CURTAIN TYPE FIRE DAMPERS
|
|
|
- Elmer Beasley
- 9 years ago
- Views:
Transcription
1 URTAIN TYPE FIRE urtain Fire Damper Basics Definition of a Fire Damper: The National Fire Protection Association (NFPA) Standard 9A defines a fire damper as "a device, installed in an air distribution system, that is designed to close automatically upon detection of heat, to interrupt migratory airflow, and to restrict the passage of flame." Although curtain fire dampers restrict flame and airflow passage as described in the NFPA definition, they are virtually transparent to heat and therefore ineffective for use in openings in fire-rated ceiling assemblies. See eiling Damper Basics, on page 3, for more details. Types of urtain Fire Dampers urtain type fire dampers are generally available in three configuration as follows: TYPE 'A' TYPE 'B' TYPE '' D Blades and frame in the airstream. Blades out of the airstream; ith blades out of airstream, provides better free area and resulting pressure drop characteristics than Type 'A', especially on smaller size dampers. Blades and frame out of the airstream; used mainly for transitioning to round or oval duct. Provides optimum pressure drop characteristics with blades and frame out of airstream. Openings in vertical fire separations ie: walls and partitions, require a vertical mount fire damper (duct runs horizontally). Gravity causes the blades to drop closed (static rated dampers). Openings in horizontal fire separations ie: floors, require a horizontal mount fire damper (duct runs vertically). orizontal mount fire dampers utilize springs to pull the blades closed. Dynamic rated fire dampers utilize closure springs in both vertical and horizontal applications to ensure the blades close fully under airflow conditions. Static Rated vs. Dynamic Rated Fire Dampers: Static fire dampers were designed for use in VA systems that shut down (fans off) in the event of a fire alarm. They have not been tested to ensure closure while air is moving in the duct. Dynamic fire dampers have been tested under specific airflow and static pressure conditions in order to ensure that the damper will close in today s VA designs that utilize 'fans on' smoke management systems. See Dynamic Fire Damper Selection Procedures in this section. Generally, a dynamic rated damper can be used in both static (fans off) or dynamic (fans on) type systems, but a static rated fire damper can only be used in a 'static' system (fans shut down during alarm). Did You Know?... Fire dampers must be mounted in a steel sleeve. The damper/sleeve assembly is held in place in the wall, partition or floor by use of retaining angles on each side of the wall etc. Ductwork shall connect to the sleeve on either side, as required, providing a connection that can 'break away' should the ductwork fall during a fire. This allows the damper/sleeve assembly to remain in the wall etc., maintaining the integrity of the fire barrier. NFPA 9A requires that fire barriers of less than 3 hours utilize a 1 1/2 hour rated fire damper. Fire barriers of 3 hours or more require a 3 hour rated fire damper. All fire dampers must be installed as per manufacturer s instructions. 9
2 DYNAMI FIRE SELETION PROEDURE Selection Procedure For Dynamic Fire Dampers Underwriters Laboratories Inc. Standard for Safety UL 555 evaluates fire dampers for use as either: (A) Fire dampers for static systems for VA systems that are automatically shut down in the event of a fire or for air transfer openings in walls or partitions; (B) Fire dampers for dynamic systems for VA systems that are operated in the event of a fire. Dynamic Fire Dampers are therefore required to close under airflow. All fire dampers must be labeled to indicate if they are to be used in static or dynamic systems. For dynamic rated dampers, this label must also indicate the maximum rated velocity through the open damper, and the maximum pressure differential across the closed damper. To attain approval for use in a dynamic system, UL Standard 555 requires that test dampers close three times (manually released) against their rated flow and shut-off pressure at ambient air temperature before heat is introduced to cause the fusible link to melt and close the damper one final time. All Manufactured Air Products dynamic curtain type fire dampers have been tested to 2 fpm (1.16 m/s) and 4" w.g. (1 kpa) static pressure. EXAMPLE #1: SINGLE SETION FIRE DAMPER To determine the maximum allowable airflow through the following damper: Type A damper 24" x 24". The maximum rated velocity is 2 fpm. 24" x 24" is 4 sq. ft. (idth in inches x eight in inches divided by 144 = sq. ft.), therefore, maximum allowable airflow is 2 fpm x 4 sq. ft. = 8, cfm. heck the maximum system pressure that could occur against a closed damper. Manufactured Air Products dynamic fire dampers have been tested and are rated to close against 4" w.g. 24" (61) EXAMPLE #2: MULTIPLE SETION FIRE DAMPER 24" (61) To determine the maximum allowable airflow through the following multi-section damper assembly: Type A damper 36" x 32" opening (the assembly will consist of four 18" x 16" dampers); The maximum rated velocity is 2 fpm. 36" x 32" is 8 sq. ft., therefore, 2 fpm x 8 sq. ft. = 16 cfm. This is the maximum allowable airflow that may be passed through the 36" x 32" opening. heck the maximum system pressure that could occur against a closed damper. Manufactured Air Products dynamic fire dampers have been tested and are rated to close against 4" w.g. 32" (813) 36" (914) 1
3 URTAIN TYPE FIRE Dynamic/Static urtain Type Fire Dampers MINIMUM AND MAXIMUM UL LASSIFIED SIZES SERIES/ MODEL TYPE SINGLE SETION MULTIPLE SETION ASSEMBLY MINIMUM SIZE MAXIMUM SIZE MAXIMUM SIZE INSTALLATION INSTALLATION INSTALLATION VERTIAL ORIZONTAL VERTIAL ORIZONTAL VERTIAL ORIZONTAL 6" x 6" 6" x 6" 24" x 24" 24" x 24" 1 72" x 24" or 36" x 48" FDDA A ontact Factory (152 x 152) (152 x 152) (61 x 61) (61 x 61) (1829 x 61 or 914 x 1219) 6" x 4" 6" x 4" 24" x 21" 24" x 21" 72" x 21" or 36" x 45" FDDB B (152 x 12) (152 x 12) (61 x 533) (61 x 533) (1829 x 533 or 914 x 1143) ontact Factory DYNAMI FDD Round R 4" dia. (12) 4" dia. (12) 2" dia. (58) 2" dia. (58) 34" dia. (864) 5" x 4" 5" x 4" 22" x 2" 22" x 2" 7" x 2" FDD Oval O (127 x 12) (127 x 12) (559 x 58) (559 x 58) (1778 x 58) ontact Factory 4" x 4" 4" x 4" 22" x 2" 22" x 2" 7" x 2" FDD Sq./Rect.SR (12 x 12) (12 x 12) (559 x 58) (559 x 58) (1778 x 58) STATI FDDA-12/14/16 A 6" x 6" 6" x 6" 24" x 24" 24" x 24" (152 x 152) (152 x 152) (61 x 61) (61 x 61) 6" x 4" 6" x 4" 24" x 21" 24" x 21" FDDB-12/14/16 B (127 x 12) (127 x 12) (559 x 58) (559 x 58) FDD-12/14/16 R 4" dia. (12) 4" dia. (12) 2" dia. (58) 2" dia. (58) FDA FDB A B 4" x 4" 4" x 4" 6" x 6" 6" x 6" 12" x 12" 2 12" x 6" (12 x 12) (12 x 12) (1524 x 1524) (1524 x 1524) (348 x 348) (2591 x 1524) 4" x 3" 4" x 4" 6" x 54" 6" x 54" 12" x 114" 12" x 54" (12 x 76) (12 x 12) (1524 x 1372) (1524 x 1372) (348 x 2896) (2591 x 1372) FD Round R 3" dia. (76) 4" dia. (12) 53" dia. (1346) 53" dia. (1346) 112" dia. (2845) 53" dia. (1346) FD Oval O FD Sq./Rect. SR FDA-12/14/16 A 4" x 3" 5" x 4" 58" x 53" 58" x 53" 118" x 112" 1" x 53" (12 x 76) (127 x 12) (1473 x 1346) (1473 x 1346) (2997 x 2845) (254 x 1346) 3" x 3" 4" x 4" 58" x 53" 58" x 53" 118" x 112" 1" x 53" (76 x 76) (12 x 12) (1473 x 1346) (1473 x 1346) (2997 x 2845) (254 x 1346) 4" x 4" 4" x 4" 48" x 48" 48" x 48" (12 x 12) (12 x 12) (1219 x 1219) (1219 x 1219) FDB-12/14/16 B 4" x 3" 4" x 4" 48" x 43" 48" x 43" (12 x 76) (12 x 12) (1219 x 192) (1219 x 192) FD-12/14/16 R 3" dia. (76) 4" dia. (12) 42" dia. (167) 42" dia. (167) FDTA FDTB A B 4" x 4" 4" x 4" 41" x 36" or 36" x 6" 41" x 36" (12 x 12) (12 x 12) (141 x 914) or (141 x 914) (914 x 1524) 4" x 3" 4" x 3" 41" x 3" or 36" x 5" 41" x 3" (12 x 76) (12 x 76) (141 x 762) or (141 x 762) (914 x 127) FDT Round R 3" dia. (76) 3" dia. (76) 34" dia. (864) 34" dia. (864) FDT Oval O FDT Sq./Rect.SR 4" x 3" 4" x 3" 39" x 29" 39" x 29" (12 x 76) (12 x 76) (991 x 737) (991 x 737) 3" x 3" 3" x 3" 39" x 29" or 34" x 49" 39" x 29" (76 x 76) (76 x 76) (991 x 737) or (991 x 737) (864 x 1245) Damper Types: Type A: Blades and frame in airstream. Type B: Blades out of airstream for minimal restriction of airflow. Type R: Round enclosure with blades and frame out of airstream for maximum free area. Type O: Oval enclosure with blades and frame out of airstream for maximum free area. Type SR: Square or rectangular enclosure with blades and frame out of airstream for maximum free area. 1 Maximum individual sections not to exceed 18" x 24" (457 x 61). 2 Maximum individual sections not to exceed 34" x 6" (864 x 1524). 11
4 DYNAMI FIRE 1 1/2 OUR STANDARD FRAME FOR USE IN DYNAMI SYSTEMS 1 1/2 OUR RATING UL 555 LASSIFIED Models: FDDA Type A FDDB Type B FDD Type R/O FDD Type SR Model FDDA The MAP FDD Series dynamic curtain fire dampers are UL/UL approved for use where building codes require protection of VA ductwork penetrations in walls, partitions or floors that have a fire resistance rating of 2 hours or less. lassified for use in dynamic systems (max. 2 4" w.g.) where the VA system remains operative in the event of a fire, the FDD Series features stainless steel closure springs for assured damper closure under airflow, corrosion resistant steel frame and blades for lasting performance, and choice of transition styles. ONSTRUTION DETAILS: FDDA FDDB FDD FDD (Type A) (Type B) (Type R/O) (Type SR) FRAME: 4 1/4" (18) wide, 4 1/4" (18) wide, 4 1/4" (18) wide, 4 1/4" (18) wide, 22 ga. (.85) roll- 22 ga. (.85) roll- 22 ga. (.85) roll- 22 ga. (.85) rollformed G6 formed G6 formed G6 formed G6 galvanized steel galvanized steel galvanized steel; galvanized steel; out of airstream out of airstream BLADES: urtain type, inter- Out of airstream. Out of airstream. Out of airstream. locking blades, 22 ga. urtain type, inter- urtain type, inter- urtain type, inter- (.85) roll-formed locking blades, 22 ga. locking blades, 22 ga. locking blades, 22 ga. G6 galvanized (.85) roll-formed (.85) roll-formed (.85) roll-formed steel G6 galvanized G6 galvanized G6 galvanized steel steel steel ENLOSURE: Type B Type Type N/A 22 ga. (.85) Round or Oval Square or Rect. galvanized steel 22 ga. (.85) 22 ga. (.85) galvanized steel galvanized steel FUSIBLE LINK: 165 F (74 ) Std. 165 F (74 ) Std. 165 F (74 ) Std. 165 F (74 ) Std. (UL Listed) 212 F (1 ) 212 F (1 ) 212 F (1 ) 212 F (1 ) available available available available BLADE Stainless steel Stainless steel Stainless steel Stainless steel LOSURE: closure springs closure springs closure springs closure springs and galvanized and galvanized and galvanized and galvanized steel locking ramps steel locking ramps steel locking ramps steel locking ramps MOUNTING: Vertical Vertical Vertical Vertical or or or or orizontal orizontal orizontal orizontal AVAILABLE Galvanized steel; Galvanized steel; Galvanized steel; Galvanized steel; SLEEVE: Specify SL Specify SL Specify SL Specify SL Option Option Option Option EIGT = NOMINAL DUT SIZE - 1/4" (6) 4 1/4" (18) INTERLOKING URTAIN BLADES UL LISTED FUSIBLE LINK (REPLAEABLE) URTAIN BLADE LOKING RAMP STAINLESS STEEL LOSURE SPRING ROLL-FORMED FRAME IDT = NOMINAL DUT SIZE - 1/4" (6) TYPE A: MODEL D11 Type A: Model FDDA 3" (76) 4 1/4" (18) VERTIAL MOUNT Vertical Mount DUT SIZE - 1/4" (6) For MIN./MAX. UL SIZES see chart on page 11. STAINLESS STEEL LOSURE SPRING URTAIN BLADE LOKING RAMP ORIZONTAL MOUNT orizontal Mount 12
5 DYNAMI FIRE 1 1/2 OUR = DUT SIZE + 1/8" (3) = DUT SIZE - 1/4" (6) Type B: Model FDDB D + 1 3/4" (44) Type R: Model FDD For overall damper dimensions see sizing chart on page 22. D + 1 3/4" (44) 1" Type O: Model FDD + 1 3/4" (44) Type SR ith ollar (Standard): Model FDD + 1 3/4" (44) Type SR ithout ollar: Model FDD DUT EIGT in inches (mm) DUT EIGT in inches (mm) PERFORMANE DATA: urtain type fire dampers impose minimal resistance to air flow in the system. The following charts indicate both free area for the different damper types and static pressure losses for various velocities. TYPE A DAMPER FREE AREA sq. ft. DUT IDT in inches (mm) (152) (35) (457) (61) (762) (914) (167) (1219)(1372) (1524) 6 (152) (35) (457) (61) (762) (914) (167) (1219) (1372) (1524) TYPE B DAMPER FREE AREA sq. ft. DUT IDT in inches (mm) (152) (35) (457) (61) (762) (914) (167) (1219)(1372) (1524) 6 (152) (35) (457) (61) (762) (914) (167) (1219) (1372) TYPE AVE FREE AREA EQUAL TO NOMINAL DUT AREA. To calculate Free Area of round duct: DIAMETER 2 x.545 = Free Area (sq ft.) To determine pressure drop across open damper, calculate free area velocity as shown, find velocity on curve and read across for s.p. differential. Free Area Velocity (fpm) = cfm Free Area Example: 1-36" x 24" Damper required for 8,5 cfm. (Type A) FAV = 85 = 17 fpm 5 sq. ft. 17 fpm located on the A curve shows a pressure drop of.7 in. wg. cfm = cubic feet per minute fpm = feet per minute velocity S.P. = static pressure in inches water gauge FAV = Free Area Velocity Imperial System Shown To convert to SI (metric) system: Multiply cfm by.4719 for liters per second fpm by.58 for meters per second in. wg. by.2486 for kilopascals sq. ft. by.929 for square meters Static Pressure.1.9 Drop.8 (in. wg.) FREE AREA VELOITY V.S. STATI TI PRESSURE DROP Free Area Velocity (fpm) 4 5 TYPE 'A' TYPE 'B' TYPE '' O TO SPEIFY SUGGESTED SPEIFIATION: Provide and install, as shown on plans and as described in specifications, Dynamic rated fire dampers as manufactured by Manufactured Air Products, meeting or exceeding the following criteria: Fire dampers shall meet the requirements of NFPA 9A and shall be manufactured, tested and labeled in accordance with UL 555 Safety Standard for Fire Dampers - Sixth Edition, June 1999, including Dynamic losure Test (formerly the Operation Test). Dampers shall be classified for dynamic closure against an airflow velocity of 2 fpm (1.16 m/s) at 4" w.g. (1 kpa) static pressure differential (across closed damper). Each fire damper shall bear a UL 1 1/2 hour fire resistance rating label in addition to label verifying the airflow and closure pressure ratings as established by the Dynamic losure Test. Each fire damper shall also be marked with the words "For use in dynamic systems". Dampers marked "For use in static systems only" are not acceptable. Each fire damper shall be complete with a 165 F (74 ) UL Listed fusible link. Fire dampers shall each include a steel sleeve of appropriate length/gauge and retaining angles, supplied by damper manufacturer to ensure proper installation in accordance with damper manufacturer s instructions. ontractor shall provide and install an access door at each fire damper, of appropriate size to allow for inspection, testing and fusible link replacement. Data submitted for approval shall include confirmation of UL qualifications in addition to manufacturer s installation instructions. Each shipment of fire dampers shall include same installation instructions. Dynamic rated fire dampers shall be Manufactured Air Products Models FDDA (Type A), FDDB (Type B), FDD (Type ). 13
6 DYNAMI FIRE 1 1/2 OUR INTEGRAL SLEEVE DYNAMI FIRE (1 1/2 OUR LISTING) FOR USE IN DYNAMI SYSTEMS. MAP integral sleeve fire dampers ensure proper damper mounting in sleeve and can be shipped direct to job site for immediate installation, eliminating costly and inconvenient shop handling. All units are constructed with 22 ga. (.85) roll-formed G6 galvanized steel integral sleeve available in 12" (35), 14" (356) or 16" (46) length. Optional 'Quick-Set' retaining angles are available to complete the installation package. TYPE A: MODEL FDDA - 12/14/16 TYPE B: MODEL FDDB - 12/14/16 A Type 'A' Blades and frame in the airstream. Model: FDDA Min. size - 6" x 6" (152 x 152) Max. size - 24" x 24" (61 x 61) L Type 'B' Blades out of airstream. Model: FDDB Min. size - 6" x 4" (152 x 12) Max. size - 24" x 21" (61 x 533) L Damper eight () Dim. 'A' 5" thru 17" (127 thru 432) 2" (51) 18" thru 21" (457 thru 533) 3" (76) ONSTRUTION DETAILS: INTEGRAL SLEEVE/FRAME: 22 ga. (.85) roll-formed G6 galvanized steel. FDDxx -12 Length 12" (35) FDDxx -14 Length 14" (356) FDDxx -16 Length 16" (46) BLADES: urtain type interlocking blades, 22 ga. (.85) roll-formed G6 galvanized steel. FUSIBLE LINK: 165 F (74 ) standard. UL Listed. 212 F (1 ) available. BLADE LOSURE: Vertical and orizontal mount. Stainless steel closure springs and galvanized steel locking ramps. TYPE R: MODEL FDD - 12/14/16 D 1" (25) D + 2" (51) D + 2" (51) Type 'R' Round transition collars. Blades partially in airstream Model: FDD Min. size - 4" dia. (12) Max. size - 2" dia. (58) L 14
7 DYNAMI FIRE 1 1/2 OUR O TO SPEIFY Intergral Sleeve Dynamic Fire Dampers Models: FDDA - 12/14/16 FDDB - 12/14/16 FDD - 12/14/16 SUGGESTED SPEIFIATION: Provide and install, as shown on plans and as described in specifications, Dynamic rated fire dampers as manufactured by Manufactured Air Products, meeting or exceeding the following criteria: Fire dampers shall meet the requirements of NFPA 9A and shall be manufactured, tested and labeled in accordance with UL 555 Safety Standard for Fire Dampers - Sixth Edition, June 1999, including Dynamic losure Test (formerly the Operation Test). Dampers shall be classified for dynamic closure against an airflow velocity of 2 fpm (1.16 m/s) at 4" w.g. (1 kpa) static pressure differential (across closed damper). Each fire damper shall bear a UL 1 1/2 hour fire resistance rating label in addition to label verifying the airflow and closure pressure ratings as established by the Dynamic losure Test. Each fire damper shall also be marked with the words "For use in dynamic systems". Dampers marked "For use in static systems only" are not acceptable. Each fire damper shall be complete with a 165 F (74 ) UL Listed fusible link. In addition, each fire damper shall be provided from the factory in an integral 22 ga. (.85) galvanized steel sleeve of (specifier select one) 12" (35), 14" (356) or 16" (46) in length complete with Manufactured Air Products 'Quick-Set' retaining angles, to ensure proper installation in accordance with damper manufacturer s instructions. ontractor shall provide and install an access door at each fire damper, of appropriate size to allow for inspection, testing and fusible link replacement. Data submitted for approval shall include confirmation of UL qualifications in addition to manufacturer s installation instructions. Each shipment of fire dampers shall include same installation instructions. Integral sleeve Dynamic rated fire dampers shall be Manufactured Air Products Models FDDA-12 or 14 or 16 (Type A), FDDB-12 or 14 or 16 (Type B), FDD-12 or 14 or 16 (Type ). 15
8 STATI FIRE 1 1/2 OUR STANDARD FRAME FOR USE IN STATI SYSTEMS 1 1/2 OUR RATING UL 555 LASSIFIED Models: FDA Type A FDB Type B FD Type Model FDA The MAP FD Series curtain fire dampers, for use in static "fans off" systems where the VA system shuts down in the event of a fire, are UL/UL approved to provide protection of VA ductwork penetrations in walls, partitions or floors that have a fire resistance rating of 2 hours or less. The FD Series features corrosion resistant steel frame and blades for performance that lasts, and a choice of transition styles and factory installed sleeves to suit duct size, making installation fast and simple. ONSTRUTION DETAILS: FDA FDB FD (Type A) (Type B) (Type ) FRAME: 4 1/4" (18) wide, 4 1/4" (18) wide, 4 1/4" (18) wide, 22 ga. (.85) roll- 22 ga. (.85) roll- 22 ga. (.85) rollformed G6 formed G6 formed G6 galvanized steel galvanized steel galvanized steel; out of airstream BLADES: urtain type, inter- Out of airstream. Out of airstream. locking blades, 22 ga. urtain type, inter- urtain type, inter- (.85) roll-formed locking blades, 22 ga. locking blades, 22 ga. G6 galvanized (.85) roll-formed (.85) roll-formed steel G6 galvanized G6 galvanized steel steel ENLOSURE: Type B Type N/A 22 ga. (.85) Round or Oval galvanized steel 22 ga. (.85) galvanized steel FUSIBLE LINK: 165 F (74 ) Std. 165 F (74 ) Std. 165 F (74 ) Std. (UL Listed) 212 F (1 ) 212 F (1 ) 212 F (1 ) available available available BLADE Vertical mount; gravity Vertical mount; gravity Vertical mount; gravity LOSURE: orizontal mount; orizontal mount; orizontal mount; stainless steel closure stainless steel closure stainless steel closure springs with galvanized springs with galvanized springs with galvanized steel locking ramps steel locking ramps steel locking ramps MOUNTING: Vertical Vertical Vertical or or or orizontal orizontal orizontal INTEGRAL SLEEVE: See Model See Model See Model 22 ga (.85) x12" (35) long FDAx-12 FDBx-12 FDx ga (.85) x14" (356) long FDAx-14 FDBx-14 FDx ga (.85) x16" (46) long FDAx-16 FDBx-16 FDx-16 For MIN./MAX. UL SIZES see chart on page 11. EIGT = NOMINAL DUT SIZE - 1/4" (6) 4 1/4" (18) INTERLOKING URTAIN BLADES UL LISTED FUSIBLE LINK (REPLAEABLE) ROLL-FORMED FRAME IDT = NOMINAL DUT SIZE - 1/4" (6) TYPE A: MODEL 11 3" (76) MODEL 11V VERTIAL MOUNT STAINLESS STEEL LOSURE SPRING Type A: Model FDA 4 1/4" (18) Vertical Mount URTAIN BLADE LOKING RAMP orizontal Mount DUT SIZE - 1/4" (6) MODEL 11 ORIZONTAL MOUNT 16
9 STATI FIRE 1 1/2 OUR = DUT SIZE + 1/8" (3) = DUT SIZE - 1/4" (6) D + 1 3/4" (44) + 1 3/4" (44) + 1 3/4" (44) Type B: Model FDB D + 1 3/4" (44) Type R: Model FD Type O: Model FD For overall damper dimensions see sizing chart on page 22. 1" Type SR ith ollar (Standard): Model FD Type SR ithout ollar: Model FD PERFORMANE DATA: urtain type fire dampers impose minimal resistance to air flow in the system. The following charts indicate both free area for the different damper types and static pressure losses for various velocities. DUT EIGT in inches (mm) DUT EIGT in inches (mm) TYPE A DAMPER FREE AREA sq. ft. DUT IDT in inches (mm) (152) (35) (457) (61) (762) (914) (167) (1219)(1372) (1524) 6 (152) (35) (457) (61) (762) (914) (167) (1219) (1372) (1524) TYPE B DAMPER FREE AREA sq. ft. DUT IDT in inches (mm) (152) (35) (457) (61) (762) (914) (167) (1219)(1372) (1524) 6 (152) (35) (457) (61) (762) (914) (167) (1219) (1372) TYPE AVE FREE AREA EQUAL TO NOMINAL DUT AREA. To calculate Free Area of round duct: DIAMETER 2 x.545 = Free Area (sq ft.) To determine pressure drop across open damper, calculate free area velocity as shown, find velocity on curve and read across for s.p. differential. Free Area Velocity (fpm) = cfm Free Area.4.3 Example: 1-36 x 24 Damper required for.2 8,5 cfm. (Type A) FAV = 85 = 17 fpm 5 sq. ft. Static Pressure.1 17 fpm located on the A curve shows a pressure drop of.7 in. wg. cfm = cubic feet per minute fpm = feet per minute velocity S.P. = static pressure in inches water gauge FAV = Free Area Velocity Imperial System Shown To convert to SI (metric) system: Multiply cfm by.4719 for liters per second fpm by.58 for meters per second in. wg. by.2486 for kilopascals sq. ft. by.929 for square meters Drop (in. wg.) FREE AREA VELOITY V.S. STATI TI PRESSURE DROP Free Area Velocity (fpm) 4 5 TYPE 'A' TYPE 'B' TYPE '' O TO SPEIFY SUGGESTED SPEIFIATION: Provide and install, as shown on plans and as described in specifications, fire dampers as manufactured by Manufactured Air Products, meeting or exceeding the following criteria: Fire dampers shall be manufactured, tested and labeled in accordance with UL 555 Safety Standard for Fire Dampers - Sixth Edition, June 1999, and shall have 1 1/2 hour fire resistance rating. Each fire damper shall bear a UL label verifying fire resistance rating in addition to intended mounting position. Fire dampers shall be suitably constructed for vertical or horizontal installation as required for each specific location. Each fire damper shall be complete with a (specifier select one) 165 F (74 ) or 212 F (1 ) UL Listed fusible link. Fire dampers shall each include a steel sleeve of appropriate length/gauge and retaining angles, supplied by damper manufacturer to ensure proper installation in accordance with damper manufacturer s instructions. ontractor shall provide and install an access door at each fire damper, of appropriate size to allow for inspection, testing and fusible link replacement. Information submitted for approval shall include confirmation of UL qualifications, pressure drop data and manufacturer s installation instructions. Each shipment of fire dampers shall include same installation instructions. Fire dampers shall be Manufactured Air Products Models FDA (Type A), FDB (Type B), FD (Type ). 17
10 STATI FIRE 1 1/2 OUR Integral Sleeve Static Fire Dampers (1 1/2 our Listing) For Use in Static Systems MAP integral sleeve fire dampers ensure proper damper mounting in sleeve and can be shipped direct to job site for immediate installation, eliminating costly and inconvenient shop handling. All units are constructed with 22 ga. (.85) roll-formed G6 galvanized steel integral sleeve available in 12" (35), 14" (356) or 16" (46) length. Optional 'Quick- Set' retaining angles are available to complete the installation package. Type A: Model FDA - 12/14/16 Type B: Model FDB - 12/14/16 A L L Type 'A' Blades and frame in the airstream. Models: FDAV Vertical and FDA orizontal Min. size - Vertical or orizontal 4" x 4" (12 x 12) Max. size -Vertical or orizontal 48" x 48" (1219 x 1219) Type 'B' Blades out of airstream. Models: FDBV Vertical and FDB orizontal Min. size - Vertical 4" x 3" (12 x 76) orizontal 4" x 4" (12 x 12) Max. size -Vertical or orizontal 48" x 43" (1219 x 192) Damper eight () Dim. 'A' 5" thru 17" (127 thru 432) 2" (51) 18" thru 27" (457 thru 686) 3" (76) 28" thru 36"(711 thru 914) 4" (12) 37" thru 43" (94 thru 192) 5" (127) ONSTRUTION DETAILS: INTEGRAL SLEEVE/FRAME: 22 ga. (.85) roll-formed G6 galvanized steel. FDxx -12 Length 12" (35) FDxx -14 Length 14" (356) FDxx -16 Length 16" (46) BLADES: urtain type interlocking blades, 22 ga. (.85) roll-formed G6 galvanized steel. FUSIBLE LINK: 165 F (74 ) standard. UL Listed. 212 F (1 ) available. BLADE LOSURE: Vertical mount model; gravity. orizontal mount models are equipped with stainless steel closure springs and galvanized steel locking ramps. Type : Model FD - 12/14/16 D 1" (25) D + 2" (51) L D + 2" (51) Type 'R' Round transition collars. Blades partially in airstream. Models: FDV Vertical and FD orizontal Min. size - Vertical 3" dia. (76) orizontal 4" dia. (12) Max. size - Vertical or orizontal 42" dia. (167) 18
11 STATI FIRE 1 1/2 OUR Integral Sleeve Static Fire Dampers Models: FDAx - 12/14/16 FDBx - 12/14/16 FDx - 12/14/16 O TO SPEIFY SUGGESTED SPEIFIATION: Provide and install, as shown on plans and as described in specifications, integral sleeve fire dampers as manufactured by Manufactured Air Products, meeting or exceeding the following criteria: Fire dampers shall be manufactured, tested and labeled in accordance with UL 555 Safety Standard for Fire Dampers - Sixth Edition, June 1999, and shall have a 1 1/2 hour fire resistance rating. Each fire damper shall bear a UL label verifying fire resistance rating in addition to intended mounting position. Fire dampers shall be suitably constructed for vertical or horizontal installation as required for each specific location. Each fire damper shall be complete with a (specifier select one) 165 F (74 ) or 212 F (1 ) UL Listed fusible link. In addition, each fire damper shall be provided from the factory in an integral 22 ga. (.85) galvanized steel sleeve of (specifier select one) 12" (35), 14" (356) or 16" (46) in length complete with Manufactured Air Products 'Quick-Set' retaining angles, to ensure proper installation in accordance with damper manufacturer s instructions. ontractor shall provide and install an access door at each fire damper, of appropriate size to allow for inspection, testing and fusible link replacement. Information submitted for approval shall include confirmation of UL qualifications, pressure drop data, and manufacturer s installation instructions. Each shipment of fire dampers shall include same installation instructions. Integral sleeve fire dampers shall be Manufactured Air Products Models FDAx-12 or 14 or 16 (Type A), FDBx-12 or 14 or 16 (Type B), FDx-12 or 14 or 16 (Type ). 19
12 STATI FIRE TINLINE 1 1/2 OUR TINLINE FRAME FOR USE IN STATI SYSTEMS 1 1/2 OUR RATING UL 555 LASSIFIED Models: FDTA Type A FDTB Type B FDT Type Model FDTA The MAP FDT Series Thinline curtain fire dampers are UL/UL approved for use where building codes require the protection of VA ductwork penetrations in walls, partitions or floors that have a fire resistance rating of 2 hours or less. The FDT Series is classified for use only in static "fans off" systems where the VA system is automatically shut down in the event of a fire alarm. The FDT Series Thinline dampers are only 2" (51) deep making them ideal for installation in narrow fire rated partitions, transfer duct openings, behind grilles or in any other application where space is limited. The FDT Series feature corrosion resistant steel frame and blades for lasting performance, and choice of transition styles and factory installed sleeves to suit duct size, making installation fast and simple. ONSTRUTION DETAILS: FDTA FDTB FDT (Type A) (Type B) (Type ) FRAME: 2" (51) wide, 2" (51) wide, 2" (51) wide, 22 ga. (.85) roll- 22 ga. (.85) roll- 22 ga. (.85) rollformed G6 formed G6 formed G6 galvanized steel galvanized steel galvanized steel; out of airstream BLADES: urtain type, inter- Out of airstream. Out of airstream. locking blades, 22 ga. urtain type, inter- urtain type, inter- (.85) roll-formed locking blades, 22 ga. locking blades, 22 ga. G6 galvanized (.85) roll-formed (.85) roll-formed steel G6 galvanized G6 galvanized steel steel ENLOSURE: Type B Type N/A 22 ga. (.85) Round or Oval galvanized steel 22 ga. (.85) galvanized steel FUSIBLE LINK: 165 F (74 ) Std. 165 F (74 ) Std. 165 F (74 ) Std. (UL Listed) 212 F (1 ) 212 F (1 ) 212 F (1 ) available available available BLADE Vertical mount; gravity Vertical mount; gravity Vertical mount; gravity LOSURE: orizontal mount; orizontal mount; orizontal mount; stainless steel closure stainless steel closure stainless steel closure springs with galvanized springs with galvanized springs with galvanized steel locking ramps steel locking ramps steel locking ramps MOUNTING: Vertical Vertical Vertical or or or orizontal orizontal orizontal AVAILABLE Galvanized steel; Galvanized steel; Galvanized steel; SLEEVE: Specify SL Specify SL Specify SL Option Option Option 2" (51) EIGT = NOMINAL DUT SIZE - 1/4" (6) INTERLOKING URTAIN BLADES UL LISTED FUSIBLE LINK (REPLAEABLE) ROLL-FORMED FRAME IDT = NOMINAL DUT SIZE - 1/4" (6) TYPE A: MODEL 21 Type A: Model FDTA 2" (51) DUT SIZE - 1/4" (6) MODEL 21V VERTIAL MOUNT Vertical Mount For MIN./MAX. UL SIZES see chart on page 11. STAINLESS STEEL LOSURE SPRING URTAIN BLADE LOKING RAMP MODEL 21 ORIZONTAL MOUNT orizontal Mount 2
13 STATI FIRE TINLINE 1 1/2 OUR 2" (51) = DUT SIZE + 1/8" (3) D + 1 3/4" (44) IDT = NOMINAL DUT SIZE - 1/4" (6) Type B: Model FDTB D + 1 3/4" (44) Type R: Model FDT For overall damper dimensions, see sizing chart on page 23. 1" Type O: Model FDT + 1 3/4" (44) Type SR ith ollar (Standard): Model FDT + 1 3/4" (44) Type SR ithout ollar: Model FDT DUT EIGT in inches (mm) DUT EIGT in inches (mm) PERFORMANE DATA: urtain type fire dampers impose minimal resistance to air flow in the system. The following charts indicate both free area for the different damper types and static pressure losses for various velocities. TYPE A TINLINE DAMPER FREE AREA sq. ft. DUT IDT in inches (mm) (152) (35) (457) (61) (762) (914) (116) 6 (152) (35) (457) (61) (762) (914) (167) (1219) (1372) (1524) TYPE B TINLINE DAMPER FREE AREA sq. ft. DUT IDT in inches (mm) (152) (35) (457) (61) (762) (914) (116) 6 (152) (35) (457) (61) (762) (914) (167) (1219) TYPE AVE FREE AREA EQUAL TO NOMINAL DUT AREA. To calculate Free Area of round duct: DIAMETER 2 x.545 = Free Area (sq ft.) To determine pressure drop across open damper, calculate free area velocity as shown, find velocity on curve and read across for s.p. differential. Free Area Velocity (fpm) = cfm Free Area Example: 1-36" x 36" Damper required for 14, cfm. (Type A) FAV = 14, = 2 fpm 7 sq. ft. 2 fpm located on the A curve shows a pressure drop of.12 in. wg. cfm = cubic feet per minute fpm = feet per minute velocity S.P. = static pressure in inches water gauge FAV = Free Area Velocity Imperial System Shown To convert to SI (metric) system: Multiply cfm by.4719 for liters per second fpm by.58 for meters per second in. wg. by.2486 for kilopascals sq. ft. by.929 for square meters O TO SPEIFY Static Pressure.1.9 Drop.8 (in. wg.) FREE AREA VELOITY V.S. STATI TI PRESSURE DROP Free Area Velocity (fpm) 4 5 TYPE 'A' TYPE 'B' TYPE '' SUGGESTED SPEIFIATION: Provide and install, as shown on plans and as described in specifications, Thinline fire dampers as manufactured by Manufactured Air Products, meeting or exceeding the following criteria: Fire dampers shall be manufactured, tested and labeled in accordance with UL 555 Safety Standard for Fire Dampers - Sixth Edition, June 1999, and shall have 1 1/2 hour fire resistance rating. Each fire damper shall bear a UL label verifying fire resistance rating in addition to intended mounting position. Fire dampers shall be suitably constructed for vertical or horizontal installation as required for each specific location. Thinline style fire damper frame shall be a maximum of 2" (51) in width, roll-formed from G6 galvanized steel. Blades shall be Thinline type, roll-formed G6 galvanized steel. Each fire damper shall be complete with a (specifier select one) 165 F (74 ) or 212 F (1 ) UL Listed fusible link. Fire dampers shall each include a steel sleeve of appropriate length/gauge and retaining angles, supplied by damper manufacturer to ensure proper installation in accordance with damper manufacturer s instructions. ontractor shall provide and install an access door at locations where the fire damper cannot be accessed through grille or duct end opening, to allow for inspection, testing and fusible link replacement. Information submitted for approval shall include confirmation of UL qualifications, pressure drop data and manufacturer s installation instructions. Each shipment of fire dampers shall include same installation instructions. Thinline fire dampers shall be Manufactured Air Products Models FDTA (Type A), FDTB (Type B), FDT (Type ). 21
14 SIZING ART STANDARD FRAME Fire Damper Sizing hart For All Standard 4 1/4" (18) Frame Fire Dampers: Series/ Models: FDD & FD Use the following chart to determine overall dimensions for Type A, B, and curtain type fire dampers: IG AT EIGT IG AT EIGT OVERALL EIGT DUT OPENING OVERALL EIGT DUT OPENING 1" OVERALL EIGT TYPE A TYPE B TYPE TYPE A DUT OPENING EIGT OVERALL EIGT IMPERIAL METRI IMPERIAL METRI 4" 6" 1 mm 1525 mm DUT EIGT 1/4" DUT EIGT 6 mm NOTE: TYPE A DAMPER OVERALL IDT = DUT OPENING 1/4" (6 mm) 3" 17" mm DUT EIGT + 2 1/8" DUT EIGT + 54 mm 18" 27" mm " + 3 1/8" " + 79 mm 28" 36" mm " + 4 1/8" " + 15 mm TYPE B 37" 45" mm " + 5 1/8" " + 13 mm 46" 54" mm " + 6 1/8" " mm NOTE: TYPE B DAMPER OVERALL IDT = DUT OPENING 1/4" (6 mm) 3" 5" mm DUT EIGT + 1 3/4" DUT EIGT + 44 mm 6" 17" mm DUT EIGT + 2 3/4" DUT EIGT + 7 mm 18" 27" mm " + 3 3/4" " + 95 mm TYPE 28" 36" 7 9 mm " + 4 3/4" " mm 37" 45" mm " + 5 3/4" " mm 46" 53" mm " + 6 3/4" " mm NOTE: TYPE DAMPER OVERALL IDT = DUT OPENING + 1 3/4" (44 mm) 22
15 SIZING ART TINLINE FRAME Fire Damper Sizing hart For Thinline 2" (51) Frame Fire Dampers: Series/ Model: FDT Use the following chart to determine overall dimensions for Type A, B, and curtain type fire dampers: IG AT EIGT IG AT EIGT OVERALL EIGT DUT OPENING OVERALL EIGT DUT OPENING OVERALL EIGT 1" TYPE A TYPE B TYPE DUT OPENING EIGT OVERALL EIGT IMPERIAL METRI IMPERIAL METRI TYPE A 4" 6" 1 mm 1525 mm DUT EIGT 1/4" DUT EIGT 6 mm NOTE: TYPE A DAMPER OVERALL IDT = DUT OPENING 1/4" (6 mm) 3" 9" mm DUT EIGT + 2 1/8" DUT EIGT + 54 mm 1" 15" mm " + 3 1/8" " + 79 mm 16" 19" mm " + 4 1/8" " + 15 mm 2" 25" mm " + 5 1/8" " + 13 mm TYPE B 26" 31" mm " + 6 1/8" " mm 32" 34" 8 85 mm " + 7 1/8" " mm 35" 4" mm " + 8 1/8" " + 26 mm 41" 46" mm " + 9 1/8" " mm 47" 5" mm " + 1 1/8" " mm NOTE: TYPE B DAMPER OVERALL IDT = DUT OPENING 1/4" (6 mm) 3" 9" mm DUT EIGT + 2 3/4" DUT EIGT + 7 mm 1" 15" mm " + 3 3/4" " + 95 mm 16" 19" mm " + 4 3/4" " mm 2" 25" mm " + 5 3/4" " mm TYPE 26" 31" mm " + 6 3/4" " mm 32" 34" 8 85 mm " + 7 3/4" " mm 35" 4" mm " + 8 3/4" " mm 41" 46" mm " + 9 3/4" " mm 47" 49" mm " + 1 3/4" " mm NOTE: TYPE DAMPER OVERALL IDT = DUT OPENING + 1 3/4" (44 mm) 23
FIRE DAMPER APPLICATION GUIDE
FIRE AND CEILING RADIATION DAMPERS FIRE DAMPER APPLICATION GUIDE Use this application guide to help determine what type of fire damper best suits the application. Below are listed the ten Metal-Fab fire
Life Safety Dampers Selection and Application Manual. Ceiling Radiation Dampers Fire Dampers Combination Fire Smoke Dampers Smoke Dampers
Life Safety Dampers Selection and Application Manual Ceiling Radiation Dampers Fire Dampers Combination Fire Smoke Dampers Smoke Dampers May 2014 1 2 Table of Contents HOW TO USE THIS MANUAL DAMPER APPLICATION
FSD35, FSD36 AND FSD37 COMBINATION FIRE and SMOKE DAMPERS
3900 Dr. Greaves Rd. Kansas City, MO 64030 (816) 761-7476 FAX (816) 765-8955 INSTALLATION INSTRUCTIONS FSD35, FSD36 AND FSD37 COMBINATION FIRE and SMOKE DAMPERS 11/2 HOUR UL555 RATED UL555S LEAKAGE RATED
4 Installation Requirements
4 Installation Requirements 9 4.1 Code Reference The authority having jurisdiction should be referenced to determine what law, ordinance or code shall apply in the use of flexible duct. Ducts conforming
COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES
COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES These guidelines are to be used for ALL commercial cooking hoods, ventilation systems and related fire suppression
AMD-23-TD. Thermal Dispersion Air Measuring Station with VCD-23 Control Damper. Application and Design. Ratings. Features and Control Options.
Application and esign Thermal ispersion Air Measuring Station with VC-23 Control amper The combines the functionality of a highly accurate thermal dispersion airflow measuring station and a low leakage
security products metric sizes Redefine your comfort zone. www.titus-hvac.com
metric sizes secure lethal objects monitoring areas suicide deterrent Redefine your comfort zone. www.titus-hvac.com humid areas prevents corrosion minimum security medium security maximum security Table
AMD-33 Air Measuring Station with VCD-33 Control Damper
Application and esign Construction Standard Optional Frame Material Galvanized Steel - Frame Material Thickness 16 ga. (1.5mm) 12 ga. (2.7mm) Frame Type 5 in. x 1 in. hat channel - Blade Material Galvanized
Basic Selection & Proper Application of Overhead Air Distribution Devices
Basic Selection & Proper Application of Overhead Air Distribution Devices GRD Selection & Application Terms Selection Throw Sound Installation Variations affect Performance Inlet Effects Basics Return
DUCT SMOKE DETECTOR D4120
Purpose/Application National and local safety standards and codes recognize the ability of air duct systems to transfer smoke, toxic gases, and flame from area to area. Sometimes smoke can be of such quantity
A ROAD MAP FOR YOUR CODE, SMOKE BARRIER & SMOKE PARTITION REQUIREMENTS
A ROAD MAP FOR YOUR CODE, SMOKE BARRIER & SMOKE PARTITION REQUIREMENTS International Code Council National Fire Protection Association Underwriters Laboratories Inc. 5203 Leesburg Pike, Suite 600 1 Batterymarch
Fan Applications & System Guide
Fan Applications & System Guide Airflow for general ventilation can be calculated by; Area Method Air Change Method Occupancy Method Ventilation Calculation Methods Area Method Derives the ventilation
Exhaust Calculation Booklet
Exhaust Calculation Booklet American Dryer Corporation 88 Currant Road Fall River MA 02720-4781 Telephone: (508) 678-9000 / Fax: (508) 678-9447 e-mail: [email protected] ADC Part No. 450450 Exhaust
Duct Design. Presented by Dave Janquart
Duct Design Presented by Dave Janquart Overview of Topics Duct design Duct insulation SMACNA Standards Factors Influencing Duct Design Equipment Losses Air Velocity Duct Material Duct Size & Shape Length
PLASTIC VOLUME CONTROL DAMPERS OVERVIEW TYPE: GGB
OVERVIEW TYPE: GGB All composite construction Rigid extruded upvc aerofoil blade section Integral blade seals for low leakage operation Individual blades driven via reinforced styrene gear wheels in maintenance
Design Information. Designing Your Dust Collection System. Typical dust or fume collection system
Design Information Designing Your Dust Collection System There are five simple steps to designing an effective and efficient dust collection system. 1. Draw a floor plan of your shop Important Terms to
plenum slot diffusers
light powered Redefine your comfort zone. www.titus-hvac.com dual-function smart logic light powered energy solutions Table of Contents PLENUM SLOT IFFUSERS products Plenum Slot iffusers Products... 4
HVAC Air Duct Leakage. Eli P. Howard, III Group Director Technical Resources SMACNA
HVAC Air Duct Leakage Eli P. Howard, III Group Director Technical Resources SMACNA Key Variables that Affect the Amount of Leakage Static Pressure Amount of Duct Openings in the Duct Surface Seams, Joints,
DRYER VENTING SPECIFICATIONS DRYER SAFETY
DRYER VENTING SPECIFICATIONS Table of Contents DRYER SAFETY...1 INSTALLATION REQUIREMENTS...4 Venting Requirements...5 DRYER INSPECTION AND CLEANING...7 Frequency of Exhaust System Cleaning...7 Inspecting
The risk assessment of fire damper installations
The risk assessment of fire damper installations June 2010 Paul White OVERVIEW OVERVIEW The purpose of this presentation is to highlight that fire dampers form a key part of the passive fire protection
Ventilation Solutions Kitchens. fantech
Ventilation Solutions Kitchens 2 Kitchens Today s kitchens have become much more than a place for cooking and food preparation. The kitchen is the heart of the home. It s the center of activity for the
Gas Unit Heaters Duct Furnaces Horizontal - 60 HZ Form No. LF24-100-400 (10/2011) LF24 Standard
LF Standard Features Horizontal unit heaters are compact in design and easy to install. Steady State Efficiencies of up to 80.%. Ideal for economical commercial heating systems. Shipped completely assembled
Type 1 dryers: Domestic dryers to be used primarily in a family living environment. Residences Individual apartments or condominiums
Dryer Exhaust Systems Types of Clothes Dryers Type 1 dryers: Domestic dryers to be used primarily in a family living environment. Residences Individual apartments or condominiums Type Sub 2 Title dryers:
SECTION 11 78 13 MORTUARY REFRIGERATORS
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 11 78 13 MORTUARY REFRIGERATORS SPEC WRITER NOTE: Delete between //---// if not applicable to project. Also delete any other item or paragraph not applicable in
Fire and Smoke Dampers: Best Practice Design Tips. An AMCA International White Paper. July 2015
July 2015 Fire and Smoke Dampers: Best Practice Design Tips An AMCA International White Paper AMCA International 30 West University Dr. Arlington Heights, IL 60004 USA www.amca.org June 2015 This white
INSTRUCTIONS FOR HOW TO PROPERLY SELECT A FAN OR BLOWER
INSTRUCTIONS FOR HOW TO PROPERLY SELECT A FAN OR BLOWER The instructions that follow are to assist you in completing the information required when making a fan or blower selection. If you need additional
OVERALL CONVEYOR WIDTH STEEL ALUMINUM MODEL # PER FT. 10 FT. 5 FT. PER FT. 10 FT. 5 FT. PER FT. 10 FT. 5 FT. PER FT. 10 FT. 5 FT.
Pick Smarter. Pick Better. Pick UNEX. Skatewheel (SW) Skatewheel Gravity Conveyor is ideally suited to convey lightweight packages and where operations require portable or temporary conveyor lines such
Commercial Gas Furnace Upflow
Commercial Gas Furnace Upflow Model G24-200 80% A.F.U.E. 200,000 Btuh Input Heating Cap. 7.5 or 10 Tons Nominal Add-On Cooling GUK FEATURES Certified by A.G.A./C.G.A. Laboratories. Heavy gauge painted
AIR CONDITIONING PRODUCTS COMPANY
Quality Products Fixed Louvers AIR CONDITIONING PRODUCTS COMPANY all Shutter Backdraft Damper Ceiling Shutter Motorized Damper Fixed Louver Ga le Shutter Drainable Louver Supply Damper Fiberglass Shutter
DESIGN AND INSTALLATION OF RESIDENTIAL FLEXIBLE DUCTWORK SYSTEMS
DESIGN AND INSTALLATION OF RESIDENTIAL FLEXIBLE DUCTWORK SYSTEMS A. SCOPE 1. This information is intended to assist contractors, installers and code officials in the proper design and installation of flexible
EDD-401. Stationary Louver Dual Drainable Blade. Application and Design. Standard Construction
Application and Design is a weather louver designed to protect air intake and exhaust openings in building exterior walls. Design incorporates a drainable head member and stationary horizontal blades to
Tremco Fire Protection Systems Group Technical Bulletin
Compartmentalization products and design play a key role in protecting lives and property from fire. Understanding the tools and techniques available for firestopping is of utmost importance to designers,
Commercial Kitchen Fire Safety
Commercial Kitchen Fire Safety Commercial grade kitchens are a common feature found in many churches today, as religious institutions are providing meals for daycares, soup kitchens, meals on wheels and
Centrifugal Fans and Pumps are sized to meet the maximum
Fans and Pumps are sized to meet the maximum flow rate required by the system. System conditions frequently require reducing the flow rate. Throttling and bypass devices dampers and valves are installed
Equivalents & Conversion Factors 406 Capacity Formulas for Steam Loads 407 Formulas for Control Valve Sizing 408-409
Engineering Data Table of Contents Page No. I II Formulas, Conversions & Guidelines Equivalents & Conversion Factors 406 Capacity Formulas for Steam Loads 407 Formulas for Control Sizing 408-409 Steam
TECHNICAL GUIDE 95.5% SINGLE STAGE GAS-FIRED RESIDENTIAL MULTI-POSITION GAS FURNACES MODELS: TG9S DESCRIPTION FEATURES
TECHNICAL GUIDE 95.5% SINGLE STAGE GAS-FIRED RESIDENTIAL MULTI-POSITION GAS FURNACES MODELS: TG9S NATURAL GAS 40-130 MBH INPUT Due to continuous product improvement, specifications are subject to change
HVAC Control & Balancing Dampers Models VCD, MBD and RBD
HVAC Control & Balancing Dampers Models VCD, MBD and RBD Selection Construction Performance H* W* August 1 2013 HVAC Control and Balancing Dampers Commercial Control Dampers are used in buildings to regulate
DUCT SYSTEMS CHAPTER 6
CHAPTER 6 DUCT SYSTEMS SECTION 601 GENERAL 601.1 Scope. Duct systems used for the movement of air in air-conditioning, heating, ventilating and exhaust systems shall conform to the provisions of this chapter
A. Air-Conditioning and Refrigeration Institute: 1. ARI 850 - Commercial and Industrial Air Filter Equipment.
SECTION 23 40 00 - HVAC AIR CLEANING DEVICES PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Activated carbon filters. 2. Extended surface rigid air filter with synthetic media. 3. Disposable panel
Fire Barriers & Fire Stopping
Presented by: Bill Lauzon, PE Lauzon Life Safety Consulting, LLC 262-945-4567 [email protected] Web: Lauzon-LSC.com Environmental Part 2 Life Safety Code Chapter 8 Fire Barriers & Fire Stopping 1 Fire
VAV Laboratory Room Airflow The Lowdown on Turndown
Technology Report March, 2003 VAV Laboratory The Lowdown on Turndown Turndown comparison of these two turndown ratios. Note the small actual airflow difference between them. control ranges are normally
Element D Services Heating, Ventilating, and Air Conditioning
PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer
HVAC Duct Construction. Bob Wasilewski Project Manager, Technical Resources SMACNA
HVAC Duct Construction Bob Wasilewski Project Manager, Technical Resources SMACNA HVAC Duct Construction Standards WHAT? WHY? HOW? Today's Program 1 st 2 nd Edition HVAC-DCS Review Joints and Limitations
Dampers and Actuators Catalog
Dampers and Actuators Catalog > for the latest product updates, visit us online at johnsoncontrols.com > johnsoncontrols.com > Building Efficiency > Integrated HVAC Systems > HVAC Control Products > Rectangular
STANDARD FOR NON-FIRE RATED ROLLING DOORS
ANSI/DASMA 203-2004 AMERICAN NATIONAL STANDARD STANDARD FOR NON-FIRE RATED ROLLING DOORS Door & Access Systems Manufacturers Association, International Sponsor: 1300 Sumner Ave Cleveland, Ohio 44115-2851
FRAME PROFILE MASONRY METAL DOOR FRAME FLUSH MASONRY KD MITER CORNER JOINT. #8 Screw (MS002485) Required on all fire rated KD frames. Bend Tabs.
FRAME PROFILE MASONRY FLUSH MASONRY KD MITER CORNER JOINT Bend Tabs Head #8 Screw (MS002485) Required on all fire rated KD frames Corner Assembly 2" (50.8) Head Jamb Head Break Away Corner Clip Spot Welds
Fire Barrier Duct Wrap 15A
3 Fire Barrier Duct Wrap 15A Commerical Kitchen Grease Duct Fire Protection System Product Data and Installation Instructions Compliance 1998 Edition Complies with International Mechanical Code Complies
National System of Garage Ventilation s Engineering Guide
National System of Garage Ventilation s Engineering Guide In designing a fume removal system, it is extremely important to determine the following: 1. Type of apparatus to be exhausted (i.e. gasoline,
Vertical Break Parallel (VBP) / Vertical Break Slant (VBS)
August, 2009 Vertical Break Parallel (VBP) / Vertical Break Slant (VBS) Type VBPA (Aluminum) / Type VBPC (Copper) Type VBSA (Aluminum) / Type VBSC (Copper) PASCOR Air Break Switch Technology PASCOR offers
V47 Series Temperature Actuated Modulating Water Valves
V47 Series Temperature Actuated Modulating Water Valves Master Catalog 125 Valves, Miscellaneous (Other Than Gas) Section V Product Bulletin V47 Issue Date 0286 Application The V47 modulating valves regulate
PRE-ASSEMBLED INSTALLATION INSTRUCTIONS FOR PACB SERIES COAL FIRED OVENS
PRE-ASSEMBLED INSTALLATION INSTRUCTIONS FOR PACB SERIES COAL FIRED OVENS OVENS MANUFACTURED BY: EARTHSTONE OVENS-6717 SAN FERNANDO RD GLENDALE CA 91201 TELEPHONE: 800-840-4915 818-553-1134 FAX: 818-553-1133
Installation Manual. Rental Services. Air Handling Units CHS-SVN01A-EN. July 2008
Installation Manual Rental Services Air Handling Units July 2008 CHS-SVN01A-EN Copyright 2008 Trane All rights reserved This document and the information in it are the property of Trane and may not be
Model/Sprinkler Identification Numbers
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500 Series TY-L 5.6 and 8.0 K-factor Upright, Pendent, and Recessed Pendent Sprinklers Standard Response, Standard Coverage General Description
Damper Selection and Sizing
Damper Selection and Sizing SECTION OF ENGINEERING MANUAL OF AUTOMATIC CONTROL 77-1 Contents Introduction... 3 Definitions... 3 Damper Selection... 4 Damper Types... 4 Parallel and Opposed Blade Dampers...
RESIDENTIAL SPRINKLER INSTALLATION GUIDE
RESIDENTIAL SPRINKLER INSTALLATION GUIDE 4077 AIR PARK DRIVE STANDISH, MICHIGAN 48658 PHONE 989-846-4583 800-248-0278 FAX 989-846-9231 www.globesprinkler.com A-15 GLOBE RESIDENTIAL SPRINKLER GUIDE DESCR.,
CHAPTER 6 DUCT SYSTEMS
CHAPTER 6 DUCT SYSTEMS SECTION MC 601 GENERAL 601.1 Scope. Duct systems used for the movement of air in air-conditioning, heating, ventilating and exhaust systems shall conform to the provisions of this
ISSUE A, MAY 2008. Mechanical Release Fire Smoke Dampers. Model 2550. Advanced Air
ISSUE A, MAY 2008 Mechanical Release Fire Smoke Dampers Model 2550 Mechanical Release Fire Smoke Dampers - Type 2550 Mechanical Release Fire Smoke Dampers Type 2550 The model 2550 is designed to close
M7RL Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. High Efficiency / Direct Vent Condensing Downflow Gas Furnace
TECHNICAL SPECIFICATIONS M7RL Series High Efficiency / Direct Vent Condensing Downflow Gas Furnace Induced Draft - 9%+ AFUE Input 4,000 thru 7,000 Btuh The high efficiency downflow gas furnace is especially
ROOF TOP MOUNTED Air Handler Specification
ROOF TOP MOUNTED Air Handler Specification PART 1: GENERAL (Model RT) Mechanical Specification 1.01 WORK INCLUDED A. Provide complete air handling unit(s) suitable for outdoor installation. Contractor
SECTION 23 34 13. A. Horsepower: Do not increase or decrease fan motor horsepower without written approval from Engineer.
PART 1 GENERAL SECTION 23 34 13 HVAC FANS 1.01 SUMMARY A. Section Includes: 1. Exhaust fans. 2. Transfer fans. B. Related Documents: 1. Drawings and general provisions of the Contract, including General
Recirculating Roof Fans Models ESRMD, ESRMDF and ERD
Recirculating Roof Fans Models ESRMD, ESRMDF and ERD Four-Way Fan Exhaust Supply Mix Recirculate BUILDING VALUE IN AIR. October 2005 Recirculating Roof Fans Exhaust/Supply/Recirculation/Mix Model ESRMD
Retardants Inc. The Decision You Make May Save A Life! 123 Columbia Court North Suite 201 Chaska, MN 55318
Fire Barrier Moldable Putty+ Pads 123 Columbia Court North Suite 201 Chaska, MN 55318 952-448-7377 FAX:952-448-2613 e-mail: [email protected] Visit Our Web Site at www.fireretardantsinc.com Protecting
CH. 2 LOADS ON BUILDINGS
CH. 2 LOADS ON BUILDINGS GRAVITY LOADS Dead loads Vertical loads due to weight of building and any permanent equipment Dead loads of structural elements cannot be readily determined b/c weight depends
HVAC Code Requirements
one and two family dwellings? Answer: SECTION 2001: GENERAL 2001.1 Air supply. Fuel-burning equipment shall be provided with a supply of air for fuel combustion, draft hood dilution and ventilation of
Class II Type B2 Laminar Flow Biological Safety Cabinets at Ordering Criteria for the National Institutes of Health
Background Class II Type B2 Laminar Flow Biological Safety Cabinets at Ordering Criteria for the National Institutes of Health This document provides guidelines for the design and installation of Class
HVAC Air Duct Leakage. November 2013 Presented By: Mark Terzigni Project Manager Technical Services SMACNA
HVAC Air Duct Leakage November 2013 Presented By: Mark Terzigni Project Manager Technical Services SMACNA Learning Objectives Understand the difference between System leakage and Duct leakage Understand
CITYPLEX TOWERS BOILER INSTALLATION ORU RFP-1138
ALTERNATE No. 2 BFS LOCATION: Locate BFS North of B-3 on new house-keeping pad. HOUSE KEEPING PAD and DRAIN CONNECTIONS: Furnish house-keeping pad for new boilers B-2 and B-3 including trench drains to
How To Order A Direct Flow Air Cleaner
Reduced Volume - Improved Performance - Flexible Packaging The patented Direct Flow technology provides the flexibility to optimize the air system performance to size ratio, meeting the demands of today
The Basics of Commercial Kitchen Exhaust Cleaning
The Basics of Commercial Kitchen Exhaust Cleaning ANSI/IKECA C 10 ANSI/IKECA C 10: Standard for Cleaning of Commercial Exhaust Systems IKECA Introduces the Kitchen Exhaust Cleaning Industry s First American
AMCA Publication 511-10 (Rev. 11-13)
AMCA Publication 511-10 (Rev. 11-13) Certified Ratings Program Product Rating Manual for Air Control Devices AIR MOVEMENT AND CONTROL ASSOCIATION INTERNATIONAL, INC. The International Authority on Air
F-900 HOPEC Bench Hood Framed Vertical Sash
F-900 Series HOPEC Bench Hoods Product Features F-900 HOPEC Bench Hood Framed Vertical Sash The ISOLATOR HOPEC (Hand Operated Positive Energy Control) bench fume hood is based on the design of Jerry Koenigsberg*.
How to Measure HVAC System Airflow
How to Measure HVAC System Airflow About National Comfort Institute National Comfort Institute is an international training Since our and beginning development in 1994 company we have trained with and
INDEX. Chapter8. air master. Perforated Ceiling Diffusers
Chapter8 INDEX A. Perforated ceiling diffuser 1. Perforated ceiling diffuser with plenum box..: APCD+P...8.1. Perforated ceiling diffuser with damper....: APCD...8. Standard sizes...8. Fixing details...8.
Filterfans. Air Flow data: PF 1000 PF 2000 PF 2500 PF 3000 PF 5000 PF 6000 PF 7000
Filterfans Patented Click & Fit design provides a hardware free installation! Poured-in foam gasket allows for quick NEMA 12 sealing against the enclosure (except PF 1000) Plastic made from strong (ABS-FR),
T 3 Series VAV Diffusers Analog Diffuser Steel Square Panel Horizontal Pattern Model: T 3 SQ
TSQ--0 7-7-07 T Series VAV Diffusers Analog Diffuser Steel Square Panel Horizontal Pattern Model: T SQ Model Configuration T SQ- Heating / Cooling Border Type (Lay-In) Full Face Nominal Round Duct Size
NMSU FIRE DEPARTMENT Commercial Kitchen Fire Suppression Worksheet
This Commercial Kitchen Automatic Fire has been created to assure all documentation has been submitted to assist you in assuring proper plans and documentations has been submitted and reviewed by New Mexico
Services Enclosures and Protected Shafts - Maintaining Compartmentation
Introduction When a fire resisting element is used to provide fire compartmentation, every opening that allows services to pass through the element must be adequately protected by sealing, or fire stopping
Decree of the Ministry of the Environment on fire safety of ventilation systems
THE NATIONAL BUILDING CODE OF FINLAND MINISTRY OF THE ENVIRONMENT Housing and Building Department Decree of the Ministry of the Environment on fire safety of ventilation systems Adopted in Helsinki, 18
Model F822 thru F834 Mulsifyre Directional Spray Nozzles, Open, High Velocity General Description
Worldwide Contacts www.tyco-fire.com Model F thru F3 Mulsifyre Directional Spray Nozzles, Open, High Velocity General Description The Mulsifyre Nozzles are open (nonautomatic) nozzles and they are designed
#506 New Multi-Family Buildings & Additions Plan Intake Submittal Checklist
#506 New Multi-Family Buildings & Additions Plan Intake Submittal Checklist Case #: Date: Project Name: Site Address: Application Submittal Building permit applications and plans can be submitted to the
The Effect of Forced Air Cooling on Heat Sink Thermal Ratings
zpero 1 The Effect of Forced Air Cooling on Heat Sink Thermal Ratings By Paul Bachman, Fellow Engineer & Ronnie Haiduk, Applications Engineer, Crydom, Inc. ABSTRACT A heat sink s ability to dissipate thermal
SOHOline and SOHO Slimline The SOHOline and SOHO Slimline offer a modular, sturdy and compact design
SOHOline and SOHO Slimline The SOHOline and SOHO Slimline offer a modular, sturdy and compact design Ideal installation for; Offices Branch Offices Schools Computer Aided Classes Government Offices Hotels
KITCHEN AND BATH REMODELING BUILDING PERMIT REQUIREMENTS
St. Louis County Department of Public Works Division of Code Enforcement KITCHEN AND BATH REMODELING BUILDING PERMIT REQUIREMENTS This guideline is intended to provide the homeowner/contractor with the
IDES-EDU. Educational Package Ventilation. Lecture 8: Sizing mechanical ventilation systems IEE/09/631/SI2.558225 28.10.2011.
Introduction Educational Package Ventilation Lecture 8: Sizing mechanical ventilation systems IEE/09/631/SI2.558225 28.10.2011 Air Flow : Relation between air flow, air speed and duct section Ventilation
Fan Selection Application
Fan Selection Application Instructions for Air Turbine Propeller s Axial Fan Selection website www.axialfanselection.com \ Air Turbine Propeller Company 22329 Perry Highway - Zelienople, PA 16037 (724)
Pyroguard Wired Glass
Fire-rated Glass Pyroguard Wired Glass Where glass becomes architecture Section 15 03 Introduction Oldcastle Glass stocks nonwired Pyroguard laminated safety glass and polished wired glass for commercial,
Miami-Dade Qualified Drainable Blade Louvered Penthouse
Application and Design is a gravity intake or exhaust louvered penthouse. Model incorporates high performance horizontal drainable style blades. Meets the performance requirements established by the Florida
RAPID RESPONSE Model RSV-1 Residential Shut-Off Valve, 1 Inch and 2 Inch (DN25 and DN50) for Dual-Purpose Residential Water Supply General Description
Worldwide Contacts www.tyco-fire.com RAPID RESPONSE Model RSV-1 Residential Shut-Off Valve, 1 Inch and 2 Inch (DN25 and DN50) for Dual-Purpose Residential Water Supply General Description The TYCO RAPID
CITY OF LONG BEACH Department of Development Services BUILDING AND SAFETY BUREAU MECHANICAL PLAN REVIEW CHECKLIST
CITY OF LONG BEACH Department of Development Services BUILDING AND SAFETY BUREAU MECHANICAL PLAN REVIEW CHECKLIST PROJECT NO.: BMEC DATE: STATUS: INFORMATION PROJECT ADDRESS: WORK DESCRIPTION: APPLICANT
Design Options (Tradeoffs) Allowed by the 2012 Building Codes for Properties with Sprinkler Systems. April 2013
Design Options (Tradeoffs) Allowed by the 2012 Building Codes for Properties with Sprinkler Systems April 2013 The National Multi Housing Council and the National Apartment Association (NMHC/NAA) have
COMMERCIAL TYPE B GAS VENT MODEL E/V 10" 30"
OMMERIL TYPE GS VENT MODEL E/V 10" 30" www.eccomfg.com GS VENT 10" 30" EO INDEX DESRIPTION... 90 E/V PIPE ND FITTINGS 10" Model... 91 12" Model... 91 92 14" Model... 92 16" Model... 93 18" Model... 93
Steel Door Institute. Fire Rated Doors and Frames
Steel Door Institute Fire Rated Doors and Frames 1 1. Nomenclature and Overview 2. Fire Rated Frames 3. SDI 118 4. Fire Rated Doors 5. Fire Rated Hardware 6. Specialty Products Table of Contents 2 Fire
Performance Rating of Room Fan- Coils
ANSI/AHRI Standard 440 with Addendum 1 (Formerly ARI Standard 440) 2008 Standard for Performance Rating of Room Fan- Coils ANSI/AHRI STANDARD 440-2008 WITH ADDENDUM 1, PERFORMANCE RATING OF ROOM FAN-COILS
Operation and Installation Manual. Max Series
Operation and Installation Manual Max Series Models 95MAX 155MAX 155ECM 155MAXRX 200MAX 200MAXRX MAXTOP 195DCS 300DCS 200ERV 200ERVD New Auto Dehumidistat Function prevents unwanted use of the dehumidistat
Technical Information
Determining Energy Requirements - & Gas Heating & Gas Heating and gas heating applications can be divided into two conditions, air or gas at normal atmospheric pressure and air or gas under low to high
Doc Ref: 2015.06.01.002. 602.783.1112 baselayer.com 2015 BASELAYER TECHNOLOGY, LLC
TM 602.783.1112 baselayer.com 2015 BASELAYER TECHNOLOGY, LLC TM D400E Data Module (60Hz) The EDGE D400E is designed to meet high power density requirements for both the HPC and Web Scale environments while
FIRE ALARM SYSTEM. A. Shop drawings shall be submitted as follows: 1. Manufacturer's published literature. for aspproval.
Polk School District Specifications for the New Fire Alarm in the Existing Building Eastside Elementary School FIRE ALARM SYSTEM 1.01 SUBMITTALS A. Shop drawings shall be submitted as follows: 1. Manufacturer's
CE6500 Energy Recovery Ventilator
ADVANCED COMMERCIAL Energy Recovery Ventilator PRODUCT SPECIFICATIONS & TECHNICAL DATA Features NOMINAL CAPACITY 5500-7000 CFM CASING Double-wall cabinet White exterior paint, -gauge galvanized steel -gauge