Chromalox PRECISION HEAT AND CONTROL. Electrical Heat Tracing Systems Design Guide
|
|
|
- Doreen Lamb
- 9 years ago
- Views:
Transcription
1 Chromalox PRECISION HEAT AND CONTROL Electrical Heat Tracing Systems Design Guide
2 INTRODUCTION TABLE OF CONTENTS TABLE OF CONTENTS Thermal Design - Pipes:.. 1 Thermal Design - Tanks:.. 6 Heating Cable Selection:. 8 Mineral Insulated Cable Design: Electrical Design: Component Selection and Accessories: Control Selection: IntelliTRACE Controls This design guide provides a step-by-step approach for the design, specification, and selection of a bill of materials for an electric heat tracing system. Electric heat tracing systems are designed to make up for the heat lost from process system equipment through the thermal insulation. In some cases, the heat tracing system can be used for system heat-up at initial startup or after a power shutdown. The information in this design guide will allow the user to design, specify, and select a complete bill of materials for freeze protection or process maintenance applications for a piping system or tank. By following the steps in this guide the user can easily select a complete bill of materials for the system, including heating cable, connection accessories, and temperature controls.
3 THERMAL DESIGN PIPES The first step in designing a heat trace system is to determine the heat loss from each pipe or tank to be traced. Collect the following data for each pipe (for tank applications go to page 6). Then follow the steps below to determine the heat loss. Maintenance Temperature, T m : Minimum Ambient Temperature, T a : Location, Indoor/ Outdoor: Wind Speed, if applicable: Nominal Pipe/ Tubing Size, D P : Additional Safety Factor, if required: Thermal Insulation Type and Thickness: Example: English Maintenance Temperature, T m : 40ºF Minimum Ambient Temperature, T a : -20ºF Location, Indoor/ Outdoor: Outdoor Wind Speed, if applicable: 10 mph Nominal Pipe/ Tubing Size, D P : 3" Steel Additional Safety Factor, if required: None Thermal Insulation Type 2" and Thickness: Cellular Glass Example: Metric Maintenance Temperature, T m : Minimum Ambient Temperature, T a : Location, Indoor/ Outdoor: Wind Speed, if applicable: Nominal Pipe/ Tubing Size, D P : Additional Safety Factor, if required: Thermal Insulation Type and Thickness: Step 1. Calculate ΔT ΔT = Tm - Ta English = 40ºF - (-20ºF) = 60ºF Metric = 4.4ºC - (-28.9ºC) = 33.3ºC Step 2. Determine Pipe Heat Loss 4.4ºC -28.9ºC Outdoor 16 kph 76 mm Steel None 51mm Cellular Glass Find Q P in Table 1 (page 2) for the nominal pipe size and insulation thickness based on ΔT. For example, for a 3" (76 mm) pipe with 2" (51 mm) insulation and ΔT = 60ºF (33.3ºC), the value for Q P is 5.5 W/ft (10.8 W/m). Step 3. Adjust for Insulation Table 1 (page 2) is based on ASTM C547 Fiberglas insulation. Q P, as found in the step above, must be adjusted for the insulation type. Multiply your heat loss by Ia, the Insulation Adjustment Factor, from the values in Table 2 (page 5). Q F = Q P x Ia For Cellular Glass, Ia = 1.48 English Q F = 3.3 W/ft x 1.48 = 4.88 W/ft Metric Q F = 10.8 W/m x 1.48 = W/m Step 4. Correct for Indoor Location/Windspeed If location is indoors multiply Q F by 0.9. Step 5. Correct for Additional Safety Factor Table 1 is based on 10% safety factor and 20 mph (32 kph) windspeed, add 5% margin for each 5 mph (8 kph) over 20 mph (32 kph). THERMAL DESIGN- PIPES THERMAL DESIGN-PIPES 1
4 2THERMAL DESIGN- PIPES Table 1 Pipe Heat Loss (Q P ) in W/ft and W/m Based on Temperature Differential and Insulation Thickness Nominal Temperature Difference Between Pipe and Ambient Pipe Size, in. (ID) mm (OD) DegºF 40ºF 50ºF 60ºF 70ºF 80ºF 90ºF 100ºF 120ºF 140ºF 160ºF 180ºF 200ºF 220ºF 240ºF 260ºF Si DegºC 23.0ºC 28.0ºC 33.4ºC 39.0ºC 44.5ºC 50.0ºC 55.6ºC 66.7ºC 77.8ºC 88.9ºC 100.0ºC 111.1ºC 122.2ºC 133.4ºC 144.5ºC 1" (25.4 mm) Insulation Thickness 1 /2" W/ft mm W/m /4" W/ft mm W/m " W/ft mm W/m /2" W/ft mm W/m " W/ft mm W/m /2" W/ft mm W/m " W/ft mm W/m " W/ft mm W/m " W/ft mm W/m " W/ft mm W/m " W/ft mm W/m " W/ft mm W/m " W/ft mm W/m " W/ft mm W/m " W/ft mm W/m " W/ft mm W/m " W/ft mm W/m " W/ft mm W/m
5 Table 1 cont'd. Nominal Temperature Difference Between Pipe and Ambient Pipe Size, in. (ID) DegºF 40ºF 50ºF 60ºF 70ºF 80ºF 90ºF 100ºF 120ºF 140ºF 160ºF 180ºF 200ºF 220ºF 240ºF 260ºF mm (OD) Si DegºC 23.0ºC 28.0ºC 33.4ºC 39.0ºC 44.5ºC 50.0ºC 55.6ºC 66.7ºC 77.8ºC 88.9ºC 100.0ºC 111.1ºC 122.2ºC 133.4ºC 144.5ºC 1.5" (38 mm) Insulation Thickness 1 /2" W/ft mm W/m /4" W/ft mm W/m " W/ft mm W/m /2" W/ft mm W/m " W/ft mm W/m /2" W/ft mm W/m " W/ft mm W/m " W/ft mm W/m " W/ft mm W/m " W/ft mm W/m " W/ft mm W/m " W/ft mm W/m " W/ft mm W/m " W/ft mm W/m " W/ft mm W/m " W/ft mm W/m " W/ft mm W/m " W/ft mm W/m THERMAL DESIGN- PIPES
6 4THERMAL DESIGN- PIPES Table 1 cont'd. Nominal Temperature Difference Between Pipe and Ambient Pipe Size, in. (ID) DegºF 40ºF 50ºF 60ºF 70ºF 80ºF 90ºF 100ºF 120ºF 140ºF 160ºF 180ºF 200ºF 220ºF 240ºF 260ºF mm (OD) Si DegºC 23.0ºC 28.0ºC 33.4ºC 39.0ºC 44.5ºC 50.0ºC 55.6ºC 66.7ºC 77.8ºC 88.9ºC 100.0ºC 111.1ºC 122.2ºC 133.4ºC 144.5ºC 2" (50.8mm) Insulation Thickness 1 /2" W/ft mm W/m /4" W/ft mm W/m " W/ft mm W/m /2" W/ft mm W/m " W/ft mm W/m /2" W/ft mm W/m " W/ft mm W/m " W/ft mm W/m " W/ft mm W/m " W/ft mm W/m " W/ft mm W/m " W/ft mm W/m " W/ft mm W/m " W/ft mm W/m " W/ft mm W/m " W/ft mm W/m " W/ft mm W/m " W/ft mm W/m
7 Table 1 cont'd. Nominal Temperature Difference Between Pipe and Ambient Pipe Size, in. (ID) DegºF 40ºF 50ºF 60ºF 70ºF 80ºF 90ºF 100ºF 120ºF 140ºF 160ºF 180ºF 200ºF 220ºF 240ºF 260ºF mm (OD) Si DegºC 23.0ºC 28.0ºC 33.4ºC 39.0ºC 44.5ºC 50.0ºC 55.6ºC 66.7ºC 77.8ºC 88.9ºC 100.0ºC 111.1ºC 122.2ºC 133.4ºC 144.5ºC 3" (76.2 mm) Insulation Thickness 1 /2" W/ft mm W/m /4" W/ft mm W/m " W/ft mm W/m /2" W/ft mm W/m " W/ft mm W/m /2" W/ft mm W/m " W/ft mm W/m " W/ft mm W/m " W/ft mm W/m " W/ft mm W/m " W/ft mm W/m " W/ft mm W/m " W/ft mm W/m " W/ft mm W/m W/ft mm W/m " W/ft mm W/m " W/ft mm W/m " W/ft mm W/m Table 2 Insulation Adjustment Factors Pipe Insulation Type Insulation Adjustment Factor Glass fiber (ASTM C547) 1.00 Calcium silicate (ASTM C533) 1.48 Cellular glass (ASTM C552) 1.48 Rigid cellular urethane (ASTM C591) 0.64 Foamed elastomer (ASTM C534) 1.16 Mineral fiber blanket (ASTM C553) 1.16 Expanded perlite (ASTM C610) THERMAL DESIGN- PIPES
8 6THERMAL DESIGN- TANKS THERMAL DESIGN-TANKS THERMAL DESIGN TANKS S H CYLINDRICAL TANK, FLAT AREA = AREA (ENDS) + AREA (SIDE) = πd 2 /2 + πdh CYLINDRICAL TANK, CONICAL AREA = AREA (TOP) + AREA (SIDE) + AREA (CONE) = πd 2 /4 + πdh + (π/2)(d+d) (D d) 2 +h 2 4 D d H CYLINDRICAL TANK, DISHED AREA = AREA (TOP) + AREA (SIDE) + AREA (BOTTOM) = (π/4)(d 2 +4h 2 ) + πdh +πd2/4 W L RECTANGULAR TANK AREA = AREA (TOP) + AREA (SIDE) + AREA (BOTTOM) = 2(WH+HL+WL) Table 3 Heat Loss (Q T) for Various Insulation Thicknesses D Insulation Thickness Heat Loss (Q T ) in. mm W/ft 2 /ºF W/m 2 /ºC 1 / / NOTE: Heat loss values based on 20 mph (32 kph) wind, 10% safety factor, and Fiberglas insulation at 50ºF (10ºC). D H H h Collect the following information for each tank. Maintenance Temperature, T m : Minimum Ambient Temperature, T a : Location, Indoor/ Outdoor: Wind Speed, if applicable: Tank Shape and Surface Area: Additional Safety Factor, if required: Thermal Insulation Type and Thickness: Example: English Maintenance Temperature, T m : 40ºF Minimum Ambient Temperature, T a : -20ºF Location, Indoor/ Outdoor: Outdoor Wind Speed, if applicable: Tank Shape and Surface Area: 20 mph Steel Horizontal Cylinder 3 ft dia. 6 ft long Additional Safety Factor, if required: None Thermal Insulation Type 2" and Thickness: Cellular Glass Example: Metric Maintenance Temperature, T m : Minimum Ambient Temperature, T a : Location, Indoor/ Outdoor: Wind Speed, if applicable: Tank Shape and Surface Area: Additional Safety Factor, if required: Thermal Insulation Type and Thickness: Step 1. Calculate ΔT ΔT = T m - T a English = 40ºF - (-20ºF) = 60ºF Metric = 4.4ºC - (-28.9ºC) = 33.3ºC 4.4ºC -28.9ºC Outdoor 32 kph Steel Horizontal Cylinder 0.92 m dia m long None 51mm Cellular Glass
9 Step 2. Determine Total Surface Area of Tank Most tanks are a combination of shapes. Determine the surface area of each section and then add the areas for each section to determine the overall surface area, A. A = πd 2 /2 + πdh English = (3.14)(3 ft) 2 /2 + (3.14)(3 ft)(6 ft) = 70.7 ft 2 Metric = (3.14)(0.92 m) 2 /2 + (3.14)(0.92 m)(1.83 m) = 6.6 m 2 Step 3. Determine Q T Find Q T in Table 3 for the corresponding insulation thickness. Step 4. Calculate Heat Loss, Q Q = (Q T)(ΔT)(A) English = (0.040 W/ft 2 /ºF)(60ºF)(70.7 ft 2 ) = 170 W Metric = (0.775 W/m 2 /ºC)(33.3ºC)(6.6m 2 ) = 170 W Step 5. Adjust for Insulation Q, as found in the step above, must be adjusted for the insulation type. Multiply your heat loss by I a, the Insulation Adjustment Factor, from the values in Table 2. Using the Insulation Adjustment Factor (I a ) for cellular glass (1.48): Q F = Q x Ia = 170 W x 1.48 = 252 W Step 6. Correct for Indoor Location/Windspeed If the application is indoors, multiply Q F by 0.9. Since Table 3 is based on 20 mph (32 kph) windspeed, add 5% margin for each additional 5 mph (8 kph) over 20 mph (32 kph). Step 7. Correct for Additional Safety Factors Step 8. Additional Equipment Heat Losses Equipment such as ladders, manways, and support legs act as heat sinks and increase the overall heat loss of the tanks. For each piece of equipment, use Table 4 to calculate equipment heat loss and add to the heat loss calculated above. For example, additional heat loss for 4 support legs: Q A = (Q S ) (ΔT) x number of legs English = (0.5 W/ºF)(60ºF) x 4 = 120 W Metric = (0.9 W/ºC)(33.3º/C) x 4 = 120 W Step 9. Calculate the Cable Length Required To determine the length required, take the total heat loss as calculated in the previous steps and divide by the chosen cable output at the maintenance temperature. (See Figures 1-4.) Q = Q F + Q A = 252 W W = 372 W SRL5-CT 40ºF = 4.8 W/ft L = 372 W 4.8 W/ft L = 78 ft Table 4 Tank Equipment Heat Loss Calculation (Q S ) Support Legs 0.5 W/ºF (0.9 W/ºC) x number of legs Ladder Manways 2.5 W/ºF (4.5 W/ºC) x number of ladders 10.0 W/ºF (18.0 W/ºC) x number of manways THERMAL DESIGN- TANKS 7
10 HEATING CABLE SELECTION HEATING CABLE SELECTION HEATING CABLE SELECTION To determine the correct cable for your application, determine the following information: Maintenance Temperature = Max. Exposure Temperature = Pipe Material = Service Voltage = Chemical Environment = Area Classification = Heat Requirement (from Thermal Design Section) = Example: English Maintenance Temperature = 40ºF Max. Exposure Temperature = 100ºF Pipe Material = Stainless Steel Service Voltage = 120V Chemical Environment = Organic Area Classification = CID2 Group B Heat Requirement (from Thermal Design Section) = 4.88 W/ft Example: Metric Maintenance Temperature = Max. Exposure Temperature = Pipe Material = Service Voltage = Chemical Environment = Area Classification = Heat Requirement (from Thermal Design Section) = 4.4ºC 37.8ºC Stainless Steel 120V Organic CID2 Group B W/m Step 1. Select Heating Cable Family Based on the maximum maintainance temperature, maximum exposure temperature, and area classification, select the heating cable family from Table 5. Note: Maximum maintenance temperatures for constant wattage cables (CWM) are dependent upon cable wattage rating and the use of alumium foil tape. See Table 6 (page 10). Example: Based on information, select the SRL (Self- Regulating Low Temperature) Cable Family. Selection: SRL * - * * 8
11 Table 5 Heating Cable Families Heating Cable Family SRL (Self-Regulating Low Temperature) SRM/E (Self-Regulating Medium Temperature) HSRL (H-Self- Regulating Low Temperature) HSRM (H-Self- Regulating Medium Temperature) CWM (Constant Wattage) MI (Mineral Insulated) Area Classification Pipe Material Maximum Maintenance Temperature F C Maximum Exposure Temperature (Power Off) F C Ordinary Plastic/Metal 150ºF 65ºC 185ºF 85ºC UL, CSA, FM GOST, Cenelec, CE, ATEX Class I, Div. 2, CSA, FM GOST, Cenelec, Gr. B, C, D (Gr. A, CSA Only) CE, ATEX Class II, Div. 2, CSA, FM GOST, Cenelec Gr. E, F, G (Gr. E, CSA Only) CE Class III, Div. 2, FM Only GOST, Cenelec, CE, ATEX Ordinary Metal Only 302ºF 150ºC 420ºF 215ºC UL, CSA, FM GOST, Cenelec, CE, ATEX Class I Div. 2, CSA, FM GOST, Cenelec, Gr. A, B, C, D, (Gr. A, CSA Only) CE, ATEX Class II, Div. 2, CSA Only GOST, Cenelec, Gr. F, G CE, ATEX Class I, Div. 1, Plastic/Metal 150ºF 66ºC 185ºF 85ºC FM Only Gr.B,C,D Class II, Div. 1, FM Only Gr.E,F,G Class III, Div. 1 FM Only Class I, Div. 1, Metal Only 302ºF 150ºC 420ºF 215ºC FM Only Gr.B,C,D Class II, Div. 1, FM Only Gr.E,F,G Class III, Div. 1 FM Only Ordinary Metal Only See Table 4 392ºF 200ºC UL, CSA Hazardous Area Consult Factory Ordinary Metal Only See Section 1,100ºF 593ºC Hazardous Area Consult Factory Approvals NOTE: It is the responsibility of the facility manager or engineer to determine the classification of an area where heat trace will be installed. The factory can help determine a suitable cable based on the information provided. U.S. Consult Factory Other Consult Factory 9HEATING CABLE SELECTION
12 10HEATING CABLE SELECTION Step 2. Select Heating Cable Construction Options Select from Table 7 the appropriate construction option for the desired level of mechanical and corrosive chemical protection. -C option cable is constructed with a tinned copper grounding braid only. -CR option cable is constructed with a tinned copper braid and polyolefin overjacket. -CT option cable is constructed with a tinned copper braid and fluoropolymer overjacket. Note: If your area classification is Class I Division 1, Class II Division 1, or Class III Division 1, the HSRL and HSRM cable families are constructed with -CT option only. Example: Since the environment in our example contained organic chemical solutions, choose the -CT option for the fluoropolymer overjacket to provide mechanical and corrosion protection. Selection: SRL*-* CT Table 6 Maximum Maintenance Temperatures for Constant Wattage Cables (CWM) Table 7 Heating Cable Construction Options Exposure Conditions Step 3. Select Thermal Output Rating 1. For Self-Regulating Cable See Figures 1 and 2 (page 12) if piping is metallic and Figures 3 and 4 (page 13) if piping is plastic. Find your actual heat loss, Q, (as previously calculated on pages 1 or 7) on the Y-axis of the graph and the maintenance temperature required on the X-axis. Select the cable for which the thermal output is Q at T m. Example: In the step above, we have chosen the SRL cable family and our piping is metallic. Therefore, refer to Figure 1. Calculated heat loss, W, is 4.88 W/ft (0 W/m). Find this point on the Y-axis. Maintenance temperature is 40ºF (4.4ºC). Find this point on the X-axis. Choose the cable that lies above this point on the graph. Selection: SRL5-*CT 2. For Constant Wattage Cable Select the cable output that most closely exceeds the calculated heat loss, Q. Cable wattage outputs offered are 4, 8, and 12 W/ft (13, 26, and 40 W/m). 3. For Mineral Insulated Cable See pages 17 and 18 for information on cable assemblies. Cable Rating, W/ft (W/m) 4 W 8 W 12 W Maximum Temperature ºF ºC ºF ºC ºF ºC Without Aluminum Tape With Aluminum Tape C -CR -CT Mineral Insulated Moisture Aqueous Solutions of Inorganic Compounds SRL, SRM/E, CWM Liquid Organic Chemicals Acids or Bases
13 In some instances, the calculated heat loss, Q, is greater than the thermal output of the highest rated cable. Should this happen, you can: Recalculate with thicker insulation. Select insulation with a lower K factor and recalculate heat loss. Use two or more heating cable runs in parallel. Spiral the heating cable. DO NOT SPIRAL WRAP CONSTANT WATTAGE CABLE. If you choose to spiral the cable: spiral factor, length of cable/ ft (m) of pipe = Q/Heater output at T m. Example, Using SRL 3-1CT: 4.88 heat loss/3.8 SRL 3-1CT output at 40ºF (4.4ºC) = 1.28 spiral factor Table 8 T-Ratings for Self-Regulating Cable Cable Family Watts / Volts T-Rating Bending the heating cable can cause damage. Therefore, it is recommended that multiple straight runs of heat trace be used instead of spiral wrapping, especially if your pipe is smaller than 3" (88.9 mm) IPS. Straight runs facilitate installation significantly. Step 4. Check T-Ratings For self-regulating cable, use Table 8 to determine if the T-rating for the cable selected is acceptable for use per area classification guidelines. The T- ratings shown in Table 8 are determined based on the product classification approach method per IEEE Standard Please consult the factory if your application requires a T-rating different from those shown in the table. Please consult the factory to determine sheath temperature for applications using constant wattage or mineral insulated cables in hazardous areas. Max. Temp F C SRL 3-1,3-2 T6 185ºF 85ºC 5-1,5-2 T5 212ºF 100ºC 8-1,8-2 T5 212ºF 100ºC 10-1,10-2 T4A 248ºF 120ºC HSRL 3-1,3-2 T6 185ºF 85ºC 5-1,5-2 T5 212ºF 100ºC 8-1,8-2 T5 212ºF 100ºC 10-1,10-2 T4A 248ºF 120ºC SRM/E 3-1,3-2 T3 392ºF 200ºC 5-1,5-2 T3 392ºF 200ºC 8-1,8-2 T3 392ºF 200ºC 10-1,10-2 T2D 419ºF (215ºC) 15-1,15-2 T2D 419ºF (215ºC) 20-1,20-2 T2D 419ºF (215ºC) HSRM 5-1,5-2 T3C 320ºF (160ºC) 8-1,8-2 T3C 320ºF (160ºC) 10-1,10-2 T3A 356ºF (180ºC) 15-1,15-2 T2C 446ºF (230ºC) 20-1,20-2 T2C 446ºF (230ºC) NOTE: In Division 2 applications the sheath temperature of the cable should not exceed 99% of the AIT (auto-ignition temperature) in ºC of the material with the lowest AIT in the atmosphere. In Division 1, the sheath temperature shall not exceed 80% of the lowest AIT in ºC. 11HEATING CABLE SELECTION
14 12HEATING CABLE SELECTION Figure 1 SRL & HSRL Thermal Output Ratings on Insulated Metal Pipe Thermal Output (W/ft) Power Output (W/ft) SRL8 & HSRL8 SRL3 & HSRL3 Cable Output versus Temperature SRL10 & HSRL10 SRL5 & HSRL Pipe Temperature (ºF) English Maintenance Temperature Thermal Output (W/m) SRL8 & HSRL Figure 2 SRM/E & HSRM Thermal Output Ratings on Insulated Metal Pipe English SRM/E10 & HSRM10 SRM/E15 & HSRM15 SRM/E8 & HSRM8 SRM/E5 & HSRM5 SRM/E3 & HSRM3 SRM/E20 & HSRM20 Cable Output versus Temperature Pipe Temperature (ºF) Power Output (W/m) Cable Output versus Temperature SRL10 & HSRL10 SRL5 & HSRL5 SRL3 & HSRL Pipe Temperature (ºC) Maintenance Temperature SRM/E8 & HSRM8 2.0 SRM/E3 & HSRM Metric Metric SRM/E20 & HSRM20 SRM/E15 & HSRM15 SRM/E10 & HSRM10 SRM/E5 & HSRM5 Cable Output versus Temperature Pipe Temperature (ºC)
15 Figure 3 SRL & HSRL Thermal Output Ratings on Plastic Pipes with Aluminum Tape Over Cable Thermal Output (W/ft) Thermal Output (W/ft) SRL8 & HSRL8 SRL10 & HSRL10 SRL5 & HSRL5 SRL3 & HSRL3 Cable Output versus Temperature Pipe Temperature (ºF) English SRL8 & HSRL8 SRL5 & HSRL5 SRL3 & HSRL3 Cable Output versus Temperature SRL10 & HSRL Pipe Temperature (ºF) Thermal Output (W/m) Thermal Output (W/m) SRL8 & HSRL8 SRL5 & HSRL5 SRL3 & HSRL3 SRL10 & HSRL Cable Output versus Temperature Pipe Temperature (ºC) Figure 4 SRL & HSRL Thermal Output Ratings on Plastic Pipes with Aluminum Tape Under and Over Cable English Metric Metric SRL10 & HSRL10 SRL8 & HSRL8 SRL5 & HSRL5 SRL3 & HSRL3 Cable Output versus Temperature Pipe Temperature (ºC) 13HEATING CABLE SELECTION
16 14HEATING CABLE SELECTION Step 5. Select Voltage Rating and Adjust for Alternate Voltages Nominal Voltage Options: 1 = 120V or 2 = 240V If the service voltage is 208V, 220V, 230V, or 277V, multiply the thermal output rating on the 240V cable by the appropriate power output factor for self-regulating cable or constant wattage cable found in Table 9. This will give the adjusted power output at the service voltage. Table 9 Output Adjustment Factors for Alternate Voltages for Self-Regulating and Constant Wattage Cables Example: Service Voltage is 120V. No need to apply any adjustment factors. Therefore, choose Option 1. Selection: SRL 5-1CT Note: If your service voltage is 208V, 220V, or 230V, make sure that after your output has been adjusted that it does not drop below the calculated heat loss. If heat loss is greater than adjusted power output choose the next highest wattage cable. Step 6. Determine Chromalox Part Number To order Chromalox self-regulating or constant wattage heating cable, consult Table 10 (page 15), for the Chromalox model number for the chosen cable. Cable Type Watts/Volts 208V 220V 230V 240V 277V SRL or HSRL % 87% 92% 100% 115% % 90% 92% 100% 113% % 91% 94% 100% 112% % 92% 95% 100% 110% SRM/E or HSRM % 86% 92% 100% 124% % 87% 92% 100% 123% % 88% 93% 100% 123% % 88% 94% 100% 122% % 90% 95% 100% 123% % 92% 95% 100% 122% CWM % 84% 92% 100% 133% % 84% 92% 100% 133% % 84% 92% 100% 133% NOTE: If your service voltage is 208V or 220V, make sure that after your output has been adjusted that it does not drop below the calculated heat loss. If heat loss is greater than adjusted power output choose the next highest wattage cable.
17 Table 10 Ordering Information for Chromalox Self-Regulating and Constant Wattage Heating Cable Heating Cable Family Model Number Specifications SRL Self-Regulating Low Temperature SRL3-1C 3 F, 120V With Tinned Copper Braid SRL3-2C 3 F, 240V SRL5-1C 5 F, 120V SRL5-2C 5 F, 240V SRL8-1C 8 F, 120V SRL8-2C 8 F, 240V SRL10-1C 10 F, 120V SRL10-2C 10 F, 240V With Braid and Polyolefin Overjacket SRL3-1CR 3 F, 120V SRL3-2CR 3 F, 240V SRL5-1CR 5 F, 120V SRL5-2CR 5 F, 240V SRL8-1CR 8 F, 120V SRL8-2CR 8 F, 240V SRL10-1CR 10 F, 120V SRL10-2CR 10 F, 240V With Braid and Fluoropolymer Overjacket SRL3-1CT 3 F, 120V SRL3-2CT 3 F, 240V SRL5-1CT 5 F, 120V SRL5-2CT 5 F, 240V SRL8-1CT 8 F, 120V SRL8-2CT 8 F, 240V SRL10-1CT 10 F, 120V SRL10-2CT 10 F, 240V SRM/E Self-Regulating Medium Temperature SRM/E3-1C 3 F, 120V With Tinned Copper Braid SRM/E3-2C 3 F, 240V SRM/E5-1C 5 F, 120V SRM/E5-2C 5 F, 240V SRM/E8-1C 8 F, 120V SRM/E8-2C 8 F, 240V SRM/E10-1C 10 F, 120V SRM/E10-2C 10 F, 240V SRM/E15-1C 15 F, 120V SRM/E15-2C 15 F, 240V SRM/E20-1C 20 F, 120V SRM/E20-2C 20 F, 240V With Braid and Fluoropolymer Overjacket SRM/E3-1CT 3 F, 120V SRM/E3-2CT 3 F, 240V SRM/E5-1CT 5 F, 120V SRM/E5-2CT 5 F, 240V SRM/E8-1CT 8 F, 120V SRM/E8-2CT 8 F, 240V SRM/E10-1CT 10 F, 120V SRM/E10-2CT 10 F, 240V SRM/E15-1CT 15 F, 120V SRM/E15-2CT 15 F, 240V SRM/E20-1CT 20 F, 120V SRM/E20-2CT 20 F, 240V 15HEATING CABLE SELECTION
18 HEATING CABLE SELECTION Table 10, cont d. Heating Cable Family Model Number Specifications SRL Self-Regulating Low Temperature HSRL3-1CT 3 50 F, 120V Division 1 Hazardous Location Cable HSRL3-2CT 3 50 F, 240V HSRL5-1CT HSRL5-2CT HSRL8-1CT HSRL8-2CT HSRL10-1CT HSRL10-2CT 5 50 F, 120V 5 50 F, 240V 8 50 F, 120V 8 50 F, 240V F, 120V F, 240V HSRM Self-Regulating Medium Temperature HSRM5-1CT 5 50 F, 120V Division 1 Hazardous Location Cable HSRM5-2CT 5 50 F, 240V HSRM8-1CT HSRM8-2CT HSRM10-1CT HSRM10-2CT HSRM15-1CT HSRM15-2CT HSRM20-1CT HSRM20-2CT 8 50 F, 120V 8 50 F, 240V F, 120V F, 240V F, 120V F, 240V F, 120V F, 240V CWM Constant Wattage Heating Cable CWM4-1C 4 W/ft, 120V With Tinned Copper Braid CWM4-2C 4 W/ft, 240V CWM8-1C CWM8-2C CWM12-1C CWM12-2C 8 W/ft, 120V 8 W/ft, 240V 12 W/ft, 120V 12 W/ft, 240V With Braid and Fluoropolymer Overjacket CWM4-1CT 4 W/ft, 120V CWM4-2CT CWM8-1CT CWM8-1CT CWM12-1CT CWM12-2CT 4 W/ft, 240V 8 W/ft, 120V 8 W/ft, 120V 12 W/ft, 120V 12 W/ft, 240V 16
19 MINERAL INSULATED CABLE DESIGN Form A Form E Total Heated Length Cold Lead Length Total Heated Length Cold Lead Length One Conductor Total Heated Length Cold Lead Length Two Conductor Mineral Insulated Cable can be manufactured into the heater designs shown below as Form A and Form E. The following information is required to properly design mineral insulated cable units. Determine the following information and contact the Chromalox Application Group for assistance (see back cover). For Pipe Length: Diameter: Material: For Tank Length: Width: Height: Radius: Diameter: Surface Area: Material: Type of Insulation: Insulation Thickness: Voltage: Maintenance Temperature: Minimum Ambient Temperature: Minimum Startup Temperature: Maximum Exposure Temperature: Area Classification: Indoor or Outdoor: Maximum Wind Speed: Corrosive(s) Present: Safety Factor: Equipment and Quantity: Flange Pair: Pipe Support: Butterfly Valve: Ball Valve: Glove Valve: Gate Valve: Desired Cable Form: Form A: Form E: One-Conductor: Two-Conductor: Desired Cold Lead Length: 17MINERAL INSULATED CABLE DESIGN MINERAL INSULATED CABLE DESIGN
20 ELECTRICAL DESIGN 18ELECTRICAL DESIGN ELECTRICAL DESIGN Circuit Breaker Selection To select the circuit breaker size, determine the following information: Maintenance Temperature: Heat Loss per Foot of Pipe, Q T : Pipe or Tubing Size: Pipe Length: Type and Number of Valves & Supports: Heating Cable Catalog Number: Minimum Start-Up Temperature: Example: English Maintenance Temperature: 40ºF Heat Loss per Foot of Pipe, Q T: 4.88 W/ft Pipe or Tubing Size: 3" steel Pipe Length: 124 ft Type and Number of Valves 2 Butterfly Valves, & Supports: 12 Pipe Hanger Supports Heating Cable Catalog Number: SRL 5-1CT Minimum Start-Up Temperature: -20ºF Example: Metric Maintenance Temperature: Heat Loss per Foot of Pipe, Q T : Pipe or Tubing Size: Pipe Length: Type and Number of Valves & Supports: Heating Cable Catalog Number: Minimum Start-Up Temperature: 4.4ºC W/m 76 mm steel 38 m 2 Butterfly Valves, 12 Pipe Hanger Supports SRL 5-1CT -28.9ºC Step 1. Determine the Total Cable Length In addition to piping, in-line equipment such as valves, flanges, and pipe supports require additional heat tracing to maintain the system operating temperatures. See Table 11 (page 19) for additional cable lengths required for each type of in-line equipment based on piping size. Calculate the total length of heating cable required by combining lengths from each component of the piping system. Example: Pipe length of 124 ft (38 m) single pass application = 124 ft (38 m) SRL 5-1CT 2 Butterfly Valves, additional cable 2.5 ft (0.76 m) each valve = 5.0 ft (1.52 m) SRL 5-1CT 12 Pipe Hanger Supports, additional cable per support is 2.0 ft (0.61 m) = 24.0 ft (7.3 m) SRL 5-1CT Total length required = 153 ft (46.82 m) SRL 5-1CT
21 Step 2. Determine the Circuit Breaker Rating 1. For Self-Regulating Cable - From Table 12 (page 20) select the circuit breaker trip rating by finding the heating cable type and the minimum expected start-up temperature. Compare the maximum circuit length for each breaker rating to the total cable length required for each pipe. Select the breaker rating whose maximum circuit length just exceeds the total cable required for the pipe. Table 11 Additional Cable Lengths Required for In-line Equipment Piping Size Gate Valve Globe Valve Ball Valve Butterfly Valve If the circuit breaker rating is predetermined, use the maximum circuit length shown in Table 12 for the cable type at the minimum startup temperature. If the required cable length exceeds the maximum circuit length, determine the number of circuits required: Number of Circuits = Total Cable Length / Maximum Circuit Length Shoe Support Hanger Support Sleeper Support Flange Pair ft/m 1 /2 in mm /4 in mm in mm /2 in mm in mm /2 in mm in mm in mm in mm in mm in mm in mm in mm in mm in mm in mm in mm in mm ELECTRICAL DESIGN
22 20ELECTRICAL DESIGN Table 12 Maximum Circuit Length by Start-Up Temperature and Breaker Size for Self-Regulating Cable Maximum Circuit Length Cable Rating Circuit Breaker 10A 15A 20A 25A 30A 40A 50A 50ºF (10ºC) Start-Up SRL / HSRL 3-1 (ft) NR NR NR NR SRL / HSRL 3-1 (m) NR NR NR NR SRL / HSRL 3-2 (ft) NR NR NR NR SRL / HSRL 3-2 (m) NR NR NR NR SRL / HSRL 5-1 (ft) NR NR NR SRL / HSRL 5-1 (m) NR NR NR SRL / HSRL 5-2 (ft) NR NR NR SRL / HSRL 5-2 (m) NR NR NR SRL / HSRL 8-1 (ft) NR NR NR SRL / HSRL 8-1 (m) NR NR NR SRL / HSRL 8-2 (ft) NR NR NR SRL / HSRL 8-2 (m) NR NR NR SRL / HSRL 10-1 (ft) NR NR SRL / HSRL 10-1 (m) NR NR SRL / HSRL 10-2 (ft) NR SRL / HSRL 10-2 (m) NR SRM/E / HSRM 3-1 (ft) NR NR NR NR SRM/E / HSRM 3-1 (m) NR NR NR NR SRM/E / HSRM 3-2 (ft) NR NR SRM/E / HSRM 3-2 (m) NR NR SRM/E / HSRM 5-1 (ft) NR SRM/E / HSRM 5-1 (m) NR SRM/E / HSRM 5-2 (ft) NR SRM/E / HSRM 5-2 (m) NR SRM/E / HSRM 8-1 (ft) NR SRM/E / HSRM 8-1 (m) NR SRM/E / HSRM 8-2 (ft) NR SRM/E / HSRM 8-2 (m) NR SRM/E / HSRM 10-1 (ft) NR SRM/E / HSRM 10-1 (m) NR SRM/E / HSRM 10-2 (ft) NR SRM/E / HSRM 10-2 (m) NR SRM/E / HSRM 15-1 (ft) SRM/E / HSRM 15-1 (m) SRM/E / HSRM 15-2 (ft) SRM/E / HSRM 15-2 (m) SRM/E / HSRM 20-1 (ft) SRM/E / HSRM 20-1 (m) SRM/E / HSRM 20-2 (ft) SRM/E / HSRM 20-2 (m) NOTE: This table takes into account start-up current characteristics of self-regulating cable and the 20% safety factor as required by the NEC Article (c). NR = Not Recommended.
23 Table 12, cont'd. Cable Rating Maximum Circuit Length Circuit Breaker 10A 15A 20A 25A 30A 40A 50A 0ºF (-18ºC) Start-Up SRL / HSRL 3-1 (ft) NR NR SRL / HSRL 3-1 (m) NR NR SRL / HSRL 3-2 (ft) NR NR NR SRL / HSRL 3-2 (m) NR NR NR SRL / HSRL 5-1 (ft) NR NR SRL / HSRL 5-1 (m) NR NR SRL / HSRL 5-2 (ft) NR NR SRL / HSRL 5-2 (m) NR NR SRL / HSRL 8-1 (ft) NR NR SRL / HSRL 8-1 (m) NR NR SRL / HSRL 8-2 (ft) NR SRL / HSRL 8-2 (m) NR SRL / HSRL 10-1 (ft) NR SRL / HSRL 10-1 (m) NR SRL / HSRL 10-2 (ft) NR SRL / HSRL 10-2 (m) NR SRM/E / HSRM 3-1 (ft) NR NR SRM/E / HSRM 3-1 (m) NR NR SRM/E / HSRM 3-2 (ft) NR NR SRM/E / HSRM 3-2 (m) NR NR SRM/E / HSRM 5-1 (ft) NR SRM/E / HSRM 5-1 (m) NR SRM/E / HSRM 5-2 (ft) NR SRM/E / HSRM 5-2 (m) NR SRM/E / HSRM 8-1 (ft) NR SRM/E / HSRM 8-1 (m) NR SRM/E / HSRM 8-2 (ft) NR SRM/E / HSRM 8-2 (m) NR SRM/E / HSRM 10-1 (ft) NR SRM/E / HSRM 10-1 (m) NR SRM/E / HSRM 10-2 (ft) NR SRM/E / HSRM 10-2 (m) NR SRM/E / HSRM 15-1 (ft) SRM/E / HSRM 15-1 (m) SRM/E / HSRM 15-2 (ft) SRM/E / HSRM 15-2 (m) SRM/E / HSRM 20-1 (ft) SRM/E / HSRM 20-1 (m) SRM/E / HSRM 20-2 (ft) SRM/E / HSRM 20-2 (m) NOTE: This table takes into account start-up current characteristics of self-regulating cable and the 20% safety factor as required by the NEC Article (c). NR = Not Recommended. 21ELECTRICAL DESIGN
24 22ELECTRICAL DESIGN Table 12, cont'd. Maximum Circuit Length Cable Rating Circuit Breaker 10A 15A 20A 25A 30A 40A 50A -20ºF (-29ºC) Start-Up SRL / HSRL 3-1 (ft) NR NR SRL / HSRL 3-1 (m) NR NR SRL / HSRL 3-2 (ft) NR NR SRL / HSRL 3-2 (m) NR NR SRL / HSRL 5-1 (ft) NR SRL / HSRL 5-1 (m) NR SRL / HSRL 5-2 (ft) NR SRL / HSRL 5-2 (m) NR SRL / HSRL 8-1 (ft) NR SRL / HSRL 8-1 (m) NR SRL / HSRL 8-2 (ft) NR SRL / HSRL 8-2 (m) NR SRL / HSRL 10-1 (ft) NR SRL / HSRL 10-1 (m) NR SRL / HSRL 10-2 (ft) NR SRL / HSRL 10-2 (m) NR SRM/E / HSRM 3-1 (ft) NR NR SRM/E / HSRM 3-1 (m) NR NR SRM/E / HSRM 3-2 (ft) NR NR SRM/E / HSRM 3-2 (m) NR NR SRM/E / HSRM 5-1 (ft) NR SRM/E / HSRM 5-1 (m) NR SRM/E / HSRM 5-2 (ft) NR SRM/E / HSRM 5-2 (m) NR SRM/E / HSRM 8-1 (ft) NR SRM/E / HSRM 8-1 (m) NR SRM/E / HSRM 8-2 (ft) NR SRM/E / HSRM 8-2 (m) NR SRM/E / HSRM 10-1 (ft) SRM/E / HSRM 10-1 (m) SRM/E / HSRM 10-2 (ft) SRM/E / HSRM 10-2 (m) SRM/E / HSRM 15-1 (ft) SRM/E / HSRM 15-1 (m) SRM/E / HSRM 15-2 (ft) SRM/E / HSRM 15-2 (m) SRM/E / HSRM 20-1 (ft) SRM/E / HSRM 20-1 (m) SRM/E / HSRM 20-2 (ft) SRM/E / HSRM 20-2 (m) NOTE: This table takes into account start-up current characteristics of self-regulating cable and the 20% safety factor as required by the NEC Article (c). NR = Not Recommended.
25 Total heating cable length required for piping is 153 ft (46.82 m) SRL 5-1CT. The minimum startup temperature for the system is -20ºF (-29ºC). Therefore, based on Table 12, the circuit breaker required is 20A. 2. For Constant Wattage Cable - Determine the total current draw by determining the circuit load in A/ft (A/m) from Table 13 and multiply this number by the total length required for the piping. Total Circuit Current Draw = Circuit Load A/ft (A/m) x Total Cable Length for the Pipe Then adjust this total current draw by the 20% safety factor required by the National Electric Code (NEC): Adjusted Current Draw = Total Circuit Current Draw x 1.20 Choose the circuit breaker rating that exceeds the adjusted current draw. To determine the number of circuits required for each pipe, divide the total cable length required by the maximum circuit length shown in Table 13 for the cable selected. Number of Circuits = Total Cable Length / Maximum Circuit Length 3. For Mineral Insulated Cable Find the total current draw by dividing the total cable wattage by the operating voltage: Total Circuit Current Draw = Total Cable Wattage/Operating Voltage Then adjust the total current draw for the 20% safety factor required by the NEC: Adjusted Current Draw = Total Circuit Current Draw x 1.20 Choose the circuit breaker rating that exceeds the adjusted current draw. Step 3. Select the Circuit Breaker The National Electric Code (NEC 1996) and European Union (EU) code require the use of ground-fault style breakers for heating cable circuit protection. If heating cable is improperly installed or physically damaged to the point that water contacts the bus wires, sustained arcing or fire could result. If arcing does occur, the fault current may be too low to trip conventional circuit breakers. Chromalox recommends the use of thermal magnetic style circuit breakers with a trip rating set at 30mA (equipment protection device) to eliminate nuisance tripping that can occur at low temperatures with magnetic type or lower rated ground fault trip breakers. The following are some ground-fault breakers that meet these requirements: Square D: Type QOB-EPD Westinghouse: Types GFEP, GFEPD Cutler-Hammer: Type QBGFEP Table 13 Circuit Load and Maximum Circuit Lengths for Constant Wattage Cable Circuit Load Maximum Circuit Length Model Number A/ft A/m ft m CWM CWM CWM CWM CWM CWM ELECTRICAL DESIGN
26 24COMPONENT SELECTION AND ACCESSORIES COMPONENT SELECTION AND ACCESSORIES COMPONENT SELECTION AND ACCESSORIES Heat tracing circuits require a power connection and an end seal. Splice and tee kits are used as required. See diagrams and tables below and on the following pages for typical system details. Choose a series of components based on area classification and preference. Figure 5 EL Series Components EL Series Components - For use in Ordinary and Division 2 Hazardous Areas as shown in Table 14. JBLT with SLK JBLT RT-JBC-1 RT-JBC-2 JBLT RT-RCL COLD LEAD RT-RES RT-TES RT-RST RT-TST Table 14 EL Series Connection Components for Installation, U.S. Only Cable Type SRL-C, SRL-CR, SRL-CT CWM-C & CWM-CT Component Model In addition, choose attachment accessories from Table 18 (page 29) based on requirements listed in Table 19 (page 29). RT-RST RT-TST Junction Box Connection Kit RT-JBC-1 UL,CSA, FM FM FM FM Junction Box JBLT UL,CSA, FM FM FM FM End Seal RT-RES UL,CSA, FM FM FM FM Tee Connection RT-RST UL,CSA, FM FM FM FM Splice Connection RT-RST UL,CSA, FM FM FM FM Junction Box Connection Kit RT-JBC-2 UL, CSA Junction Box JBLT UL,CSA, FM FM FM FM End Seal RT-TES UL, CSA Tee Connection RT-TST UL, CSA Splice Connection RT-TST UL, CSA NOTE: EL Series not to be used with SRME cable. SLK-1 and SLK-2 are no longer offered. Approvals Class I Class II Ordinary Div. 2 Div. 2 Class III Area Gr. B, C, D Gr. G Div. 2
27 Figure 6 DL Series Components DL Series Components - DL Series Accessories include enclosures molded of durable Ryton PPS plastic material and are rated NEMA 4X. For use in Ordinary and Division 2 Hazardous Areas as shown in the table below. RTPC-XSL RTPC-X TO SUPPLY POWER RTST-XSL RTES-X RTST-X Additional accessories are required (see Table 18 and Table 19, page 29) for descriptions and part numbers): RTPC models require 1 conduit hub. RTPC and RTST models require 1 pipe strap each to fasten the kit to the pipe. Grommets are required for DL Series Components. (See Table 16): Each cable entry requires 1. Each RTPC (Power Connection) requires at least 1. Each RTST (Splice & Tee) requires at least 3. RTST-X 25COMPONENT SELECTION AND ACCESSORIES
28 26COMPONENT SELECTION AND ACCESSORIES Table 15 DL Series Connection Components for Installation, U.S. Only Cable Type SRL-C SRL-CR & SRL-CT SRM/E-C SRM/E-CT Approvals Component Model Class I Class II Ordinary Div. 2 Div. 2 Class III Areas Gr. B, C, D Gr. F, G Div. 2 Power Connection Kit RTPC-1 UL, CSA, FM CSA, FM CSA, FM FM Power Connection Kit w/ Signal Light, 120V RTPC-1SL1 UL, CSA, FM Power Connection Kit w/ Signal Light, V RTPC-1SL2 UL, CSA, FM Power Connection Kit w/ Signal Light, 277V RTPC-1SL3 UL, CSA, FM End Seal Kit RTES-1 UL, CSA, FM CSA, FM CSA, FM FM End Seal Kit w/ Signal Light, 120V RTST-1SL1 UL, CSA, FM End Seal Kit w/ Signal Light, V RTST-1SL2 UL, CSA, FM End Seal Kit w/ Signal Light, 277V RTST-1SL3 UL, CSA, FM Splice and Tee Kit RTST-1 UL, CSA, FM CSA, FM CSA, FM FM Power Connection Kit RTPC-2 UL, CSA, FM CSA, FM CSA, FM FM Power Connection Kit w/ Signal Light, 120V RTPC-2SL1 UL, CSA, FM Power Connection Kit w/ Signal Light, V RTPC-2SL2 UL, CSA, FM Power Connection Kit w/ Signal Light, 277V RTPC-2SL3 UL, CSA, FM End Seal Kit RTES-1 UL, CSA, FM CSA, FM CSA, FM FM End Seal Kit w/ Signal Light, 120V RTST-2SL1 UL, CSA, FM End Seal Kit w/ Signal Light, V RTST-2SL2 UL, CSA, FM End Seal Kit w/ Signal Light, 277V RTST-2SL3 UL, CSA, FM Splice and Tee Kit RTST-2 UL, CSA, FM CSA, FM CSA, FM FM Power Connection Kit RTPC-7 UL, CSA, FM CSA, FM CSA, FM FM Power Connection Kit w/ Signal Light, 120V RTPC-7SL1 UL, CSA, FM Power Connection Kit w/ Signal Light, V RTPC-7SL2 UL, CSA, FM Power Connection Kit w/ Signal Light, 277V RTPC-7SL3 UL, CSA, FM End Seal Kit RTES-7 UL, CSA, FM CSA, FM CSA, FM FM End Seal Kit w/ Signal Light, 120V RTST-7SL1 UL, CSA, FM End Seal Kit w/ Signal Light, V RTST-7SL2 UL, CSA, FM End Seal Kit w/ Signal Light, 277V RTST-7SL3 UL, CSA, FM Splice and Tee Kit RTST-7 UL, CSA, FM CSA, FM CSA, FM FM Power Connection Kit RTPC-8 UL, CSA, FM CSA, FM CSA, FM FM Power Connection Kit w/ Signal Light, 120V RTPC-8SL1 UL, CSA, FM Power Connection Kit w/ Signal Light, V RTPC-8SL2 UL, CSA, FM Power Connection Kit w/ Signal Light, 277V RTPC-8SL3 UL, CSA, FM End Seal Kit RTES-8 UL, CSA, FM CSA, FM CSA, FM FM End Seal Kit w/ Signal Light, 120V RTST-8SL1 UL, CSA, FM End Seal Kit w/ Signal Light, V RTST-8SL2 UL, CSA, FM End Seal Kit w/ Signal Light, 277V RTST-8SL3 UL, CSA, FM Splice and Tee Kit RTST-8 UL, CSA, FM CSA, FM CSA, FM FM
29 Table 15, con't. Cable Type CWM-CT CWM-C Table 16 Grommets for DL Series Components Cable Type RTO/Capillary Type Blank SRL-C SRL-CR, SRL-CT CWM-C CWM-CT SRL-MC SRL-MCR, SRL-MCT SRM/E-C SRM/E-CT Component Model Class I Class II Ordinary Div. 2 Div. 2 Class III Areas Gr. B, C, D Gr. F, G Div. 2 Power Connection Kit RTPC-3 UL, CSA, FM CSA, FM CSA, FM FM Power Connection Kit w/ Signal Light, 120V RTPC-3SL1 UL, CSA, FM Power Connection Kit w/ Signal Light, V RTPC-3SL2 UL, CSA, FM Power Connection Kit w/ Signal Light, 277V RTPC-3SL3 UL, CSA, FM End Seal Kit RTES-3 UL, CSA, FM CSA, FM CSA, FM FM End Seal Kit w/ Signal Light, 120V RTST-3SL1 UL, CSA, FM End Seal Kit w/ Signal Light, V RTST-3SL2 UL, CSA, FM End Seal Kit w/ Signal Light, 277V RTST-3SL3 UL, CSA, FM Splice and Tee Kit RTST-3 UL, CSA, FM CSA, FM CSA, FM FM Power Connection Kit RTPC-4 UL, CSA, FM CSA, FM CSA, FM FM Power Connection Kit w/ Signal Light, 120V RTPC-4SL1 UL, CSA, FM Power Connection Kit w/ Signal Light, V RTPC-4SL2 UL, CSA, FM Power Connection Kit w/ Signal Light, 277V RTPC-4SL3 UL, CSA, FM End Seal Kit RTES-4 UL, CSA, FM CSA, FM CSA, FM FM End Seal Kit w/ Signal Light, 120V RTST-4SL1 UL, CSA, FM End Seal Kit w/ Signal Light, V RTST-4SL2 UL, CSA, FM End Seal Kit w/ Signal Light, 277V RTST-4SL3 UL, CSA, FM Splice and Tee Kit RTST-4 UL, CSA, FM CSA, FM CSA, FM FM Grommet Model No. GRS GRO GR1 GR2 GR3 GR4 GR5 GR6 GR7 GR8 Approvals 27COMPONENT SELECTION AND ACCESSORIES
30 28COMPONENT SELECTION AND ACCESSORIES Figure 7 HL Series Components HL Series Components For use in Division 1 Hazardous Areas with HSRL and HSRM Heating Cables. Cable Type HSRL- CT HSRM- CT HL-ES TO SUPPLY POWER HL-PC Table 17 HL Series Components HL-T Additional accessories are required (see Table 18 and Table 19, page 29 for descriptions and part numbers): All models require 2 pipe straps to fasten kit to pipe. Approvals Component Model Class I Class II Div. 1 Div. 1 Class III Gr.B,C,D Gr.E,F,G Div.1 Power Connection HL-PC FM FM FM End Seal HL-ES FM FM FM Tee Connection HL-T FM FM FM Splice Connection HL-S FM FM FM Power Connection HL-PC FM FM FM End Seal HL-ES FM FM FM Tee Connection HL-T FM FM FM Splice Connection HL-S FM FM FM HL-S
31 Table 18 Attachment Accessories, U.S. Only Designation Pipe Strap for 1 /2" to 3 /4" (21.3 mm to 26.7 mm) pipes Pipe Strap for 1" to 3 1 /2" (33.4 mm to mm) pipes Pipe Strap for 2 1 /2" to 9" (73.0 mm to mm) pipes Fiberglass Tape 2 1 /2" (73.0 m) wide, 180 ft (55 m) roll Fiberglass Tape 2 1 /2" (73.0 mm) wide, 66 ft (20 m) roll Nylon Cable Ties, Interlocking, 100 per pack Aluminum Tape 2 1 /2" (73.0 mm) wide, 180 ft (55 m) roll Conduit Hub Attachment 3 /4" (18.80 mm) NPT Conduit Hub Attachment 3 /4" (18.80 mm) NPT w/ground connector Mounting Plate for Installing RTPC & RTST on Flat Surface Caution Labels, 5 per pack applied at 10 ft (3 m) intervals Model Table 19 Attachment Requirements - Minimum Number of Kits Required per 100 ft (30 m) of Pipe Length Minimum No. of Kits Required Per 100 ft (30 m) of Pipe Pipe Size CT-100 FT-1 FT-2 PS-1 PS-3 PS-10 FT-1 FT-2 CT-100 AT-1 CCH-1 CCH-2 MP-1 CL-1 1 /2" (21.3 mm) /4" (26.7 mm) " (33.4 mm) /4" (42.2 mm) /2" (48.3 mm) " (60.3 mm) /2" (73.0 mm) " (88.9 mm) /2" (101.6 mm) " (114.3 mm) " (141.3 mm) " (168.3 mm) " (219.1 mm) " (273.1 mm) " (323.9 mm) " (355.6 mm) " (406.4 mm) " (457.2 mm) " (508.0 mm) " (609.6 mm) NOTE: Strap fiberglass tape or cable ties at 1-ft (0.31-m) intervals to hold cable to metal pipe. Use aluminum tape for non-metal pipe concentrically under and over heating cable to aid in heat transfer. 29COMPONENT SELECTION AND ACCESSORIES
32 30COMPONENT SELECTION AND ACCESSORIES Table 20 Connection Accessories for Heat Trace Installation Outside of the United States Cable Type SRL SRL-C SRL-CR & SRL-CT SRME Component Model Approvals Power Connection - Polyester BJP002N ATEX Power Connection - Aluminum BJA001 ATEX Termination Kit for Use with Power Connection Kit KCA001 ATEX End Seal Kit C Maximum Temperature KIE002A ATEX Polyamide Ex'e' Gland with Cable Sealing Washer and Backnut KECPE001 ATEX Brass Ex'e' Gland with Cable Sealing Washer and Backnut KECME001 ATEX Splice and Tee Kit - Shrink-On Sleeve RT-RST ATEX Splice and Tee Kit - Fast Connection Domo Click ATEX Power Connection - Polyester BJP002N ATEX Power Connection - Aluminum BJA001 ATEX Power Connection - EEx'e' Polyester BJEP004N ATEX Power Connection - EEx'e' Aluminum BJEA004 ATEX Power Connection - EEx'd' Aluminum BJDA004N ATEX Termination Kit for Use with Power Connection Kit KCA001 ATEX End Seal Kit C Maximum Temperature KIE002A ATEX Polyamide Ex'e' Gland with Cable Sealing Washer and Backnut KECPE001 ATEX Brass Ex'e' Gland with Cable Sealing Washer and Backnut KECME001 ATEX Splice and Tee Kit - Shrink-On Sleeve RT-RST ATEX Splice and Tee Kit - Fast Connection Domo Click ATEX In-Line Splice Kit - Hazardous Areas KEJ-Ex ATEX Power Connection - Polyester BJP002N ATEX Power Connection - Aluminum BJA001 ATEX Power Connection - EEx'e' Polyester BJEP004N ATEX Power Connection - EEx'e' Aluminum BJEA004 ATEX Power Connection - EEx'd' Aluminum BJDA004N ATEX Termination Kit for Use with Power Connection Kit KCA001 ATEX End Seal Kit C Maximum Temperature KIE002C ATEX Polyamide Ex'e' Gland with Cable Sealing Washer and Backnut KECPE003 ATEX Brass Ex'e' Gland with Cable Sealing Washer and Backnut KECME003 ATEX Splice and Tee Kit - Shrink-On Sleeve RT-RST ATEX Splice and Tee Kit - Fast Connection Domo Click ATEX In-Line Splice Kit - Hazardous Areas KEJ-Ex ATEX Power Connection - Polyester BJP002N ATEX Power Connection - Aluminum BJA001 ATEX Termination Kit for Use with Power Connection Kit KCA001 ATEX End Seal Kit C Maximum Temperature KIE002A ATEX Polyamide Ex'e' Gland with Cable Sealing Washer and Backnut KECPE004 ATEX Brass Ex'e' Gland with Cable Sealing Washer and Backnut KECME004 ATEX Splice & Tee Kit - Shrink-On Sleeve RT-RST ATEX KECPE001 KECME001 KECPE003 KECME003 KECPE004 KECME004 KECPE005 KECME005 Domo Click KCA001 RT-RST KEJ-Ex BJP002N BJA001 BJEP00 KIE002A KEI002C BJEA004 BJEA004N
33 Table 20, con't. Cable Type SRME-CT SRME-C Component Model Approvals Power Connection - Polyester BJP002N ATEX Power Connection - Aluminum BJA001 ATEX Power Connection - EEx'e' Polyester BJEP004N ATEX Power Connection - EEx'e' Aluminum BJEA004 ATEX Power Connection - EEx'd' Aluminum BJDA004N ATEX Termination Kit for Use with Power Connection Kit KCA001 ATEX End Seal Kit C Maximum Temperature KIE002A ATEX Polyamide Ex'e' Gland with Cable Sealing Washer and Backnut KECPE004 ATEX Brass Ex'e' Gland with Cable Sealing Washer and Backnut KECME004 ATEX Splice and Tee Kit - Shrink-On Sleeve RT-RST ATEX In-Line Splice Kit - Hazardous Areas KEJ-Ex ATEX Power Connection - Polyester BJP002N ATEX Power Connection - Aluminum BJA001 ATEX Power Connection - EEx'e' Polyester BJEP004N ATEX Power Connection - EEx'e' Aluminum BJEA004 ATEX Power Connection - EEx'd' Aluminum BJDA004N ATEX Termination Kit for Use with Power Connection Kit KCA001 ATEX End Seal Kit C Maximum Temperature KIE002C ATEX Polyamide Ex'e' Gland with Cable Sealing Washer and Backnut KECPE005 ATEX Brass Ex'e' Gland with Cable Sealing Washer and Backnut KECME005 ATEX Splice and Tee Kit - Shrink-On Sleeve RT-RST ATEX In-Line Splice Kit - Hazardous Areas KEJ-Ex ATEX Table 21 Attachment Accessories for Heat Trace Installation Outside the U.S. Designation Fiberglass Adhesive Tape, 90 C Maximum Temperature, 50 m Long Fiberglass Adhesive Tape, 110 C Maximum Temperature, 50 m Long Fiberglass Adhesive Tape, 180 C Maximum Temperature, 33 m Long Aluminum Adhesive Tape, 95 C Maximum Temperature, 50 m Long Through Bulkhead Kit, SRL & SRL-C Cable Through Bulkhead Kit, SRL-CR & SRL-CT Cable Through Bulkhead Kit, SRM & SRM-C Cable Through Bulkhead Kit, SRM-CT Cable Insulation Outlet Kit Box Support Bracket for use with Power Connection Kit - Vertical Box Support Bracket for use with Power Connection Kit - Horizontal Self-Adhesive Warning Labels RCC1 RCC3 RCC4 KSCA003 FT02 FT03 FT04 AT03 RCC1 RCC3 RCC4 Model FT04 FT02 FT03 AT03 RCC1 RCC3 RCC4 RCC5 KSCA003 KSB001 KSB002 CL02 KSB001 KSB002 31COMPONENT SELECTION AND ACCESSORIES
34 COMPONENT SELECTION AND ACCESSORIES CONTROL SELECTION Typical heat trace temperature control is accomplished by one of two methods: ambient air sensing or pipe wall sensing. When designing a heat trace system with relatively few circuits, temperature controls can be accomplished by using single-point on/off controls. When designing a system with a large number of circuits or a system that protects critical plant functions, it is often advantageous to use central control panels that employ electronic control. Ambient Air Sensing Control In an ambient air sensing control system, a thermostat is used to sense ambient air and switch Figure 8 RTAS Ambient Air Sensing Control Thermostats Approvals: Ordinary Areas: UL, CSA, FM Enclosure: NEMA 4X Ryton PPS Setpoint Range: 0º to 225ºF (-18º to 107ºC), Factory Preset at 40ºF (4.4ºC) Deadband: 10% of Range Operating Temperature Range: -40º to 160ºF (-40º to 70ºC) Scale Division: 10ºF (5.6ºC) Switch Type: SPDT Switch Rating: 22A at 120/250/480 Vac Sensor: 9/16" (14.29 mm) OD x 3" (76.2 mm) L Stainless Steel Maximum Sensor Exposure Temperature: 450ºF (230ºC) This unit can serve as power connection box. Heating cable can be terminated directly into enclosure. Requires a sealing grommet for the type of cable being used. the heating cable on and off at a preset ambient temperature. For a small number of circuits singlepoint thermostats can be used to switch individual circuits on and off. If a large number of circuits is involved, a single strategically located thermostat can be used in conjunction with a contactor to switch all circuits on or off at a preset temperature. Select your thermostat from among the figures below based on your installation needs for operating voltage, switching current, setpoint range, and area classification. NOTE: If your circuit current exceeds the switch rating of the device selected, use the device in conjunction with a contactor suitable for your circuit current. 32
35 Figure 9 RTAS-EP Ambient Air Sensing Control Thermostats Approvals: Ordinary Areas: UL, CSA, FM Class I, Div. 2, Groups B,C,D: CSA, FM Class II, Div. 2, Groups F,G: CSA, FM Class III, Div. 2: FM Enclosure: NEMA 4X Ryton PPS Setpoint Range: 0º - 225ºF (-18º to 107ºC), Factory Preset at 40ºF (4.4ºC) Deadband: 10% of Range Operating Temperature Range: -40º to 160ºF (-40º to 70ºC) Scale Division: 10ºF (5.6ºC) Switch Type: SPDT Switch Rating: 11A at 120/250 Vac Sensor: 9/16" (14.29 mm) OD x 3" (76.2 mm) L Stainless Steel Maximum Sensor Exposure Temperature: 450ºF (230ºC) This unit can serve as power connection box. Heating cable can be terminated directly into enclosure. Requires a sealing grommet for the type of cable being used. Figure 10 B-100 Ambient Air Sensing Control Thermostats Approvals: Ordinary Areas: UL, CSA Enclosure: NEMA 4X Setpoint Range: 15º to 140ºF (-10º to 60ºC) Deadband: 2% of Range Operating Temperature Range: -40º to 160ºF (-40º to 71ºC) Switch Type: SPDT Switch Rating: 22A at 120/250/480 Vac Sensor: 9/16" (14.29 mm) OD x 3" (76.2 mm) L Stainless Steel 33CONTROL SELECTION CONTROL SELECTION
36 CONTROL SELECTION Figure Ambient Air Sensing Control Thermostats B-121 Ambient Air Sensing Control Thermostats Approvals: Ordinary Areas: UL, CSA, FM Class I, Groups B,C,D: FM Class II, Groups E, F,G: FM Class III: FM Enclosure: NEMA 4X,7,9 Cast Aluminum Setpoint Range: 15º to 140ºF (-10º to 60ºC) Deadband: 2% of Range Operating Temperature Range: -40º to 160ºF (-40º to 71ºC) Switch Type: SPDT Switch Rating: 22A at 120/250/480 Vac Sensor: 9/16" (14.29 mm) OD x 3" (76.2 mm) L Stainless Steel Line Sensing Control Line sensing control is used for process maintenance applications where the process temperature must be controlled within a moderate or narrow band. In a pipe wall sensing control system, a thermostat or RTD is used to sense pipe wall temperature and switch the heating cable on and off at a preset temperature. For a small number of circuits, single-point thermostats can be used to switch individual circuits on and off. If a large number of circuits is involved, a centralized panel board and electronic circuit monitoring system is often used. See next section on intellitrace controls. Select your thermostat from the figures below based on your installation needs for operating voltage, switching current, set point range, and area classification. NOTE: If your circuit current exceeds the switch rating of the device selected, use the device in conjunction with a contactor suitable for your circuit current. Figure 12 RTBC Line Sensing Control Thermostat Approvals: Ordinary Areas: UL, CSA, FM Enclosure: NEMA 4X Ryton PPS Setpoint Range: 0º to 400ºF (-18º to 200ºC) Deadband: 10% of Range Operating Temperature Range: -40º to 160ºF (-40º to 71ºC) Scale Division: 10ºF (5.6ºC) Switch Type: SPDT Switch Rating: 22A at 120/250/480 Vac Sensor: 1/8" (3.175 mm) OD x 11 5/8" ( mm) L Bulb, 10 ft (3 m) Stainless Steel Capillary Maximum Sensor Exposure Temperature: 450ºF (230ºC) This unit can serve as power connection box. Heating cable can be terminated directly into enclosure. Requires a sealing grommet for the type of cable being used. 34
37 Figure 13 RTBC-EP Line Sensing Control Thermostat Part No.: Approvals: Ordinary Areas: UL, CSA, FM Class I, Div. 2, Groups B, C, D:CSA FM Class II, Div. 2, Groups F, G: CSA FM Class III, Div. 2: FM Enclosure: NEMA 4X Ryton PPS Setpoint Range: 0º to 400ºF (-18º to 200ºC) Deadband: 10% of Range Operating Temperature Range: -40º to 160ºF (-40º to 71ºC) Scale Division: 10ºF (5.6ºC) Switch Type: SPDT Switch Rating: 22A at 120/250/480 Vac Sensor: 1/8" (3.175 mm) OD x 11 5/8" ( mm) L Bulb, 10 ft (3 m) Stainless Steel Capillary Figure 14E-100 Line Sensing Control Thermostat E-100 Line Sensing Control Thermostat Approvals: Ordinary Areas: UL, CSA Enclosure: NEMA 4X Setpoint Range: 25º to 325ºF (-5º to 163ºC) Deadband: 2% of Range Operating Temperature Range: -40º to 160ºF (-40º to 71ºC) Switch Type: SPDT Switch Rating: 22A at 120/250/480 Vac Sensor: 1/8" (3.175 mm) OD x 11 5/8" ( mm) L Bulb, 10 ft (3 m) Stainless Steel Capillary Figure Line Sensing Control Thermostat E-121 Line Sensing Control Thermostat Approvals: Ordinary Areas: UL, CSA, FM Class I, Groups B,C,D: CSA, FM Class II, Groups E, F,G: CSA, FM Class III: FM Enclosure: NEMA 4X, 7, 9 Setpoint Range: 25º to 325ºF (-5º to 163ºC) Deadband: 10% of Range Operating Temperature Range: -58º to 160ºF (-50º to 71ºC) Switch Type: SPDT Switch Rating: 22A at 120/250/480 Vac Sensor: 1/8" (3.175 mm) OD x 11 5/8" ( mm) L Bulb, 10 ft (3 m) Stainless Steel Capillary Maximum Sensor Exposure Temperature: 450ºF (230ºC) This unit can serve as power connection box. Heating cable can be terminated directly into enclosure. Requires a sealing grommet for the type of cable being used. 35CONTROL SELECTION
38 intellitrace CONTROLS 36intelliTRACE CONTROLS The intellitrace System is a complete control solution designed for heat trace applications, such as process temperature maintenance, freeze protection, and roof/gutter de-icing. The modular design of the intellitrace control panel and components allows users to select only features needed for their specific heat trace installation. This system uses microprocessor-based control and comes completely pre-wired and assembled. A variety of options is available that include three different AC line voltages (120, 240, and 277), RS-485 communications interface, and ground fault indicator. Single-Loop Line-Sensing Control Panel 12.5" (31.75 cm) 12.94" (32.89 cm) 10.5" (26.67 cm) 8.0" (20.32 cm) ø0.31 x 0.5" (1.27 cm) CONTROLLER Chromalox 83 CAUTION HAZARD OF ELECTRIC SHOCK DISCONNECT ALL POWER BEFORE SERVICING THIS UNIT GR/RESET Chromalox Front View 6.25" (15.88 cm) Side View 12.5" (31.75 cm) 1.75" (4.45 cm) Technical Specifications Supply Voltage: 120, 240 and 277 Operating Environment: 30º to 120ºF (0º to 40ºC) Communications: RS-485 MODBUS* Input Voltage: Thermocouple J,K,L,N,R,S,RTD, current, Field Programmable for ºF or ºC Output: Solid State Relay 40ºC Current Alarm (Low): 0 to 30A in 1A Increments Ground Fault Alarm Trip: 5 to 100mA Temperature Alarms: Process, Deviation, Band, High/Low, Latching/ Non-Latching (Manual/Automatic Reset) Programmable. Control Modes: Field Selectable On/Off, PID, SMART Ordering Information Model HTLS Series Heat Trace Panel HTLS UL Listed Single-Phase Temperature/Monitor Heat Trace Panel. NEMA 4X fiber glass enclosure 12.5" (31.75 cm) H x 10.5" (26.67 cm) W x 6.25" (15.24 cm) D. Includes complete prewired controller, solid state relay mounted on external heatsink, current transformer to measure operating current, and temperature/current alarms. PID or On/Off control, digital dual displays, terminal blocks for field connections, and optional GFI Indication or Shutdown. Code Amps 1 30 Code Voltage Vac Vac Vac Code Digital Indicating Temperature Controller /16 DIN Dual Four Digit Display, Alarm Outputs, and Current Input /16 DIN Dual Four Digit Display, Alarm Outputs, Current Input and RS-485 Code GFI Options 0 None V (Includes GFI Module, Shutdown Contactor, and Illuminated Reset Switch) V (Includes GFI Module, Shutdown Contactor, and Illuminated Reset Switch) V (Includes GFI Module, Shutdown Contactor, and Illuminated Reset Switch) Code 0 Add to complete model number HTLS Typical Model Number *MODBUS is a registered trademark of Gould Inc.
39 IntelliTRACE Dual-Loop Line Sensing Control Panel Technical Specifications Supply Voltage: Operating Environment: Communications: Input Voltage: 120, 208, 240 and 277 Vac Three Phase 30º to 104ºF (-1º to 40ºC) RS-485 MODBUS* Thermocouple J,K,L,N,R,S,RTD, Current, and Voltage Field Programmable, for ºF or ºC Output: Solid State Relay 40ºC Current Alarm (Low): 0 to 30A in 1A Increments Ground Fault Alarm Trip: 5 to 100mA Temperature Alarms: Process, Deviation, Band, High/Low, Latching/Non-Latching (Manual/Automatic Reset) Programmable. Control Modes: Field Selectable On/Off, PID, SMART Ordering Information Model IntelliTRACE 2000 Series Line Sensing Heat Trace Panel HTLS For indoor/outdoor applications. cul and UL Listed NEMA 4X rated enclosure 16 in. H x 14 in. W x 8 in. D (406mm H x 356mm W x 203mm D). Factory pre-wired for quick installation. Includes solid state relays, current transformer, high/low temperature alarms, low current alarm, on/off or PID control, universal sensor inputs, dual digital displays, terminal blocks for field connections, and loop enable/disable. Options include ground fault monitoring or shutdown and RS-485 communications. Code Number of Loops 2 30A Rating Code Voltage Vac Vac Vac Vac Code Controller Controller Controller with Communications Code Ground Fault Monitoring 0 None 1 GFI 120 Vac (Includes Shutdown Contactor and Illuminate Reset Switch) 2 GFI 240 Vac (Includes Shutdown Contactor and Illuminate Reset Switch) 3 GFI 277 Vac (Includes Shutdown Contactor and Illuminate Reset Switch) 4 GFI 208 Vac (Includes Shutdown Contactor and Illuminate Reset Switch) Code Enclosure Heater 0 None 1 Thermostat Controlled Enclosure Heater HTLS Typical Model Number *MODBUS is a registered trademark of Gould Inc. 37intelliTRACE CONTROLS intellitrace CONTROLS
40 intellitrace CONTROLS intellitrace Multi-Loop Line-Sensing Control Panel Technical Specifications Supply Voltage: 120, 240 and 277 Vac Three-Phase Operating Environment: 30 to 120 F (0 to 40 C) Communications: RS-485 MODBUS* Input: RTD 100Ω Platinum Three-Wire Maximum Current: 24A/Ckt Temperature Alarms: High/Low 2 F Deadband Non-Latching Ground Fault Alarm: Adjustable 25 to 500mA, Factory 30mA Continuity Alarm: < 2A Non-Latching Load Management: 15-Second Non-Overlap to Reduce In-Rush Auto-Cycle: Programmable to 720 Hr (30 days) Failed Sensor Output Setting: 0% to 100% Control Mode: On/Off with Adjustable Deadband Ordering Information Model HTLS Series Heat Trace Panel HTLS cul Listed Floor Mount NEMA 4 Steel Enclosure. Includes prewired controller, two-pole contactors, current transformer to measure operating currents, high/low temperature alarms, On/Off control, RTD sensor input, color touchscreen programming, GFI indication or shutdown, common alarm output, Hand/Off/Auto selection loop enable/disable, and auto-cycle feature. Code Number of Loops 8 Independent Loops of Heat Trace Control Code Voltage Vac Vac Vac Code Circuit Breaker Rating Selection 1 15A Thermal Magnetic Circuit Breakers 2 20A Thermal Magnetic Circuit Breakers 3 30A Thermal Magnetic Circuit Breakers Code Cabinet Heater 0 None 1 Thermostat Controller Enclosure Heater Code Pressurization Control System 0 None 1 Type Z for Class I Division 2 Hazardous Location HTLS Typical Model Number 38 *MODBUS is a registered trademark of Gould Inc.
41 intellitrace Multi-Loop Ambient-Sensing Control Panel Technical Specifications Supply Voltage: 120, 240 and 277 Vac Three-Phase Operating Environment: 30º to 120ºF (0º to 40ºC) Communications: RS-485 MODBUS* Maximum Current: 24A/Ckt Ground Fault Alarm: Adjustable 25 to 500mA, Factory 30mA Continuity Alarm: < 2A Non-Latching Load Management: 15-Second Non-Overlap to Reduce In-Rush Auto-Cycle: Programmable to 720 Hr (30 days) Control Mode: Optional Ambient Sensing Controller Ordering Information Model HTAS Series Heat Trace Panel HTAS cul Listed Floor Mount NEMA 4 Steel Enclosure. Includes optional ambient sensing controller, two-pole contactors current transformer to measure operating currents, continuity alarms, color touchscreen programming, GFI indication or shutdown, common alarm output, Hand/Off/Auto selection, loop enable/disable, and auto-cycle feature. Code Number of Loops 8 Independent Loops of Heat Trace Control Code Voltage Vac Vac Vac Code Circuit Breaker Rating Selection 1 15A Thermal Magnetic Circuit Breakers 2 20A Thermal Magnetic Circuit Breakers 3 30A Thermal Magnetic Circuit Breakers Code Cabinet Heater 0 None 1 Thermostat Controller Enclosure Heater Code Ambient Sensing Controller 0 None (Remote Mounted) , Three-Digit, Dual Display 1/16 Din Controller w/ Temp Alarms , Three-Digit, Dual Display 1/16 Din Controller w/ Temp Alarms Code Pressurization Control System 0 None 1 Type Z for Class I Division II Hazardous Location HTAS Typical Model Number *MODBUS is a registered trademark of Gould Inc. 39intelliTRACE CONTROLS
42 intellitrace CONTROLS intellitrace Controls for Hazardous Location Applications Description The Chromalox HTLSC1D2 series panels are microprocessor based temperature control and monitoring units for heat tracing used in freeze protection and process temperature control applications. This series of panels can be configured for ambient or line sensing control. The HTLSC1D2 series implement a scaleable design such that they can be configured with or without communications, ground fault monitoring or enclosure heater. This unique format offers a design that can be tailored both by price and features to meet the most challenging demands in heat trace applications. For example: The HTLSC1D2 series can be networked together via RS-485 MODBUS and the Chromalox Windows based Chromasoft SpecView software package. The optional ground fault monitoring addresses the national electric code requirements and reduces the cost of installing costly ground-fault circuit breakers. In the event of sub-zero temperatures the optional enclosure heater is available. The Chromalox HTLSC1D2 series offers single and dual loop designs and are approved for Class 1 Division 2 Areas. The HTLSC1D2 series have programmable inputs (thermocouple, RTD, ma, VDC), On/Off or PID control, Auto-tune function, High/Low temperature alarms, current alarm, and sensor failure indication. The heat tracing circuit is switched by a 30 amp solid state relay rated at 40 C ambient. The Chromalox HTLSC1D2 series panel comes ready to install and includes control and power wiring terminal blocks for field connections. 40
43 HTLS C1D2 Single-Loop Sensing Control Panel Front View Side View Technical Specifications Area of Use: Class 1 Division 2 Approvals: UL, cul, CE Supply Voltage: 120, 208, 240, 277, and 480 Vac. Ambient Operating Temperature: 32 to 104 F (0 to 40 C), -32 to 104 F (-35.5 to 40 C) with Optional Enclosure Heater. Protection: NEMA 4X Fiber Glass Communications: RS-485 MODBUS* Temperature Sensor Input: J, K, T, E, B, R, S, N, L, PT100, mv, ma, V Output: Solid State Relay Rated 40 C. Current Alarm (Low): 0-50A in.1a Resolution. Temperature Alarms: Field Selectable Deviation High/Low, Deviation Band High/Low, Process Low /High, Latching, Non-Latching. Control Modes: Field Selectable On/Off, PID, Auto-Tune. Ground Fault Alarm: Adjustable Trip Level 30 to 300mA; Adjustable Trip Delay 0 to 1 sec. Ordering Information Model HTLSC1D2 Series Heat Trace Panel HTLSC1D2 cul, UL and CE Listed Single Loop Line Sensing Temperature/Monitor Heat Trace Panel. Factory pre-wired for quick installation. Includes: Solid State Relay, Current Transformer, High-Low Temperature Alarms, Low Current Alarm, On/Off or PID Control, Universal Sensor Inputs, Dual Digital Displays, Terminal Blocks for Field Connections, Loop Enable/Disable, NEMA 4X rated Enclosure (16 H x 14 W x 8 D) for Indoor/Outdoor Applications. Options Include: Ground Fault Monitoring, Digital Communications and Enclosure Heater. Code Amps 1 30 Code Voltage Vac Vac Vac Vac Vac Code Controller 0 ETR Controller 1 ETR Controller with Communications Code Ground Fault Monitoring 0 None 1 Ground fault Module (Includes Illuminated Reset Switch) Code Enclosure Heater 0 None 1 Thermostat Controlled Enclosure Heater HTLSC1D Typical Model Number *MODBUS is a registered trademark of Gould Inc. 41intelliTRACE CONTROLS
44 intellitrace CONTROLS HTLS C1D2 Dual-Loop Sensing Control Panel Front View Side View Technical Specifications Area of Use: Class 1 Division 2 Approvals: UL, cul, CE Supply Voltage: 120, 208, 240, 277, and 480 Vac. Ambient Operating Temperature: 32 to 104 F (0 to 40 C), -32 to 104 F (-35.5 to 40 C) with Optional Enclosure Heater. Protection: NEMA 4X Fiber Glass Communications: RS-485 MODBUS* Temperature Sensor Input: J, K, T, E, B, R, S, N, L, PT100, mv, ma, V Output: Solid State Relay Rated 40 C. Current Alarm (Low): 0 to 50A in.1a Resolution. Temperature Alarms: Field Selectable Deviation High/Low, Deviation Band High/Low, Process Low /High, Latching, Non-Latching. Control Modes: Field Selectable On/Off, PID, Auto-Tune. Ground Fault Alarm: Adjustable Trip Level 30 to 300mA; Adjustable Trip Delay 0 to 1 sec. Ordering Information Model HTLSC1D2 Series Heat Trace Panel HTLSC1D2 cul, UL and CE Listed Dual Loop Line Sensing Temperature/Monitor Heat Trace Panel. Factory pre-wired for quick installation. Includes: Solid State Relay, Current Transformer, High-Low Temperature Alarms, Low Current Alarm, On/Off or PID Control, Universal Sensor Inputs, Dual Digital Displays, Terminal Blocks for Field Connections, Loop Enable/Disable, NEMA 4X rated Enclosure (18 H x 16 W x 10 D) for Indoor/Outdoor Applications. Options Include: Ground Fault Monitoring, Digital Communications and Enclosure Heater. Code Amps 2 30 Code Voltage Vac Vac Vac Vac Vac Code Controller 0 ETR Controller 1 ETR Controller with Communications Code Ground Fault Monitoring 0 None 1 Ground fault Module (Includes Illuminated Reset Switch) Code Enclosure Heater 0 None 1 Thermostat Controlled Enclosure Heater HTLSC1D Typical Model Number 42 *MODBUS is a registered trademark of Gould Inc.
45
46 Chromalox Value-Added Products and Services Are Available Worldwide Worldwide Customer Service Argentina Australia Austria Belgium Bolivia Brazil Canada Chile China Colombia Costa Rica Dominican Republic Ecuador Egypt El Salvador England France Germany Greece Guatemala Honduras Hong Kong Iceland India Indonesia Iran Israel Japan Korea Kuwait Lebanon Malaysia Mexico Netherlands Nicaragua Norway Pakistan Peru Puerto Rico R.O.C. (Taiwan) Saudi Arabia Singapore Sweden Switzerland Thailand Turkey United States Venezuela United Arab Emirates Chromalox PRECISION HEAT AND CONTROL 103 Gamma Drive Ext. Pittsburgh, PA USA Phone: (412) Fax: (412) Toll-Free: Eltron Chromalox Eltron House Whitehorse Road Croydon, Surrey, CR9 2NA, UK Tel: +44 (0) Fax: +44 (0) Etirex Chromalox Route de Château-Thierry Noyant et Aconin F SOISSONS Cedex, France Tel: +33 (0) Fax: +33 (0) Chromalox, Inc. PJ304-3
Self-Regulating Low Temperature Heating Cable
PDS SRL Self-Regulating Low Temperature Heating Cable Self-Regulating, Energy Efficient 16 AWG Buss Wire Circuit Lengths to 660 Feet Process Temperature Maintenance to 150 F (65 C) Maximum Continuous Exposure
Heating Cable. Construction
Mineral Insulated High Temperature A C Constant Wattage Series Resistance Heating Cable Sets Process Temperature Maintenance to F (593 C) Maximum Exposure Temperature 4 F (76 C) (Power Off) Corrosion Resistant
Pictorial Index... A-14 Introduction to Heat Trace Cable Systems... 6-2 Installation Examples... 6-3 Engineering Guide... 6-4 Heat Loss Tables...
Pictorial Index....................... A-14 Introduction to Heat Trace Cable Systems............... 6-2 Installation Examples................... 6-3 Engineering Guide..................... 6-4 Heat Loss
Pipe Freeze Protection Design/Install Guide
Pipe Freeze Protection Design/Install Guide Page 1 of 16 Pipe Freeze Protection Design / Install Guide CONTENTS Introduction Page 3 STEP 1 Information Required Page 4 STEP 2 Design Considerations Page
Installation Instructions. Industrial Heating Cable Products
Installation Instructions Industrial Heating Cable Products PJ438-21 161-057884-001 September, 2014 Important General Instructions These instructions are to be followed when installing Chromalox Heating
Nelson MI Cable is a high performance, industrial grade heat tracing cable used for applications requiring:
Alloy 825 Sheath Custom Fabricated Heating Elements Magnesium Oxide Insulation Description: Mineral insulated cable is a metal sheathed cable that uses a metallic conductor as the heating element. The
Self-Regulating Pipe Tracing Heating Cable Specification/Application Guide. Polyolefin. Performance and Rating Data
TSR Self-Regulating Pipe Tracing Heating Cable Specification/Application Guide READ CAREFULLY PRINCIPLE OF OPERATION Easy Heat TSR is a self-regulating heating cable that automatically varies its heat
Heat Tracing Products
Applications Electric Industrial Process Maintenance Applications Commercial Applications Chromalox heating cable line includes cables suitable for most process maintenance, pipe and vessel freeze protection
UNITHERM UNITHERM 2256/2266 SELF-REGULATING ELECTRIC TRACE TUBING
UNITHERM UNITHERM 2256/2266 SELF-REGULATING ELECTRIC TRACE TUBING HIGH TEMPERATURE MAINTENANCE AND STEAM CLEANED LINES Principal of Operation Unitherm 2256/2266 HTM (High Temperature Maintenance) Electric
Thermwire. Selection Guide. Freeze Protection Heating Cable. Thermwire -Wrap. Pre-Assembled. Thermwire-Comp. Thermwire-Melt.
Thermwire Freeze Protection Heating Cable Selection Guide Pipe Freeze Protection Heating Cable Pre-Assembled Pipe Freeze Protection Heating Cable with Attached Cord & Plug Thermwire-Comp Refrigeration
Complex Piping Design Guide for Self-Regulating Heating Cables
Complex Piping Design Guide for Self-Regulating Heating Cables Introduction... 4 Computer Aided Design Program... 4 Heat Tracing Design Outline... 5 Basis for a Good Design... 5-14 Step 1: Establish Design
Installation, Operation and MAINTENANCE INSTRUCTIONS. Industrial Heating Cable Products IMPORTANT GENERAL INSTRUCTIONS
Chromalox Installation, Operation and MAINTENANCE INSTRUCTIONS DIVISION 4 SALES REFERENCE DATE SERVICE REFERENCE (Supersedes PJ438-16) JULY, 2010 SECTION RT PJ438-18 161-057884-001 Industrial Products
Type FLX Freezer Floor Frost Heave Protection DESIGN GUIDE
Type FLX Freezer Floor Frost Heave Protection DESIGN GUIDE Commercial Products Type FLX TM Freezer Floor Frost Heave Protection DESIGN GUIDE Contents Introduction...2 Application Information... 2-3 Product
BSX TM. Self-Regulating Heating Cable. Product Specifications
BSX TM Freeze Protection or Process Temperature Maintenance BSX self-regulating heating cables are designed to provide freeze protection or process temperature maintenance to metallic and nonmetallic piping,
HEAT TRACING PRODUCTS
PJ-324 HEAT TRACING PRODUCTS Training Manual CHROMALOX FOR INTERNAL USE ONLY Copyright 1998, E. L. Wiegand Div. Emerson Electric The facts and the recommendations made in this publication are based on
SELF-REGULATING PIPE TRACING HEATER CABLE
SELF-REGULATING PIPE TRACING HEATER CABLE Installation & Operation Manual TABLE OF CONTENTS GENERAL INFORMATION... 1 How Heating Systems Work...1 PRODUCT SELECTION... 1 RECEIPT & STORAGE... 1 Receipt...1
Electric Heat Tracing INSTALLATION PROCEDURES
INSTALLATION PROCEDURES The following installation procedures are suggested guidelines for the installation of a Thermon electric heat tracing system 1. Individuals installing these products are responsible
Mineral Insulated Heating
Self-Regulating Mineral Insulated cables This section provides an overview and general design guidelines for mineral insulated heat-tracing systems. For complete design assistance, contact your Pentair
MIQ TM Mineral Insulated Heating Cable INSTALLATION PROCEDURES. (North America)
MIQ TM Mineral Insulated INSTALLATION PROCEDURES (North America) MIQ TM Mineral Insulated The following installation procedures are suggested guidelines for the installation of a Thermon MIQ mineral insulated
Installation Instructions DTS-HAZ DTS-HAZ-DC. for Use with Self-Regulating & Constant Wattage Heating Cables
Installation Instructions DTS-HAZ DTS-HAZ-DC for Use with Self-Regulating & Constant Wattage Heating Cables PJ944-9 5625-81049 May 2013 1 2 DTS-HAZ Self-Regulating & Constant Wattage Heating Cables Junction
Heat Tracing Sales Mt. Airy, Maryland www.heattracingsales.com 410-795-2223. Installation Instructions
Chromalox Installation Instructions DIVISION 4 SALES REFERENCE DATE SERVICE REFERENCE SECTION DTS (Supersedes PJ944-5) PJ944-6 161-562581-049 MARCH, 2012 DTS-HAZ For Use With Self-Regulating & Constant
DTS-HAZ DTS-HAZ-DC. Installation Instructions. for use with Self-Regulating, Constant Wattage & Mineral Insulated Electric Heating Cables
Installation Instructions DTS-HAZ DTS-HAZ-DC for use with Self-Regulating, Constant Wattage & Mineral Insulated Electric Heating Cables 1 PJ944-10 5625-81049 May 2015 2 DTS-HAZ & DTS-HAZ-DC 1 2 3 8 12
Screw Plug Immersion Heaters
Immersion Heaters Overview Immersion Heaters consist of hairpin bent tubular elements brazed or welded into a screw plug and provided with terminal enclosures for electrical connections. Immersion Heaters
NELSON HEAT TRACING SYSTEMS
DESCRIPTION The HASK-P Hazardous Area Seal Kit provides the cable termination and explosion proof seal parts needed to make the power end electrical connections associated with Nelson Heat Tracing Systems
PRODUCT / APPLICATION INFORMATION
Abstract This paper will discuss performance life testing and stability testing used for self-regulating heating cables. It will show how the techniques were developed and evolved from the 970 s to the
for Hazardous Division 1 Locations
Self-Regulating Heat-Tracing Systems for Hazardous Division 1 Locations Design and Installation Guide Power-Limiting Mineral Insulated Longline RTB Tubing Bundles Tank Snow and Ice Control and Monitoring
COLD LEAD OPTIONS FOR XMI MINERAL INSULATED (MI) HEATING CABLES
COLD LEAD OPTIONS FOR XMI MINERAL INSULATED (MI) HEATING CABLES PRODUCT OVERVIEW XMI with standard MI cold lead and Type X connector MI cable heated section PRODUCT OVERVIEW XMI with PyroFLX cold lead
Electric Heat Tracing INSTALLATION PROCEDURES
INSTALLATION PROCEDURES Complete Electric Heat Tracing System... Types of Heating Cables 1... Self-Regulating Heating Cables: BSX (refer to Form TEP0067U) 1725 II 2 G & D Ex e II T5 or T6 DEMKO 02ATEX0132424,
Installation & Maintenance
Installation & Maintenance SELF-REGULATING HEATER CABLE CONTENTS GENERAL INFORMATION... 4 How Heating Systems Work...4 PRODUCT SELECTION... 4 RECEIPT & STORAGE... 4 Receipt...4 Storage...4 Withdrawal from
8146/5 Series Breaker Panelboards
8146/5 Series Breaker Panelboards DISTRIBUTION BREAKER PANELBOARDS FOR HAZARDOUS & CORROSIVE ENVIRONMENTS Breaker Panels Features: Wide variety of Flameproof branch circuit breakers for Zone 1 & Division
Industrial Heat Tracing INSTALLATION AND MAINTENANCE MANUAL FOR MINERAL INSULATED CABLE SYSTEMS APPLIED TO PIPES AND VESSELS
Industrial Heat Tracing INSTALLATION AND MAINTENANCE MANUAL FOR MINERAL INSULATED CABLE SYSTEMS APPLIED TO PIPES AND VESSELS INDUSTRIAL HEAT TRACING SOLUTIONS WWW.PENTAIRTHERMAL.COM Important Safeguards
Terminal Box. Specifications TNCN
Terminal box The /TNCC range comprises many standard sizes of enclosures manufactured in stainless steel 316L for maximum environmental protection. The main body is manufactured from minimum 1,5 mm sheet
STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM
STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM Installed in Pre-engineered Steel Buildings Provides Lowest Cost Construction Method for CORROSIVE AND WET Environments PREFERRED SOLUTIONS, INC.
920 Series. Dual-point heat-tracing control system. Product overview. 920*E4FWL*SIS302*SS3102 shown
Self-Regulating 920 Series Dual-point heat-tracing control system Power-Limiting Mineral Insulated 920*E4FWL*SIS302*SS3102 shown Product overview The DigiTrace 920 is a compact, full-featured, microprocessor-based,
Appendix J: Engineering Specification for Electrical Heat-Tracing Systems
Appendix J: Engineering Specification for Electrical Heat-Tracing Systems Contents 1 Scope........................................................... 11 2 Codes, Approvals, and Standards......................................
SnoTrace KSR Surface Snow and Ice Melting INSTALLATION PROCEDURES
SnoTrace Surface Snow and Ice Melting INSTALLATION PROCEDURES SnoTrace INSTALLATION PROCEDURES Refer to the SnoTrace Cable Testing Report for required recording of test data and circuit information. Upon
INFRARED RADIANT HEATERS. air heaters
INFRARED RADIANT HEATERS OVERVIEW Economic, efficient, and clean, WATTCO infrared radiant heaters are designed for comfort heating applications that require radiant heat in indoor, outdoor, and exposed
Explosion-Proof Electric Unit Heaters
Type FX4 FX4 Explosion-Proof Electric Air Heaters FX4 heaters are UL listed and/or CSA certified for use in hazardous locations. They are designed for dry indoor industrial applications such as oil refineries,
Heat Pipe Selection Revision 12/04/2001
Heat Pipe Selection Revision 12/04/2001 Heat pipes are being used very often in particular applications when conventional cooling methods are not suitable. Once the need for heat pipe arises, the most
B. ASTM C 533 Calcium Silicate Block and Pipe Thermal Insulation. C. ASTM C 547 Mineral Fiber Preformed Insulation
PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is
TubeTrace, ThermoTube
TubeTrace, ThermoTube and Custom CEMS Tubing Bundles INSTALLATION PROCEDURES English Units TubeTrace & ThermoTube Tubing Bundles Receiving, Storing and Handling... 1. Inspect materials for damage incurred
Calculating Heat Loss by Mark Crombie, Chromalox
Calculating Heat Loss by Mark Crombie, Chromalox Posted: January 30, 2006 This article deals with the basic principles of heat transfer and the calculations used for pipes and vessels. By understanding
RayClic Connection System Installation Instructions
F M -W RayClic Connection System Installation Instructions RayClic WARNING: Shock Hazard 718K Pipe Heating Cable with HWAT, IceStop, also Listed De-icing and and XL-Trace heating Snow Melting Equipment
Mineral Insulated Heater Cable. Installation & Operation Manual
Mineral Insulated Heater Cable Installation & Operation Manual CONTENTS general information...1 How Heating Systems Work...1 PrOduct selection...1 RECEIPT & STORAGE...1 PIPE LENGTH VERFICATION...1 DRAWINGS...2
Terminal Boxes Series 8146
Series > Enclosures in shock-resistant glass fibre reinforced polyester resin > basic enclosure sizes various heights > Fitted according to the customer's requirements > For terminals up to max. 00 mm
MTI10 Insertion and MTL10 In-line Thermal Mass Flowmeter and Temperature Transmitter
Thermal Mass meter and Temperature Transmitter Description The MTI10 insertion thermal mass flowmeter and the MTL10 in-line thermal mass flowmeter provide accurate mass flow measurement of clean, dry gases
WaterMAG. Electromagnetic Flowmeter for Water Applications. Model MCB10A OVERVIEW APPLICATIONS FEATURES. No. SS2-MCB100-0100
WaterMAG Electromagnetic Flowmeter for Water Applications OVERVIEW The WaterMAG is an electromagnetic flowmeter for water measurement applications based on field proven Azbil Corporation's technologies.
100% EMI Emission Containment
100% EMI Emission Containment Designed for Longer Service Life Highly Flexible for Easier Handling and Faster Installation Authorized Distributor Industrial VFD Cables Index n Variable Frequency Drive
KSR-SK-DB In-Line Splice Kit KSR Snow Melting Cable INSTALLATION PROCEDURES
KSR-SK-DB In-Line Splice Kit KSR Snow Melting Cable INSTALLATION PROCEDURES KSR-SK-DB The following installation procedures are suggested guidelines for the installation of in-line cable splices. They
Frost Heave Protection System Installation and Operation Manual for Self-Regulating Heating Cable Systems
Frost Heave Protection System Installation and Operation Manual for Self-Regulating Heating Cable Systems FHP Self-regulating Heating Cable Systems 1 / 17 WARNING: Fire and Shock Hazard Raychem frost heave
SYSTEM 1850-SE SERVICE ENTRANCE CABLE SYSTEM
Pyrotenax SYSTEM 1850-SE SERVICE ENTRANCE CABLE SYSTEM Contents Introduction This section provides an overview of general circuit design considerations and installation guidelines for a Pyrotenax System
Light Duty Commercial Electric Water Heater
Features Heavy Duty Construction Hydrastone cement lining provides longer tank life Copper-silicon tappings cannot rust or corrode High impact composite jacket eliminates damage during installation and
AT500 Magnetostrictive Level Transmitter. Compact magnetostrictive liquid level transmitter for direct insertion K-TEK Products
Data sheet DS/AT500-EN Rev. M AT500 Magnetostrictive Level Transmitter Compact magnetostrictive liquid level transmitter for direct insertion K-TEK Products Features Mounts from Top of Tank High Resolution
Electro-Magnetic Flowmeters COPA-XT 2-Wire DT43
Data Sheet Electro-Magnetic Flowmeters COPA-XT 2-Wire DT43 2-Wire Operation Significantly reduces installation costs when compared to a traditional 4-wire magmeter. ±0.5% of rate system accuracy. Patented
Industrial Heat-Tracing Installation and Maintenance Manual
Industrial Heat-Tracing Installation and Maintenance Manual Self-Regulating and Power-Limiting Heating Cable Systems WARNING: Fire and shock hazard. Raychem heat-tracing systems must be installed correctly
2.12. page 223 2.12. Products for Explosion hazardous Environment
2.12 page 223 2.12 Products for Explosion hazardous Environment Non-electric valves for explosion 2.12.1 page 224 hazardous environment The following manually and mechanically actuated valves are available
Hook-Up and Lead Wire
3.1 Hook-Up and Lead Wire 3 Table of Contents Hook-Up & Lead Wire Page Introduction: UL Style & CSA Type Listings 3.2 PVC 3.3 3.8 300V, 80 C 3.3 300V, 105 C 3.4 600V, 105 C 3.5 (Type MW) MIL-W-76C-PVC:
4 Posiflow Proportional Solenoid Valves
4 Posiflow Solenoid Brass or Stainless Steel Bodies 1/4" to 1/2" NPT 2/2 Features Flow rates adjustable between 0% and 100% of rating Flow rate can also be regulated by a range of electrical inputs (sensors,
% ^ ) 0.55 W Low Power Solenoid Valves Aluminum, Brass, or Stainless Steel Bodies 1/4" to 1" NPT. 2/2 3/2 4/2 5/2 5/3 SERIES Low Power
.55 W Solenoid Valves Aluminum, Brass, or Stainless Steel Bodies /" to " NPT / 3/ / 5/ 5/3 Features Molded one-piece solenoid with highly efficient solenoid cartridge and.55 W low wattage coil Standard
MAC-120HE-01 Air-Cooled Chiller
MAC-120HE-01 Air-Cooled Chiller 10 Ton / 120,000 BTUH Air-Cooled Chiller 208/230-1-50/60 1 HVAC Guide Specifications Air-Cooled Liquid Chiller Nominal Size: 10 Tons Multiaqua Model Number: MAC-120HE-01
Contact Information: 4031-0001 Electrical Connection Kit for CL Series Constant Wattage Temptrace for Low Temperature Maintenance.
Technical Data Sheet & Installation Instructions for 4031-0001 Electrical Connection Kit for CL Series Constant Wattage Temptrace for Low Temperature Maintenance Bulletin CL-II Contact Information: Parker
XL-Trace System Installation and Operation Manual
XL-Trace System Installation and Operation Manual Pipe freeze protection and flow maintenance WARNING: Fire and shock hazard. This heat-tracing system must be installed correctly to ensure proper operation
One Year Warranty. Stock U.S. # of Volts Weight CONN. Height Dia. Watts # GAL. Elements INS. Inches NATURAL GAS* Six Year Warranty
One Year Warranty ELECTRIC Stock U.S. # of Volts Weight CONN. Height Dia. Watts # GAL. Elements INS. Inches Fused Ceramic Shield tank lining is corrosion-resistant for years of dependability. Adjustable
RTB Tubing Bundles Installation Guide Heating solutions for instrument and small-diameter process lines
RTB Tubing Bundles Installation Guide Heating solutions for instrument and small-diameter process lines 1 / 20 WARNING: Fire and shock hazard. Raychem heat-tracing systems must be installed correctly to
INSTALLATION AND OPERATION INSTRUCTIONS - (LOW FLOW MODELS) (Before installation, compare electrical needed for the model of heater selected)
CHRONOMITE INSTANT-FLOW WATER HEATER INSTALLATION AND OPERATION INSTRUCTIONS - (LOW FLOW MODELS) (Before installation, compare electrical needed for the model of heater selected) TABLE 1 Model No. Wattage
M SERIES REFRIGERANT COIL MODULE REFRIGERANT COILS for R-22, R-407C, R-410A
Bulletin 20-20.2 / July 2012 M SERIES REFRIGERANT COIL MODULE REFRIGERANT COILS for R-22, R-407C, R-410A ➀ ➁ ➂ Model Number Key M 2430 C L 1 - A - ➀ Unit Type M=Modular Nominal Capacity 2430=24000 to 30000
Voltage Loss Formula s
www.litz-wire.com HM Wire International Inc. Phone: 330-244-8501 Fax: 330-244-8561 Voltage Loss Formula s www.hmwire.com Voltage loss in a wire is synonymous to pressure loss in a pipe. Electric current
Pump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling
Pump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling 250_P1 R10/7/2015 Copyright 2015 Liberty Pumps Inc. All rights reserved. Specifications subject to change without notice.
VIPERFLEX ELECTRIC CABLE
VIPERFLEX Flexible Low Voltage Electric Cable - 0.6/1kV (Rubber insulated) H07 RN-F & H07 BN-F Single Core 2-Core 2-Core and Earth 3-Core and Earth 4-Core and Earth Multi-Core and Earth H07 RCN-F & H07
ELECTRICAL SAFETY Information Bulletin
ELECTRICAL SAFETY Information Bulletin January 2016 CEC-10 [rev-9] Page 1 of 8 CANADIAN ELECTRICAL CODE SUBJECT: Section 10 Grounding and Bonding Rule 10-204 Grounding Connections for Alternating-Current
SECTION 15190 HVAC INSULATION. A. All work specified in this Section is subject to the provisions of Section 15010.
SECTION 15190 HVAC INSULATION PART ONE - GENERAL PART 1 - GENERAL 1.01 DESCRIPTION A. All work specified in this Section is subject to the provisions of Section 15010. B. All insulation products shall
SPECIFICATIONS FOR STEEL PIPE
SPECIFICATIONS FOR STEEL PIPE Published pipe standards serve three functions. 1. They dictate manufacturing and testing requirements and prescribed methods of measuring the required mechanical and physical
BILL OF QUANTITY FOR THE HVAC WORKS OF The Institute of space technology, near Toll Plaza (G.T. Road,) Islamabad
BILL OF QUANTITY FOR THE HVAC WORKS OF The Institute of space technology, near Toll Plaza (G.T. Road,) Islamabad PLEASE MARK TICK ON LEFT BOX WHICH EQUIPMENT YOU HAVE QUOTED PROPOSAL BASED ON CHINESE EQUIPMENT
TABLE 1. Rugged cast aluminum alloy casing,celcon waterways with nichrome parts White (unless stainless steel housing)
CHRONOMITE INSTANT-FLOW MICRO WATER HEATER INSTALLATION AND OPERATION INSTRUCTIONS - (LOW FLOW MODELS) (Before installation, compare electrical needed for the model of heater selected) TABLE 1 Model No.
LHD LINEAR HEAT D ETECTIONN
Tri-Metallic Core: Steel provides tensile strength Copper increase conductivity Tin for corrosion resistance LHD LINEAR HEAT D ETECTIONN TECHNICAL DATA Temperature Rating: 155 F (68 C) (typical temperature)
BOWL ASSEMBLY SELECTION Select impeller in exactly the same manner as for lineshaft type pump. Note comments under WELL SIZE.
SUBMERSIBLE PUMP selection A submersible pump consists of the following basic elements: < Bowl Assembly < Motor < Cable < Drop Pipe < Surface Plate (with)(without) discharge elbow DATA REQUIRED FOR SELECTION
Technical Data. Dimensions
0102 Model Number Features Comfort series 5 mm flush Usable up to SIL 2 acc. to IEC 61508 Accessories BF 18 Mounting flange, 18 mm EXG-18 Quick mounting bracket with dead stop Technical Data specifications
Instrumentation Cable...14-17. Power Cable...2-11. Assembly Solutions...32
Severe Cold Durability Exceeds CSA Cold Bend / Cold Impact (-0 C/-35 C) Drilling Mud Resistant Flame Retardant Certified to IEC 9-3 (33-3A) and IEEE 580 Oil Resistant Assemblies...3-33 Ester Based Mud
Product. for your Project. Our. All at one sight
All at one sight Our Product for your Project self-limiting HeaTIng TaPes fluoropolymer-insulated HeaTIng Cable mineral-insulated HeaTIng Cable ConTRol TeCHnIqUe 2 We focus on the projects you wish to
Gexol. Gexol. The Global Cable Solutions Company. Designed for safe, reliable performance in the harshest oil and gas operating environments
Gexol Gexol World Class World Class Designed for safe, reliable performance in the harshest oil and gas operating environments Power Control Instrument VFD The Global Cable Solutions Company Gexol World
PTFE Slide Bearings 04/10 149
04/10 149 1.0 GENERAL INFORMATION In a wide range of applications, PTFE Slide bearings are superior to conventional expansion plates, rollers and rocker arm type supports. They support petrochemical plant,
General Allowances for Insulation & Cladding
TRADE OF Industrial Insulation PHASE 2 Module 1 Sheet Metal and Insulation Fundamentals UNIT: 4 General Allowances for Insulation & Cladding Produced by In cooperation with subject matter expert: Michael
NFPA 2001: Standard for Clean Agent Fire Extinguishing Systems NFPA 70: National Electrical Code (NEC) NFPA 72: National Fire Alarm Code
Part 1 - GENERAL 1.1 DESCRIPTION OF WORK A. Design and installation of an engineered Kidde ECS Advanced Delivery Systems (ADS), clean agent/waterless fire suppression system employing DuPont FM-200 agent,
2 WAY (2/2) AND 3 WAY (3/2) BRASS AND STAINLESS STEEL SOLENOID VALVES
2 WAY (2/2) AND 3 WAY (3/2) BRASS AND STAINLESS STEEL SOLENOID VALVES DIRECT ACTING Brochure N-289 SPECIFICATIONS Port Size: 1/8 and1/4 Solenoid Valve for air, oil, water and other fluids Flow Direction:
Trade of Electrician. Three-phase Distribution Boards And Socket Circuits
Trade of Electrician Standards Based Apprenticeship Three-phase Distribution Boards And Socket Circuits Phase 2 Module No. 2.3 Unit No. 2.3.2 COURSE NOTES Created by Charlie Walsh - Athlone TC Revision
Data Sheet VITOSOL 100. Flat collectors for the utilisation of solar energy. Vitosol 100. Part nos. and prices: see price list
VITOSOL 100 Flat collectors for the utilisation of solar energy Data Sheet Part nos. and prices: see price list File in: Vitotec 1 Manual, Index 16 Vitosol 100 Type s 1.7 Vitosol 100 Type s 2.5 Vitosol
Technical Information
Determining Energy Requirements - & Gas Heating & Gas Heating and gas heating applications can be divided into two conditions, air or gas at normal atmospheric pressure and air or gas under low to high
RayClic Connection System Installation Instructions
RayClic Connection System Installation Instructions Description RayClic-S Splice Kit RayClic-T Tee and End Seal Kit RayClic-X Cross and End Seal Kit These kits are for use with Raychem IceStop, XL-Trace
CIR. Index. Gexol. Standard CIR UL Listed Type TC-ER. Crush and Impact Resistant Without External Armoring. Arctic CIR UL Listed Type TC-ER-HL*
Gexol CIR Crush and Impact Resistant Without External Armoring Passes the same stringent crush and impact testing required by UL 2225 for Type MC-HL n Available in Standard and Arctic Grade Jackets n Highly
DIESEL-FUELED, BLOWN AIR, DUCTABLE HEATERS
DIESEL-FUELED, BLOWN AIR, DUCTABLE HEATERS Electronic thermostatically controlled Low power consumption Compact space saving size Short heat-up times Dehumidification of the cabin Quiet when running Combustion
5/3/2010. Article 500 address the requirements for hazardous locations: Wiring Equipment
Two Documents are used for the Classification of Combustible Dusts and Hazardous Locations: NFPA 499-Recommended Practices for the Classification of Combustible Dusts and Hazardous Locations for Electrical
SECTION 16461 DRY-TYPE TRANSFORMERS
SECTION 16461 PART 1 - GENERAL 1.1 SECTION INCLUDES A. Furnishing and installation of and testing of cast resin dry type MV/LV distribution transformer in accordance with specifications and drawings. Any
PHOTOVOLTAIC (PV) solar panels. Specification. Electricity - CE & ISO 9000 certified. 83W panel. 180W panel Maximum power:
PHOTOVOLTAIC (PV) solar panels Electricity - CE & ISO 9000 certified Photovoltaic solar panels convert sunlight into useful electricity. ZEDfabric supplies high quality mono-crystalline silicon cell PV
Model F822 thru F834 Mulsifyre Directional Spray Nozzles, Open, High Velocity General Description
Worldwide Contacts www.tyco-fire.com Model F thru F3 Mulsifyre Directional Spray Nozzles, Open, High Velocity General Description The Mulsifyre Nozzles are open (nonautomatic) nozzles and they are designed
PLUGS & RECEPTACLES. INNOVATIVE EXPLOSION PROTECTION by R. STAHL 1-800-782-4357
Series Features: Color coding and pin configuration makes it physically impossible to mate plugs and receptacles of different voltages and current ratings (per IEC 60 309-2). Interlocked switch mechanism
TARIFF CODE and updates standard
TARIFF CODE and updates standard No HS CODE AHTN CODE PRODUCT DESCRIPTION PRODUCT TYPE STANDARDS IDENTIFIED 7207 Semi finished products of iron or non alloy steel Containing by weight less than 0.25% of
ESFR DRY PENDENT SPRINKLER VK502 (K14.0) TECHNICAL DATA
December 19, 2013 Sprinkler 122j 1. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Dry Pendent Sprinkler VK502 is a fast response fusible element type sprinkler designed for use in storage areas
HYDRAULIC AND LUBE OIL HEATERS HYDRAULIC AND LUBE OIL HEATERS. HL Series. Warren Electric Corporation
HYDRAULIC AND LUBE OIL HEATERS HYDRAULIC AND LUBE OIL HEATERS HL Series Warren Electric Corporation Welcome to Warren Electric Quality and Design Excellence has over 35 years of experience in the design
Aeration Air & Digester Gas Flow Metering Using Thermal Mass Technology. HWEA 2011 Conference Craig S. Johnson
Aeration Air & Digester Gas Flow Metering Using Thermal Mass Technology HWEA 2011 Conference Craig S. Johnson Presentation Overview Introduction Aeration Air & Digester gas challenges Gas flow metering
