Power Separation Guidelines for SYSTIMAX Installations
|
|
|
- Morris Joseph
- 9 years ago
- Views:
Transcription
1 SYSTIMAX Solutions Power Separation Guidelines for SYSTIMAX Installations Design and installation guidelines August
2 1.0 General These guidelines are based on extensive testing and modeling performed by CommScope Labs and by standards committees (especially by TIA in the US). The guidelines outline the minimum requirements for registration of SYSTIMAX installations for the 20-Year Extended Product Warranty and Applications Assurance Program. The exception is for installations with SYSTIMAX x297/x298 cables where the guidelines outline in Section 4.0 shall apply. Unless otherwise stated, the power cables are assumed to be non-armored. Applicable local or national safety regulations take precedence whenever their required separation distances are larger than those specified in this document. For example: In the UK, if no mechanical divider is present between the data and power cables, BS 6701 requires a minimum separation distance of 50 mm (2 in) for voltages less than 600 Va.c. In the USA, Article of NEC Ed 2002 states the following for Class 1 circuits: o o Communications wires and cables shall be separated at least 50 mm (2 in) from conductors of any electric light, power, Class 1, non-power-limited fire alarm, or medium power network-powered broadband communications circuits. -- Exception No. 1: Where either (1) all of the conductors of the electric light, power, Class 1, non-power-limited fire alarm, and medium power network-powered broadband communications circuits are in a raceway or in metal-sheathed, metal-clad, nonmetallicsheathed, Type AC, or Type UF cables, or (2) all of the conductors of communications circuits are encased in raceway. -- Exception No. 2: Where the communications wires and cables are permanently separated from the conductors of electric light, power, Class 1, non-power-limited fire alarm, and medium power network-powered broadband communications circuits by a continuous and firmly fixed non-conductor, such as porcelain tubes or flexible tubing, in addition to the insulation on the wire. In the US, ANSI/TIA-942 Telecommunications Infrastructure Standard for Data Centers and ANSI/TIA-1005 Telecommunications Infrastructure Standard for Industrial Premises provide power separation requirements in Clause 7.3 and Clause 5.2 respectively. These requirements are fully in alignment with SYSTIMAX guidelines and can be adhered to except for 1 to 15 power cables where SYSTIMAX guidelines will apply. In Europe, EN :2000 has been revised and the new published standard (EN :2009) specifies separation requirements in Clause 6 that are similar to SYSTIMAX guidelines. Section 4.0 of this document will correlate SYSTIMAX guidelines with EN :2009 requirements. 2
3 2.0 Power Cables Rating: Va.c 415V and I 100A The following guidelines are applicable to power cables rated 415 volts (Va.c) or less and 100 amperes (A) maximum. Unless otherwise stated, the power cables are assumed to be non-armored. For SYSTIMAX installations of cable lengths of up to 90 meters (295 ft), zero separation distance is required for branch/radial circuits that meet all the following conditions: Limited to one power cable rated at 110/240V, 20A, single-phase (phase-to-neutral or earth). The power cable or cord must have Live (L), Neutral (N) and Earth (E) conductors contained within a common sheath (that is, sheathed power cables). If loose (individual) conductors are used as power cables, these conductors must be bunched or maintained close together to minimise inductive coupling. A ring circuit can be considered to be equivalent to two branch circuits, e.g. a ring circuit of 40A is considered to be equivalent to two branch circuits of 20A each. In this case, the guidelines for 20A apply. Powering typical office equipment. The main electrical service entrance is protected with surge arresters (transient voltage surge suppressor) according to the applicable local/national codes (for equipment safety). In addition, all the following requirements shall also be met: The building itself shall be suitably protected from direct lightning strikes according to the applicable local or national codes. Multi-channel outlet boxes or compartments where individual power conductors and Category 5 or higher cabling are introduced to serve a workstation require 6 mm (0.25 in) separation. If loose, open (spaced) power conductors are used and not bunched or maintained close together, a minimum separation of 50 mm (2 in) is required. For all fluorescent light fixtures and associated power cables (in the vicinity of the light fixtures see Figure 1), the separation distance is 50 mm (2 in). Power and SYSTIMAX cables shall cross over at right angles. However, a bridge may be required to meet national/local safety codes. Figure 1: Example of fluorescent lighting fixtures 3
4 The following considerations should also be given: If multi-channel plastic raceways (i.e. compartmentized plastic trunking) are used, the power cables should be installed in the bottom compartment and the data cables in the top or vice versa (as per IEC/EN guidelines). If loose (individual) power conductors are used, they must be bunched or maintained close together within the trunking. The use of surge suppressors in branch circuits can further limit the propagation of electrical surges. These must be installed according to the applicable local/national codes (for equipment safety). Table 1 provides additional separation requirements beyond those given above. This table is normally applicable to cabling in the horizontal and work area subsystems. The following points should be noted: The power conductor cross-sectional area is the minimum requirement for use. S is the required separation distance between the power and data cables. L is the total data cable horizontal length and NOT just the coupled length (i.e. length parallel to the power cable). Testing carried out by TIA in the US indicated that coupled length beyond 10 meter (33 ft) has little effect on frame errors. Normal power operating condition is assumed. If the power cables are armoured, then the separation distances provided in Table 1 can be halved. However, the armouring must completely surround the cable (except at the socket) and must be properly bonded and earthed in accordance with the applicable local or national regulations. If Table 1 is not applicable, the following requirements shall apply: Feeder power circuits (i.e. supply for branch circuits, etc.) or large groupings (> 30 power cables) of branch circuits shall maintain a minimum of 600 mm (2 ft) separation from data cables and patch panels in open frames (Figure 2). This situation typically arises in the communication/equipment rooms where the power distribution units (PDUs) are located as shown in Figure 3. The 600 mm (2 ft) separation distance can be halved, i.e. 300 mm (1 ft) if the power cables are armoured. These power cables can be loose-laid or installed on cable baskets (Figure 2). Alternatively, the 300 mm (1 ft) separation is also applicable if the power cables and/ or data cables are installed on separate cable trays. These trays can have slots for easy attachment of the cables. These slots must be small, i.e. 50 mm (2 in) x 10 mm (0.4 in), and parallel to the axis of the tray as shown in Figure 4. Cable baskets shall not be used. Figure 5 provides an example of a typical installation requirement. The various separation distances are derived as follow: In the vicinity of the equipment room subsystem, there are 72 and 36 power cables. Hence 600 mm (2 ft) separation distance is required. In the horizontal subsystem, there are 9 power cables. Hence, from Table 1, the separation distance is 100 mm (4 in). In the work area subsystem, there are 2 power cables. Hence, from Table 1, the separation distance is 4 mm (0.16 in). At the multi-channel outlet boxes, the separation distance is 6 mm (0.25 in). 4
5 Table 1: Additional Separation Guidelines for 110/240V, Single-Phase (Phase-to-Neutral or Earth) Power Cables. Total Data Cable Total Number Power Conductor Maximum Current Horizontal of Power Separation Cross-sectional Area Rating, I (A) Length, L Cables, N Distance, S 1 mm 2 ( in 2 ) m (295 ft) mm 2 ( in 2 ) m (295 ft) m (0.16 in) 1 mm 2 ( in 2 ) m (295 ft) m (4 in) Figure 2: Separation requirements between power cables and data cables 5
6 Note 1: If armoured power circuits are used, the separation distance can be reduced to 300 mm (1ft). Figure 3: Separation requirements between PDU power cables and data cables/patch panels Note 1: If armoured power circuits are used, the separation distance can be reduced to 300 mm (1ft). In this situation, cable baskets can be used. Figure 4: Separation requirements when using cable trays
7 Figure 5: Example of an installation requirement 3.0 Power Cables Rating: Va.c > 415V and/or I > 100A If the conditions and/or separation distances provided in Section 2 cannot be achieved, then zero separation distance is permitted when the data cables and/or the power cables are enclosed in metallic trunking or conduit. All the following conditions then apply: The metallic trunking/conduit must completely enclose the cables and be continuous. The metallic trunking/conduit must be properly bonded and earthed in accordance with the applicable local or national regulations, for example, IEE Wiring Regulations (BS 7671) in the UK or NEC in the USA. The trunking/conduit must be at least 1 mm (0.04 in) thick if made of galvanised (low carbon) steel or 2 mm (0.08 in) thick if made of aluminium. However, if the above conduit/trunking thickness cannot be achieved, then Table 2 shall apply. 7
8 Table 2: Trunking/conduit material and thickness requirements Separation Distance, mm (inches) Galvanised Steel Thickness, mm (inches) Aluminium 600 (24) 0.05 (0.002) 0.1 (0.004) 300 (12) 0.1 (0.004) 0.2 (0.008) 150 (6) 0.2 (0.008) 0.5 (0.02) Table 75 (3) 2: Trunking/conduit 0.5 (0.02) material and thickness requirements 1 (0.04) 0 (0) 1 (0.04) 2 (0.08) Fibre cabling is recommended if none of the above conditions can be achieved. 4.0 EN :2009 Standard and SYSTIMAX Guidelines The EN :2009 standard provides power separation requirements in Clause 6. In this standard, the minimum separation requirement A is calculated by multiplying the minimum separation S (obtained from Table 4) by the power cabling factor P (obtained from Table 5). The value of S depends upon the segregation classification of the IT cable of Table 3. This segregation classification depends on the transverse conversion loss (TCL) for unscreened balanced (U/UTP) cables or coupling attenuation for screened balanced (F/UTP, F/FTP, S/FTP) cables. The segregation classification of SYSTIMAX cables is given in Table 3. Table 3: EN segregation classification for SYSTIMAX cables SYSTIMAX Cables x061 (U/UTP) x071 (U/UTP) x091 (U/UTP) x291 (F/UTP) x297 (S/FTP) x298 (S/FTP) EN Segregation Classification b c c c d d Table 4 provides the minimum separation requirement A, according to EN and compares it with the minimum separation guidelines from SYSTIMAX. Hence for 230V, 1-phase and 20A electrical circuits, the power separation requirements of EN can be adhered to. 8
9 Table 4: Comparing EN and SYSTIMAX minimum separation requirements Minimum Separation Requirement, A (mm) for 230V, 1-phase, 20A electrical circuits Quantity of circuits b (x061) c (x071, x091, x291) SYSTIMAX 1 to to to to to to to to to > CommScope, Inc. All rights reserved. Visit our website at or contact your local CommScope representative or BusinessPartner for more information. All trademarks identified by or TM are registered trademarks or trademarks, respectively, of CommScope, Inc. TP EN 11/12
Screened cable and data cable segregation
December 2007 Screened cable and data cable segregation Can an armoured power cable be considered a screened cable and how does this relate to power and data cable segregation? The short answer is yes;
EN 50174-1 and EN 50174-2: 2008 Integrated standards for telecommunications cabling installation
EN 50173-1 EN 50173-2 EN 50173-3 EN 50173-4 EN 50173-5 EN 50346 EN 50174-1 EN 50174-2 EN 50174-3 DESIGN INSPECTION TESTING PLANNING INSTALLATION National Standards National Regulations EN 50174-1 and EN
SYSTIMAX SCS PowerSum and GigaSPEED XL Cabling Installation Guidelines
SYSTIMAX SCS PowerSum and GigaSPEED XL Cabling Installation Guidelines This document contains critical information regarding the installation of a certified SYSTIMAX SCS that meets or exceeds performance
800 Communications Circuits
ARTICLE 800 Communications Circuits INTRODUCTION TO ARTICLE 800 COMMUNICATIONS CIRCUITS This article has its roots in telephone technology. Consequently, it addresses telephone and related systems that
Specifying an IT Cabling System
Specifying an IT Cabling System This guide will help you produce a specification for an IT cabling system that meets your organisation s needs and gives you value for money. You will be able to give your
2014 NEC Guide Lines for Home Owner Doing Electrical Work on their Property
2014 NEC Guide Lines for Home Owner Doing Electrical Work on their Property A brief summary of the most used code references for residential wiring State of Idaho Division of Building Safety Electrical
Separation of power and information technology cabling
Technical bulletin Separation of power and information technology cabling Date: 08/2006 This technical bulletin provides you with information on specific technical subjects. It is based on the current
Chapter 9. Bonding and Grounding
Chapter 9 Bonding and Grounding Objectives Describe why the cable should be bonded Describe bonding and grounding procedures Define Bonding and Grounding Explain Safety Benefits and intent of bonding and
Coaxial Cable Entry Panels, Coax and Grounding Connectors. Technical Note
Coaxial Cable Entry Panels, Coax and Grounding Connectors Technical Note Coaxial Cable Entry Panels, Coax and Grounding Connectors Surge Protection Solutions for PTC 2 Coaxial Cable Entry Panels, Coax
Trial Exams C. Standards and Regulations. Examination No: GH-08-C- 1 hour and 5 minutes plus 10 minutes reading time
Trial Exams C Standards and Regulations Examination No: GH-08-C- This test is intended to gauge your knowledge of essential information contained within AS/CA S009:2013. To qualify for an allpication to
Article 10 - ADMINISTRATIVE SECTION
Article 10 - ADMINISTRATIVE SECTION 10.1 TITLE These Administrative Regulations along with the requirements included in the 2011 Edition of the National Electrical Code (NFiPA-70-2011) as adopted by the
ELECTRICAL INSPECTION BULLETIN (Effective 2000-03-01)
ELECTRICAL INSPECTION BULLETIN (Effective 2000-03-01) Rule 28-900 Standby Generator Installations Due to the increasing number of standby generator installations being established to maintain continuity
Standards. www.nordx.com 5 ANSI/TIA/EIA-569-A (CSA T530)
The primary focus of this standard is to provide design specifications and guidance for all building facilities relating to telecommunications cabling systems and components. This standard identifies and
Introduction to Data Centre Design
Introduction to Data Centre Design Barry Elliott BSc RCDD MBA CEng Earthing, grounding and bonding November 09 Earthing what s the point Safety from electrical hazards Reliable signal reference within
DOMESTIC ELECTRICAL INSTALLATION CERTIFICATE (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations)
DOMESTIC ELECTRICAL INSTALLATION CERTIFICATE (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations) DETAILS OF THE CLEINT Client and address ADDRESS OF THE INSTALLATION Installation
RESIDENTIAL ELECTRICAL REQUIREMENTS (REVISED 3/28/2008) PERMIT REQUIREMENTS:
RESIDENTIAL ELECTRICAL REQUIREMENTS (REVISED 3/28/2008) PERMIT REQUIREMENTS: Signed completed Electrical Permit application form. Minnesota law requires all electrical work is to be performed by licensed,
The National Armored Cable Manufacturers Association Presents. Installation Standard for Types AC and MC Cables
The National Armored Cable Manufacturers Association Presents Installation Standard for Types AC and MC Cables An ANSI Standard Original document jointly produced by NECA and NACMA as Standard for Installing
Session 14 Cable Support Systems
Session 14 Cable Support Systems Cable Support Systems in the IEC World A new IEC Standard, IEC61537 2001 has been developed If full details of the cabling layout are available then the likely cable load
Minimum Standards for Data/Voice Infrastructure in New Building Construction
UNIVERSITY OF WATERLOO Minimum Standards for Data/Voice Infrastructure in New Building Construction 12/17/2012 Offices 1. Two Work Area Outlets (WAO) on opposite walls, each with 2 jacks 2. Each WAO shall
270526-TC Grounding and Bonding for Telecommunications Systems
270526-TC Grounding and Bonding for Telecommunications Systems Part 1 - General Related Documents The following related sections of the OT standards shall also be applicable to this section. OT Engineer
Code Compliance for Spring Steel Fasteners Based on the 2005 NEC
Code Compliance for Spring Steel Fasteners Based on the 2005 NEC B-Line has recognized the need for a reference source, detailing the National Electrical Code requirements for Spring Steel Fasteners. The
CommScope Intelligent Building Infrastructure Solutions (IBIS)
SYSTIMAX Solutions CommScope Intelligent Building Infrastructure Solutions (IBIS) Questions & Answers Q. What is an Intelligent Building? A. An intelligent building can be defined as one which provides
MONTGOMERY COUNTY EXECUTIVE REGULATION Offices of the County Executive. 101 Monroe Street. Rockville, Maryland 20850
Montgomery County Regulation on: ADOPTION OF THE 2008 NATIONAL ELECTRICAL CODE DEPARTMENT OF PERMITTING SERVICES Issued by County Executive Regulation # 15-09 Authority: Code Section 17-2 and 17-3 Supersedes:
Presenters Brett Weiss, Gabe Martinez, Brian Kroeger.
1 Presenters Brett Weiss, Gabe Martinez, Brian Kroeger. Topics to be covered: Cable identification Purpose of the various cable types Installation techniques Building Infrastructure Overview of networking
ELECTRICAL - WIRING DESIGN AND PROTECTION SELF INSPECTION CHECKLIST
Name of School: OPTIONAL INFORMATION Date of Inspection: Vocational Program/Course/Room: Signature of Inspector: ELECTRICAL - WIRING DESIGN AND PROTECTION SELF INSPECTION CHECKLIST Guidelines: This checklist
AFUMEX LSX LOW SMOKE ZERO HALOGEN SCREENED WIRING CABLES BS8436 BASEC APPROVED PRODUCT DATASHEET & APPLICATIONS GUIDE KEY BENEFITS:
PRODUCT DATASHEET & APPLICATIONS GUIDE BASEC APPROVED AFUMEX LSX LOW SMOKE ZERO HALOGEN SCREENED WIRING CABLES BS8436 KEY BENEFITS: BASEC approved for the full size range of BS8436 (1.0mm 2 to 2.5mm 2
MASTER ELECTRICIAN CODE EXAMINATION EXAMINATION REFERENCE MATERIAL AND CONTENT OUTLINE. Answers to sample questions: CONTENT OUTLINE
Answers to sample questions: Question Answer Reference 1 4 Section 362.12(6) 2 2 Table 310-16; 310.15(B)(2)(a) 3 4 Table. 250-66 4 2 Table 430.250 & 430.52 5 2 American Electrician Handbook, Figure 7-159
Unified requirements for systems with voltages above 1 kv up to 15 kv
(1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to
1.1 SYSTEM DESCRIPTION.1 Data system includes data outlets and wiring for office and school applications.
Issued 2005/06/01 Section 16743 Data System Page 1 of 7 PART 1 GENERAL 1.1 SYSTEM DESCRIPTION.1 Data system includes data outlets and wiring for office and school applications..2 Data system equipment
Excerpts from the Canadian National Building Code (NBC)
Excerpts from the Canadian National Building Code (NBC) Reproduced here with Permission of the Copyright Owner, the National Research Council of Canada, Institute for Research in Construction. For more
Electrical Grounding. Appendix C
Appendix C Electrical Grounding Low-Voltage Equipment Grounding The most frequently cited Office of Safety and Health Administration (OSHA) electrical violation is improper occupational grounding of equipment
BASIC NEC CODE RULES AND DESIGN PRACTICE
BASIC NEC CODE RULES AND DESIGN PRACTICE Wire Ampacity and Size Circuit Breaker Size 1. Maximum loading for any branch circuit is 80% of rating of circuit for ampacity of wire for any load. NEC 220-2,
No Phone Line II-48 System
Used in conjunction with an EntraGuard Telephone Entry System, the -48 provides No Phone Line communication and door or gate control through existing building telephone lines without the need to purchase
PALM BEACH COUNTY AMENDMENTS TO THE NATIONAL ELECTRICAL CODE, 1999 EDITION
PALM BEACH COUNTY AMENDMENTS TO THE NATIONAL ELECTRICAL CODE, 1999 EDITION CODING: Words underlined are additions to the 1999 NEC Words stricken are deletions to the 1999 NEC Adopted by Ordinance 99-73
CHAPTER 2 EXAMPLES AND TABLES
CHAPTER 2 EXAMPLES AND TABLES COMMENTARY AT 210.20(A) EXCEPTION An overcurrent device that supplies continuous and noncontinuous loads must have a rating that is not less than the sum of 100 percent of
SOLAR PV STANDARD ELECTRICAL PLAN Microinverter Systems for Single Family Dwellings
*** Provide this document to the inspector along with ALL system installation instructions *** Project Address: Scope: Standard plan for the installation of grounded microinverter solar PV systems, not
EARTHING AND BONDING AT SECONDARY SUBSTATIONS
DISTRIBUTION CONSTRUCTION MANUAL SECTION 4 - SUBSTATIONS ISSUE B SEPT 1996 4.4.4 EARTHING AND BONDING AT SECONDARY SUBSTATIONS 1 SCOPE This section of the Distribution Construction Manual lays down the
Installation Guide Content for P250xV-240 microinverters
A C M o d u l e Installation Guide Content for P250xV-240 microinverters May 15, 2012 2011-2012 SolarBridge Technologies, Inc. All Rights Reserved. No part of this publication may be reused in any manner
AC Module Installation Guide Content
AC Module Installation Guide Content for ET-P660250AC May 9, 2012 2011-2012 ET Solar Group All Rights Reserved. No part of this publication may be reused in any manner nor in any form or format without
Errata NFPA 70. Proposed 2014 Edition
Errata NFPA 70 National Electrical Code (Report on Proposals) Reference: 12-109 (Log #1618) Panel Meeting Action Proposed 2014 Edition The National Electrical Code Technical Correlating Committee notes
CURRENT RATINGS MORE THAN A CABLE
CURRENT RTINGS Updated for the 17th Edition of the IEE Wiring Regulations MORE THN CBLE C O M P N Y EI CBLES, DURHM ROD, BIRTLEY, CO DURHM. DH3 2R Tel: +44 (0)191 410 3111 Fax: +44 (0)191 410 8312 E-mail:
Grounding & Bonding Why it is done And How to Install Properly
Grounding & Bonding Why it is done And How to Install Properly The technical information provided herein is to assist qualifi ed persons in planning and installing electric service to farms and residences.
Top Commercial / Residential Electrical Requirements *
Department of Community Development Building Division 4800 West 92 nd Avenue Westminster, Colorado 80031 For Information call (303) 658-2075 Fax (303) 706-3922 www.westminsterpermits.com Top Commercial
GUIDELINES FOR UTILITY INSTALLATIONS Part 1 - Wire Lines and Communications Cables
Engineering Department SEPTEMBER, 2007 GUIDELINES FOR UTILITY INSTALLATIONS Part 1 - Wire Lines and Communications Cables General Requirements This section applies to all public and private utilities,
Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016. Underground branch circuit feeding a detached garage:
Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016 * Garage construction requires permits (electrical, building) * Permits must be applied for at the time. * Dial
SUBJECT: NO MORE 300 VOLTS IN PLTC PRINT LEGEND
Belden Electronics Division P.O. Box 1980 Richmond, Indiana 47375-1980 2200 U.S. Highway 27 South Richmond, Indiana 47374-7279 Telephone: 765 983 5200 Facsimile: 765 983 5825 SUBJECT: NO MORE 300 VOLTS
The U.S. Department of Labor projects that electrician careers will grow to 698,200 by 2022.
The U.S. Department of Labor projects that electrician careers will grow to 698,200 by 2022. Train now for affordable Electrician careers and get wired for success. Residential Electrician Diploma Program
Direction of current flow through conductor. Fig. 1 Magnetic field generated by current flow
ingle Conductor Cable Copper heathed Cable heath Currents ingle conductor cables present certain application considerations that do not arise in multiconductor cable installations. These considerations
AC and DC Drive System Installation Information
Purpose This document contains the Parker SSD Drives recommendations for installing drive systems. These instructions must be followed for safe and reliable operation. Instructions CODES AND REGULATIONS
Electrical Code (NEC) Snake Tray Cable Management Solutions
Cable Pathway Use and Selection and the National Electrical Code (NEC) By Eric J. Sadler, BSME MIT Snake Tray Cable Management Solutions References: All references to the NEC in this presentation are taken
MOBILE HOME SERVICE REQUIREMENTS GAS
ELECTRIC AND GAS 1.0 INDEX 1.0 INDEX 2.0 PURPOSE 3.0 GENERAL 4.0 REFERENCE MATERIAL 5.0 TYPICAL UNDERGROUND UTILITY LAYOUT 6.0 METER PAD DETAILS 7.0 GENERAL INSTALLATION PROCEDURES 8.0 PEDESTAL SPECIFICATIONS
Structured Cabling, Earthing & Equipotential Bonding
White Paper Information and Communication Technology Structured Cabling, Earthing & Equipotential Bonding English Rev. 1.0.1 / 2012-06-01 1 Abstract All Dallmeier network products (PoE cameras, recorders,
TIA 569 Standards Update Pathways & Spaces. Ignacio Diaz, RCDD April 25, 2012
TIA 569 Standards Update Pathways & Spaces Ignacio Diaz, RCDD April 25, 2012 The purpose of this Standard is to standardize specific pathway and space design and construction practices in support of telecommunications
Cabinets 101: Configuring A Network Or Server Cabinet
Cabinets 101: Configuring A Network Or Server Cabinet North, South and Central America White Paper May 2012 www.commscope.com Contents Background Information 3 What is a network or server cabinet? 3 What
3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance
SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD SEN I N D E X Description 10 STANDARD TECHNICAL REQUIREMENTS 11 Standards 12 General Operating Conditions 13 General Description Of Switchboard 131 Structure 132
Lightning Arresters P30027 18 KVA P30038 10 KVA. Description & Installation
Lightning Arresters P30027 18 KVA P30038 10 KVA Description & Installation Printed in USA 09/11 TO330 Rev. B Table of Contents Page 1.0 SCOPE 2 2.0 PRODUCT OVERVIEW 2 2.1 Intended Uses 2 2.2 Lightning
INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1
City of Cotati Building Division 201 W. Sierra Ave. Cotati, CA 94931 707 665-3637 Fax 792-4604 INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1 Any PV system on a new structures should be included
Canopy Surge. User Manual
Canopy Surge Suppressor User Manual SS00-UM-en Issue 2 May 2003 2003 Motorola, Inc. All rights reserved. Printed in the U.S.A Notices Safety Precautions: Before beginning your installation, please read
Project Name: Nortrax Section 26 41 00 Project No: 13-013 SURGE PROTECTION DEVICES Page 1
Page 1 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. General: Drawings and general provisions of the Contract, including General and Supplementary Conditions and Divisions 1 Specification sections apply to
How to Estimate the Cost of a Clean Room and Data Center Equipment Electrical Work. Section 2 Types of Methods of Measurements page 4
How to Estimate the Cost of a Clean Room and Data Center Equipment Electrical Work Table of Contents Section 1 Introduction page 3 Section 2 Types of Methods of Measurements page 4 Section 3 Project Specific
GUIDELINES FOR WIRING SINGLE FAMILY DWELLING UNITS
GUIDELINES FOR WIRING SINGLE FAMILY DWELLING UNITS This guideline has been prepared to assist the owner/occupant of a single family dwelling with compliance to the requirements of the National Electrical
Voltage Drop. Voltage Drop 1
Voltage Drop The technical information provided herein is to assist qualifi ed persons in planning and installing electric service to farms and residences. Qualified person is defi ned in Article 100 of
DIVISION 27 COMMUNICATIONS. A. System design shall be completed by a Registered Communications Distribution Designer (RCDD).
DIVISION 27 COMMUNICATIONS 27 00 00 COMMUNICATIONS A. System design shall be completed by a Registered Communications Distribution Designer (RCDD). B. Comply with American National Standards Institute
DIVISION 26 - ELECTRICAL SECTION 26 05 20 CABLES FOR INSTRUMENTATION
DIVISION 26 - ELECTRICAL PART 1 - GENERAL 1.01 SUMMARY A. Section Includes 1. Instrumentation Cables 1.02 SUBMITTALS A. Submit in accordance with requirements of Section 01 33 00. B. Product Data: Submit
READ THIS MANUAL BEFORE PROCEEDING WITH THE INSTALLATION. FAILURE TO FOLLOW THE INSTALLATION INSTRUCTIONS MAY VOID YOUR WARRANTY!
READ THIS MANUAL BEFORE PROCEEDING WITH THE INSTALLATION. FAILURE TO FOLLOW THE INSTALLATION INSTRUCTIONS MAY VOID YOUR WARRANTY! The main power to any existing system must be disconnected prior to the
Shunt lock function 3066
Version: January 2004 Contents Alarm System Activation unit Deactivation unit Digital locking cylinder or Smart Relay 1.0 Method of Operation 4 1.1 General 4 1.2 Turning the Alarm System On 4 1.3 Turning
Enphase Engage Cable and Accessories
INSTALLATION MANUAL Enphase Engage Cable and Accessories 141-00016, Rev 03 Corporate Headquarters Contact Information Enphase Energy Inc. 1420 N. McDowell Blvd. Petaluma, CA 94954 USA Phone: +1 707-763-4784
Fundamentals of Power
Fundamentals of Power Fundamentals of Power 2008 American Power Conversion Corporation. All rights reserved. All trademarks provided are the property of their respective owners. Learning Objectives At
WHITE PAPER Fire & safety performance standards
WHITE PAPER Fire & safety performance standards Terminologies describing Fire Performance Terminologies describing Fire Performance often present a challenge to understand as how they apply to a cable
Grounding of Electrical Systems NEW CODE: Grounding and Bonding
Grounding of Electrical Systems NEW CODE: Grounding and Bonding Presented By Scott Peele PE Grounding of Electrical Systems Outline Defining the Terms Why should I Ground? Types of Grounding Systems Separately
TELECOMMUNICATIONS STRUCTURED CABLING GUIDELINES AND SPECIFICATIONS. University of Chicago IT Services Infrastructure Services October 2011
TELECOMMUNICATIONS STRUCTURED CABLING GUIDELINES AND SPECIFICATIONS IT Services Infrastructure Services October 2011 Table of Contents 1 Introduction... 4 1.1 Planning and Design... 4 1.2.1 Roles and Responsibilities...
SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL
SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL 1.1 SUMMARY A. This section describes the requirements for the installation of Power Monitors and associated
1. Furnish and install faceplate and modular jacks at each single gang outlet as described below:
Washington University in St. Louis Building: Communication Specification: Research Voice/Network/Typical 1. Furnish and install faceplate and modular jacks at each single gang outlet as described below:
IRRIGATION PUMPING Table of Contents - Section 900
IRRIGATION PUMPING Table of Contents - Section 900 PARAGRAPH 900.1 GENERAL 1 900.2 METERING REQUIREMENTS 1 900.3 CUSTOMER S CONTROL EQUIPMENT 2 900.4 SERVICE CONDUCTOR REQUIREMENTS 2 900.5 RECOMMENDATIONS
Power Distribution Considerations for Data Center Racks
Power Distribution Considerations for Data Center Racks Power Distribution Considerations for Data Center Racks Table of Contents 3 Overview 4 At what voltage do you run all the IT equipment? 4 What electrical
Questions and Answers for Heating and A/C Contractors
1. How do we accomplish grounding of furnaces and / or water heaters on two wire circuits? 250.134 Equipment Fastened in Place or Connected by Permanent Wiring Methods (Fixed) Grounding. Unless grounded
NUIG Campus Network - Structured Cabling System Standards Information s Solutions & Services (ISS)
NUIG Campus Network - Structured Cabling System Standards Information s Solutions & Services (ISS) Revision date 28 th January 2014 The purpose of this document is to assist Building Refurbishment and
SYSTEM 1850-SE SERVICE ENTRANCE CABLE SYSTEM
Pyrotenax SYSTEM 1850-SE SERVICE ENTRANCE CABLE SYSTEM Contents Introduction This section provides an overview of general circuit design considerations and installation guidelines for a Pyrotenax System
Short Circuit Current Calculations
Introduction Several sections of the National Electrical Code relate to proper overcurrent protection. Safe and reliable application of overcurrent protective devices based on these sections mandate that
Common Electrical Hazards in the Workplace Including Arc Flash. Presented by Ken Cohen, PhD, PE & CIH (Ret.)
Common Electrical Hazards in the Workplace Including Arc Flash Presented by Ken Cohen, PhD, PE & CIH (Ret.) 1 What s New In February 1972, OSHA incorporated the 1971 edition of the National Fire Protection
Protect your home and family with Advanced Technology from Cutler-Hammer
Protect your home and family with Advanced Technology from Cutler-Hammer Residential Home Fire Statistics Annually - over 415,000 Residential Fires Annually - over 40,000 electrical fires over 350 deaths
No Phone Line System. Quick Start Guide NPL II. 1.0 Installation
Used in conjunction with EntraGuard Gold Telephone Entry Systems, the provides No Phone Line communication and door or gate control through existing building telephone lines without the need purchase phone
Voltage Drop (Single-Phase)
Voltage Drop (Single-Phase) To Find: To Find Voltage Drop Formula: 2 x K x L x I V.D. = ------------------- C.M. Variables: C.M. = Circular Mill Area (Chapter 9, Table 8) To Find Voltage Drop Percentage
2012 Electrical Code Changes Module 2 Sections 6-16
2012 Electrical Code Changes Module 2 Sections 6-16 ETEL-11(02)-00 (2012-03-26) Table of Contents Section 6 Services and Service Equipment... 2 Section 8 Circuit Loading and Demand Factors... 6 Section
5SV Residual Current Protective Devices
s Siemens AG 2013 SENTRON 5SV Residual Current Protective Devices New portfolio for reliable personnel, material and fire protection Safe protection against residual currents Residual current protective
LSA-PLUS Series 2 Connection and Disconnection Modules and Accessories
LSA-PLUS Series 2 Connection and Disconnection Modules and Accessories 2015 PRODUCT CATALOG 2ND EDITION LSA-PLUS Series 2 Connection and Disconnection Modules and Accessories A technically and commercially
ELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS:
ELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS: Chapter 12 of the Burlington Code of ordinances allows owner occupants of single family homes to do their own wiring if they choose. If you choose to
Model Number Electrical Compatibility Module Connector Type. M250-60-2LL-S22 60 cell PV module MC-4 Type 2 Locking
TECHNICAL BRIEF M250 Microinverter System Installation Planning The M250 Microinverter The Enphase M250 Microinverter is a powerful and efficient grid-tied microinverter. It is compatible with most 60-cell
Definition AC Power Distribution
COMMON AC POWER DISTRIBUTION CONFIGURATIONS The input voltage needed to power electronic equipment is provided by the manufacture in the product specifications. Matching this requirement to the facility
GROWTH MANAGEMENT DEPARTMENT 201 SE 3 rd ST, (Second Floor), Ocala, FL 34471 (352) 629-8421; FAX: (352) 629-8264
BUILDING CODE GUIDELINES FOR ELECTRICAL INSPECTIONS Building Code compliance is the obligation of design professionals and/or contractors. Plan Review and Inspection Guidelines are intended to be used
Electrical Drawings - Table of Contents
Electrical Drawings - Table of Contents E1.0 Lighting Plan E1.1 Power Plan E2.0 Electrical Specifications E2.1 Electrical Specifications E3.0 Panel Schedule E3.1 Load Summary 1 2 1 Panel Schedule LP1
Project files. Customer copy Legrand copy
20 years warranties Project files Structured cabling Systems categories 6A, 6 & 5e Customer copy Legrand copy TO BENEFIT FROM LEGRAND WARRANTIES 1 Complete and sign the Identity document: Worksite details*,
CONSTRUCTION STANDARD ELECTRIC OPERATIONS ORGANIZATION
Page 1 of 11 ****This Standard Supercedes BECo CS2.13-2.3 & ComElectric OH Construction Manual, System Grounding Section, drawings CGND, GRDSUM, and C2**** 1.0 Bill of Materials GROUNDING AND BONDING POLE-MOUNTED
Voltage Rated operating voltage [kv] 12 24 Rated power frequency withstand voltage [kv] 28 50 Rated lightning impulse withstand voltage [kv] 75 125
Standards and Regulations IEC 62271-200 ; VDE 0671-200 ; BS EN 62271-200 Technical Data MC3-12 MC3-24 Voltage Rated operating voltage [kv] 12 24 Rated power frequency withstand voltage [kv] 28 50 Rated
Electrical Code Regulation
Electrical Code Regulation St. Clair County has adopted the 2005 National Electrical Code in its entirety for the unincorporated areas of the county and all communities that have contracted with the county