1 pero 1 Three Phase Solid State Relays & Their Application in Three Phase Motor Circuits By Paul Bachman, Fellow Engineer, Dr. Oscar Montero, R&D Manager, and Doug Sherman, FSAE Manager, Crydom, Inc. ABSTRACT Three phase Solid State Relays (SSRs) have been available since shortly after the introduction of Single Phase SSRs in The first of these relays were nothing more than 3 individual SSRs with a common input connection packaged in a single housing. This basic design concept remains, for the most part, unchanged today. However, even though the function of single-phase and three phase relays are quite similar, their applications can vary significantly. This is primarily due to the characteristics of three phase power circuits and the attributes/ demands of three phase loads, particularly inductive loads. The proper selection and application of three phase SSRs for Motor control applications depends not only upon a comprehensive understanding of three phase SSRs, but also of the three phase power system and typical loads as well. This paper includes a summary review of three phase power systems, the characteristics of common three phase Motor loads, and a comprehensive discussion of three phase SSRs and their application relative to such loads.
2 INTRODUCTION Solid State Relays are used in a wide variety of electrical load-switching applications, including Professional Cooking Equipment, Plastics Machinery, Packaging Machinery, Lighting Systems, Medical Equipment, Laboratory Ovens, Beverage Dispensing Equipment, HVAC&R systems, and many other industrial or commercial applications. However, for the purpose of understanding these applications relative to the use of SSRs for their control, the vast majority of loads can be grouped into two primary categories: heating and motion control. Obviously this is not an all-inclusive grouping as there are other applications outside of the scope of these two categories such as lighting and power distribution systems. However, a majority of Design Engineers specifying SSRs apply them to one of these two general types of three phase loads as shown in Figure 1 below. The focus here is on Motor loads while a companion paper focuses on Heating loads. Figure 1 - Block diagram depicting three-phase loads controlled by Three-phase SSRs. While every application is different and requires its own scrutiny, focusing on these two main categories allows us to generalize about the characteristics of the applications and the subsequent requirements placed upon the SSRs used to perform the switching functions for each. Moreover, limiting the focus to higher-power systems utilizing three phase networks to energize the load(s) covers some of the most demanding commercial and industrial applications where SSRs are used today.
3 THREE PHASE SSRs DEFINED and DESCRIBED As previously mentioned above, a three phase SSR is essentially 3 individual single phase SSRs packaged in a single housing with a common input so that each SSR is energized simultaneously. In fact, it is not uncommon for engineers to use 3 individual SSRs to switch power to a three phase load. This is usually done out of preference or where a pre-packaged three phase SSR is not suitable for one reason or another. However, the more common and simplistic approach is to use a three phase SSR to provide the switching function. This simplifies wiring and usually reduces overall space requirements within the panel. The main attributes of SSRs, whether single or three phase are: contact less turn on and turn off which means no arcing, contact bounce or acoustic noise; high speed switching; long life expectancy; low input control power requirements; zero current turn off which substantially minimizes electrical transients especially when switching inductive loads; and zero voltage turn on which can minimize turn current surges and their resulting transients. Three phase SSRs are intended to control three phase AC loads, which might otherwise be switched by Electromechanical Relays, Contactors or three phase Mercury Relays or Contactors. For three phase resistive heating applications, zero-crossing three phase SSRs are commonly used. These versions will switch power to the load at the zero-voltage crossing point of each phase in order to minimize inrush currents. Random turn-on SSRs are recommended for switching inductive loads, such as motors, compressors, or transformers where it is desirable to switch on 3 phases on at exactly the same moment. All AC output SSRs (excepting special versions built with FETs or IGBTs) turn off at zero current irrespective of whether they are zero voltage or random turn-on SSRs, and thus reduce transients caused by opening a load with a magnetic field that collapses resulting in transients. Considerations when incorporating SSRs in three phase applications include: thermal power dissipation in the SSR due to losses in the output power semiconductors which often requires the use of external heat sinks to maintain allowed operating temperature; electrical transients carried on the power lines or created by switching reactive loads that may require additional transient protection for the SSR; and selection of zero voltage or non-zero voltage turn on depending upon load type.
4 THREE PHASE POWER SYSTEMS Three phase electric power is the most common method for distributing electric power worldwide. Figure 2 depicts three phase power as provided by three voltage waveforms for three conductors carrying alternating current at the same frequency but with a shift of 120º between any two of the three phases (instantaneous peak values at different times). Three phase power is typically used to power large motors or other high-power loads and offers several advantages over equivalent single-phase or two-phase systems including: Three phase power provides the most consistent supply of current and therefore power. There is always at least 2 phases delivering power to the load where as single phase systems have zero power delivered for a short time each half cycle. Three phase systems tend to be more economical as they use less conductor material to transmit power than single or two-phase systems providing the same power level. Neutral conductors can use less material or be eliminated completely as the phase currents cancel out one another in a balanced load. In this circumstance where the neutral is eliminated it is also possible to control the load by switching only 2 of the 3 phases which offers further advantages by reducing the number of relays or contacts required. Power transfer is constant into a linear and balanced load, which helps reduce vibration in three phase motors compared to single phase motors of equivalent HP. Three phase systems produce a magnetic field rotating in one direction, which helps simplify motor design and offers the ability to easily reverse a motor s direction of rotation by swapping two of the three phases. Figure 2 Three-phase power systems
5 THREE PHASE INDUCTION MOTOR LOADS Three phase induction motors have 3 individual coils and while they may be wired in either a wye or delta configuration much like three phase heaters, the wye configuration is the more common and preferred configuration (Figure 3). The design and placement of the coils is such that for each revolution of the motor, the three interspersed magnetic fields generate rotational torque on the rotor, causing it to turn. This design creates more mechanical force with less current per phase than for equivalent rated single phase motors. Due to the 120 separation between the coils, there is significantly greater starting torque and less vibration than for single phase motors, and often no need for start capacitors to provide additional current to overcome high inertial or compressor loads. Figure 3 Wye and Delta connection of Three-phase motors Consequently, three phase induction motors are used in many industrial applications to operate loads such as pumps, compressors, valves, conveyors, and many other motor-driven devices. They are relatively simple in design, efficient, smaller, less expensive and generally more durable than single-phase motors with comparable ratings. For three phase motors, the following formula applies: HP = 3 x I L x V L x Eff x pf (1) 746 Where HP is horsepower, V L is line voltage, I L is line current, Eff is the motor s efficiencyas a decimal value, and pf is power factor.
6 Therefore the line current per phase or FLA (full load amperes) in a three phase motor operating at its maximum specified horse power would be calculated as: FLA = I L = HP x 746 (2) 3 x V L x Eff x pf Similarly, when the motor s Kilowatt rating is known, the line current per phase or FLA would be calculated as follows: FLA = I L = KW x 1000 (3) 3 x V L x Eff x pf Therefore, when the motor s Kva rating is known, the line current per phase or FLA would be calculated as follows: FLA = I L = KVA x 1000 (4) 3 x V L Locked rotor current (I LRA ) is calculated as follows: I LRA = 577 x HP x KVA/HP (5) V R Where KVA/HP is motor slip calculated as a % reduction in RPM from the synchronous RPM to actual RPM (see Table 1 below), and V R is the motor s rated nominal AC operating voltage. If the actual operating line voltage is different, then the locked rotor current will vary directly as the line voltage varies (I LRA x (V L /V R )). Code KVA/HP Code KVA/HP Code KVA/HP Code KVA/HP A F L S B G M T C H N U D I P V 22.4 & Up E K R Table 1 - Motor slip value codes Note: formulas (1), (2), (3), (4), (5) & Table 1 courtesy of Baldor Electric Company.
7 It is evident that the actual HP delivered by the motor depends on the line voltage (V L ) applied to its terminals. Furthermore, the line current (I L ) drawn by the motor also depends on V L as well as the actual mechanical load attached to the motor s shaft. It is important to recognize the following points regarding I L : During motor starting operation: I L reaches its highest value as the motor tries to overcome the mechanical inertia imposed mainly by the mechanical load. As shown in Figure 4, this is a transitory condition that may last from several cycles to seconds depending on the nature of the mechanical load. This current is also known as Locked Rotor Current, I LRA, and is calculated using equation (5). During motor steady state operation: As the motor speeds up, the current I L decreases until it settles at an operational value that matches the HP delivered to the load. The highest value for I L corresponds to the motor rated current or Full Load Current, FLA. Figure 4 - Typical LRA and FLA waveforms for an AC motor.
8 The current through a motor load can then be said to have two main components: I Load =I transient + I steady-state (6) Where I Load is the per phase current flowing though both the load and consequently the switch or relay. In particular, I transient is negligible for Resistive loads hence I Load can be approximated to I steady-state. However, for Motor loads, I transient can be considered equivalent to Locked Rotor Amps (LRA), while I steady-state can be considered equivalent to Full Load Amps (FLA). LRA values can be 5 to 7 times FLA values for several seconds depending on the type of motor and application. Example Line Current Calculation for a three phase Induction Motor Calculate the full load and locked rotor line currents per phase for a 5 HP, 440 VAC, 85% efficient, 0.7 power factor three phase induction motor with slip code E operating in a 40 C ambient: I L = HP x x V L x Eff x pf I L = I L = 5 x x 440 x.85 x amps per phase For locked rotor rating, the range of lower to higher values is calculated as follows: I LRA = I LRA = 577 x HP x KVA/HP V R 577 x 5 x 4.5 (lower limit) 440 I LRA = 29.5 amps Using the upper limit of slip (5.0), I LRA = 32.8 amps For this example, locked rotor currents would fall between 29.5 and 32.8 amps per phase.
9 Safety Agency Standards Relative to Solid State Relays SSRs may be rated by their manufacturer for operation in certain types of applications. The most common rating categories pertain to applications for resistive loads and motor loads. The main difference between these two ratings is that SSRs for motor applications must be rated to handle both LRA and FLA. The following table (Table 2) summarizes the three most common standards for Solid State Relays in motor applications. Standard UL508 IEC62314 IEC Classification Motor Controller Motor Load, LC B Motor Controllers, AC-53a Table 2 SSR Motor Load Ratings per Relevant Standards Standards mentioned in Table 2 require that switches intended for controlling Motor loads be able to handle load currents that resemble LRA conditions. As a result, a given SSR would have different Load current ratings for Resistive loads or Motor loads. Essentially, the SSRs Resistive load rating is derated when applied to Motor loads. For instance, an SSR capable of carrying 50A resistive current could be rated as a 17A SSR when placed in motor control applications. SSRs for three phase Induction Motor Applications Historically the most common devices used for switching power to induction motors are electromechanical relays and contactors. However, as demand for improved performance and reliability increases, solid state relays are being applied in growing numbers. As with resistive load controls, this can be accomplished with 3 individual SSRs, one three phase SSR, or with 2 SSRs (or 1 dual SSR) where codes permit. The major advantages of SSRs for three phase induction motor control are as follows: All solid state construction eliminates mechanical fatigue within the relay Contact less, arc free silent operation High speed switching allowing very precise control Logic compatible low input control power Electronic AC and DC coils which eliminate transients created when EMR Contactor coils are operated Zero current load turn off eliminating transients Extremely long life when compared to mechanical relays or contactors 4000 VAC isolation input to output RoHS compliant
10 Start/Stop Motor Applications Most applications utilizing three phase motors simply require the motor to turn on and off as depicted on Figure 5. For example, an industrial fan would typically run in only one direction to circulate air and would therefore only need to be switched on and off. A compressor is another example of a three phase load where the motor simply needs a connection to a three phase AC supply circuit for proper operation. These applications typically use a simple three phase solid state relay, contactor or motor starter switch to apply power simultaneously to all 3 of the motor s windings in response to a single input control signal to the contactor. The power factor for induction motor loads can be quite low (<.6) so there can be a significant shift between the voltage and current of each phase (phase current lags behind the phase voltage). Zero-crossing solid state relays are typically not suitable for such applications as the relay will only turn on when the AC sine wave is close to the zero-crossing point. With three phase AC systems each phase is shifted 120 from the other 2 phases which means Figure 5 - Simple three phase motor that zero voltage SSRs in each phase will turn on sequentially, not simultaneously as needed. Also due to the phase shifts associated with induction motors, the relay may fail to turn on due to insufficient latching current through the output SCRs before the line voltage exceeds the zero-cross window. In some cases, the relay may operate erratically and half-wave or only provide power to one or two phases of the motor. Therefore, random turn-on (sometimes called instantaneous or asynchronous turn-on) solid state relays are recommended. The output of a random turn-on relay will switch power to its load within 100us of the input signal being applied, regardless of the voltage amplitude of the AC sine wave. Thus all three phases will be supplied to the motor simultaneously and phase shifts between current and voltage no longer affect the turn on performance of the solid state relay.
11 Load Current Transient conditions must also be considered when specifying solid state relays for use with motor loads. Depending upon the size of the motor and the load placed upon the motor itself, the inrush current when it is first energized can be 5 to 7 times its normal operating current. This overload which can potentially be as high as the motor s Locked Rotor Amps (LRA) will gradually decrease to its Full Load Amps (FLA) rating over several AC cycles as the motor begins to rotate (see Figure 4 above), but the relay and associated connections must be sized properly to prevent them from being damaged during start-up. Consideration must also be given to the possibility that a motor may stall under certain conditions which would result in line current equal to or greater than the motor s LRA value. In this circumstance, over current protection must be employed to protect both the relay and the motor. Voltage Transient protection is also another consideration for SSRs. Nearly all AC mains carry transients to one degree or another created when loads wired to the same or adjacent circuits are switched. These transients can easily be several thousand volts in amplitude and result in damage to SSRs wired to these lines. For both reliability and safety, it is advisable to provide transient protection for all SSRs controlling 3 phase induction motors. Such protection may be available internal to the SSR, or applied external to the SSR. The most commonly applied devices are MOVs which have very good power dissipation ratings, but are somewhat slow to react to fast transients. However, bi-directional TVS diodes provide very good performance for fast transients although their dissipation ratings are somewhat lower than MOVs. Motor Reversing Applications Some loads such as sun-tracking solar panel systems utilize motors to reposition solar panels throughout the day to follow the path of the sun across the sky. In this application, not only does the motor have to start and stop repeatedly, it must also reverse its direction of rotation to return the panels to their original position in order to greet the sun the following morning. This requires a motor control that not only energizes the motor, but also reverses its direction of rotation when needed. Figure 5 above illustrates a simple wiring diagram for controlling a three phase motor with a contactor. When the contactor is energized it switches the three phases of the AC mains to the motor which then begins to rotate accordingly. It will continue to rotate at a constant speed and direction for as long as the contacts remain closed. However, if the connection of any two phases of the AC mains to the contactor are interchanged (connect L1 to terminal #2 and L2 to terminal #1, for example), the direction of the motor rotation will reverse when it is re-energized. Of course, physically changing the wiring connections on the contactor every time there is a need to change the direction of the motor is impractical. Therefore, a means is needed to do this automatically when a direction command is provided by a controller. Traditionally this was accomplished by using discrete components, multiple mechanical relays or, more conveniently, a three phase motor-reversing contactor. However, mechanical solutions have the same drawbacks associated with any electromechanical device. The most significant of these drawbacks is life expectancy, especially in applications where the motor is repeatedly bumped or inched in order to achieve a specific position.
12 One possible motor-reversing solution that addresses the problems associated with mechanical contacts is the utilization of multiple single-phase solid state relays. As seen in Figure 6, L1 of the AC mains is connected directly to the motor. SSR #1 and SSR #3 connect either L2 or L3 to the second leg of the motor, and SSR #2 and SSR #4 connect either L2 or L3 to the third leg of the motor. When SSRs #1 & #2 are energized, the motor will rotate in one direction. To reverse the direction, SSRs #1 & #2 are de-energized, and SSRs #3 & #4 are energized, effectively swapping the connection of L2 and L3 to the motor leads. Figure 6 - Four SSR motor-reversing circuit, with direct connection of the third phase to the motor. Note: Important remarks regarding the use of multiple SSRs in a motor-reversing application: 1) Motors used in reversing applications may be mechanically more robust due to the demands placed upon the motor, but electrically, the same issues apply as for induction motors used in simple start/stop applications as noted earlier. 2) The system controlling the SSRs must have an interlock circuit that prevents the forward and reverse relays from turning on simultaneously! Failure to comply with this requirement may result in a phase-to-phase short through the relays. a very dramatic and unwanted effect. 3) Relays with internal over voltage protection must not be used in motor-reversing applications. An internal TVS may switch on the output of the SSR when subjected to an electrical transient, effectively creating a phase-to-phase short. A Metal Oxide Varistor (MOV) may be placed across the output of each SSR to provide protection from transients. 4) A fifth SSR can be used to switch the third phase of the motor if this is required by the application. It is not necessary for this relay to be part of the interlock circuit directly, but it must be energized at the same time as either the forward or reverse relays to prevent the motor from being damaged when only 2 phases are energized.
13 Another and generally preferred solution for many motor reversing applications is to utilize a motor-reversing solid state relay. A motor-reversing SSR offers two significant advantages over the methods discussed previously: 1) all four SSRs are contained in one industry-standard three phase SSR package thus minimizing wiring connections; 2) the interlock circuit is already built into the SSR. As can be seen in figure 7, two of the three phases are wired through a motorreversing SSR and the third phase is connected directly to the motor. When a logic signal is applied to the forward control terminal, the SSR switches L1 and L2 directly to the motor. When the signal is removed from the forward control terminal and applied to the reverse control terminal, the SSR switches the connection of L1 and L2, which reverses the direction of the motor. If a logic signal is simultaneously placed on the forward and reverse control terminals, the SSR will shut off or remain off. External MOVs can be added to the circuit to provide additional protection from over voltage conditions if they are not already included with the reversing SSR. As demonstrated in Figure 7, the Reversing SSR has 4 separate output circuits to provide the motor-reversing function and therefore 4 MOVs are required (regardless of whether they are external or already built into the relay). Also, as with any electrical circuit, proper fusing and a suitable disconnect from the AC mains is required. Figure 7 - Simplified Motor-Reversing SSR wiring diagram.
14 Selecting SSRs for 3 Phase Induction Motor Applications To select an SSR for a 3 phase induction motor application, the following information is required: Motor Power in HP, watts or KVA Nominal AC 3 Phase supply voltage Operating ambient temperature for the SSR in the application Operation mode: start/stop or reversing For most motor loads, if the motor s power factor is not known, it is a common practice to assume the load s power factor (Cos Θ) It is also prudent to include a 20% safety margin to allow for line, load and operational variances. Once this information is known, one of the following processes can be used to determine the SSR rating for the application and then a suitable model with that rating can be selected: A) The most straight forward approach is to coordinate the SSR s horse power/voltage rating with the motor s horse power/operating voltage rating. This approach, excepting details related to the mounting, heat sinking and control voltage selection for the SSR, pretty much eliminates most calculations in the selection process because the transient currents have already been accommodated in the relay rating. B) Calculate the motor s worst case line current requirements under start and run conditions at its operating voltage, and then select a suitable SSR based upon its output current/voltage rating. In this case, some calculations using formulas presented earlier in this paper may be required. Table 3 illustrates typical UL recognized horse power and FLA current ratings for various 3 phase type motor start/stop and reversing SSRs. HP Ratings at Three phase SSR, HP/FLA Reversing SSR, HP/FLA D53TP25X D53TP50X CTRX6025 D53RV25X D53RV50X 240V 1HP/4.2A 3HP/9.6A - 1HP/4.2A 3HP/9.6A 480V 3HP/4.8A 7.5HP/11A 3HP/4.8A 3HP/4.8A 7.5HP/11A 600V 5HP/6.1A 10HP/11A Table 3 - Crydom three phase SSR UL motor controller ratings.
15 Table 4 illustrates typical UL recognized horse power and FLA current rating for various single phase SSRs suitable for 3 phase motor start/stop and reversing applications HP Ratings at CWD CWD CWD CWD V 3HP/17A 5HP/28A 7.5HP/40A 10HP/50A 480V 5HP/14A 7.5HP/21A 10HP/26A 15HP/34A Table 4 - Crydom single phase SSR UL motor controller ratings. In the example sited earlier for a 5 HP 440 VAC three phase motor, the line currents were calculated to be 8.2 amps. The addition of a 20% safety margin results in a suggested SSR rating of 9.8 amps per phase or channel. Using method (A) above and Table 3 for 3 phase SSRs, there is one matching SSR and 1 matching reversing SSR rated >440 VAC. Note that in each case the rated FLA current is greater than the example s calculated current of 9.8 amps. Using Table 4 for single phase SSRs, there are several possible matches. Again, the FLA current rating for each is greater than the example s 9.8 amps, so an array of 3 (or 4 SSRs for reversing applications) could be selected to control the example 3 phase motor load. Considerations for SSR power dissipation Once the minimum SSR output rating for the application is determined based upon horse power or FLA, the power dissipation in the SSR(s) and the ambient temperature that will be present in the SSRs mounting area must be determined to calculate its effect on the required rating. Most AC output SSRs will have an average on-state forward voltage drop of between 1.0 and 1.2 volts. The effect of this voltage drop is that 1 to 1.2 watts of energy are generated in the power assembly of the SSR per ampere of conducted load current, which must be dissipated into the surrounding environment. Heat Sinks are the most common means of facilitating this dissipation. The solid state relay may be mounted directly to a heat sink if it is purchased as an accessory component, or it may be integral to the SSR itself. Using the previous example and assuming an average SSR forward voltage drop of 1.1 volts, the total power dissipation for the SSRs in the three phase circuit would be calculated as follows: P SSR = V f x I L x 3 (7) P SSR = 1.1 x 9.8 x 3 P SSR = 32.5 watts
16 Therefore, 32.5 watts will have to be dissipated into the ambient surrounding the SSR regardless of whether the SSR has an integral or external heat sink. Note: In a motor reversing application with the same capacity motor, the total power dissipation in the SSR would be 67% of that calculated for the start/stop operation since only 2 SSRs rather than 3 are used at any one time. The same would be true for three phase applications where only two lines are switched by 2 single phase or 1 dual output SSR. Selecting three phase SSRs with Integral Heat Sinks SSRs with integral heat sinks are the easiest to select because most of the thermal calculations have already been considered in its ratings. Figure 8 is a typical output current rating verses ambient temperature curve for an SSR with integral heat sink. In the example sited above for an Induction motor with calculated line current of 9.8 amps per phase or 29.4 amps in total for all three phases, the SSR represented by this diagram will operate within its allowed ratings up to about 80 C ambient. Should the ambient temperature surrounding the SSR in the application exceed 80 C, a different SSR/heat sink combination with higher rating must be selected. Figure 8 - SSR w/integral Heat Sink Total Combined Output Rating verse Ambient Temperature Three phase SSRs with integral heat sinks are available in either DIN rail mount or panel mount. In either case, the selection process is the same. The line current has to be determined along with line voltage and operational ambient temperature. Once this is done, it is a fairly simple matter to consult product specifications and review the output current verses ambient temperature charts similar to Figure 8. In the application example given above of a 5HP Induction motor with 9.8 amps line current per phase, a three phase SSR rated at least 10 amps, FLA, per channel must be selected. However, ambient temperature effects whether the heat sink supplied with the SSR is sufficient to allow proper operation in the example applications 40 C ambient.
17 Utilizing the chart in Figure 8 as an example, indicates that the SSR represented by the chart would easily operate in a 40 C ambient. However, if the application ambient were higher than 80 C, then an SSR with a higher output rating verses ambient temperature would have be selected (e.g. 25 amps/phase SSR). When selecting a Crydom DIN rail mounted or Panel Mounted SSR for three phase motor loads, there are two possible options as shown in Table 5 below. One CTRD6025R DIN rail mounted SSR One HS053-D53TP25D-10 panel mounted SSR/Heat Sink assembly Note: Above part numbers are examples only. There is a large selection of suitably rated SSRs available from Crydom. Table 5 - SSR options to implement three phase Induction Motor load control using DIN rail mounted or panel mounted SSR(s) with integral heat sinks.
18 Selecting three phase SSRs with Separate External Heat Sinks In those cases where the SSR(s) and heat sink are separate components, it becomes necessary to determine the required minimum value heat sink rating to maintain a safe operating temperature for the SSR. There are numerous technical papers including Crydom White Papers that describe this process in detail and Crydom also provides a simple Heat Sink Selection Tool on its web site for this purpose should additional information be needed. Generally, most AC output SSRs have a maximum allowed internal operating temperature of 125 C or less. Consequently, the selection of the SSR is determined by the combination of the SSRs power dissipation due to the application load current, operating ambient temperature where the SSR is mounted, and SSR thermal impedance specification. The minimum heat sink rating (R ΘHS ) in degrees C per watt for a given application can be calculated as follows: R ΘHS = ((125 Tamb) / P SSR ) - R ΘSSR - R ΘTI (8) Where: Tamb = the operating ambient temperature in C P SSR = the total power in watts dissipated in the SSR(s) for all 3 phases R ΘSSR = specified SSR thermal impedance C/W R ΘTI = specified thermal impedance of the thermal interface material placed between the SSR and heat sink R ΘSSR Note: the thermal interface material is placed between the mounting surface of the SSR and the heat sink to compensate for any surface irregularities that might increase thermal impedance and diminish SSR performance. These materials generally have a thermal impedance of between 0.03 and 0.1 C/W depending on their composition and thickness. In the application example given previously of a 5 HP Induction Motor with 9.8 amps line current per phase, and a three phase SSR rated at 10 amps per channel operating in a 40 C ambient with R ΘSSR of 0.25 C/W, using formula (8), the minimum heat sink rating would be calculated as follows: R ΘHS = (( / 32.5) R ΘHS = 2.3 C/W
19 Figure 9 is a representative thermal derating curve for a typical three phase panel mounted SSR showing its allowed output rating per phase for a motor load verses ambient temperature for various heat sink ratings. Figure 9 - Output Rating per Phase of a three phase SSR verses Ambient Temperature In the example calculation and SSR selection above, the calculation determined that a heat sink with at least a 2.3 C/W rating was required. More efficient heat sinks with lower numerical value thermal impedances can of course be utilized with the beneficial effect of lowering SSR operating temperatures, improved reliability and life expectancy. When selecting a Crydom Panel Mounted SSR for three phase motor loads there are three possible options as shown in Table 6 below. The following options are deemed suitable for the current example: One D53TP10D-10 three phase SSR + HS103 Three CWD single-phase SSR + HS103 One CC4825D2VR Dual SSR + HS201 Note: Above part numbers are examples only. There is a large selection of suitably rated SSRs available from Crydom. Once the SSR has been selected the next step is to use the Heat Sink Selection Tool to complete the SSR and Heat sink selection.
20 Table 6 - SSR options to implement three phase Induction Motor load control using Panel mounted SSR(s) with external heat sink.
21 SUMMARY Solid State Relays, whether single or three phase, are ideal for the control of three phase induction motors. Proper selection of the SSR for any given application requires knowledge of the motor s power rating, operation voltage, ambient temperature and wiring configuration/function. A variety of SSRs are available for a wide range of operating conditions up to 600 VAC and > 50 amps per phase, in either Panel or DIN rail mount configurations. Heat sinking is required for the proper operation of SSRs in all applications and technical information on their selection is readily available. For additional information on Solid State Relays with Motor Controller ratings, contact Crydom or visit Copyright 2011, All rights reserved. The materials and information on this document are intended for informational purposes only. Materials are copyrighted and are protected by worldwide copyright laws and treaty provisions. They may not be copied, reproduced, modified, published, uploaded, posted, transmitted, or distributed in any way, without Crydom's prior written permission. Crydom does not warrant the accuracy or completeness of the information, text, graphics, links or other items contained within this document. Crydom may make changes to these materials, or to the products described therein, at any time without notice. Crydom makes no commitment to update the Materials.
How To Select A Solid State Relay For A Three Phase Resistive Load
pero 1 Three Phase Solid State Relays & Their Application in Three Phase Heating Circuits By Paul Bachman, Fellow Engineer, Dr. Oscar Montero, R&D Manager, and Doug Sherman, FSAE Manager, Crydom, Inc.
Figure 1 - Crydom 3RHP Three-phase Hybrid Solid State Contactor. Crydom Inc.
Crydom RHP Series 3 Phase Hybrid Solid State Contactor By Paul Bachman Fellow Engineer, Crydom, Inc. ABSTRACT Solid State Relays and Contactors (SSRs) have been available in one form or the other for over
Solid-State Relays (SSRs) vs Electromechanical Relays (EMRs)
Oct 2010 Solid-State Relays (SSRs) vs Electromechanical Relays (EMRs) A study on worldwide relays market found the market size of solid state relays to be between $200M and $600M, which represent 17% of
The Effect of Forced Air Cooling on Heat Sink Thermal Ratings
zpero 1 The Effect of Forced Air Cooling on Heat Sink Thermal Ratings By Paul Bachman, Fellow Engineer & Ronnie Haiduk, Applications Engineer, Crydom, Inc. ABSTRACT A heat sink s ability to dissipate thermal
DC Motor control Reversing
January 2013 DC Motor control Reversing and a "Rotor" which is the rotating part. Basically there are three types of DC Motor available: - Brushed Motor - Brushless Motor - Stepper Motor DC motors Electrical
SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS
SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS UNIT OBJECTIVES After studying this unit, the reader should be able to Describe the different types of open single-phase motors used to drive
RC NETWORKS SALES GUIDE
SALES GUIDE INTRODUCTION TO Recent developments in electronic equipment have shown the following trends: Increasing demands for numerical control machines, robotics and technically advanced appliances
Line Reactors and AC Drives
Line Reactors and AC Drives Rockwell Automation Mequon Wisconsin Quite often, line and load reactors are installed on AC drives without a solid understanding of why or what the positive and negative consequences
FREQUENCY CONTROLLED AC MOTOR DRIVE
FREQUENCY CONTROLLED AC MOTOR DRIVE 1.0 Features of Standard AC Motors The squirrel cage induction motor is the electrical motor motor type most widely used in industry. This leading position results mainly
Section 10. Application Manual for NEMA Motors. Special Applications
Special Applications 1 Power Factor Correction 1 Methods of Starting 3AC Induction Motors 5 3 Duty Cycles and Inertia 3 4 Horsepower Determination 30 5 Formulas and General Data 34 Power Factor Correction
EET272 Worksheet Week 8
EET272 Worksheet Week 8 answer questions 1-5 in preparation for discussion for the quiz on Monday. Finish the rest of the questions for discussion in class on Wednesday. Question 1 Questions We will now
WYE-DELTA AND SOLID STATE STARTER APPLICATION GUIDE
WHITE PAPER WYE-DELTA AND SOLID STATE STARTER APPLICATION GUIDE EXPLANATION AND ASSISTANCE FOR APPLYING SOLID STATE SOFT STARTERS IN TRADITIONAL REDUCED VOLTAGE APPLICATIONS Introduction..............................................................2
AND8008/D. Solid State Control Solutions for Three Phase 1 HP Motor APPLICATION NOTE
Solid State Control Solutions for Three Phase 1 HP Motor APPLICATION NOTE INTRODUCTION In all kinds of manufacturing, it is very common to have equipment that has three phase motors for doing different
Rotary Phase Converters
FACTS from Ronk Electrical Industries, Inc. Bulletin 11981 Rotary Phase Converters ROTOVERTER Pat. No. 3,670,238 ROTO-CON Pat. No. 4,158,225 What are the ROTO-CON and ROTOVERTER power converters? The ROTO-CON
Chapter 5. Components, Symbols, and Circuitry of Air-Conditioning Wiring Diagrams
Chapter 5 Components, Symbols, and Circuitry of Air-Conditioning Wiring Diagrams Objectives Upon completion of this course, you will be able to: Explain what electrical loads are and their general purpose
Principles of Adjustable Frequency Drives
What is an Adjustable Frequency Drive? An adjustable frequency drive is a system for controlling the speed of an AC motor by controlling the frequency of the power supplied to the motor. A basic adjustable
SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original
SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original A motor starter is a combination of devices to allow an induction motor to start, run and stop according
PowerFlex Dynamic Braking Resistor Calculator
Application Technique PowerFlex Dynamic Braking Resistor Calculator Catalog Numbers 20A, 20B, 20F, 20G, 22A, 22B Important User Information Solid-state equipment has operational characteristics differing
Digital Energy ITI. Instrument Transformer Basic Technical Information and Application
g Digital Energy ITI Instrument Transformer Basic Technical Information and Application Table of Contents DEFINITIONS AND FUNCTIONS CONSTRUCTION FEATURES MAGNETIC CIRCUITS RATING AND RATIO CURRENT TRANSFORMER
Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager
Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager Introduction There is a growing trend in the UPS industry to create a highly efficient, more lightweight and smaller UPS
VOLTAGE REGULATOR AND PARALLEL OPERATION
VOLTAGE REGULATOR AND PARALLEL OPERATION Generator sets are operated in parallel to improve fuel economy and reliability of the power supply. Economy is improved with multiple paralleled generators by
GENERATOR SELECTION. a. Three phase - 120/208V, 3 phase, 4W wye; 277/408, 3 phase, 4W wye; * 120/240V 3 phase, 4W Delta
GENERATOR SELECTION Generators must be sized to handle their load based on the continuous KW, kilowatt load, and KVA, kilovoltamp load, and the worst case starting load KW + KVA. They must be derated for
Electric Motor Brake Horsepower Calculations
Electric Motor Brake Horsepower Calculations By Norm Christopherson These motor calculations are contained here as they apply to the changing conditions of the blower motor when pulley adjustments are
Single Phase Soft Starter
Single Phase Soft Starter Installation & Operating Manual 6/02 Table of Contents Section 1 General Information................................................... 1 1 General Description................................................
Variable Transformers Product Design & Engineering Data
Variable Transformers Product Design & Engineering Data Product Design & Engineering Data Type 1010B Cutaway General Information STACO ENERGY PRODUCTS CO. is a leading manufacturer of variable transformers,
Variable Frequency Drives - a Comparison of VSI versus LCI Systems
Variable Frequency Drives - a Comparison of VSI versus LCI Systems Introduction TMEIC is a leader in the innovative design and manufacture of large ac variable f requency drive systems. TMEIC has been
Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw
4 937 DESIO Current valve for AC 24 V pulse/pause control of electrical loads up to 30 kw SEA45.1 Use The current valve is used for the control of electric heating elements in heating, ventilation and
Specifying a Variable Frequency Drive s
Specifying a Variable Frequency Drive s Put on by Bruce Reeves and Jeremy Gonzales Dykman Electrical Covering the Western US For all of your VFD and Soft Start and Motor Needs How To Specify a Variable
Speed Control Methods of Various Types of Speed Control Motors. Kazuya SHIRAHATA
Speed Control Methods of Various Types of Speed Control Motors Kazuya SHIRAHATA Oriental Motor Co., Ltd. offers a wide variety of speed control motors. Our speed control motor packages include the motor,
Three-phase AC circuits
Three-phase AC circuits This worksheet and all related files are licensed under the Creative Commons Attribution License, version 1.0. To view a copy of this license, visit http://creativecommons.org/licenses/by/1.0/,
Torque control MSF Softstarter
Torque control MSF Softstarter INTRODUCTION Soft starting an AC motor refers to any one of several starting methods that limit the starting current and torque of the motor. The method discussed in this
Technical catalogue. Modular DIN rail components Installation contactors
Technical catalogue Modular DIN rail components Installation contactors Installation Contactors Overview... ESB Installation Contactors 0 A / AC-/AC-7a ESB0...4 4 A / AC-/AC-7a ESB4...5 40 A / AC-/AC-7a
C Standard AC Motors
C Standard AC Standard AC C-1 Overview, Product Series... C-2 Constant... C-9 C-21 C-113 Reversible C-147 Overview, Product Series Constant Reversible Electromagnetic Brake C-155 Electromagnetic Brake
SYNCHRONOUS MACHINES
SYNCHRONOUS MACHINES The geometry of a synchronous machine is quite similar to that of the induction machine. The stator core and windings of a three-phase synchronous machine are practically identical
Power surges can also be generated by equipment in your facility such as:
Power Quality Surge Suppressors What is Surge Protection A surge suppressor can be the first and best defense against the instant or gradual destruction of electrical equipment. Compared to the replacement
Fundamentals of Inverter Fed Motors
Fundamentals of Inverter Fed Motors Technical Manual 10/02 MN780 Contents Page The Growing Use Of Inverters.................................................................. 1 How Inverters Affect Motors....................................................................
What Is Regeneration?
What Is Regeneration? Braking / Regeneration Manual Regeneration Overview Revision 1.0 When the rotor of an induction motor turns slower than the speed set by the applied frequency, the motor is transforming
AC-Synchronous Generator
Design Description AC Generators come in two basic types synchronous and non-synchronous. Synchronous generators lock in with the fundamental line frequency and rotate at a synchronous speed related to
Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller
Overview/Modes of Operation Bulletin 150 Smart Motor Controller The SMC-3 is a compact, simple to use, solid-state motor controller designed to operate 3-phase motors. It features a built-in overload relay
APPLICATION NOTE TESTING PV MICRO INVERTERS USING A FOUR QUADRANT CAPABLE PROGRAMMABLE AC POWER SOURCE FOR GRID SIMULATION. Abstract.
TESTING PV MICRO INVERTERS USING A FOUR QUADRANT CAPABLE PROGRAMMABLE AC POWER SOURCE FOR GRID SIMULATION Abstract This application note describes the four quadrant mode of operation of a linear AC Power
3) What is the difference between "Insulating", "Isolating", and "Shielded Winding" transformers?
Tyco Electronics Corporation Crompton Instruments 1610 Cobb International Parkway, Unit #4 Kennesaw, GA 30152 Tel. 770-425-8903 Fax. 770-423-7194 1) What is a transformer and how does it work? A transformer
Product Data Bulletin
Product Data Bulletin Power System Harmonics Causes and Effects of Variable Frequency Drives Relative to the IEEE 519-1992 Standard Raleigh, NC, U.S.A. INTRODUCTION This document describes power system
Application Information
Moog Components Group manufactures a comprehensive line of brush-type and brushless motors, as well as brushless controllers. The purpose of this document is to provide a guide for the selection and application
Three phase circuits
Three phase circuits THREE PHASE CIRCUITS THREE-PHASE ADVANTAGES 1. The horsepower rating of three-phase motors and the kva rating of three-phase transformers are 150% greater than single-phase motors
Manual motor starter MS116
Data sheet Manual motor starter MS116 Manual motor starters are electromechanical devices for motor and circuit protection. These devices offer local motor disconnect means, manual ON/ OFF control, and
POWER AND VOLTAGE RATING
POWER AND VOLTAGE RATING SCOPE: The purpose of this document is to take the confusion out of power and voltage ratings in specifications and in product information publications. This will be accomplished
Motor Protection Voltage Unbalance and Single-Phasing
Motor Protection Voltage Unbalance and Single-Phasing Cooper Bussmann contributes the following information, which is an excerpt from their 190-page handbook SPD Selecting Protective Devices Based on the
ABB 1. Three-phase monitoring relay CM-PFS. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories. Application.
1SR 430 824 F9300 Features Monitoring of three-phase mains for phase sequence and failure Powered by the measuring circuit 2 c/o (SPDT) contacts 1 LED for status indication Approvals R: yellow LED - relay
DIRECT CURRENT GENERATORS
DIRECT CURRENT GENERATORS Revision 12:50 14 Nov 05 INTRODUCTION A generator is a machine that converts mechanical energy into electrical energy by using the principle of magnetic induction. This principle
Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000
Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000 Description Firetrol FTA1000 Full Voltage Fire Pump Controllers are intended for use with electric motor driven fi re pumps
Current and Temperature Ratings
Document 361-1 Current and Temperature Ratings Introduction This application note describes: How to interpret Coilcraft inductor current and temperature ratings Our current ratings measurement method and
Equipment: Power Supply, DAI, Synchronous motor (8241), Electrodynamometer (8960), Tachometer, Timing belt.
Lab 9: Synchronous motor. Objective: to examine the design of a 3-phase synchronous motor; to learn how to connect it; to obtain its starting characteristic; to determine the full-load characteristic of
Phase-Control Alternatives for Single-Phase AC Motors Offer Smart, Low-Cost, Solutions Abstract INTRODUCTION
Phase-Control Alternatives for Single-Phase AC Motors Offer Smart, Low-Cost, Solutions by Howard Abramowitz, Ph.D EE, President, AirCare Automation Inc. Abstract - Single Phase AC motors continue to be
AMFA-27 AMFA-29. Operator s Manual & Installation Instructions. Rev. 2.5
AMFA-27 AMFA-29 Operator s Manual & Installation Instructions Rev. 2.5 Date: 17 July, 2010 Permanently-connected, utility Interactive, single-phase, inverters Model AMFA-27 WIND TURBINE INVERTER (240 VAC
Synchronous motor. Type. Non-excited motors
Synchronous motor A synchronous electric motor is an AC motor in which the rotation rate of the shaft is synchronized with the frequency of the AC supply current; the rotation period is exactly equal to
The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies
The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies DATE: November 17, 1999 REVISION: AUTHOR: John Merrell Introduction In some short circuit studies, the X/R ratio is ignored when comparing
2. A conductor of length 2m moves at 4m/s at 30 to a uniform magnetic field of 0.1T. Which one of the following gives the e.m.f. generated?
Extra Questions - 2 1. A straight length of wire moves through a uniform magnetic field. The e.m.f. produced across the ends of the wire will be maximum if it moves: a) along the lines of magnetic flux
Effective: September 10, 2006 Vermont Attachment 1 to Rule 5.500 Public Service Board Page 1 of 6
Public Service Board Page 1 of 6 STANDARD APPLICATION FOR INTERCONNECTION OF GENERATION RESOURCES IN PARALLEL TO THE ELECTRIC SYSTEM OF: (Interconnecting Utility) Preamble and Instructions: An owner of
ETZGAR CONVEYOR COMPANY Controls Section v12.05
Section 7 Controls Page Description 7-1 Controls Index 7-2 Motor Data, Enclosure Rating and Abbreviations 7-3 Controls Safety Guidelines 7-4 Fixed Speed Controls Packages 7-5 Three Phase AC Variable Speed
Power Supplies 3. SDN-P DIN Rail Series
SDN-P DIN Rail Series The SDN DIN Rail power supplies provide industry leading performance. Sag Immunity, transient suppression and noise tolerant, the SDN series ensures compatibility in demanding applications.
Understanding the Alternator
http://www.autoshop101.com THIS AUTOMOTIVE SERIES ON ALTERNATORS HAS BEEN DEVELOPED BY KEVIN R. SULLIVAN PROFESSOR OF AUTOMOTIVE TECHNOLOGY AT SKYLINE COLLEGE SAN BRUNO, CALIFORNIA ALL RIGHTS RESERVED
Power Supplies. 1.0 Power Supply Basics. www.learnabout-electronics.org. Module
Module 1 www.learnabout-electronics.org Power Supplies 1.0 Power Supply Basics What you ll learn in Module 1 Section 1.0 Power Supply Basics. Basic functions of a power supply. Safety aspects of working
Sentron Series Circuit Breakers
Sentron Series Circuit Breakers Siemens Sentron Series circuit breakers are available in nine frame sizes: ED, FD, JD, LD, LMD, MD, ND, PD, and RD. Sentron Series circuit breakers have a wide range of
SHIP SERVICE GENERATORS (AC)
CHAPTER 14 SHIP SERVICE GENERATORS (AC) INTRODUCTION All generators change mechanical energy into electrical energy. This is the easiest way to transfer power over distances. Fuel is used to operate the
Diode Applications. by Kenneth A. Kuhn Sept. 1, 2008. This note illustrates some common applications of diodes.
by Kenneth A. Kuhn Sept. 1, 2008 This note illustrates some common applications of diodes. Power supply applications A common application for diodes is converting AC to DC. Although half-wave rectification
7-41 POWER FACTOR CORRECTION
POWER FTOR CORRECTION INTRODUCTION Modern electronic equipment can create noise that will cause problems with other equipment on the same supply system. To reduce system disturbances it is therefore essential
CONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE. General purpose single phase thyristors and solid state relays Product data.
425 CONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE General purpose single phase thyristors and solid state relays Product data abc 425 EUROCUBE A complete range of low cost solid state relays and
Three-phase monitoring relay CM-PFE
Data sheet Three-phase monitoring relay CM-PFE The CM-PFE is a three-phase monitoring relay that monitors the phase parameter phase sequence and phase failure in three-phase mains. 2CDC 251 005 S0012 Characteristics
SAFETY PRECAUTIONS AND INSTRUCTIONS FOR USE OF TECHNICAL INFORMATION
SAFETY PRECAUTIONS AND INSTRUCTIONS FOR USE OF TECHNICAL INFORMATION Please read and understand the product instruction manual before installing, servicing or operating Yaskawa products. Technical content
How to Turn an AC Induction Motor Into a DC Motor (A Matter of Perspective) Steve Bowling Application Segments Engineer Microchip Technology, Inc.
1 How to Turn an AC Induction Motor Into a DC Motor (A Matter of Perspective) Steve Bowling Application Segments Engineer Microchip Technology, Inc. The territory of high-performance motor control has
Sierra Dual 24 Volt Brushless DC Motor Controller Product Specification
Sierra Dual 24 Volt Brushless DC Motor Controller Product Specification Assembly 025A0215 600A0942 Rev. A May 14, 2012 025A0215 Brushless DC Motor Controller Page 1 Revision History ECN # Date Rev Description
BOWL ASSEMBLY SELECTION Select impeller in exactly the same manner as for lineshaft type pump. Note comments under WELL SIZE.
SUBMERSIBLE PUMP selection A submersible pump consists of the following basic elements: < Bowl Assembly < Motor < Cable < Drop Pipe < Surface Plate (with)(without) discharge elbow DATA REQUIRED FOR SELECTION
INSTALLATION AND MAINTENANCE INSTRUCTIONS FOR THREE PHASE INDUCTION MOTORS
INSTALLATION AND MAINTENANCE INSTRUCTIONS FOR THREE PHASE INDUCTION MOTORS Frames 143T - 449TZ 5100 North IH 35 Round Rock, Texas 78681 Phone: 800-451-8798 512-255-4141 Fax: 512-244-5512 RECEIVING 1. Check
8 Speed control of Induction Machines
8 Speed control of Induction Machines We have seen the speed torque characteristic of the machine. In the stable region of operation in the motoring mode, the curve is rather steep and goes from zero torque
SYNCHRONOUS MACHINE TESTING WITH MOTOR CIRCUIT ANALYSIS INSTRUMENTATION
SYNCHRONOUS MACHINE TESTING WITH MOTOR CIRCUIT ANALYSIS INSTRUMENTATION Introduction Howard W. Penrose, Ph.D., CMRP Vice President, Engineering and Reliability Services Dreisilker Electric Motors, Inc.
12S, 14S, 15S Series. Time Delay Relays and Sequencers. Time Delay Relays and Sequencers. Features and Benefits. Switch Actions and Configurations
12S, 14S, 15S Series Time Delay Relays and Sequencers Time Delay Relays and Sequencers The Therm-O-Disc type 12S, 14S and 15S series time delay relays and sequencers are field-proven devices for controlling
3-Phase AC Calculations Revisited
AN110 Dataforth Corporation Page 1 of 6 DID YOU KNOW? Nikola Tesla (1856-1943) came to the United States in 1884 from Yugosiavia. He arrived during the battle of the currents between Thomas Edison, who
MasterINTERFACE 39 Series - Relay interface modules
MasterINTERFACE 39 Series - Relay interface modules Common features Space saving 6.2 mm wide Connections for 16-way jumper link Integral coil indication and protection circuit Secure retention and easy
Drive circuit basics + V. τ e. Industrial Circuits Application Note. Winding resistance and inductance
ndustrial Circuits Application Note Drive circuit basics For a given size of a stepper motor, a limited space is available for the windings. n the process of optimizing a stepper motor drive system, an
38 SERIES. Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A. EMR Electromechanical Relays. Common features. SSR Solid State Relays. 6.
38 Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A 38 Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit 6.2 mm wide EMR - DC, AC or AC/DC
IEC style contactors - long electrical and mechanical life Complete range from mini-contactors to 630 Amp i n d u c t i ve AC3 ra t i n g s Wide
- long al and mechanical life Complete range from mini-contactors to 630 Amp i n d u c t i ve AC3 ra t i n g s Wide range coils +0% to -30% Finger safe terminals Four-pole versions available NO + NC and
Bourns Resistive Products
Bourns Resistive Products Diverse Requirements Drive Innovations to Pulse Resistors Introduction Countless circuits depend on the protection provided by one of the most fundamental types of passive components:
SIZING THE PRIMARY POWER SYSTEM FOR RESISTANCE WELDERS
SIZING THE PRIMARY POWER SYSTEM FOR RESISTANCE S By Jack Farrow, May, 2004 WELDING TECHNOLOGY CORPORATION ABSTRACT Information on how to select the correct size of substation transformer and 480V bus to
..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark...
..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark... TIME MARK CORPORATION 11440 EAST PINE STREET TULSA, OK 74116 USA tel 918 438-1220 fax 918 437-7584 www.time-mark.com
AC Induction Motor Slip What It Is And How To Minimize It
AC Induction Motor Slip What It Is And How To Minimize It Mauri Peltola, ABB Oy, Helsinki, Finland The alternating current (AC) induction motor is often referred to as the workhorse of the industry because
New High Current MOSFET Module Offers 177 µω R DS(on)
ew High Current Offers 177 µω R D(on) By William C. Kephart, Eric R. Motto Application Engineering owerex Incorporated Abstract This paper describes a new family of high current modules optimized for industrial
D-Line Contactors, Overload Relays and Accessories
D-Line Contactors, Overload Relays and Accessories Class 850 CONTENTS Description......................................................Page General Information...............................................
Data Sheet. AC Industrial Electric Motors
Data Pack B Issued ovember 2005 1502325812 Data Sheet AC Industrial Electric Motors Standards organisations The RS-ABB range of ac induction motors is produced to common European standards, these being
Introduction. Upon completion of Basics of AC Motors you should be able to:
Table of Contents Introduction...2 AC Motors...4 Force and Motion...6 AC Motor Construction... 12 Magnetism... 17 Electromagnetism... 19 Developing a Rotating Magnetic Field...24 Rotor Rotation...29 Motor
However, industrial applications may utilize a relay, which short-circuits the ICL path after the inrush sequence.
Application note for Inrush Current Limiters (ICL) Turning on electrical devices generally cause high inrush currents which can damage electronic components and cause interruption of the line voltage if
ATTACHMENT F. Electric Utility Contact Information Utility Name. For Office Use Only
ATTACHMENT F CATEGORY 2 GENERATOR INTERCONNECTION APPLICATION FOR ALL PROJECTS WITH AGGREGATE GENERATOR OUTPUT OF MORE THAN 20 KW BUT LESS THAN OR EQUAL TO 150 KW Also Serves as Application for Category
Step Voltage Regulators
Step Voltage Regulators Don Wareham Field Application Engineer Today s Agenda Introduction Voltage Regulator theory Voltage Regulator application considerations Installation and proper bypassing Wrap-up/questions
Lab 8: DC generators: shunt, series, and compounded.
Lab 8: DC generators: shunt, series, and compounded. Objective: to study the properties of DC generators under no-load and full-load conditions; to learn how to connect these generators; to obtain their
KINETIC ENERGY RECOVERY SYSTEM BY MEANS OF FLYWHEEL ENERGY STORAGE
ADVANCED ENGINEERING 3(2009)1, ISSN 1846-5900 KINETIC ENERGY RECOVERY SYSTEM BY MEANS OF FLYWHEEL ENERGY STORAGE Cibulka, J. Abstract: This paper deals with the design of Kinetic Energy Recovery Systems
Unit 33 Three-Phase Motors
Unit 33 Three-Phase Motors Objectives: Discuss the operation of wound rotor motors. Discuss the operation of selsyn motors. Discuss the operation of synchronous motors. Determine the direction of rotation
Equipment: Power Supply, DAI, Wound rotor induction motor (8231), Electrodynamometer (8960), timing belt.
Lab 13: Wound rotor induction motor. Objective: to examine the construction of a 3-phase wound rotor induction motor; to understand exciting current, synchronous speed and slip in this motor; to determine
AF09-30-22-.. / AF09Z-30-22-.. 2-stack 3-pole Contactors AC / DC Operated - with Screw Terminals
Technical Datasheet 1SBC101403D0201 24/03/11 AF09-30-22-.. / AF09Z-30-22-.. 2-stack 3-pole Contactors AC / DC Operated - with Screw Terminals AF09(Z) contactors are used for controlling power circuits
PROPER SELECTION OF CONTROL CIRCUIT TRANSFORMERS WHITE PAPER BULLETIN 1497, 1497A, AND 1497B
WHITE PAPER PROPER SELECTION OF CONTROL CIRCUIT TRANSFORMERS BULLETIN 1497, 1497A, AND 1497B CONTROL CIRCUIT TRANSFORMERS The proper selection of the control circuit transformers is important for suitable
The Basics of Digital Multimeters
IDEAL INDUSTRIES INC. The Basics of Digital Multimeters A guide to help you understand the basic Features and Functions of a Digital Multimeter. Author: Patrick C Elliott Field Sales Engineer IDEAL Industries,