TC 1818a. Operating Guide. Control Module SWM-015.5

Size: px
Start display at page:

Download "TC 1818a. Operating Guide. Control Module SWM-015.5"

Transcription

1 TC 1818a Control Module Operating Guide SWM-015.5

2 This guide is intended solely for use by owners of Thermon HeatChek TM heat tracing control and monitoring units. This manual describes operation for TC 1818 controllers with fi rmware released in Earlier versions of fi rmware may not include all features described in this manual. This manual is considered proprietary and is protected by copyright. Use by others without expressed written consent of Thermon is strictly prohibited. Thermon 1999, 2005, 2008, 2010 HeatChek and TraceView are tradenames of Thermon Manufacturing Company.

3 TC 1818a Control Module INDEX The TC 1818a Module... 4 TC 1818a Module Specifications... 8 Typical HeatChek Control and Monitoring Units... 9 Programming The TC 1818a The TC 1818a in Operation Configuring the TC 1818a for Ambient Sensing or Dual RTD Control Programming and Operating the TC 1818a in an Ambient Sensing Control Mode Programming and Operating the TC 1818a with Dual Input RTDs for a Single Control Circuit Typical Control Applications Communications Options and Accessories Help Attachment A: TC 1818a Command Flowchart

4 TC 1818a Control Module THE TC 1818a MODULE The TC 1818a is a microprocessor-based temperature control and monitoring module developed specifi cally for heat tracing. The multi-circuit module can provide heat tracing control, digital information display and alarms for high temperature, low temperature, high current, low current, high ground leakage current, circuit fault, and damaged temperature sensor for up to eighteen heat tracing circuits. Resettable minimum and maximum temperatures seen are retained for display on demand. The TC 1818a module operates independently and can also be connected to a data highway for remote systems communication functions through a personal computer or a distributed control system (DCS). 4

5 Operating Guide DATA DISPLAY The TC 1818a module utilizes a backlit Liquid Crystal Display (LCD) for reporting temperatures, currents, and other operating parameters. Alarm LED's in conjunction with the information display indicate high temperature, low temperature, high heater current, low heater current, high ground leakage, sensor fault, and circuit fault alarm status. Additional LED s indicate status of power to the TC 1818a, power to the heat tracing circuits, CPU status, and the general controller alarm status. DATA ENTRY The TC 1818a has a 16 key "tactile feel" membrane switch keypad which provides for modifi cation (with security key access) of all control parameters as well as permits inquiries into the status of any circuit being controlled or monitored. ALARM RELAY The TC 1818a module is provided with three independent normally open, close on alarm, solid state alarm relay contacts, rated 1A at 120/240 VAC. The fi rst of these relays activates in the event of any alarm. The second relay contact activates when any "trip" designated alarms occur. Inverse mode operation on either of these alarms is also confi gurable. The third alarm contact provides information regarding the status of internal module CPU diagnostics. CONTROL RELAY The TC 1818a module can be confi gured with up to eighteen DC outputs each having a sink current capability of VDC for switching up to 18 solid state power relays. MODULE POWER The TC 1818a module is convertible from 120 VAC to 208/ to 240 VAC instrument voltage (50 to 60 HZ) from a slide selector switch. COMMUNICATIONS Each TC 1818a module is provided with an RS-485 communications port for connection through a two wire twisted shielded pair network into a PC. The Modbus ASCII or RTU protocol at 9600 baud rate communications streams may also be interfaced into the distributed control system (DCS). INPUT/OUTPUT MODULE INTERLINK Each TC 1818a can be interlinked with up to three six point sensor input modules and three six circuit power output modules through ribbon cable connections. 5

6 TC 1818a Control Module The TC 1818a is designed to be an integral part of a HeatChek TM control and monitoring unit. Each unit typically includes one or more TC 1818a modules, power output modules, and sensor input modules, all inter-connecting wiring and ribbon cables, and an electrical enclosure suitable for the environment. POWER OUTPUT MODULES Each TC 1818a power output module is confi gured with six solid state power relays. The single switch SSR30 relays utilized are zero crossing solid state with a single cycle surge capacity of 600A and a one second overcurrent capacity of 80A. The dual switch SSR15 relays are zero crossing solid state with a single cycle surge capacity of 500A and a one second overcurrent capacity of 80A. Design current rating limits for these power output modules are determined by the relay type, enclosure size, ambient conditions, and heat sink style (maximum of 30A per single switch relay and 15A for each switch in a dual switch relay). See Table 1 for details. Each power output module is provided complete with input/output terminal blocks for up to six heat tracing circuits, ribbon cable up to 15 ft (4.6 m) in length, connectors for linking to the TC 1818a control module, and a "touch safe" polycarbonate cover mounting assembly. Table 1: Current Rating Maximum Total Heater Current Through Solid State Relays Per Enclosure Enclosure Option Heat Sink Style C 6SSR30C Heat Sink Style C 6SSR15C PS4, SS4 360A 180A PS5, SS5 576A 288A Current ratings are based on outdoor ambients of 104 o F (40 o C) with solar loading. Contact the factory for ratings at higher ambient conditions or for ratings in larger enclosure sizes. The 6SSR30C includes six single switch solid state relays suitable for controlling up to 30 amperes per switch. The 6SSR15C includes six dual switch solid state relays suitable for controlling up to 15 amperes per switch. 6

7 Operating Guide CONTROL AND MONITORING UNIT A HeatChek control and monitoring unit utilizing the TC 1818a module, solid state relay power output modules, sensor input modules, and a NEMA 4 or 4X enclosure is approved/certifi ed for use in Class I, Division 2 Hazardous (classifi ed) as well as Ordinary (non-classifi ed) Locations. These units include the following warning markings: CAUTION! CIRCUITS MAY BE ENERGIZED This marking intends that the user must disconnect all power sources to the panel prior to servicing. This marking indicates a location that must be grounded in accordance with local and national requirements. 7

8 TC 1818a Control Module TC 1818A MODULE SPECIFICATIONS The TC 1818a module has the general specifi cations as detailed below: Control and Monitoring Capacity: Eighteen resistive heat tracing circuits up to 30 amps per circuit (depending on switch type) Module Supply Voltage: Operating Frequency: Power Consumption: VAC or VAC 50 to 60 Hz Nominal 40 watts per TC 1818a module Module Operating Ambient: -40 o F to +140 o F (-40 o C to +60 o C) Maximum Storage Ambient: 158 o F (70 o C) Data Retention: Power Clamp Function: Non volatile EEPROM Programmable for power levels from 20 to 100% maximum power Input: Up to eighteen 3 wire o F (0 o C) platinum RTD's Temperature Range (Control): Control: -40 o F to 932 o F (-40 o C to 500 o C) with programmable control band in increments of one degree On-Off, On-Off with Softstart, Proportional, Proportional Self-Adjust Module Dimensions: 4-1/2" x 19" x 7-1/2" (114 mm x 482 mm x 191 mm) Operating Current Alarm Ground Leakage Alarm/Trip: Self-Test Frequency: High: 1.0 to 30.0 A Low: 0.0 to 30.0 A 30 to 150 ma Programmable from 2 to 99 hours 8

9 Operating Guide TYPICAL HEATCHEK CONTROL AND MONITORING UNITS The TC 1818a is modular in construction and can be confi gured in a variety of HeatChek control and monitoring units. INFORMATION Additional design selection and engineering information may be found in Form T-1008-E. Specifi c wiring and equipment arrangement details are usually provided in drawings included within the HeatChek control and monitoring unit at time of shipment. 9

10 TC 1818a Control Module PROGRAMMING THE TC 1818A MODULE ACCESSING THE PROGRAM MODE Turn the key to the vertical position and then press the PROG key to enter the programming mode. PROG The TC 1818a will then display the following message: PROGRAM MODE ENABLED SELECT FUNCTION KEY Then select the desired function key (e.g. MAINTAIN TEMP). MAINTAIN TEMP If the function key is not a global function (e.g. CONFIG, DATA HWY, etc.) then the following message appears. PROGRAM CIRCUIT=1 Select the desired circuit by pressing the UP or DOWN arrow keys and then pressing the ENTER key. In order to set all circuits to a common value, press the UP arrow key until "ALL THE SAME VALUE" appears. PROGRAM = ALL THE SAME VALUE Press ENTER to globally set a control or operating parameter. 10

11 Operating Guide MAINTAIN TEMPERATURE (PROGRAM MODE) The following is a typical message which might appear: MAINTAIN TEMP=104 F NEW VALUE=104 F Momentarily pressing the UP or DOWN arrow keys will cause the NEW VALUE to change by 1 degree increments. Holding the key down results in a 10 degree incremental change. If an upper or lower limit is reached, a MAX or MIN message will appear on the second line. This indicates that either the absolute maximum or minimum value has been reached or that the value has reached an alarm value. MAINTAIN TEMP=104 F NEW VALUE=50 F Once the desired temperature value is set, press the ENTER key to save the value. The controller will then exit the programming mode and return to the Scan Mode RETURN TO SCAN MODE 11

12 TC 1818a Control Module HIGH TEMPERATURE ALARM (PROGRAM MODE) Pressing the HIGH TEMP ALARM function key results in a display message such as the following: HIGH TEMP ALARM HIGH TEMP ALARM=160 F NEW VALUE=160 F The TC 1818a is set to alarm at 160 o F on the current circuit number. Should the control temperature reach 160 o F, the red "ALARM ON" LED on the TC 1818a will begin to fl ash and the "HIGH TEMP" LED will illuminate when the circuit in alarm appears on the INFORMATION DISPLAY. In addition, the alarm relay contact will close (depending on confi guration, inverse action may occur). To change the current value, press the UP or DOWN arrow keys to increase or decrease the current HIGH TEMP ALARM setpoint. HIGH TEMP ALARM=160 F NEW VALUE=120 F 12

13 Operating Guide Once the desired temperature value is set, press the ENTER key to save the value. Next, the following typical message will appear: 2 HIGH TEMP SEEN=200 F RESET? (Y/N) At some point since this controller was last reset, the temperature has attained 200 F. Press the UP arrow key and ENTER to clear this value and begin anew at the current value. Pressing ENTER or PROG key results in the current value of 200 F being retained. Subsequently, the TC 1818a returns to the Scan Mode. RETURN TO SCAN MODE 13

14 TC 1818a Control Module LOW TEMPERATURE ALARM (PROGRAM MODE) Pressing the LOW TEMP ALARM function key results in a display message such as the following: LOW TEMP ALARM LOW TEMP ALARM=50 F NEW VALUE=50 F The TC 1818a is set to alarm at 50 o F on the current circuit number. Should the control temperature drop to 50 o F, the "ALARM ON" LED on the TC 1818a will begin to fl ash and the "LOW TEMP" LED will illuminate when the circuit in alarm appears on the INFORMATION DISPLAY. In addition, the alarm relay contact will close (depending on confi guration, inverse action may occur). To change the present value, press the UP or DOWN arrow keys to increase or decrease the present LOW TEMP ALARM setpoint.once the desired temperature value is set, press the ENTER key to save the value. LOW TEMP ALARM=50 F NEW VALUE=35 F 14

15 Operating Guide Next, the following typical message will appear: 2 LOW TEMP SEEN=40 F RESET? (Y/N) At some point since this controller was last reset, the control temperature has dropped to 40 F. Pressing the ENTER key results in the present value of 40 F being retained. Press the UP arrow key and ENTER to clear the stored value and begin anew at the current value. Subsequently, the TC 1818a returns to the Scan Mode. RETURN TO SCAN MODE 15

16 TC 1818a Control Module HEATER CURRENT (PROGRAM MODE) Pressing the HEATER CURRENT key (when the TC 1818a is confi gured with solid state relays and is set for On-Off with Soft Start, Proportional, or Proportional with Self-Adjust) results in a display message as typically given below: HEATER CURRENT POWER AT MAINT TEMP=22% NEW VALUE=22% In this case, the power clamp function is currently in the active or enabled mode. In this mode, the TC 1818a will (through the zero crossing solid state relay provided) use cycle omission techniques to limit the maximum power available to the heater to the value shown (to some value less than the heater would ordinarily provide) at the temperature control setpoint. For more details, refer to pages 27 and 28. Pressing the ENTER key will retain the current mode of operation. Pressing the UP or DOWN arrow key and pressing ENTER will result in the altering of the power percentage and hence result in the limiting of heater power when "ON" at the temperature control setpoint. 16

17 Operating Guide The TC 1818a will now return to Scan Mode. RETURN TO SCAN MODE The TC 1818a is provided with a built-in "Soft Start" power up feature when confi gured in the On-Off with Soft Start, Proportional, or Proportional Self-Adjust modes. This feature will utilize cycle omission techniques to ramp up to maximum allowable heater power in a span of approximately 5.5 minutes. This ramp up feature is designed to specifi cally address a) cold start power surges associated with self limiting and power limiting heaters, and b) minimize overshoot which may sometimes be present when utilizing high output heaters in low heat loss applications. Should the TC 1818a be confi gured in the On-Off mode, no programming functions such as Power Clamping are available. In addition, no "Soft Start" control functions will be active. 17

18 TC 1818a Control Module GROUND CURRENT (PROGRAM MODE) Pressing the GROUND CURRENT function key results in a display message such as the following: GROUND CURRENT GROUND CURRENT ALARM=40mA NEW VALUE=40mA The TC 1818a is set to alarm at heater and associated wiring ground leakage current of 40mA on the chosen circuit number. Should the ground leakage value reach 40mA, the "ALARM ON" LED on the TC 1818a will begin to fl ash and the "GROUND CURRENT" LED will illuminate when the circuit in alarm appears on the INFORMATION DISPLAY. In addition, the alarm relay contact will close (depending on confi guration, inverse action may occur). To change the value, press the UP or DOWN arrow keys to increase or decrease the GROUND CURRENT ALARM setpoint. GROUND CURRENT ALARM=40mA NEW VALUE=30mA Once the desired new value is set, press the ENTER key to save the value. Subsequently, the TC 1818a returns to the Scan Mode. RETURN TO SCAN MODE 18

19 Operating Guide HIGH CURRENT ALARM (PROGRAM MODE) Pressing the HIGH CURRENT ALARM function key results in a display message such as the following: HIGH CURRENT ALARM HIGH CURRENT ALARM=20.0A NEW VALUE=20.0A The TC 1818a is set to alarm at heater current levels above 20 Amperes on the present circuit number. Should the heater current reach 20A, the "ALARM ON" LED on the TC 1818a will begin to fl ash and the "HIGH CURRENT" LED will illuminate when the circuit in alarm appears on the INFORMATION DISPLAY. In addition, the alarm relay contact will close (depending on confi guration, inverse action may occur). To change the value, press the UP or DOWN arrow keys to increase or decrease the HIGH CURRENT ALARM setpoint. HIGH CURRENT ALARM=20.0A NEW VALUE=25.0A Once the desired new value is set, press the ENTER key to save the value. Subsequently, the TC 1818a returns to the Scan Mode. RETURN TO SCAN MODE 19

20 TC 1818a Control Module LOW CURRENT ALARM (PROGRAM MODE) Pressing the LOW CURRENT ALARM function key results in a display message such as the following: LOW CURRENT ALARM LOW CURRENT ALARM=1.0A NEW VALUE=1.0A The TC 1818a is set to alarm at heater current levels below 1 Ampere. Should the heater current drop to 1A, the "ALARM ON" LED on the TC 1818a will begin to fl ash and the "LOW CURRENT" LED will illuminate when the circuit in alarm appears on the INFORMATION DISPLAY. In addition, the alarm relay contact will close (depending on confi guration, inverse action may occur). To change the value, press the UP or DOWN arrow keys to increase or decrease the LOW CURRENT ALARM setpoint. LOW CURRENT ALARM=1.0A NEW VALUE=2.0A Once the desired new value is set, press the ENTER key to save the value. Subsequently, the TC 1818a returns to the Scan Mode. RETURN TO SCAN MODE 20

21 Operating Guide CONFIG (PROGRAM MODE) The CONFIG key provides access to setting all global control parameters on the TC 1818a. Pressing the CONFIG key results in the following display prompt: RTD FAULT TURNS CKT ON CHANGE? (Y/N) A "Yes" entry will result in an "Open" relay condition in the event of a RTD sensor failure. Press the UP arrow key for "Yes" or DOWN arrow key for "No." Then press the ENTER key to save. A "No" entry will result in a "Closed" relay condition in the event of a RTD sensor failure. Subsequently, the TC 1818a follows with the below message on the information display: GROUND CURRENT TRIP OFF CHANGE? (Y/N) The TC 1818a is currently set to NOT trip the heater circuits if a high ground leakage condition occurs, but rather will only "fl ash" the "ALARM ON" LED and close the standard alarm relay (open in inverse operation). To retain the present mode of GROUND CURRENT TRIP operation, press the ENTER key. Pressing the UP arrow key and ENTER will result in the TC 1818a setting being changed to GROUND CURRENT TRIP ON. 21

22 TC 1818a Control Module The TC 1818a will then prompt for the preferred HIGH CURRENT trip setting. HIGH CURRENT TRIP OFF CHANGE? (Y/N) The TC 1818a is currently set to NOT trip the heater circuits if a high heater current alarm condition occurs, but rather will only "fl ash" the "ALARM ON" LED and close the standard alarm relay (open in inverse operation). To retain the present mode of HIGH CURRENT ALARM operation, press the ENTER key. Pressing the UP arrow key and ENTER will result in the TC 1818a setting being changed to HIGH CURRENT TRIP ON. Once set in this manner, the heater circuits will trip (open heater relay contacts) should a heater current alarm condition occur. The TC 1818a will now require that the operator 1) press the ACKNOWLEDGE key, 2) and the high current alarm condition be cleared prior to automatic control being restored. The TC 1818a next prompts for the HIGH TEMP ALARM trip setting. HIGH TEMP TRIP OFF CHANGE? (Y/N) 22

23 Operating Guide The TC 1818a is currently set to NOT trip the heater circuits if a high temperature alarm condition is reached, but rather to only "fl ash" the "ALARM ON" LED and close the standard alarm relay (open in inverse operation). To retain the present mode of HIGH TEMP ALARM operation, press the ENTER key. Pressing the UP arrow key and ENTER will result in the TC 1818a setting being changed to HIGH TEMP TRIP ON. Once set in this manner, the heater circuits will trip (open heater relay contacts) should a high temperature alarm condition occur. The TC 1818a will now require that the operator 1) press the ACKNOWLEDGE key, 2) and the high current alarm condition be cleared prior to automatic control being restored. The TC 1818a is provided with On-Off, On-Off with Soft Start, Proportional, and Proportional with Self-Adjust control options. The information display next prompts for the type of control to be selected. In the ON-OFF control mode, the heater circuit will turn on and off within the programmed control band value. CONTROL = ON/OFF CHANGE? (Y/N) Press the DOWN arrow and ENTER key to accept this control type. Otherwise, to change the control type, press the UP arrow key and the ENTER key. The ON-OFF with SOFT-START option allows the circuit to be gradually powered up by zero crossing cycle omission over a span of approximately 5.5 minutes. Thereafter, the heater circuit will turn on and off within the programmed control band value. CONTROL = SOFT/START CHANGE? (Y/N) 23

24 TC 1818a Control Module To retain the present setting, press the ENTER key. To change the control type, press the UP arrow key and the ENTER key. The PROPORTIONAL option will now control the heater within the programmed control band using a proportional algorithm. This algorithm will adjust the power at maintain from 20% - 100% (or programed value). CONTROL = PROPORTIONAL CHANGE? (Y/N) To retain the present setting, press the ENTER key. To change the control type, press the UP arrow key and the ENTER key. CONTROL = SELF ADJUST CHANGE? (Y/N) With the SELF-ADJUST feature, the TC 1818a will measure the inherent system error and will automatically adjust the proportional control parameters to decrease the deviation from setpoint to a minimal value. To retain the present setting, press the ENTER key. To change the control type, press the UP arrow key and the ENTER key. Note the SELF-ADJUST control option is only available in the SINGLE RTD controller confi guration. 24

25 Operating Guide The TC 1818a offers the option of setting the standard alarm relay switch to be "Closed on Alarm" or "Open on Alarm." The information display next prompts for alarm preferences. STD ALARM CLOSED ON ALARM CHANGE? (Y/N) Press the ENTER key to retain the current setting. Press the UP arrow key and the ENTER key to change the alarm switch action. The TC 1818a also offers the option of setting the second TRIP alarm relay switch to be "Closed on Alarm" or "Open on Alarm." The information display next prompts for alarm preferences. TRIP ALARM CLOSED ON ALARM CHANGE? (Y/N) 25

26 TC 1818a Control Module Press the ENTER key to retain the current setting. Press the UP arrow key and the ENTER key to change the alarm switch action. The TC 1818a is standardly provided with a SELF TEST function which turns each of the heater circuits "On" and "Off" and looks for the appropriate changes in the relay heater current. During the heater "On" state, the TC 1818a also checks for the presence of both "LOW CURRENT" alarms and "GROUND CURRENT" alarms. The TC 1818a prompts for the desired settings for the "SELF TEST." AUTO SELF TEST = OFF NEW VALUE = OFF MIN. The SELF TEST function is currently disabled. Press the ENTER key to retain this setting. Press the UP arrow key and the ENTER key to change to an automatic SELF TEST interval from 2 to 99 hours. Subsequently the TC 1818a returns to the Scan Mode. RETURN TO SCAN MODE 26

27 Operating Guide CONTROL BAND (PROGRAM MODE) Pressing the CONTROL BAND key results in the following display prompt: CONTROL BAND=3 o F NEW VALUE=3 o F If confi gured in the "On-Off" or "Soft Start" control mode, the TC 1818a will turn on the heater at the maintain temperature setpoint and will turn off at 3 o F above this value. ON-OFF CONTROL WITH 100% POWER Maintain Temp 100% 0% Heater Power Control Band If programmed to operate in the "Proportional Mode", and the "Power at Maintain Temperature" is set at 100%, the TC 1818a will operate at 100% power below the maintain temperature setpoint and will ramp down in power within the control band and subsequently turn off when above the maintenance temperature plus control band. PROPORTIONAL WITH 100% POWER Maintain Temp 100% 20% 0% Heater Power Control Band 27

28 TC 1818a Control Module If the "Power at Maintain Temperature" has been programmed to some other value (for example, 62%), the TC 1818a will operate at that power level value at the maintenance temperature and the control band range will adjust as shown below. PROPORTIONAL WITH 62% POWER 100% Maintain Temp Control Band 62% 20% 0% Heater Power Adjusted Control Band When confi gured in the "Proportional with Self-Adjust" mode, the TC 1818a will initially operate in the "Proportional Mode" and will subsequently begin to automatically adjust the slope of the power ramp down. The "Power at Maintain Temperature" will decrease until power output matches the demand. PROPORTIONAL WITH SELF-ADJUST Maintain Temp 100% 55% Steady State 0% Heater Power Control Band 28

29 Operating Guide To retain present control band setting, press the ENTER key. Press the UP or DOWN arrow key to increase or decrease the control band and press ENTER to save the new value. Subsequently, the TC 1818a returns to the Scan Mode. RETURN TO SCAN MODE 29

30 TC 1818a Control Module HEATER ENABLE (PROGRAM MODE) The TC 1818a can be factory confi gured for operation with a variety of pipe sensing, ambient sensing, and RTD assignment confi gurations. When programming the HEATER ENABLE settings in one of these control confi gurations, the following alternate prompt window messages may appear. For the controller confi guration SINGLE RTD INPUTS, the following message will appear Prompt Window Message ENABLED CHANGE? (Y/N) DISABLED CHANGE? (Y/N) FORCE HEATER ON? (Y/N) Explanation The ENABLED prompt will appear on all process sensing circuits. These circuits will turn on when the TC 1818a senses a process temperature below the maintain temperature setpoint. The DISABLED prompt allows the option of disabling this control circuit for service work. The FORCE HEATER ON prompt allows the option of temporarily turning on the heater circuit for diagnostic purposes. For the controller confi guration 1 AMB / SINGLE RTD INPUTS, the following message will appear. Prompt Window Message ENABLED (AMBIENT SENSE) CHANGE? (Y/N) ENABLED (PIPE SENSE) CHANGE? (Y/N) DISABLED CHANGE? (Y/N) FORCE HEATER ON? (Y/N) Explanation The ENABLED (AMBIENT SENSE) prompt will appear for all ambient sensed heater circuits. These heater circuits will turn on when the TC 1818a senses an ambient temperature on Heater Circuit 1 which is below the maintain temperature setpoint. Other circuits may appear as ENABLED (PIPE SENSE). In that case, these heater circuits will turn on when the TC 1818a senses a pipe or heated surface temperature which is below the maintain temperature setpoint. In this controller confi guration, CIRCUIT 1 must be set as AMBIENT SENSE. The DISABLED prompt allows the option of disabling this control circuit for service work. The FORCE HEATER ON prompt allows the option of temporarily turning on the heater circuit for diagnostic purposes. 30

31 Operating Guide For the controller confi guration 2 AMB/ SINGLE RTD INPUTS, the following message will appear. Prompt Window Message ENABLED (AMBIENT SENSE) CHANGE? (Y/N) ENABLED (PIPE SENSE) CHANGE? (Y/N) DISABLED CHANGE? (Y/N) FORCE HEATER ON? (Y/N) Explanation The ENABLED (AMBIENT SENSE) prompt will appear for all ambient sensed heater circuits. These heater circuits will turn on when the TC 1818a senses an ambient temperature on Heater Circuit 1 or 2 which is below the maintain temperature setpoint. Other circuits may appear as ENABLED (PIPE SENSE). In that case, these heater circuits will turn on when the TC 1818a senses a process temperature which is below the maintain temperature setpoint. In this controller confi guration, CIRCUIT 1 and 2 must be set as AMBIENT SENSE. The DISABLED prompt allows the option of disabling this control circuit for service work. The FORCE HEATER ON prompt allows the option of temporarily turning on the heater circuit for diagnostic purposes. For the controller confi guration 1 or 2 RTD INPUTS, the following message will appear. Prompt Window Message ENABLED (ONE RTD) CHANGE? (Y/N) ENABLED (TWO RTD'S) CHANGE? (Y/N) DISABLED CHANGE? (Y/N) FORCE HEATER ON? (Y/N) Explanation These heater circuit prompts appear when using dual RTD input controller confi gurations. In these cases, the heater circuits will turn on when the TC 1818a senses a process temperature (on one or both RTD sensors) which is below the maintain temperature setpoint. The DISABLED prompt allows the option of disabling this control circuit for service work. The FORCE HEATER ON prompt allows the option of temporarily turning on the heater circuit for diagnostic purposes. 31

32 TC 1818a Control Module For the controller confi guration 1 AMB/ 1 or 2 RTD INPUTS, the following message will appear. Prompt Window Message ENABLED (AMBIENT SENSE) CHANGE? (Y/N) ENABLED (TWO RTD'S) CHANGE? (Y/N) ENABLED (ONE RTD) CHANGE? (Y/N) DISABLED CHANGE? (Y/N) FORCE HEATER ON? (Y/N) Explanation These prompts appear when using dual RTD process sensing as well as ambient sensing circuit controller confi gurations. These heater circuits will turn on when the TC 1818a senses an ambient temperature (based on the value of the RTD reading in Circuit 1) which is below the maintain temperature setpoint. Other circuit prompts may appear as ENABLED (ONE RTD or TWO RTD'S). In these cases, the heater circuits will turn on when the TC 1818a senses a process temperature (on one or both RTD sensors) which is below the maintain temperature setpoint. Except in the case of CIRCUIT 1 which must be AMBIENT SENSE in this factory confi guration, all other circuits may be set as AMBIENT SENSE or ONE or TWO RTDS control. The DISABLED prompt allows the option of disabling this control circuit for service work. The FORCE HEATER ON prompt allows the option of temporarily turning on the heater circuit for diagnostic purposes. For the controller confi guration 2 AMB/ 1 or 2 RTD INPUTS, the following message will appear. Prompt Window Message Explanation ENABLED (AMBIENT SENSED) CHANGE? (Y/N) ENABLED (ONE RTD) CHANGE? (Y/N) ENABLED (TWO RTD) CHANGE? (Y/N) These prompts appear when using dual RTD process sensing as well as ambient sensing circuit controller confi gurations. These heater circuits will turn on when the TC 1818a senses an ambient temperature (based on the lower value of the RTD reading in Circuit 1 and 2) which is below the maintain temperature setpoint. Other circuit prompts may appear as ENABLED (ONE RTD or TWO RTDS). In that case, these heater circuits will turn on when the TC 1818a senses a process temperature (on one or both RTD sensors) which is below the maintain temperature setpoint. Except in the case of CIRCUIT 1 and 2 which must be AMBIENT SENSE in this controller confi guration, all other circuits may be set as AMBIENT SENSE or ONE or TWO RTDS control. 32

33 Operating Guide Prompt Window Message Explanation DISABLED CHANGE? (Y/N) FORCE HEATER ON? (Y/N) The DISABLED prompt allows the option of disabling this control circuit for service work. The FORCE HEATER ON prompt allows the option of temporarily turning on the heater circuit for diagnostic purposes. Starting programming by pressing the PROG key. PROG Subsequently, press the HEATER ENABLE key. HEATER ENABLE Select the desired circuit by pressing the UP or DOWN arrow keys and then pressing the ENTER key. Depending on the TC 1818a controller confi guration, variations in the prompt message may be seen. PROGRAM CIRCUIT = 1 A prompt message as shown below will then appear. ENABLED CHANGE? (Y/N) This heater circuit is currently enabled and will turn on when the TC 1818a senses a temperature below the maintain temperature setpoint. 33

34 TC 1818a Control Module If the TC 1818a is set for an ambient control confi guration the following two enable prompt messages will appear. ENABLED (AMBIENT SENSE) CHANGE? (Y/N) Pressing the DOWN arrow key will leave the heater enabled in the ambient sense mode. Press the UP arrow key and the ENTER key. The TC 1818a will now prompt as follows. ENABLED (PIPE SENSE) CHANGE? (Y/N) Pressing the DOWN arrow key and the ENTER key will result in enabling the heater as a pipe sensing circuit. Pressing the UP arrow key will result in the following new prompt. DISABLED CHANGE? (Y/N) Pressing the DOWN arrow key and the ENTER key wil result in disabling the heater circuit and thus result in the removal of external heat from the pipe or heated surface. The TC 1818a will next prompt as follows. FORCE HEATER ON? (Y/N) Press the UP arrow key and the ENTER key to retain this setting. In this operating mode, the heater will remain ON as long as no programmed alarm limits are exceeded. Pressing the DOWN arrow and ENTER key will result in the TC 1818a returning to SCAN MODE. RETURN TO SCAN MODE 34

35 Operating Guide DATA HIGHWAY (PROGRAM MODE) Pressing the DATA HIGHWAY key results in the following display prompt: DATA HIGHWAY=4 NEW VALUE=4 The TC 1818a is currently identifi ed as address number 4. This unique address allows the data highway communications software to identify the information being sent by the controller with a location and heater circuit number. To retain the present address value, press the ENTER key. Press the UP or DOWN arrow key to increase or decrease the address value and press ENTER to confi rm the new address. The TC 1818a has the capability to choose the Modbus ASCII or the Modbus RTU protocols. MODBUS ASCII CHANGE? Y/N Pres the ENTER key to retain the current Modbus protocol. Press the UP arrow key to change the protocols. Press the ENTER key to confi rm the new settings. 35

36 TC 1818a Control Module The TC 1818a allows the successive numbering of circuit numbers for a group of modules. As shown below, the TC 1818a prompts for the beginning circuit number for the control module being programmed. 1ST CIRCUIT NUMBER=1 NEW VALUE = 1 MIN. Press the ENTER key to retain the current beginning circuit number. Press the UP arrow key to arrive at the desired starting point and the ENTER key to confi rm the new starting circuit number. The TC 1818a then returns to the Scan Mode. 36

37 Operating Guide THE TC 1818A IN OPERATION POWER UP (SCAN MODE) On power up, the TC 1818a will display the following two start-up screen messages. THERMON TC 1818a COPYRIGHT RTD INPUTS 18 RELAY OUTPUTS This prompt message indicates that this TC 1818a controller has been confi gured to control eighteen heater circuits with eighteen individual RTD inputs. Depending on the TC 1818a controller confi guration, variations in the above message sequence may be seen. Then the TC 1818a will go into Scan Mode. 37

38 TC 1818a Control Module Once in Scan Mode operation, in the standard factory confi guration the TC 1818a will sequentially indicate the temperature reading along with the maintain temperature. CKT 1 TEMP=51 F MAINTAIN TEMP=50 o F CKT 4 TEMP=51 F MAINTAIN TEMP=50 F CKT 2 TEMP=122 F MAINTAIN TEMP=120 F CKT 5 TEMP=122 F MAINTAIN TEMP=120 F CKT 3 TEMP=605 F MAINTAIN TEMP=600 F CKT 6 TEMP=605 F MAINTAIN TEMP=600 F Upon displaying all temperature information for all confi gured circuits, the TC 1818a will subsequently return to the fi rst circuit and repeat the display sequence. Refer to page 53 for more details on alternate control options and prompt messages. 38

39 Operating Guide WHEN IN ALARM (SCAN MODE) Un-Acknowledged Alarms When an alarm condition occurs, the "ALARM ON" LED will begin to fl ash, the "ALARM TYPE" LED's will illuminate when the specifi c circuit in alarm appears on the INFORMATION DISPLAY, and the standard alarm relay will close. Acknowledged Alarms To acknowledge an alarm condition, press the ALARM ACK key. The fi rst alarm condition will be indicated in the INFORMATION DISPLAY. Pressing the ALARM ACK key again will acknowledge this alarm. Repeat this sequence to determine the nature of additional alarms. Acknowledged alarms are indicated by the suffi x Ack appearing when the alarm condition is displayed. Acknowledged alarms will continue to be displayed until the alarm condition clears. When all alarms have been acknowledged then the ALARM ON light on the controller will cease fl ashing but will stay ON until all alarm conditions have cleared. Manual Reset If a TRIP option has been set on a circuit, then all alarms for that circuit must be acknowledged before they will clear. When TRIP has been triggered, the alarm for that trip must be acknowledged and the alarm condition must clear before automatic control is restored. Automatic Reset When no TRIP options have been set, the alarms will automatically clear when the alarm condition has cleared. 39

40 TC 1818a Control Module ACCESSING DATA (DISPLAY MODE) Press the MAINTAIN TEMP key to display the Maintain Temperature for all circuits as typically shown. MAINTAIN TEMP MAINTAIN TEMP CIRCUIT 1=50 F MAINTAIN TEMP CIRCUIT 4=50 F MAINTAIN TEMP CIRCUIT 2=120 F MAINTAIN TEMP CIRCUIT 5=120 F MAINTAIN TEMP CIRCUIT 3=600 F MAINTAIN TEMP CIRCUIT 6=600 F RETURN TO SCAN MODE Press the HEATER CURRENT key to display the Heater Amperage for all enabled circuits as typically shown. HEATER CURRENT HEATER CURRENT CIRCUIT 1=1.0A HEATER CURRENT CIRCUIT 4=1.0A HEATER CURRENT CIRCUIT 2=5.0A HEATER CURRENT CIRCUIT 5=5.0A HEATER CURRENT CIRCUIT 3=20.0A HEATER CURRENT CIRCUIT 6=20.0A RETURN TO SCAN MODE 40

41 Operating Guide Press the CONFIG key to display the global settings for all trip and control functions, to view the interval between self tests, and to do a manual SELF TEST on the circuits. A typical display sequence is shown. RTD FAULT TURNS CKT OFF GROUND CURRENT TRIP ON HIGH CURRENT TRIP OFF HIGH TEMP TRIP ON CONTROL = ON/OFF STD ALM CLOSED ON ALARM TRIP ALM CLOSED ON ALARM 2 RTD ALARM DEADBAND TEMP = 1 F * * NOTE: This information screen only appears when a circuit is confi gured for dual RTD inputs. AUTO SELF TEST ON INTERVAL 2 HOURS CIRCUIT TEST IN PROGRESS TESTING CIRCUIT #1 CIRCUIT TEST IN PROGRESS TESTING CIRCUIT #4 CIRCUIT TEST IN PROGRESS TESTING CIRCUIT #2 CIRCUIT TEST IN PROGRESS TESTING CIRCUIT #5 CIRCUIT TEST IN PROGRESS TESTING CIRCUIT #3 CIRCUIT TEST IN PROGRESS TESTING CIRCUIT #6 RETURN TO SCAN MODE 41

42 TC 1818a Control Module Press the CONTROL BAND key to display the control band settings for all circuits as typically shown. CONTROL BAND CONTROL BAND CIRCUIT 1=2 F CONTROL BAND CIRCUIT 4=2 F CONTROL BAND CIRCUIT 2= 3 F CONTROL BAND CIRCUIT 5=3 F CONTROL BAND CIRCUIT 3= 10 F CONTROL BAND CIRCUIT 6=10 F Subsequently, the TC 1818a returns to Scan Mode. RETURN TO SCAN MODE 42

43 Operating Guide Press the GROUND CURRENT key to display ground leakage current from heater and associated wiring on all circuits as typically shown. GROUND CURRENT GROUND CURRENT CIRCUIT 1=15mA GROUND CURRENT CIRCUIT 4=15mA GROUND CURRENT CIRCUIT 2=5mA GROUND CURRENT CIRCUIT 5=5mA GROUND CURRENT CIRCUIT 3=10mA GROUND CURRENT CIRCUIT 6=10mA Subsequently the Information display will begin displaying the ground leakage alarm/trip settings for each circuit. GROUND CURRENT ALARM CIRCUIT 1=40mA GROUND CURRENT ALARM CIRCUIT 4=40mA GROUND CURRENT ALARM CIRCUIT 2=30mA GROUND CURRENT ALARM CIRCUIT 5=30mA GROUND CURRENT ALARM CIRCUIT 3=50mA GROUND CURRENT ALARM CIRCUIT 6=50mA Upon completion of the display of the ground current alarm/trip values on all circuits, the TC 1818a returns to Scan Mode. RETURN TO SCAN MODE 43

44 TC 1818a Control Module Press the HEATER ENABLE key to display if the heater status is set as enabled. The heater status can be enabled, disabled, forced on, or tripped. HEATER ENABLE HEATER CIRCUIT 1= ENABLED HEATER CIRCUIT 4 = ENABLED HEATER CIRCUIT 2= ENABLED HEATER CIRCUIT 5 = ENABLED HEATER CIRCUIT 3= ENABLED HEATER CIRCUIT 6 = FORCED ON Refer to page 54 for more details on alternate HEATER ENABLE prompt messages. Subsequently, the TC 1818a returns to Scan Mode. RETURN TO SCAN MODE 44

45 Operating Guide Press the HIGH TEMP ALARM key to display the High Temperature Alarm Setpoint and Highest Temperature Seen for all circuits as typically shown. HIGH TEMP ALARM HIGH TEMP ALARM CIRCUIT 1=130 F HIGH TEMP ALARM CIRCUIT 4=130 F HIGH TEMP ALARM CIRCUIT 2=20 F HIGH TEMP ALARM CIRCUIT 5=200 F HIGH TEMP ALARM CIRCUIT 3=700 F HIGH TEMP ALARM CIRCUIT 6= 700 F The TC 1818a will then begin to scroll through the highest stored value of temperature for each circuit. HIGH TEMP SEEN CIRCUIT 1=200 F HIGH TEMP SEEN CIRCUIT 4=200 F HIGH TEMP SEEN CIRCUIT 2=300 F HIGH TEMP SEEN CIRCUIT 5=300 F HIGH TEMP SEEN CIRCUIT 3=700 F HIGH TEMP SEEN CIRCUIT 6=700 F Subsequently, the TC 1818a returns to Scan Mode. RETURN TO SCAN MODE 45

46 TC 1818a Control Module Press the HIGH CURRENT alarm key to display the High Heater Current Alarm setpoint as typically shown. HIGH CURRENT ALARM HIGH CURRENT ALARM CIRCUIT 1=5.0A HIGH CURRENT ALARM CIRCUIT 4=5.0A HIGH CURRENT ALARM CIRCUIT 2= 10A HIGH CURRENT ALARM CIRCUIT 5=10A HIGH CURRENT ALARM CIRCUIT 3=30A HIGH CURRENT ALARM CIRCUIT 6=30A The TC 1818a then returns to Scan Mode. RETURN TO SCAN MODE Press the DATA HWY key to display the Data Highway address setting for the module and check the data highway communication status (respectively). DATA HWY DATA HIGHWAY ADDRESS=18 COMM STATUS=IN A "COMM STATUS" of IN or OUT denotes direction of the message transmittals (the absence of IN or OUT indicates that data highway communications link has not been established). Subsequently, the TC 1818a then returns to Scan Mode. RETURN TO SCAN MODE 46

47 Operating Guide Press the LOW TEMP ALARM key to display the Low Temperature Alarm Setpoint and Lowest Temperature Seen for all circuits as typically shown. LOW TEMP ALARM LOW TEMP ALARM CIRCUIT 1=35 F LOW TEMP ALARM CIRCUIT 4=35 F LOW TEMP ALARM CIRCUIT 2=75 F LOW TEMP ALARM CIRCUIT 5=75 F LOW TEMP ALARM CIRCUIT 3=450 F LOW TEMP ALARM CIRCUIT 6=450 F The TC 1818a will then begin to scroll through the lowest stored value of temperature for each circuit. LOW TEMP SEEN CIRCUIT 1=37 F LOW TEMP SEEN CIRCUIT 4=37 F LOW TEMP SEEN CIRCUIT 2=75 F LOW TEMP SEEN CIRCUIT 5=75 F LOW TEMP SEEN CIRCUIT 3=550 F LOW TEMP SEEN CIRCUIT 6=550 F Upon completing the display of all the LOW TEMP SEEN data, the TC 1818a returns to Scan Mode. RETURN TO SCAN MODE 47

48 TC 1818a Control Module Press the LOW CURRENT alarm key to display the Low Heater Current Alarm setpoint for all circuits as typically shown. LOW CURRENT ALARM LOW CURRENT ALARM CIRCUIT 1=1.0A LOW CURRENT ALARM CIRCUIT 4=1.0A LOW CURRENT ALARM CIRCUIT 2=8.0A LOW CURRENT ALARM CIRCUIT 5=8.0A LOW CURRENT ALARM CIRCUIT 3=12.0A LOW CURRENT ALARM CIRCUIT 6=12.0A After scanning through all circuits, the TC 1818a returns to Scan Mode. RETURN TO SCAN MODE 48

49 Operating Guide UNDERSTANDING ALARM CONDITIONS When temperature related alarm conditions do occur, the below information may be useful in establishing the cause and appropriate action. HIGH TEMPERATURE (HIGH TEMP) Low Limit: Maintain temperature plus control band value High Limit: 1100 o F or 600 o C Range: 0 o F to 1100 o F or 0 o C to 600 o C Cause: Sensed temperature exceeds programmed high temperature alarm setpoint Controller Action Taken: Alarm Only or Alarm and Trip Heater (if trip is set) LOW TEMPERATURE (LOW TEMP) Low Limit: -40 o F or -40 o C High Limit: Maintain temperature value Range: -40 o F to 1099 o F or -40 o C to 599 o C Cause: Sensed temperature is below programmed low temperature alarm setpoint Controller Action Taken: Alarm Only RTD FAULT Cause: Controller Action Taken: RTD resistance not in the 70 to 300 ohms range Alarm and heater are energized or alarm and heater are turned off depending on programming confi guration. 49

50 TC 1818a Control Module When heater related alarms occur, the below information may be useful in establishing a cause and an appropriate action. HIGH CURRENT (HIGH CURRENT) Low Limit: Low current alarm value High Limit: 30.0A Range: 1 to 30.0A Cause: Heater current is more than high current alarm value Controller Action Taken: Alarm Only or Alarm and Trip Heater (if trip is set) LOW CURRENT (LOW CURRENT) Low Limit: 0.0A High Limit: High current alarm value Range: 0 to 30.0A Cause: Heater current is less then low current alarm value Controller Action Taken: Alarm Only HIGH GROUND CURRENT (HIGH GND CUR) Low Limit: 30mA High Limit: 150mA Range: 30 to 150mA Cause: An excessive heater/wiring leakage current is present Controller Action Taken: Alarm Only or Alarm and Trip Heater (if trip is set) CIRCUIT FAULT (CKT FAULT) Checks For: Damaged relay or loss of current during "heater on" cycle Cause: Relay locked open or closed, breaker off, or heater/wiring disconnected Controller Action Taken: Alarm Only POWER OFF Cause: Controller Action Taken: Reset Procedure: Loss of voltage to unit None Power off message will clear itself after 30 minutes or can be manually cleared with the ALARM ACK key 50

51 Operating Guide CONFIGURING THE TC 1818A FOR AMBIENT SENSING OR DUAL RTD CONTROL The TC 1818a is standardly confi gured for process sensing with one RTD input assigned to each relay output circuit. The operating descriptions in this manual to this point have covered using the TC 1818a when set up as a "Standard Control" confi guration. Depending on the fi rmware level, the TC 1818a can also be factory or fi eld confi gured for up to fi ve other control confi gurations. The six possible control confi gurations are identifi ed in the below list. Configuration SINGLE RTD INPUTS Description Conventional process sensing control - one RTD input for each heat tracing circuit. 1 AMB/SINGLE Ambient sensing RTD in Circuit 1 controlling all RTD INPUTS designated ambient sensing circuits with conventional process sensing control on all process sensing circuits (one RTD input for each heat tracing circuit). 2 AMB/SINGLE Ambient sensing RTD's in Circuit 1 and 2 and controlling RTD INPUTS all designated ambient sensing circuits based on the lowest RTD reading with conventional process sensing control on all process sensing circuits (one RTD input for each heattracing circuit). 1 or 2 RTD INPUTS Single and dual RTD process sensing control - one or two RTD inputs for each heat tracing circuit as designated. 1 AMB/ 1 or 2 RTD INPUTS Ambient sensing RTD in Circuit 1 controlling all designated ambient sensing circuits with single or dual RTD process sensing control on all process sensing circuits. 2 AMB/ 1 or 2 RTD INPUTS Ambient sensing RTD's in Circuit 1 and 2 and controllingl all designated ambient sensing circuits based on the lowest RTD reading with single or dual RTD process sensing control on all process sensing circuits. 51

52 TC 1818a Control Module In order to factory or fi eld program the TC 1818a for any confi guration other than the standard SINGLE RTD INPUTS, fi rst momentarily press the DATA HWY key. DATA HWY Next press and hold the MAINTAIN TEMP key for about 5 seconds. MAINTAIN TEMP The following prompt window message will next appear. ITEM TO CONFIGURE Press the CONFIG key. CONFIG The current setting for the TC 1818a control confi guration will appear. SINGLE RTD INPUTS CHANGE? (Y/N) Press the UP arrow key and ENTER to change or press the DOWN arrow key and ENTER to accept the current confi guration and then return to SCAN MODE. RETURN TO SCAN MODE 52

53 Operating Guide It is intended that this confi guration setting be set prior to programming in all heat tracing circuit parameters. If it is necessary to change the settings once the unit is installed in the fi eld, it is recommended that all heat tracing circuit parameters be entered again. ALTERNATE CONTROL CONFIGURATIONS IN OPERATION Information screens will vary slightly depending on which alternate control confi guration is enabled. A summary of the alternate message screens which may be seen during the SCAN MODE of operation are listed below: Message Window CKT 1 TEMP = 51 F HEATER POWER= 100% AMB CKT 1 TEMP = 51 F HEATER FORCED ON CKT 1 TEMP = 51 F MAINTAIN TEMP = 50 o F PS Description Where a heater circuit on the TC 1818a controller has been programmed for ambient sensing control operation, this information screen indicates the temperature being read by the RTD on this circuit number and also indicates the percentage of power being supplied to the circuit. When the power clamping function or ambient proportional control is utilized, the percentage "time on" can vary from 100% to as low as 20%. This information screen indicates that the temperature being read by the RTD on this circuit number is 51 o F and that the heater has been "forced on". In the "forced on" mode, the circuit will remain on as long as no programmed alarm limits are exceeded. This programmed setting is primarily used for fi eld diagnostic testing. Where a heater circuit on the TC 1818a controller has been programmed for process temperature sensing operation, this information screen indicates the temperature being read by the RTD on this circuit number as well as the actual maintain temperature programmed. 53

54 TC 1818a Control Module Message Window CKT 1 TEMP = 51 F, 53 F HEATER POWER=100% AMB CKT 1 TEMP = 51 F, 53 F HEATER FORCED ON CKT 1 TEMP = 51 F, 53 F MAINTAIN TEMP = 50 F PS Description Where a heater circuit on the TC 1818a controller has been programmed for ambient sensing control operation with dual RTD inputs, this information screen indicates the temperatures being read by the RTDs on this circuit number and also indicates the percentage of power being supplied to the circuit. When the power clamping function or ambient proportional control is utilized, the percentage "time on" can vary from 100% to as low as 20%. This information screen indicates that the temperatures being read by the dual RTDs programmed to sense temperature for this circuit number and that the heater has been "forced on". This program setting is primarily used for fi eld diagnostic testing. Where a heater circuit on the TC 1818a controller has been programmed for dual RTD process temperature sensing operation, this information screen indicates the temperatures being read by the RTDs on this circuit number as well as the actual maintain temperature programmed. When inquiring as to the heater status (enabled, disabled, forced on, or tripped) by pressing the HEATER ENABLE key, the following alternate message screens may be seen: Message Window HEATER CIRCUIT 3= ENABLED AMB Description This information screen identifi es the Circuit 3 as being enabled as an ambient sensing RTD circuit. HEATER CIRCUIT 3= ENABLED PS This information screen identifi es the Circuit 3 as being enabled as a process temperature sensing RTD circuit. HEATER CIRCUIT 4= ENABLED 1RTD This information screen identifi es the Circuit 4 as being enabled with one RTD sensor input. HEATER CIRCUIT 4= ENABLED 2RTD This information screen identifi es the Circuit 4 as being enabled with dual RTD sensor inputs. 54

55 Operating Guide PROGRAMMING AND OPERATING THE TC 1818A IN AN AMBIENT SENSING CONTROL MODE The TC 1818a control module should fi rst be confi gured to allow wide band proportional temperature control in ambient sensing control applications. The simplest controller confi guration to implement ambient sensing control are the single RTD input controller confi gurations listed below: 1 AMB/ SINGLE RTD INPUTS 2 AMB/ SINGLE RTD INPUTS When programmed for one of these controller confi gurations, the TC 1818a control module will accept one ambient sensing RTD input (Circuit 1) or two ambient sensing RTD inputs (Circuit 1 and 2), and will read this input or the lower of the two values into all other ambient sense enabled circuits for control purposes. While most of the TC 1818a operation in this mode is identical to that previously described (recognizing, of course, that the temperature being acted upon is the ambient value), there are a few differences which are described in the following sections. 55

56 TC 1818a Control Module HEATER ENABLE (PROGRAM MODE) To program the control mode of each circuit, press sequentially the PROG key and the HEATER ENABLE key. The TC 1818a will prompt for the selection of the desired circuit (or All the Same Value). PROGRAM CIRCUIT=1 Press the UP or DOWN arrow key and ENTER. The TC 1818a will indicate the present setting (Ambient Sensing, Pipe Sensing, or Disabled). Press the UP arrow key to change the value and then the ENTER key to accept the new value. ENABLED (AMBIENT SENSE) CHANGE? (Y/N) ENABLED (PIPE SENSE) CHANGE? (Y/N) The confi guration restrictions on combinations of process (pipe) sensing and ambient sensing circuits are: Circuit 1 for single RTD sensor input must be retained as ambient sensing control circuit. Circuit 1 and 2 for dual RTD sensor inputs must be retained as ambient sensing control circuits. Proportional control mode must be utilized on both ambient and process (pipe) sensed circuits. 56

57 Operating Guide MAINTAIN TEMP (PROGRAM MODE) In order to set the maintain temperature when using ambient sensing control, press the PROG key. The TC 1818a will prompt for the function to program. PROGRAM MODE ENABLED SELECT FUNCTION KEY Press the MAINTAIN TEMP key. The TC 1818a will next prompt for the selection of the desired circuit (or All the Same Value). PROGRAM CIRCUIT=2 Press the UP or DOWN arrow key and ENTER. The TC 1818a will prompt for the maintain temperature as follows: MAINTAIN TEMP=120 F NEW VALUE=120 F When in ambient sensing control mode, the minimum ambient temperature should be entered here (this is the 100% heater power value in wide band proportional control). To change the present maintain temperature value, press the UP or DOWN arrow key until the proper value is displayed. MAINTAIN TEMP=120 F NEW VALUE=-20 F Press the ENTER key to accept the new value. The TC 1818a will then return to the Scan Mode operation. 57

58 TC 1818a Control Module CONTROL BAND (PROGRAM MODE) In order to set the control range for ambient sensing control, press the PROG key. The TC 1818a will prompt for the function to program. PROGRAM MODE ENABLED SELECT FUNCTION KEY Press the CONTROL BAND key. The TC 1818a will next prompt for the selection of the desired circuit (or All the Same Value). PROGRAM CIRCUIT=1 Press the UP or DOWN arrow key and ENTER. The TC 1818a will prompt for the control band as follows: CONTROL BAND=5 F NEW VALUE=5 F 58

59 Operating Guide When in wide band ambient sensing control mode, the control band will be between the minimum ambient temperature (the 100% heater power value) and the ambient temperature at which power off is to occur (the process fl uid minimum desired temperature value). To change the present control band value, press the UP or DOWN arrow key until the proper value is displayed. CONTROL BAND=5 F NEW VALUE=70 F Press the ENTER key to accept the new value. Note that with these settings, full power to the heaters will occur at -20 F and power will turn off at 50 F. The TC 1818a will then return to the Scan Mode operation. RETURN TO SCAN MODE SCANNING DATA (DISPLAY MODE) When in the SCAN mode of operation, the TC 1818a will display the following screen on all ambient sensed control circuits in a single RTD controller confi guration. Circuit 1 Ambient Sensing RTD CKT 3 TEMP= -20 F HEATER POWER=100% AMB or Circuit 1and 2 Ambient Sensing RTD's CKT 3 TEMP= -20 F, -19 F HEATER POWER=100% AMB The TC 1818a thus indicates the RTD input temperature which represents the ambient temperature values measured on Circuit 1 (and Circuit 2 if confi gured) and is additionally indicating the power level that this particular circuit is operating at. 59

60 TC 1818a Control Module PROGRAMMING AND OPERATING THE TC 1818a WITH DUAL INPUT RTDS FOR A SINGLE CONTROL CIRCUIT The TC 1818a control module may be factory or fi eld confi gured to allow for using single or dual RTD inputs on either ambient sensing or process sensing applications. The following three controller confi guration options are available for this purpose: Controller Configuration 1or 2 RTD INPUTS 1AMB/ 1 or 2 RTD INPUTS Application Process sensing applications Process sensing applications and single ambient sensor in fi rst circuit 2 AMB/ 1 or 2 RTD INPUTS Process sensing applications and ambient sensors in fi rst and second circuit The above factory confi guration options are specifi cally designed for controlling a heat tracing circuit with either single or dual RTD input sensor control circuits. When setting up circuit assignments for these factory confi guration types, the heat tracing circuits that are to be set up with dual RTD's will always be assigned in pairs. That is, the RTD's on Circuit 1 and 2, Circuit 3 and 4, Circuit 5 and 6, and so on should be considered as paired circuits. As one example, when dealing with dual RTD's with process sensing, if Circuit 6 were to be programmed for a dual RTD input control the TC 1818a controller would use the RTD's in Circuit 5 and 6 in controlling the power relay for Circuit 6. The relay associated with Circuit 5 could be disabled or could be used to control a second pass of heater if Circuit 5 were also confi gured as a dual RTD process sensing input (using RTD 5 and RTD 6 for control). 60

61 Operating Guide As another example, in a "1 AMB/ 1 or 2 RTD INPUTS" controller confi guration, if Circuit 6 were to be programmed for a dual RTD input control it would again use the RTD's in Circuit 5 and 6 in controlling the power relay for Circuit 6. In this case, however, the relay on Circuit 5 could additionally be used as a control power relay on an ambient sensed circuit operating based on the RTD input from Circuit 1. The specifi c control strategy for a dual RTD control circuit in any of these factory confi guration types is as follows: The heat tracing circuit controls off of the lowest RTD reading except in the event that a temperature value on either RTD falls within the alarm dead band of the high temperature alarm value. In this event, that RTD will become the controlling temperature reading. The heat tracing circuit will go into low or high alarm if either RTD reading in the pair exceeds the programmed low or high alarm limit value. For more details on setting up a mixed single and dual RTD control mode, refer to Examples 5 and 6. 61

62 TC 1818a Control Module TYPICAL CONTROL APPLICATIONS EXAMPLE 1 - AMBIENT SENSING FREEZE PROTECTION - PROPORTIONAL CONTROL WITH SOLID STATE RELAY OUTPUT When confi gured with solid state relays, the TC 1818a may be used in ambient sensing wide band proportional control. This method of control is ideal in tracing designs where simple ambient sensing RTD's and freeze protection is required. In this mode of control, the TC 1818a will (by cycle omission techniques) proportionally increase the power to the heat tracing as the ambient temperature drops. A typical application for this type of control might be the freeze protection of water lines in a water treatment facility. Assume the following heat tracing operating design Heat Tracing Type: Self-Regulating Parallel Heater Cable Safety Factor: 30% Minimum Ambient: -20 F Minimum Water Maintain Temp: 40 F A typical list of the key TC 1818a settings is as given below: Control Parameter Setting Controller Confi guration 1 AMB/ SINGLE RTD INPUTS Control Method Proportional Maintain Temperature* -20 F Percent Power at Maintain Temp. 100% Control Band 60 F * Note that the maintain temperature is the temperature where 100% power is supplied to the heater. Having set in these values along with appropriate alarm settings, the following control can typically be achieved. Pipe Temperature Power 100% Pipe 20% Power % -20 Ambient Temperature (degf) 40 62

63 Operating Guide EXAMPLE 2 - FOUNDATION HEAVE PROTECTION - PROPORTIONAL WTH SELF-ADJUST CONTROL WITH SOLID STATE RELAY OUTPUT Cryogenic vessels and refrigerated rooms often utilize heating systems beneath to prevent heaving due to the freezing of the soil/foundation base structure. A typical heat tracing application of this type might require an operating tracing design as follows: Internal Room Temperature: -27 F Minimum Maintain Temperature of Soil: 40 F Maximum Foundation Temperature: 80 F Heater Cable Type: Constant Wattage Design Safety Margin: 42% The TC 1818a control module using foundation temperature sensing RTD's in each heating zone can be typically set at the control settings given below: Control Parameter Setting Controller Confi guration SINGLE RTD INPUTS Control Method Proportional with Self-Adjust Maintain Temperature 50 F Control Band 30 F High Alarm Temperature 90 F High Temperature Trip On Low Alarm Temperature 38 F 63

64 TC 1818a Control Module These settings assume the system was designed with a 42% safety margin. By clamping the power to the 70% value, the heater output should match the heat load. The heater should be continually operating using cycle omission techniques in a warming mode (and will thus minimize condensation within the heating system). After attaining 50 F, the TC 1818a will linearly reduce power (the minimum level of power is 20% after 9 F rise) until an equilibrium value between 50 F and 80 F is obtained. In the unlikely event that the 80 F setting is exceeded, the control will de-energize the heater circuit. A high temperature alarm will activate should the RTD sensor detect a temperature above the 90 F value and the circuit will trip. Having set in these values as well as the appropriate other limit/control values, the following typical control can be achieved. Power 100% 70% Typical Controlled Soil Temperature 20% 0% Soil Temperature (degf) 80 64

65 Operating Guide EXAMPLE 3 - PROCESS TEMPERATURE MAINTENANCE - PROPORTIONAL CONTROL WITH SOLID STATE RELAY OUTPUT The TC 1818a features the option of proportional control for those applications where close temperature control is required on process piping which may have varying process temperature conditions. A typical heat traced piping application might be a corn syrup viscosity control application. Due to the sensitivity of the syrup to color degradation the syrup must be maintained below 90 F. Typical heat tracing design requirements are listed as follows: Syrup Maintain Temperature: 80 F Heater Cable Type: Constant Wattage Maximum Syrup Temperature: 90 F The TC 1818a control module utilizing pipe sensing RTD's could be typically set as shown below: Control Parameter Setting Controller Confi guration SINGLE RTD INPUTS Control Method Proportional Maintain Temperature 80 F Control Band 10 F High Alarm Temperature 90 F High Temperature Trip On Low Alarm Temperature 75 F Power at Maintain Temperature 100% Having set in these values as well as the appropriate other limit/control values, the following typical control can be achieved. Power 100% Pipe Control Point 20% 0% Controlband Pipe Temperature (degf) 90 65

66 TC 1818a Control Module EXAMPLE 4 - PROCESS TEMPERATURE CONTROL - MECHANICAL RELAYS Extremely versatile, the TC 1818a can be confi gured with RM-1 or RM-2 mechanical relay output options. This option is often selected in high heat output tracing applications where either high current or high voltage switching is required. One such tracing application might be the temperature maintenance of a long sulfur transfer line. Typical tracing design requirements are listed as follows: Heater Cable Type: Mineral Insulated Series Cable Voltage Switched: 277 Vac Current Switched: 49A Sulfur Maintenance Temperature: 282 F Sulfur Freeze Point: 260 F Sulfur Congeal Point: 320 F The TC 1818a control module with pipe sensing RTD's could be typically as shown below: Control Parameter Setting Controller Confi guration SINGLE RTD INPUTS Control Method On/Off Maintain Temperature 282 F Control Band 5 F High Alarm Temperature 300 F Low Alarm Temperature 260 F Having set in these values as well as the appropriate other limit/control values, the following typical control can be achieved. Pipe Temperature (degf) Time 66

67 Operating Guide EXAMPLE 5 - PROCESS TEMPERATURE CONTROL - SINGLE AND DUAL RTD SENSING It is sometimes considered advantageous to use dual RTD sensors on a critical heat tracing application such as a 50% caustic line. In this way, the power to the heater can be based on the input of two discrete temperature inputs rather than one. In addition, in the event of an RTD fault, the operator can be alarmed, the circuit can be acknowledged, and the RTD can be repaired without turning the heat tracing circuit OFF. For this application, the typical design requirements are as listed below: Product Maintenance Temperature: 80 F Product Freeze Point: 54 F Heater Cable Type: Self Regulating Parallel Cable Maximum Caustic Temperature: 100 F The TC 1818a control module utilizing pipe sensing RTD's could be typically set as indicated below: Control Parameter Setting Controller Confi guration 1 or 2 RTD INPUTS Control Method Proportional Maintain Temperature 80 F Control Band 5 F High Alarm Temperature 90 F High Temperature Trip ON Low Alarm Temperature 60 F Power at Maintain Temperature 100% 67

68 TC 1818a Control Module Considering that we have only three heat tracing circuits, the TC 1818a would be set up as a six point unit with a controller confi guration of "1 or 2 RTD INPUTS". The heat tracing circuit assignments would be as follows: Circuit No. Setting 1 Enabled (2 RTD) 2 Disabled 3 Enabled (2 RTD) 4 Disabled 5 Enabled (2 RTD) 6 Disabled In this case power relays on circuits 2, 4 and 6 will not be connected to the heat tracing. Alternately, in a case where both power relays were to be used to maximize the current switching capability, the following circuit assignments could also be used. Circuit No. Setting 1 Enabled (2 RTD) 2 Enabled (2 RTD) 3 Enabled (2 RTD) 4 Enabled (2 RTD) 5 Enabled (2 RTD) 6 Enabled (2 RTD) In this circuit assignment, all circuit relays are controlling off of dual RTD inputs. Note that this confi guration is also applicable in center feed arrangements for two heat tracing circuits running in opposite directions from power. 68

69 Operating Guide EXAMPLE 6 - PROCESS TEMPERATURE AND AMBIENT SENSING CONTROL - SINGLE AND DUAL RTD SENSING In many applications there are a variety of control applications. Some may be the critical applications such as the 50% caustic in Example 5 and some may be simple water freeze protection. For this combination application, the typical design requirements are as listed below: 50% Caustic Product Maintenance Temperature: 80 F Product Freeze Point: 54 F Heater Cable Type: Self Regulating Parallel Cable Maximum Caustic Temperature: 100 F Number of Circuits: Two Process Sensing Water Product Maintenance Temperature: 50 F Product Freeze Point: 32 F Heater Cable Type: Self Regulating Parallel Cable Number of Circuits: Four Ambient Sensing The TC 1818a control module utilizing pipe sensing RTD's could be typically set as indicated below: Control Parameter Setting Controller Confi guration 1 AMB/ 1 or 2 RTD INPUTS Control Method On-Off Caustic Circuits Maintain Temperature 80 F Control Band 5 F High Alarm Temperature 90 F High Temperature Trip ON Low Alarm Temperature 60 F Water Circuits Maintain Temperature 50 F Control Band 5 F High Alarm Temperature 120 F High Temperature Trip Off Low Alarm Temperature 40 F Considering that we have only six heat tracing circuits, the TC 1818a would be set up as a six point unit with a controller confi guration of "1 AMB/ 1 or 2 RTD INPUTS". 69

70 TC 1818a Control Module The heat tracing circuit assignments would be as follows: Circuit No. Setting 1 Enabled (Ambient Sensed) 2 Enabled (Ambient Sensed) 3 Enabled (2 RTD) 4 Enabled (Ambient Sensed) 5 Enabled (2 RTD) 6 Enabled (Ambient Sensed) In this case, power relays on circuits 1, 2, 4 and 6 will be controlling ambient sensed circuits based on the RTD input on Circuit 1. Circuit 3 and its power relay will be controlling based on the RTD inputs from Circuit 3 and Circuit 4. Circuit 5 and its power relay will be controlling based on the RTD inputs from Circuit 5 and Circuit 6. 70

71 Operating Guide COMMUNICATIONS The TC 1818a is standardly provided with an RS485 communications port. This port allows for communication through a Modbus ASCII and RTU protocols to a PC workstation or to the facility distributed control system (DCS). Through this communications link, most of the operating parameters which are programmable at the module can be accessible at the central PC workstation or DCS system console. For communications linking between the TC 1818a and a PC workstation, refer to the TraceView TM Network Explorer Operating Guide. For communications linking information between the TC 1818a and the facility distributed control system (DCS), refer to DCS Operations Guide, SWM-008.X. 71

72 TC 1818a Control Module OPTIONS AND ACCESSORIES Thermon can provide a variety of options and accessories to complete the installation. Some typical accessories are listed below. SW-TVNE TraceViewTM Network Explorer is a PC-based communications software package developed specifi cally for centralized control and monitoring of the various fi eld mounted HeatChekTM units. TraceView Network Explorer, operating within the Windows environment, allows the changing of control and alarm setpoints, adjustment of controller operating parameters, and acknowledgement of all alarms from the control room or motor control center. TraceView Network Explorer permits the viewing of heat tracing isometrics on demand and allows online access to heat tracing and controller diagnostic information. Continuous data logging and reporting of heat tracing operations/alarm status as well as historical trend data storage (for later retrieval to spreadsheet or database software) is also provided. TraceView Network Explorer can be confi gured for up to sixteen communication ports (with each program instance allowing up to 247 HeatChek control and monitoring units 1 ). Communications can be achieved at distances up to 4000 ft. (1220 m) on the RS485 two wire twisted shielded communication link. RTD-100 This three wire resistance temperature detector (RTD) is rated to 500 F (260 C). Provided with a standard aluminum termination head, the RTD sensor is insulated with fi berglass and shielded with Type 316 stainless steel housing. IM-1 Interface module for linking RS485 two-wire twisted shielded pair into RS232 port of PC. DCALXX Interposing DC alarm relays can be added for use in ordinary and hazardous locations to interface to plant DCS systems. 1 A minimum of one repeater module is recommended for every thirty-one control and monitoring modules confi gured into a data highway. 72

73 Operating Guide HELP This HeatChek control and monitoring unit is intended to be used with only the support of this instruction booklet. If special support needs do arise, Thermon provides local support through its area representatives and affi liate companies as well as through a toll free user support line. For toll free support dial HEAT(4328). Information may also be obtained by accessing the Thermon Website at 73

74 TC 1818a Control Module ATTACHMENT A: TC 1818A COMMAND FLOWCHART Note: Security key must be in the vertical position for the TC 1818 to allow programming. MAINTAIN TEMPERATURE PROGRAM NEW PROG MAINTAIN TEMP ENTER ENTER CIRCUIT VALU E CONTROL BAND PROGRAM NEW PROG CONTROL BAND ENTER ENTER CIRCUIT VALUE HIGH TEMPERATURE ALARM PROGRAM NEW RESET HIGH PROG HIGH TEMP ALARM ENTER ENTER ENTER CIRCUIT VALUE TEMP SEEN LOW TEMPERATURE ALARM PROGRAM NEW RESET LOW PROG LOW TEMP ALARM ENTER ENTER ENTER CIRCUIT VALUE TEMP SEEN HIGH CURRENT ALARM PROGRAM NEW PROG HIGH CURRENT ALARM ENTER ENTER CIRCUIT LOW CURRENT ALARM PROGRAM VALU E NEW PROG LOW CURRENT ALARM ENTER ENTER CIRCUIT VALU E 74

75 Operating Guide ATTACHMENT A: TC 1818A COMMAND FLOWCHART Note: Security key must be in the vertical position for the TC 1818 to allow programming. GROUND CURRENT ALARM PROGRAM NEW PROG GROUND CURRENT ENTER ENTER CIRCUIT VALU E DATA HIGHWAY PROGRAM NEW PROG DATA HWY ENTER ENTER CIRCUIT VALU E CIRCUIT # ENABLE (PIPE SENSE) CIRCUIT # ENABLE (AMBIENT SENSE) HEATER ENABLE/DISABLE CIRCUIT # DISABLE PROG HEATER ENABLE PROGRAM CIRCUIT CHANGE? YES NO ENTER FORCE HEATER ON YES NO CIRCUIT FORCED ON CIRCUIT ENABLED/DISABLED ALARM ACKNOWLEGE ALARM ACK CIRCUIT # REPORTED FAULT ALARM ACK CIRCUIT # REPORTED FAULT ACK REPORTED FAULT HAS BEEN ACKNOWLEDGED 75

76 THERMON... The Heat Tracing Specialists 100 Thermon Dr. P.O. Box 609 San Marcos, TX Phone: (512) Facsimile: (512) HEAT Part Number: 80505

TC 202a Control Module

TC 202a Control Module TC 202a Control Module Operating Guide SWM-004.7 This guide is intended solely for use by owners of Thermon HeatChek TM heat tracing control and monitoring units. This manual is considered proprietary

More information

920 Series. Dual-point heat-tracing control system. Product overview. 920*E4FWL*SIS302*SS3102 shown

920 Series. Dual-point heat-tracing control system. Product overview. 920*E4FWL*SIS302*SS3102 shown Self-Regulating 920 Series Dual-point heat-tracing control system Power-Limiting Mineral Insulated 920*E4FWL*SIS302*SS3102 shown Product overview The DigiTrace 920 is a compact, full-featured, microprocessor-based,

More information

Product overview. 2000 mm. 100 mm

Product overview. 2000 mm. 100 mm Panel mounted electronic multi-circuit heat-tracing control, monitoring and power distribution system Product overview CABLE DUCT Card Rack Modules TERMINAL STRIP PLINTH MAIN SWITCH 800 mm USER INTERFACE

More information

Advanced Heat-Tracing Control System

Advanced Heat-Tracing Control System Advanced Heat-Tracing Control System Product Overview Heat-tracing system NGC-30 system Remote configuration and monitoring with Raychem Supervisor software The Raychem NGC-30 is a multi-circuit electronic

More information

Controller Automation, Model II+

Controller Automation, Model II+ Controller Automation Page 2 of 2 Automation with the RADAK II+ power controller II+ I/O Points: Inputs 5 Programmable Digital inputs 2 Dedicated digital inputs (Channel select and External SCR control

More information

THERMAL MANAGEMENT SOLUTIONS

THERMAL MANAGEMENT SOLUTIONS t2000 Series Electronic heat-tracing controller Product Overview /COMMUNICATIONS INTERACE CARRIER REQ TO SEND The DigiTrace heat trace controller is designed to provide the benefits associated with single

More information

Input signal Maximum Range Accuracy. Thermocouple E -50 to 700 C (-58 to 1832 F) ±1 C

Input signal Maximum Range Accuracy. Thermocouple E -50 to 700 C (-58 to 1832 F) ±1 C F4 Process Controller Installation and Operation Guide SAFETY ALERTS The symbols below are used on the equipment and throughout this document to draw the user s attention to important operational and safety

More information

ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL

ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL RANCO INSTALLATION INSTRUCTIONS ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL Relay Electrical Ratings PRODUCT DESCRIPTION The Ranco ETC is a microprocessor-based family of electronic temperature controls,

More information

TC-9102 Series Surface Mount Temperature Controllers

TC-9102 Series Surface Mount Temperature Controllers TC-9102 Series Surface Mount Temperature Controllers General Description & Applications The TC-9102 Series Temperature Controller offers a versatile solution for a wide variety of applications that may

More information

Electronic Control Devices The European Product Catalogue 2007

Electronic Control Devices The European Product Catalogue 2007 FX07 Field Controller (1/4) FX07 Field Controller Display Model Dimensions in mm (inches) The FX07 is a terminal unit controller in the Facility Explorer range of products. The controller is designed specifically

More information

RISH CON - Hz. Salient Features : Application : Product Features: FREQUENCY TRANSDUCER

RISH CON - Hz. Salient Features : Application : Product Features: FREQUENCY TRANSDUCER Application : The RISH CON - Hz transducer is used for frequency measurement. The output signal is proportional to measured frequency and is either load independent DC Current or load independent DC Voltage.

More information

NELSON VOLTAGE MONITOR INSTALLATION & PROGRAMMING MANUAL

NELSON VOLTAGE MONITOR INSTALLATION & PROGRAMMING MANUAL NELSON VOLTAGE MONITOR INSTALLATION & PROGRAMMING MANUAL CONTENTS GENERAL INFORMATION...3 INSTALLATION...3 FIELD WIRING...4 PROGRAMMING...4 Circuit Monitor Options...5 Power Frequency...5 Alarm Silence

More information

Auto-tune PID. Temperature Controller BRAINCHILD FEATURES

Auto-tune PID. Temperature Controller BRAINCHILD FEATURES Auto-tune PID Temperature Controller FEATURES Easy-to-use Fuzzy modified PID heat & cool control Fast A-D sampling rate (5 times/s) Universal input (PT100, thermocouple) with high accuracy 18-bit A-D Analog

More information

TURBOtech srl. SED-635 Digital Excitation System. Industrial Electronics Sector FEATURES

TURBOtech srl. SED-635 Digital Excitation System. Industrial Electronics Sector FEATURES SED-635 Digital Excitation System SED-635 is a complete excitation system capable of adapting to control synchronous generators of any size. The integration of the TOUCH SCREEN operator interface and a

More information

Operational Overview and Controls Guide

Operational Overview and Controls Guide DOCUMENT: ECSEQ2-1 EFFECTIVE: 02/14/07 SUPERSEDES: 02/26/03 Operational Overview and Controls Guide Standard Two or Three Pump Type VFD Booster Controls 6700 Best Friend Road. Norcross, GA 30071. (770)

More information

O C M III. Open Channel Flow Monitor

O C M III. Open Channel Flow Monitor O C M III Open Channel Flow Monitor Part 1. General 1.1 Scope A. This section describes the requirements for an ultrasonic flow transmitter with sensor and temperature compensation probe. B. Under this

More information

User Manual. Humidity-Temperature Chart Recorder. Model RH520

User Manual. Humidity-Temperature Chart Recorder. Model RH520 User Manual Humidity-Temperature Chart Recorder Model RH520 Introduction Congratulations on your purchase of the Extech RH520 Temperature + Humidity Chart Recorder. The RH520 measures and displays Temperature,

More information

Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000

Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000 Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000 Description Firetrol FTA1000 Full Voltage Fire Pump Controllers are intended for use with electric motor driven fi re pumps

More information

Application/Connection Examples

Application/Connection Examples This Quick Start Guide is designed to familiarize the user with the connection and configuration of the DTS-305 DIN rail mounted single / 3 phase power & energy meter with RS-485 or TCP communications.

More information

Ground Resistance Clamp On Tester

Ground Resistance Clamp On Tester USER MANUAL Ground Resistance Clamp On Tester MODEL 382357 Introduction Congratulations on your purchase of Extech s 382357 Ground Resistance Tester. This Clamp on device allows the user to measure ground

More information

Installation & Operation Manual ISC-Intellitrace Supervisory Controller

Installation & Operation Manual ISC-Intellitrace Supervisory Controller Installation & Operation Manual ISC-Intellitrace Supervisory Controller 1 PK513 0037-75533 July 2014 Table of Contents Section Page Important Information... 3 License Agreement... 3 Safety Precautions...

More information

Zlinx Wireless I/O. Peer-to-Peer and Modbus I/O B&B ELECTRONICS PRODUCT INFORMATION

Zlinx Wireless I/O. Peer-to-Peer and Modbus I/O B&B ELECTRONICS PRODUCT INFORMATION Modular, Customizable Wire Replacement 128 / 256 Bit AES Encryption Software Selectable RF Transmit Power Software Selectable Over-the-air Data Rate Modbus ASCII /RTU Compatible Wide Operating Temperature

More information

ACS-30-EU-EMDR-10-MOD

ACS-30-EU-EMDR-10-MOD Multi-application heat tracing Control and Monitoring in commercial and residential buildings Roof & Gutter de-icing sensor module Technical Information Approvals Module IP rating Ambient operating temperature

More information

Operational Overview and Controls Guide. Two or Three Pump IronHeart Lite with Variable Frequency Drives

Operational Overview and Controls Guide. Two or Three Pump IronHeart Lite with Variable Frequency Drives DOCUMENT: ECSEQ6-0 EFFECTIVE: 09/23/10 SUPERSEDES: Operational Overview and Controls Guide Two or Three Pump IronHeart Lite with Variable Frequency Drives 6700 Best Friend Road. Norcross, GA 30071. (770)

More information

TrueAlarm Fire Alarm Systems

TrueAlarm Fire Alarm Systems TrueAlarm Systems UL, ULC, CSFM Listed; FM Approved* Network Annunciators; es Features Provides a dedicated local area network (LAN) for connection of a TrueSite workstation server to remote clients: es

More information

2. Terminal arrangement. Default (PV display) (SV display) Communication protocol selection Selects the Communication protocol. Modbus ASCII mode:

2. Terminal arrangement. Default (PV display) (SV display) Communication protocol selection Selects the Communication protocol. Modbus ASCII mode: COMMUNICATION INSTRUCTION MANUAL TEMPERATURE CONTROLLER KT4, KT8 and KT9 No.KTC1E6 2009.05 To prevent accidents arising from the misuse of this controller, please ensure the operator receives this manual.

More information

TEMON 8-C. Doc. N MO-0370-ING TEMPERATURE MONITOR DEVICE TYPE TEMON 8-C OPERATION MANUAL. Microener - Copyright 2010 FW 2.2 Date 01.12.2008 Rev.

TEMON 8-C. Doc. N MO-0370-ING TEMPERATURE MONITOR DEVICE TYPE TEMON 8-C OPERATION MANUAL. Microener - Copyright 2010 FW 2.2 Date 01.12.2008 Rev. TEMPERATURE MONITOR DEVICE TYPE TEMON 8-C OPERATION MANUAL Microener - Copyright 2010 FW 2.2 Date 01.12.2008 Rev. 0 1. Generality 3 2. Introduction 3 3. Accessories and Options 3 4. Installation 3 5. Connection

More information

T7560A,B,C Digital Wall Module

T7560A,B,C Digital Wall Module T7560A,B,C Digital Wall Module HONEYWELL EXCEL 5000 OPEN SYSTEM BEFORE INSTALLATION All wiring must comply with local electrical codes and ordinances or as specified on installation wiring diagrams. Digital

More information

TABLE 1: Wiring Terminals. Connect to... 1C 1H 2C 2H 1H1C 2H1C 2H2C 3H2C

TABLE 1: Wiring Terminals. Connect to... 1C 1H 2C 2H 1H1C 2H1C 2H2C 3H2C Installation TURN OFF POWER TO THE SYSTEM AT THE MAIN POWER PANEL TO AVOID ELECTRICAL SHOCK. Installation should be carried out by an electrician or a qualified technician. 1.1 Find a Location for the

More information

INSTALLATION/PROGRAMMING INSTRUCTIONS E4KP ENTRYCHECK

INSTALLATION/PROGRAMMING INSTRUCTIONS E4KP ENTRYCHECK Security Door Controls 3580 Willow Lane, Westlake Village, CA 91361-4921 (805) 494-0622 Fax: (805) 494-8861 www.sdcsecurity.com E-mail: [email protected] INSTALLATION/PROGRAMMING INSTRUCTIONS E4KP

More information

Process Alarm Solutions

Process Alarm Solutions Process Alarm Solutions Reliable Supervision and Control www.selco.com SELCO flexible alarm panels for supervision and control SELCO provides efficient and reliable solutions for alarm monitoring of electrical

More information

DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS

DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS Features: INSTALLATION Install in accordance with NFPA 70. DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS Up to 1.95 Amps Load Capacity Class 2 Rated Outputs Overload, Over Voltage, and Short

More information

SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS

SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS TABLE OF CONTENTS 1. Warnings...2 2. Accessibility Of Appliance...3 3. Unit Dimensions And Specifications...3 4. Unit Specifications

More information

DREXELBROOK. USonic-R Series. Ultrasonic Level Measurement System. User Friendly

DREXELBROOK. USonic-R Series. Ultrasonic Level Measurement System. User Friendly DREXELBROOK A Leader In Level Measurement Solutions USonic-R Series Ultrasonic Level Measurement System User Friendly Set the measurement range directly in inches, feet, millimeters, centimeters, or meters

More information

Flow Monitoring System

Flow Monitoring System FMS-3 Product Data Sheet PS-00028 April 1997 Flow Monitoring System FMS-3 Flow Monitoring System The Micro Motion FMS-3 Flow Monitoring System is a microprocessor-based batch controller with rate, total,

More information

9452/9453 Installation and User Guide

9452/9453 Installation and User Guide 9452/9453 Installation and User Guide Compatible Equipment 9425 Remote Keypad 9040 Internal Sounder 660 Speech Communicator 8440 4-Channel Minicom 496330 Issue 1 1 of 10 9452/3 Introduction The 9452 and

More information

MAKING MODERN LIVING POSSIBLE. AK-SC255 On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS

MAKING MODERN LIVING POSSIBLE. AK-SC255 On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS MAKING MODERN LIVING POSSIBLE AK-SC255 On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS How to Use This Guide Read this Guide completely as you install and start up your new AK-SC 255 controller.

More information

NX Series Inverters. HVAC Pocket Programming Guide

NX Series Inverters. HVAC Pocket Programming Guide NX Series Inverters HVAC Pocket Programming Guide HVAC Pocket Programming Guide HVAC Pocket Programming Guide / Contents This guide provides a single reference document for the user of NXL HVAC (product

More information

Firmware version: 1.10 Issue: 7 AUTODIALER GD30.2. Instruction Manual

Firmware version: 1.10 Issue: 7 AUTODIALER GD30.2. Instruction Manual Firmware version: 1.10 Issue: 7 AUTODIALER GD30.2 Instruction Manual Firmware version: 2.0.1 Issue: 0.6 Version of the GPRS transmitters configurator: 1.3.6.3 Date of issue: 07.03.2012 TABLE OF CONTENTS

More information

OVR Three-Phase Recloser and PCD Control Style Guide 1VAL264001-SG October 13, 2009 Revision F

OVR Three-Phase Recloser and PCD Control Style Guide 1VAL264001-SG October 13, 2009 Revision F OVR Three-Phase Recloser and PCD Control Style Guide 1VAL264001-SG October 13, 2009 Revision F The OVR three-phase recloser style guide aids in the proper selection of your OVR three-phase style number.

More information

Model 5511 Filler Controller User s Manual Version 1.1 October 2011

Model 5511 Filler Controller User s Manual Version 1.1 October 2011 Thompson Scale Company WEIGHING SYSTEMS & PACKAGING MACHINERY CONTROLS 2758 Bingle Road Houston, Texas 77055 Phone: 713/932-9071 Fax: 713/932-9379 www.thompsonscale.com Model 5511 Filler Controller User

More information

RMM2 Heat-Tracing Remote Monitoring Module for the Raychem NGC Control System Installation Instructions

RMM2 Heat-Tracing Remote Monitoring Module for the Raychem NGC Control System Installation Instructions Heat-Tracing Remote Monitoring Module for the NGC Control System Installation Instructions Tools Required 3 mm slotted screwdriver 3/8 hex key (for -4X only) Approvals Nonhazardous locations Type NM LISTED

More information

3500/22M Transient Data Interface

3500/22M Transient Data Interface 3500/22M Transient Data Interface Bently Nevada* Asset Condition Monitoring Description The 3500 Transient Data Interface (TDI) is the interface between the 3500 monitoring system and GE s System 1* machinery

More information

TAC I/NETTM MR-VAV-AX. Application Specific MicroRegulator TM

TAC I/NETTM MR-VAV-AX. Application Specific MicroRegulator TM TAC I/NETTM TM TAC s TM has an extensive range ofpre-engineered VAV control sequences, which combined with a fully integrated actuator and airflow transducer, makes it a low Total Installed Cost solution

More information

www.sebury.com.cn Digital Keypad Use s Manual

www.sebury.com.cn Digital Keypad Use s Manual K3 K4 www.sebury.com.cn Digital Keypad Use s Manual Contents Introduction Introduction Specifications Intramural Interface Circuit 3 Mounting 3 Wiring 5 Power UP 7 Engineer Programming Mode 7 The K3/K4

More information

Regards from the Team at Rheology Solutions.

Regards from the Team at Rheology Solutions. Rheology Solutions is the sole Australian distributor of this product range and we welcome the opportunity of discussing your application requirements. We hope the information you are seeking is contained

More information

WATER LEAK DETECTION SYSTEM WLDS-10 INSTALLATION & COMMISSIONING

WATER LEAK DETECTION SYSTEM WLDS-10 INSTALLATION & COMMISSIONING WATER LEAK DETECTION SYSTEM WLDS-10 INSTALLATION & COMMISSIONING DESCRIPTION: An electronic control panel used in conjunction with one pulse meter (water meter with pulse output proportional to flow rate)

More information

RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features:

RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features: Application : RISH Master 3490 DS measures important electrical parameters of Utility (in normal mode) & Generators (in Power back up) in three phase and single phase Network & replaces the multiple analog

More information

SM6 Series Circuit Breaker Monitors CONSOLIDATED. Electronics, Inc. MONITORING THE FUTURE

SM6 Series Circuit Breaker Monitors CONSOLIDATED. Electronics, Inc. MONITORING THE FUTURE Series Circuit Breaker Monitors CONSOLIDATED Electronics, Inc. MONITORING THE FUTURE Why SF Gas Density Monitors? 6 Cut Maintenance Costs Your capital investment may be recovered with the elimination of

More information

Technical Information POWER PLANT CONTROLLER

Technical Information POWER PLANT CONTROLLER Technical Information POWER PLANT CONTROLLER Content The Power Plant Controller offers intelligent and flexible solutions for the control of all PV power plants in the megawatt range. It is suitable for

More information

User and installation manual

User and installation manual User and installation manual aquaero 5 The information contained in this manual is subject to change without prior notice. All rights reserved. Current as of April 2011 ENGLISH: PAGE 1 DEUTSCH: SEITE 13

More information

Product Description Digital Solid State Starting Electric Fire Pump Controllers FTA1930

Product Description Digital Solid State Starting Electric Fire Pump Controllers FTA1930 Product Description Digital Solid State Starting Electric Fire Pump Controllers FTA1930 Description Firetrol FTA1930 Digital Solid State Starting Fire Pump Controllers feature soft start, soft stop and

More information

SFC-200 SERIES FIRE ALARM CONTROL PANELS. SFC-200 Series Fire Alarm Control Panels. Features. Description

SFC-200 SERIES FIRE ALARM CONTROL PANELS. SFC-200 Series Fire Alarm Control Panels. Features. Description SFC-200 SERIES FIRE ALARM CONTROL PANELS SFC-200 Series Fire Alarm Control Panels Description Summit s SFC-200 Series fire alarm control panels consist of six and twelve zone models which are equipped

More information

FLOW CALCULATOR INSTRUCTION MANUAL MESURES BAMOPHOX 759 26-06-2007 759 M1 02 E MES FLOW CALCULATOR 759-02/1

FLOW CALCULATOR INSTRUCTION MANUAL MESURES BAMOPHOX 759 26-06-2007 759 M1 02 E MES FLOW CALCULATOR 759-02/1 BAMOPHOX 759 E - M FLOW CALCULATOR INSTRUCTION MANUAL MESURES 22, Rue de la Voie des Bans - Z.I. de la Gare - 95100 ARGENTEUIL Tél : (33) 01 30 25 83 20 - Web : www.bamo.fr Fax : (33) 01 34 10 16 05 -

More information

Model: DC-A2IO Advanced HVAC Controller

Model: DC-A2IO Advanced HVAC Controller Model: DC-A2IO Advanced HVAC Controller Job Name: Schedule Reference: Date: DC-A2IO Advanced HVAC Controller Package PAC-IF01 M-Net Adapter AL2-14MR-D α2 Simple Application Controller Accessories AL2-2DA

More information

NEWTECH PRO 1-2-3 KVA ONLINE UNINTERRUPTIBLE POWER SUPPLY USER MANUAL

NEWTECH PRO 1-2-3 KVA ONLINE UNINTERRUPTIBLE POWER SUPPLY USER MANUAL NEWTECH PRO 1-2-3 KVA ONLINE UNINTERRUPTIBLE POWER SUPPLY USER MANUAL [email protected] / www.tuncmatik.com Table of Contents 1. Important Safety Warning 2 1-1. Transportation 2 1-2. Preparation 2 1-3.

More information

Uninterruptible Power Supply

Uninterruptible Power Supply 96-01101 / rev. 2e / 2-2-12 Uninterruptible Power Supply EXCEPTIONAL SUPPORT & PROTECTION Uninterruptible Power Supply with Energy Saver design that is optimized to address the needs of A/V systems Features

More information

Contents. Introduction

Contents. Introduction TION Contents Introduction...1 Basics...2 Main Menu Structure...3 Time Schedule Menu...4 Settings Menu...5 Reports Menu...6 Date / Time Adjustment Menu...7 Introduction TION is an advanced control device

More information

VLT 6000 HVAC. Contents

VLT 6000 HVAC. Contents Contents Introduction Safety...3 Safety Guidelines...3 Warnings Against Unintended Start...3 Introduction...4 About this manual...4 Assumptions...4 References...4 Trademarks...5 Programming the VLT 6000

More information

MLC 9000+ TM Maximum Productivity and Versatility for Control without Compromise!

MLC 9000+ TM Maximum Productivity and Versatility for Control without Compromise! Data Sheet Maximum Productivity and Versatility for Control without Compromise! Basic Bus Communication Module DESCRIPTION The Basic Bus Communication Module (BCM) is part of the MLC 9000+ DIN rail mount

More information

User Guide. Heavy Duty Dissolved Oxygen Meter. Model 407510

User Guide. Heavy Duty Dissolved Oxygen Meter. Model 407510 User Guide Heavy Duty Dissolved Oxygen Meter Model 407510 Introduction Congratulations on your purchase of Extech's Heavy Duty Dissolved Oxygen / Temperature Meter which simultaneously displays Dissolved

More information

THYRISTORS T1-1PH from 850A to 2700A Specifications Universal 1 Phase Thyristor Unit 55-77-03-62, March 2012

THYRISTORS T1-1PH from 850A to 2700A Specifications Universal 1 Phase Thyristor Unit 55-77-03-62, March 2012 Technical Information THYRISTORS T1-1PH from 850A to 2700A Specifications Universal 1 Phase Thyristor Unit 55-77-03-62, March 2012 GENERAL DESCRIPTION THYRISTORS T1-1PH is a full digital and universal

More information

713 Open Channel Flowmeter and Transmitter. All-in-one package for open channel flow measurement.

713 Open Channel Flowmeter and Transmitter. All-in-one package for open channel flow measurement. and Transmitter All-in-one package for open channel flow measurement. 3.1 NEW Class 1, Division 1 Approved Sensor As our products are continuously improved, we reserve the right to make any change in the

More information

NC-12 Modbus Application

NC-12 Modbus Application NC-12 Modbus Application NC-12 1 Table of Contents 1 Table of Contents... 2 2 Glossary... 3 SCADA...3 3 NC-12 Modbus in general... 3 4 Entire system... 4 4.1 PFC to PC connection alternatives...4 4.1.1

More information

HEAT HEAT COOL HEAT PUMP COOL

HEAT HEAT COOL HEAT PUMP COOL OWNER S MANUAL RESIDENTIAL THERMOSTAT P/N P374-1800 HEAT COOL HEAT PUMP Su AUTO 0I20: Pm 74 COOL HEAT 27 7-DAY MABLE DIGITAL THERMOSTAT 3 Configurable Outputs Accepts Optional Humidity Module: Control

More information

Panasonic/Sanyo A/C Interface Modbus RTU Installation Instructions

Panasonic/Sanyo A/C Interface Modbus RTU Installation Instructions Panasonic/Sanyo A/C Interface Modbus RTU Installation Instructions Preface Safety warnings To avoid injury, or damage to the Modbus interface, read all installation and configuration instructions in this

More information

Part Number 129777-01 Revision A, January 1996. 3500 Monitoring System Rack Configuration and Utilities Guide

Part Number 129777-01 Revision A, January 1996. 3500 Monitoring System Rack Configuration and Utilities Guide Part Number 129777-01 Revision A, January 1996 3500 Monitoring System Rack Configuration and Utilities Guide Copyright 1995 Bently Nevada Corporation All Rights Reserved. No part of this publication may

More information

Contents. Document information

Contents. Document information User Manual Contents Document information... 2 Introduction... 3 Warnings... 3 Manufacturer... 3 Description... Installation... Configuration... Troubleshooting...11 Technical data...12 Device Scope: PCB

More information

Automation System TROVIS 6400 TROVIS 6493 Compact Controller

Automation System TROVIS 6400 TROVIS 6493 Compact Controller Automation System TROVIS 6400 TROVIS 6493 Compact Controller For panel mounting (front frame 48 x 96 mm/1.89 x 3.78 inch) Application Digital controller to automate industrial and process plants for general

More information

MCR1900 Media Converter 19-Slot Chassis

MCR1900 Media Converter 19-Slot Chassis MCR1900 Media Converter 19-Slot Chassis Installation Guide Part #5500304-11 Copyright Statement This document must not be reproduced in any way whatsoever, either printed or electronically, without the

More information

WEA-Base. User manual for load cell transmitters. UK WEA-Base User manual for load cell transmitters Version 3.2 UK

WEA-Base. User manual for load cell transmitters. UK WEA-Base User manual for load cell transmitters Version 3.2 UK WEA-Base User manual for load cell transmitters 1 Contents 1. Technical data... 3 2. Assembly... 4 2.1 Power supply... 4 2.2 Load cells... 4 2.3 RS-485... 4 2.4 Relays... 5 2.5 Digital input... 5 2.6 Analogue

More information

Instruction book IQAN-MDM. Publ. no. HY17-8328/UK Edition June, 2007

Instruction book IQAN-MDM. Publ. no. HY17-8328/UK Edition June, 2007 Instruction book IQAN-MDM Publ. no. HY17-8328/UK Edition June, 2007 Contents 1 Introduction...............................................................3 Safety symbols................................................................

More information

MTII4200 level Transmitter Installation, Operation & Maintenance Instructions

MTII4200 level Transmitter Installation, Operation & Maintenance Instructions Specialists in Liquid Level Indication MTII4200 level Transmitter Installation, Operation & Maintenance Instructions Section: M500 Bulletin: M500.31 Date: 01-26-12 Supersedes: 04-22-08 1. INTRODUCTION

More information

EQUIPMENT SPECIFICATIONS

EQUIPMENT SPECIFICATIONS EQUIPMENT SPECIFICATIONS IC-1600 Intelligent Controller The IC-1600 Intelligent Controller is a fully intelligent panel that has a complete database on board. It operates in conjunction with the Access

More information

Industrial Control Solutions

Industrial Control Solutions Industrial Control Solutions NGC-30 Advanced Heat-Tracing Control System industrial heat tracing solutions www.pentairthermal.com Raychem ngc-30 Raychem NGC-30 is an advanced electronic multipoint control,

More information

AuCom s IMS2 soft starters are a total motor starting solution, combining highlevel functionality with ease of use:

AuCom s IMS2 soft starters are a total motor starting solution, combining highlevel functionality with ease of use: AuCom s IMS2 soft starters are a total motor starting solution, combining highlevel functionality with ease of use: advanced soft start and soft stop control protection functions that operate even when

More information

How To Control A Power Supply With A Mini Transmitter And Switch (Power Supply)

How To Control A Power Supply With A Mini Transmitter And Switch (Power Supply) transmitter (2 wire) / switch for continuous or On/Off Control Indication, monitoring, transmitting and continuous or On/Off control in one device Output signal 4...20 ma, 2-wire for continuous control

More information

Electronic Control Devices The European Product Catalogue 2007

Electronic Control Devices The European Product Catalogue 2007 FX14 Field Controller (1/4) FX14 Field Controller The FX14 is an equipment field controller in the Facility Explorer range of products. The controller is designed specifically for commercial Heating, Ventilating,

More information

AIS750 Series Alarm Annunciator

AIS750 Series Alarm Annunciator Unparallel, modular, multipoint design with Integrated controllers Two Operation Modes (Stand-alone & Serial) All sizes confi gurable up to 440 Alarm Points RS485 / RS232 Serial Communication Manual &

More information

+ A + + - B V B - - + + + NO NC V COM - - - PV PV

+ A + + - B V B - - + + + NO NC V COM - - - PV PV + - A + B B - V + - NO NC COM + - + - V + - PV PV Ramp Soak 100 70 50 30 3 5 3 8 5 3 Minute Steam Heating Sensor Cooling Water PID Hotplate Specifications Input power supply AC 100 to 240V, 50/60Hz, DC

More information

OPERATING INSTRUCTIONS SECURITY SYSTEM KIT NO.: 08E51-EP4-101. 2004 American Honda Motor Co., Inc. - All Rights Reserved. 1

OPERATING INSTRUCTIONS SECURITY SYSTEM KIT NO.: 08E51-EP4-101. 2004 American Honda Motor Co., Inc. - All Rights Reserved. 1 OPERATING INSTRUCTIONS SECURITY SYSTEM KIT NO.: 8E5-EP4-24 American Honda Motor Co., Inc. - All Rights Reserved. Contents Introduction... 3 Emergency Disarming During Alarming... 4 During the Entry Delay

More information

Temperature & Humidity SMS Alert Controller

Temperature & Humidity SMS Alert Controller Temperature & Humidity Alert Controller METERS 3 simple steps starting the unit: Insert the SIM card Plug in the sensors connectors Connect the AC power cord. Specifications: AC 90~260V Auto Select Internal

More information

Heat Tracing Sales Mt. Airy, Maryland www.heattracingsales.com 410-795-2223. Installation Instructions

Heat Tracing Sales Mt. Airy, Maryland www.heattracingsales.com 410-795-2223. Installation Instructions Chromalox Installation Instructions DIVISION 4 SALES REFERENCE DATE SERVICE REFERENCE SECTION DTS (Supersedes PJ944-5) PJ944-6 161-562581-049 MARCH, 2012 DTS-HAZ For Use With Self-Regulating & Constant

More information

Electric Heat Tracing INSTALLATION PROCEDURES

Electric Heat Tracing INSTALLATION PROCEDURES INSTALLATION PROCEDURES The following installation procedures are suggested guidelines for the installation of a Thermon electric heat tracing system 1. Individuals installing these products are responsible

More information

BT300 HVAC Drives Conventional Bypass (C-Bypass) Options

BT300 HVAC Drives Conventional Bypass (C-Bypass) Options BT300 HVAC Drives Conventional Bypass (C-Bypass) Options Description The BT300 Conventional Bypass is a companion package for the family of BT300 HVAC Drives. For information on the family of BT300 HVAC

More information

P R O D U C T S P E C I F I C A T I O N MSA Ultima X Series Sensor/Transmitter Specification

P R O D U C T S P E C I F I C A T I O N MSA Ultima X Series Sensor/Transmitter Specification P R O D U C T S P E C I F I C A T I O N MSA Ultima X Series Sensor/Transmitter Specification 1.0 This specification details the attributes and operating characteristics of the MSA Ultima X Series sensors/transmitters.

More information

PID Microprocessor temperature controllers CTD43 - CTD46 - CTH46

PID Microprocessor temperature controllers CTD43 - CTD46 - CTH46 PID Microprocessor temperature controllers CTD43 - CTD46 - CTH46 Display 1. Red measurement display (or the set point for CTD 43 by pressing, indicated by a flashing decimal point). 2. Green display of

More information

SmartOnline 200-240V 6kVA 4.2kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 6U Rack/Tower, DB9 Serial, Hardwire

SmartOnline 200-240V 6kVA 4.2kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 6U Rack/Tower, DB9 Serial, Hardwire SmartOnline 200-240V 6kVA 4.2kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 6U Rack/Tower, DB9 Serial, Hardwire MODEL NUMBER: SU6000RT3UHV Highlights 6000VA / 6kVA / 4200W on-line double-conversion

More information

How to make a diagnostic on TeSysT to start the network?

How to make a diagnostic on TeSysT to start the network? How to make a diagnostic on TeSysT to start the network? I- Type of publication Typical application Best know Method (BKM) Troubleshooting guide Level 2 use Internal use Customer II- Product - Product

More information

Technical data. General specifications. Indicators/operating means. 30 Hz Multiplex operation 30 Hz / n, n = number of sensors, n 5

Technical data. General specifications. Indicators/operating means. 30 Hz Multiplex operation 30 Hz / n, n = number of sensors, n 5 Model Number Single head system Features Parameterization interface for the application-specific adjustment of the sensor setting via the service program ULTRA 000 programmable switch outputs Hysteresis

More information

LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA. General Specification

LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA. General Specification 08/17/12 Rev2 LTR Series General Specification 700 VA to 2.1 KVA 1.0 General LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA General Specification This specification describes the features and

More information

Freeze Protection Thermostats MODELS SST 2. Installation and Operation Manual

Freeze Protection Thermostats MODELS SST 2. Installation and Operation Manual Freeze Protection Thermostats MODELS SST 2 Part Number 22744 MANUAL We Manage Heat Installation and Operation Manual Environmental Technology, Inc. 1850 N Sheridan Street South Bend, Indiana 46628 (574)

More information

Technical Information

Technical Information Date of last update: Oct-11 Ref: D7.8.4/1011/E Application Engineering Europe CORESENSE DIAGNOSTICS FOR STREAM REFRIGERATION COMPRESSORS CoreSense Diagnostics for Stream Refrigeration Compressors... 1

More information

User Manual. Hybrid 1KW-5KW INVERTER / CHARGER. Version: 1.1

User Manual. Hybrid 1KW-5KW INVERTER / CHARGER. Version: 1.1 User Manual Hybrid 1KW-5KW INVERTER / CHARGER Version: 1.1 Table of Contents ABOUT THIS MANUAL... 1 Purpose... 1 Scope... 1 SAFETY INSTRUCTIONS... 1 INTRODUCTION... 2 Product Overview... 3 INSTALLATION...

More information

Automatic Transfer Switch Controller

Automatic Transfer Switch Controller Automatic Transfer Switch Controller Decision-Makerr MPAC 1500 Model KBS with Decision-Makerr MPAC 1500 Controller Applicable Models Model Description KCS Standard-Transition Any Breaker ATS ] KCP Programmed-Transition

More information

Dyeing Programmer DP - 01

Dyeing Programmer DP - 01 Dyeing Programmer DP - 01 Display and Controls. 1) Display: 16/2 alphanumeric display 2) Temperature range: 0 to 150 degree. 3) Resolution: 1 degree. 4) Accuracy: +/- 1 degree. 5) Temperature control setting:

More information

JNIOR. Overview. Get Connected. Get Results. JNIOR Model 310. JNIOR Model 312. JNIOR Model 314. JNIOR Model 410

JNIOR. Overview. Get Connected. Get Results. JNIOR Model 310. JNIOR Model 312. JNIOR Model 314. JNIOR Model 410 The INTEG is an Ethernet I/O (digital, analog) device that monitors and controls a small set of process signals. functions as both basic I/O for integration with another application or system AND as a

More information

How To Power A Power Control On An Ip40 (Ipl) With A Power Supply (Iplug) With An Ip20 Controller (Iphones) With Power Control (Power Control) With No Antenna) With The Ip20 (Power)

How To Power A Power Control On An Ip40 (Ipl) With A Power Supply (Iplug) With An Ip20 Controller (Iphones) With Power Control (Power Control) With No Antenna) With The Ip20 (Power) MODEL NUMBER: ISC910-1-0-GB-XX ISC911-5-0-GB-XX IXP20 CONTROLLER SPECIFICATIONS Working Environment Plastic Housing... Power ImproX IXP20 Controller INSTALLATION MANUAL Designed to work in an indoor (dry)

More information

GPD 506/P5 Start-up Procedure and Checklist

GPD 506/P5 Start-up Procedure and Checklist GPD 506/P5 Start-up Procedure and Checklist Preparation for GPD506/P5 Drive Start-Up...2 HVAC Start-Up Procedure for GPD 506/P5 WITH Bypass Option:...4 HVAC Start-Up Procedure for GPD 506/P5 WITHOUT Bypass

More information

Alpha Climatic Programmable Modulating Boiler Energy Manager. Installation and User Instructions

Alpha Climatic Programmable Modulating Boiler Energy Manager. Installation and User Instructions Alpha Climatic Programmable Modulating Boiler Energy Manager Part No 3.022144 (Hard Wired) Part No 3.022143 (Radio Frequency) Installation and User Instructions 1. Description The Alpha Climatic energy

More information