PRODUCT / APPLICATION INFORMATION
|
|
|
- Mitchell Morgan
- 10 years ago
- Views:
Transcription
1 Abstract This paper will discuss performance life testing and stability testing used for self-regulating heating cables. It will show how the techniques were developed and evolved from the 970 s to the present How these techniques re used to establish ratings on the latest high temperature heating cables will also be discussed. INTRODUCTION Self-regulating conductive polymer heating cables are widely used for freeze protection and process temperature maintenance in industrial applications. In these applications the cost of downtime is significant. Therefore, it is critical that heat tracing provide the required heat to maintain operating conditions over the expected life of the process unit. The question arises, How does one establish or project long term performance and stability of a self-regulating heating cable?. The typical expectation for industrial applications is that the cable will function for 5 to 20 years. Basic Constructions First it is important to understand the basic constructions of self-regulating heating cables. The heating element of a self-regulating heating cable is a conductive polymer that exhibits a PTC effect. As the temperature of the heating element increases, its electrical resistivity increases. Thus, the conductive polymer has a positive temperature coefficient for resistance (PTC). The power output or thermal output decreases with increasing temperature. A typical construction for a self-regulating heating cable is shown in Figure. Figure Bus Conductors Heating Element Primary Dielectric Metallic Braid Outer Jacket This shows a monolithic construction with the heating element or core between two conductors. This forms a parallel circuit so the heating cable can be cut to length without changing its lineal power output. The heating element consists of carbon black mixed into a semicrystalline polymer. The melting point of the polymer dictates the self-regulating temperature or shut-off temperature. Polyethylene based heating cores are primarily used for low temperature, freeze protection applications, while fluoropolymer based heating cores are used for process temperature maintenance and higher temperature exposure applications. The primary jacket provides the dielectric insulation. Metallic braid, usually tinned copper surrounds the primary jacket and serves as a ground path. For additional mechanical protection and corrosion resistance there is an outer polymer jacket over the braid. Another self-regulating cable construction is shown in Figure 2. Figure 2 Bus Conductors Spacer Heating Element (Fiber) Primary Jacket Metallic Braid Outer Jacket Here instead of a monolithic core or heating element, the heating element is a fiber that is spirally wrapped around two bus conductors with a non-conducting polymer spacer separating the bus conductors. This heating element fiber is a conductive polymer. Contact between the bus conductor and fiber heating element is enhanced with an electrically conductive paste. A primary dielectric jacket surrounds the fiber heating elements. Like the previous monolithic construction, a metal braid and outer jacket are included with the fiber construction self-regulating heating cable. Form PAF Thermon Manufacturing Co. Subject to change without prior notice.
2 Factors for Long-Term Performance and Stability With conductive polymer heating elements, the aging mechanism is primarily oxidation with temperature and time. In most cases the resistance of the conductive polymer increases with temperature and time. Thus, the self-regulating heating cable is fail-safe from a burnout standpoint and excessive sheath temperatures in hazardous areas. However, it is important that the cable provide the rated power for maintaining the specified temperatures. Service life of a self-regulating heating cable is not only dependent on the polymer used for the heating element using long term performance and stability but, also is dependent on the processing. There are three key factors in manufacturing a self-regulating heating cable for long-term performance and stability: heating core homogeneity, contact resistance between heating element and bus conductor, and a closely conforming primary dielectric jacket. Heating core homogeneity - The mixing of carbon black with the polymer base is critical. Mixing is done in a compounding process. If the core does not have good homogeneity, hot spots can occur across the heating element due to localized variations in resistance. With time this results in localized thermal run away and a non-functioning heating cable. Contact between the bus conductor and the heating element - Reliable self-regulating heating cables have low contact resistance between the bus conductor and the heating element. Poor contact is somewhat like a cold joint where there is excessive heat build up. In time the localized resistance increases to the point where the heating cable is not producing its rated power. Loose primary jacket - If there are air gaps between the heating element and the primary jacket, heat transfer from the heating cable will be impeded. This results in potentially higher than normal heating core temperatures. In turn this results in faster oxidation and reduction in heating cable output. While there are other factors affecting life and stability, these three are the major factors. Temperature Ratings Due to the temperature dependence of polymers on retained properties, the temperature rating of a selfregulating heating cable is the key factor affecting performance life and stability. However, one will find not a single temperature rating, but a number of temperature rating terms for self-regulating heating cables. These terms are described as follows: Maximum maintain temperature The highest temperature of the pipe or vessel that the heating cable is capable of maintaining continuously in an energized condition. The service life expectation is 5 to 20 years. Maximum intermittent temperature - The highest temperature that the heat tracing cable may be exposed for a period of time as declared by the manufacturer. This last definition may need more explanation. Since polymer properties are time/temperature dependent, higher ratings to accommodate exposures such as steam clean or purge could be established which are higher than the continuous temperature exposure ratings. The intermittent rating is typically 000 hours of cumulative exposure. This addresses steam clean exposure over the expected system life (5-20 years) in industrial applications. Another factor in intermittent exposure is whether or not the heating cable is energized during the exposure. The power condition (energized or de-energized) is declared by the manufacturer. Performance Life and Stability Testing Since the introduction of self-regulating heating cables in the early 970 s, numerous methods have been used to establish performance life and stability. This section will describe test methods used as they evolved from the 970 s to the present.
3 Accelerated Aging Testing One of the first approaches used to project life of a conductive polymer heating cable was based on the Arrhenius equation. The test technique is described in UL 746B. In the 970 s many temperature ratings for polymer dielectric insulations on wire were based on UL 746B accelerated aging techniques. The material properties such as tensile and elongation of the polymer insulation changed with time and temperature according to the Arrhenius reaction rate equation: K = A exp (-E/RT) Where: K = specific reaction rate A = constant E = activation energy of the reaction R = gas constant T = temperature By taking the natural log (Loge) of both sides, the equation becomes, Loge (time) = constant + [(/2.303) (E/RT)] Or Loge (time) = a + b / T Loge(time) becomes a linear relationship with temperature. This lends itself to obtaining experimental results over short periods and being able to a project temperature at a longer time. For wire insulation an end point was typically defined such as 50% retained elongation or tensile strength. Then specimens of the polymer material were exposed to a range of elevated temperatures.tensile and elongation measurements are made on a schedule. When the end point is attained for a given specimen, the exposure time and temperature were recorded. Figure 3 shows typical data for 50% retained elongation. Elongation, % Retained Figure 3 Tensile Elongation vs. Time & Temp T T2 Time T3 Failure T is the highest temperature exposure and T5 is the lowest. As the Arrhenius equation would predict, as temperature decreases, it takes longer to reach the end point. By taking this data and plotting it with Loge (time) on the y-axis and the reciprocal of absolute temperature on the x-axis a straight line is formed. Time/temperature data taken for 6 months to 24 months that will provide adequate data for a straight-line correlation that can be extrapolated to longer times (years) to find the intersection of /T. The resulting temperature becomes the rated temperature for that time period or life definition. Refer to Figure 4. Loge Time o Failure Figure 4 Projected Life, Tensile Elongation Projected Life at T X T T 2 T 3 T oven T 4 T X T4 Failure Defined as 50% Decrease in Elongation
4 For conductive polymer heating cables the same concepts can be applied except with a different end point criterion. As stated earlier, conductive polymer heating cables increase in resistance with time and temperature. Therefore, retained power % or percentage resistance increase is the most indicative end point for long-term performance projections. In this case the time and temperature data is recorded for the 25% resistance increase end point. Refer to Figures 5. Resistance time Resistance initial Figure 5 Retained Resistance vs. Time and Temp. T T 2 T3 Time Failure Similar to the wire insulation case, data can be acquired over a period of 6 months to 24 months, and then an extrapolation can be made for establishing the temperature rating for 20 years or more for the heating cable. Refer to Figure 6. Loge Time to Failure Figure 6 Projected Life S/R Heating Cable Projected Life at T X T T 2 T 3 T oven T 4 T x T 4 Failure Defined as 25% Increase in Resistance UL 746B provides a basis for accelerated aging and life projections of materials. In the case of wire insulating material the test specimens are strips of the polymer to be evaluated. In the case of conductive polymer heating cables, sections or short lengths of heating cable are used. Strictly adhering to UL 746B, the specimens are placed in the various temperature controlled ovens in a passive or de-energized state. However, the heating cable is an active element and the test can be constructed to develop the correlation with the heating cable specimen active or in an energized condition. To do this the cable temperature in the oven must be measured and this temperature used for the time/ temperature end point. However, while accelerated aging testing provided a basis to project life of a self-regulating heating cable at a temperature, other forms of testing are necessary. A heating cable can have a 20-year life expectancy based on passive accelerated aging testing and yet degrade to an unacceptable level of performance in weeks under active conditions of voltage and temperature cycling. This can be due to the previously mentioned processing conditions that result in poor heating core homogeneity, high contact resistance between heating element and bus conductor, and a loose primary dielectric jacket. For example, a heating cable with poor contact between the bus conductor and heating core would not exhibit any abnormal degradation in performance with passive (non-energized) accelerated aging testing, but would increase rapidly in resistance with active (energized cyclic testing. As a result, various forms of short term active cyclic testing were developed to assure stability.
5 IEEE 55 Benchmark Test In the early 990s self-regulating heating cables were the most common approach to electrical heat tracing. Users relied on manufacturer s ratings for long-term performance. IEEE Standard 55 had been in use since 983 yet did not have any testing requirements addressing longer-term performance and stability. The IEEE 55 Working Group established for the second 5-year review cycle decided to address this issue. The matter was compounded in complexity because no longer was maximum maintain temperature the only temperature rating; maximum intermittent temperature was frequently used. Key elements for test conditions were identified: High temperature exposure Power/voltage cycling (active testing) Heating cable specimens based on the entire resistance range The resulting test conditions incorporating these elements in the IEEE 55 Std 997 are: Test specimens are selected to represent the maximum and minimum resistance Exposure at the maximum declared maintain temperature Heating cable is continuously cycled - 2 minutes energized at rated voltage and 3 minutes de-energized Duration of the test is 32 weeks (5376 hours) If intermittent temperature rating is used - Heating cable is exposed to declared maximum intermittent temperature for a time period of 8 hours per week - Power ON or OFF condition during this exposure is based on the manufacturer s rating At the completion of the test after 32 weeks the acceptance criterion is based on power output change. The window is, 0.75 < Pfinal / Pinitial <.20 This requires the heating cable to retain 75% of its initial power output and to not increase in power by more than 20%. The IEEE Service Life Performance Benchmark test provided a means of establishing long term performance and stability based on the stated temperature ratings of the cable. Since the heating cable is energized for the maximum maintain temperature exposure, and if specified for maximum intermittent exposure, actual worst-case conditions are tested. In North America approval agencies have adopted this test as a requirement.
6 IEEE 55 Benchmark Test 2004 In the 990s higher temperature cable options were being developed. Polymers such as perfluoroalkoxy fluorocarbon resin (PFA) were being used for the heating element. At the time PFA was introduced, accelerated aging testing per IEEE- and UL 746B found no correlation to enable projection of a temperature rating for 0 or 20 years. For wire and cable applications long-term performance was established by measuring retained properties over 20,000 hours at 285 C which is just below the melt temperature of PFA. Therefore, use of UL 746 B for projecting life and establishing temperature ratings was not possible with these higher temperature conductive polymer self-regulating heating cables. The IEEE Service Life Performance Benchmark test required 32 weeks. Since this test had become part of the approval process, the time required for the test became a factor in product development time and market introduction. The CSA 30.3 Working Group in Canada as well as the IEEE 55 Working Group in the USA (established for the third 5-year review cycle) decided to address this issue. The goal was to develop an equally stringent test which would provide an indication of long-term performance but which could be accomplished in a shorter period of time. The key factor is doing this was introducing thermal stress. The new shorter duration test incorporated the following: Test specimens are selected to represent the maximum and minimum resistance The heating cable is thermally cycled - Between the manufacturer s declared maximum maintain temperature and 23 C - Minimum time dwell at each extreme temperature is 5 minutes. - Total duration is 500 cycles Following the 500 cycles is the test for maximum intermittent temperature rating - The cable is exposed at the maximum rated temperature for 250 hours. - Power ON of OFF condition during this exposure is based on the manufacturer s rating After these exposures the same acceptance criterion as used in the IEEE Benchmark test which is based on power output is applied < Pfinal / Pinitial <.20 To further validate this test, self-regulating cables with a known long-term stable performance were tested along with cables that had shown deterioration in performance with time. The results confirmed the Benchmark test is a reliable screen or indicator of long-term life and stability of self-regulating heating cables. NEW HIGH TEMPERATURE HEATING SOLUTONS In the past twenty years compounding equipment and extrusion techniques have advanced. This has provided the capability to manufacture self-regulating heating cables with high performance high temperature polymers such as PFA. A recently introduced self-regulating cable based on a PFA polymer heating element was developed with goal of () high heating core homogeneity, (2) no contact resistance between bus conductors, and (3) tight primary jacket over heating core. For this new heating cable a high degree of homogeneity is achieved through use of state-of the-art compounding equipment and techniques. The contact between the bus conductors and polymer is optimized with a monolithic type heating element construction. The primary dielectric jacket is integral to the core, which maximizes heat transfer from the heating element. The combination of the monolithic construction and integral jacket results in uniform power flux and the lowest core temperature for the lineal heating provided. This new high temperature heating cable is capable of lineal power output of 64 0 C with an operating voltage of 230 Vac. Based on the IEEE Benchmark test, the temperature ratings achieved are: Maximum maintain temperature - 2 C Maximum intermittent temperature Energized - 25 C De-energized C
7 Test results for the energized exposure are shown in Figure 7. After 500 cycles from 23 C to 2 C and a 250 hour exposure to 25 C, the change in power output were an increase of 4% for the higher wattage cable and a 8% decrease for the lower wattage cable. These changes are well within the requirements of IEEE 55 and indicate stability Per Centage Power Retention or Gain Figure 7 Performance After Thermal Ageing Benchmark Maintain Temp 2 o C Maximum Intermittent Exposure Temp Maximum Minimum Power On 25 o C Thermal Cycles Low Resistance High Resistance SUMMARY With the advent of self-regulating conductive polymer heating cables in the early 970 s, a method to establish product life and stability was needed. Accelerated aging testing based on the Arrhenius equation was used along with short term cyclic testing. Heating cable life could be projected as a function of rated operating temperature. However, manufacturing faults were not always detected with accelerated aging tests based on UL 746B and IEEE. Active testing (heating cable energized) was employed in the 980 s to detect improper processing faults that can lead to deterioration in power output with time. These active testing methods were refined and became part of the IEEE heat tracing standard as the Benchmark Service Life Test for heating cables. This test provided basis for intermittent temperature exposure ratings of S/R heating cables. It also provides the ability to establish temperature ratings for S/R cables using high temperature polymers such as PFA which do not follow Arrhenius techniques for projecting life at a rated temperature In the latest version of CSA 30.3 published in 2003 and IEEE 55 published in 2004, the severity of the exposure is increased by changing from voltage cycling to thermal cycling. This allowed a reduction is in test duration from 32 weeks to 2 weeks. The major North American approval agencies, UL and FM use the IEEE Benchmark test and CSA uses the virtually identical Performance After Thermal Ageing Test in CSA 30.3 as a requirement in approvals for self-regulating heating cables. With advances in processing equipment and techniques that address some of the processing challenges of the past, self-regulating heating cables are available with high lineal power outputs and high temperature exposure ratings. Their temperature ratings for long -term life and stability are established with service life tests such in IEEE and CSA REFERENCES [] IEEE Recommended Practice: General Principles for Temperature Limits in the Rating of Electric Equipment and for the Evaluation of Electrical Insulation. Reaffirmed September 22, [2] IEEE Standard IEEE Standard for the Testing, Design, Installation, and Maintenance of Electrical Resistance Heat Tracing for Industrial Applications. Revision of IEEE Std [3] UL 746B Standard for Polymeric Materials; Long Term Property Evaluations. August 28, 996. VITAE Richard H. Hulett received a BSME, in 964 and an MSME in 965 from Stanford University. He is the Senior Vice President of Electrical Products for Thermon Manufacturing Company, where he has been employed for 0 years. He was previously employed by Raychem for 20 years. He has been a member of the IEEE and the IEEE/IAS/PCIC for the past 25 years. He is currently a member of the IEEE Standards Board. As a member of PCIC, he has been on the Standards Subcommittee, where he has served as chair, from 993-present. He has been a member of the IEEE 55 Working Group since 979, where he has served as Chair, since 985. He is also a member of the Codes and Regulations Working Group and the Chemical Subcommittee. Mr. Hulett is a member of the American Society of Mechanical Engineers, since 964. He has received the David C. Azbill Award and the IEEE Standards Medallion.
BSX TM. Self-Regulating Heating Cable. Product Specifications
BSX TM Freeze Protection or Process Temperature Maintenance BSX self-regulating heating cables are designed to provide freeze protection or process temperature maintenance to metallic and nonmetallic piping,
Sizing Circuit Breakers for Self-Regulating Heat Tracers
Sizing Circuit Breakers for Self-Regulating Heat s Effective Resistance (ohm/m) Introduction Circuit breaker sizing for S/R tracers is quite easily accomplished by using the specification sheet data or
Self-Regulating Low Temperature Heating Cable
PDS SRL Self-Regulating Low Temperature Heating Cable Self-Regulating, Energy Efficient 16 AWG Buss Wire Circuit Lengths to 660 Feet Process Temperature Maintenance to 150 F (65 C) Maximum Continuous Exposure
Pictorial Index... A-14 Introduction to Heat Trace Cable Systems... 6-2 Installation Examples... 6-3 Engineering Guide... 6-4 Heat Loss Tables...
Pictorial Index....................... A-14 Introduction to Heat Trace Cable Systems............... 6-2 Installation Examples................... 6-3 Engineering Guide..................... 6-4 Heat Loss
Nelson MI Cable is a high performance, industrial grade heat tracing cable used for applications requiring:
Alloy 825 Sheath Custom Fabricated Heating Elements Magnesium Oxide Insulation Description: Mineral insulated cable is a metal sheathed cable that uses a metallic conductor as the heating element. The
Heating Cable. Construction
Mineral Insulated High Temperature A C Constant Wattage Series Resistance Heating Cable Sets Process Temperature Maintenance to F (593 C) Maximum Exposure Temperature 4 F (76 C) (Power Off) Corrosion Resistant
Cable Size Selection for Energy Efficiency
Cable Size Selection for Energy Efficiency Introduction The traditional method for determining the appropriate cable size for a particular installation involves the selection of the smallest size conductor
Insulation Resistance Testing of Low Voltage Cables in the Field
Insulation Resistance Testing of Low Voltage Cables in the Field Table of Contents 1. Background...3 1.1. Before Making Measurements...3 1.2. How to Apply the Temperature Correction Factor...4 1.2.1. Calculation...4
NEMA Magnet Wire Thermal Class Ratings
NEMA Magnet Wire Thermal Class Ratings How to Use Them, and How They are Derived Ron Beeckman Essex Group, Inc. Thermal Class of Magnet Wire is Based upon: Temperature Index: (ASTM): A number which permits
Electric Heat Tracing INSTALLATION PROCEDURES
INSTALLATION PROCEDURES The following installation procedures are suggested guidelines for the installation of a Thermon electric heat tracing system 1. Individuals installing these products are responsible
Complex Piping Design Guide for Self-Regulating Heating Cables
Complex Piping Design Guide for Self-Regulating Heating Cables Introduction... 4 Computer Aided Design Program... 4 Heat Tracing Design Outline... 5 Basis for a Good Design... 5-14 Step 1: Establish Design
Heat Trace Fundamentals. Monte Vander Velde, P.E. President, Interstates Instrumentation
Heat Trace Fundamentals Monte Vander Velde, P.E. President, Interstates Instrumentation Contents Introduction... 3 Purpose of Heat Trace... 3 Types of Heat Trace... 4 Steam Trace vs. Electric Trace...
UNITHERM UNITHERM 2256/2266 SELF-REGULATING ELECTRIC TRACE TUBING
UNITHERM UNITHERM 2256/2266 SELF-REGULATING ELECTRIC TRACE TUBING HIGH TEMPERATURE MAINTENANCE AND STEAM CLEANED LINES Principal of Operation Unitherm 2256/2266 HTM (High Temperature Maintenance) Electric
Heat Tracing is the use of an externally applied heat source to a pipeline to compensate for heat losses through the thermal insulation.
Heat Tracing is the use of an externally applied heat source to a pipeline to compensate for heat losses through the thermal insulation. Heat tracing evolved from the need to maintain the flow of low,
Appendix J: Engineering Specification for Electrical Heat-Tracing Systems
Appendix J: Engineering Specification for Electrical Heat-Tracing Systems Contents 1 Scope........................................................... 11 2 Codes, Approvals, and Standards......................................
CABLE 101. The Basics of Wire & Cable. Copyright 2007, Belden Inc.
CABLE 101 The Basics of Wire & Cable Copyright 2007, Belden Inc. KEY TERMS Insulations Jacket Capacitance Attenuation Velocity of propagation Dielectric strength Dielectric constant Working voltage Elongation
Thermwire. Selection Guide. Freeze Protection Heating Cable. Thermwire -Wrap. Pre-Assembled. Thermwire-Comp. Thermwire-Melt.
Thermwire Freeze Protection Heating Cable Selection Guide Pipe Freeze Protection Heating Cable Pre-Assembled Pipe Freeze Protection Heating Cable with Attached Cord & Plug Thermwire-Comp Refrigeration
Type FLX Freezer Floor Frost Heave Protection DESIGN GUIDE
Type FLX Freezer Floor Frost Heave Protection DESIGN GUIDE Commercial Products Type FLX TM Freezer Floor Frost Heave Protection DESIGN GUIDE Contents Introduction...2 Application Information... 2-3 Product
FLEXTREME AND FLEXTREME IF
FLEXTREME AND FLEXTREME IF SOOW / SJOOW Flexible Cord TF Cable manufactures a superior industrial cable that offers a high value cosmetic appearance and greater mechanical strength by eliminating design
KALPANA INDUSTRIES LTD. TECHNICAL DATA SHEET
1 KALPANA INDUSTRIES LTD. TECHNICAL DATA SHEET KI XL - 03 / KI-SC 10 TWO COMPONENT AMBIENT CURABLE POLYETHYLENE COMPOUND FOR INSULATION OF LOW VOLTAGE POWER CABLE DESCRIPTION : KI polyethylene compound
Effect of Temperature on Wireline Cables Technical Bulletin Ten
The oil and gas industry exposes manufacturers and service companies to some of the most challenging environments anywhere. During wireline operations, cables are routinely run tens of thousands of feet
WHITE PAPER Fire & safety performance standards
WHITE PAPER Fire & safety performance standards Terminologies describing Fire Performance Terminologies describing Fire Performance often present a challenge to understand as how they apply to a cable
Chromalox PRECISION HEAT AND CONTROL. Electrical Heat Tracing Systems Design Guide
Chromalox PRECISION HEAT AND CONTROL Electrical Heat Tracing Systems Design Guide INTRODUCTION TABLE OF CONTENTS TABLE OF CONTENTS Thermal Design - Pipes:.. 1 Thermal Design - Tanks:.. 6 Heating Cable
What are the basic electrical safety issues and remedies in solar photovoltaic installations?
What are the basic electrical safety issues and remedies in solar photovoltaic installations? Presented by: Behzad Eghtesady City of Los Angeles Department of Building and Safety Topics Covered Photovoltaic
Session Five: Modern XLPE Materials for Extruded Energy Cable Systems
Session Five: Modern XLPE Materials for Extruded Energy Cable Systems Abstract Hakan Lennartsson Senior Technical Service Manager, Borouge Hong Kong Pte. Ltd. The first medium voltage cables using extruded
SnoTrace KSR Surface Snow and Ice Melting INSTALLATION PROCEDURES
SnoTrace Surface Snow and Ice Melting INSTALLATION PROCEDURES SnoTrace INSTALLATION PROCEDURES Refer to the SnoTrace Cable Testing Report for required recording of test data and circuit information. Upon
New Cable Tie Type Classifications
1 New Cable Tie Type Classifications UL 62275 United States CSA C22.2 No. 62275 Canada NMX-J-623-ANCE Mexico Technically Equivalent to IEC 62275 All cable ties are not created equal!!! With an increasing
Thermocouple Wire & Cable
Thermocouple Wire & Cable TRM Ltd & MICC Ltd Temperature House 21 Sedling Road Wear Industrial Estate Washington Tyne & Wear NE38 9BZ PVC Extruded Example Applications: Permanent Sensor Fabrication, Laboratories,
Protection Systems. A UTC Fire & Security Company F-73-01. Linear Heat Detector FEATURES DESCRIPTION APPLICATIONS BENEFITS
Effective: May 2007 AlarmLine TM R Protection Systems Linear Heat Detector A UTC Fire & Security Company F-73-01 FEATURES Integrating Type Linear Heat Detector Analog Sensing Field Adjustable Alarm Set
WIRE, TERMINAL AND CONNECTOR REPAIR CONDUCTORS
CONDUCTORS Conductors are needed to complete the path for electrical current to flow from the power source to the working devices and back to the power source. Special wiring is needed for battery cables
IEEE POWER ENGINEERING SOCIETY CHICAGO CHAPTER THE OKONITE COMPANY WEDNESDAY JANUARY 11, 2006 JIM FITZGERALD ENGINEERING LINGO
IEEE POWER ENGINEERING SOCIETY CHICAGO CHAPTER THE OKONITE COMPANY WEDNESDAY JANUARY 11, 2006 JIM FITZGERALD ENGINEERING LINGO WHEN YOU HEAR AN ENGINEER SAY A NUMBER OF DIFFERENT APPROACHES ARE BEING IMPLEMENTED
Pipe Freeze Protection Design/Install Guide
Pipe Freeze Protection Design/Install Guide Page 1 of 16 Pipe Freeze Protection Design / Install Guide CONTENTS Introduction Page 3 STEP 1 Information Required Page 4 STEP 2 Design Considerations Page
The soot and scale problems
Dr. Albrecht Kaupp Page 1 The soot and scale problems Issue Soot and scale do not only increase energy consumption but are as well a major cause of tube failure. Learning Objectives Understanding the implications
ALARMLINE ANALOGUE Linear Heat Detection System
ALARMLINE ANALOGUE Alarmline Analogue sensor cable senses temperature variations by continuously monitoring the resistance of specially doped N.T.C. polymeric insulation. A change in temperature produces
HEAT TRACING PRODUCTS
PJ-324 HEAT TRACING PRODUCTS Training Manual CHROMALOX FOR INTERNAL USE ONLY Copyright 1998, E. L. Wiegand Div. Emerson Electric The facts and the recommendations made in this publication are based on
CATHODIC PROTECTION SYSTEM DESIGN
CATHODIC PROTECTION SYSTEM DESIGN Presented By DENIS L ROSSI P.E. CORROSION ENGINEER New England C P Inc. Corrosion Fundamentals What is corrosion? It is defined as the degradation or deterioration of
Uniprise Solutions COAX 101. White Paper. www.commscope.com
Uniprise Solutions COAX 101 White Paper www.commscope.com Structured cable systems have very thorough standards for fiber optic and twisted pair installations. The cabling components and installed systems
CTI TECHNICAL BULLETIN Number 9: A publication of the Cable Tray Institute
CTI TECHNICAL BULLETIN Number 9: A publication of the Cable Tray Institute Cable Tray Wiring Systems Have Many Cost Advantages Cost is usually a major consideration in the selection of a wiring system.
Reliability requires consulting engineers and end users to grasp design, maintenance basics. By Reza Tajali, P.E. Square D Power Systems Engineering
LOW VOLTAGE CIRCUIT BREAKER GUIDELINES FOR DATA CENTERS Reliability requires consulting engineers and end users to grasp design, maintenance basics By Reza Tajali, P.E. Square D Power Systems Engineering
Stephen G. Whitley, Senior Vice President & Chief Operating Officer
Peter T. Brandien Vice President, System Operations To: Stephen G. Whitley, Senior Vice President & Chief Operating Officer From: Peter T. Brandien Re: Discussion of Cable Technologies Under Evaluation
This chapter is devided into two sections:
This chapter is devided into two sections: Page Installation requirements........................................................................ 127 The installation process..........................................................................
POWER AND VOLTAGE RATING
POWER AND VOLTAGE RATING SCOPE: The purpose of this document is to take the confusion out of power and voltage ratings in specifications and in product information publications. This will be accomplished
Mineral Insulated Cable A cable for today and tomorrow!
Mineral Insulated Cable A cable for today and tomorrow! Bill Davis Technical and Business Development Director If MIC had never been introduced, the industry would be actively pursuing the development
Avoiding Burning Through: Control the Inside Surface Temperature, Not the Pressure
Originally published in the Canadian Welding Association Journal, Spring 2013, pp 30 39 Welding on In service Pipelines: Dispelling Popular Myths and Misconceptions Bill Amend Sr. Principal Engineer, Welding
ELECTRIC HEATER COMPANY Operating and Maintenance Manual For Immersion Heating Elements
ELECTRIC HEATER COMPANY Operating and Maintenance Manual For Immersion Heating Elements HUBBELL ELECTRIC HEATER COMPANY P.O. BOX 288 STRATFORD, CT 06615 PHONE: (203) 378-2659 FAX: (203) 378-3593 INTERNET:
Fire Performance Standard
Fire Performance Standard At present, in cable industry, Fire Retardant, Low Smoke Halogen Free (LSZH), Low Smoke Fume (LSF) and Fire Resistant cables are all described as Fire survival Cables. Flame Retardant
Avoiding AC Capacitor Failures in Large UPS Systems
Avoiding AC Capacitor Failures in Large UPS Systems White Paper #60 Revision 0 Executive Summary Most AC power capacitor failures experienced in large UPS systems are avoidable. Capacitor failures can
CORNING CABLE SYSTEMS GENERIC SPECIFICATION FOR TIGHT BUFFER OPTICAL FIBER CABLES FOR INTER- AND INTRABUILDING APPLICATIONS.
CORNING CABLE SYSTEMS GENERIC SPECIFICATION FOR TIGHT BUFFER OPTICAL FIBER CABLES FOR INTER- AND INTRABUILDING APPLICATIONS September 2006 Revision 7 Corning Cable Systems reserves the right to update
Wire and Cable Product Guide
Wire and Cable Product Guide Applications Elvax resins with low vinyl acetate content, typically 9 to 15%, are well suited for compounding into primary insulation of UL listed, type XHHW building wire,
PT-6000 Power Tower INSTALLATION MANUAL SPECIFICATIONS
PT-6000 Power Tower INSTALLATION MANUAL 10.5 9.75 12 22.75 10.75 MAXIMUM SOIL HEIGHT: DO NOT ALLOW FILL TO EXCEED THIS LEVEL! 11.5 4 4 13 Optional PT-BASE for new installations or when previous 2000/6000
Chapter 9. Bonding and Grounding
Chapter 9 Bonding and Grounding Objectives Describe why the cable should be bonded Describe bonding and grounding procedures Define Bonding and Grounding Explain Safety Benefits and intent of bonding and
UGVCL/SP/591/11KV HT AB CABLE
TECHNICAL SPECIFICATION FOR 11KV AERIAL BUNCHED CABLES FOR OVERHEAD LINES (CROSSED LINKED POLYTHENE DRY GAS CURED) 1. SCOPE This specification covers requirements of XLPE insulated, 11 KV Aerial Bunched
Top Drive Service Loops. Conventional, Enhanced and Superior Solutions for Drilling Applications
Top Drive Service Loops Conventional, Enhanced and Superior Solutions for Drilling Applications Linking the future As the worldwide leader in the cable industry, Prysmian Group believes in the effective,
Cable Limiters. Increase System Reliability Decrease Downtime PRODUCT GUIDE
Limiters Increase System Reliability Decrease Downtime PRODUCT GUIDE Mersen Limiters Increase system reliability and versatility with Mersen Limiters. Increase system reliability and versatility with Mersen
This paper describes Digital Equipment Corporation Semiconductor Division s
WHITEPAPER By Edd Hanson and Heather Benson-Woodward of Digital Semiconductor Michael Bonner of Advanced Energy Industries, Inc. This paper describes Digital Equipment Corporation Semiconductor Division
Flexible cables for submersible products
Flexible cables for submersible products Standards SUBCAB cables complies with the following general standards: IEC 6045 (general) IEC 608 class 5 (conductor) IEC 608-- CLAUSE 9 (oil resistant) IEC 608--
ICM Project Underground Infrastructure and Cable
EB 0 00 Tab Schedule B ( pages) ICM Project Underground Infrastructure and Cable Handwell Replacement Segment (THESL) EB 0 00 Tab Schedule B I EXECUTIVE SUMMARY. Project Description 0 The handwell replacement
SELF-REGULATING PIPE TRACING HEATER CABLE
SELF-REGULATING PIPE TRACING HEATER CABLE Installation & Operation Manual TABLE OF CONTENTS GENERAL INFORMATION... 1 How Heating Systems Work...1 PRODUCT SELECTION... 1 RECEIPT & STORAGE... 1 Receipt...1
KSR-SK-DB In-Line Splice Kit KSR Snow Melting Cable INSTALLATION PROCEDURES
KSR-SK-DB In-Line Splice Kit KSR Snow Melting Cable INSTALLATION PROCEDURES KSR-SK-DB The following installation procedures are suggested guidelines for the installation of in-line cable splices. They
HVAC Super Pro FAQ. Can HVAC SUPER PRO be used on both hard and soft copper and aluminum tubing?
HVAC Super Pro FAQ Application What is the working time for HVAC SUPER PRO? HVAC SUPER PRO can be left on the tubing and connector for several minutes, but when the tubing is inserted into the connector
Defining the Needs of Modern Data Center Power Systems, Low Voltage Circuit Breaker Application
Defining the Needs of Modern Data Center Power Systems, Low Voltage Circuit Breaker Application by Reza Tajali, P.E. Square D Company ABSTRACT In modern data centers, Uninterruptible Power Supplies (UPS)
Use & Care Manual. Electric Tankless Water Heaters. With Installation Instructions for the Installer AP15447 (10/10)
Use & Care Manual With Installation Instructions for the Installer Electric Tankless Water Heaters The purpose of this manual is twofold: one, to provide the installer with the basic directions and recommendations
Installation Instructions. Industrial Heating Cable Products
Installation Instructions Industrial Heating Cable Products PJ438-21 161-057884-001 September, 2014 Important General Instructions These instructions are to be followed when installing Chromalox Heating
Electric heat tracing
PIPELINE DESIGN Figure 1. Shorter, more complex piping at a process plant. Electric heat tracing Neil Malone, Heat Trace, UK, discusses electric heat tracing of long pipelines. In considering electric
Carbon Cable. Sergio Rubio Carles Paul Albert Monte
Carbon Cable Sergio Rubio Carles Paul Albert Monte Carbon, Copper and Manganine PhYsical PropERTieS CARBON PROPERTIES Carbon physical Properties Temperature Coefficient α -0,0005 ºC-1 Density D 2260 kg/m3
TAN δ (DELTA) CABLE TESTING OVERVIEW AND ANSWERS TO FREQUENTLY ASKED QUESTIONS. What Is Tan δ, Or Tan Delta?
TAN δ (DELTA) CABLE TESTING OVERVIEW AND ANSWERS TO FREQUENTLY ASKED QUESTIONS What Is Tan δ, Or Tan Delta? Tan Delta, also called Loss Angle or Dissipation Factor testing, is a diagnostic method of testing
Oscar E. Morel UtilX Corporation
Oscar E. Morel UtilX Corporation Time Domain Reflectometry (TDR) has been the preferred technique to assess: Cable length Splice number and spatial location, and Metallic neutral condition Tests for neutral
Caledonian Submersible Pump Cables for Oil Industry >> IEEE 1018 >> IEEE 1019 >> API RP 11S5
Caledonian Submersible Pump Cables for Oil Industry >> IEEE 1018 >> IEEE 1019 >> API RP 11S5 Caledonian Windmill Cables COMPANY PROFILE Table of Content Caledonian, established in 1978, offers one of the
Electric Heat Tracing INSTALLATION PROCEDURES
INSTALLATION PROCEDURES Complete Electric Heat Tracing System... Types of Heating Cables 1... Self-Regulating Heating Cables: BSX (refer to Form TEP0067U) 1725 II 2 G & D Ex e II T5 or T6 DEMKO 02ATEX0132424,
ENERGY TRANSFER SYSTEMS AND THEIR DYNAMIC ANALYSIS
ENERGY TRANSFER SYSTEMS AND THEIR DYNAMIC ANALYSIS Many mechanical energy systems are devoted to transfer of energy between two points: the source or prime mover (input) and the load (output). For chemical
T A B L E T 1 T E S T S A N D I N S P E C T I O N C A B L E P C U T A N D P C U T - A
T A B L E T 1 1 of 7 Tests & Inspection Cable PCUT & PCUT-A (Table T1) T E S T S A N D I N S P E C T I O N C A B L E P C U T A N D P C U T - A No. Test Scale MOC Requirements G 20:10:001:01 Defined Test
GroundRod AC Substation Earthing Tutorial
1 GroundRod AC Substation Earthing Tutorial 1. Functions of an earthing system The two primary functions of a safe earthing system are: To ensure that a person who is in the vicinity of earthed facilities
PTC-Resistor Temperature-Sensors MINIKA to DIN 44 081 and DIN 44 082
PTC-Resistor Temperature-Sensors MINIKA to DIN 44 081 and DIN 44 082 General PTC-resistor temperature sensors (also called PTC-resistors or thermistors) are temperatur dependent semiconductor resistors
NELSON HEAT TRACING SYSTEMS
DESCRIPTION The HASK-P Hazardous Area Seal Kit provides the cable termination and explosion proof seal parts needed to make the power end electrical connections associated with Nelson Heat Tracing Systems
WIRE AND CABLE ENGINEERING GUIDE
Excerpt From Prysmian s WIRE AND CABLE ENGINEERING GUIDE Page 1 of 8 CABLE TESTING Testing represents an integral part in the life of a cable. A cable will be subjected to multiple tests in its lifetime
ARC FLASH CALCULATIONS & LABELING REQUIREMENTS
ARC FLASH CALCULATIONS & LABELING REQUIREMENTS Presented by: Edmund Elizalde EYP Mission Critical Facilities, Inc. Slides by: Lonnie Lindell SKM Systems Analysis, Inc. 1 Agenda NEC 110.16 NFPA 70E IEEE
Product Safety Considerations for Insulation Coordination of Low- Voltage Equipment. Scott Aldous, Compliance Engineer
Product Safety Considerations for Insulation Coordination of Low- Voltage Equipment Scott Aldous, Compliance Engineer What is Insulation Coordination? From IEC 60664-1, Edition 1.2: So what does that mean
Application Note. Soldering Methods and Procedures for 1st and 2nd Generation Power Modules. Overview. Analysis of a Good Solder Joint
Soldering Methods and Procedures for 1st and 2nd Generation Power Modules Overview This document is intended to provide guidance in utilizing soldering practices to make high quality connections of Vicor
Fault location on power cables. Fault location on power cables
Fault location on power cables Fault location on power cables Contents: 1. Introduction 2. Construction of power cables 3. Cable faults 01. Introduction Fault location on communication and power cables
COLD LEAD OPTIONS FOR XMI MINERAL INSULATED (MI) HEATING CABLES
COLD LEAD OPTIONS FOR XMI MINERAL INSULATED (MI) HEATING CABLES PRODUCT OVERVIEW XMI with standard MI cold lead and Type X connector MI cable heated section PRODUCT OVERVIEW XMI with PyroFLX cold lead
A quick product finder for commercial applications JUDD WIRE INC. A member of the Sumitomo Electric Industries group of companies
A quick product finder for commercial applications JUDD WIRE INC. A member of the Sumitomo Electric Industries group of companies Select, Customize, Order & Receive Products with Ease This catalog contains
The Electrical Properties of Materials: Resistivity
The Electrical Properties of Materials: Resistivity 1 Objectives 1. To understand the properties of resistance and resistivity in conductors, 2. To measure the resistivity and temperature coefficient of
13 common causes of motor failure
13 common causes of motor failure Application Note What to look for and how to improve asset uptime Motors are used everywhere in industrial environments and they are becoming increasingly complex and
Polyolefin Heat Shrink Tubing for Tight-Tolerance Medical Applications
Polyolefin Heat Shrink Tubing for Tight-Tolerance Medical Applications Understanding the Advantages and Development Process By Apur Lathiya Vice President and General Manager, Vesta Thermoplastics Division
Heat Pipe Selection Revision 12/04/2001
Heat Pipe Selection Revision 12/04/2001 Heat pipes are being used very often in particular applications when conventional cooling methods are not suitable. Once the need for heat pipe arises, the most
Shelf Life Prediction Of Medical Gloves
Shelf Life Prediction Of Medical Gloves Presented for the ASTM WG Committee for Medical Glove Expiration Dating Guidance By Uday Karmarkar Akron Rubber Development Laboratory, Inc. [email protected]
Basic RTD Measurements. Basics of Resistance Temperature Detectors
Basic RTD Measurements Basics of Resistance Temperature Detectors Platinum RTD resistances range from about 10 O for a birdcage configuration to 10k O for a film type, but the most common is 100 O at 0
INTERNATIONAL STANDARD
INTERNATIONAL STANDARD IEC 60502-1 Second edition 2004-04 Power cables with extruded insulation and their accessories for rated voltages from 1 kv (U m = 1,2 kv) up to 30 kv (U m = 36 kv) Part 1: Cables
Heat Tracing Sales Mt. Airy, Maryland www.heattracingsales.com 410-795-2223. Installation Instructions
Chromalox Installation Instructions DIVISION 4 SALES REFERENCE DATE SERVICE REFERENCE SECTION DTS (Supersedes PJ944-5) PJ944-6 161-562581-049 MARCH, 2012 DTS-HAZ For Use With Self-Regulating & Constant
Stephanie Watson. Service Life of Electrical Cable and Condition Monitoring Methods
Service Life of Electrical Cable and Condition Monitoring Methods Stephanie Watson Polymeric Materials Group Materials and Structural Systems Division Engineering Laboratory [email protected] Outline
G670 Intermittent Pilot Ignition Controls
Installation Sheets Manual 121 Gas Combustion Combination Controls and Systems Section G Technical Bulletin Issue Date 0300 Intermittent Pilot Ignition Controls Figure 1: Intermittent Pilot Ignition Control
Self-Regulating Pipe Tracing Heating Cable Specification/Application Guide. Polyolefin. Performance and Rating Data
TSR Self-Regulating Pipe Tracing Heating Cable Specification/Application Guide READ CAREFULLY PRINCIPLE OF OPERATION Easy Heat TSR is a self-regulating heating cable that automatically varies its heat
Power Supply Cables and Connectors
Power Supply Cables and Connectors Often during the excitement of designing a challenging new system, some of the more mundane engineering aspects get overlooked. This is especially true of connections
RE-ENTERABLE SPLICE CLOSURE KITS. (For Air Core None Pressurized Cable)
Triple T Broadband Public Co., Ltd. Outside Plant Standard Sector Specification No. OES-001-027-04 Issued: RE-ENTERABLE SPLICE CLOSURE KITS (For Air Core None Pressurized Cable) 1. SCOPE 1.1. This specification
RayClic Connection System Installation Instructions
F M -W RayClic Connection System Installation Instructions RayClic WARNING: Shock Hazard 718K Pipe Heating Cable with HWAT, IceStop, also Listed De-icing and and XL-Trace heating Snow Melting Equipment
Lead & Magnet Wire Connection Methods Using the Tin Fusing Method Joyal A Division of AWE, Inc.
Lead & Magnet Wire Connection Methods Using the Tin Fusing Method Joyal A Division of AWE, Inc. Abstract The technology for connecting lead and magnet wires for electric motors and electro mechanical devices
Contact Information: 4031-0001 Electrical Connection Kit for CL Series Constant Wattage Temptrace for Low Temperature Maintenance.
Technical Data Sheet & Installation Instructions for 4031-0001 Electrical Connection Kit for CL Series Constant Wattage Temptrace for Low Temperature Maintenance Bulletin CL-II Contact Information: Parker
INTERNATIONAL TELECOMMUNICATION UNION #/.3425#4)/. ).34!,,!4)/.!.$ 02/4%#4)/. /& #!",%3!.$ /4(%2 %,%-%.43 /& /543)$% 0,!.43
INTERNATIONAL TELECOMMUNICATION UNION )454, TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU #/.3425#4)/. ).34!,,!4)/.!.$ 02/4%#4)/. /& #!",%3!.$ /4(%2 %,%-%.43 /& /543)$% 0,!.43 /04)#!, &)"2% #!",%3 &/2
International Electrotechnical Commission Standards
International Electrotechnical Commission Standards Standard IEC 60028 IEC 60038 IEC 60050-461 IEC 60055-1 IEC 60055-2 IEC 60092-101 IEC 60092-350 IEC 60092-351 IEC 60092-352 IEC 60092-353 IEC 60092-354