INERGEN Acoustics Testing Position Paper
|
|
|
- Jemima Nichols
- 10 years ago
- Views:
Transcription
1 INERGEN Acoustics Testing Position Paper
2
3 INERGEN Acoustics Testing Position Paper 1 The Issue In recent years, there has been considerable confusion in the marketplace about why some data center hard disk drives (HDDs) are damaged in the wake of clean-agent fire suppression system discharge. When the issue first came to light, the fire suppression community was mystified as it searched for a cause. Was it the sudden increase in room pressure during clean-agent discharge? The discharge gas itself? Or, was some other part of the fire suppression process to blame? And, perhaps most puzzling, what caused the phenomenon to surface at that time? Clean-agent fire suppression systems had been discharged successfully in data centers for years without incident. What changed? When we began to investigate a possible cause, the finger of suspicion quickly pointed to noise, as some of the initial incidents reportedly took place when fire suppression warning alarms sounded without agent discharge. Early industry testing also indicated noise was to blame and some in the fire protection community began to take action based on those preliminary results. At Tyco, we wanted to be certain. As a leader in clean-agent fire suppression, our duty was to fully understand the data degradation phenomenon. We sought guidance from IBM in monitoring the state and performance of HDDs during discharges and collaborated with Nelson Acoustics, an industry-leading acoustics consultant, to conduct what we believe is the most exhaustive study of the issue to date. Tyco s Position Under a test protocol developed jointly by Tyco, IBM and Nelson Acoustics, we conducted a series of trials in which a clean-agent fire suppression system was discharged in an environment containing HDDs typically found in data centers. The results confirm a single cause of data degradation: disk drive sensitivity to noise. As HDDs have evolved to store more and more data on each square inch of disk space, the tolerance for the data head to be off track has shrunk accordingly. It s likely that the reduced tolerance resulted in greater sensitivity to noise. As a result of the changing technology, we are taking the following steps to better protect our customers hardware: We are redesigning our INERGEN system nozzle to reduce its acoustic footprint. We will pursue agency approval of the redesigned components and will provide listed, backward-compatible replacement nozzles. We recommend the data center industry take additional noise-control measures to reduce risk. It s important to note that our tests involved the discharge of inert gas only; halocarbon testing may be conducted at a future date. This position paper details the findings of our study and the planned strategy to minimize disruptive noise generated in the data center environment.
4 REVISIONS NO. LINEAR DIMENSIONS IN INCHES, WHEN TOLERANCES ARE NOT GIVEN, THEY ARE: IN. 2 PLACE ± PLACE ± ANGLES ± 0.5 MATERIAL A.Q.L. DEFECT CLASSIFICATION C CRITICAL MAJOR OUT ITS EXPRESS PERMISSION. SCALE DATE DRAWN BY CHECKED BY APPROVED BY USED ON DWG. REQ'D R DESCRIPTION ANSUL INCORPORATED ONE STANTON STREET MARINETTE, WI LOCATION DRAWING NUMBER REV. INERGEN Acoustics Testing Position Paper 2 Our Study Components The tests were conducted over a series of days and included: Fifteen discharges of INERGEN agent into an enclosure containing 35 operating HDDs from four major manufacturers typically found in commercial data centers. Multiple piping and component configurations based on real-life data gathered from actual discharge incidents. (See Figures 1, 2 and 3.) The testing of various audible alarm devices (horn, bell, strobe and siren) to determine their impact independent of an agent discharge. Extensive measurement and recording instrumentation that documented the physical effects and performance of the HDDs in terms of impact on Input/Output (I/O) performance. o A.wav file (sound recording) was taken of actual inert gas discharges. This sound recording was used to benchmark hard drive performance. o The hard drive performance was monitored each time the.wav file was cycled and each time the db level was increased. INERGEN Component Locations (Set-Up A) REV. DESCRIPTION DATE BY APP'D RELEASE 312 (26') NOTES: 1. NOZZLES ARE 3/4" 2. REDUCER UNION IS 1" 3. MANIFOLD TO BE SCHEDULE PIPE TO NOZZLES IS 3/4" SCHEDULE NOZZLES TO BE ~7.5' ABOVE FLOOR 6. NOZZLE/DEFLECTOR TO BE WITHIN 6" OF WALL. Two 180 Nozzles, 60 second and 120 second discharges. NOZZLES 180 (15') HORNS/SIRENS INSIDE HAZARD AREA 164 (~13.5') DOOR PANEL & PULL STATION LOCATION OUTSIDE TEST/HAZARD AREA ROOM 139/061, SET UP A NOZZLES 60 SECOND & 120 SECOND DISCHARGES TESTS #12, 13, 16, 17 DO NOT SCALE PRINT THIS DRAWING IS THE PROPERTY OF ANSUL INCORPORATED AND SHALL NOT BE USED, REPRO- DUCED, OR TRANSFERRED WITH- ANSUL 01-Mar-10 ROOM 139/061 SET-UP A ROOMDA A Figure 1
5 REVISIONS REVISIONS NO. NO. LINEAR DIMENSIONS IN INCHES, WHEN TOLERANCES ARE NOT GIVEN, THEY ARE: IN. 2 PLACE ± PLACE ± ANGLES ± 0.5 MATERIAL LINEAR DIMENSIONS IN INCHES, WHEN TOLERANCES ARE NOT GIVEN, THEY ARE: IN. 2 PLACE ± PLACE ± ANGLES ± 0.5 MATERIAL A.Q.L. DEFECT CLASSIFICATION C CRITICAL MAJOR THIS DRAWING IS THE PROPERTY OF ANSUL INCORPORATED AND SHALL NOT BE USED, REPRO- DUCED, OR TRANSFERRED WITH- OUT ITS EXPRESS PERMISSION. SCALE A.Q.L. DEFECT CLASSIFICATION C CRITICAL MAJOR THIS DRAWING IS THE PROPERTY OF ANSUL INCORPORATED AND SHALL NOT BE USED, REPRO- DUCED, OR TRANSFERRED WITH- OUT ITS EXPRESS PERMISSION. SCALE DATE DRAWN BY CHECKED BY APPROVED BY USED ON DWG. REQ'D R DESCRIPTION ANSUL INCORPORATED ONE STANTON STREET MARINETTE, WI LOCATION DRAWING NUMBER REV. DATE DRAWN BY CHECKED BY APPROVED BY USED ON DWG. REQ'D R DESCRIPTION ANSUL INCORPORATED ONE STANTON STREET MARINETTE, WI LOCATION DRAWING NUMBER REV. INERGEN Acoustics Testing Position Paper 3 INERGEN Component Locations (Set-Up B) REV. DESCRIPTION DATE BY APP'D RELEASE 155 (~13') NOTES: 1. NOZZLE IS 1" 2. REDUCER IS 1" 3. MANIFOLD TO BE SCHEDULE PIPE TO NOZZLE IS 1". 5. NOZZLE TO BE ~7.5' ABOVE FLOOR. One 360 Nozzle, 60 second and 120 second discharges. 78 (~6.5' - 7') ROOM 139/061, SET UP B NOZZLES 60 SECOND & 120 SECOND DISCHARGES TESTS #18, 19, 20 DO NOT SCALE PRINT ANSUL 01-Mar-10 ROOM 139/061 SET-UP B SETUPB A INERGEN Component Locations (Set-Up C) Figure 2 REV. DESCRIPTION DATE BY APP'D RELEASE 77" (~6.5') 77" (~6.5') NOTES: 1. NOZZLES ARE 3/4" & 1/2" (TEST 21, TEST 22) 2. REDUCER UNION IS 1". 3. MANIFOLD TO BE SCHEDULE SEE PRINT FOR PIPE SIZE. 5. NOZZLES TO BE ~7.5' ABOVE FLOOR. Two 360 Nozzles, 60 second discharge. 78 (~7') 3/4" SCHEDULE 40 PIPE 3/4" SCHEDULE 40 PIPE 156 (~12.5') 1" SCHEDULE 40 PIPE ROOM 139/061, SET UP C NOZZLES 60 SECOND & 120 SECOND DISCHARGES TESTS # 21 DO NOT SCALE PRINT ANSUL 01-Mar-10 ROOM 139/061 SET-UP C SETUPC A Figure 3
6 INERGEN Acoustics Testing Position Paper 4 Our Study Results Two primary conclusions were drawn from the joint study. 1. The mere introduction of INERGEN agent itself into the enclosure housing the HDDs did not result in degradation of HDD performance. 2. High-decibel sound levels with high frequency content were found to disrupt HDD performance as shown below in Figure 4. Figure 4 Our study shows disruptive sound levels can be produced either by a system discharge or, to a lesser degree, by certain audible devices used to sound an alarm prior to discharge. Our testing criteria assumed a hard drive could drop to no lower than 20% of its I/O performance (80% degradation) and still be expected to return to its normal operating condition.
7 INERGEN Acoustics Testing Position Paper 5 System Discharge Noise In a clean-agent fire suppression discharge, the pressure used to expel gas makes a significant amount of noise. In our study, we tested both currently existing system nozzles (See Figure 5) and a prototype nozzle designed to minimize noise (See Figure 6). Figure 5 Figure 6
8 INERGEN Acoustics Testing Position Paper 6 System Alarm Noise Clean-agent system alarms typically include one or more horns, bells, strobes and sirens. According to standards and codes, these alarm devices must generate sound levels between 90 and 120 db. In our investigation, we tested the sound generated by each of the four common alarm devices on hard disk drive performance. The horn, bell and strobe - with levels between db - all had no negative effect on HDD performance. (See Figure 7.) The pneumatic pressure siren was shown to have a measurable impact on I/O per second. In one server, performance was reduced by 20% to 50%. Sirens average db. (See Figure 8.) The study also concluded that certain sizes and classifications of HDDs exhibit more or less sensitivity to these levels. Figure 7 Figure 8
9 INERGEN Acoustics Testing Position Paper 7 Our Strategy Moving Forward As a result of our comprehensive testing, we have developed a strategy to minimize disruptive noise generated in the data center environment. We will: Redesign our fire suppression system nozzle to reduce its acoustic footprint based on the results of our 2010 tests. Pursue agency approval of the redesigned components and provide listed, backward-compatible replacement nozzles. Recommend that data centers take additional noise-control measures to minimize risk. Redesign System Components We are redesigning our system components to have the lowest acoustic footprint possible without impacting agent distribution based on our 2010 testing of HDDs typically found in commercial data centers. Pursue Agency Approval We recognize the critical need to offer system components that meet agency approval, and we will pursue those certifications with the component redesign. We also recognize that achieving certification takes time. In the interim, we will consider bringing a redesigned solution to market to satisfy the emergency needs of our customers. Recommend Additional Noise-Control Measures While our redesigned nozzle will be critical to minimizing disruptive noise in the data center environment, we believe - and our tests have shown - that additional measures can be taken immediately to further mitigate risk. De-energizing equipment prior to clean-agent discharge remains the recommendation of various codes and standards, such as NFPA 75 Protection of Information Technology Equipment which states, The power to all electronic equipment shall be disconnected upon actuation of a gaseous agent total flooding system... Where possible, we recommend removing power from HDDs prior to any discharge event. This will allow the drive to park and greatly reduce the likelihood of data loss or damage. If removing power is not possible, we recommend installers and end users take the following steps to mitigate the impact of sound levels on HDD performance: Consult with the computer equipment provider about noise sensitivity. Increase the number and decrease the spacing of suppression system nozzles used in order to decrease sound levels. Avoid very short discharge times. While extended discharge times were not shown to have any substantive effect on sound levels, it is possible that very short discharge times - less than 60 seconds - could result in higher sound levels. Avoid the use of pneumatic sirens which were shown to have a measurable impact on HDD performance. (See Figure 8, page 6)
10 INERGEN Acoustics Testing Position Paper 8 Recommend Additional Noise-Control Measures (Continued) Check with your IT equipment manufacturer to see if rack doors with foam lined acoustic baffles are available for your equipment. The baffles reduce noise reaching the HDDs and were shown in our tests to significantly improve performance during high sound level testing. (See Figure 9.) Test Discharge Time Nozzle db Server A Server B Server C Server D No Doors 120s Prototype drives off line 1 drive destroyed 1 drive off line 3 drives off line With Doors 120s Prototype drive off line No errors No errors No errors Figure 9 Our Commitment We recognize that in data center environments, downtime and loss of data can be crippling. We are committed to ensuring that the very fire suppression equipment designed to protect data from fire does not contribute to its degradation. We will minimize the acoustic impact of our fire suppression system on data center hard drives based on the decibel and frequency thresholds identified in our 2010 study. We will achieve this goal by redesigning system components and by recommending that our customers take additional steps, as outlined in this document, to mitigate risk. Moving forward, we will continually monitor the impact of our system discharge sound levels in the data center environment. References For additional information on this topic, view/download the following documents: Fire Suppressant Impact on Hard Disks The Availability Digest, February, Potential Problems with Computer Hard Disks when Fire Extinguishing Systems Are Released Siemens Switzerland Ltd. Building Technologies, Hard Drive Performance Degradation Due to High Level Noise in Data Centers International Business Machines, September
11 One Stanton Street Marinette, WI (United States, Canada) (International) Copyright 2012 Tyco Fire Products LP. All rights reserved. Form No. F
Data Centre alwas protected always up and running.
Data Centre alwas protected always up and running. Stefano Valdrighi - Siemens Business continuity is the critical asset to protect 609,500 Average cost per downtime 7,908 Average cost per minute The total
EXHIBIT A SCOPE OF WORK
EXHIBIT A SCOPE OF WORK 1. (Contractor) shall provide fire alarm system maintenance/repair/testing services as described herein to the California Department of Veterans Affairs (hereinafter CDVA, CalVet,
Fire Protection Options for Data Centres
Fire Protection Options for Data Centres Mark L. Robin, PhD DuPont Chemicals & Fluoroproducts [email protected] Introduction Modern data centres are characterized by spaces filled with ever-increasing
Potential problems with computer hard disks when fire extinguishing systems are released
Extinguishing White Paper Potential problems with computer hard disks when fire extinguishing systems are released Disclaimer All statements, information and recommendations in this document are believed
EXETER TOWNSHIP DRY OR WET CHEMICAL FIRE SUPPRESSION SYSTEMS
DRY OR WET CHEMICAL FIRE SUPPRESSION SYSTEMS POLICY STATEMENT This policy applies to NEW Dry or Wet chemical fire suppression systems. The Authority Having Jurisdiction will not waive major criteria in
University of Houston Master Construction Specifications Insert Project Name
SECTION 21 22 13 - SAPPHIRE CLEAN-AGENT FIRE SUPPRESSION SYSTEM PART 1 GENERAL 1.1 RELATED DOCUMENTS A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and this Section
Vehicle Fire Protection. An Ownerʼs Manual for ANSUL Fire Suppression/Detection Systems
Vehicle Fire Protection An Ownerʼs Manual for ANSUL Fire Suppression/Detection Systems 002792 Off-road vehicles do have fires Statistics show that off-road vehicles burn with alarming frequency. These
SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS
SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS I. APPLICATION AND DEFINITIONS 1.01 Authorization for Standards 1.02 Application of Standards 1.03 Definitions
ANSUL. Restaurant Fire Suppression Systems ANSUL UL 300 ANSUL. LOW ph
Restaurant Fire Suppression Systems UL 300 LOW ph The Ansul R-102 System. State-of-the-art in restaurant fire protection. Meeting the fire protection challenge. In 1962, Ansul recognized that there was
ENGINEERING SPECIFICATION. Engineering Specification SAPPHIRE 42 Bar
Engineering Specification SAPPHIRE 42 Bar PART 1 GENERAL 1.1 DESCRIPTION OF WORK This specification outlines the requirements for a "Total Flood" SAPPHIRE Clean Agent Fire Suppression System. The work
Amerex CPS FM-200 Waterless Pre-engineered Fire Suppression System
Amerex CPS FM-200 Waterless Pre-engineered Fire Suppression System A Simple Solution An Affordable Approach An Industry Innovation I N T R O D U C T I O N A SIMPLE SOLUTION. AN AFFORDABLE How many days
FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011
FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011 COLORADO SPRINGS FIRE DEPARTMENT Division of the Fire Marshal If you have any questions or comments regarding the
PLAN SUBMITTAL REQUIREMENTS FOR SPRAY BOOTHS AND SPRAYING ROOMS EXTINGUISHING SYSTEMS
January 1997 PLAN SUBMITTAL REQUIREMENTS FOR SPRAY BOOTHS AND SPRAYING ROOMS EXTINGUISHING SYSTEMS 1.0 PERMIT 1.1 After receipt of a Building Permit from the City of San Jose Building Department, submit
2014 Limited Plan Submittal Checklist
City of Aurora Public Works Department WET AND DRY CHEMICAL HOOD SUPPRESSION SYSTEM 2014 Limited Plan Submittal Checklist Building Division 15151 E. Alameda Parkway, Ste 2400 Aurora, CO 80012 303-739-7420
Alarm and Detection/Suppression
Alarm and Detection/Suppression Fire Safety American Fire Technologies To provide special hazard services world wide to the industrial market through the integration of components and services Clean Agent
COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES
COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES These guidelines are to be used for ALL commercial cooking hoods, ventilation systems and related fire suppression
Maximum uptime and optimum fire safety for your data center
Maximum uptime and optimum fire safety for your data center Integrated and tailored fire safety solutions from one partner Answers for infrastructure. Complete solutions for a safe data center with a single
Maximum uptime and optimum fire safety for your data center
Maximum uptime and optimum fire safety for your data center Integrated and tailored fire safety solutions from one partner Answers for infrastructure. Complete solutions for a safe data center with a single
PLAN REVIEW GUIDE FOR FIRE ALARM
PLAN REVIEW GUIDE FOR FIRE ALARM PROJECT NAME: PERMIT # PROJECT ADDRESS: CONTACT PERSON: PHONE Fire alarm system installation information shall be provided on the appropriate architectural and electrical
NMSU FIRE DEPARTMENT Commercial Kitchen Fire Suppression Worksheet
This Commercial Kitchen Automatic Fire has been created to assure all documentation has been submitted to assist you in assuring proper plans and documentations has been submitted and reviewed by New Mexico
TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST
TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST In order to provide a comprehensive plan review in a timely manner, and to insure the design and installation of fire alarm systems
CBD-233. Fire Alarm and Detection Systems
Page 1 of 5 CBD-233. Fire Alarm and Detection Systems Originally published August 1984. R.H.L. McEwen Fire alarm systems are normally required by building codes. In the case of new buildings, this is usually
melbourne//australia data center specifications internet + intellectual property + intelligence tel: +61 2 9948 8888 fax: +61 2 9948 1111
internet + intellectual property + intelligence We thank you for the opportunity to work with you regarding your colocation needs in Melbourne,. We can colocate standard rack-mountable servers or other
IMO. 8 June 1998 *** I:\CIRC\MSC\848.WPD INTERNATIONAL MARITIME ORGANIZATION 4 ALBERT EMBANKMENT LONDON SE1 7SR
INTERNATIONAL MARITIME ORGANIZATION 4 ALBERT EMBANKMENT LONDON SE1 7SR E Telephone: 0171-735 7611 Fax: 0171-587 3210 Telex: 23588 IMOLDN G IMO Ref. T4/4.03 MSC/Circ.848 8 June 1998 REVISED GUIDELINES FOR
Required Certification Documentation. Contractor's installation certification for range hood fire suppression systems.
OFFICE OF UNIVERSIT BUILDING OFFICIAL PROJECT/CONSTRUCTION MAGER: Sample Manager Required Aboveground only Required Certification Documentation Contractor s material and test certifications for both above
FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS
FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011, Updated March 2012 COLORADO SPRINGS FIRE DEPARTMENT Division of the Fire Marshal If you have any questions or
Bold items are particular to the City of Euless
EULESS FIRE DEPARTMENT FIRE MARSHAL S OFFICE INFORMATION LINE: Revised 2/12 Fire Chief Wes Rhodes Fire Marshal Paul Smith EFD-FMO 3-2 2009 International Fire & Building Code as Amended NFPA Standards Adopted
NYC SUB-SYSTEMS INSTALLATION & SERVICE REQUIREMENTS OF THE FDNY
NYC SUB-SYSTEMS INSTALLATION & SERVICE REQUIREMENTS OF THE FDNY Presented by: James Goerl Metro Protection Systems, Inc. [email protected] Agenda Introduction & Learning Objectives History
FIRE-FIGHTING DESIGN BRIEF REPORT
P a g e 1 SECTION 04 (Doc.No.A/DBR 001) FIRE-FIGHTING DESIGN BRIEF REPORT P a g e 2 1.0 SCOPE 2.0 STANDARDS AND CODES 3.0 TYPES OF SYSTEM PROPOSED 4.0 FIRE HYDRANT SYSTEM 5.0 AUTOMATIC SPRINKLER SYSTEM
city of edmonds development information
#B17 city of edmonds development information Commercial Kitchen Hood & Hood Fire Suppression System Permit Submittal Requirements PERMIT REQUIRED: CODES: FEES: A Commercial Kitchen Hood Mechanical Permit
SCHOOL FIRE AND LIFE SAFETY INSPECTION CHECKLIST
SCHOOL FIRE AND LIFE SAFETY INSPECTION CHECKLIST School Name: School Address: Town: Phone: Inspected By (Please Print): Inspection Organization Name: Inspector Phone: Date of Inspection: Building Name:
City of Columbus Department of Building and Zoning Services
City of Columbus Department of Building and Zoning Services Introduction This manual is designed to provide you, the contractor, owner or design professional with a step-by-step guide to our process, beginning
For Data Center and Control Room Applications
For Data Center and Control Room Applications Nearly zero wetting No costly clean up or equipment replacement Sustainable design Quick system recharge, minimal downtime No need for assurance of tight room
For Data Center and Control Room Applications
For Data Center and Control Room Applications Nearly zero wetting No costly clean up or equipment replacement Sustainable design Quick system recharge, minimal downtime No need for assurance of tight room
SECTION 16720 - FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines
PART 1 -- GENERAL 1.1 WORK OF THIS SECTION SECTION 16720 - City of San Diego, CWP Guidelines A. The WORK of this Section includes providing manual and automatic fire alarm and smoke detection systems meeting
Technologies Gas extinguishing systems. MX 1230 Fire Extinguishing Systems Fighting Fire using 3M Novec 1230
Technologies Gas extinguishing systems MX 1230 Fire Extinguishing Systems Fighting Fire using 3M Novec 1230 ire protection Efficient and compact MX 1230 fire extinguishing systems fight fires using Novec
SECTION 16853 ZONED (DC LOOP) FIREALARM SYSTEM
SECTION 16853 ZONED (DC LOOP) FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1
CAL FIRE/San Luis Obispo County Fire Fire Prevention Bureau
CAL FIRE/San Luis Obispo County Fire Fire Prevention Bureau g GUIDELINE FOR SAFETY REQUIREMENTS FOR HAUNTED HOUSES PURPOSE This guide is intended to provide safety standards and regulations for the construction
Aerosol Fire Suppression. Your Choice for Special Hazard Fire Protection
Aerosol Fire Suppression Your Choice for Special Hazard Fire Protection Traditional Special Hazard Fire Protection Centers Around Two Technologies Water deluge and chemical agent fixed systems protect
FIRE PROTECTION SYSTEMS ACCEPTANCE INSPECTION AND TESTING PROCEDURE
ACCEPTANCE INSPECTION AND TESTING PROCEDURE Wet Pipe Sprinkler Systems...2 Dry Pipe Sprinkler Systems...2 Clean Agent Fire Extinguishing System...4 Total Flooding Systems...4 Fire Dampers...5 Smoke Dampers...5
Inert Gas Extinguishing System Two Minute Discharge Study. Gene Hill, P.E. Brad Stilwell
Inert Gas Extinguishing System Two Minute Discharge Study Gene Hill, P.E. Brad Stilwell Page 2 ABSTRACT Fire testing per UL 2127 and FM 5600 was done with an inert gas extinguishing system utilizing IG-100,
FIRE CODE INTERPRETATION
FIRE CODE INTERPRETATION March 2008 ISSUE: Existing Fire Alarm Systems FCI-08-06 Page 1 of 9 The purpose of this bulletin is to identify conditions where a building fire alarm system may be subject to
Module 5. Fire and Emergency Alarm System Part I- Basics
Module 5 Fire and Emergency Alarm System Part I- Basics 1 This module will describe: 1. Components and the arrangements of components in fire and emergency alarm systems. 2. How these systems work. 3.
City of Bettendorf Fire Alarm System Requirements
City of Bettendorf Fire Alarm System Requirements Section 907 of the 2009 Edition of the International Fire Code (IFC) and Section 10-7-3 of the Municipal Code provide fire alarm requirements. IFC Section
NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems
NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems 1.0 Purpose A. The following guideline provides the minimum standards and requirements for fire alarm systems. 2.0
Automatic fire-extinguishing systems for commercial cooking
Automatic fire-extinguishing systems for commercial cooking Leading Items First Ignited in Eating and Drinking Establishment Structure Fires, 2000-2004 Annual Averages Cooking materials, incl. food and
VDI Mixer/Amplifier/Multiplier Chains (MixAMCs)
VDI Mixer/Amplifier/Multiplier Chains (MixAMCs) VDI s MixAMCs provide high performance broadband downconversion and frequency extension of microwave spectrum analyzers into the THz range. Models are currently
CO 2. fire extinguishing systems
fire extinguishing systems Extinguishing technique is a colourless, odourless and electrical non-conductive gas. In systems the is mixed with a special identifiable odour. The extinguishing effect of is
FIRE DETECTION/INERGEN SUPPRESSION SYSTEM ENGINEERING SPECIFICATIONS
PART 1 - GENERAL FIRE DETECTION/INERGEN SUPPRESSION SYSTEM ENGINEERING SPECIFICATIONS 1.01 DESCRIPTION OF WORK: A. Design and installation of an engineered fire detection and INERGEN total flooding, gaseous
WASTE Application Form - Dublin Waste to Energy SECTION J ACCIDENT PREVENTION & EMERGENCY RESPONSE
SECTION J ACCIDENT PREVENTION & EMERGENCY RESPONSE Describe the existing or proposed measures, including emergency procedures, to minimise the impact on the environment of an accidental emission or spillage.
37 ALARM SYSTEMS 37. Chapter 37 ALARM SYSTEMS. 37.2. Permit required for automatic protection device.
37 ALARM SYSTEMS 37 37.1. Definitions. Chapter 37 ALARM SYSTEMS 37.2. Permit required for automatic protection device. 37.3. Procedure for issuance of permit. 37.4. Time extension for permit applications
Fire Alarm System Plans Submittal Guidelines For New and Existing Systems
Fire Alarm System Plans Submittal Guidelines For New and Existing Systems SCOPE The Temecula Fire Prevention Bureau (TFPB) has established the following requirements for the submittal of all fire alarms,
ENGINEERING SPECIFICATIONS
ENGINEERING SPECIFICATIONS FM-200 CLEAN-AGENT FIRE SUPPRESSION SYSTEM with PYRO-CHEM DETECTION/RELEASE SYSTEM March 2001 SECTION 1 - GENERAL I. SCOPE This specification outlines the requirements for a
DATA CENTER FIRE PROTECTION
DATA CENTER FIRE PROTECTION DATA CENTER FIRE PROTECTION The following is a summary of a few key fire protection, detection, and suppression technologies used by Minimax Fire Solutions in data centers and
Data Center Due Diligence List
Data Center Due Diligence List Name and address of site facility Date constructed Building owner/date purchased by current owner Name of previous owner Adjacent Property Descriptions North South East West
POSITION STATEMENT THE ENGINEER AND THE ENGINEERING TECHNICIAN DESIGNING FIRE PROTECTION SYSTEMS. July 28, 2008
SOCIETY OF FIRE PROTECTION ENGINEERS (SFPE) NATIONAL SOCIETY OF PROFESSIONAL ENGINEERS (NSPE) NATIONAL INSTITUTE FOR CERTIFICATION IN ENGINEERING TECHNOLOGIES (NICET) POSITION STATEMENT THE ENGINEER AND
USER INSTRUCTIONS CONTENTS
CONTENTS Full Set [1]...2 Part Set [2]...2 Night Set [3]...3 Unsetting...3 Unsetting after or during an alarm...3 Testing the system [5]...3 Isolating zones [6]...4 Reprogramming codes [8]...4 Chime facility
The Mission Critical Fire Protection Experts
The Mission Critical Fire Protection Experts Protection Systems Protection Systems HFC-227ea / FM200 / FE-227 FE-25 / ECARO-25 Novec 1230 Inergen / Argonite Halon Drop-in Systems High and Low Pressure
FIRE ALARM SYSTEM SUBMITTAL CHECKLIST AND APPLICATION
PERMITS AND INSPECTIONS FIRE ALARM SYSTEM SUBMITTAL CHECKLIST AND APPLICATION 911 Assigned PROJECT LOCATION Subdivision: Lot: Blk: Sec: PROJECT New Construction Addition/Remodel Demolition Other: Number
Transformer Deluge Systems
Transformer Deluge Systems How Do Transformer Fires Ignite? Common causes of transformer failure: Weather-related events such as lightning Short circuits in electrical equipment The most common cause is
DuPont FM-200 COMPARISON TESTING IN A SIMULATED DATA PROCESSING/TELECOMMUNICATIONS FACILITY
DuPont FM-200 COMPARISON TESTING IN A SIMULATED DATA PROCESSING/TELECOMMUNICATIONS FACILITY DuPont FM-200 and Automatic Sprinkler Systems Mark L. Robin and Eric W. Forssell, DuPont Fluoroproducts Data
All You Ever Wanted to Know About Fire Extinguishers...
All You Ever Wanted to Know About Fire Extinguishers... There are basically four different types or classes of fire extinguishers, each of which extinguishes specific types of fire. Newer fire extinguishers
Advanced Fire Protection in Data Centres
Advanced Fire Protection in Data Centres Jeff Klein, Honeywell Life Safety, 26 June 2012, Copyright 2012 System Sensor Europe. All rights reserved. The Challenge for Mission Critical Data Centres Fuel
CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services
CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services 575 E. Flamingo Road, Las Vegas, NV 89119 (702) 455-7316 FAX (702) 455-7347 105.8a-6.1 TITLE: FIRE ALARM SYSTEM REQUIREMENTS SCOPE: This guideline
Safer.Smarter.Tyco. Watermist fire protection Technology you can trust
Safer.Smarter.Tyco. Watermist fire protection Technology you can trust / 2 / / 3 / Trust in Tyco Tyco s AquaMist Systems Tyco Fire Protection Products helps to keep people, property and the environment
Element D Services Heating, Ventilating, and Air Conditioning
PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer
Efficient servicing. Easy maintenance. High level of uptime.
Efficient servicing. Easy maintenance. High level of uptime. At LEVEL we believe that efficient servicing, easy maintenance and a high level of uptime must be given top priority when developing products
FOR CERTIFICATION AS PRESCRIBED BY THE STATE FIRE PREVENTION COMMISSION ON NOVEMBER 11, 2009 IN ACCORDANCE WITH THE STATE FIRE PREVENTION REGULATIONS
EXAMINATION REQUIREMENTS FOR FIRE SUPPRESSION SYSTEM CERTIFICATION AS PRESCRIBED BY THE STATE FIRE PREVENTION COMMISSION ON NOVEMBER 11, 2009 IN ACCORDANCE WITH THE STATE FIRE PREVENTION REGULATIONS REGULATION
MISSION CRITICAL FACILITIES DESIGN UPS BATTERY ROOM ENVIRONMENT CRITICAL DESIGN CONSIDERATIONS
MISSION CRITICAL FACILITIES DESIGN UPS BATTERY ROOM ENVIRONMENT CRITICAL DESIGN CONSIDERATIONS Allen Wood Vice President Data Center Division Engineering Design Group INTRODUCTION It can be very effectively
CONSTRUCTION FIRE SAFETY PLANNING GUIDELINES
CONSTRUCTION FIRE SAFETY PLANNING GUIDELINES Review the following information pertaining to Construction Fire Safety Planning: B.C. Building Code Sections 8.1 up to and including Subsection 8.2.3 B.C.
Static Spark Ignites Flammable Liquid during Portable Tank Filling Operation
Static Spark Ignites Flammable Liquid during Portable Tank Filling Operation No. 2008-02-I-IA (September 2008) Key Lessons for Safe Handling and Storage of Flammables Ensure that equipment, such as fill
Data Center Rack Systems Key to Business-Critical Continuity. A White Paper from the Experts in Business-Critical Continuity TM
Data Center Rack Systems Key to Business-Critical Continuity A White Paper from the Experts in Business-Critical Continuity TM Executive Summary At one time, data center rack enclosures and related equipment
12 Things Facility Managers Need to Know About Critical Power System Installation
12 Things Facility Managers Need to Know About Critical Power System Installation Are you considering managing your next power system installation in-house? As a facilities manager or other facility professional,
GenStore Archive Cabinet
GenStore Archive Cabinet Setup and Maintenance Manual Version A April 2014 Two GenStore Archives shown mounted on optional table stand. 2 Contents Getting Started... 4 Using this Manual...4 Safety Precautions...4
Standard the the Raising
Raising the Standard Introduction to BS 5839-1:2013 An Overview of the BS 5839 1:2013 for professionals who are responsible for the provision of fire detection and alarm systems for buildings Agenda Introduction
Y7230A CO 2 Alarm System
Y7230A CO 2 Alarm System FOR CO 2 GAS DETECTION PRODUCT DATA FEATURES APPLICATION Y7230A CO 2 alarm system is used to detect gas leaking from CO 2 beverage dispensing systems and posts an alarm to occupants
Remote PC Guide Series - Volume 2a
Document Version: 2013-03-04 This guide provides hardware model-specific guidance in server configuration, with BIOS and RAID configuration instructions for the Dell R710. This guide is part of a multi-volume
Data center solutions from Siemens. For the factories of the 21 st century. siemens.com/datacenters
Data center solutions from Siemens For the factories of the 21 st century siemens.com/datacenters We face the challenges for the factories of the 21 st century Based on our vast experience, we offer a
BNA FEDERAL CREDIT UNION DISASTER RECOVERY PLAN
BNA FEDERAL CREDIT UNION DISASTER RECOVERY PLAN INTRODUCTION The need for a contingency plan for business interruptions is vital to the operations of the BNA Federal Credit Union. Without such a plan,
TOP 10 NOISE CONTROL TECHNIQUES
TOP 10 NOISE CONTROL TECHNIQUES The following are 10 simple noise control techniques that have wide application across the whole of industry. In many cases, they will produce substantial noise reductions
ISA CERTIFIED AUTOMATION PROFESSIONAL (CAP ) CLASSIFICATION SYSTEM
ISA CERTIFIED AUTOMATION PROFESSIONAL (CAP ) CLASSIFICATION SYSTEM Domain I: Feasibility Study - identify, scope and justify the automation project Task 1: Define the preliminary scope through currently
presents Cooking With Fire Fixed Fire Suppression & Exhaust Systems for Cooking Environments Monday, 17 June, 13
presents Cooking With Fire Fixed Fire Suppression & Exhaust Systems for Cooking Environments Who is the AFSA? Safe and Secure Alberta Fire Safety Association Fire industry members working together to improve
Data Center Presentation
Data Center Presentation The NetSource Datacenter. Agenda General Layout of Data Center Policies and Procedures Designed to Latest Standards High Performance High Reliability High Security Design Details
(2) Various fire sections enclosed by various classes of fire divisions; (3) Arrangement of fire detectors and manual fire alarm stations;
(1979) (Rev.1 1990) (Rev.2 1996) (Rev.3 Jan 2012) Safety features.1 Fire protection and extinction.1.1 General Fire protection arrangements and fire extinguishing systems are to be in accordance with the
DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS
Features: INSTALLATION Install in accordance with NFPA 70. DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS Up to 1.95 Amps Load Capacity Class 2 Rated Outputs Overload, Over Voltage, and Short
DESIGNING DATA CENTERS & SERVER ROOMS
DESIGNING DATA CENTERS & SERVER ROOMS Compton s Designing Data Center Services are an enterprise-wide, consultative approach to help you manage mission critical environments. The services encompass the
FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM RECORD OF COMPLETION
FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance and approval. It shall be permitted to modify this
INTER-NOISE 2006 3-6 DECEMBER 2006 HONOLULU, HAWAII, USA
INTER-NOISE 2006 3-6 DECEMBER 2006 HONOLULU, HAWAII, USA An effective new approach to isolate plumbing stub-outs in residential construction Jeffrey P. Kwolkoski, P.E., INCE Bd. Cert. a D. L. Adams Associates,
IBM Storwize Rapid Application Storage solutions
IBM Storwize Rapid Application Storage solutions Efficient, integrated, pretested and powerful solutions to accelerate deployment and return on investment. Highlights Improve disk utilization by up to
PERFORMANCE AT HAND. RED LINE Hand Portable Fire Extinguishers
PERFORMANCE AT HAND RED LINE Hand Portable Fire Extinguishers MODEL 5 The Model 5 has a slim design for use on vehicles and machinery where space is limited. Typical applications include small trucks,
Fire Alarm and Detection Systems And Central Station Monitoring Plan Submittal Guidelines
Fire Alarm and Detection Systems And Central Station Monitoring Plan Submittal Guidelines Red Oak Fire Rescue Office of the Fire Marshal 547 N. Methodist Red Oak, TX 75154 Phone: 469-218-7713 Fax: 468-218-7719