Appendix J: Engineering Specification for Electrical Heat-Tracing Systems
|
|
|
- Katrina Porter
- 9 years ago
- Views:
Transcription
1 Appendix J: Engineering Specification for Electrical Heat-Tracing Systems Contents 1 Scope Codes, Approvals, and Standards Materials Engineering Testing Scope This specification covers the requirements of materials and support services for heat-tracing systems supplied by the vendor. Neither the supply of the materials related to the connection of the power supply nor the installation of the entire system is part of this specification. 2 Codes, Approvals, and Standards The electric heat-tracing system shall conform to this specification. It shall be designed, manufactured, and tested in accordance with the applicable requirements of the latest edition of the following codes and standards. FM Factory Mutual Research Corporation IEEE 515 Institute Of Electrical and Electronics Engineers NEC U.S. National Electric Code (NFPA 70) NEMA National Electrical Manufacturers Association NESC National Electrical Safety Code UL 746B Underwriters Laboratories, Inc. ANSI American National Standards Institute IEC 216 International Electro-Mechanical Commission BS6351 British Standard for Electrical Surface CSA CSA International Tyco Thermal Controls (800)
2 1. Self- Regulating 3 Electric Heat Trace System Materials 2. Power- Limiting 3.1 Self-Regulating The decision between self-regulating heating cable and power-limiting heating cable shall be made considering the need for a T-rating that is not dependent on the specific application (this is provided by self-regulating heating cables) and the number of runs of heat tracing required for the application. In some applications power-limiting heaters can use fewer runs due to higher power output at higher temperatures. A. Self-regulating heating cable shall vary its power output relative to the temperature of the surface of the pipe or the vessel. The cable shall be designed such that it can be crossed over itself and cut to length in the field. B. Self-regulating heating cable shall be designed for a useful life of 20 years or more with power on continuously, based on the following useful life criteria: 1. Retention of at least 75 percent of rated power after 20 years of operation at the maximum published continuous exposure (maintain) temperature. 2. Retention of at least 90 percent of rated power after 1000 hours of operation at the maximum published intermittent exposure temperature. The testing shall conform to UL 7468, IEC Part 1. C. A warranty against manufacturing defects for a period of 10 years shall be available. D. All cables shall be capable of passing a 2.5 kv dielectric test for one minute (ASTM 2633) after undergoing a 0.5 kg-m impact (BS 6351, Part 1, ) FREEZE-PROTECTION SYSTEMS 3. Mineral Insulated 4. Longline 5. Tubing Bundles 6. Tank 7. Snow and Ice A. The heating cable shall consist of two 16 AWG or larger nickel-plated copper bus wires, embedded in a self-regulating polymeric core that controls power output so that the cable can be used directly on plastic or metallic pipes. shall have a temperature identification number (T-rating) of T6 (185 F or 85 C) without use of thermostats. B. A ground-fault protection device set at 30 ma, with a nominal 100-ms response time, shall be used to protect each circuit. C. The heating cable shall have a tinned copper braid with a resistance less than the heating cable bus wire resistance as determined in type test (ASTM, B193, Sec. 5). The braid shall be protected from chemical attack and mechanical abuse by a modified polyolefin or fluoropolymer outer jacket. D. In order to provide rapid heat-up, to conserve energy, and to prevent overheating of fluids and plastic pipe, the heating cable shall have the following minimum self-regulating indices: Table G.1 Minimum Self-Regulating Indices Cable S.R. Index (W/ F) S.R. Index (W/ C) 3 W/ft W/ft W/ft W/ft The self-regulating index is the rate of change of power output in watts per degree Fahrenheit or watts per degree Celsius, as measured between the temperatures of 50 F (10 C) and 100 F (38 C) and confirmed by the type test and published data sheets. (800) Tyco Thermal Controls Control and Monitoring 9. Heat Trace Panel 10.Engineered Products 11.Steam Tracing 12.Technical Data Sheets 13. Appendices 14.Index
3 E. In order to ensure that the self-regulating heating cable does not increase power output when accidentally exposed to high temperatures, resulting in thermal runaway and self-ignition, the cable shall produce less than 0.5 watts per foot (1.64 watts per meter) when energized and heated to 350 F (177 C) for 30 minutes. After this test, if the cable is reenergized, it must not have an increasing power output leading to thermal runaway. F. In order to confirm 3.1B, the self-regulating heating cable shall retain at least 90 percent of its original power output after having been cycled 300 times between 5O F (10 C) and 210 F (99 C), allowing at least six minutes of dwell time at each temperature. G. The heating cable shall be Raychem BTV-CT or BTV-CR self-regulating heater, with continuous exposure (maintain) capability up to 150 F (65 C) and intermittent exposure capability up to 185 F (85 C), as manufactured by Tyco Thermal Controls PROCESS-TEMPERATURE MAINTENANCE WITH NO STEAM EXPOSURE A. The heating cable shall consist of two 16 AWG or larger nickel-plated copper bus wires, embedded in a self-regulating polymeric core that controls power output so that the cable has a temperature identification number (T-rating) of T4 (275 F or 135 C) without use of thermostats. B. A ground-fault protection device set at 30 ma, with a nominal 100-ms response time, shall be used to protect each circuit. C. The heating cable shall have a tinned copper braid with a resistance less than the heating cable bus wire resistance as determined in a type test (ASTM, B193, Sec. 5). The braid shall be protected from chemical attack and mechanical abuse by a fluoropolymer outer jacket. D. In order to confirm 3.1B, the self-regulating heating cable shall retain at least 90 percent of its original power output after having been cycled 300 times between 50 F (10 C) and 300 F (110 C), allowing at least six minutes of dwell time at each temperature. E. The heating cable shall be Raychem QTVR-CT self-regulating heater, for continuous and intermittent exposure capability up to 225 F (110 C), as manufactured by Tyco Thermal Controls FREEZE PROTECTION AND PROCESS TEMPERATURE MAINTENANCE WITH STEAM EXPOSURE A. The heating cable shall consist of two 14 AWG nickel-plated copper bus wires, separated by a fluoropolymer spacer and helically wrapped with a self-regulating fluoropolymer fiber that controls power output so that the cable has an unconditional temperature identification number (T-rating) of T2C (446 F or 230 C) or lower without use of thermostats. B. A ground-fault protection device set at 30 ma, with a nominal 100-ms response time, shall be used to protect each circuit. C. The heating cable shall have a tinned copper braid with a resistance less than the heating cable bus wire resistance as determined in a type test (ASTM, B193, Sec. 5). The braid shall be protected from chemical attack and mechanical abuse by a fluoropolymer outer jacket. D. In order to confirm 3.1B, the self-regulating heating cable shall retain at least 90 percent of its original power output after having been cycled 300 times between 50 F (10 C) and 450 F (232 C), allowing at least six minutes of dwell time at each temperature. E. The heating cable shall be Raychem XTV-CT self-regulating heater, for continuous exposure (maintain) capability up to 250 F (121 C) and intermittent exposure capability up to 420 F (215 C or 250 psi steam), as manufactured by Tyco Thermal Controls Tyco Thermal Controls (800)
4 1. Self- Regulating 3.2 Power-Limiting SYSTEMS FOR DIVISION 1 HAZARDOUS (CLASSIFIED) LOCATIONS The following requirements shall apply in addition to the criteria specified in paragraph 3.1.1, 3.1.2, or A. The self-regulating heating cable shall be specifically FM-approved or CSA-certified for use in Division 1 locations. B. A ground fault protection device set at 30 ma, with a nominal 100 ms response time, shall be used to protect each circuit. C. The temperature identification number (T-rating) of the cable used shall comply with FM and CSA requirements as applicable. D. Connection methods used with the cable shall be compatible and approved as a part of the system manufactured and supplied by the heating cable vendor for use in the Division 1 location. E. For plastic pipe and vessel applications, the heating cable shall be Raychem HBTV-CT self-regulating heater, with continuous exposure capability up to 150 F (65 C) and intermittent exposure capability up to 185 F (85 C), as manufactured by Tyco Thermal Controls. F. The heating cable shall be Raychem HQTV-CT self-regulating heater, for continuous and intermittent exposure capability up to 225 F (11O C), as manufactured by Tyco Thermal Controls. G. The heating cable shall be Raychem HXTV-CT self-regulating heater, for continuous exposure (maintain) capability up to 250 F (121 C) and intermittent exposure capability up to 420 F (215 C or 250 psi steam), as manufactured by Tyco Thermal Controls. 2. Power- Limiting 3. Mineral Insulated 4. Longline 5. Tubing Bundles 6. Tank 7. Snow and Ice All heat-tracing applications with continuous exposure (maintain) temperatures to 455 F (230 C) or power-off exposure temperatures to 482ºF (250ºC) shall use power-limiting cables cables. Continuous exposure (maintain) temperatures are based on wattage and voltage used, consult with vendor for specific cable temperature limits. Applications below 482ºF (250ºC) continuous exposure, power-off, shall consider power-limiting cables if more than one run of self-regulating heating cable is required. The decision between self-regulating heating cable and power-limiting heating cable shall be made considering the need for a T-rating that is not dependent on the specific application (this is provided by self-regulating heating cables) and the number of runs of heat tracing required for the application. In some applications power-limiting heaters can use fewer runs due to higher power output at higher temperatures. A. Power-limiting heating cable shall use a metallic heating element that varies its power output relative to the temperature of the surface of the pipe or the vessel. The cable shall be a parallel-zoned heating cable with a positive temperature coefficient heating element spirally wound around a flexible glass fiber core. B. A ground fault protection device set at 30 ma, with a nominal 100-ms response time, shall be used to protect each circuit. C. Maximum heating cable sheath temperature, per either the FM or CSA method of calculation, shall be submitted with the bid or design for all Division 1 and Division 2 applications. D. The power-limiting heating cable shall have 12AWG copper bus wires. E. A warranty against manufacturing defects for a period of 10 years shall be available. F. All cables shall be capable of passing a 2.5 kv dielectric test for one minute (ASTM 2633) after undergoing a 0.5 kg-m impact (BS 6351, Part 1, ). G. The heating cable shall be Raychem VPL-CT power-limiting heater, with continuous exposure (maintain) capability of 300ºF (150ºC) and intermittent exposure capability up to 482ºF (250ºC), as manufactured by Tyco Thermal Controls. (800) Tyco Thermal Controls Control and Monitoring 9. Heat Trace Panel 10.Engineered Products 11.Steam Tracing 12.Technical Data Sheets 13. Appendices 14.Index
5 3.3 Mineral Insulated Cable Systems All heat-tracing applications with continuous exposure (maintain) temperatures above 300 F (150 C) 455 F (230 C) or intermittent exposure temperatures above 482 F (250 C) shall use factory-terminated, mineral insulated (MI) cables. A. MI cable shall be magnesium oxide insulated, with copper or alloy conductors and an Incoloy 825 sheath. The heating section of the cable shall be joined to a cold lead also made of Incoloy 825. B. Each cable shall be factory-terminated to the required length, consisting of the lengths required for the pipe or equipment, plus an allowance for areas of additional heat loss such as valves flanges fittings, supports, and the like, plus a reasonable excess to allow for field variations. The cold lead section shall be seven feet long unless otherwise specified. C. Maximum heating cable sheath temperature, per either the FM or CSA method of calculation, shall be submitted with the bid or design for all Division 1 and Division 2 applications. D. Each cable shall be shipped with the catalog number marked on the outside of the package, and a permanent metallic cable tag containing the heating cable length, wattage, voltage, and current draw. If the cable has been designed for a hazardous location, the tag shall also indicate the area classification and heat-tracing circuit number. E. The heating cable shall be Pyrotenax brand Alloy 825 MI, mineral insulated heating cable with a maximum application temperature for the heating units of 1022ºF (550ºC) and a maximum exposure temperature for the heating cable of 1238ºF (670ºC), as manufactured by Tyco Thermal Controls. 3.4 Long-Line Systems A. Self-Regulating, Two-Wire geometry, Freeze Protection ( feet). For freeze protection applications, without high temperature exposure, up to 1250 feet, a two-wire self-regulating heater is often the best choice. 1. The heating cable shall consist of two 10 AWG nickel-plated copper bus wires embedded in a self-regulating polymeric core that controls power output so that the cable can be used directly on plastic or metallic pipes. The cables shall have a temperature identification number (T-rating) of T6 (185 F or 85 C) without use of thermostats. 2. The heating cable shall have a tinned copper braid with a resistance less than the heating cable bus wire resistance as determined in a type test (ASTM, B193, Sec. 5). The braid shall be protected from chemical attack and mechanical abuse by a fluoropolymer outer jacket. 3. The heating cable shall be Raychem LBTV2-CT self-regulating heater, with continuous exposure capability up to 150 F (65 C) and intermittent exposure capability up to 185 F (85 C), as manufactured by Tyco Thermal Controls. B. Self-Regulating, VL geometry, Freeze Protection ( ,000 feet). For freeze protection applications, without steam exposure, above 1250 feet up to 12,000 feet a self-regulating freeze protection heater in a VL geometry is often the best choice. 1. The heating cable shall consist of two 10 AWG nickel-plated copper bus wires embedded in a self-regulating polymeric core, plus three additional 10 AWG nickel-plated copper bus wires. The cable shall be able to be connected directly to a 3-phase, 4-wire, 480 Vac or 600 Vac source. 2. The heating cable shall have a tinned copper braid with a resistance less than the heating cable bus wire resistance as determined in a type test (ASTM, B193, Sec. 5). The braid shall be protected from mechanical abuse by a modified polyolefin outer jacket or from mechanical abuse and chemical attack by a fluoropolymer outer jacket. 3. The heating cable shall be Raychem VLBTV2-CT self-regulating heater, with continuous exposure capability up to 150 F (65 C) and intermittent exposure capability up to 185 F (85 C), manufactured Tyco Thermal Controls Tyco Thermal Controls (800)
6 C. Self-Regulating, VL geometry, Freeze Protection and Process Temperature Maintenance with Steam Exposure ( feet). For process temperature maintenance and freeze protection with steam exposure a self-regulating process temperature maintenance heater in a VL geometry is often the best choice. 1. The heating cable shall consist of two 14 AWG nickel-plated copper bus wires embedded in a self-regulating polymeric core, plus three additional 14 AWG nickel-plated copper bus wires. The cable shall be able to be connected directly to a 3-phase, 4-wire, 480 Vac or 600 Vac source. 2. The heating cable shall have a tinned copper braid with a resistance less than the heating cable bus wire resistance as determined in a type test (ASTM, B193, Sec. 5). The braid shall be protected from chemical attack and mechanical abuse by a fluoropolymer outer jacket. 3. The heating cable shall be Raychem VLKTV2-CT self-regulating heater, with continuous exposure capability up to 250 F (121 C) and intermittent exposure capability up to 420 F (215 C or 250 psi steam) as manufactured by Tyco Thermal Controls. D. Constant-wattage Series Resistance, Freeze Protection and Process Temperature Maintenance up to 250ºF with Steam Exposure (500-8,000 feet). For process temperature maintenance and freeze protection with steam exposure a constant wattage series resistance heater is often the best choice, particularly when more than one run of self-regulating heater is needed. 1. The heating cable shall be a series resistance constant wattage heater. It shall consist of one or two copper conductors or copper alloy conductors insulated with high temperature heavy-walled fluoropolymer. 2. The heating cable shall have a tinned or nickel-plated copper braid with a resistance less than the heating cable bus wire resistance as determined in a type test (ASTM, B193, Sec. 5). The braid shall be protected from chemical attack and mechanical abuse by a fluoropolymer outer jacket. 3. The heating cable shall be constant wattage Raychem SC, with continuous exposure capability up to 400 F (204 C) and Raychem SCH with continuous exposure capability up to 482 F (250 C) as manufactured by Tyco Thermal Controls. E. Skin-effect Tracing Systems, Circuit lengths up to 15 miles, Freeze Protection and Process Temperature Maintenance up to 392ºF (200ºC), with or without Steam Exposure. For very long lines, process-temperature maintenance and freeze-protection skin-effect tracing is usually the best choice. 1. The heating system shall consist of an electrically insulated, temperature-resistant conductor with high temperature heavy walled fluoropolymer insulation installed inside a heat tube and connected to the tube at the far end. 2. The heat tube shall be ferromagnetic and thermally coupled to the carrier pipe that is being traced. 3. The design must be done by the manufacturer 4. The installation should be done under the supervision of the manufacturer. 5. The heat-tracing system system shall be Tracer STS (Skin-effect Tracing System) longline heating system as manufactured by Tyco Thermal Controls. 1. Self- Regulating 2. Power- Limiting 3. Mineral Insulated 4. Longline 5. Tubing Bundles 6. Tank 7. Snow and Ice 8. Control and Monitoring 9. Heat Trace Panel 10.Engineered Products 11.Steam Tracing 12.Technical Data Sheets (800) Tyco Thermal Controls Appendices 14.Index
7 3.5 Termination for Self-Regulating and Power Limiting A. All connection components used to terminate heating cables, including power connectors, splices, tees, and connectors, shall be approved for the respective area classification and approved as a system with the particular type of heating cable in use. Under no circumstances shall terminations be used which are manufactured by a vendor other than the cable manufacturer. B. In order to keep connections dry and corrosion resistant, components shall be constructed of non-metallic, electrostatic, charge-resistant, glass-filled, engineered polymer enclosure rated NEMA 4X. The component stand shall allow for up to 4 inches (100 mm) of thermal insulation. C. Terminals shall be spring clamp wire connection type to provide reliable connection, maintenance-free operation and ease of reentry. D. cable terminations shall use cold-applied materials and shall not require the use of a heat gun, torch or hot work permit for installation. E. Components shall be rated to a minimum installation temperature of 40ºF ( 40ºC), minimum usage temperature of 75ºF ( 60ºC) and maximum pipe temperature of 482ºF (250ºC). F. The component system shall be Raychem JBM-100-A-L connection kit complete with integral LED power indicating light to serve as complete power, splice or tee connection for up to three Raychem BTV, QTVR, XTV, or VPL industrial parallel heating cables as manufactured by Tyco Thermal Controls. 3.6 Thermostats and Contactors A. Freeze protection systems shall operate using self-regulating control or with the Digitrace Digitrace AMC-1A or Digitrace AMC-F5 thermostat and the Digitrace E A or Digitrace E304-40A contactor in ordinary areas, and Digitrace AMC-1H thermostat with Digitrace E307-40A contactor in hazardous locations, as supplied by Tyco Thermal Controls. B. Process temperature maintenance systems shall operate using self-regulating control or with Digitrace AMC-1B thermostat and Digitrace E A or Digitrace E304-40A contactor in ordinary areas and Digitrace E507S-LS or Digitrace RAYSTAT-EX-03-A thermostats and Digitrace E307-40A contactor in hazardous locations, as supplied by Tyco Thermal Controls. 3.7 Heat-Trace Panels A. For freeze protection or group control process-temperature maintenance systems, distribution panels shall be wall-mounted enclosures, including a panel board with ground fault protection devices (30 ma trip level). The panels shall provide ground fault alarm capabilities. If more than one circuit is required, a main contactor shall be used. The panels shall operate with ambient-sensing or proportional ambient-sensing controllers. The panel shall be the Tracer HTPG heat tracing panel as manufactured by Tyco Thermal Controls. B. For individual control process temperature maintenance systems, distribution panels shall be wall-mounted enclosures, including a panel board with ground fault protection devices (30 ma trip level). The panels shall provide ground fault alarm capabilities. Circuits shall be switched by individual contactors operated by line-sensing controllers. The panel shall be the Tracer HTPI heat tracing panel as manufactured by Tyco Thermal Controls Tyco Thermal Controls (800)
8 1. Self- Regulating 3.8 Control and Monitoring Systems. All control and monitoring systems shall be capable of communicating with a host PC for central programming, status review and alarm annunciation. All systems shall include, but not be limited to, the following: A. Alarm limits and set-point temperatures shall be programmable from the central monitoring and control panel in ºF and ºC. The system shall include an alphanumeric display with multilanguage support and password protection or lockable cabinet to prevent unauthorized access to the system. B. The system shall be switched by an external solid-state or mechanical relay with a minimum rating of 30 amps. C. The system shall be capable of assigning one or more RTDs to a circuit to monitor temperature. The controller shall be capable of one RTD to control the heater circuit and a second RTD for another control point or to measure sheath temperature of a heater for high temperature cutout. D. The system shall monitor temperature, voltage and line current to the systems E. The system shall monitor ground-fault current and offer the option of alarm or trip if the ground fault exceeds the selectable level SINGLE- OR DUAL-CIRCUIT CONTROL AND MONITORING DEVICES. A. The system shall be field-mounted and shall have FM or CSA approval for Class I, Division 2, Groups A, B, C, D when using a solid state switching device. B. The system shall provide user with the option of line-sensing control with a user- selectable dead band, ambient sensing, proportional ambient sensing (PASC), and power limiting control modes. C. The system shall provide an isolated triac alarm relay or a dry contact relay for alarm annunciation back to a Distributed Control System (DCS). D. Electrical code approved ground fault detection equipment shall be integral to the controller to simplify installation and reduce total cost. E. Enclosure type shall be NEMA 4X fiberglass reinforced plastic (FRP) or stainless steel for corrosion resistance and protection from moisture. F. DigiTrace units may be network ready to provide communication to a host PC running Windows based Supervisor software for central programming, status review and alarm annunciation. DigiTrace units shall support the Modbus RTU or ASCII/HTCBus communications protocol and be supplied complete with RS-485 communications interface capability. G. The system shall be DigiTrace 910 or DigiTrace 920 heat-tracing control systems, as manufactured by Tyco Thermal Controls. 2. Power- Limiting 3. Mineral Insulated 4. Longline 5. Tubing Bundles 6. Tank 7. Snow and Ice 8. Control and Monitoring 9. Heat Trace Panel 10.Engineered Products 11.Steam Tracing 12.Technical Data Sheets (800) Tyco Thermal Controls Appendices 14.Index
9 3.8.2 MULTICIRCUIT HARD-WIRED CONTROL AND MONITORING SYSTEMS - RACK MOUNTED H. The system shall have FM or CSA approval for Class I, Division 2, Groups A, B, C, D. when using a solid state switching device or using electromechanical relays and a Z-purge system. I. The system shall provide an isolated triac alarm relay for alarm annunciation back to a Distributed Control System (DCS). J. Electrical code approved ground fault detection equipment shall be integral to the controller to simplify installation and reduce total cost. K. Multicircuit hard-wired control and monitoring systems shall be rack mounted complete with integral power distribution panels. L. The panel shall be complete with individual control contactors, circuit breakers, power transformers (adjacent to each panel), space heaters or panel cooling system as required. M.Units shall be network ready to provide communication to a host PC running Windows based Supervisor software for central programming, status review and alarm annunciation. DigiTrace units shall support the Modbus RTU or ASCII/HTCBus communications protocol and be supplied complete with RS-485 communications interface capability. N. The system shall be DigiTrace T2000 heat-tracing control systems, as manufactured by Tyco Thermal Controls MULTICIRCUIT DISTRIBUTED-ARCHITECTURE CONTROL AND MONITORING SYSTEM A. The control and monitoring system shall be capable of controlling heat-tracing circuits with line-sensing control, ambient-sensing control, or proportional ambient-sensing control (PASC). The system shall be capable of using resistance temperature detectors (RTDs) which are wired directly to the central monitoring systems, to a remote module that communicates with the central monitoring system over a twisted pair, or to a temperature transmitter that communicates to a remote module over the bus wires of the heater (Powerline carrier technology). B. For temperature monitoring without power-line carrier technology the system shall use resistance temperature detectors (RTDs) which are wired to the central monitoring and control panel or to a remote module that communicates with the central monitoring and control system via a twisted pair. For temperature control the system shall use on-off control methods with contactors addressed through the central monitoring and control panel. C. The non-power-line carrier part of the system shall be compatible with all types of heating cables and capable of performing the following functions: 1. Monitoring and controlling pipe temperatures. 2. Providing real-time temperature and alarm log readouts. 3. Providing alarms in the event of low or high pipe temperature, or in case of sensor failure. 4. Providing remote alarm annunciation. 5. Interfacing with personal computers and DCS systems Tyco Thermal Controls (800)
10 1. Self- Regulating 4 Engineering D. The system shall be capable of utilizing power line carrier technology that uses the heating cable bus wires and power distribution wiring for communication, thus eliminating additional field instrument/sensor wiring. Temperature transmitters shall monitor heating cable continuity and temperature at any point along the heat-tracing circuit, including teed-off heating segments and the end of the circuit. The temperature monitoring the system shall use resistance temperature detectors (RTDs) wired directly to the temperature transmitters. Electrical isolation between the plant environment and the system shall be provided by dedicated, shielded, heattracing isolation transformers and filters. E. The system shall use on-off control methods to maintain temperatures of heat-tracing circuits. Process temperature control shall be accomplished using contactors addressed through the central monitoring and control panel. The contactors shall be grouped into a common NEMA 12, 4 or 4X-rated enclosure. Ambient temperature control and proportional ambient sensing control (PACS) shall be accomplished using dry contacts in the central monitoring and control panel to switch an auxiliary contactor, which in turn energizes or de-energizes heat-tracing circuits. F. The power-line carrier part of the system shall be compatible with all types of parallel heating cables and capable of performing the following functions: 1. Monitoring and controlling pipe temperatures. 2. Monitoring heating cable continuity and ground leakage current if GFPDs are used. 3. Providing alarms in the event of low or high pipe temperatures, loss of heating cable continuity, loss of panel power, loss of service voltage to the heating cable, sensor failure, or microprocessor failure. 4. Providing time-stamped temperature and alarm log readouts. 5. Performing self-diagnostic routines for commissioning and troubleshooting. 6. Interfacing with DCS systems. G. The monitoring and control system shall be the DigiTrace 200N monitoring and control system as manufactured by Tyco Thermal Controls. A. The vendor shall be given a line list from which to design and estimate a complete heattracing system. The bid package shall also include area layout and orthographic drawings. B. The vendor shall provide a detailed design utilizing standard heat-tracing design software, such as Tyco Thermal Controls TraceCalc Pro software or iequal. At minimum, the design must provide the following: 1. Circuit identification number. 2. Maintain temperature. 3. Line size and insulation. 4. Heat loss for pipe, valves, and supports. 5. Amount and type of heating cable required. 6. Spiral requirements. 7. cable service voltage. 8. cable power output at the maintain temperature. 9. Minimum and maximum maintain temperature vs. minimum and maximum ambient temperatures. 10. Circuit breaker and transformer sizing. C. The vendor shall provide heat-tracing isometric drawings at the buyer s request, using either hard copy or machine-readable CAD inputs. (800) Tyco Thermal Controls Power- Limiting 3. Mineral Insulated 4. Longline 5. Tubing Bundles 6. Tank 7. Snow and Ice 8. Control and Monitoring 9. Heat Trace Panel 10.Engineered Products 11.Steam Tracing 12.Technical Data Sheets 13. Appendices 14.Index
11 5 Testing A. Factory inspections and tests for self-regulating, power limiting, series constant wattage and constant wattage (M.I.) heater cables shall include but are not limited to the following: 1. Testing shall be done per the latest IEEE Std. 515 test section and applicable manufacturer s standards. 2. In the field, all heater cables shall be meggered. The following separate field megger readings shall be taken on each self-regulating and each M.I. heater cable: a. Heater cable shall be meggered when received at jobsite before installation. b. Heater cable shall be meggered after installation, but before insulation is applied. c. Heater cable shall be meggered after insulation has been installed. 3. All three of the above field megger readings shall be greater than 20 megohms. Otherwise, the heater cable is not acceptable and shall be replaced. 4. Field megger tests shall be recorded for each heater cable, and certified reports shall be submitted to User. Tyco Thermal Controls 300 Constitution Drive Menlo Park, CA Tel (800) Fax (800) Tyco Thermal Controls (800)
Industrial Heat Tracing Products and Services
Industrial Heat Tracing Products and Services Before You Buy, Weigh the Facts Tyco Thermal Controls is The Leading Full-Service Integrator Complete Construction, Project Management and Maintenance Provider
920 Series. Dual-point heat-tracing control system. Product overview. 920*E4FWL*SIS302*SS3102 shown
Self-Regulating 920 Series Dual-point heat-tracing control system Power-Limiting Mineral Insulated 920*E4FWL*SIS302*SS3102 shown Product overview The DigiTrace 920 is a compact, full-featured, microprocessor-based,
Control and Monitoring
Self-Regulating Control and Part 1: Control and Options This section provides complete information for the design and selection of heattracing control and monitoring systems. Part 1 identifies control
Nelson MI Cable is a high performance, industrial grade heat tracing cable used for applications requiring:
Alloy 825 Sheath Custom Fabricated Heating Elements Magnesium Oxide Insulation Description: Mineral insulated cable is a metal sheathed cable that uses a metallic conductor as the heating element. The
Advanced Heat-Tracing Control System
Advanced Heat-Tracing Control System Product Overview Heat-tracing system NGC-30 system Remote configuration and monitoring with Raychem Supervisor software The Raychem NGC-30 is a multi-circuit electronic
Self-Regulating Low Temperature Heating Cable
PDS SRL Self-Regulating Low Temperature Heating Cable Self-Regulating, Energy Efficient 16 AWG Buss Wire Circuit Lengths to 660 Feet Process Temperature Maintenance to 150 F (65 C) Maximum Continuous Exposure
Industrial Heat-Tracing Installation and Maintenance Manual
Industrial Heat-Tracing Installation and Maintenance Manual Self-Regulating and Power-Limiting Heating Cable Systems WARNING: Fire and shock hazard. Raychem heat-tracing systems must be installed correctly
Electric Heat Tracing INSTALLATION PROCEDURES
INSTALLATION PROCEDURES The following installation procedures are suggested guidelines for the installation of a Thermon electric heat tracing system 1. Individuals installing these products are responsible
Type FLX Freezer Floor Frost Heave Protection DESIGN GUIDE
Type FLX Freezer Floor Frost Heave Protection DESIGN GUIDE Commercial Products Type FLX TM Freezer Floor Frost Heave Protection DESIGN GUIDE Contents Introduction...2 Application Information... 2-3 Product
Pipe Freeze Protection Design/Install Guide
Pipe Freeze Protection Design/Install Guide Page 1 of 16 Pipe Freeze Protection Design / Install Guide CONTENTS Introduction Page 3 STEP 1 Information Required Page 4 STEP 2 Design Considerations Page
THERMAL MANAGEMENT SOLUTIONS
t2000 Series Electronic heat-tracing controller Product Overview /COMMUNICATIONS INTERACE CARRIER REQ TO SEND The DigiTrace heat trace controller is designed to provide the benefits associated with single
Mineral Insulated Heating
Self-Regulating Mineral Insulated cables This section provides an overview and general design guidelines for mineral insulated heat-tracing systems. For complete design assistance, contact your Pentair
BSX TM. Self-Regulating Heating Cable. Product Specifications
BSX TM Freeze Protection or Process Temperature Maintenance BSX self-regulating heating cables are designed to provide freeze protection or process temperature maintenance to metallic and nonmetallic piping,
PRODUCT / APPLICATION INFORMATION
Abstract This paper will discuss performance life testing and stability testing used for self-regulating heating cables. It will show how the techniques were developed and evolved from the 970 s to the
Complex Piping Design Guide for Self-Regulating Heating Cables
Complex Piping Design Guide for Self-Regulating Heating Cables Introduction... 4 Computer Aided Design Program... 4 Heat Tracing Design Outline... 5 Basis for a Good Design... 5-14 Step 1: Establish Design
MIQ TM Mineral Insulated Heating Cable INSTALLATION PROCEDURES. (North America)
MIQ TM Mineral Insulated INSTALLATION PROCEDURES (North America) MIQ TM Mineral Insulated The following installation procedures are suggested guidelines for the installation of a Thermon MIQ mineral insulated
for Hazardous Division 1 Locations
Self-Regulating Heat-Tracing Systems for Hazardous Division 1 Locations Design and Installation Guide Power-Limiting Mineral Insulated Longline RTB Tubing Bundles Tank Snow and Ice Control and Monitoring
Heating Cable. Construction
Mineral Insulated High Temperature A C Constant Wattage Series Resistance Heating Cable Sets Process Temperature Maintenance to F (593 C) Maximum Exposure Temperature 4 F (76 C) (Power Off) Corrosion Resistant
Pictorial Index... A-14 Introduction to Heat Trace Cable Systems... 6-2 Installation Examples... 6-3 Engineering Guide... 6-4 Heat Loss Tables...
Pictorial Index....................... A-14 Introduction to Heat Trace Cable Systems............... 6-2 Installation Examples................... 6-3 Engineering Guide..................... 6-4 Heat Loss
Protection Systems. A UTC Fire & Security Company F-73-01. Linear Heat Detector FEATURES DESCRIPTION APPLICATIONS BENEFITS
Effective: May 2007 AlarmLine TM R Protection Systems Linear Heat Detector A UTC Fire & Security Company F-73-01 FEATURES Integrating Type Linear Heat Detector Analog Sensing Field Adjustable Alarm Set
Chromalox PRECISION HEAT AND CONTROL. Electrical Heat Tracing Systems Design Guide
Chromalox PRECISION HEAT AND CONTROL Electrical Heat Tracing Systems Design Guide INTRODUCTION TABLE OF CONTENTS TABLE OF CONTENTS Thermal Design - Pipes:.. 1 Thermal Design - Tanks:.. 6 Heating Cable
XL-Trace System Installation and Operation Manual
XL-Trace System Installation and Operation Manual Pipe freeze protection and flow maintenance WARNING: Fire and shock hazard. This heat-tracing system must be installed correctly to ensure proper operation
Thermwire. Selection Guide. Freeze Protection Heating Cable. Thermwire -Wrap. Pre-Assembled. Thermwire-Comp. Thermwire-Melt.
Thermwire Freeze Protection Heating Cable Selection Guide Pipe Freeze Protection Heating Cable Pre-Assembled Pipe Freeze Protection Heating Cable with Attached Cord & Plug Thermwire-Comp Refrigeration
SELF-REGULATING PIPE TRACING HEATER CABLE
SELF-REGULATING PIPE TRACING HEATER CABLE Installation & Operation Manual TABLE OF CONTENTS GENERAL INFORMATION... 1 How Heating Systems Work...1 PRODUCT SELECTION... 1 RECEIPT & STORAGE... 1 Receipt...1
RMM2 Heat-Tracing Remote Monitoring Module for the Raychem NGC Control System Installation Instructions
Heat-Tracing Remote Monitoring Module for the NGC Control System Installation Instructions Tools Required 3 mm slotted screwdriver 3/8 hex key (for -4X only) Approvals Nonhazardous locations Type NM LISTED
UNITHERM UNITHERM 2256/2266 SELF-REGULATING ELECTRIC TRACE TUBING
UNITHERM UNITHERM 2256/2266 SELF-REGULATING ELECTRIC TRACE TUBING HIGH TEMPERATURE MAINTENANCE AND STEAM CLEANED LINES Principal of Operation Unitherm 2256/2266 HTM (High Temperature Maintenance) Electric
Heat Trace Fundamentals. Monte Vander Velde, P.E. President, Interstates Instrumentation
Heat Trace Fundamentals Monte Vander Velde, P.E. President, Interstates Instrumentation Contents Introduction... 3 Purpose of Heat Trace... 3 Types of Heat Trace... 4 Steam Trace vs. Electric Trace...
LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA. General Specification
08/17/12 Rev2 LTR Series General Specification 700 VA to 2.1 KVA 1.0 General LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA General Specification This specification describes the features and
Self-Regulating Pipe Tracing Heating Cable Specification/Application Guide. Polyolefin. Performance and Rating Data
TSR Self-Regulating Pipe Tracing Heating Cable Specification/Application Guide READ CAREFULLY PRINCIPLE OF OPERATION Easy Heat TSR is a self-regulating heating cable that automatically varies its heat
Installation Instructions. Industrial Heating Cable Products
Installation Instructions Industrial Heating Cable Products PJ438-21 161-057884-001 September, 2014 Important General Instructions These instructions are to be followed when installing Chromalox Heating
ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL
RANCO INSTALLATION INSTRUCTIONS ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL Relay Electrical Ratings PRODUCT DESCRIPTION The Ranco ETC is a microprocessor-based family of electronic temperature controls,
SnoTrace KSR Surface Snow and Ice Melting INSTALLATION PROCEDURES
SnoTrace Surface Snow and Ice Melting INSTALLATION PROCEDURES SnoTrace INSTALLATION PROCEDURES Refer to the SnoTrace Cable Testing Report for required recording of test data and circuit information. Upon
Product overview. 2000 mm. 100 mm
Panel mounted electronic multi-circuit heat-tracing control, monitoring and power distribution system Product overview CABLE DUCT Card Rack Modules TERMINAL STRIP PLINTH MAIN SWITCH 800 mm USER INTERFACE
Freeze Protection Thermostats MODELS SST 2. Installation and Operation Manual
Freeze Protection Thermostats MODELS SST 2 Part Number 22744 MANUAL We Manage Heat Installation and Operation Manual Environmental Technology, Inc. 1850 N Sheridan Street South Bend, Indiana 46628 (574)
Electric Heat Tracing INSTALLATION PROCEDURES
INSTALLATION PROCEDURES Complete Electric Heat Tracing System... Types of Heating Cables 1... Self-Regulating Heating Cables: BSX (refer to Form TEP0067U) 1725 II 2 G & D Ex e II T5 or T6 DEMKO 02ATEX0132424,
26 3213.13 Diesel Engine Driven Generators Page 1 of 6
Last Update: December 8, 2014 A. Description of System Consultant s Handbook Page 1 of 6 1. Provide a diesel engine driven electric generating unit, factory assembled, tested and certified to operate at
Lessons Learned, Best Practices and Observations. 2014 2016 Plant Winterization Visits
Lessons Learned, Best Practices and Observations 2014 2016 Plant Winterization Visits EQUIPMENT PROTECTION: Although some of the observations and practices were unique to an entity, the following can be
TubeTrace, ThermoTube
TubeTrace, ThermoTube and Custom CEMS Tubing Bundles INSTALLATION PROCEDURES English Units TubeTrace & ThermoTube Tubing Bundles Receiving, Storing and Handling... 1. Inspect materials for damage incurred
Sanitary Type Electronic Flow Switches
Industries Pharmaceutical Sanitary Type Electronic Flow Switches Food and Beverage Biotechnology Semiconductor Water Treatment S Series Ameritrol, Inc. Instruments and Controls Features No Moving Parts
COLD LEAD OPTIONS FOR XMI MINERAL INSULATED (MI) HEATING CABLES
COLD LEAD OPTIONS FOR XMI MINERAL INSULATED (MI) HEATING CABLES PRODUCT OVERVIEW XMI with standard MI cold lead and Type X connector MI cable heated section PRODUCT OVERVIEW XMI with PyroFLX cold lead
Electronic Flow Switches
Industries Electronic Flow Switches Petrochemical Refining Oil Production Water Treatment Pharmaceutical Food and Beverage Pulp and Paper Power Production Gas Processing Mining Biotechnology Semiconductor
SM6 Series Circuit Breaker Monitors CONSOLIDATED. Electronics, Inc. MONITORING THE FUTURE
Series Circuit Breaker Monitors CONSOLIDATED Electronics, Inc. MONITORING THE FUTURE Why SF Gas Density Monitors? 6 Cut Maintenance Costs Your capital investment may be recovered with the elimination of
TC 1818a. Operating Guide. Control Module SWM-015.5
TC 1818a Control Module Operating Guide SWM-015.5 This guide is intended solely for use by owners of Thermon HeatChek TM heat tracing control and monitoring units. This manual describes operation for TC
Heat Tracing Systems. Course No: E04-019 Credit: 4 PDH. A. Bhatia
Heat Tracing Systems Course No: E04-019 Credit: 4 PDH A. Bhatia Continuing Education and Development, Inc. 9 Greyridge Farm Court Stony Point, NY 10980 P: (877) 322-5800 F: (877) 322-4774 [email protected]
Installation & Maintenance
Installation & Maintenance SELF-REGULATING HEATER CABLE CONTENTS GENERAL INFORMATION... 4 How Heating Systems Work...4 PRODUCT SELECTION... 4 RECEIPT & STORAGE... 4 Receipt...4 Storage...4 Withdrawal from
Insulation Resistance Testing of Low Voltage Cables in the Field
Insulation Resistance Testing of Low Voltage Cables in the Field Table of Contents 1. Background...3 1.1. Before Making Measurements...3 1.2. How to Apply the Temperature Correction Factor...4 1.2.1. Calculation...4
ALARMLINE ANALOGUE Linear Heat Detection System
ALARMLINE ANALOGUE Alarmline Analogue sensor cable senses temperature variations by continuously monitoring the resistance of specially doped N.T.C. polymeric insulation. A change in temperature produces
Industrial Heat Tracing INSTALLATION AND MAINTENANCE MANUAL FOR MINERAL INSULATED CABLE SYSTEMS APPLIED TO PIPES AND VESSELS
Industrial Heat Tracing INSTALLATION AND MAINTENANCE MANUAL FOR MINERAL INSULATED CABLE SYSTEMS APPLIED TO PIPES AND VESSELS INDUSTRIAL HEAT TRACING SOLUTIONS WWW.PENTAIRTHERMAL.COM Important Safeguards
White Paper SolarEdge Three Phase Inverter System Design and the National Electrical Code. June 2015 Revision 1.5
White Paper SolarEdge Three Phase Inverter System Design and the National Electrical Code June 2015 Revision 1.5 Shalhevet Bar-Asher; SolarEdge Technologies, Inc. Bill Brooks, PE; Brooks Engineering LLC
Industrial Control Solutions
Industrial Control Solutions NGC-30 Advanced Heat-Tracing Control System industrial heat tracing solutions www.pentairthermal.com Raychem ngc-30 Raychem NGC-30 is an advanced electronic multipoint control,
SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches
SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches PART 1 GENERAL 1.01 Scope Optional Standby Power Generator Systems A. Furnish and install automatic transfer switches
NELSON HEAT TRACING SYSTEMS
DESCRIPTION The HASK-P Hazardous Area Seal Kit provides the cable termination and explosion proof seal parts needed to make the power end electrical connections associated with Nelson Heat Tracing Systems
RTB Tubing Bundles Installation Guide Heating solutions for instrument and small-diameter process lines
RTB Tubing Bundles Installation Guide Heating solutions for instrument and small-diameter process lines 1 / 20 WARNING: Fire and shock hazard. Raychem heat-tracing systems must be installed correctly to
In-Line Electronic Flow Switches
In-Line Electronic Flow Switches Industries Petrochemical Refining Oil Production Water Treatment Pharmaceutical Food and Beverage Pulp and Paper Power Production Gas Processing Mining Biotechnology Semiconductor
KSR-SK-DB In-Line Splice Kit KSR Snow Melting Cable INSTALLATION PROCEDURES
KSR-SK-DB In-Line Splice Kit KSR Snow Melting Cable INSTALLATION PROCEDURES KSR-SK-DB The following installation procedures are suggested guidelines for the installation of in-line cable splices. They
Heat Tracing Sales Mt. Airy, Maryland www.heattracingsales.com 410-795-2223. Installation Instructions
Chromalox Installation Instructions DIVISION 4 SALES REFERENCE DATE SERVICE REFERENCE SECTION DTS (Supersedes PJ944-5) PJ944-6 161-562581-049 MARCH, 2012 DTS-HAZ For Use With Self-Regulating & Constant
AlarmLine Addressable Linear Heat Detector
Line Addressable Linear Heat Detector P/N 7-0001-00 Effective: March 2008 K-7-02 FEATURES UL Listed FM Approved CSFM MEA (pending) Low-cost interface between Line sensor cable and control panel accepting
DTS-HAZ DTS-HAZ-DC. Installation Instructions. for use with Self-Regulating, Constant Wattage & Mineral Insulated Electric Heating Cables
Installation Instructions DTS-HAZ DTS-HAZ-DC for use with Self-Regulating, Constant Wattage & Mineral Insulated Electric Heating Cables 1 PJ944-10 5625-81049 May 2015 2 DTS-HAZ & DTS-HAZ-DC 1 2 3 8 12
Frost Heave Protection System Installation and Operation Manual for Self-Regulating Heating Cable Systems
Frost Heave Protection System Installation and Operation Manual for Self-Regulating Heating Cable Systems FHP Self-regulating Heating Cable Systems 1 / 17 WARNING: Fire and Shock Hazard Raychem frost heave
Installation Instructions DTS-HAZ DTS-HAZ-DC. for Use with Self-Regulating & Constant Wattage Heating Cables
Installation Instructions DTS-HAZ DTS-HAZ-DC for Use with Self-Regulating & Constant Wattage Heating Cables PJ944-9 5625-81049 May 2013 1 2 DTS-HAZ Self-Regulating & Constant Wattage Heating Cables Junction
MTI10 Insertion and MTL10 In-line Thermal Mass Flowmeter and Temperature Transmitter
Thermal Mass meter and Temperature Transmitter Description The MTI10 insertion thermal mass flowmeter and the MTL10 in-line thermal mass flowmeter provide accurate mass flow measurement of clean, dry gases
RayClic Connection System Installation Instructions
F M -W RayClic Connection System Installation Instructions RayClic WARNING: Shock Hazard 718K Pipe Heating Cable with HWAT, IceStop, also Listed De-icing and and XL-Trace heating Snow Melting Equipment
Heat Tracing is the use of an externally applied heat source to a pipeline to compensate for heat losses through the thermal insulation.
Heat Tracing is the use of an externally applied heat source to a pipeline to compensate for heat losses through the thermal insulation. Heat tracing evolved from the need to maintain the flow of low,
T7079A,B Solid State Remote Temperature Controllers
T7079A,B Solid State Remote Temperature Controllers FEATURES PRODUCT DATA Switch selection of heat or cool mode. Temperature sensing up to 400 feet. Does not require field calibration. 0K NTC temperature
SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT
SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT PART 1 - GENERAL 1.1 DESCRIPTION A. The Work specified in this Section consists of designing, furnishing and installing factory-assembled
SECTION 16720 - FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines
PART 1 -- GENERAL 1.1 WORK OF THIS SECTION SECTION 16720 - City of San Diego, CWP Guidelines A. The WORK of this Section includes providing manual and automatic fire alarm and smoke detection systems meeting
PART 8: FIELD WIRING. n WARNING NOTICE. Boiler Manual
PART 8: FIELD WIRING A. INSTALLATION MUST COMPLY WITH: 1. National Electrical Code and any other national, state, provincial or local codes or regulations. 2. In Canada, CSA C22.1 Canadian Electrical Code
TC 202a Control Module
TC 202a Control Module Operating Guide SWM-004.7 This guide is intended solely for use by owners of Thermon HeatChek TM heat tracing control and monitoring units. This manual is considered proprietary
Contact Information: 4031-0001 Electrical Connection Kit for CL Series Constant Wattage Temptrace for Low Temperature Maintenance.
Technical Data Sheet & Installation Instructions for 4031-0001 Electrical Connection Kit for CL Series Constant Wattage Temptrace for Low Temperature Maintenance Bulletin CL-II Contact Information: Parker
Applications. Remote Display Mounting Kits
June 200 Sheet 105 Surge Protection Products TVSS General Description Clipper Power System Visor Series.1-5 Clipper Power System Visor Series General Description Eaton s Cutler-Hammer leading-edge surge
READ THIS MANUAL BEFORE PROCEEDING WITH THE INSTALLATION. FAILURE TO FOLLOW THE INSTALLATION INSTRUCTIONS MAY VOID YOUR WARRANTY!
READ THIS MANUAL BEFORE PROCEEDING WITH THE INSTALLATION. FAILURE TO FOLLOW THE INSTALLATION INSTRUCTIONS MAY VOID YOUR WARRANTY! The main power to any existing system must be disconnected prior to the
What are the basic electrical safety issues and remedies in solar photovoltaic installations?
What are the basic electrical safety issues and remedies in solar photovoltaic installations? Presented by: Behzad Eghtesady City of Los Angeles Department of Building and Safety Topics Covered Photovoltaic
CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH
CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH Cat transfer switches are designed for a variety of standby power applications. They provide flexibility, reliability and value in a
Product Description Primary Resistance Starting Electric Fire Pump Controllers FTA1500
Product Description Primary Resistance Starting Electric Fire Pump Controllers FTA1500 Description Firetrol FTA1500 Primary Resistance Fire Pump Controllers use resistors in the line to reduce line voltage
Commercial Semi-Instantaneous Water Heaters
FEATURES HWI Models A. O. Smith s HWI models are available for operation with steam or boiler water as the energy source. They are factory assembled with components sized, piped and checked at the factory
Products and services
commercial HEAT TRACING Products and services THERMAL BUILDING SOLUTIONS WWW.PENTAIRTHERMAL.COM BUILDING & INFRASTRUCTURE SOLUTIONS We provide quality solutions for winter safety, comfort and performance
Submit shop drawings for equipment provided under this section Shop drawings shall indicate:
Section 16435 - SWITCHBOARDS Introduction Part 1 - General Reference The work under this section is subject to requirements of the Contract Documents including the General Conditions, Supplementary Conditions,
CalMod Design-Build Electrification Services
SECTION 28 16 00 INTRUSION DETECTION SYSTEM PART 1 - GENERAL 1.1 DESCRIPTION A. This section describes the detailed technical requirements for the Intrusion Detection System (IDS), where the Contractor
BURSTCHECK LINE OF RUPTURE DISC BURST INDICATORS
BURSTCHECK LINE OF RUPTURE DISC BURST INDICATORS INTRODUCTION Rupture discs are often used as primary pressure relief devices and to isolate pressure relief valves. When used as a primary pressure relief
E-Version SECTION 15318 - CHLORINATION SYSTEM PART 1 - GENERAL PART 2 - PRODUCT
SECTION 15318 - CHLORINATION SYSTEM PART 1 - GENERAL 1.1. SCOPE OF WORK A. Under this item the Contractor shall furnish and install a sodium hypochlorite solution metering system complete with all accessories
TC-9102 Series Surface Mount Temperature Controllers
TC-9102 Series Surface Mount Temperature Controllers General Description & Applications The TC-9102 Series Temperature Controller offers a versatile solution for a wide variety of applications that may
Heat Tracing Products
Applications Electric Industrial Process Maintenance Applications Commercial Applications Chromalox heating cable line includes cables suitable for most process maintenance, pipe and vessel freeze protection
Explosion-Proof Electric Unit Heaters
Type FX4 FX4 Explosion-Proof Electric Air Heaters FX4 heaters are UL listed and/or CSA certified for use in hazardous locations. They are designed for dry indoor industrial applications such as oil refineries,
Installation, Operation and MAINTENANCE INSTRUCTIONS. Industrial Heating Cable Products IMPORTANT GENERAL INSTRUCTIONS
Chromalox Installation, Operation and MAINTENANCE INSTRUCTIONS DIVISION 4 SALES REFERENCE DATE SERVICE REFERENCE (Supersedes PJ438-16) JULY, 2010 SECTION RT PJ438-18 161-057884-001 Industrial Products
ACS-30-EU-EMDR-10-MOD
Multi-application heat tracing Control and Monitoring in commercial and residential buildings Roof & Gutter de-icing sensor module Technical Information Approvals Module IP rating Ambient operating temperature
Single Phase Soft Starter
Single Phase Soft Starter Installation & Operating Manual 6/02 Table of Contents Section 1 General Information................................................... 1 1 General Description................................................
ELECTRIC HEATER COMPANY Operating and Maintenance Manual For Immersion Heating Elements
ELECTRIC HEATER COMPANY Operating and Maintenance Manual For Immersion Heating Elements HUBBELL ELECTRIC HEATER COMPANY P.O. BOX 288 STRATFORD, CT 06615 PHONE: (203) 378-2659 FAX: (203) 378-3593 INTERNET:
CoolTop. A unique water cooled air-conditioning unit for server room cooling from the top AC-TOPx-CW-240/60
CoolTop A unique water cooled air-conditioning unit for server room cooling from the top AC-TOPx-CW-240/60 Application CoolTop is a new, unique air conditioning unit especially designed for datacenters.
www.klmtechgroup.com TABLE OF CONTENT
Page : 1 of 13 Project Engineering Standard www.klmtechgroup.com KLM Technology #03-12 Block Aronia, Jalan Sri Perkasa 2 Taman Tampoi Utama 81200 Johor Bahru Malaysia ELECTIRAL GROUNDING TABLE OF CONTENT
The National Armored Cable Manufacturers Association Presents. Installation Standard for Types AC and MC Cables
The National Armored Cable Manufacturers Association Presents Installation Standard for Types AC and MC Cables An ANSI Standard Original document jointly produced by NECA and NACMA as Standard for Installing
TABLE 1. Rugged cast aluminum alloy casing,celcon waterways with nichrome parts White (unless stainless steel housing)
CHRONOMITE INSTANT-FLOW MICRO WATER HEATER INSTALLATION AND OPERATION INSTRUCTIONS - (LOW FLOW MODELS) (Before installation, compare electrical needed for the model of heater selected) TABLE 1 Model No.
2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.
2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. Relays) Part 1 General 1.1 CONDITIONS AND REQUIREMENTS: A. Refer to
HL Series - Commercial Heaters Tankless Water Heating Solutions
HL Series - Commercial Heaters 5-18 kw (17,000-61,400 BTUs) Low flow activation options at.15 and.25 GPM (0.6 and 0.9 L-Min) Certified Lead-Free Design Variable Temp Heat Exchanger Pressure Drop Advantage
SECTION 18370 SIGNAL WIRE AND CABLE
SECTION 18370 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for all cable and wire required for signal and signal power system wiring to wayside shelters, junction boxes, and factory
Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000
Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000 Description Firetrol FTA1000 Full Voltage Fire Pump Controllers are intended for use with electric motor driven fi re pumps
PT-6000 Power Tower INSTALLATION MANUAL SPECIFICATIONS
PT-6000 Power Tower INSTALLATION MANUAL 10.5 9.75 12 22.75 10.75 MAXIMUM SOIL HEIGHT: DO NOT ALLOW FILL TO EXCEED THIS LEVEL! 11.5 4 4 13 Optional PT-BASE for new installations or when previous 2000/6000
SYSTEM 1850-SE SERVICE ENTRANCE CABLE SYSTEM
Pyrotenax SYSTEM 1850-SE SERVICE ENTRANCE CABLE SYSTEM Contents Introduction This section provides an overview of general circuit design considerations and installation guidelines for a Pyrotenax System
Solid State Timers Type F
Solid State Timers Type F Class 9050 CATALOG CONTENTS Description.....................................................Page Product Descriptions............................................. 3 Application
SECTION 271525 OPTICAL FIBER CABLES AND ACCESSORIES. A. Interior Raceways, Fittings, and Accessories: Section 260532.
SECTION 271525 OPTICAL FIBER CABLES AND ACCESSORIES PART 1 GENERAL 1.01 RELATED WORK SPECIFIED ELSEWHERE A. Interior Raceways, Fittings, and Accessories: Section 260532. B. Wiring, General - 600 Volts