Gorges - Changzhou HVDC : Ready to Bring Bulk Power to East

Three Gorges - Changzhou HVDC : Ready to Bring Bulk Power to East The 4 th International Conference on Power Transmission & Distribution Technology 2003 14-16 October, 2003, Changsha 2003 Three Gorges - Changzhou HVDC : Ready to Bring Bulk Power to East Abhay Kumar Mats

More information

Power transformers. Special transformers Railway

Power transformers. Special transformers Railway Power transformers Special transformers Railway A leader in railway systems Our compact and low-weight transformers fully comply with the customer s specifications. The products are developed together

More information

Circuit Breaker LTB D with Motor Drive. Motor Drive. ABB PP/H/HV - Page 1. Ed 2006-04

Circuit Breaker LTB D with Motor Drive. Motor Drive. ABB PP/H/HV - Page 1. Ed 2006-04 Circuit Breaker LTB D with Motor Drive Motor Drive ABB PP/H/HV - Page 1 Ed 2006-04 Technology Traditional technology Traditional spring operating mechanism: Closing mechanism ABB PP/H/HV - Page 2 Tripping

More information

Wide Area Monitoring Current Continental Europe TSOs Applications Overview

Wide Area Monitoring Current Continental Europe TSOs Applications Overview Wide Area Monitoring Current Continental Europe TSOs Applications Overview Version 5 System Protection & Dynamics Working Group 20th September 2015 1. Content 1. Content... 2 2. Introduction... 3 3. Main

More information

Safety technique. Emergency stop module BO 5988 safemaster

Safety technique. Emergency stop module BO 5988 safemaster Safety technique Emergency stop module BO 5988 safemaster 0221562 Function diagram Pushbutton on Mains or emergencystop () K1 According to EC Directive for machines 98/37/EG According to IEC/E 60204-1

More information

Unified requirements for systems with voltages above 1 kv up to 15 kv

Unified requirements for systems with voltages above 1 kv up to 15 kv (1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to

More information

General Validation Test Program for Wind Power Plants Connected to the Hydro-Québec Transmission System

General Validation Test Program for Wind Power Plants Connected to the Hydro-Québec Transmission System General Validation Test Program for Wind Power Plants Connected to the Hydro-Québec Transmission System Direction Planification des actifs et expertise de transport February 2011 TABLE OF CONTENTS 1. CONDUCTING

More information

HVDC ENABLING THE TRANSITION TO AN ENERGY SYSTEM BASED ON RENEWABLES

HVDC ENABLING THE TRANSITION TO AN ENERGY SYSTEM BASED ON RENEWABLES HVDC ENABLING THE TRANSITION TO AN ENERGY SYSTEM BASED ON RENEWABLES O. Vestergaard 1, B. Westman 2, G. McKay 3, P. Jones 4, J. Fitzgerald 5, B. Williams 6 1+2 ABB AB, Sweden, ole.vestergaard@se.abb.com,

More information

B4-207. Konti-Skan 1 HVDC Pole Replacement

B4-207. Konti-Skan 1 HVDC Pole Replacement 21, rue d'artois, F-75008 Paris http://www.cigre.org B4-207 Session 2004 CIGRÉ Konti-Skan 1 HVDC Pole Replacement P L Sorensen 1, B Franzén 2, J D Wheeler 3, R E Bonchang 3, C D Barker 3, R M Preedy 3,

More information

Stand Alone POTS Fiber Optic System. P31372 Station (Subscriber) Unit P31379 Remote (Exchanger) Unit. Description & Installation

Stand Alone POTS Fiber Optic System. P31372 Station (Subscriber) Unit P31379 Remote (Exchanger) Unit. Description & Installation Stand Alone POTS Fiber Optic System P31372 Station (Subscriber) Unit P31379 Remote (Exchanger) Unit Description & Installation Printed in USA 09/11 TO466 Rev. A Table of Contents Page 1.0 SCOPE 2 2.0 PRODUCT

More information

factsheet High Voltage Direct Current Electricity technical information

factsheet High Voltage Direct Current Electricity technical information factsheet High Voltage Direct Current Electricity technical information Introduction High voltage direct current (HVDC) technology is one of the technical options National Grid can consider for the future

More information

Assessment of the Technical Issues relating to Significant Amounts of EHV Underground Cable in the All-island Electricity Transmission System

Assessment of the Technical Issues relating to Significant Amounts of EHV Underground Cable in the All-island Electricity Transmission System Assessment of the Technical Issues relating to Significant Amounts of EHV Underground Cable in the All-island Electricity Transmission System Summary Report November 2009 Technical Report on using EHV

More information

14.5GHZ 2.2KW CW GENERATOR. GKP 22KP 14.5GHz WR62 3x400V

14.5GHZ 2.2KW CW GENERATOR. GKP 22KP 14.5GHz WR62 3x400V 14.5GHZ 2.2KW CW GENERATOR GKP 22KP 14.5GHz WR62 3x400V UTILIZATION OF GKP 22KP GENERATOR With its characteristics of power stability whatever the load, very fast response time at a pulse, low ripple,

More information

Fundamentals of Power Electronics. Robert W. Erickson University of Colorado, Boulder

Fundamentals of Power Electronics. Robert W. Erickson University of Colorado, Boulder Robert W. Erickson University of Colorado, Boulder 1 1.1. Introduction to power processing 1.2. Some applications of power electronics 1.3. Elements of power electronics Summary of the course 2 1.1 Introduction

More information

DDX 7000 & 8003. Digital Partial Discharge Detectors FEATURES APPLICATIONS

DDX 7000 & 8003. Digital Partial Discharge Detectors FEATURES APPLICATIONS DDX 7000 & 8003 Digital Partial Discharge Detectors The HAEFELY HIPOTRONICS DDX Digital Partial Discharge Detector offers the high accuracy and flexibility of digital technology, plus the real-time display

More information

ABB PSPS Erich Steinmann; Generator control-2013

ABB PSPS Erich Steinmann; Generator control-2013 ABB PSPS Erich Steinmann; Generator control-2013 GENERATOR CONTROL THE MODULAR SOLUTION FOR GENERATORS To make sure that power is efficiently converted into electric energy, it is necessary to supervise

More information

A Live Black-start Capability test of a Voltage Source HVDC Converter

A Live Black-start Capability test of a Voltage Source HVDC Converter CIGRÉ-676 2015 CIGRÉ Canada Conference 21, rue d Artois, F-75008 PARIS http : //www.cigre.org Winnipeg, Manitoba, August 31-September 2, 2015 A Live Black-start Capability test of a Voltage Source HVDC

More information

Transformers. Special transformers Reactors products

Transformers. Special transformers Reactors products Transformers Special transformers Reactors products Reactors Custom designed, custom built ABB Oy Transformers has extensive experience and numerous references from different reactor applications, having

More information

Overview of the 500MW EirGrid East-West Interconnector, considering System Design and Execution-Phase Issues

Overview of the 500MW EirGrid East-West Interconnector, considering System Design and Execution-Phase Issues Overview of the 500MW EirGrid East-West Interconnector, considering System Design and Execution-Phase Issues J Egan, P O Rourke EirGrid Plc, Republic of Ireland john.egan@eirgrid.com paul.o rouke@eirgrid.com

More information

ELECTRICAL ENGINEERING DESIGN CRITERIA APPENDIX F

ELECTRICAL ENGINEERING DESIGN CRITERIA APPENDIX F ELECTRICAL ENGINEERING DESIGN CRITERIA APPENDIX F TABLE OF CONTENTS Appendix F - Electrical Engineering Design Criteria F.1 Introduction...F-1 F.2 Codes and Standards...F-1 F.3 Switchyard and Transformers...F-1

More information

FACTS. Solutions to optimise network performance GRID

FACTS. Solutions to optimise network performance GRID Solutions to optimise network performance GRID Solutions to optimise your network Our worldwide presence: Better solutions for your network all around the world Tampere Philadelphia Stafford Konstanz Beijing

More information

CONSULTATION PAPER FOR PROPOSED MODIFICATIONS TO THE TRANSMISSION CODE

CONSULTATION PAPER FOR PROPOSED MODIFICATIONS TO THE TRANSMISSION CODE CONSULTATION PAPER FOR PROPOSED MODIFICATIONS TO THE TRANSMISSION CODE Closing date for submission of representations: 30 th Sep 2014, 5 pm 18 AUG 2014 ENERGY MARKET AUTHORITY 991G Alexandra Road #01-29

More information

Power transformers. Generator step-up and system intertie power transformers Securing high-quality AC transmission

Power transformers. Generator step-up and system intertie power transformers Securing high-quality AC transmission Power transformers Generator step-up and system intertie power transformers Securing high-quality AC transmission Generator step-up transformers Built to withstand continuous full load Generator step-up

More information

POWER SYSTEM HARMONICS. A Reference Guide to Causes, Effects and Corrective Measures AN ALLEN-BRADLEY SERIES OF ISSUES AND ANSWERS

POWER SYSTEM HARMONICS. A Reference Guide to Causes, Effects and Corrective Measures AN ALLEN-BRADLEY SERIES OF ISSUES AND ANSWERS A Reference Guide to Causes, Effects and Corrective Measures AN ALLEN-BRADLEY SERIES OF ISSUES AND ANSWERS By: Robert G. Ellis, P. Eng., Rockwell Automation Medium Voltage Business CONTENTS INTRODUCTION...

More information

Cost Benefit Methodology for Optimal Design of Offshore Transmission Systems

Cost Benefit Methodology for Optimal Design of Offshore Transmission Systems Centre for Sustainable Electricity and Distributed Generation Cost Benefit Methodology for Optimal Design of Offshore Transmission Systems Predrag Djapic and Goran Strbac July 2008 FUNDED BY BERR URN 08/1144

More information

THE NEPTUNE REGIONAL TRANSMISSION SYSTEM 500 kv HVDC PROJECT

THE NEPTUNE REGIONAL TRANSMISSION SYSTEM 500 kv HVDC PROJECT 21, rue d Artois, F-75008 PARIS B4-118 CIGRE 2008 http : //www.cigre.org THE NEPTUNE REGIONAL TRANSMISSION SYSTEM 500 kv HVDC PROJECT E. STERN, J. NASH - NEPTUNE RTS, LLC (U.S.A.) C. SCHOENIGER, C. BARTZSCH

More information

MOBILE SYSTEM FOR DIAGNOSIS OF HIGH VOLTAGE CABLES (132KV/220KV) VLF-200 HVCD

MOBILE SYSTEM FOR DIAGNOSIS OF HIGH VOLTAGE CABLES (132KV/220KV) VLF-200 HVCD MOBILE SYSTEM FOR DIAGNOSIS OF HIGH VOLTAGE CABLES (132KV/220KV) VLF-200 HVCD VERY LOW FREQUENCY (VLF) - PARTIAL DISCHARGES AND TANGENT DELTA HV/EHV POWER CABLES DIAGNOSTIC AND ON-SITE FIELD TESTING WITH

More information

Survey of Harmonics Measurements in Electrical Distribution Systems

Survey of Harmonics Measurements in Electrical Distribution Systems Survey of Harmonics Measurements in Electrical Distribution Systems Leon M. Tolbert, Member, IEEE Oak Ridge National Laboratory* P.O. Box 28, Bldg Oak Ridge, TN 3783-6334 Alexandria, VA 2235-3862 Phone:

More information

Timing Errors and Jitter

Timing Errors and Jitter Timing Errors and Jitter Background Mike Story In a sampled (digital) system, samples have to be accurate in level and time. The digital system uses the two bits of information the signal was this big

More information

ENERGY AND ENVIRONMENTAL SAVINGS IN STEEL MAKING BY MEANS OF SVC LIGHT

ENERGY AND ENVIRONMENTAL SAVINGS IN STEEL MAKING BY MEANS OF SVC LIGHT ENERGY AND ENVIRONMENTAL SAVINGS IN STEEL MAKING BY MEANS OF SVC LIGHT Rolf Grünbaum, Tomas Gustafsson ABB Power Systems AB AC Systems Division SE-721 64 Vasteras Sweden Phone: +46 21 32 40 00 rolf.grunbaum,

More information

Circulating Current Relay. Type IRXm

Circulating Current Relay. Type IRXm Circulating Current Relay Type IRXm ABB a global technology leader ABB is a global leader in Power and Automation technologies that enable utility and industry customers to improve performance while lowering

More information

Discover the power of e-learning! The Quick Guide to AC Variable Frequency

Discover the power of e-learning! The Quick Guide to AC Variable Frequency The Quick Guide to AC Variable Frequency This ebook is meant as an easy guide to any electrical or electronic engineer or technician, who would like to know how modern ac variable frequency drives work.

More information

System Protection Schemes in Eastern Denmark

System Protection Schemes in Eastern Denmark System Protection Schemes in Eastern Denmark Joana Rasmussen COWI A/S, Energy Department System Protection Schemes in Eastern Denmark 1.Advanced system protection schemes are investigated and perspectives

More information

Current and voltage measuring relays

Current and voltage measuring relays Current and voltage measuring relays RXIK 1, RXEEB 1 and Page 1 Issued June 1999 Changed since July 1998 Data subject to change without notice RXIK 1 RXEEB 1 (SE980082) (SE980081) (SE970869) Features Application

More information

COMPARISON OF THE FACTS EQUIPMENT OPERATION IN TRANSMISSION AND DISTRIBUTION SYSTEMS

COMPARISON OF THE FACTS EQUIPMENT OPERATION IN TRANSMISSION AND DISTRIBUTION SYSTEMS COMPARISON OF THE FACTS EQUIPMENT OPERATION IN TRANSMISSION AND DISTRIBUTION SYSTEMS Afshin LASHKAR ARA Azad University of Dezfoul - Iran A_lashkarara@hotmail.com Seyed Ali NABAVI NIAKI University of Mazandaran

More information

PROGRAM CRITERIA FOR ELECTRICAL ENGINEERING TECHNOLOGY

PROGRAM CRITERIA FOR ELECTRICAL ENGINEERING TECHNOLOGY PROGRAM CRITERIA FOR ELECTRICAL ENGINEERING TECHNOLOGY Scope These program criteria apply to programs having titles involving Electrical Engineering Technology including: electrical engineering, electrical

More information

Submarine Cable Power Transmission using DC High-Voltage Three-Level Converters

Submarine Cable Power Transmission using DC High-Voltage Three-Level Converters Submarine Cable Power Transmission using DC High-Voltage Three-Level Converters João Antunes, IST (jlantunes@gmail.com) Astract This paper is about multilevel converters used in High Voltage Direct Current

More information

TURBOtech srl. SED-635 Digital Excitation System. Industrial Electronics Sector FEATURES

TURBOtech srl. SED-635 Digital Excitation System. Industrial Electronics Sector FEATURES SED-635 Digital Excitation System SED-635 is a complete excitation system capable of adapting to control synchronous generators of any size. The integration of the TOUCH SCREEN operator interface and a

More information

..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark...

..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark... ..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark... TIME MARK CORPORATION 11440 EAST PINE STREET TULSA, OK 74116 USA tel 918 438-1220 fax 918 437-7584 www.time-mark.com

More information

FRCC Standards Handbook. FRCC Automatic Underfrequency Load Shedding Program. Revision Date: July 2003

FRCC Standards Handbook. FRCC Automatic Underfrequency Load Shedding Program. Revision Date: July 2003 F R C C FRCC Standards Handbook FRCC Automatic Underfrequency Load Shedding Program Revision Date: July 2003 FRCC Underfrequency Load Shedding Program Modification and Approval Process Requests to modify

More information

Product brochure Multi Functional Switchgear PASS M00 72.5 kv Flexible and compact switchgear solutions for windfarms

Product brochure Multi Functional Switchgear PASS M00 72.5 kv Flexible and compact switchgear solutions for windfarms Product brochure Multi Functional Switchgear PASS M00 72.5 kv Flexible and compact switchgear solutions for windfarms The future of Wind Farms As offshore wind farms move towards deploying higher capacity

More information

CUSTOMER REQUIREMENTS AT POWER SUBSTATIONS

CUSTOMER REQUIREMENTS AT POWER SUBSTATIONS CUSTOMER REQUIREMENTS AT POWER SUBSTATIONS Customer Handout Date Aug 2, 2010 Version 1.0 File Name Customer Requirements At Power Substations Document Id Outside Plant Engineering 1 Table Of Contents 1.0

More information