1 Construction Services Building Strategy Standards for Wiring Telecommunications Networks in Cornwall Council Buildings Version 4.2 April 12 th 2012 Environment
2 Building Strategy Standards for Wiring Telecommunications Contents 1 Introduction 3 2 Horizontal distribution cabling Specification and standards Density of outlet distribution Outlet location and cable containment Service to desks Testing of UTP cabling 5 3 Telephone distribution cabling General principles Specification and standards Testing of telephone cabling 6 4 Network wiring centres Location Patch frames Patch cables 8 5 Backbone cabling Fibre optic backbone Mechanical Performance Optical Specifications Fibre Optic Connectors Fibre Optic Patch Cords Compliance with international standards Testing Telephone backbone General principles Specifications and standards Testing 11 6 Implementation 11 7 Warranty 12 8 Documentation and labelling Labelling Documentation 13 9 Acceptance 13 Version 4.2 2
3 1.0 Introduction This document outlines the standards to which telecommunications cabling must conform for any new works, additions to existing installations and repairs. Standards for electrical installation are documented elsewhere. Where a supplier wishes to respond to both the telecommunications and electrical elements of a given tender both standards will apply. New cabling installations will be expected to support the following applications: Ethernet local area networks at 10Mbps, 100Mbps and 1000Mbps. Data Centre local area networks at 10Gbps Power over Ethernet PABX analogue extensions. PABX digital extensions. ISDN2 circuits. PTO analogue circuits. Video baseband and RGB RS232 at up to 19.2Kbps. For each installation a Schedule will be supplied which will document the detail of the requirement together with any variations to this specification. As well as complete installations suppliers may be invited to provide a terminate and test service in relation to cables run in by others. The following conditions will apply in all cases: A documented network design including outlet quantity and layout must be agreed with the Council s Project Manager before work commences. Acceptance testing will be required to confirm that the installed system meets the defined specifications and standards. All cabling work will be fully documented. In addition, unless otherwise agreed or specified in the Schedule: Wiring to final outlet destination points in new office installations will be via 4-pair Category 5e UTP cables. Wiring to final outlet destination points in new data centre installations will be via 4-pair Category 6a Shielded UTP cables. Wiring to final outlet destination points in existing installations will be via 4-pair Category 5e or Category 6a cables to match the existing. Links between wiring closets and campus buildings will be via fibreoptic cables (50/125 OM3 Multimode) Voice connections between wiring closets and exchanges will be via copper pair cables. Additions to existing installations will use components from the same manufacturer. New data centre installations will use components from the same manufacturer. All cables, trunking and other components will be constructed of low smoke, zero halogen (LS0H) / low smoke and fumes (LSF) materials. Version 4.2 3
4 2.0 Horizontal distribution cabling 2.1 Specification and standards The cable and component quality and the installation and termination techniques must, as a minimum, comply with all relevant parts of EN50173 and EN50174; Cat 5 enhanced / Cat 6a standards, to support application class D. The cable is to be unshielded four twisted pair, with nominal impedance 100. Outlets will conform to EN (eight position modular connector) and be capable of receiving 24 AWG solid and stranded wires terminated by insulation displacement methods. Termination is to be to the T568B standard. The following installation standards will apply: The length of each horizontal cable from patch panel to telecommunications outlet is not to exceed 90 metres Maximum bending radius during installation of 75mm Maximum final bending radius of 25mm Maximum pulling load of 38 kg/m Cables to be secured at both ends using the fixings provided Cable ties are not to be over-tightened to a point where they cause strain on the cable sheathing Segregation from power of 150mm unless contained in purposedesigned multi-compartment trunking, in which case the length of the parallel run should be kept to a minimum 2.2 Density of outlet distribution Unless otherwise specified in the Schedule, the density of outlets will be based on floor area and will be as follows, where the term outlet should be taken to mean a single RJ45 point. The outlets will be evenly distributed around the area. For a data-only installation in a normal work area the minimum density is to be 2 outlets (1 double outlet) for every 9 sq m. For a voice and data installation in a normal work area the minimum density is to be 4 outlets (2 double outlets) for every 9 sq m. For installations in classrooms the minimum density is to be 4 outlets (2 double outlets) for every 9 sq m. For other locations such as computer rooms and meeting rooms the density may be higher or lower than normal and will be specified in the Schedule. 5.3 Outlet location and cable containment In all cases, double outlets will be mounted on single gang faceplates and quad outlets will be mounted on double faceplates. All containment will be surface-mounted unless otherwise stated. Perimeter trunking at dado rail height is the preferred method of containment in areas of normal outlet density. Where possible, the bottom of the trunking should be at least 25 mm above normal desk height. Trunking at skirting level should be used only where dado trunking is impracticable. Existing trunking Version 4.2 4
5 should be used where feasible in which case the supplier will be responsible for fitting suitable back-boxes. Individual wall-mounted back-boxes should be used in areas of low outlet density. Outlets will not be mounted on moveable partition walls unless an adequate distribution cannot otherwise be achieved; in such circumstances the preferred solution is to install the horizontal termination in the ceiling space above. Where the smaller dimension of a room exceeds 8m, provision will be made for locating outlets remotely from the walls using purpose-made poles or floor-boxes. Installation practice is to ensure that the cable is not subjected to excessive lateral or longitudinal strain in installation and that support by tie wrap of cable bundles is provided at 0.5m intervals on vertical runs and 1.5m intervals on horizontal runs. Minimum bending radii of 20 times cable diameter during installation and 10 times diameter after installation will be maintained at all times. Cable pair twist must be maintained during stripping and termination. Where main cable runs are located above suspended ceilings or below floors, basket or tray fixed to the building structure will be used. This will also apply to cable run between building floor levels. Under floor installations in particular must be adequately protected from attack by vermin. Baskets / trays should not be more than 60% full in a new installation. Under no circumstances will cables be loose-laid. 5.4 Service to desks The supplier may be required to provide the service to the desks in which case the following will apply: Extension from horizontal outlet to user workplace will normally be by drop leads direct to the desk, terminated at each end in RJ45 plugs. These cables will be factory made and conform to the cable and connector specifications required to meet EN50173 enhanced application class D standards. The cable feed into the desk should be installed through appropriate desk cable management. Where cable management does not exist, cable ties, trunking, etc. must be used to secure cables appropriately. Approximately one metre free tail should be left for equipment connection, and the remainder neatly contained within the desk. 5.5 Testing of UTP cabling Unless otherwise specified in the Schedule, 100% of the installed UTP cables will be tested in accordance with the latest draft of EIA/TIA TSB67. The tests are to include: Length Wire map Attenuation NEXT ELFEXT ACR Return loss Propagation delay Delay skew Version 4.2 5
6 NEXT, ELFEXT and ACR should ideally be tested under power sum conditions. Details of the test equipment to be used and documentary evidence of regular calibration will be required. 3.0 Telephone distribution cabling 3.1 General principles Three types of telephony service may be encountered: IP Telephony as part of a structured cabling system PBX-based with separate distribution using voice-grade cable PBX-based as part of a structured cabling system IP Telephony requires only compatibility with Power over Ethernet. Separate distribution using voice-grade cable will follow the standards set out in Section 5.2. The remainder of this section applies where PBX-based telephony is used as part of a structured cabling system. The precise wiring configuration will be specified in the Schedule. The telephone system supplier will terminate the extension wiring on a Test Jack Frame (TJF). The wiring contractor will terminate the distribution wiring on an adjacent Main Distribution Frame (MDF) which will, in turn, be connected by multi-pair voice-grade cable to voice patch panels in the main (or only) wiring centre. Where there is more than one wiring centre the distribution will be in accordance with Paragraph An additional provision of 20% beyond that which is currently required should be made to allow future phone provision to be satisfied through patching rather than physical rewiring. Distribution frames and boxes should not be mounted at floor or ceiling level or behind furniture or cabinets. 3.2 Specification and standards Unless otherwise specified, two pairs will be connected to each voice patch panel outlet; pair 1 will be connected to RJ45 pins 4&5 and pair 2 will be connected to pins 3&6. The MDF must be connected by a dedicated 6mm 2 cable to a clean earth point in accordance with BS7671. All voice cabling is to comply with BS6701. copper cable within buildings is to conform to the BT CW1308 specification and will be terminated on punch-down strips type 237A. The frames onto which the wires are connected will be clearly labelled in ascending numerical order, allowing for each connected circuit to be documented with a frame, row, and location detail, e.g. 1A-39-6 will relate to a circuit connected to frame 1A, row 39, location 6. The following jumper wire colours will be used with punch-down strips: Green/yellow ISDN connections Blue/yellow wire Analogue connections Red/white Digital connections At no point should jumper wires be pulled tight or bend more than 90 o. 3.3 Testing of telephone cabling Unless otherwise specified in the Schedule, 100% of the installed cabling will be tested for: Version 4.2 6
7 Continuity Attenuation Insulation Wire map 4.0 Network wiring centres 4.1 Location Suitable locations for wiring centres must be agreed in advance and will be specified in the Schedule. Office areas, kitchens and any areas subject to excessive dust, damp or temperature extremes should not to be used. 4.2 Patch frames The Schedule will specify whether patch panels are to be installed in an open frame or an enclosed cabinet. Enclosed cabinets should have a toughened glass or acrylic lockable front door and removable steel sides via internal release. Floor-standing cabinets should have a lockable steel back door. If the cabinet is not fully enclosed it should be located in a secure room for security purposes. The cabinet or frame must be equipped with effective vertical and horizontal cable management. The frame is to be a minimum of 700mm wide and a minimum depth of 600mm to permit tidy vertical routing of patch cords and installation of PoE switches. Where servers (including VoIP controllers) are to be accommodated the minimum depth is to be 1000mm. The Schedule will specify if the density of the patch ports is 24 ports per row with horizontal cable management included every two rows, or 48 ports per row with horizontal cable management included every other row. To facilitate cable tracing vertical cable management must take the form of bars or loops rather than plates with holes. Unless otherwise specified, the standard configuration for wiring frames should be as shown in the diagram below. Fibre Cable connections are to be terminated at the top of the frame with copper voice ports underneath. Unless specified in the schedule the voice ports are to only take up 1U in space. The total space occupied by the outlet patch must not exceed 75% of the frame capacity. To meet this condition in large installations multiple identical frames should be combined with clear access between. Cabinets and frames up to 22u in height are to be equipped with a power strip with a minimum of six 13A sockets. Larger cabinets and frames are to be equipped with a minimum of 12 sockets. Sockets should be off-set from the centre line and / or spaced so as to permit the use of typical lowvoltage power supply units. If specified in the Schedule a rack-mounted UPS is to be supplied and installed as shown in the diagram and the power strip connected to its output. The mains supply to the cabinet or frame is to be taken from a switched / fused spur fed from a clean radial circuit and labelled with the distribution board reference. In addition the frame must be connected to a clean earth source in accordance with current IEE wiring regulations BS7671. Version 4.2 7
8 Horizontal cable management to be fitted every 2U if using 24 ports, or every 1U if using 48 ports. 4.3 Patch cables Patch cables will be factory made and conform to the cable and connector specifications required to meet EN50173 enhanced application class D standards. The following coloured cables will be used to signify the type of connection: GREY Non-critical data RED Critical voice or data BLUE Non-critical voice GREEN Cross-over between active devices BLACK DMZ / restricted access MAROON ISDN or BT Direct dial (ISDN lines have yellow tag on end). YELLOW Test environments ORANGE Public / shared networks BROWN Uncontrolled / untrusted networks PINK Server management (including ILO) Patch cables must be of appropriate length and routed tidily using horizontal and vertical cable management. Version 4.2 8
9 5.0 Backbone cabling 5.1 Fibre optic backbone Unless otherwise specified in the Schedule, new optical fibre cable shall consist of multimode graded-index 50/125 m (minimum OM3 standard) the following specifications: Mechanical Performance Cable minimum bend radius: 20 times cable diameter during installation and 10 times cable diameter after installation. Buffered fibre minimum bend radius: 19 mm Operating temperature range: -10 to +50 degrees C Storage temperature range: -40 to +70 degrees C Optical Specifications Maximum fibre loss shall meet or exceed the following specifications: 3.0 db/km at 850 nm 1.0 db/km at 1300 nm Minimum bandwidth shall meet or exceed the following specifications: 400 MHz-km at 850 nm 600 MHz-km at 1300 nm Numerical aperture : Fibre Optic Connectors SC style connectors shall be used which meet or exceed the following specifications: Operating temperature: -10 to +75 degrees C Average loss: 0.3 db Extensions or modifications to existing 62.5/125µ cables should use ST style connectors Fibre Optic Patch Cords Fibre patch cords for new installations shall consist of duplex, buffered, graded-index 50/125 µm (minimum OM3 standard) fibres. Unless otherwise specified, fibre patch cords shall be terminated at both ends with dual SC connectors. The fibre patch cords are to meet the following specifications: minimum bend radius: 30mm operating temperature: -10 to +70 degrees C loss: 0.4 db per mated connector minimum bandwidth at 850nm: 400 MHz-km minimum bandwidth at 1300nm: 600 MHz-km 62.5/125µm patch cords with ST style connectors may be specified for extensions or modifications to existing installations Compliance with international standards Fibre-optic cabling will conform to BS7718. Multi Mode Fibre Minimum OM3 (ISO11801) Version 4.2 9
10 5.1.6 Testing 100% of the installed fibre-optic cables will be tested after termination at both ends. The tests will comprise a simple measurement of power loss, and an OTDR test at 850nm and 1300nm wavelengths to demonstrate that the installed cable meets the parameters specified in paragraph Telephony backbone General principles This section applies where PBX-based telephony is used as part of a structured cabling system. No installation should be carried out using voice grade cable. Where multiple wiring centres are to be used the preferred solution is to employ a main voice patch panel and one or more subsidiary voice patch panels in the main wiring centre as shown in Diagram 5.2.1(a) below. The MDF is to be connected to the main patch panel and each of the remote wiring centres is to be connected to a subsidiary patch panel. Crossconnection between the main and subsidiary patch panels is made using UTP patch leads. Wiring Centre 2 TJF MDF Main Wiring Centre Cat5 Patch Subsidiary Voice Patch Main Voice Patch a Wiring Centre 3 PBX 5.2.1(a) - Preferred distribution Alternatively, a multi-pair cable from the MDF may be terminated on a distribution point (DP) in each remote wiring centre as shown in Diagram 5.2.1(b) below. The DP (consisting of punch down strips type 237A mounted in a suitable box) will then be connected to the voice patch panel. The multi-pair cable terminations at the MDF should be clearly labelled. The label should indicate the wiring centre names and the individual voice port numbers. Version
11 Wiring Centre 1 DP TJF MDF a DP Wiring Centre 2 PBX 5.2.1(b) - Alternative distribution Specifications and standards All voice cabling is to comply with BS6701. copper cable within buildings is to conform to the BT CW1308 specification. Where copper cable is run between buildings, either outdoor grade cable to CW1128 specification or indoor / outdoor cable to CW1308B specification will be used. Outdoor cable should be terminated within 1m of the entry point into the building and extended using indoor cable. Cables will be terminated at Distribution Points (DPs) consisting of punch-down strips type 237A mounted in suitable boxes. Where specified in the Schedule surge arrestors are to be fitted at the ends of outdoor cables. These should be Oneac Line Analogue Protectors from Chloride Power, order code US10AP200 or US10AP1. The strips onto which the wires are connected will be clearly labelled in ascending numerical order, allowing for each connected circuit to be documented with a frame, row, and location detail, e.g. 1A-39-6 will relate to a circuit connected to frame 1A, row 39, location Testing Unless otherwise specified in the Schedule, 100% of the installed cabling will be tested for: Continuity Attenuation Insulation Wire map 6.0 Implementation The timetable for installation will be as defined in the schedule, where any interface with other contractors, particularly with regard to provision of Version
12 containment and power, will also be noted. The supplier must nominate a project manager who will be responsible for all aspects of the installation and for liaison with the Council s representatives including site visits. Sound working practice must be employed throughout. The supplier is responsible for drilling any necessary holes and attaching fittings and equipment to buildings. Every reasonable precaution must be taken in order not to cause damage or compromise the structural integrity. Where appropriate the council s project manager should be consulted. The council s Project Manager is responsible for ensuring the building the work is due to take place in has a full and valid type 2 asbestos report. This report needs to include all areas of the building that work is to take place including wall cavities, attic spaces and otherwise unused areas of the building not just the office space. If this report is not available then work will have to be rescheduled until a new asbestos survey is carried out by EP&E Labs. A flow chart for how to progress the asbestos report is attached to the bottom of this document, and for people with access to the Cornwall Council Intranet the full process can be found here. The supplier is responsible for ensuring that they request the above asbestos report for all work areas they are required to work in if the report isn t presented to them at the time of an initial survey. All further issues should be mailed to [email protected] Redundant and waste materials must be disposed of in accordance with the current WEEE Directives. Every effort should be made to avoid breaching fire breaks. Where a breach is unavoidable the break must be made good using an approved material such that current fire regulations are adhered to. The supplier must, at all times, adhere to the Council s current Health & Safety policies. In particular, safe working practices must be employed and work areas must be kept free from accumulations of materials, debris and equipment. Hazardous areas must be cordoned off and prominent warnings displayed. 7.0 Warranty A comprehensive warranty will be required providing the following minimum cover: 1 year on component defects 15 years on conformance to specification Suppliers must state whether or not the warranty is underwritten by a system manufacturer. Any caveats and conditions must be stated and agreed in advance. 8.0 Documentation and labelling 8.1 Labelling Patch panels, the Main Distribution Frame, and any Distribution Boxes used are to be fully labelled with clear unambiguous information. Cables will be individually labelled at a point 150mm from each termination. Telecommunications outlets will be labelled in a logical sequence around each room and the home terminations on the patch panel will also be Version
13 presented in a logical order and labelled with the corresponding outlet number. Where multiple wiring cabinets or frames are in use each frame will be labelled and its number referenced on corresponding outlets (e.g. Outlet 1A/025 is terminated on Frame1A, Outlet 2A/120 is terminated on Frame2A), this is to ensure any future expansion in a patch panel with multiple frames follows a logical numbering order. For large installations this detail will be specified on the schedule. 8.2 Documentation The following minimum documentation is to be supplied: Test results as identified above these may be in electronic form provided they are accompanied by a certificate confirming that each cable conforms to the test requirements identified above. A plan of the installation with cable routes and outlet numbers marked on it. Preferably this should be in AutoCAD (.dxf) or Microsoft Visio (.vsd) format. Appropriate warranties as defined above. A certificate to confirm that the voice cabling conforms to BS In addition for larger works (100 outlets or more): As installed cable distribution details in Microsoft Excel format, associating each cable and outlet with its location. Face plans of main distribution frame, patch panels and cabinets. Details of the wiring configuration used throughout for both horizontal wiring and for voice patch panels. 9.0 Acceptance Final acceptance will be dependent on the following: Confirmation that the installation meets this specification and the associated schedule in all respects. Receipt of satisfactory test results and documentation as described in paragraph 8. Receipt of the warranty as described in paragraph 7. The supplier will be required to remedy, at no cost to the council: Any and all deficiencies and non-compliance identified at handover Any faults that develop during the warranty period Version
14 Identify work/maintenance to be carried out Does it affect the fabric or materials within the property? NO Proceed with work/maintenance activity. YES Is the Asbestos Management Plan/Register available? NO Does the work involve breaking into or through Inaccessible Areas? YES Stop Work Contact ESL before proceeding YES NO Consult Register Can the affected material(s) be positively identified as non-acm s? NO Stop Work Contact ESL before proceeding Contact ESL for advice before proceeding Stop Work YES Does the Register indicate any ACM s that could be affected? YES Proceed with work/maintenance activity. NO Does the work involve breaking into or through Inaccessible Areas? YES Stop Work Contact ESL before proceeding. NO Proceed with work/maintenance activity. Monitor the maintenance/ works operations NO Are any suspicious materials encountered? YES Stop Work Contact ESL before proceeding ESL ACM KEY Engineering Services Laboratory Asbestos Containing Material Start of Process Completion Work by Premises Coordinator Work by Premises Coordinator with ESL Work by Premises Coordinator with Contractor Version
15 Prepared by: Strategic Planning and Standards Property Services 12 th April 2012 Rev Introduction: Category 6 UTP cable to be used in new installations. 1. Introduction: All components to be made from LS0H / LSF materials. 4.2 Patch frames: Minimum depth 1000mm where servers to be accommodated Introduction: Category 5e UTP cable to be used in new office installations. 1. Introduction: Category 6a Shielded UTP cable to be used in new data centre installations. 1. Introduction: New data centre installations will use components from the same manufacturer. 5.1 Fibre: Multi Mode Fibre Minimum OM3 (ISO11801) Patch Frames: 24 port and 48 port configurations to be used. 4.2 Patch Frames: New layout for patch panels. 4.2 Patch Frames: Only 1U s worth of voice ports are required unless specified. 5.2 Telephony Backbone: Section needs to be added to cover VoIP 6 Implementation: Council Project Managers responsibility to obtain full Asbestos reports for all areas of the building, not just office space. 8.1 Labelling: Each frame in a cab to have its own number scheme to enable future expansion to follow logical number order. If you would like this information in another format please contact: Cornwall Council County Hall Treyew Road Truro TR1 3AY Telephone: [email protected] Version
1.1 SYSTEM DESCRIPTION.1 Data system includes data outlets and wiring for office and school applications.
Issued 2005/06/01 Section 16743 Data System Page 1 of 7 PART 1 GENERAL 1.1 SYSTEM DESCRIPTION.1 Data system includes data outlets and wiring for office and school applications..2 Data system equipment
Specifying an IT Cabling System
Specifying an IT Cabling System This guide will help you produce a specification for an IT cabling system that meets your organisation s needs and gives you value for money. You will be able to give your
NUIG Campus Network - Structured Cabling System Standards Information s Solutions & Services (ISS)
NUIG Campus Network - Structured Cabling System Standards Information s Solutions & Services (ISS) Revision date 28 th January 2014 The purpose of this document is to assist Building Refurbishment and
IT Services Converged Network Installation Specification:
IT Services Converged Network Installation Specification: Author: Phil Gregory Status: Published Last Modified: 21 August 2015 Last Modified by: Phil Gregory Updates: Version Date (Initial) Comments 1.1401
Network Design. Yiannos Mylonas
Network Design Yiannos Mylonas Physical Topologies There are two parts to the topology definition: the physical topology, which is the actual layout of the wire (media), and the logical topology, which
Category 6 Solutions. 4. Category 6 Solutions. 09/08 400836IN TrueNet Structured Cabling. Introduction... 4.2. Cable... 4.3. Patch Panels... 4.
Category 6 Solutions Introduction... 4.2 Cable... 4.3 Patch Panels... 4.4 Modules... 4.6 Patch Cords... 4.12 Outlets... 4.16 Faceplates...4.18 4. 1 Search Category 6 Solutions Introduction ADC KRONE s
Installation Manual For Support Call 01704 807114 or email [email protected]
Installation Manual Hip Smart Hub (Standard BT and BT FTTP Sites) The Home Network Hub houses the Home Owner s Broadband Router and connects the hardwired network ports on that Router to three network
NTU Data Communications Cabling Specification
NTU Networking Standards Document Circulation List NTU Data Communications Cabling Specification Purpose of this Document This document sets out the specification required for NTU data communications cabling
ADC Structured Cabling Solutions
ADC Structured Cabling Solutions The highest performing cross-connect system in the world HighBand Wall Mount Patching Solution Reliable, secure and cost effective ADC s HighBand cross connect solution
Terminating 25-Pair Cable and 4-Pair Cross Connects
Terminating 25-Pair Cable and 4-Pair Cross Connects Estimated Time: 90 minutes Number of Teams: 2 Number of Team Members: one to four This Lab has four major parts that will be addressed separately. 1.
Information and Communication Technology Network Cabling Infrastructure Standard
Approved on Dec-2005 by Eugene Formato Manager, Communications Services Last Amended Aug-2009 by Jarren Beveridge Network Engineer, Communications Services Scheduled for Review Jan-2010 Information and
Cat 5, 6 or 7? Standards. Background. A University Standard for Structured Wiring. Network Points Installed. British Standards.
Cat 5, 6 or 7? A University Standard for Structured Wiring. Background isolutions recently formed Incorporates all IT service providers within the University. Focus on all ICT needs of the user and the
ANSI/TIA/EIA - 568-A, Commercial Building Telecommunications Cabling Standard.
WIRING STANDARD INTRODUCTION This standard defines a telecommunications wiring system for North Dakota State Agencies, offices or buildings that will support a multi-product environment. The purpose of
LSA-PLUS Series 2 Connection and Disconnection Modules and Accessories
LSA-PLUS Series 2 Connection and Disconnection Modules and Accessories 2015 PRODUCT CATALOG 2ND EDITION LSA-PLUS Series 2 Connection and Disconnection Modules and Accessories A technically and commercially
LIEBERT VNSA Installation Sheet
LIEBERT VNSA Installation Sheet Description The Liebert vnsa network switch is designed for connecting multiple Ethernet-ready devices and comes in various models. The unit may have: A Liebert icom display
DIVISION 27 COMMUNICATIONS. A. System design shall be completed by a Registered Communications Distribution Designer (RCDD).
DIVISION 27 COMMUNICATIONS 27 00 00 COMMUNICATIONS A. System design shall be completed by a Registered Communications Distribution Designer (RCDD). B. Comply with American National Standards Institute
TCTC Cabling Specifications
TCTC Cabling Specifications Purpose: To provide a standard specification that will be used for all Tri County Technical College (TCTC) facilities requiring structured cabling installation. Product specifications,
Panduit 28 AWG Patch Cords Installation Guideline
Panduit 28 AWG Installation Guideline Introduction Panduit is a leading supplier of Structured Cabling Systems and Unified Physical Infrastructure. Panduit solutions enable the physical infrastructure
STANDARDS FOR STRUCTURED CABLING FOR GOVERNMENT, MINISTRIES, DEPARTMENTS AND AGENCIES
STANDARDS FOR STRUCTURED CABLING FOR GOVERNMENT, MINISTRIES, DEPARTMENTS AND AGENCIES 2013 DOCUMENT DETAILS Security Classification Authority Author Documentation Status Government/Public National Information
HARTING Ethernet Cabling 8-poles Overview
Ethernet Cabling 8-poles Overview RJ45 Connectors [on page 8] System cables [on page 12] Distribution modules and Outlets [on page 17] Connectors [on page 20] System cables [on page 26] Panel feed-throughs
InstaPATCH Cu Cabling Solutions for Data Centers
SYSTIMAX Solutions InstaPATCH Cu Cabling Solutions for Data Centers Design Guidelines August 2008 www.commscope.com Contents Overview 1 Instapatch Cu Solution Specification 2 Harness Assembly Design 3
IT&T Infrastructure Standards
Technology Services IT&T Infrastructure Standards Version 1.5 17 th April 2015 Page 1 Table of contents 1 CHANGE HISTORY... 3 1.1 DOCUMENT HISTORY... 3 1.2 REVIEWERS... 3 1.3 APPROVALS... 3 2 INTRODUCTION...
Presenters Brett Weiss, Gabe Martinez, Brian Kroeger.
1 Presenters Brett Weiss, Gabe Martinez, Brian Kroeger. Topics to be covered: Cable identification Purpose of the various cable types Installation techniques Building Infrastructure Overview of networking
Standard Comms Rooms Specification
Standard Comms Rooms Specification Room Configuration Electrical General Distribution Boards Small Power Lighting Containment Fire Detection General To be defined in the project brief but should meet requirements
A guide to connecting to fibre optic networks for homeowners, architects, builders and developers.
A guide to connecting to fibre optic networks for homeowners, architects, builders and developers. Chorus is New Zealand s largest telecommunications utility company. We maintain and build the local access
The Evolution of Copper Cabling Systems from Cat5 to Cat5e to Cat6 Copper Cabling Standards and Technical Aspects
The Evolution of Copper Cabling Systems from Cat5 to Cat5e to Cat6 Copper Cabling Standards and Technical Aspects White Paper /7/0 Executive Summary Now that the TIA/EIA-568-B.- Category 6 Copper Cabling
Category 6 UTP - Cabling System
AMP NETCONNECT Category 6 UTP Cabling System...... real Category 6 Performance, both on Component as well as on System level! Owing to the extreme high performance of the AMP NETCONNECT Category 6 UTP
1. Furnish and install faceplate and modular jacks at each single gang outlet as described below:
Washington University in St. Louis Building: Communication Specification: Research Voice/Network/Typical 1. Furnish and install faceplate and modular jacks at each single gang outlet as described below:
NORTH ORANGE COUNTY COMMUNITY COLLEGE DISTRICT SECTION 27 10 00 STRUCTURE CABLING TESTING
RELATED SECTIONS: NORTH ORANGE COUNTY COMMUNITY COLLEGE DISTRICT Section 27 00 00 General Requirements Section 27 02 00 General Communication Requirements Section 27 05 26 Grounding and Bonding for Communications
Minimum Standards for Data/Voice Infrastructure in New Building Construction
UNIVERSITY OF WATERLOO Minimum Standards for Data/Voice Infrastructure in New Building Construction 12/17/2012 Offices 1. Two Work Area Outlets (WAO) on opposite walls, each with 2 jacks 2. Each WAO shall
Emergency Telephone Systems
Standard Issued Date: 22 May 2014 Important Warning This document is one of a set of standards developed solely and specifically for use on the rail network owned or managed by the NSW Government and its
Structured Wiring Specifications ERAU Daytona Beach Campus (Dec 14 2011)
Structured Wiring Specifications ERAU Daytona Beach Campus (Dec 14 2011) A. Objectives The Information Technology (IT) Department of Embry-Riddle Aeronautical University (ERAU) seeks to establish a standards-based
Peak Atlas IT. RJ45 Network Cable Analyser Model UTP05. Designed and manufactured with pride in the UK. User Guide
GB05-6 Peak Atlas IT RJ45 Network Cable Analyser Model UTP05 Designed and manufactured with pride in the UK User Guide Peak Electronic Design Limited 2001/2012 In the interests of development, information
Communications Infrastructure Standards & Specifications
Communications Infrastructure Standards & Specifications Copper and Optical Fibre Cabling Specification Revisioning version date Author 1.0 2/4/2013 Sean McHugh 1.1 9/7/2013 Sean McHugh Page 1 Table of
108-93018 05 APR 2016 Rev M
Product Specification 108-93018 05 APR 2016 Rev M Copper LAN Cable 1. SCOPE 1.1. Content This specification describes the general requirements for CommScope copper LAN cable. 2. APPLICABLE DOCUMENTS The
UT Southwestern Medical Center Information Resources Cable Installation Standard
UT Southwestern Medical Center Information Resources Cable Installation Standard PART 1- GENERAL 1.01 SUMMARY A. Furnish and install wire, cable, devices, equipment, and accessories for a complete system
SECTION 25110 TELECOMMUNICATION ROOMS
PART 1 - GENERAL 1.1 SUMMARY A. SCOPE SECTION 25110 TELECOMMUNICATION ROOMS 1. This section includes the minimum installation requirements for equipment and cabling infrastructure in Telecommunication
5-port / 8-port 10/100BaseTX Industrial Ethernet Switch User Manual
5-port / 8-port 10/100BaseTX Industrial Ethernet Switch User Manual Content Overview... 1 Introduction... 1 Features... 3 Packing List... 4 Safety Precaution... 4 Hardware Description... 5 Front Panel...
NoteLocker 8 NoteLocker 8 as a Floor-standing Solution
NoteLocker NoteLocker 8 NoteLocker 8 as a Floor-standing Solution NoteLocker 8 is a modular storage and charging cabinet with 8 separate storage compartments. In each compartment a laptop, mobile phone,
Installing a Physical Network. Chapter 8
Installing a Physical Network Chapter 8 Contents Recognize and describe the function of basic components in a structured cabling system Explain the process of installing structured cable Install a network
LevelOne IFE-0500 4-Port PoE + 1-Port TP Industrial Fast Ethernet Switch User Manual
LevelOne IFE-0500 4-Port PoE + 1-Port TP Industrial Fast Ethernet Switch User Manual Ver. 1.0.0-0711 1 FCC Warning This Equipment has been tested and found to comply with the limits for a Class-A digital
Cable Installation Project
Cable Installation Project 1. Intent. It is the intent of the U.S. Court of Appeals to install Category 6 (CAT6) data cabling in the Robert F. Peckham Federal Building and United States Courthouse, 280
TELEPHONE CABLING TECHNOLOGY INFINITY CABLING
TELEPHONE CABLING TECHNOLOGY Main Types Outdoor Voice Grade Telephone Cable Heavy Duty Type, Weatherproof, Sun Protected, Mechanical protection from damage. Some types can be buried in the ground. Cable
SECTION 17400 ACCESS CONTROL SYSTEM. CONDITIONS OF THE CONTRACT AND DIVISION 1, as applicable, apply to this Section.
SECTION 17400 ACCESS CONTROL SYSTEM CONDITIONS OF THE CONTRACT AND DIVISION 1, as applicable, apply to this Section. PART 1 - GENERAL 1.1 RELATED WORK A. 16060 Grounding and Bonding B. 16070 Electrical
SECTION 27 13 24 COMMUNICATIONS OPTICAL FIBER OSP CABLING
SECTION 27 13 24 COMMUNICATIONS OPTICAL FIBER OSP CABLING PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications includes all labor necessary to perform and complete
SHEET 1 COMMUNICATION NETWORKS COMPUTER AND TELEPHONE SYSTEMS
STRUCTURED CABLING SHEET 1 COMMUNICATION NETWORKS COMPUTER AND TELEPHONE SYSTEMS INTRODUCTION In recent years, communications have taken on a crucial role in development for businesses. Communications
Polymer Coated Fiber Cable (PCF)
Polymer Coated Fiber Cable (PCF) Panduit has introduced a Polymer Coated Fiber (PCF) to their fiber cable offering available in 50µm and 62.5µm core diameters. Along with this cable having a stronger durability
Intelligent Cable Management Systems
Intelligent Cable Management Systems Bringing Practical Application Karen Pearson - Leviton Why Cable Management Matters Performance Cooling and air-handling Maintenance ANSI/TIA 569* Telecommunication
DESIGN GUIDELINES. Local Area Network
DESIGN GUIDELINES Local Area Network The total oversight and management responsibilities for information assurance (IA) and protection of DoDEA s critical infrastructure fall under the purview of the DoDEA
TrueAlarm Fire Alarm Systems
TrueAlarm Systems UL, ULC, CSFM Listed; FM Approved* Network Annunciators; es Features Provides a dedicated local area network (LAN) for connection of a TrueSite workstation server to remote clients: es
Network Cabling Guide
Network Cabling Guide Poor or incorrectly installed network cabling can cause numerous problems with your computer network. Whilst we recommend that you employ a network / cabling specialist to wire and
Structured Cabling, Earthing & Equipotential Bonding
White Paper Information and Communication Technology Structured Cabling, Earthing & Equipotential Bonding English Rev. 1.0.1 / 2012-06-01 1 Abstract All Dallmeier network products (PoE cameras, recorders,
Utilities and existing services
Construction Services Building standards for mechanical and electrical installations Utilities and existing services October 2012 Directorate: Environment Construction Services - Building standards for
BIX Cross-Connect System Distribution Connectors, Multiplying Connectors and Modular Jack Connectors
C O M M E R C I A L N E T W O R K I N G C O P P E R 15.13 Distribution Connectors, Multiplying Connectors and Modular Jack Connectors A0393146 QCBIX1A4 Connector BIX Distribution Connector The BIX Distribution
Case Study. Molex PDS Delivers Voice and Data Streams around Shanghai Unicom Tower
, the headquarters office of China Unicom Shanghai Branch, is a 26-floor building located at 1031 Changning Road, Shanghai. The cabling system (PDS) to be installed here is to carry all the voice and data
Trial Exams C. Standards and Regulations. Examination No: GH-08-C- 1 hour and 5 minutes plus 10 minutes reading time
Trial Exams C Standards and Regulations Examination No: GH-08-C- This test is intended to gauge your knowledge of essential information contained within AS/CA S009:2013. To qualify for an allpication to
Planning for 10Gbps Ethernet over UTP Questions to Ask When Planning the Cabling Plant WHITE PAPER
Planning for 10Gbps Ethernet over UTP Questions to Ask When Planning the Cabling Plant WHITE PAPER Questions to Ask When Planning the Cabling Plant Planning a copper cabling plant to support 10Gbps transmission
SECTION 16750 VOICE AND DATA COMMUNICATION CABLING
SECTION 16750 VOICE AND DATA COMMUNICATION CABLING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Store drawing set and general provisions of the Contract, including General and Supplementary Conditions and
Excel Pre-terminated Copper and Fibre Optic Systems
Excel Pre-terminated Copper and Fibre Optic Systems Excel is a world-class premium performing end-to-end infrastructure solution - designed, manufactured, supported and delivered - without compromise.
Managing High-Density Fiber in the Data Center: Three Real-World Case Studies
Managing High-Density Fiber in the Data Center: Three Real-World Case Studies CHALLENGE In today s data center, fiber optic links have become more vital than ever for transmitting data to and from a large
21 st Century Campus Network Responsibility Matrix 5/26/10
Definitions: DoIT Standards This column details the minimal configuration, which DoIT has defined in order to provide a campus-wide standard level of service. Departments may request services, which exceeds
HP UPS R1500 Generation 3
HP UPS R1500 Generation 3 Installation Instructions Part Number 650952-001 NOTE: The rating label on the device provides the class (A or B) of the equipment. Class B devices have a Federal Communications
How To Set Up A Minipatch System For A Small Office Or Home Use
Issue : 4 Wood Communications Networking Products Catalogue Small Office & Home Solution Small Office / Home Solution Min LAN Comms Cabinets - Multimedia Panel - Soho Ethernet Switches - Multiroom Audio/Video,
Chapter 4 Connecting to the Internet through an ISP
Chapter 4 Connecting to the Internet through an ISP 1. According to Cisco what two things are essential to gaining access to the internet? a. ISPs are essential to gaining access to the Internet. b. No
USER GUIDE. 2 Channel POTS Mux DIN Fiber Link System. Introduction SYSTEM INSTALLATION INFORMATION. The leader in rugged fiber optic technology.
The leader in rugged fiber optic technology. USER GUIDE! Lifetime Warranty U-04 015A-01 Channel POTS Mux DIN Fiber Link System SYSTEM INSTALLATION INFORMATION Introduction The Channel POTS Mux DIN Fiber
ATTACHMENT F 050R6800016 - CABLE AND WIRING SERVICES FUNCTIONAL AREA I PRICE PROPOSAL FORM Amendment 6
050R6800016 CABLE AND WIRING SERVICES (Column A) (Column B) (Column C) (Column D) (Column E) (Column F) (Column G) (B+C+D+E)*F= G Item Description PER 100' RUN PER 150' RUN PER 200' RUN PER 300' RUN QUANTITY
BLACK BOX. Secure network ports from unauthorized access and accidental disconnects.
FC black process black LockPORT Security Patch Cables CAT5e, CAT6 and Fibre 5th black Secure network ports from unauthorized access and accidental disconnects. BLACK BOX» LockPORT cables stay locked in
SECTION 28 05 00 COMMON WORK RESULTS FOR ELECTRONIC SAFETY AND SECURITY
SECTION 28 05 00 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specifications Sections, apply
Session 2; Cabling Technology in the Data Centre Media Choices; Copper Twisted Pair
Presentation; Session 2; Cabling Technology in the Data Centre Media Choices; Copper Twisted Pair 5 th April 2010 Paul Mathews MInstSMM, CCNA, MIEEE Global Channel Manager Media Types Physical Layer Cabling;
Accelerating Light. Copper Cabling Solutions. Category 6A
Accelerating Light Copper Cabling Solutions Category 6A Category 6A Copper Cabling Solutions Fibernet designs and manufactures premium, high performance copper communication infrastructure and connectivity
Home Cabling Installation Guide
Home Cabling Installation Guide Wiselan Home Cabling Installation Guide * This document should be treated as a guide only. In no way does it replace any regulation. This Document is subject to copyright
E Series. E Series. Category 6 and 5e. Features
E Series Category 6 and 5e CommScope, world leader in copper and fiber connectivity, offers the E Series product line as the ideal solution to all your infrastructure needs for safe and reliable data transmission.
SECTION 16715 TELECOMMUNICATIONS ACCEPTANCE TESTING
PART 1 - GENERAL 1.1 SECTION INCLUDES A. Testing Publications and Standards B. Inspection and testing procedures for copper and fiber optic cable, RF CATV / MATV systems, and the antenna systems. C. Documentation
Security & Surveillance Cabling Systems
Security & Surveillance Cabling Systems Security and Surveillance Cabling Systems The video security industry is growing and ever-changing, offering a wealth of opportunity for today s security professionals.
01. HARTING RJ INDUSTRIAL RJ45 ETHERNET CONNECTORS
. HARTING RJ INDUSTRIAL ETHERNET CONNECTORS Ethernet is is coming up to standard industrial interface. Therefore, automation devices such as controllers, sensors and actuators feature possess on one or
Wired and Wireless Network Request for Proposal New Washington County High School Facility
Washington County Board Of Education P.O. Box 716 501 Industrial Drive Sandersville, GA 31082 (478) 552-3981 FAX (478) 552-3128 Description Wired and Wireless Network Request for Proposal New Washington
DATA CENTRES POWERED BY EXCEL
DATA CENTRES POWERED BY EXCEL MAXIMISE EFFICIENCY BOOST PERFORMANCE INCREASE R.O.I. WITHOUT COMPROMISE Excel is a world-class premium performance end-to-end infrastructure solution. Designed, manufactured,
R&Mfreenet Advanced Cat 6 A Unshielded Connection Module
R&Mfreenet Advanced R&Mfreenet Advanced Cat 6 A Connection Module The R&Mfreenet Cat 6 A unshielded connection modules, part of the Advanced cabling system, are ideal for voice, fast data transmissions
ANSI/TIA/EIA-606. Administration Standard for the Telecommunications Infrastructure of Commercial Buildings
ANSI/TIA/EIA-606 Administration Standard for the Telecommunications Infrastructure of Commercial Buildings Distributed by NDS INFORMATION- TELECOM SYSTEM --------------------------------------------- Head
Square D Clipsal DIN-Rail Four-Channel Auxiliary Input Unit
Square D Clipsal DIN-Rail Four-Channel Auxiliary Input Unit SLCLE5504AUX for Use with Wired C-Bus Networks Instruction Bulletin Retain for future use. Square D Clipsal DIN-Rail Four-Channel Auxiliary Input
AT&T. PARTNER Plus Door Phone. Installation and Operation Manual
AT&T PARTNER Plus Door Phone Installation and Operation Manual Copyright 1990 AT&T All Rights Reserved Printed in U.S.A. CIC# 999-500-317 OII722050-051 Issue 1 October 1990 PARTNER Plus Door Phone is a
Vertical Phone System Upgrades 2014. Scope of Work
Vertical Phone System Upgrades 2014 Scope of Work Project Overview Install new Vertical phone system and phones on site. Complete testing with API helpdesk. Remove old phone system, phones and box up for
4-Port 10/100Mbps with PoE + 1-Port 100FX Industrial Ethernet Switch Wide Temperature
4-Port 10/Mbps with + 1-Port FX Industrial Ethernet Switch Wide Temperature 15 F Fiber Optic Link Capability for Flexible Distance Extension The series equips one Base-FX port that provides more flexibility
Fibre Optic Indoor/Outdoor Cable
Volition TM Fibre Optic Indoor/Outdoor Cable Tough enough to take it. Easy to handle. The Volition Network Solutions Indoor/Outdoor Fibre Optic Cable from 3M includes horizontal and backbone cable with
Structured Cabling Statement of Work
Structured Cabling Statement of Work Multiple Locations June 15, 2010 Page 1 A. GENERAL a. San Joaquin County (referred to as Owner ) is requesting proposals for a new structured cabling infrastructure
Fire. The Fire Installers Mate. A guide to fire alarm systems design
Fire The Fire Installers Mate A guide to fire alarm systems design BS 5839 Part 1:2002 A guide to BS 5839 Part 1:2002 Disclaimer This booklet is not intended to be a comprehensive guide to all aspects
ANSI/TIA/EIA-570. 570-A A Revisited. Residential Telecommunications Cabling Standard (Draft 6/22/99) Larry L. Hamlin, RCDD
BICS I CABLING INSTALLATION PROGRAM ANSI/TIA/EIA-570 Residential Telecommunications Cabling Standard (Draft 6/22/99) Larry L. Hamlin, RCDD Copyright BICSI, October 1999 -A Revisited 1.1 Purpose standardize
IP DSLAM IDL-2402. Quick Installation Guide
IP DSLAM IDL-2402 Quick Installation Guide Table of Contents Package Contents... 3 Overview... 4 Setup the IDL series IP DSLAM... 5 Safety Instruction... 5 Hardware Installation... 6 WEB Configuration...
European Normative EN50173-1. system
European Normative EN50173-1 for generic/structured cabling system Pietro Nicoletti Studio Reti s.a.s piero[at]studioreti.it www.studioreti.it Cabl-New-2003-Engl - 1 P. Nicoletti: see note pag. 2 Copyright
INDOOR PHONE INSTALLATION (CONCEALED) TECHNICAL SPECIFICATION
TÜRK TELEKOMÜNİKASYON KASYON A.Ş. DIRECTORSHIP OF OPERATION AND MAINTENANCE Operation Directorate of Access Networks INDOOR PHONE INSTALLATION (CONCEALED) TECHNICAL SPECIFICATION ANKARA 2008 CONTENTS 1.
Cat7/Class F New Installation Concept New infrastructure. Handbook
Cat7/Class F New Installation Concept New infrastructure Handbook contents 1 Introduction 3 2 What is the Cat7/Class F installation concept 3 3 Distribution centre 3 3.1 Patch Modules 3 4 How to handle
Copper Pre-terminated Assemblies
Copper Pre-terminated Assemblies Copper Pre-Terminated Trunk Assemblies Overview Copper Pre-Terminated trunk assemblies are the perfect solution for Enterprise / Premise & Data Centre applications where
Standard Buccaneer - Ethernet
IP6 rated compliant PUR jacket on cable Shielded system shielded coupler Shroud on RJ45 Screw coupling Rewireable flex connector PCB mounted panel connector IDC termination panel connector Earth lead version
Data Center. Pre-terminated. Patch Panel System. Cabling Systems Simplified. Patch Panels. 10G + Gigabit. Patch Cords. Plug & Play Installation
Data Center Pre-terminated Patch Panel System Patch Panels Plug & Play Installation 10G + Gigabit Patch Cords Bundled + Labeled Cabling Systems Simplified Our Mission At Cablesys, our mission is to simplify
STATE OF OHIO DEPARTMENT OF TRANSPORTATION SUPPLEMENTAL SPECIFICATION 804 FIBER OPTIC CABLE FOR TRAFFIC SIGNAL INTERCONNECT JANUARY 19, 2007
804.01 Description 804.02 General 804.03 Materials 804.04 Fan-Out Kit 804.05 Drop Cable 804.06 Fiber Optic Patch Cord 804.07 Termination Panel 804.08 Fusion Splice 804.09 Fiber Optic Connector 804.10 Splice
Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points
Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points Features SELV Compliant No Detection Passive Injector Gigabit Compatible Full Protection
Generic Category 5e Cabling Specification
Telecommunications Cabling System Technical Specification Category 5e Tyco Electronics Corporation provides this information as a courtesy to its customers and potential customers. Customer should review