installation & maintenance manual CFP 2/4/8 ZONE FIRE ALARM REPEATER PANEL approved document no. DFU rev 2
|
|
|
- Laurence Palmer
- 9 years ago
- Views:
Transcription
1 CFP 2/4/8 ZONE FRE ALARM REPEATER PANEL CFP 2/4/8 ZONE FRE ALARM REPEATER PANEL installation & maintenance manual approved document no. DFU731 rev 2 CFP REPEATER PANEL NSTALLATON & MANTENANCE MANUAL Approved Document No. DFU731 Rev 2 1
2 CFP 2/4/8 ZONE FRE ALARM REPEATER PANEL CONTENTS mportant Notes... 3 Basic Overview and Key Features... 4 First Fix... 5 Cable types and limitations...5 Mains wiring...5 Mounting the enclosure... 8 Second Fix... 8 nstalling the Power Supply PCB...8 Connecting the Mains...8 Connecting the Stand-by batteries...8 nstalling the Network Driver Card...1 Setting the Network Driver Card s address and segment number Connecting the Network wiring...12 nstalling the Main Control PCB...12 Fault Diagnosis Technical Specifications Errors & Omissions Excepted. The Manufacturer of this product operates a policy of continuous improvement and reserves the right to alter product specifications at its discretion and without prior notice. All of the instructions covered in this manual have been carefully checked prior to publication. However, no responsibility can be accepted by the Manufacturer for any inaccuracies or for any misinterpretation of an instruction or guidance note. 2 CFP REPEATER PANEL NSTALLATON & MANTENANCE MANUAL Approved Document No. DFU731 Rev 2
3 CFP 2/4/8 ZONE FRE ALARM REPEATER PANEL MPORTANT NOTES This equipment must only be installed and maintained by a suitably skilled and technically competent person. THS EQUPMENT S A PECE OF CLASS 1 EQUPMENT AND MUST BE EARTHED About this manual This nstallation & Maintenance Manual explains how to install, commission and maintain the Repeater Panel. t must be read in conjunction with the separate User Manual / Log Book and the main nstallation / Maintenance Manual, both of which are supplied with the Master panel. This Manual must not be left accessible to the User. System design Fire Alarm system design is beyond the scope of this document. A basic understanding of general Fire Alarm System components and their use is assumed. We strongly recommend that a suitably qualified and competent person is consulted in connection with the design of the Fire Alarm System and that the System is commissioned and serviced in accordance with the laid down specification and National standards. The Fire Officer concerned with the property should be contacted at an early stage in case he has any special requirements. We recommend you read BS 5839: Pt 1: 1988 Fire Detection and Alarm Systems for Buildings (Code of Practice for System Design, nstallation and Servicing) available at your local reference library or from the BS. Equipment guarantee This equipment is not guaranteed unless the complete system is installed and commissioned in accordance with the laid down National standards by an approved and competent person or organisation. Caution : mportant Notice WHEN CONNECTED, THE POWER SUPPLY PCB NSDE THE FRE ALARM PANEL STORES VOLTAGES AT UP TO 4Vd.c. AND MAY BE LETHAL F TOUCHED. DO NOT TOUCH THE PCB WHLST THE RED HAZARDOUS VOLTAGE PRESENT NDCATOR S LT. Anti-static handling guidelines Please ensure that the following electro-static handling precautions are taken immediately prior to handling the Panel s PCBs or any other static-sensitive components. Before handling any static-sensitive items, operators should rid themselves of any personal electrostatic charge by momentarily touching any sound connection to safety earth, e.g. a radiator. Always handle PCBs by their sides and avoid touching the legs of any components. PCBs should be stored in a clean, dry place which is free from vibration, dust and excessive heat. Retaining the PCBs in a suitable cardboard box will also guard them against mechanical damage. This product has been manufactured in conformance with the requirements of all applicable EU Council Directives. CFP REPEATER PANEL NSTALLATON & MANTENANCE MANUAL Approved Document No. DFU731 Rev 2 3
4 CFP 2/4/8 ZONE FRE ALARM REPEATER PANEL BASC OVERVEW & KEY FEATURES A maximum of eight Repeaters can be used per system, each with its own mains power supply and requiring its own battery-back-up supply. Each Repeater repeats the indicators of the Master panel and allows the User access to all Access Level 1 and Access Level 2 functions from remote parts of a site. Communication with the Master panel is achieved using network driver cards (one provided per Repeater), communicating over screened two-wire fire resistant cable of up to 1 km in length. To allow communication to take place, an additional network driver card must be fitted at the Master panel. The Repeater panel s enclosure is flush or surface mountable 4 CFP REPEATER PANEL NSTALLATON & MANTENANCE MANUAL Approved Document No. DFU731 Rev 2
5 CFP 2/4/8 ZONE FRE ALARM REPEATER PANEL FRST FX The Network wiring should be installed to meet BS 5839: Pt1: 1988 and BS 7671 (Wiring Regulations). Other National standards of installation should be used where pertinent. Cable types and limitations The Repeater network should be wired in two core screened fire resistant cable, each of the cores being of at least 1mm c.s.a. (E.g. Firetuff, Firecell, MCC or similar). The wiring should be laid out in a daisy chain configuration, i.e. not in a star, and with no spurs. End of line terminations are not required, and no special consideration is required for the positioning of the Main panel or the addressing order of the Repeaters. The total cable length should not exceed 1km. Please refer to the typical Repeater Network diagram shown below: Fig 1 : Typical Repeater Network Wiring Maximum distance = 1km REPEATER 1 MASTER REPEATER 2 REPEATER 5 REPEATER 8 SPUR WRNG NOT ALLOWED SPUR WRNG NOT ALLOWED = daisy chain wiring To avoid data corruption and earth loops, the Repeater network wiring screens should be connected to earth at the Master panel only. Power Supply Each repeater includes its own Power Supply that must be supplied locally from the Mains, and also requires a backup battery supply. The power is not drawn from the Master panel as this would demand much larger batteries in the Master panel and the connection of extra power carrying conductors. Mains wiring The requirement for the Mains supply to the Repeater is fixed wiring, using three core cable (no less than.75mm 2 and no more than 2.5mm 2 ) or a suitable three conductor system, fed from an isolating switch fuse spur, fused at 3A. This should be secure from unauthorised operation and be marked FRE ALARM: DO NOT SWTCH OFF. The Mains supply must be exclusive to the Repeater Panel. For information on how to connect Mains to the Panel s Power Supply PCB, see pages 8 and 9. CFP REPEATER PANEL NSTALLATON & MANTENANCE MANUAL Approved Document No. DFU731 Rev 2 5
6 CFP 2/4/8 ZONE FRE ALARM REPEATER PANEL Mounting the Enclosure Panel location The panel MUST be sited internally in an area which is NOT subject to conditions likely to affect its performance, e.g. damp, salt-air, water ingress, extremes of temperature, physical abuse, etc. t should be sited at a height where it is easily accessible and in a prominent position within the building. deally, the indicators on the front of the enclosure should be at eye level. Typical locations for repeaters are at alternative entrances to a building (the Master should always be fitted at the entrance most likely to be used by the emergency services), or on each floor of a multi-storey building. Enclosure details The repeater is supplied with a plastic detachable lid, a plastic back box and a three separate PCBs. The relative location of the PCBs are indicated in Figure 1 below: The Panel can be surface or semi-flush mounted. To expose the base mounting holes, the base PCBs must first be removed. Removing the lid and base PCBs PCBs are static-sensitive devices. We strongly advise that relevant anti-static handling precautions are observed when handling them (see page 3 for recommended guidelines). Figure 2 : Location of the Repeater Panel s base PCBs and removal details NETWORK DRVER CARD MAN CONTROL PCB To SK1 on the reverse of the Main Control PCB POWER SUPPLY PCB To SK2 on the reverse of the Main Control PCB or push tab and gently lift cable 1 Take the repeater panel out of its box and undo the four lid screws using the torx key provided. Remove the lid to expose the Main Control PCB (the Power supply PCB and Network Driver Card are located underneath). 2 Carefully remove the five retaining screws on the Main Control PCB and slide the PCB up and over the mounting pillars, taking care not to damage any of the components. 3 Disconnect the telecoms-style connecting cables at on the Power Supply PCB and on the Network Driver Card, making sure that the cables remain connected to the reverse of the Main Control PCB to prevent them being misplaced. Care should be taken when detaching this connector to depress the locking tab to prevent damage. 4 Disconnect the 2-way polarised loom from on the Power Supply PCB and pull the Power Supply s earth strap off the spade connector at the main chassis earth point. 5 Carefully remove the three retaining screws on the Power Supply PCB and slide the PCB up and over the mounting pillars, again taking care not to damage any of the components. 6 Carefully remove the two retaining screws on the Network Driver Card and slide the cardup and over the mounting pillars, again taking care not to damage any of the components. 6 CFP REPEATER PANEL NSTALLATON & MANTENANCE MANUAL Approved Document No. DFU731 Rev 2
7 CFP 2/4/8 ZONE FRE ALARM REPEATER PANEL We recommend the lid and PCBs are now removed from site to prevent accidental damage. Storing the PCBs in a suitable cardboard box will also guard them against mechanical damage. Removing the knock-outs Decide carefully how the network wiring will be brought into the panel with reference to figure 3 below and remove the required knock-outs for cable entry. The knock-outs should be removed with a sharp tap in the rim of the knock-out using a flat broad-bladed screwdriver. Use of excessive force could damage the enclosure around the knock-out. Always ensure if a knock-out is removed, the hole is filled with a good quality cable gland. Any unused knock-outs must be securely blanked off. t is essential that the 23Va.c. Mains cable is fed into the enclosure via one of the inlets at the top right hand corner of the enclosure. (For further CRTCAL information on Mains connection please refer to Connecting the Mains on Pages 8 and 9). Fixing the base to the wall Figure 3 : nternal view of back box with PCBs removed / side view for flush mounting 365mm 75mm includes 'dimples' 22mm WALL Using the five mounting holes provided, fix the base securely onto/into the wall. The mounting holes are suitable for use with No.8 roundhead or countersunk woodscrews. Assess the condition and construction of the wall and use a suitable screw fixing. Any dust or swarf created during the fixing process must be kept out of the repeater panel and great care must be taken not to damage any wiring or components. CFP REPEATER PANEL NSTALLATON & MANTENANCE MANUAL Approved Document No. DFU731 Rev 2 7
8 CFP 2/4/8 ZONE FRE ALARM REPEATER PANEL SECOND FX Connecting the panel Connecting the repeater panel s internal connections and PCBs is best undertaken immediately prior to Commissioning. Before you begin, we recommend cable integrity is verified throughout the installation. mportant: DO NOT use an insulation tester ( Megger ) with any network drivers connected. Faults occurring in the wiring which are not picked up at this stage will almost certainly result in spurious and intermittent faults when the equipment is energised. nstalling the Power Supply PCB The Power Supply PCB combines the functions of a Mains to d.c. switched mode power supply unit, battery charging unit and battery monitoring unit. WHEN CONNECTED, THE POWER SUPPLY PCB STORES VOLTAGES AT UP TO 4Vd.c. AND MAY BE LETHAL F TOUCHED. DO NOT TOUCH THE PCB WHLST THE RED HAZARDOUS VOLTAGES PRESENT NDCATOR S LT. Under no circumstances should the repeater panel be operated without the Power Supply PCB correctly mounted in the panel s enclosure and the three retaining screws securely tightened. The PCB should be positioned in the panel as shown in Figure 4 on Page 9. Connecting the Mains The general requirement for the Mains supply to this equipment is described on Page 5. DO NOT attempt to connect Mains to the panel until you are fully conversant with the layout and features of the Power Supply PCB, as described above and in Figure 4 on Page 9. The incoming Mains cable should be brought into the panel at the top right hand side of the enclosure and terminated at the connector block (CONN1) on the Power Supply PCB. Make sure the Mains earth wire is connected directly to this connector block and NOT to the secondary base earth post which is provided for making off detector and sounder circuit screens. The Power Supply PCB s earth strap MUST be connected to the spade on the chassis earth post before operation. The spade is compressed against a shoulder on the post via the lowest nut. The earth post may appear loose, this intended by design. Connecting the stand-by batteries Two new, good quality and fully charged 12V Valve Regulated Lead Acid batteries are required as the emergency stand-by power supply for the repeater panel. Caution: No other type of batteries should be used due to risk of explosion. The batteries should be connected in series and located in the repeater s enclosure as shown in Figure 5. The battery leads, link wire and nylon tie wraps are provided in the panel s accessory pack. Run the battery leads through the slits in the panel s lower plastic ribs and secure the batteries into position using the nylon tie-wraps as shown. The panel s sophisticated battery monitoring unit protects the batteries against deep discharge by activating a cut off circuit when the stand-by supply voltage reaches 21V approx. f batteries are not fitted, are discharged or in poor condition, a PSU Fault will show at the repeater panel. The capacity of the batteries used in the repeater will depend upon the required stand-by time. For 24 hour stand-by use 1.2A Hr batteries. For 72 hour stand-by use 2.1 A Hr batteries. These capacities take into account an ageing factor over a battery life of 5 years. Battery capacity for Master panels depends on other factors and therefore larger sized batteries may be required, see main panel installation instructions for details. Always dispose of used batteries according to the battery manufacturer s instructions. 8 CFP REPEATER PANEL NSTALLATON & MANTENANCE MANUAL Approved Document No. DFU731 Rev 2
9 CFP 2/4/8 ZONE FRE ALARM REPEATER PANEL Figure 4 : Power Supply PCB layout and mains connection details ncoming Mains cable must be segregated from other cables and should only enter the Panel through either of these knock-outs. Good quality cable glands must always be fitted. L N L N PRMARY FUSE F1 FUSE CONN1 L = Live; N = Neutral, = Earth. PSU earth strap Do not operate the Panel without this strap connected 1ATH 25V HRC The incoming mains earth wire must be connected to the terminal marked and not to the base earth post. (The PSU earth strap connects the PCB to the base earth post). Primary fuse (F1) 2 x 5mm 1A HRC Ceramic to EC 127 (EN6127 Part 2). Do not use any other type or size of fuse in this position. Battery fuse (F2) 2 x 5mm 1A6 F to EC 127 (EN6127 Part 2). Do not use any other type or size of fuse in this position. Battery leads (supplied in the Panel s accessory pack). See below for connection details. DO NOT ADJUST BATTERY FUSE 1.6AF + Red To Battery Black BAT1 PLK2 AUX 24V To Main Control PCB Hazardous voltages present light When lit red, hazardous voltages will be present on the components in the shaded area of the PCB. DO NOT TOUCH. Certain components are charged to this hazardous voltage during operation, and this charge is bled away after the mains supply has been removed. When the red light extinguishes, the charge has leaked away to a safe level. Figure 5: Battery location and connection details for repeaters Link wire Nylon tie wraps + Run the battery leads (supplied in the Panel's accessory pack) through the slits in the plastic ribs LOCATON OF SMALL SZED BATTERES typically 1.2 AHr LOCATON OF MEDUM SZED BATTERES typically 2.1 AHr CONNECTON OF LEADS TO POWER SUPPLY PCB Note: larger batteries (up tp 3.3 Ahr in size) will fit in the enclosure. However, these would normally only be used in master panels -refer to the main panel instructions for further details. CFP REPEATER PANEL NSTALLATON & MANTENANCE MANUAL Approved Document No. DFU731 Rev 2 9
10 CFP 2/4/8 ZONE FRE ALARM REPEATER PANEL nstalling the Network Driver Card The repeater s Network Driver Card must be securely positioned inside the repeater panel as shown in Figure 6 (below) using the two retaining screws provided. Figure 6 : Fitting the Network Driver Card A B C A B NETWORK DRVER CARD To SK1 on the reverse of the Main Control PCB POWER SUPPLY PCB mportant: Before installing the Network Driver Card, isolate the Mains supply and disconnect the panel s battery back-up supply. (Mains can be removed by carefully pulling the 5mm connector block, CONN1, from the Power Supply PCB). To SK2 on the reverse of the Main Control PCB Connect the two-way polarised power supply loom between on the Network Driver Card and on the Power Supply PCB as shown. An additional Network Driver Card must also be fitted at the Master panel. This should be installed in exactly the same way as above UNLESS the Master panel has a Relay Output Board fitted, in which case Figure 7 (below) should be referenced instead. Figure 7: Fitting the Network Driver Card to a Master Panel with a Relay Output Board A B C A B NETWORK DRVER CARD PL3 To SK1 on the reverse of the Main Control PCB RELAY OUTPUT CARD PL4 To SK2 on the reverse of the Main Control PCB POWER SUPPLY PCB mportant: Before installing the Network Driver Card, isolate the Mains supply and disconnect the Panel s battery back-up supply. (Mains can be removed by carefully pulling the 5mm connector block, CONN1, from the Power Supply PCB). When fitting a Network Driver Card to a Master Panel which has a Relay Output Board fitted:- Connect the Network Driver Card s two-way power supply loom between on the Network Driver Card and on the Relay Output Board. Connect the Network Driver Card s telecoms-style data connection cable between on the Network Driver Card and on the Relay Output Board. f in doubt, please refer to the instructions supplied with the Relay Output Board itself. MPORTANT: Before proceeding to fit the repeater and Master panel s Main Control PCBs, you must first assign their Network Driver Cards with an address and segment number, as described on page CFP REPEATER PANEL NSTALLATON & MANTENANCE MANUAL Approved Document No. DFU731 Rev 2
11 CFP 2/4/8 ZONE FRE ALARM REPEATER PANEL Setting the Network Driver Card s address and segment number The Master panel monitors any repeaters connected to it by periodically checking their address numbers. Each repeater must therefore have its own unique address number assigned to it, as should the Master panel itself. Also, for future expansion, every Network device must be identified by means of its Segment. All repeaters (and the Master panel) must belong to the same Segment and we suggest that Segment number 1 is used throughout the repeater network. Up to eight repeaters may be connected to one Master panel. Their Address and segment numbers, and those of the Master, are set via the 8 Way switch on the Network Driver Card, as detailed in Figure 8 below:- Figure 8 : Network Driver Card Address and Segment numbers ON NETWORK DRVER CARD DP SWTCH BNARY SEGMENT BNARY ADDRESS DECMAL SEGMENT DECMAL ADDRESS addresses 9 to 14 are not used due to a limit of 8 repeaters per CFP master EXAMPLE ON SEGMENT ADDRESS }= 1 }= 3 ADDRESS 15 RESERVED FOR MASTER PANEL ONLY Please note that address must not be used and that the Master panel s address must always be set at 15. The addresses of the repeaters do not need to run sequentially, i.e. it is permissible to have just repeater addresses 2 and 5 on the system. However, no two repeaters should have the same address. Repeaters can also be addressed in any order on the Network wiring. Network Driver Cards only read their 8 Way switches when they are powered up, so changing their addresses whilst they are powered up has no effect. The Master panel looks for the presence of repeater panels all the time. Once a repeater is seen, but then disappears, the Master panel shows this as a fault. See fault diagnosis section on page 13 for further details. f a repeater needs to be removed from the system, simply remove the power from the system, disconnect the repeater, then power the system back up. The Master panel will now only see the repeaters that are left on the system. CFP REPEATER PANEL NSTALLATON & MANTENANCE MANUAL Approved Document No. DFU731 Rev 2 11
12 CFP 2/4/8 ZONE FRE ALARM REPEATER PANEL Connecting the Network wiring Connect the network wiring to the relevant Network Driver Cards as illustrated in Figure 9 below. (t should be noted that the network driver cards terminal blocks can be removed from their PCBs for ease of installation). At the Master panel only, all network earth screens should be adequately insulated and connected to the base earth post as shown. The base earth must then be connected to terminal C on the master panel s Network Driver Card. At Repeater panels, all incoming and outgoing network earth screens should be connected to terminal C only. DO NOT connect the screens to the repeater s base earth post and DO NOT connect the repeater s base earth post to terminal C. Figure 9: Typical Network Wiring AT REPEATERS, CONNECT A TO A, B TO B & TERMNATE NCOMNG AND OUTGONG EARTH SCREENS TO TERMNAL C TO NEXT REPEATER F REQURED A B A B A B A B A BCAB A BCAB TO NEXT REPEATER F REQURED SET REPEATER ADDRESS AND SEGMENT NUMBER AS DETALED ON PAGE 11 REPEATER PANEL NETWORK DRVER CARD SET REPEATER ADDRESS AND SEGMENT NUMBER AS DETALED ON PAGE 11 REPEATER PANEL NETWORK DRVER CARD! TERMNATE EARTH SCREENS TO THE BASE EARTH PONT AT THE MASTER PANEL ONLY. A B C A B MASTER PANEL NETWORK DRVER CARD crimped connection nut washers SET MASTER PANEL'S ADDRESS AND SEGMENT NUMBER AS DETALED ON PAGE 11 (ADDRESS NO. MUST BE 15) Do not untighten lower nut MASTER PANEL nstalling the Main Control PCB When all of the Network wiring is in place, the repeater s Main Control PCB can be securely positioned inside the panel using the five retaining screws. (solate the Mains supply and disconnect the battery back-up supply before you do this). As the PCB is presented to the panel, remember to attach the two telecoms-style connecting cables to the Power Supply PCB and Network Driver Card PCB as described below: SKT1 on the reverse of the Main Control PCB to on the Power Supply PCB SKT2 on the reverse of the Main Control PCB to on the Network Driver Card On Master panels only, if a Relay Output Card is fitted, SKT2 on the Main Control PCB should be connected to on the Relay Output Card. CAUTON: Do not connect the two telecom style cables incorrectly as this will cause irrepairable damage to the Main Control PCB when the panel is powered up. f in doubt, refer to figures 6 and 7 on page 1. When all ofthe PCBs are correctly in place, reapply power and test the system for correct operation. 12 CFP REPEATER PANEL NSTALLATON & MANTENANCE MANUAL Approved Document No. DFU731 Rev 2
13 CFP 2/4/8 ZONE FRE ALARM REPEATER PANEL FAULT DAGNOSS Overview f a repeater loses power, but is still connected to the network, it will not stop the rest of the repeater network operating. However, short and open circuits on the network wiring will cause complete or partial loss of communication between the Master panel and the Repeaters. The Master panel s Repeater Fault light flashes yellow when it cannot communicate with one or more repeaters. To ascertain which of the repeater panels are faulty:- 1. Remove the Master panel s lid and press the Access Level Three Functions button on the Main Control PCB to gain access to the panel s Engineer functions (see below). SYSTEM FAULT SW8 REPEATER FAULT HEAD OUT OPEN CRCUT SHORT CRCUT CONCDENCE DELAYS TEST ACCESS NONLATCHNG LEVEL THREE FUNCTONS 2. Continue pressing the Access Level Three Functions button until the Repeater Fault light pulses. Any existing zone fault indicators are suppressed and the zone indicator(s) corresponding to the repeaters in Fault are illuminated. For example, if repeater 2 and 7 are faulty, the Fault indicators for zones 2 and 7 will be lit. To escape Access Level Three press the Escape Access button at any time. Repeater Power Supply Faults Failure of a repeater panel s PSU is shown locally and is indicated by the Repeater s Power Supply Fault indicator flashing yellow. A Power Supply Fault is indicative of one or more of the following faults. Pages 8 & 9 of this manual must be referenced when carrying out any of the suggested action described below. The Mains supply is too low or has failed completely. Symptoms: the panel runs on batteries, but not on Mains. The red hazardous voltages present light on the Power Supply PCB is lit. Suggested action: (a) solate the Mains supply and remove the Mains connector block (CONN1) from the Power Supply PCB. (b) Position the connector block so that the live and neutral connections can be probed. Taking all due precaution, reapply the Mains and measure the voltage. (c) solate the Mains supply again. f the reading was incorrect (see Technical Specifications, page 14) repair the Mains supply. f the reading was correct, check again to see if the red hazardous voltages present light on the Power Supply PCB is lit. f it is and the panel still doesn t run on Mains, the Power Supply PCB is faulty and should be replaced. The Primary Mains fuse (F1) is ruptured. Symptoms: the panel runs on batteries, but not on Mains. The red hazardous voltages present light on the Power Supply PCB is off. Suggested action: (a) solate the Mains supply, remove the Main Control PCB and check the PSU s Primary Mains fuse (F1) for continuity. (b) f the Fuse is ruptured it will be due to excessive Mains surge or a PSU fault. Check the components on the PSU for damage. f none is found replace the fuse with the correct type and reconnect the Mains supply. f the red hazardous voltages present light does not come on with 22V Mains applied and a good fuse, then the PSU is faulty and should be replaced. (continued overleaf) CFP REPEATER PANEL NSTALLATON & MANTENANCE MANUAL Approved Document No. DFU731 Rev 2 13
14 CFP 2/4/8 ZONE FRE ALARM REPEATER PANEL The Battery Fuse (F2) is ruptured. Symptoms: the panel runs on Mains, but not on batteries. Suggested action: (a) solate the Mains supply and disconnect the batteries. (b) Remove the Main Control PCB and check the Battery Fuse (F2) on the Power Supply PCB for continuity. (c) f the fuse is ruptured check the Power Supply PCB and Main Control PCB for signs of damage. f none is found, replace the Fuse with the correct type, ensuring that the fuse clip is not damaged when re-inserting the fuse. (d) Refit the Main Control PCB and reconnect the batteries. f the green Supply Present light is lit, reconnect the Mains supply and check that the power supply fault has cleared. f the Supply Present light is not lit, either the Power Supply PCB or the Main Control PCB is faulty and should be replaced. (e) f the Battery Fuse (F2) is intact, proceed to check the battery voltage (see below). The Battery voltage is too low. Symptoms : the Panel runs on Mains, but may or may not run on batteries. f the Mains supply has failed and the battery supply has been discharged to the point where the voltage is too low (i.e less than 21V), the panel will automatically turn off to avoid damaging the batteries by allowing them to deep discharge. The panel will not restart unless fresh, fully charged batteries are connected, or the Mains supply is restored. CFP REPEATER PANEL TECHNCAL SPECFCATONS Mains supply voltage 23 V ±1% 5/6Hz nternal power supply 27Vd.c.Nominal Supply and battery charger monitored for failure YES (battery charger is also temperature compensated) Batteries monitored for disconnection & failure YES Batteries protected against deep discharge YES (Deep discharge cut off approx. 21 Volts) Battery size and type (for 24 hours stand-by) 2 x 12V 1.2A Hr VRLA (Valve Regulated Lead Acid) connected in series Battery size and type (for 72 hours stand-by) 2 x 12V 2.1A Hr VRLA (Valve Regulated Lead Acid) connected in series Mains Fuse 24V 1A HRC Ceramic 2mm compliant to EC (EN6127 PT2) Battery Fuse 1.6A F 2mm compliant to EC (EN6127 PT2) Maximum network cable length 1 km Physical size / Dimensions Size = 38 x 235 x 96mm appox; Weight (without batteries) 1.75kg OPERATNG CONDTONS Operating conditions All components are selected to operate within their specification when conditions outside the enclosure comply with class 3k5 of EC : to +4 C 14 CFP REPEATER PANEL NSTALLATON & MANTENANCE MANUAL Approved Document No. DFU731 Rev 2
CFP 2/4/8 ZONE ECONOMY FIRE ALARM CONTROL PANEL. installation & maintenance manual. Approved Document No. DFU7002030 Rev 1
CFP 2/4/8 ZONE ECONOMY FIRE ALARM CONTROL PANEL installation & maintenance manual Approved Document No. DFU7002030 Rev 1 CFP 2/4/8 ZONE ECONOMY FIRE ALARM PANEL CONTENTS Basic Overview and Key Features...3
LPCB APPROVED CFP 2/4/8 ZONE FIRE ALARM CONTROL PANEL. installation & maintenance manual. Approved Document No. DFU7004010 Rev 1
LPCB APPROVED CFP 2/4/8 ZONE FIRE ALARM CONTROL PANEL installation & maintenance manual Approved Document No. DFU7004010 Rev 1 CONTENTS EN54 Compliance Statement...3 Basic Overview & Key Features...3 Important
BARDIC. 4 & 8 Zone Fire Panels Zircon range. Data, installation, operation and maintenance. by Honeywell
Data, installation, operation and maintenance 4 & 8 Zone Fire Panels Zircon range BARDIC by Honeywell LED flashing LED Continuous FAULT DISABLE/TEST Power General Fault Sounder Fault/ Disable System Fault
INTRODUCTION. The data provided is for The Standard Products and any variation will be dealt with at the end of this manual.
INTRODUCTION The information provided herein covers the range of products known as the 'Sensor 901' series. The range of equipment is designed to meet the requirements of BS 5839 parts 1 & 4 1988. The
FIREvac VOICE ALARM CONTROL PANEL INSTALLATION & MAINTENANCE MANUAL
FIREvac VOICE ALARM CONTROL PANEL INSTALLATION & MAINTENANCE MANUAL Page 2 of 41 FIREvac Voice Alarm Control Panel Installation & Maintenance Manual This manual details the operation of: FIREvac Voice
VoCALL - CFVCM/CFVCWM & CFVCX8. Fire Telephone & Disabled Refuge Network System. User Manual & Log Book
VoCALL - CFVCM/CFVCWM & CFVCX8 Fire Telephone & Disabled Refuge Network System User Manual & Log Book VoCALL Fire Telephone & Disabled Refuge Network System Introduction A VoCALL Emergency Voice Communications
HM-W536 Install Guide
HM-W536 Install Guide 9/13/2013 IMPORTANT SAFETY INSTRUCTIONS Warning - When using electrical devices, basic safety precautions should be followed to reduce the risk of fire, electrical shock or injury.
3. MOUNTING THE FIRE ALARM PANEL... 7 3.1 PLANNING CABLE ENTRY 3.2 FIXING THE BACKBOX TO THE WALL
INSTALLATION MANUAL CONTENTS 1. INTRODUCTION. 3 1.1 HANDLING THE PCBS 1.2 USING THIS MANUAL 1.3 ABOUT THE PREMIER SX FACP & INTEGRAL PSE 1.4 DESIGNING THE SYSTEM 1.5 EQUIPMENT GUARANTEE 2. FIRST FIX GUIDELINES.
MIC-WKT and MIC-WKT-IR
MIC-WKT and MIC-WKT-IR Installation Manual Bosch Security Systems EN Installation and Operation Manual MIC-WKTI and MIC-WKT-IR Installation Manual EN 2 MIC-WKT and MIC-WKT-IR Washer Pump Drive Card Kits
CB200W Water Leak Detection Panel Application Guide
Checked by: AJC Approved by: JBJ Contents CB200W Water Leak Detection Panel Application Guide 1. Cabinet Specifications... 2 2. Panel Hardware Specifications... 3 3. Panel Configuration... 4 4. Technical
INFINITY 8 INSTALLATION MANUAL FIRE ALARM CONTROL PANEL INSTALLATION MANUAL
FIRE ALARM CONTROL PANEL INSTALLATION MANUAL Approved Document No. GLT-201-7-1 CONTENTS 1. INTRODUCTION... 1.1 HANDLING THE PCBS... 1.2 USING THIS MANUAL... 1.3 ABOUT THE INFINITY FIRE ALARM CONTROL PANEL
Drayton Digistat +2RF/+3RF
/+3RF Programmable Room Thermostat Wireless Model: RF700/22090 Model: RF701/22092 Power Supply: Battery - Thermostat Mains - Digistat SCR Invensys Controls Europe Customer Service Tel: 0845 130 5522 Customer
LD2 One & Two Zone Water Detection Alarm Installation and Operation Manual
CMR Electrical Ltd Bolton House Five Chimneys Lane Hadlow Down East Sussex TN22 4DX Tel: 01825 733600 LD2 One & Two Zone Water Detection Alarm Installation and Operation Manual Contents 1) Operation 2)
SELECTION, APPLICATION AND MAINTENANCE
DIESEL PROTECTION SYSTEMS Automatic Diesel Engine Shut Down System for Safe Area Applications SELECTION, APPLICATION AND MAINTENANCE Series 300 Series 310 SYSTEM DESCRIPTION Suitable for attended engine
12 Volt 30 Amp Digital Solar Charge Controller Installation & Operation Manual
12 Volt 30 Amp Digital Solar Charge Controller Installation & Operation Manual This 30Amp charge controller is designed to protect your 12Volt Lead-acid or Gel-cell battery from being overcharge by solar
WD-AMX Water Detection Controllers
Page 1 of 5 WD-AMX Water Detection Controllers Features: Benefit: LED Status of leak status VFC output Audible alarm Auto or manual reset alarm output Uses an isolated AC signal which prevents oxidation
FIREDEX 2200. Conventional Fire Panels
68 Flexible, high specification system Choice of 1, 2, 4 or 8 zones Simple one-shot auto-reset user test facility Approved to EN54 Maintenance free poly switch circuit protection, with auto reset Class
EVC40 EMERGENCY VOICE COMMUNICATION SYSTEM
EVC40 EMERGENCY VOICE COMMUNICATION SYSTEM INSTALLATION MANUAL Protec Fire Detection PLC, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT. Telephone: +44 (0) 1282 717171 Fax: +44 (0) 1282 717273
INFRARED QUARTZ WALL HEATER
INFRARED QUARTZ WALL HEATER MODEL NO: IQ2000 PART NO: 6939004 MOUNTING & OPERATION INSTRUCTIONS GC0715 INTRODUCTION Thank you for purchasing this CLARKE Infrared Wall Heater. Before attempting to use this
Packard Bell Easy Repair
Your digital playground Packard Bell Easy Repair EasyNote MX Series Hard Disk Drive Repair Instructions www.packardbell.com Your digital playground Important Safety Check Instructions You must read all
12 Volt 30 Amp Digital Solar Charge Controller
12 Volt 30 Amp Digital Solar Charge Controller User s Manual WARNING Read carefully and understand all INSTRUCTIONS before operating. Failure to follow the safety rules and other basic safety precautions
(68.52) X. June 2000 Supercedes February 2000. xenex CONVENTIONAL FIRE DETECTION & ALARM SYSTEM. we look @ business differently
(68.52) X June 2000 Supercedes February 2000 xenex CONVENTIONAL FIRE DETECTION & ALARM SYSTEM.... we look @ business differently XENEX SYSTEM ARCHITECTURE Note: This schematic is for guidance only please
Operating Instructions
Important information: These instructions contain safety information, read and follow them carefully. Dialight will not accept any responsibility for injury, damage or loss which may occur due to incorrect
Installation and Operation Manual
GST102 GST104 Conventional Alarm Control Panel nstallation and peration Manual (ssue3.03, November 2005) nstallation and peration Manual The ntelligent Solution CNTENTS 1 General... 1 2 Technical Specifications...
TS510 & TS500. Installation & User Guide. Compatible Equipment
Installation & User Guide Compatible Equipment TS510 REM - Remote Keypad 9040 - Loudspeaker DC54/58 - Digital Communicator SD1+ - Speech Dialler 496525 Issue A 1 of 10 TS510 and TS500 Overview Introduction
Conventional Fire Detection and Extinguishant Control System Specification
Conventional Fire Detection and Extinguishant Control System Specification Page 1 of 9 Scope Furnish a complete 24VDC Conventional, electrically supervised, combined fire detection and extinguishant release
ST Series POWER SUPPLIES USER INSTRUCTIONS
Introduction These instructions detail the installation and operation requirements for the ST20 & ST35 power supplies. These have been designed for operation in RV s providing a DC power system, with optional
Single Channel Loop Detector
Single Channel Loop Detector Model - LD100 Series The LD100 is a single channel inductive loop detector designed for parking and access control applications. The detector is connected to an inductive loop
victron energie USER MANUAL GEBRUIKSAANWIJZING GEBRAUCHSANWEISUNG Victron Atlas 12/850
victron energie USER MANUAL GEBRUIKSAANWIJZING GEBRAUCHSANWEISUNG Victron Atlas 12/850 SECTIONS ENGLISH 1 NEDERLANDS 27 DEUTSCH 55 This page intentionally left blank. ENGLISH USER MANUAL Victron Atlas
MULTI XS 3600. Battery charger. For lead-acid batteries 1,2-120Ah
MULTI XS 3600 Battery charger For lead-acid batteries 1,2-120Ah User s Manual and a guide to professional battery charging For Starter/Deep Cycle batteries EN INTRODUCTION Congratulations on your purchase
TOYOTA Tundra 2007 - BACK-UP CAMERA SYSTEM Preparation
Preparation Part Number(s): PT233-34070, PT923-35070-11, PT923-35070-43 NOTE: Part number of this accessory may not be the same as part number shown. Back Up Monitor Kit Contents PT923-35070-11 / PT923-35070-43
When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description
Samba OPLC SM35-J-R20 Installation Guide The Unitronics SM35-J-R20 offers the following onboard I/Os: 12 Digital Inputs, configurable via wiring to include: 1 HSC/Shaft-encoder Input, 2 Analog inputs (only
REB 1 REB 3 REB 5 REB 6 REB 8 REB 10 REB 12 REB 16
REB 1 REB 3 REB 5 REB 6 REB 8 REB 10 REB 12 REB 16 Manually Operated Electronic Speed Controller Single Phase For all applications using suitably specified single-phase induction motor fans 1 GENERAL The
INSTALLATION & SERVICE MANUAL. Display Panel
INSTALLATION & SERVICE MANUAL Display Panel The PowerLine EMS TM is a specialized power distribution and energy management system intended to be used in recreational vehicles. The Control Module is housed
INSTALLATION GUIDE. Card Reader & Controller with KIM Swipe Reader for Solitaire 850 / 950 / 850L Learnlok PK2930
INSTALLATION GUIDE Card Reader & Controller with KIM Swipe Reader for Solitaire 850 / 950 / 850L Learnlok PK2930 Card Reader and Controller Model 3.5 with KIM Swipe Reader Table of Contents 1. Features..................................
WATER LEAK DETECTION SYSTEM WLDS-10 INSTALLATION & COMMISSIONING
WATER LEAK DETECTION SYSTEM WLDS-10 INSTALLATION & COMMISSIONING DESCRIPTION: An electronic control panel used in conjunction with one pulse meter (water meter with pulse output proportional to flow rate)
FIRERAY 2000 Installation Guide
FIRERAY 2000 Installation Guide Features Range 33ft to 330 ft. 24Vdc operation Selectable alarm thresholds Low current consumption Ground level electronics Manual or Automatic reset System Description
Alarm over IP. IRIS Touch Home Installation Manual. Version 1.0 ENGLISH. Now certified and compliant with EN50131, EN50136 Security Grade 4 ATS6
Alarm over IP IRIS Touch Home Installation Manual Version 1.0 ENGLISH Now certified and compliant with EN50131, EN50136 Security Grade 4 ATS6 1. Introduction No more bulky batteries, just one sleek unit
TIG INVERTER INSTRUCTION MANUAL
TIG INVERTER INSTRUCTION MANUAL Contents Warning General Description Block Diagram Main Parameters Circuit Diagram Installation and Operation Caution Maintenance Spare Parts List Troubleshooting 3 4 4
SHOT BLAST CABINET MODEL NO: CSB20B
SHOT BLAST CABINET MODEL NO: CSB20B PART NO: 7640110 USER INSTRUCTIONS GC0216 INTRODUCTION Thank you for purchasing this CLARKE Shot Blast Cabinet which is designed for professional workshop use. Before
StorTrends 3400 Hardware Guide for Onsite Support
StorTrends 3400 Hardware Guide for Onsite Support MAN-3400-SS 11/21/2012 Copyright 1985-2012 American Megatrends, Inc. All rights reserved. American Megatrends, Inc. 5555 Oakbrook Parkway, Building 200
OPL BASIC. Dosing System for Professional Laundry machines. Contents
OPL BASIC Dosing System for Professional Laundry machines Contents 1 Getting Started. Page 2 2 Installation. Page 4 3 Set Up & Operation. Page 8 4 Maintenance & Accessories. Page 10 5 Troubleshooting Page
INSTALLATION INSTRUCTIONS
LIGHTING CONTROL PANELS 4 AND 8 RELAYS INSTALLATION INSTRUCTIONS INSTALLATION OVERVIEW The installation instructions contained in this document are provided as a guide for proper and reliable installation.
GST301. (Single Protection Zone) Operation Manual
GST301 Gas Extinguishing Control Panel (Single Protection Zone) Operation Manual 2 of 19 CONTENTS 1 OVERVIEW... 4 2 TECHNICAL DATA... 4 3 STRUCTURES... 5 3.1 FRONT SURFACE DESCRIPTION... 5 3.1.1 Indicators...
Introduction. Safety Guidelines. Part Numbers. Operation and Maintenance Manual. Operation and Maintenance Manual
Operation and Maintenance Manual Introduction Read all instructions thoroughly. Installation of the OilTector must comply with all Federal, State and Local Codes, Regulations and Practices. The OilTector
Oil and Coolant Circulating Heating System. Model - OCSM
Oil and Coolant Circulating Heating System Model - OCSM Installation & Operation Manual 216280-000 REV 2 Identifying Your System The HOTSTART heating system is designed to heat fluids for use in marine
PSDC 08128. PSDC 12V/8A/8x1A Power supply for up to 8 analog cameras PTC/TOPIC.
PSDC 08128 v.1.2 PSDC 12V/8A/8x1A Power supply for up to 8 analog cameras PTC/TOPIC. EN** Edition: 9 from 25.05.2015 Supersedes the edition: 8 from 12.12.2014 the 8x 1A/12V DC power output for powering
Automatic Transfer Switch FT-10 Network Control Communications Module (CCM-T) Kit 541 0811
Instruction Sheet 1-2003 Automatic Transfer Switch FT-10 Network Control Communications Module (CCM-T) Kit 541 0811 PURPOSE OF KIT A CCM-T is used to monitor and control an automatic transfer switch. The
RayClic Connection System Installation Instructions
RayClic Connection System Installation Instructions Description RayClic-S Splice Kit RayClic-T Tee and End Seal Kit RayClic-X Cross and End Seal Kit These kits are for use with Raychem IceStop, XL-Trace
Packard Bell Easy Repair 1. Packard Bell Easy Repair
Packard Bell Easy Repair Hard Disk Drives Important Safety Check Instructions You must read all instructions carefully before you begin work and comply with the procedures set out below. Failure to comply
AXIS T81B22 DC 30W Midspan
INSTALLATION GUIDE AXIS T81B22 DC 30W Midspan ENGLISH About this Document This document includes instructions for installing AXIS T81B22 on your network. Previous experience of networking will be beneficial
INSTRUCTIONS FOR THE INSTALLATION AND OPERATION OF ACTIVATOR II
INSTRUCTIONS FOR THE INSTALLATION AND OPERATION OF ACTIVATOR II ELECTRONIC TRAILER BRAKE CONTROL 5500 FOR 2, 4, 6 & 8 BRAKE SYSTEMS IMPORTANT: READ AND FOLLOW THESE INSTRUCTIONS CAREFULLY. KEEP THESE INSTRUCTIONS
CFP 2/4/8 ZONE CONVENTIONAL FIRE ALARM CONTROL PANEL. user manual & log book. Approved Document No. DFU7001020 Rev 1
CFP 2/4/8 ZONE CONVENTIONAL FIRE ALARM CONTROL PANEL user manual & log book Approved Document No. DFU7001020 Rev 1 CONTENTS Safety...3 Important information regarding the safe use of this fire alarm panel
Manual for Fire Suppression & Methane Detection System
Manual for Fire Suppression & Methane Detection System Fogmaker North America Post address: 150 Gordon Dr Exton, PA 19341 Delivery address: 150 Gordon Dr Exton, PA 19341 Tel: 610-265-3610 Fax: 610-265-8327
SERVICE MANUAL RESIDENTIAL ELECTRIC AND LIGHT DUTY COMMERCIAL ELECTRIC WATER HEATERS. Troubleshooting Guide and Instructions for Service
RESIDENTIAL ELECTRIC AND LIGHT DUTY COMMERCIAL ELECTRIC WATER HEATERS SERVICE MANUAL Troubleshooting Guide and Instructions for Service (To be performed ONLY by qualified service providers) Models Covered
Mobile Data Power Model: MDP-25
Mobile Data Power Model: MDP-25 Topic Section Features... 2 Operational Features Summary... 2 Back-up Battery Power Internal Charger Voltage Spike Protection RF Noise Filtering Warning of Imminent Loss
AN500T, AN1000, AN1000T, AN1500, AN1500T AN2000, AN2000T
Product Instruction Manual Accona AN500T, AN1000, AN1000T, AN1500, AN1500T AN2000, AN2000T Panel heater v16.5/5 Version 3.2 Jan 2015 Contents 1. Important safety points 2. Installation 2.1. Wall mounting
Emergency Voice Communication Systems EVCS Network 8 Data Sheet
Emergency Voice Communication Systems EVCS Network 8 Data Sheet The Emergency Voice Communications System (EVCS) Network 8 is for use as a Fire Telephone system, Disabled Refuge Call system or as a combined
Digi-Motor Installation Guide
Digi-Motor Installation Guide Installation Video...located at marsdelivers.com Digi-Motor Installation Guide Digi-Motor For technical assistance with your Azure Digi-Motor, call the MARS technical support
conventional system operation
conventional system operation detection line operation Conventional detection systems normally operate on a 24VDC line. In the standby condition, the detectors will draw a low current, typically less than
Wolflite Safety Handlamp H-251E
Wolflite Safety Handlamp H-251E & H-251 Mk1 & Mk2 Wolflite Safety Handlamp H-251E H 18Y H 17 H 31Y H 21A H 30 H 24 H 26 H 19 H 25 H 03 H 15Y H 22 H 104 H 29 H 66 H 13 H 14 H 09 H 12 H 48 H 11 H 62 H 63
RayClic Connection System Installation Instructions
F M -W RayClic Connection System Installation Instructions RayClic WARNING: Shock Hazard 718K Pipe Heating Cable with HWAT, IceStop, also Listed De-icing and and XL-Trace heating Snow Melting Equipment
Best Methods for Safe Hipot Testing
Best Methods for Safe Hipot Testing When working with electrical safety test equipment, instruments that output potentially dangerous voltages and currents, it is always important to regular review and
Single Station Remote Alarm
ADI 5106G Certified ISO 9001:2000 Single Station Remote Alarm 529 5106-01-120 529 5106-01-220 INSTALLATION AND OPERATING INSTRUCTIONS Carefully Read These Instructions Before Operating Controls Corporation
Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points
Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points Features SELV Compliant No Detection Passive Injector Gigabit Compatible Full Protection
Lighting Controls ! WARNING RISK OF ELECTRIC SHOCK. Installation Instructions DESCRIPTION
GE Lighting Installation Instructions Lighting Controls Centralized Lighting Control Panel Interior Catalog Number CLCINTxx DESCRIPTION The Centralized Lighting Control System is a small network of relay
430 Power/Electronics Replacement
Replacing the main board WARNING Before proceeding, turn off the main power switch and unplug the power cord. Caution Make sure you are properly grounded with an ESD strap before continuing. The main printed
Product and Applications Description. Application Programs. Example of Operation. GAMMA instabus Technical Product-Information.
Product and Applications Description The power supply units N 125/x2 can supply DC 24 V power from an additional pair of terminals (yellowwhite). This DC 24 V output voltage can be used to power e.g. an
Advantium 2 Plus Alarm
ADI 9510-B Advantium 2 Plus Alarm INSTALLATION AND OPERATING INSTRUCTIONS Carefully Read These Instructions Before Operating Carefully Read These Controls Corporation of America 1501 Harpers Road Virginia
FIRE ALARM SYSTEM TECHNICAL SPECIFICATIONS Page 1 of 10
TECHNICAL SPECIFICATIONS Page 1 of 10 FIRE DETECTION AND ALARM SYSTEM Scope Furnish a complete 24V DC conventional, electrically supervised, zone annunciated, fire detection and alarm system as specified
IO-RM3 3-Stage Relay Module
Page 1 of 6 IO-RM3 3-Stage Relay Module Features: Benefits: Link selectable modes binary, heat/cool, staged or sequenced On/Off/Auto links for ease of commissioning DIN Rail mounting Fault finding LED
T7560A,B,C Digital Wall Module
T7560A,B,C Digital Wall Module HONEYWELL EXCEL 5000 OPEN SYSTEM BEFORE INSTALLATION All wiring must comply with local electrical codes and ordinances or as specified on installation wiring diagrams. Digital
Installation. Smart-UPS VT and MGE Galaxy 3500. Maintenance Bypass Panel with Power Distribution (wall-mount) 10-30 kva 208 V
Installation Smart-UPS VT and MGE Galaxy 3500 Maintenance Bypass Panel with Power Distribution (wall-mount) 10-30 kva 208 V Contents Safety... 1 SAVE THESE INSTRUCTIONS...............................
IO-DIM6 6-Channel, Digital to Analogue Converters
Page 1 of 6 IO-DIM6 6-Channel, Digital to Analogue Converters Features: Benefits: Input status indication Calibrated output DIN Rail mounting Expands controller input capacity Fault finding LED indication
Air-cooled Generator Battery Charger Installation Guidelines
Air-cooled Generator Battery Charger Installation Guidelines Table of Contents Table of Contents...Inside Front Cover Section 1 General Information... IFC 1.1 Introduction...IFC 1.2 Battery Charger Compatibility...
CM705B - Universal Expander Module CM707B - Plug On Zone Expander Security Systems
CM705B - Universal Expander Module CM707B - Plug On Zone Expander Security Systems EN Security System CM705B CM705B - Universal Expander Module The CM705B universal expander provides a cost effective way
2 Wire Electronic Time Delay Switch. 2 Wire Slave Switch. 3 Wire Electronic Time Delay Switch
2 Wire Electronic Time Delay Switch Cat No. DS1 2 Wire Slave Switch Cat No. DSS 3 Wire Electronic Time Delay Switch Cat No. DS2 Installation & Operating Instructions DS1/DSS Instructions for Installation
MANUAL. * Supply plugs may differ to suit your wall socket. EN 3. Continue to press the MODE-button to combine charging program with charging options.
MX MANUAL CONGRATULATIONS to the purchase of your new professional switch mode battery charger. This charger is included in a series of professional chargers from CTEK SWEDEN AB and represents the latest
DLP-PU/E Instruction Manual
Instruction Manual BEFORE USING THE POWER SUPPLY UNIT Pay attention to all warnings and cautions before using the unit. Incorrect usage could lead to an electrical shock, damage to the unit or a fire hazard.
OWNER S MANUAL 2.5/3.0 ACS PANEL (ADVANCED CONTROL SYSTEM) 7725 Lougheed Highway Burnaby, BC V5A 4V8 Canada
2.5/3.0 ACS PANEL (ADVANCED CONTROL SYSTEM) OWNER S MANUAL 7725 Lougheed Highway Burnaby, BC V5A 4V8 Canada Tel: (604) 420-1585 Fax: (604) 420-1591 http:// www. statpower.com PROsine 2.5/3.0 ACS Panel
Operation and Installation Manual
Operation and Installation Manual RCM-10 Remote Control Monitor and RSM-10 Remote Status Monitor for the CNA-100 & CNA-200 Automations Revision 1.1 9/98 WARRANTY INFORMATION The RCM-10 Remote Control
TROUBLESHOOTING GUIDE
TROUBLESHOOTING GUIDE LESTRONIC II BATTERY CHARGER FOR MOTIVE POWER BATTERIES PLEASE SAVE THESE IMPORTANT SAFETY AND OPERATING INSTRUCTIONS For correct operation of the equipment, it is important to read
PASSIVE INFRARED INTRUSION DETECTOR PASSIVE INFRAROOD DETECTOR DETECTEUR D INTRUSION PASSIF INFRAROUGE
MODEL HAA51 PASSIVE INFRARED INTRUSION DETECTOR PASSIVE INFRAROOD DETECTOR DETECTEUR D INTRUSION PASSIF INFRAROUGE OPERATING MANUAL HAA51 PASSIVE INFRARED INTRUDER DETECTOR INTRODUCTION HAA51 Passive Infrared
ESP 120 M1, ESP 208 M1, ESP 240 M1, ESP 415 M1, ESP 277 M1, ESP 480 M1 and M1R variants. Installation instructions ESP M1/M1R mains protectors
ESP 120 M1, ESP 208 M1, ESP 240 M1, ESP 415 M1, ESP 277 M1, ESP 480 M1 and M1R variants Installation instructions Contents Key points of installation Before installation Installation Installation check
TraceTek TTDM Series Leak Detection and Location Modules Replacement Parts Installation Instructions
TraceTek TTDM Series Leak Detection and Location Modules Replacement Parts Installation Instructions TRACETEK TraceTek TTDM Replacement Parts General Information These instructions detail the steps to
CX Zoner Installation & User Guide
CX Zoner Installation & User Guide Cloud Electronics Limited 140 Staniforth Road, Sheffield, S9 3HF England Tel +44 (0)114 244 7051 Fax +44 (0)114 242 5462 e-mail [email protected] web site http://www.cloud.co.uk
MODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE
DESCRIPTION MODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE DESCRIPTION The SST Model 5010 Two Channel Smoke/Fire Detection Module provides two independent detection input channels for the NOVA-5000
ELITE-L Series. ELITE - Low Voltage / Dry contact Remote Control System
ELITE-L Series ELITE - Low Voltage / Dry contact Remote Control System Applications Garden Lighting Pond pumps Remote outdoor Switching Access control Industrial control Features 4 switched channels 1000W
ML 1012 v.1.2 ML13,8V/1A Buffer power supply module, linear.
ML 1012 v.1.2 ML13,8V/1A Buffer power supply module, linear. EN Edition: 6 from 10.03.2014 Supercedes the edition: 5 from 16.09.2013 Features: uninterrupted supply of 13,8VDC/1A supply voltage: external
Operating and Maintenance Instructions MEDIPOINT 125 MEDICAL GAS CENTRAL ALARM
Operating and Maintenance Instructions MEDIPOINT 125 MEDICAL GAS CENTRAL ALARM CONTENTS SECTION 0. SAFETY, STORAGE AND HANDLING DATA 0.1 Indentification of symbols 0.2 Environmental conditions 0.3 Environmental
6x 54w SuperZoo T5 HIGH FREQUENCY ELECTRONIC CONTROLLER LUMINAIRE
1 SAFETY, INSTALLATION AND MAINTENANCE INSTRUCTIONS FOR: ASZ01, ASZ02, ASZ03, ASZ04 6x 54w SuperZoo T5 HIGH FREQUENCY ELECTRONIC CONTROLLER LUMINAIRE Unit Weight: 8.5 Kg Dimensions: L1440*W400*H80mm Power
Repeaters and Mimics Data Sheet
Repeaters and Mimics Data Sheet IDR series repeaters and mimics allow vital information from a Notifier fire system to be communicated to points around a building remote from the fire alarm control panel.
Master Time Clock MTC-200 MTC-400 MTC-600. Users Manual
Master Time Clock MTC-200 MTC-400 MTC-600 Users Manual Toll Free (888)713-0373 Phone (972)987-4408 FAX (877)720-9291 www.midwest-time.com [email protected] TABLE OF CONTENTS TOPIC PAGE GENERAL DESCRIPTION
HID H4 BI-XENON FITTING GUIDE. Carefully read the following notes before starting work.
HID H4 BI-XENON FITTING GUIDE Carefully read the following notes before starting work. WARNING! This HID kit should only be installed by someone competent in vehicle wiring and electrics. Incorrect fitment
INSTALLATION OPERATION AND MAINTENANCE INSTRUCTIONS FOR EXHEAT INDUSTRIAL IMMERSION HEATERS (INCLUDING FLAMEPROOF)
INSTALLATION OPERATION AND MAINTENANCE INSTRUCTIONS FOR EXHEAT INDUSTRIAL IMMERSION HEATERS (INCLUDING FLAMEPROOF) Please read these instructions thoroughly before installation and ensure they are passed
ZAPPY 3 OWNER S MANUAL. Read this manual completely before riding your Electric ZAPPY 3.
ZAPPY 3 OWNER S MANUAL Read this manual completely before riding your Electric ZAPPY 3. TECHNICAL INFORMATION Model No. : ZAPPY 3 Product size Type of motor Motor power Battery type Battery Charger Charging
User Manual THR840DUK Digital Thermostat
User Manual THR840DUK Digital Thermostat 50051982-001 Rev. A WARNING: This product must be correctly installed and configured to work properly (see pages 12-24). If you are not experienced in wiring electrical
www.ringautomotive.co.uk Instructions: Retain these instructions for future reference SmartChargePro35 RSCPR35-12v, 2 / 8 / 16 / 35A
SmartChargePro7 RSCPR7-12v, 7A SmartChargePro10 RSCPR10-12v, 10A SmartChargePro15 RSCPR15-12v, 15A SmartChargePro25 RSCPR25-12v, 2 / 6 / 12 / 25A SmartChargePro35 RSCPR35-12v, 2 / 8 / 16 / 35A SmartChargePro50
SigTEL Compact. Emergency Voice Communication System (EVCS) Installation and Configuration Manual. Approved Document No.
Communication System (EVCS) Installation and Configuration Manual Approved Document No. DAU0000081 Rev 4 Contents AN EXPLANTION OF TERMS AND DEFINITIONS USED IN THESE INSTRUCTIONS IS LISTED IN SECTION