Selection & Application Guidelines Performer scroll compressors Single 20 to 110 kw Hz
|
|
|
- Tabitha Dickerson
- 9 years ago
- Views:
Transcription
1 Selection & Application Guidelines Performer scroll compressors Single 20 to 110 kw Hz R22, R407C, R134a, R404A/R507A
2 CONTENTS PERFORMER SCROLL COMPRESSION PRINCIPLE... 4 COMPRESSOR MODEL DESIGNATION... 5 Nomenclature... 5 Connection details... 5 TECHNICAL SPECIFICATIONS Hz data Hz data... 7 OPERATING ENVELOPES... 8 Application envelopes at dew temperatures... 8 Application envelopes at mean temperatures PIPING CONNECTIONS Suction and discharge connections Sight glass Schrader Oil drain ELECTRICAL CONNECTIONS AND WIRING Motor voltage Electrical connections Suggested wiring diagrams logic Danfoss MCI soft-start controller SYSTEM DESIGN RECOMMENDATIONS Refrigerant charge limit and compressor protection Crankcase heater Liquid line solenoid valve (LLSV)...17 Pump-down cycle Suction accumulator Liquid receiver Protection against flooded starts and liquid floodback Discharge gas temperature protection (DGT) Refrigerant charge limits and compressor protection Motor protection Internal motor protection External motor protection Phase sequence and reverse rotation protection Cycle rate limit Voltage unbalance High and low pressure protection High pressure Low pressure Internal pressure relief valve...23 Essential piping design considerations SPECIFIC APPLICATION RECOMMENDATIONS Low ambient compressor operations Low ambient operation and minimum pressure differential Low ambient start-up Head pressure control under low ambient conditions Crankcase heaters... 24
3 CONTENTS Low load operations Brazed plate heat exchangers Reversible heat pump systems Crankcase heaters Discharge temperature thermostat Discharge line & reversing valve Suction line accumulator SOUND AND VIBRATION MANAGEMENT Sound generation in a refrigeration / air conditioning system Compressor sound radiation Mechanical vibrations Gas pulsation INSTALLATION Compressor handling Mounting Removing connections shipping plugs System cleanliness Tubing Filters driers Brazing and soldering Copper to copper connections Dissimilar metals connection Compressor connection System pressure test Leak detection Vacuum pump-down and moisture removal Refrigerant charging Commissioning Oil level checking and top-up Oil level check Oil top-up ACCESSORIES Connectors and valves Lubricants Crankcase heaters Discharge temperature protection Compressor acoustic hood ORDERING INFORMATION AND PACKAGING Ordering information Packaging... 38
4 PERFORMER SCROLL COMPRESSION PRINCIPLE In a Danfoss Performer scroll compressor, the compression is performed by two scroll elements located in the upper part of the compressor above the motor (see adjacent figure). Suction gas enters the compressor at the suction connection. The gas then flows around the motor and enters at the bottom side through the openings as shown. Oil droplets separate from the suction gas and fall into the oil sump. All of the suction gas passes through the electrical motor, thus ensuring complete motor cooling in all applications. After exiting the electrical motor, the gas enters the scroll elements where compression takes place. A check valve is located directly above the fixed scroll discharge port; this feature prevents the compressor from running backwards once the power has been switched off. Ultimately, the discharge gas leaves the compressor at the discharge connection. The figure below illustrates the entire compression process. The center of the orbiting scroll traces a circular path around the center of the fixed scroll. This movement creates symmetrical compression pockets between the two scroll elements. Low pressure suction gas is trapped within each crescent-shaped pocket as it gets formed; continuous motion of the orbiting scroll serves to seal the pocket, which decreases in volume as the pocket moves towards the center of the scroll set increasing the gas pressure. Maximum compression is achieved once a pocket reaches the center where the discharge port is located; this stage occurs after three complete orbits. Compression is a continuous process: when one quantity of gas is being compressed during the second orbit, another quantity is entering the scrolls and yet another is being discharged all at the same time. First orbit: SUCTION Second orbit: COMPRESSION Third orbit: DISCHARGE 4
5 COMPRESSOR MODEL DESIGNATION Nomenclature Performer scroll compressors are available both as single compressors and as tandem units. The example below presents the single compressor codification (technical reference shown on compressor nameplate). For tandem assemblies, please refer to the Performer Parallel Application Guidelines documentation. Family, lubricant & refrigerant Nominal capacity Voltage Version Evolution Index S Z S 4 R S Y A 9 A A C A Family, lubricant & refrigerant SM: Scroll, mineral oil, for R22 SY: Scroll, POE lubricant, for R22 SZ: Scroll, POE lubricant, for R407C - R134a Nominal capacity in thousand Btu/h at 60 Hz, R22, ARI conditions UL index Motor protection type Internal overload protector Internal thermostat V C R Version V: brazed C: brazed R: rotolock Description Applies to S S Voltage Motor voltage code: 3: /3/60 4: /3/50-460/3/60 6: 230/3/50 7: 500/3/50-575/3/60 9: 380/3/60 Electronic protection module AA AB MA MB *For trio assemblies, please contact Danfoss A: brazed A: 24V A: brazed B: 115/230V M: rotolock A: 24V M: rotolock B: 115/230V S 240* - 300* - 380* Connection details MODEL SM/SZ SM/SZ Version V R C SY/SZ SY/SZ 380 Suction and discharge connection brazed rotolock brazed rotolock brazed brazed Oil sight glass threaded threaded threaded threaded threaded threaded Oil equalization connection 3/8 flare 3/8 flare 3/8 flare 1/2 flare 1/2 flare 1/2 flare Oil drain connection - 1/4 NPT 1/4 NPT 1/4 NPT 1/4 NPT 1/4 NPT MA MB AA AB AA AB Low pressure gauge port (schrader) 1/4 flare 1/4 flare 1/4 flare 1/4 flare 1/4 flare 1/4 flare 5
6 TECHNICAL SPECIFICATIONS 50-Hz data R22 SINGLE Model Nominal Cap. 60 Hz TR Nominal cooling capacity W Btu/h Power input kw A max A COP W/W Efficiency E.E.R. Btu/h /W Sound power db(a) Swept volume cm 3 /rev Displacement m 3 /h Oil charge dm 3 SM SM SM SM SM SM SM SM SM SM SM SM SY SY SY Net weight kg R407C SINGLE SZ SZ SZ SZ SZ SZ SZ SZ SZ SZ SZ SZ SZ SZ SZ TR = Ton of Refrigeration COP = Coefficient Of Performance EER = Energy Efficiency Ratio Rating conditions SM/SY compressors SZ compressors Refrigerant R22 R407C Frequency 50 Hz 50 Hz Standard rating conditions ARI standard conditions - Evaporating temperature 7.2 C 7.2 C (dew point) Condensing temperature 54.4 C 54.4 C (dew point) Sub-cooling 8.3 K 8.3 K Superheat 11.1 K 11.1 K Subject to modification without prior notification For full data details and capacity tables refer to Online Datasheet Generator : 6
7 TECHNICAL SPECIFICATIONS 60-Hz data R22 SINGLE Model Nominal Cap. 60 Hz TR Nominal cooling capacity W Btu/h Power input kw A max A COP W/W Efficiency E.E.R. Btu/h /W Sound power db(a) Swept volume cm 3 /rev Displacement m 3 /h Oil charge dm 3 SM SM SM SM SM SM SM SM SM SM SM SM SY SY SY Net weight kg R407C SINGLE SZ SZ SZ SZ SZ SZ SZ SZ SZ SZ SZ SZ SZ SZ SZ TR = Ton of Refrigeration COP = Coefficient Of Performance EER = Energy Efficiency Ratio Rating conditions SM/SY compressors SZ compressors Refrigerant R22 R407C Frequency 60 Hz 60 Hz Standard rating conditions ARI standard conditions - Evaporating temperature 7.2 C 7.2 C (dew point) Condensing temperature 54.4 C 54.4 C (dew point) Sub-cooling 8.3 K 8.3 K Superheat 11.1 K 11.1 K Subject to modification without prior notification For full data details and capacity tables refer to Online Datasheet Generator : 7
8 OPERATING ENVELOPES Application envelopes at dew temperatures The figures below show the operating envelopes for SM / SY compressors with refrigerant R22 and for SZ compressors with refrigerants R407C, R134a, R404A and R507A. The discharge temperature depends on the combination of evaporating temperature, condensing temperature and suction gas superheat. Because of this dependence, discharge temperature limits are indicated by a double line. The solid line represents the limit should the superheat be 11.1 K or less. The dashed line, on the other hand, provides the limit when the superheat is 30 K. For superheat values between 11.1 K and 30 K, these two lines may be interpolated. The operating limits serve to define the envelope within which reliable operations of the compressor are guaranteed: Maximum discharge gas temperature: +135 C Maximum ambient temperature: +63 C (for SM / SZ 084 to 185), + 52 C (for SY / SZ 240 to 380) A suction superheat below 5 K is not recommended due to the risk of liquid floodback Maximum superheat of 30 K Minimum and maximum evaporating and condensing temperatures as per the operating envelopes. SM 084 to SM 185 SY 240 to SY 380 R Condensing temp. limits Cond. temp. ( C) S.H. = 11.1 K S.H. = 30 K SUPERHEAT Evap. temp. ( C) SZ 084 to SZ 185 R134a Condensing temp. limits Cond. temp. ( C) S.H. = 11.1 K S.H. = 30 K SUPERHEAT Evap. temp. ( C) 8
9 OPERATING ENVELOPES SZ R134a Condensing temp. limits Cond. temp. ( C) S.H. = 11.1 K S.H. = 30 K SUPERHEAT Evap. temp. ( C) SZ 084 to SZ 185 R404A / R507A Condensing temp. limits Cond. temp. ( C) S.H. = 11.1 K S.H. = 30 K SUPERHEAT Evap. temp. ( C) SZ 084 to SZ 185 R407C at DEW temperature (refer to the explanation p.10) Cond. temp. ( C) Condensing temp. limits S.H. = 11.1 K Dew temperature conditions S.H. = 30 K SUPERHEAT Evap. temp. ( C) SZ 240 to SZ 380 R407C at DEW temperature (refer to the explanation p.10) Cond. temp. ( C) Condensing temp. limits S.H. = 11.1 K Dew temperature conditions S.H. = 30 K SUPERHEAT Evap. temp. ( C) 9
10 OPERATING ENVELOPES Application envelopes at mean temperatures Dew temperature and mean temperature for R407C Refrigerant R407C is a zeotropic mixture, which causes a temperature glide in both the evaporator and condenser. When discussing evaporating and condensing temperatures therefore, it is important to indicate whether these are DEW point values or MEAN point values. In the figure below, the dashed lines reflect constant temperature and do not correspond with the constant pressure lines. pressure (log) Mean For a given cycle, the MEAN point temperatures are typically about 2 to 3 C lower than DEW point temperatures. In these Selection and Application Guidelines, Danfoss Commercial Compressors displays temperatures as DEW point values. The performance tables for R407C (see p. 6-7) are also based on DEW point values. Dew The following operating diagrams show the difference between mean and dew temperature application envelopes. Mean Dew enthalpy Dew temperature Condensing temp. limits Dew temperature conditions 60 Cond. temp. ( C) S.H. = 11.1 K S.H. = 30 K SUPERHEAT Example for SZ 084 to Evap. temp. ( C) Mean temperature Condensing temp. limits Mean temperature conditions 60 Cond. temp. ( C) S.H. = 11.1 K S.H. = 30 K SUPERHEAT Example for SZ 084 to Evap. temp. ( C) 10
11 PIPING CONNECTIONS Brazed version Rotolock version 1 ➁ Suction and discharge connections SM / SZ 084 SM / SZ 090 SM / SZ 100 SM / SZ 110 SM / SZ 115 SM / SZ 120 SM / SZ 125 SM / SZ 148 SM / SZ 161 SM / SZ 160 SM / SZ 175 SM / SZ 185 SY / SZ 240 SY / SZ 300 SY / SZ 380 Brazed Rotolock 1 Adaptor ➁ Suction 1 1/8 - - Discharge 3/4 - - Suction 1 1/8 - - Discharge 3/4 - - Suction 1 1/8 - - Discharge 3/4 - - Suction 1 3/8 - - Discharge 7/8 - - Suction 1 3/8 1 3/4 1 1/8 Discharge 7/8 1 1/4 3/4 Suction 1 3/8 - - Discharge 7/8 - - Suction 1 3/8 1 3/4 1 1/8 Discharge 7/8 1 1/4 3/4 Suction 1 3/8 - - Discharge 7/8 - - Suction 1 3/8 - - Discharge 7/8 - - Suction 1 5/8 2 1/4 1 3/8 Discharge 1 1/8 1 3/4 7/8 Suction 1 5/8 2 1/4 1 3/8 Discharge 1 1/8 1 3/4 7/8 Suction 1 5/8 2 1/4 1 3/8 Discharge 1 1/8 1 3/4 7/8 Suction 1 5/8 2 1/4 1 5/8 Discharge 1 1/8 1 3/4 1 1/8 Suction 1 5/8 2 1/4 1 5/8 Discharge 1 1/8 1 3/4 1 1/8 Suction 2 1/8 - - Discharge 1 3/8 - - Sight glass Schrader Oil drain All Performer scroll compressors come equipped with a sight glass which may be used to determine the amount and condition of the oil contained within the sump. The oil fill connection and gauge port is a 1/4" male flare connector incorporating a Schrader valve. The oil drain connection allows oil to be removed from the sump for changing, testing, etc. The fitting contains an extension tube into the oil sump to more effectively remove the oil. The connection is composed of a female 1/4" NPT fitting. Note : On SY / SZ , it is not possible to drain oil from the suction connection. Oil fill connection and gauge port Oil drain connection 11
12 ELECTRICAL CONNECTIONS AND WIRING Motor voltage Performer scroll compressors are available in five different motor voltages. Motor voltage code 3 and 9 for 60 Hz, motor code 6 for 50 Hz and motor code 4 and 7 for both 50 and 60 Hz. Nominal voltage 50 Hz Voltage range 50 Hz Nominal voltage 60 Hz Voltage range 60Hz Motor voltage code 3 Motor voltage code 4 with thermostat protector and internal overload (S S 185) Motor voltage code 4 with PTC and electronic module (S S 380) Motor voltage code 6 Motor voltage code 7 Motor voltage code V Hz 400V Hz 230V Hz 500V Hz V V V V V Hz 460V Hz 460V Hz - 575V Hz Hz V V V V V Electrical connections Electrical power is connected to the compressor terminals by Ø 4.8 mm (3/16 ) screws. The maximum tightening torque is 3 Nm. Use a 1/4 ring terminal on the power leads. Terminal box wiring for SM / SZ * compressors * Except for motor voltage code 3 The terminal box is provided with a Ø 29 mm hole for the power supply and a Ø 29 mm knockout. The protection rating of the terminal box is IP54 when correctly sized IP54- rated cable glands are used. IP ratings according to IEC 529 Power supply Terminal box ø 29 mm knockout Terminal box wiring for SM / SZ (motor code 3) The terminal box is provided with 2 double knockouts for the power Cover holding screw (x2) Torque: 2.2 N.m. Discharge gas thermostat kit (optional) supply and 3 knockouts for the safety control circuit. Discharge gas pipe Belt type cranckase heater (optional) Terminal box Power supply 1/4 spade connector Safety control circuit motor thermostat 12
13 ELECTRICAL CONNECTIONS AND WIRING The 2 power supply, double knockouts accommodate the following diameters: Ø 44 mm / Ø 1 3/4 hole (for a 1 1/4 conduit) and Ø 34mm / Ø 1 3/8 hole (for a 1 conduit), Ø 32.1 mm / Ø 1.26 hole and Ø 25.4 mm / Ø 1 hole. The 3 other knockouts are as follows: Ø 20.5 mm / Ø 0.81 Ø 22 mm / Ø 7/8 (for a 1/2 conduit) Ø 16.5 mm / Ø 0.65 The protection rating of the terminal box is IP54 when correctly sized IP54 rated cable glands are used. Connect the internal safety thermostat with 1/4 female spade connectors. Terminal box wiring for SY / SZ The terminal box is provided with 4 double knockouts for the power supply and 4 knockouts for the safety control circuit. The 4 power supply double knockouts accommodate the following diameters: Ø 22 mm / Ø 7/8 hole and Ø 16.5 mm / Ø 0.65 knockout Ø 22 mm / Ø 7/8 hole and Ø 16.5 mm / 0.65 knockout Ø 43.7 mm / Ø 1 23/32 hole and Ø 34.5 mm / 1 23/64 knockout Ø 40.5 mm / Ø 1.59 hole and Ø 32.2 mm / 1.27 knockout The 4 others knockouts are as follows: Ø 20.5 mm / Ø 0.81 Ø 20.5 mm / Ø 0.81 Ø 50 mm / Ø 1 31/32 Ø 25.2 mm / Ø 0.99 The protection rating of the terminal box is IP54 when correctly sized IP54- rated cable glands are used. IP ratings according to IEC 529. Cover holding screws (x4) Torque: 2.2 N.m. Discharge gas thermostat kit (optional) Black Blue Brown Discharge gas pipe M1, M2 Control circuit Power supply Belt type cranckase heater Power supply Electronic protection module wiring The motor protection module comes preinstalled within the terminal box and is accompanied with both phase sequence protection and pre-wired thermistor connections. The module must be connected to a power supply of the appropriate voltage. The module terminals are 6.3 mm size Faston type. L1 L2 L3 Black Blue Brown Phase sequence input Internal control contact L N S1 S2 M1 M2 Module power 24 or 115/230 vac Safety circuit Thermistor connection 13
14 ELECTRICAL CONNECTIONS AND WIRING Suggested wiring diagrams logic Compressor models SM / SZ CONTROL CIRCUIT L1 L3 L2 CONTROL CIRCUIT L1 L3 L2 Q1 Q1 F1 F1 F1 F1 KM KA KA KA KS KM F2 KA KA KA KS KM F2 KS A1 A3 180 s A2 HP T1 T3 T2 A1 A3 180 s A2 BP T1 T3 T2 BP TH HP KS DGT M KS TH DGT M KM KA LLSV KS KM KA KS Wiring diagram with pump-down cycle Wiring diagram without pump-down cycle A Suggested wiring diagrams logic Compressor models SM / SZ CONTROL CIRCUIT L1 L3 L2 CONTROL CIRCUIT L1 L3 L2 Q1 Q1 F1 F1 KM KA KA KA KS KM F1 F1 KA KA KA KS KM F2 F2 A1 T1 T2 T1 T2 KS BP A3 180s A2 TH HP T3 M A1 A3 180s A2 BP HP T3 M KS DGT 1 2 KS TH DGT 1 2 KM KA LLSV KS KM KA KS Wiring diagram with pump-down cycle Wiring diagram without pump-down cycle Short cycle timer fonction ~ KA A1 A2 A1 A3 TH 160 s TH T T A2 KA ~ 14
15 ELECTRICAL CONNECTIONS AND WIRING Suggested wiring diagrams logic Compressor models SY / SZ A1 A3 A1 A3 A2 A2 Wiring diagram with pump-down cycle Wiring diagram without pump-down cycle Legends Control device...th Optional short cycle timer (3 min) s Control relay... KA Liquid Line Solenoid valve... LLSV Compressor contactor... KM Safety lock out relay... KS Pump-down control & L.P. switch... BP H.P. safety switch...hp Fused disconnect...q1 Fuses...F1 External overload protection...f2 Compressor motor... M Motor safety thermostat... thm Discharge gas thermostat...dgt Motor Protection Module... MPM Thermistor chain...s Danfoss MCI soft-start controller The inrush current for the Performer scroll compressors with motor code 4 (400V / 3 / 50Hz or 460V / 3 / 60Hz) can be reduced using the Danfoss digitally-controlled MCI compressor soft starter. MCI soft starters are designed to reduce the starting and stopping current of 3-phase AC motors; MCI soft starters can reduce the in-rush current by up to 40%, thereby eliminating the detrimental effects of high starting torque surges and costly demand charges from the resultant current spike. Upon starting, the controller gradually increases the voltage supplied to the motor until full-line voltage has been reached. All settings, such as ramp-up time and initial torque, are preset at the factory and do not require modification. * By-pass contactor (K1) required. See application example p.16 Compressor model SM / SZ 084 SM / SZ 090 SM / SZ 100 SM / SZ 110 SM / SZ Soft start reference ambient max. 40 C MCI 15C Soft start reference ambient max. 55 C MCI 15C MCI 25C SM / SZ 120 SM / SZ SM / SZ MCI 25C MCI 25C* SY / SZ MCI 50C* SY / SZ 380 Contact Danfoss 15
16 ELECTRICAL CONNECTIONS AND WIRING MCI with bypass contactor By means of the built-in auxiliary contact (23-24) the bypass function is easily achieved, see wiring diagram below. No heat is generated from the MCI. As the contactor always switches in no-load condition it can be selected on the basis of the thermal current (AC-1). (13-14 contact not applicable with MCI 25C) Input controlled soft start When the control voltage is applied to A1 - A2, the MCI soft starter will start the motor, according to the settings of the ramp-up time and initial torque adjustments. When the control voltage is switched OFF, the motor will switch off instantaneously. 16
17 SYSTEM DESIGN RECOMMENDATIONS Refrigerant charge limit and compressor protection Performer scroll compressors incorporate internal safety devices such as motor temperature protection, reverse rotation protection and a discharge gas check valve. Additional safety devices or system components may however be required to ensure adequate protection of the compressor. Depending on the system configuration and application, one or several of the following methods should be considered. Crankcase heater When the compressor is idle, the oil temperature in the sump of the compressor must be maintained at no lower than 10 K above the saturation temperature of the refrigerant on the low-pressure side. This requirement ensures that the liquid refrigerant is not accumulating in the sump. A crankcase heater is only effective if capable of sustaining this level of temperature difference. Tests must be conducted to ensure that the appropriate oil temperature is maintained under all ambient conditions (temperature and wind). However, below 5 C ambient temperature and a wind speed of above 5 m/sec, we recommend that the heaters be thermally insulated in order to limit the surrounding energy losses. Since the total system charge may be undefined, a crankcase heater is recommended on all stand-alone compressors and split systems. In addition, any system containing a refrigerant charge in excess of the maximum recommended system charge for compressors requires a crankcase heater. A crankcase heater is also required on all reversible cycle applications. Notes: Belt-type crankcase heater accessories are available from Danfoss (see page 34). The heater must be energized for a minimum of 12 hours before initial start-up (compressor service valves opened) and must remain energized whenever the compressor is off. Provide separate electrical supply for the heaters so that they remain energized even when the machine is out of service (eg. seasonal shutdown). Liquid line solenoid valve (LLSV) An LLSV may be used to isolate the liquid charge on the condenser side, thereby preventing against charge transfer or excessive migration to the compressor during off-cycles. The quantity of refrigerant on the lowpressure side of the system can be further reduced by using a pump-down cycle in association with the LLSV. Pump-down cycle A pump-down cycle represents one of the most effective ways to protect against the off-cycle migration of liquid refrigerant. Once the controls has been satisfied, a solenoid valve closes on the condenser outlet. The compressor then pumps the majority of the system charge into the condenser and receiver before the system stops on the low pressure pump-down switch. This step reduces the amount of charge on the low side in order to prevent offcycle migration. Recommended settings of the low-pressure pump-down switch can be found in the table on p. 22. For suggested wiring diagrams, please see p Suction accumulator A suction accumulator offers protection against refrigerant floodback at start-up, during operations or after defrosting (heat pump). Sustained and repeated liquid slugging and floodback can seriously impair the oil s ability to lubricate. The suction line accumulator also protects against off-cycle migration by providing additional internal free volume to the low side of the system. The accumulator should not be sized for less than 50% of the total system charge. Tests must be conducted to determine the actual refrigerant holding capacity needed for the application. 17
18 SYSTEM DESIGN RECOMMENDATIONS Liquid receiver A liquid receiver is highly recommended on split systems and remote condenser systems with a total refrigerant charge in excess of the recommended maximum for the compressor. Because of the long refrigerant lines these systems have a relatively high system charge which is hard to define with accuracy. Further these types of systems quite often tend to be overcharged in the field. By installing a liquid receiver, a pump-down cycle can then be introduced in order to safely store the refrigerant charge during the off-cycles, which greatly reduces the chance of refrigerant migration back to the compressor. On unitary or close-coupled systems, where the system refrigerant charge is expected to be both correct and definable the entire system charge may be stored in the condenser during pumpdown if all components have been properly sized. Protection against flooded starts and liquid floodback Flooded starts occur when a compressor starts up with a large quantity of liquid refrigerant in the compressor. Liquid finds its way into a compressor by means of off-cycle migration. Liquid floodback occurs when liquid refrigerant returns to a compressor while it is running. Excessive liquid refrigerant in the compressor will cause oil dilution, liquid washout of oil from the bearings, or loss of oil from the sump. The crankcase heater will not be effective if the system design allows for uncontrolled floodback to the compressor during running or starting. Performer scroll compressors can tolerate occasional flooded starts as long as the system charge does not exceed that given in the table in the following section. Performer scrolls can also handle intermittent floodback, yet system design must be such that repeated and excessive floodback is not possible. Off-cycle refrigerant migration occurs when the compressor is located at the coldest part of the installation, when the system uses a bleed-type expansion device, or if liquid can migrate from the evaporator into the compressor sump by gravity. If the system charge exceeds the limit shown in the table, a crankcase heater must be used. During operations, liquid floodback may be detected by measuring either the oil sump temperature, which should be at least 10 K above the saturated suction temperature, or the discharge gas temperature, which should be at least 30 K above the saturated discharge temperature. If at any time during operations, the oil sump temperature drops to within 10 K or less above the saturated suction temperature, or should the discharge gas temperature be less than 30 K above the saturated discharge temperature, the lubricant will become excessively diluted and tests would have to be performed in order to select an appropriate compressor protection method. Repetitive liquid floodback testing must be carried out under TXV threshold operating conditions: a high pressure ratio and minimum load, along with the measurement of both suction superheat and discharge gas temperature. Discharge gas temperature protection (DGT) DGT protection is required if the high and low pressure switch settings do not protect the compressor against operations beyond its specific application envelope. Please refer to the examples below, which illustrates where DGT protection is required (Example 1) and where it is not (Example 2). Example 1 (R22, SH = 11 K) LP switch setting: LP1 = 1.8 bar (g) (-17 C) HP switch setting: HP1 = 25 bar (g) (62 C) Risk of operation beyond the application envelope. DGT protection required. Example 2 (R22, SH = 11 K) LP switch setting: LP2 = 2.9 bar (g) (-7 C) HP switch setting: HP2 = 21 bar (g) (55 C) No risk of operation beyond the application envelope. No DGT protection required. 18
19 SYSTEM DESIGN RECOMMENDATIONS A discharge temperature protection device must be installed on all heat pumps. In reversible air-to-air and airto-water heat pumps the discharge temperature must be monitored during development test by the equipment manufacturer. The DGT should be set to open at a discharge gas temperature of 135 C. Notes: The compressor must not be allowed to cycle on the discharge gas thermostat. Continuous operations beyond the compressor s operating range will cause serious damage to the compressor! A DGT accessory is available from Danfoss Commercial Compressors: refer to page Cond. temp. ( C) DGT - limit Example 1 Example 2 HP1 HP LP1 LP2 R Evap. temp. ( C) Refrigerant charge limits and compressor protection The refrigerant charge limits listed in the table below will help evaluate the required compressor protection in relation with the system charge and the application. Notes: For reversible heat pump systems and other specific applications, please refer to section "Specific Application Recommendations". Compressor models S 084 S 090 S 100 S 110 S 120 S 115 S 125 S 148 S 160 S 161 S 175 S 185 Refrigerant charge limit (kg) S 240 S 300 S 380 BELOW charge limit ABOVE charge limit Cooling only systems, Packaged units No test or additional safeties required REQ REQ Refrigerant migration & floodback test Crankcase heater Cooling only systems with remote condensor and split system units REC Refrigerant migration & floodback test REC Crankcase heater, because full system charge is not definable (risk of overcharging) REQ REQ REC Refrigerant migration & floodback test Crankcase heater Liquid receiver Reversible heat pump system REQ REQ REQ Specific tests for repetitive floodback Crankcase heater Discharge gas thermostat REC Recommended REQ Required No test or additional safeties required The above chart represents basic guidelines for reliable compressor operations and safety. Please contact Danfoss technical support for any deviations from these guidelines. 19
20 SYSTEM DESIGN RECOMMENDATIONS Motor protection Internal motor protection Compressor models SM / SZ have been provided with an internal overload motor protection to prevent against excessive current and temperature caused by overloading, low refrigerant flow phase loss or incorrect motor rotation. The cutout current is the MCC value listed in the data sheets. While not compulsory, an additional external overload protection is still advisable for either alarm or manual reset. The protector is located in the star point of the motor and, should it be activated, will cut out all three phases. It will be reset automatically. Compressor models SM / SZ have been provided with a bimetallic single-pole, single-throw thermostat located in the motor windings. In the event of motor overheating caused by low refrigerant flow or improper motor rotation, the thermostat will open. Because the thermostat is an automatic reset device, it must be wired within a lockout safety circuit with a manual reset to restart the unit. For overcurrent and phase loss protection, an external overload protector must be used for the SM / SZ 115, 125, 160, 175 and 185 models. The table below shows the protection method for the various compressor models. Compressor models SY / SZ are delivered with a preinstalled motor protection module inside the terminal box. This device provides for efficient and reliable protection against overheating and overloading as well as phase loss/reversal.the motor protector comprises a control module and PTC sensors embedded in the motor winding. The close contact between thermistors and windings ensures a very low level of thermal inertia.the motor temperature is being constantly measured by a (PTC) thermistor loop connected on S1-S2. If any thermistor exceeds its response temperature, its resistance increases above the trip level (4,500 Ω) and the output relay then trips (i.e. contacts M1-M2 are open). After cooling to below the response temperature (resistance < 2,750 Ω), a 5 minute time delay is activated. After this delay has elapsed, the relay is once again pulled in (i.e. contacts M1-M2 closed). The time delay may be cancelled by means of resetting the mains (L-N disconnect) for approx. 5 sec. Compressor model SM / SZ SM / SZ Overheating protection Overcurrent protection Locked rotor protection Single-phasing protection Internal Internal Internal Internal Internal Compulsory external overload protector SY / SZ Internal Internal Internal Internal External motor protection All safety devices must comply with the requirements of the pertinent certification authorities in the country where the compressor will be used. The external overload protector can be either a thermal overload relay or a circuit breaker. A thermal overload relay should be set to trip at not more than 140% of the compressor-rated load current. A circuit breaker, on the other hand, should be set at not more than 125% of the compressor rated load current. The rated load current is the maximum current expected during operations of the considered application; it can be found either in the corresponding data sheets or in the Danfoss Commercial Compressors selection program 20
21 SYSTEM DESIGN RECOMMENDATIONS for all compressors. The tripping current must never exceed the MMT value found in the data sheets; the MMT value appears as "A.Max" on the compressor nameplate. Further requirements for the external overload protector are: Overcurrent protection: The protector must trip within 2 minutes at 110% of the Maximum Must-Trip current. Locked rotor protection: The protector must trip within 10 seconds upon starting at a locked rotor current. Single-phasing protection: The protector must trip when one of the three phases fails. Phase sequence and reverse rotation protection Use a phase meter to establish the phase orders and connect line phases L1, L2 and L3 to terminals T1, T2 and T3, respectively. The compressor will only operate properly in a single direction, and the motor is wound so that if the connections are correct, the rotation will also be correct. Compressor models SM / SZ 084 to 185 incorporate an internal reverse vent valve which will react in the presence of reverse rotation and will allows refrigerant to circulate through a by-pass from the suction to the discharge. Although reverse rotation is not destructive, even over long periods of time up to several days it should be corrected as soon as possible. Reverse rotation will be obvious to the user as soon as power is turned on; the compressor will not build up any pressure, the sound level will be abnormally high and power consumption will be minimal. If reverse rotation symptoms occur, shut the compressor down and connect the phases to their proper terminals. If reverse rotation is not halted, the compressor will cycle off on the internal motor protection. Compressor models SY / SZ 240 to 380 are delivered with an electronic module which provides protection against phase reversal and loss at start-up. Apply the recommended wiring diagrams from page 15. The circuit should be thoroughly checked in order to determine the cause of the phase problem before re-energizing the control circuit. The phase sequencing and phase loss monitoring functions are active during a 5 sec. window 1 sec. after compressor start-up (power on L1-L2-L3). Should one of these parameters be incorrect, the relay would lock out (contact M1- M2 open). The lockout may be cancelled by resetting the power mains (disconnect L-N) for approximately 5 sec. Compressor Start Phase monitoring Phase sequence module logic Cycle rate limit The system must be designed in a way that guarantees a minimum compressor running time of 2 minutes so as to provide for sufficient motor cooling after start-up along with proper oil return. Note that the oil return may vary since it depends upon system design. There must be no more than 12 starts per hour (6 when a resistor soft-start accessory is introduced); a number higher than 12 reduces the service life of the motor-compressor unit. If necessary, place an anti-short-cycle timer in the control circuit, connected as shown in the wiring diagram (p14-15). A three-minute (180-sec) time out is recommended. 21
22 SYSTEM DESIGN RECOMMENDATIONS Voltage unbalance The operating voltage limits are shown in the table on page 12.The voltage applied to the motor terminals must lie within these table limits during both start-up and normal operations. The maximum allowable voltage unbalance is 2%. Voltage unbalance causes high amperage over one or several phases, which in turn leads to overheating and possible motor damage. Voltage unbalance is given by the formula: % voltage Vavg - V1-2 + Vavg - V1-3 + Vavg - V2-3 unbalance = 2 x Vavg x 100 Vavg = Mean voltage of phases 1, 2, 3. V1-2 = Voltage between phases 1 & 2. V1-3 = Voltage between phases 1 & 3. V2-3 = Voltage between phases 2 & 3. High and low pressure protection High pressure A high-pressure (HP) safety switch is required to shut down the compressor should the discharge pressure exceed the values shown in the table below. The high-pressure switch can be set to lower values depending on the application and ambient conditions. The HP switch must either be placed in a lockout circuit or consist of a manual reset device to prevent cycling around the high-pressure limit. If a discharge valve is used, the HP switch must be connected to the service valve gauge port, which must not be isolated. Note: Because power consumption of scroll compressors is almost directly proportional to discharge pressure, the high-pressure control can be used to indirectly limit the maximum current draw. A high-pressure control used in this manner however can never replace an external overload protector. Low pressure A low pressure (LP) safety switch must be used. Deep vacuum operations of a scroll compressor can cause internal electrical arcing and scroll instability. Performer scroll compressors exhibit high volumetric efficiency and may draw very low vacuum levels, which could induce such a problem. The minimum low-pressure safety switch (loss of charge safety switch) setting is given in the following table. For systems without pump-down, the LP safety switch must either be a manual lockout device or an automatic switch wired into an electrical lockout circuit. The LP switch tolerance must not allow for vacuum operations of the compressor. LP switch settings for pumpdown cycles with automatic reset are also listed in the table below: R22 R407C R134a R404A/R507A Working pressure range high side bar (g) Working pressure range low side bar (g) Maximum high pressure safety switch setting bar (g) Minimum low pressure safety switch setting * bar (g) Minimum low pressure pump-down switch setting ** bar (g) *LP safety switch shall never be bypassed. ** Recommended pump-down switch settings: 1.5 bar (R22, R407C, R404A) or 1 bar (R134a) below nominal evaporating pressure. 22
23 SYSTEM DESIGN RECOMMENDATIONS Internal pressure relief valve The SY / SZ 240 to SY / SZ 380 incorporate an internal relief valve set to open between the internal high and low pressure sides of the compressor when the pressure differential between the discharge and suction pressures surpasses 31 to 38 bar. This safety feature prevents the compressor from developing dangerously high pressures should the high pressure cutout, for whatever reason, fail to shut down the compressor. HP LP Relief valve Essential piping design considerations Proper piping practices should be employed to ensure adequate oil return, even under minimum load conditions with special consideration given to the size and slope of the tubing coming from the evaporator. Tubing returns from the evaporator should be designed so as not to trap oil and to prevent oil and refrigerant migration back to the compressor during off-cycles. If the evaporator lies above the compressor, as is often the case in split or remote condenser systems, the addition of a pump-down cycle is strongly recommended. If a pump-down cycle were to be omitted, the suction line must have a loop at the evaporator outlet to prevent refrigerant from draining into the compressor during off-cycles. If the evaporator were situated below the compressor, the suction riser must be trapped so as to prevent liquid refrigerant from collecting at the thermal bulb location (see fig. 1). When the condenser is mounted at a higher position than the compressor, a suitably sized «U»-shaped trap close to the compressor is necessary to prevent oil leaving the compressor from draining back to the discharge side of the compressor during off cycle. The upper loop also helps avoid condensed liquid refrigerant from draining back to the compressor when stopped (see fig. 2). Piping should be designed with adequate three-dimensional flexibility. It should not be in contact with the surrounding structure, unless a proper tubing mount has been installed. This protection proves necessary to avoid excess vibration, which can ultimately result in connection or tube failure due to fatigue or wear from abrasion. Aside from tubing and connection damage, excess vibration may be transmitted to the surrounding structure and generate an unacceptable noise level within that structure as well (for more information on noise and vibration, see the section on: "Sound and vibration management" p.27). HP max. 4 m 0.5% >4 m/s LP HP U-trap Condenser max. 4 m 8 to 12 m/s 0.5% >4m/s Evaporator LP fig 1 fig 2 23
24 SPECIFIC APPLICATION RECOMMENDATIONS Low ambient compressor operations Low ambient operations and minimum pressure differential The Performer scroll compressor requires a minimum pressure differential of 3 to 4 bar between the suction and discharge pressures to force the orbiting scroll-down against the oil film on the thrust bearing. Anything less than this differential and the orbiting scroll can lift up, causing a metal-to-metal contact. It is therefore necessary to maintain sufficient discharge pressure in order to ensure this pressure differential. Care should be taken during low ambient operations when heat removal from air-cooled condensers is greatest and head pressure control may be required for low ambient temperature applications. Operation under low pressure differential may be observed by a significant increase in the sound power level generated by the compressor. Low ambient start-up Under cold ambient conditions (<0 C), upon start-up the pressure in the condenser and, if present, the receiver may be so low that a sufficient pressure differential across the expansion device cannot be developed to properly feed the evaporator. As a result, the compressor may go into a deep vacuum, which can lead to compressor failure due to internal arcing and instability in the scroll members. Under no circumstances should the compressor be allowed to operate under vacuum. The low-pressure control must be set in accordance with the table on page 22 in order to prevent this from happening. Low pressure differentials can also cause the expansion device to «hunt» erratically, which might cause surging conditions within the evaporator, with liquid spillover into the compressor. This effect is most pronounced during low load conditions, which frequently occur during low ambient conditions. Head pressure control under low ambient conditions Several possible solutions are available to prevent the compressor from drawing down to a vacuum upon startup under low ambient conditions. In air-cooled machines, cycling the fans with a head pressure controller will ensure that the fans remain off until the condensing pressure has reached a satisfactory level. In water-cooled units, the same can be performed using a water regulator valve that is also operated by head pressure, thereby ensuring that the water valve does not open until the condensing pressure reaches a satisfactory level. Note: The minimum condensing pressure must be set at the minimum saturated condensing temperature shown in the application envelopes. Under very low ambient conditions, in which testing has revealed that the above procedures might not ensure satisfactory condensing and suction pressures, the use of a liquid receiver with condenser and receiver pressure regulators would be possible. For further information, please contact Danfoss Technical Support. Crankcase heaters Crankcase heaters are strongly recommended on all refrigerant systems where the compressor is exposed to cold ambient temperatures, especially split and remote condenser installations. The crankcase heater will minimize refrigerant migration caused by the large temperature gradient between the compressor and the remainder of the system. 24
25 SPECIFIC APPLICATION RECOMMENDATIONS Low load operations Brazed plate heat exchangers Reversible heat pump systems Brazed plate heat exchange needs very little internal volume to satisfy the set of heat transfer requirements. Consequently, the heat exchanger offers very little internal volume for the compressor to draw vapor from on the suction side. The compressor can then quickly enter into a vacuum condition; it is therefore important that the expansion device be sized correctly and that a sufficient pressure differential across the expansion device be available to ensure adequate refrigerant feed into the evaporator. This aspect is of special concern when operating the unit under low ambient and load conditions. For further information on these conditions, please refer to the previous sections. Due to the small volume of the brazed Transients are likely to occur in reversible heat pump systems, i.e. a changeover cycle from cooling to heating, defrost or low-load short cycles. These transient modes of operation may lead to liquid refrigerant carryover (or floodback) or excessively wet refrigerant return conditions. As such, reversible cycle applications require specific precautions for ensuring a long compressor life and satisfactory operating characteristics. Regardless of the refrigerant charge in the system, It is recommended that the unit be tested and monitored at minimum load and, if possible, during low ambient conditions as well. During conditions of low load on the system, the following considerations should be taken into account to ensure proper system operating characteristics. The superheat setting of the expansion device should be sufficient to ensure proper superheat levels during low loading periods. A minimum of 5 K stable superheat is required. In addition, the refrigerant charge should be sufficient to ensure proper subcooling within the condenser so as to avoid the risk of flashing in the liquid line before the expansion device. The expansion device should be sized to ensure proper control of the refrigerant flow into the evaporator. An oversized valve may result in erratic control. This consideration is especially important in manifolded units where low load conditions may require the frequent cycling of compressors. This can lead to liquid refrigerant entering the compressor if the expansion valve does not provide stable refrigerant superheat control under varying loads. Condenser fans should be cycled in such a way that the minimum pressure differential is maintained between the suction and discharge pressures. Variable-speed fans can also be used to control the amount of heat to be removed from the condenser. The compressors should be run for a minimum period in order to ensure that the oil has sufficient time to properly return to the compressor sumps and that the motor has sufficient time to cool under conditions of lowest refrigerant mass flows. plate heat exchanger, no pump-down cycle is normally required. The suction line running from the heat exchanger to the compressor must be trapped to avoid refrigerant migration to the compressor. When using a brazed plate heat exchanger as the condensing coil, a sufficient free volume for the discharge gas to accumulate is required in order to avoid excess pressure buildup. At least 1 meter of discharge line is necessary to generate this volume. To help reduce the gas volume immediately after start-up even further, the supply of cooling water to the heat exchanger may be opened before the compressor starts up so as to remove superheat and condense the incoming discharge gas more quickly. specific tests for repetitive floodback are required to confirm whether or not a suction accumulator needs to be installed. A crankcase heater and discharge gas thermostat are required for reversible heat pump applications. The following considerations cover the most important issues in the realm of common applications. Each application design however should be thoroughly tested to ensure acceptable operating characteristics. 25
26 SPECIFIC APPLICATION RECOMMENDATIONS Crankcase heaters Crankcase heaters are mandatory on reversible cycle applications given the high probability of liquid migration back to the compressor sump during off-cycles due to the outdoor location of most units and operations during low ambient conditions. Discharge temperature thermostat Heat pumps frequently utilize high condensing temperatures in order to achieve a sufficient temperature rise in the medium being heated. At the same time, they often require low evaporator pressures to obtain sufficient temperature differentials between the evaporator and the outside temperature. This situation may result in high discharge temperature; as such, it is mandatory that a discharge gas thermostat be installed on the discharge line to protect the compressor from excessive temperatures. Operating the compressor at too high discharge temperatures can result in mechanical damage to the compressor as well as thermal degradation of the compressor lubricating oil and a lack of sufficient lubrication. The discharge gas thermostat should be set to shut down the compressor in the event discharge gas rises above 135 C. Discharge line and reversing valve The Performer scroll compressor is a high volumetric machine and, as such, can rapidly build up pressure in the discharge line if gas in the line becomes obstructed even for a very short period of time which situation may occur with slow-acting, reversing valves in heat pumps. Discharge pressures exceeding the operating envelope may result in nuissance high pressure switch cutouts and place excess strain on both the bearings and motor. To prevent such occurrences, it is important that a 1 meter minimum discharge line length be allowed between the compressor discharge port and the reversing valve or any other restriction. This gives sufficient free volume for the discharge gas to collect and to reduce the pressure peak during the time it takes for the valve to change position. At the same time, it is important that the selection and sizing of the reversing or 4 way valve ensure that the valve switches quickly enough to prevent against too high discharge pressure and nuisance high pressure cutouts. Check with the valve manufacturer for optimal sizing and recommended mounting positions. Suction line accumulator The use of a suction line accumulator is strongly recommended in reversible-cycle applications as a result of the possibility of a substantial quantity of liquid refrigerant remaining in the evaporator, which acts as a condenser during the heating cycle. This liquid refrigerant can then return to the compressor, either flooding the sump with refrigerant or as a dynamic liquid slug when the cycle switches back to a defrost cycle or to normal cooling operations. Sustained and repeated liquid slugging and floodback can seriously impair the oil s ability to lubricate the compressor bearings.this situation can be observed in wet climates where it is necessary to frequently defrost the outdoor coil in an air source heat pump. In such cases a suction accumulator becomes mandatory. 26
27 SOUND AND VIBRATION MANAGEMENT Sound generation in a refrigeration / air conditioning system Typical sound and vibration in Refrigeration and Air-Conditioning systems encountered by design and service engineers may be broken down into the following three source categories. Sound radiation: This generally takes an airborne path. Mechanical vibrations: These generally extend along the parts of the unit and structure. Gas pulsation: This tends to travel through the cooling medium, i.e. the refrigerant. The following sections will focus on the causes and methods of mitigation for each of the above sources. Compressor sound radiation For sound radiating from the compressor, the emission path is airborne and the sound waves are traveling directly from the machine in all directions. The Performer scroll compressor is designed to be quiet and the frequency of the sound generated is pushed into the higher ranges, which not only are easier to reduce but also do not generate the penetrating power of lower-frequency sound. Use of sound-insulation materials on the inside of unit panels is an effective means of substantially reducing the sound being transmitted to the outside. Ensure that no components capable of transmitting sound/vibration within the unit come into direct contact with any non-insulated parts on the walls of the unit. Because of the Performer s unique design of a full-suction gas-cooled motor, compressor body insulation across its entire operating range is possible. Accoustic hoods are available from Danfoss Commercial Compressors as accessories. These hoods are quick and easy to install and do not increase the overall size of the compressors to a great extend. Refer to page 35 for sound attenuation and code numbers. Mechanical vibrations Vibration isolation constitutes the primary method for controlling structural vibration. Performer scroll compressors are designed to produce minimal vibration during operations. The use of rubber isolaters on the compressor base plate or on the frame of a manifolded unit is very effective in reducing vibration being transmitted from the compressor(s) to the unit. Rubber grommets are supplied with all Performer compressors. Once the supplied rubber grommets have been properly mounted, vibration transmitted from the compressor base plate to the unit are held to a strict minimum. In addition, it is extremely important that the frame supporting the mounted compressor be of sufficient mass and stiffness to help dampen any residual vibration potentially transmitted to the frame. For further information on mounting requirements, please refer to the section on mounting assembly. The tubing should be designed so as to both reduce the transmission of vibrations to other structures and withstand vibration without incurring any damage. Tubing should also be designed for three-dimensional flexibility. For more information on piping design, please see the section entitled "Essential piping design considerations" p. 23. Gas pulsation The Performer scroll compressor has been designed and tested to ensure that gas pulsation has been optimized for the most commonly encountered air conditioning pressure ratio. On heat pump installations and other installations where the pressure ratio lies beyond the typical range, testing should be conducted under all expected conditions and operating configurations to ensure that minimum gas pulsation is present. If an unacceptable level is identified, a discharge muffler with the appropriate resonant volume and mass should be installed. This information can be obtained from the component manufacturer. 27
28 INSTALLATION Compressor handling Each Performer scroll compressor is delivered with two lift rings. Always use these rings when lifting the compressor. A spreader bar rated for the mass of the compressor is highly recommended to ensure a better load distribution. Given that the center of gravity on the scroll is very high, the use of one lifting lug will result in an unstable load. The compressor mass is too great for the single lug to handle, and the risk is run that the lug could separate from the compressor with extensive damage and possible personal injury as a result. The use of lifting hooks closed with a clasp and certified to lift the weight of the compressor is also highly recommended (see the adjacent figure). Always respect the appropriate rules concerning lifting objects of the type and weight of these compressors. When the compressor is mounted as part of an installation, never use the lift rings on the compressor to lift the entire installation, which may be too heavy for lifting in this manner. Maintain the compressor in an upright position during all handling maneuvers. Never apply force to the terminal box with the intention of moving the compressor, as the force placed upon the terminal box will cause extensive damage to both the box and the eventual motor protection module compo- Mounting All compressors come delivered with four rubber mounting grommets and metal sleeve liners that serve to isolate the compressor from the base frame. These grommets attenuate to a great extent the transmission of compressor vibrations to the base frame. The rubber grommets must be compressed until contact between the flat washer and the steel-mounting sleeve is established. The required bolt size for the SM / SZ 084 to 185 compressors is HM8. This bolt must be tightened to a torque of 21 Nm. The bolts and washers are supplied with the assembly kit. The required bolt size for the SY / SZ 240 to 380 compressors is HM10. The minimum required flat washer outside diameter is 27 mm. Mounting bolts must be tightened to a torque of 40 Nm. These bolts and washers are not supplied with the compressor. Note: The large flat washer must be positioned in place before shipping the unit with the compressor installed. Lock washer HM 8 Bolt Flat washer Compressor base plate Steel mounting sleeve Rubber g rommet Nut 28 mm SM-SZ 084 to
29 INSTALLATION Lock washer* HM 10 Bolt* Large Flat* 27 mm washer Compressor base plate Steel mounting sleeve Rubber grommet 36 mm Nut* SY-SZ 240 to 380 *Not supplied with compressor Removing connections shipping plugs Before the suction and discharge plugs are removed, the nitrogen holding charge must be released via the suction schrader valve to avoid an oil mist blowout. Remove the suction plug first and the discharge plug afterwards. The plugs shall be removed only just before connecting the compressor to the installation in order to avoid moisture from entering the compressor. When the plugs are removed, it is essential to keep the compressor in an upright position so as to avoid oil spillage. System cleanliness The refrigerant compression system, regardless of the type of compressor used, will only provide high efficiency and good reliability, along with a long operating life, if the system contains solely the refrigerant and oil it was designed for. Any other substances within the system will not improve performance and, in most cases, will be highly detrimental to system operations. The presence of non-condensable substances and system contaminants, such as metal shavings, solder and flux, have a negative impact on compressor service life. Many of these contaminants are small enough to pass through a mesh screen and can cause considerable damage within a bearing assembly. The use of highly-hygroscopic polyester oil in R407C compressors requires that the oil be exposed to the atmosphere just as little as possible. System contamination is one of main factors affecting equipment reliability and compressor service life. It is important therefore to take system cleanliness into account when assembling a refrigeration system. During the manufacturing process, circuit contamination may be caused by: Brazing and welding oxides, Filings and particles from the removal of burrs in pipe-work, Brazing flux, Moisture and air. Consequently, when building equipment and assemblies, the following precautions must be taken: Never drill holes into the pipe-work after installation. Tubing Only use clean and dehydratated refrigeration-grade copper tubing. Tubecutting must be carried out so as not to deform the tubing roundness and to ensure that no foreign debris remains within the tubing. Only refrigerant-grade fittings should be used and these must be of both a design and size to allow for a minimum pressure drop through the completed assembly. Follow the brazing instructions next pages. 29
30 INSTALLATION Filter driers For new installations with SY / SZ compressors with polyolester oil, Danfoss Commercial Compressors recommends using the Danfoss DML 100%- moleculair sieve, solid core filter drier. Molecular sieve filter driers with loose beads from third party suppliers shall be avoided. For servicing of existing installations where acid formation is present the Danfoss DCL solid core filter driers containing activated alumina are recommended. Also for new installations with SM compressors with mineral oil the Danfoss DCL drier is recommended. The drier is to be oversized rather than undersized. When selecting a drier, always take into account its capacity (water content capacity), the system refrigeration capacity and the system refrigerant charge. Brazing and soldering Copper to copper connections When brazing copper-to-copper connections, the use of a copper/phosphorus brazing alloy containing 5% silver or more with a melting temperature of below 800 C is recommended. No flux is required during brazing. Dissimilar metals connection When manipulating dissimilar metals such as copper and brass or steel, the use of silver solder and anti-oxidant flux is necessary. Compressor connection When brazing the compressor fittings, do not overheat the compressor shell, which could severely damage certain internal components due to excessive heating. Use of a heat shield and/or a heat-absorbent compound is highly recommended. Due to the relatively sizable tubing and fitting diameters used for the large scroll, a double tipped torch using acetylene is recommended for the S brazing operation. For rotolock version compressors, solder sleeves are available. For brazing the suction and discharge connections, the following procedure is advised: Make sure that no electrical wiring is connected to the compressor. Protect the terminal box and compressor painted surfaces from torch heat damage (see diagram). Remove the teflon gaskets when brazing rotolock connectors with solder sleeves. Use only clean refrigeration-grade copper tubing and clean all connections. Use brazing material with a minimum of 5% silver content. heat shield Purge nitrogen or CO 2 through the compressor in order to prevent against oxidation and flammable conditions. The compressor should not be exposed to the open air for extended periods. Use of a double-tipped torch is recommended. Apply heat evenly to Area A until the brazing temperature is reached. Move the torch to Area B and apply heat evenly until the brazing temperature has been reached there as well, and then begin adding the brazing material. Move the torch evenly around the joint, in applying only enough brazing material to flow the full circumference of the joint. Move the torch to area C only long enough to draw the brazing material C B A 30
31 INSTALLATION into the joint, but not into the compressor. Remove all remaining flux once the joint has been soldered with a wire brush or a wet cloth. Remaining flux would cause corrosion of the tubing. Ensure that no flux is allowed to enter into the tubing or compressor. Flux is acidic and can cause substantial damage to the internal parts of the system and compressor. The polyolester oil used in SY / SZ compressors is highly hygroscopic and will rapidly absorb moisture from the air. The compressor must therefore not be left open to the atmosphere for a long period of time. The compressor fitting plugs shall be removed just before brazing the compressor. Before eventual unbrazing the compressor or any system component, the refrigerant charge must be removed from both the high- and low-pressure sides. Failure to do so may result in serious personal injury. Pressure gauges must be used to ensure all pressures are at atmospheric level. For more detailed information on the appropriate materials required for brazing or soldering, please contact the product manufacturer or distributor. For specific applications not covered herein, please contact Danfoss Commercial Compressors for further information. System pressure test Always use an inert gas such as nitrogen for pressure testing. Never use other gasses such as oxygen, dry air or acetylene as these may form an inflammable mixture. Do not exceed the following pressures: Maximum compressor test pressure (low side) 25 bar (g) Maximum compressor test pressure (high side) Maximum pressure difference between high and low side of the compressor: 32 bar (g) 24 bar Pressurize the system on HP side first then LP side to prevent rotation of the scroll. Leak detection Leak detection must be carried out using a mixture of nitrogen and refrigerant or nitrogen and helium, as indicated in the table below. Never use other gasses such as oxygen, dry air or acetylene as these may form an inflammable mixture. Pressurize the system on HP side first then Low side. Compressor model Leak detection with refrigerant Leak detection with a mass spectrometer SM-SY compressors Nitrogen & R22 Nitrogen & Helium SZ compressors Nitrogen & R134a or R407C Nitrogen & Helium Note 1: Leak detection with refrigerant may be forbidden in some countries. Check local regulations. Note 2: The use of leak detecting additives is not recommended as they may affect the lubricant properties. 31
32 INSTALLATION Vacuum pump-down and moisture removal Moisture obstructs the proper functioning of both the compressor and the refrigeration system. Air and moisture reduce service life and increase condensing pressure, which causes abnormally high discharge temperatures that are then capable of degrading the lubricating properties of the oil. The risk of acid formation is also increased by air and moisture, and this condition can also lead to copper plating. All these phenomena may cause both mechanical and electrical compressor failures. The typical method for avoiding such problems is a vacuum pump-down executed with a vacuum pump, thus creating a minimum vacuum of 500 microns (0.67 mbar). Please refer to Bulletin "Vaccum pump down and dehydration procedure". Refrigerant charging For the initial charge the compressor must not run and eventual service valves must be closed. Charge refrigerant as close as possible to the nominal system charge before starting the compressor. This initial charging operation must be done in liquid phase as much as possible away from the compressor: the best location is on the liquid line between the condenser outlet and the filter drier. Then during commissioning, when needed, a complement of charge can be done in liquid phase: slowly throttling liquid in on the low pressure side as far away as possible from the compressor suction connection. The refrigerant charge quantity must be suitable for both summer and winter operations. Commissioning Oil level checking and top-up Oil level check When the compressor is running under stabilised conditions the oil level must be visible in the sight glass. The presence of foam filling in the sight glass undicates large concentration of refrigerant in the oil and / or presence of liquid returning to the compressor. The oil level can also be checked a few The system must be monitored after initial start-up for a minimum of 60 minutes to ensure proper operating characteristics such as: Proper metering device operation and desired super heat readings, Suction and discharge pressure are within acceptable levels, Correct oil level in compressor sump indicating proper oil return, Low foaming in sight glass and compressor sump temperature 10 K above saturation temperature to show that there is no refrigerant migration taking place, Acceptable cycling rate of compressors, including duration of run times, Current draw of individual compressors within acceptable values (RLA ratings), No abnormal vibrations and noise. minutes after the compressor stops, the level must be between 1/4" and 3/4" of sight glass. When compressor is off the level in the sight glass can be influenced by the presence of refrigerant in the oil. Oil top-up Always use original Danfoss Commercial Compressors specified oil type from new cans. Top-up the oil while the compressor is running. Use the Schrader connector and a suitable pump or any other accessible connector on the compressor suction line. See Bulletin "Lubricants, filling in instructions for Danfoss Commercial Compressors". Please note that the compressors SZ and SY use different viscosity POE oil, respectively 160SZ and 320SZ. 32
33 ACCESSORIES Connectors and valves Model Solder sleeve adaptor set Code n Suct. ODF Solder sleeve Disch. ODF Suct. ODF Rotolock valve set 7/8" 3/4" 7/8" 3/4" V07-V SM/SZ * 1"1/8 3/4" 1"1/8 3/4" V02-V "3/4 1"1/4 1"3/8 7/8" 1"3/8 7/8" V10-V /8" 3/4" 7/8" 3/4" V07-V SM/SZ * 1"1/8 3/4" 1"1/8 3/4" V02-V "3/4 1"1/4 1"3/8 7/8" 1"3/8 7/8" V10-V /8" 3/4" 7/8" 3/4" V07-V SM/SZ * 1"1/8 3/4" 1"1/8 3/4" V02-V "3/4 1"1/4 1"3/8 7/8" 1"3/8 7/8" V10-V SM/SZ * 1"1/8 3/4" 1"1/8 3/4" V02-V "3/8 7/8" 1"3/8 7/8" V10-V "3/4 1"1/4 SM/SZ ** 1"1/8 3/4" 1"1/8 3/4" V02-V "3/8 7/8" 1"3/8 7/8" V10-V "3/4 1"1/4 SM/SZ * 1"1/8 3/4" 1"1/8 3/4" V02-V "3/8 7/8" 1"3/8 7/8" V10-V "3/4 1"1/4 SM/SZ ** 1"1/8 3/4" 1"1/8 3/4" V02-V "3/8 7/8" 1"3/8 7/8" V10-V "3/4 1"1/4 SM/SZ * 1"1/8 3/4" "3/8 7/8" 1"3/8 7/8" V10-V "3/4 1"1/4 SM/SZ ** 1"3/8 7/8" 1"3/8 7/8" V08-V "5/8 1"1/8 1"5/8 1"1/8 V03-V "1/4 1"3/4 SM/SZ * 1"1/8 3/4" "3/8 7/8" 1"3/8 7/8" V10-V "3/4 1"1/4 SM/SZ ** 1"3/8 7/8" 1"3/8 7/8" V08-V "5/8 1"1/8 1"5/8 1"1/8 V03-V "1/4 1"3/4 SM/SZ ** 1"3/8 7/8" 1"3/8 7/8" V08-V "5/8 1"1/8 1"5/8 1"1/8 V03-V "1/4 1"3/4 SY/SZ 240-1"5/8 1"1/8 1"5/8 1"1/8 V03-V "1/4 1"3/4 SY/SZ 300-1"5/8 1"1/8 1"5/8 1"1/8 V03-V "1/4 1"3/4 SY/SZ Solder sleeve adaptor set not available at printing date - - Disch. ODF Rotolock size of: Rotolock version compressors, solder sleeve, adaptor set and rotolock valve Type Code n Suct. Disch. ODF: Outer diameter female. * Solder sleeve adaptor set accessory required to convert brazed version compressor to rotolock. ** Rotolock version compressors exist for these compressor models. Sizes of solder sleeves included in the solder sleeve adaptor set accessory. Solder sleeves Also denotes the standard sleeve sizes supplied with rotolock version compressors. Rotolock valves Standard rotolock valve sets. Lubricants SM / SY / SZ compressors use different oil types as indicated below. Always use original Danfoss Commercial Compressors specified oil type from new cans. Compressor model Oil type Oil name For initial compressor oil charge refer to page 6-7. Please refer to "Lubricant, filling in instructions for Danfoss Commercial Compressors" for detailed oil specifications and top-up method. code number 1 litre can 2 litre can 5 litre can SM compressors Mineral 160P SZ compressors P.O.E. 160 SZ SY compressors P.O.E. 320 SZ
34 ACCESSORIES Crankcase heaters The belt-type crankcase heater accessories are designed to protect the compressor against off-cycle migration of refrigerant Optimum location area h 1/2 h 1/3 h Code no. Description Application Pack size Belt type crankcase heater, 65 W, 110 V, CE mark, UL SM/SZ Belt type crankcase heater, 65 W, 110 V, CE mark, UL SM/SZ Belt type crankcase heater, 65 W, 230 V, CE mark, UL SM/SZ Belt type crankcase heater, 65 W, 230 V, CE mark, UL SM/SZ Belt type crankcase heater, 65 W, 400 V, CE mark, UL SM/SZ Belt type crankcase heater, 50 W, 110 V, UL SM/SZ Belt type crankcase heater, 50 W, 240 V, UL SM/SZ Belt type crankcase heater, 50 W, 400 V, UL SM/SZ Belt type crankcase heater, 50 W, 460 V, UL SM/SZ Belt type crankcase heater, 75 W, 575 V, UL SM/SZ Belt type crankcase heater, 75 W, 110 V, CE mark, UL SM/SZ Belt type crankcase heater, 75 W, 230 V, CE mark, UL SM/SZ Belt type crankcase heater, 75 W, 230 V, CE mark, UL SM/SZ Belt type crankcase heater, 75 W, 400 V, CE mark, UL SM/SZ Belt type crankcase heater, 100 W, 110 V, UL SM/SZ Belt type crankcase heater, 100 W, 240 V, UL SM/SZ Belt type crankcase heater, 75 W, 400 V, UL SM/SZ Belt type crankcase heater, 75 W, 575 V, UL SM/SZ Belt type crankcase heater, 130 W, 110 V, CE mark, UL SY/SZ Belt type crankcase heater, 130 W, 230 V, CE mark, UL SY/SZ Belt type crankcase heater, 130 W, 230 V, CE mark, UL SY/SZ Belt type crankcase heater, 130 W, 400 V, CE mark, UL SY/SZ
35 ACCESSORIES Discharge temperature protection The discharge gas temperature must not exceed 135 C. The discharge gas thermostat accessory kit includes all components required for installation, as shown below. The thermostat must be attached to the discharge line within 150 mm from the compressor discharge port. Discharge thermostat kit code number: Thermostat Discharge line Bracket Insulation Compressor acoustic hoods Compressor acoustic hoods have been developed to meet specific extra-low noise requirements. The covers incorporate soundproofing materials and offer excellent high and low frequency attenuation. Compressor model attenuation* (at 50Hz) db(a) Hood code number SM / SZ SM / SZ SM / SZ SM / SZ SM / SZ ** SM / SZ SY / SZ SY / SZ * Attenuation of compressor sound power level measured in free space ** not available for code 3 version compressors 35
36 ORDERING INFORMATION AND PACKAGING Ordering information Compressor model Design Connections Performer scroll compressors may be ordered from Danfoss Commercial Compressors in either industrial packs (Multiple packaging) or in single packs (Individual packaging). Motor protection Code no /3/60 460/3/60 400/3/50 The below tables lists the code numbers for industrial packs. For ordering single packs please replace the last digit with an " I ". SM /SY compressors in industrial-pack (Multiple packaging) 230/3/50 575/3/60 500/3/50 R22 380/3/60 SM084 Single Brazed Int SM084-3VM SM084-4VM SM084-6VM SM084-7VM SM084-9VM SM090 Single Brazed Int SM090-3VM SM090-4VM SM090-6VM SM090-7VM SM090-9VM SM100 Single Brazed Int SM100-3VM SM100-4VM SM100-6VM SM100-7VM SM100-9VM SM110 Single Brazed Int SM110-3VM SM110-4VM SM110-6VM SM110-7VM SM110-9VM SM115 Single Brazed T SM115-3CAM SM115-4CAM SM115-6CAM SM115-7CAM SM115-9CAM Rotolock T SM115-3RM SM115-4RM SM115-6RM SM115-7RM SM115-9RM SM120 Single Brazed Int SM120-3VM SM120-4VM SM120-6VM SM120-7VM SM120-9VM SM125 Single Brazed T SM125-3CAM SM125-4CAM SM125-6CAM SM125-7CAM SM125-9CAM Rotolock T SM125-3RM SM125-4RM SM125-6RM SM125-7RM SM125-9RM SM148 Single Brazed Int SM148-3VAM SM148-4VAM SM148-6VAM SM148-7VAM SM148-9VAM SM160 Single Brazed T SM160-3CBM SM160-4CBM SM160-6CBM SM160-7CAM SM160-9CBM Rotolock T SM160-3RAM SM160-4RAM SM160-6RAM SM160-7RAM SM160-9RAM SM161 Single Brazed Int SM161-3VAM SM161-4VAM SM161-6VAM SM161-7VAM SM161-9VAM SM175 SM185 SY240 SY300 Single Single Single Single Brazed T SM175-3CAM SM175-4CAM SM175-6CAM SM175-7CAM SM175-9CAM Rotolock T SM175-3RM SM175-4RM SM175-6RM SM175-7RM SM175-9RM Brazed T SM185-3CAM SM185-4CAM SM185-6CAM SM185-7CAM SM185-9CAM Rotolock T SM185-3RM SM185-4RM SM185-6RM SM185-7RM SM185-9RM Brazed M24 SY240A3AAM SY240A4AAM SY240A6AAM SY240A7AAM SY240A9AAM Brazed M230 SY240A3ABM SY240A4ABM SY240A6ABM SY240A7ABM SY240A9ABM Rotolock M24 SY240A3MAM SY240A4MAM SY240A6MAM SY240A7MAM SY240A9MAM Rotolock M230 SY240A3MBM SY240A4MBM SY240A6MBM SY240A7MBM SY240A9MBM Brazed M24 SY300A3AAM SY300A4AAM SY300A6AAM SY300A7AAM SY300A9AAM Brazed M230 SY300A3ABM SY300A4ABM SY300A6ABM SY300A7ABM SY300A9ABM Rotolock M24 SY300A3MAM SY300A4MAM SY300A6MAM SY300A7MAM SY300A9MAM Rotolock M230 SY300A3MBM SY300A4MBM SY300A6MBM SY300A7MBM SY300A9MBM Int = Internal motor protection T = Internal thermostat. Additional external protection required M24 = Electronic motor protection module located in terminal box 24 V M230 = Electronic motor protection module located in terminal box 115 / 230 V SY380: data not available at the printing date of this document 36
37 ORDERING INFORMATION AND PACKAGING SZ compressors in industrial-pack (Multiple packaging) Compressor model Design Connections Motor protection R407C / R134a Code no /3/60 460/3/60 400/3/50 230/3/50 575/3/60 500/3/50 380/3/60 SZ084 Single Brazed Int SZ084-3VM SZ084-4VM SZ084-6VM SZ084-7VM SZ084-9VM SZ090 Single Brazed Int SZ090-3VM SZ090-4VM SZ090-6VM SZ090-7VM SZ090-9VM SZ100 Single Brazed Int SZ100-3VM SZ100-4VM SZ100-6VM SZ100-7VM SZ100-9VM SZ110 Single Brazed Int SZ110-3VM SZ110-4VM SZ110-6VM SZ110-7VM SZ110-9VM Brazed T SZ115-3CAM SZ115-4CAM SZ115-6CAM SZ115-7CAM SZ115-9CAM SZ115 Single Rotolock T SZ115-3RM SZ115-4RM SZ115-6RM SZ115-7RM SZ115-9RM SZ120 Single Brazed Int SZ120-3VM SZ120-4VM SZ120-6VM SZ120-7VM SZ120-9VM Brazed T SZ125-3CAM SZ125-4CAM SZ125-6CAM SZ125-7CAM SZ125-9CAM SZ125 Single Rotolock T SZ125-3RM SZ125-4RM SZ125-6RM SZ125-7RM SZ125-9RM SZ148 Single Brazed Int SZ148-3VAM SZ148-4VAM SZ148-6VAM SZ148-7VAM SZ148-9VAM Brazed T SZ160-3CBM SZ160-4CBM SZ160-6CBM SZ160-7CAM SZ160-9CBM SZ160 Single Rotolock T SZ160-3RAM SZ160-4RAM SZ160-6RAM SZ160-7RAM SZ160-9RAM SZ161 Single Brazed Int SZ161-3VAM SZ161-4VAM SZ161-6VAM SZ161-7VAM SZ161-9VAM SZ175 SZ185 SZ240 SZ300 SZ 380 Single Single Single Single single Brazed T SZ175-3CAM SZ175-4CAM SZ175-6CAM SZ175-7CAM SZ175-9CAM Rotolock T SZ175-3RM SZ175-4RM SZ175-6RM SZ175-7RM SZ175-9RM Brazed T SZ185-3CAM SZ185-4CAM SZ185-6CAM SZ185-7CAM SZ185-9CAM Rotolock T SZ185-3RM SZ185-4RM SZ185-6RM SZ185-7RM SZ185-9RM Brazed M24 SZ240A3AAM SZ240A4AAM SZ240A6AAM SZ240A7AAM SZ240A9AAM Brazed M230 SZ240A3ABM SZ240A4ABM SZ240A6ABM SZ240A7ABM SZ240A9ABM Rotolock M24 SZ240A3MAM SZ240A4MAM SZ240A6MAM SZ240A7MAM SZ240A9MAM Rotolock M230 SZ240A3MBM SZ240A4MBM SZ240A6MBM SZ240A7MBM SZ240A9MBM Brazed M24 SZ300A3AAM SZ300A4AAM SZ300A6AAM SZ300A7AAM SZ300A9AAM Brazed M230 SZ300A3ABM SZ300A4ABM SZ300A6ABM SZ300A7ABM SZ300A9ABM Rotolock M24 SZ300A3MAM SZ300A4MAM SZ300A6MAM SZ300A7MAM SZ300A9MAM Rotolock M230 SZ300A3MBM SZ300A4MBM SZ300A6MBM SZ300A7MBM SZ300A9MBM Brazed M24 - SZ380A4CAM Brazed M230 - SZ380A4CBM Int = Internal motor protection T = Internal thermostat. Additional external protection required M24 = Electronic motor protection module located in terminal box 24 V M230 = Electronic motor protection module located in terminal box 115 / 230 V 37
38 ORDERING INFORMATION AND PACKAGING Packaging Multipack Single pack (Individual packaging) Compressor models Nbr* Length mm Width mm Height mm Gross weight kg Static stacking pallets Length mm Width mm Height mm Gross weight kg SM/SZ SM/SZ SM/SZ SM/SZ SM/SZ SM/SZ SM/SZ SM/SZ SY/SZ SY/SZ SY/SZ * Nbr = number of compressors per pallet Industrial pack (Multiple packaging) Compressor models Nbr* Length mm Width mm Height mm Gross weight kg Static stacking pallets SM/SZ SM/SZ SM/SZ SM/SZ SM/SZ SM/SZ SM/SZ SM/SZ SY/SZ SY/SZ SY/SZ
39
40 Danfoss Commercial Compressors Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed. All trademarks in this material are property of the respective companies. Performer, Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved. FRCC.PC.003.A March
Reciprocating Compressors MT/MTZ 50-60 Hz
Selection & Application Guidelines Reciprocating Compressors MT/MTZ 50-60 Hz R22 - R407C - R134a - R404A/R507A RECIPROCATING COMPRESSORS CONTENTS MANEUROP RECIPROCATING COMPRESSORS... p 3 COMPRESSOR MODEL
Why and How we Use Capacity Control
Why and How we Use Capacity Control On refrigeration and air conditioning applications where the load may vary over a wide range, due to lighting, occupancy, product loading, ambient weather variations,
Table V. Troubleshooting Checklist for Refrigeration Systems. Air or non-condensable gas in system. Inlet water warm.
Table V Troubleshooting Checklist for Refrigeration Systems TROUBLE POSSIBLE CAUSE CORRECTIVE MEASURE High condensing pressure. Low condensing pressure. Air or non-condensable gas in system. Inlet water
Maneurop reciprocating compressors. MT/MTZ 50-60 Hz - R22 - R407C - R134a - R404A / R507A MAKING MODERN LIVING POSSIBLE
MAKING MODERN LIVING POSSIBLE Maneurop reciprocating compressors MT/MTZ 50-60 Hz - R22 - R407C - R134a - R404A / R507A REFRIGERATION & AIR CONDITIONING DIVISION Selection & Application guidelines Contents
ECOCIAT. Domestic hot water heat recovery unit
Heat recovery unit Domestic hot water High energy efficiency with R410A Compact and quiet Scroll compressors Brazed-plate heat exchangers Heating Heat recovery ENVIRONMENTALLY HFC R410A PROTECTION DE FRIENDLY
Oil and Coolant Circulating Heating System. Model - OCSM
Oil and Coolant Circulating Heating System Model - OCSM Installation & Operation Manual 216280-000 REV 2 Identifying Your System The HOTSTART heating system is designed to heat fluids for use in marine
543-0032-00, 943-0032-00. User s Manual
543-0032-00, 943-0032-00 User s Manual 1 Comfort Alert Diagnostics Faster Service And Improved Accuracy The Comfort Alert diagnostics module is a breakthrough innovation for troubleshooting heat pump and
technical data air conditioning systems RXS20-25-35E (single phase) FBQ-B8V1-B8V3B Split Heat Pump Condensing Units Split Sky Air
technical data RXS20-25-35E FBQ-B8V-B8V3B (single phase) Split Heat Pump Condensing Units air conditioning systems Split Sky Air Outdoor Units R-40A RXS-E2VB Split Sky Air Outdoor Units Features O u t
MAC-120HE-01 Air-Cooled Chiller
MAC-120HE-01 Air-Cooled Chiller 10 Ton / 120,000 BTUH Air-Cooled Chiller 208/230-1-50/60 1 HVAC Guide Specifications Air-Cooled Liquid Chiller Nominal Size: 10 Tons Multiaqua Model Number: MAC-120HE-01
Table Z. Troubleshooting Chart for Air Conditioners. Cause
Troubleshooting Chart for Air Conditioners Type of Unit Complaint Cause With open-type compressor Electric motor will not start Power failure Check circuit for power source Compressor stuck Locate cause
Technical Information
Date of last update: Oct-11 Ref: D7.8.4/1011/E Application Engineering Europe CORESENSE DIAGNOSTICS FOR STREAM REFRIGERATION COMPRESSORS CoreSense Diagnostics for Stream Refrigeration Compressors... 1
Heating, Ventilation, Air Conditioning and Refrigeration (HVACR)
Heating, Ventilation, Air Conditioning and Refrigeration (HVACR) I. Demonstrate safety skills in typical HVACR work situations to NATE Core Installer Knowledge Areas for Technician Excellence for Safety
It will be available soon as an 8.5 X 11 paperback. For easier navigation through the e book, use the table of contents.
The System Evaluation Manual and Chiller Evaluation Manual have been revised and combined into this new book; the Air Conditioning and Refrigeration System Evaluation Guide. It will be available soon as
Engineering Recommendation on: Accumulators Revised 6-17-99 Issued January 10, 1979 Page 1 of 7
Issued January 10, 1979 Page 1 of 7 Accumulators have long been recognized by the industry as an effective means of maintaining good system balance by storing excess refrigerant as the condenser or evaporator
Indoor coil is too warm in cooling mode or too cold in heating mode. Reversing valve or coil thermistor is faulty
Codes Room Air Conditioner range: Indoor unit alarm s If timer lamp flashes for 1 second on, 1 second off, this indicates pre heating on the coil during heating mode and is not an error. If timer lamp
MP-4000 Alarm List (Software version 2.4.3 or later)
Service Bulletin SUBJECT: MP4000 Alarm s BULLETIN: C 100 DATE: June 19, 2013 ALARM LIST Where it is possible the alarm number is kept the same as for MP-3000. MP-3000 holds alarm number from 0 to 127.
HP switch LP switch Discharge thermo Comp. Surface thermo
1 Specifications Zubadan Model Name PUHZ-SHW80VHA PUHZ-SHW11VHA PUHZ-SHW11YHA Power supply (phase, cycle, voltage) 1φ, V, Hz 1φ, V, Hz 3φ, 0V, Hz Max. current A 9.5 35.0 13.0 Breaker size A 3 16 Outer
Over 30% 2-40 TR. Air Conditioning Danfoss compressors For comfort and precise cooling. www.danfoss.com. energy savings
MAKING MODERN LIVING POSSIBLE Air Conditioning Danfoss compressors For comfort and precise cooling With scroll and reciprocating technologies Over 30% energy savings with Danfoss inverter scrolls accelerate
AE21-1319 R6 December 2013. Digital Capacity Control for Copeland Scroll Refrigeration Compressors AE21-1319 R6
AE21-1319 R6 December 2013 Digital Capacity Control for Copeland Scroll Refrigeration Compressors TABLE OF CONTENTS Section Page Section Page Safety Safety Instructions...2 Safety Icon Explanation...2
Heat Pump Water Heater IOM Manual
Heat Pump Water Heater IOM Manual Installation Operation & Maintenance This manual is intended as an aid to qualified service personnel for proper installation, operation and maintenance of the heat pump
SECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS
SECTION 15750 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for roof mounted, self-contained units, with electric cooling, and electric or reverse refrigeration cycle (heat pump) heating
Skills Canada National Competition Instructions and Competition Details 38 Refrigeration and Air Conditioning / Post - Secondary May 27-30, 2015 -
Skills Canada National Competition Instructions and Competition Details / Post - Secondary May 27-30, 2015 - Saskatoon 1. Test Project Details This project is designed to test the range of skills used
SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM
SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop air conditioning unit (5 tons and smaller). 2. Roof curb. 1.2
Technical Information
Date of last update: Jul-05 Ref: Application Engineering Europe OIL PRESSURE SAFETY CONTROL FOR SEMI-HERMETICS 1 Oil Pressure Differential Switches The oil pressure differential switch breaks the control
Geothermal Alliance of Illinois. TXVs Theory and Fundamentals John Haug Senior Application Engineer Emerson Climate Technologies - Flow Controls
Geothermal Alliance of Illinois TXVs Theory and Fundamentals John Haug Senior Application Engineer Emerson Climate Technologies - Flow Controls Thermal Expansion Valve Topics Anatomy Operation Terms &
LOBOY 16 AIR CONDITIONERS
INSTRUCTION MANUAL FOR: LOBOY 16 AIR CONDITIONERS McLean Midwest Corp. dba: McLean Cooling Technology 11611 Business Park Blvd. N Champlin, MN 55316 Tel: 763-323-8200 Fax: 763-576-3200 www.mcleancoolingtech.com
Water Fired Chiller/Chiller-Heater. WFC-S Series: 10, 20 and 30 RT Cooling
Water Fired Chiller/Chiller-Heater WFC-S Series: 1, 2 and 3 RT Cooling W E A R E F R I E N D L Y T O T H E E A R T H Water Fired SINGLE-EFFECT Chiller or Chiller-Heater Absorption Principle Cooling Cycle
Low Profile Unit Cooler
Super-Flo Now available with EC Motors High Efficiency / High Reliability Low Profile Unit Cooler Publication No. 411.4 November, 2008 S A N I T A T I O N F O U N D A T I O N A L N A T I O N Air Defrost
R22. K Control. Indoor Unit. Nomenclature. Compatibility PL H 3 G K H B. Unit style Heat Pump Horse Power
R22. K Control. Indoor Unit. Nomenclature. PL H 3 G K H B Compatibility Unit style Heat Pump Horse Power Control Boost Heaters R22. K Control. Outdoor Unit. Nomenclature. PU H 3 Y K A Compatibility Outdoor
A/C refrigerant system, overview
Page 1 of 19 87-18 A/C refrigerant system, overview A/C refrigerant system, identification Typical A/C refrigerant system with expansion valve and receiver drier 1 - Evaporator 2 - Expansion valve 3 -
Service manual. Website: www.andico.com.au CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL.
Website: www.andico.com.au Service manual CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL. - ONLY FOR AUTHORISED SERVICE PERSONNEL. MODELS: MPK1-09CR-QB8 MPK1-12ER-QB6
Scroll Compressors for Air Conditioning ZR18K* to ZR380K*, ZP24K* to ZP485K*
Scroll Compressors for Air Conditioning ZR18K* to ZR380K*, ZP24K* to ZP485K* 1 Safety instructions... 1 1.1 Icon explanation... 1 1.2 Safety statements... 1 1.3 General instructions... 2 2 Product description...
Refrigeration Basics 101. By: Eric Nelson
Refrigeration Basics 101 By: Eric Nelson Basics Refrigeration is the removal of heat from a material or space, so that it s temperature is lower than that of it s surroundings. When refrigerant absorbs
Any Service Technician Can Fix It A Good Service Technician Can Figure Out What s Wrong With It.
I Dave s Statement If the thermostat calls for cooling, and the furnace fan is running properly, and the coil airflow is adequate, and the condenser fan is running properly, and the condenser airflow is
Refrigerant Changeover Guidelines R-22 to R-407C. Leading the Industry with Environmentally Responsible Refrigerant Solutions
Refrigerant Changeover Guidelines R-22 to R-407C Leading the Industry with Environmentally Responsible Refrigerant Solutions Copeland does not CFC advocate the wholesale changeover of HCFC HCFC refrigerants
Split System Heat Pump Product Data
Split System Heat Pump Product Silver 14 4A6H4 1 1 /2-5 Tons PUB. NO. 12-1175-07 Contents Features and Benefits 2 Model Nomenclature 3 General 4 Product Specifications 4 A-weighted Sound Power Level [db(a)]
APPLICATION GUIDELINE & SERVICE MANUAL R 410A & R 22 Split System AC & HP
APPLICATION GUIDELINE & SERVICE MANUAL TABLE OF CONTENTS PAGE PAGE UNIT IDENTIFICATION... 2 REFRIGERATION SYSTEM REPAIR... 24 26 SAFETY CONSIDERATIONS... 4 INTRODUCTION... 4 INSTALLATION GUIDELINE... 4
POLICY BULLETIN Tecumseh Compressor Company Compressor Group
to Bulk Milk Coolers and Other System Page 1 of 5 Overall reliability can be enhanced if there exists a complete understanding of the features, system design, installation requirements, processing, charging
D A T A S H E E T. TX6 Thermo Expansion Valves. Alco Controls TX6. Features. Introduction. Construction
ALCO s series of Thermo -Expansion Valves are designed for air conditioning, chillers, rooftops, close control, A/C transportation, heat pumps, industrial cooling process and refrigeration applications.
D A T A S H E E T. TX3 Thermo Expansion Valves. Alco Controls TX3. Features. Introduction. Description of bulb charges
ALCO s TX3 series of Thermo -Expansion Valves are designed for air conditioning, heat pumps and commercial refrigeration applications. The TX3 is ideal for those applications requiring hermetic / compact
SYLLABUS For BASIC TRADE COURSE (360 Hours) On REFRIGERATION AND AIR CONDITIONING
SYLLABUS For BASIC TRADE COURSE (360 Hours) On REFRIGERATION AND AIR CONDITIONING INDEX 1. Introduction 3 2. Objectives 3 3. Employment Opportunity 4 4. Course Structure 4 5. Entry Qualification 4 6. List
HERZ-Thermal Actuators
HERZ-Thermal Actuators Data Sheet 7708-7990, Issue 1011 Dimensions in mm 1 7710 00 1 7710 01 1 7711 18 1 7710 80 1 7710 81 1 7711 80 1 7711 81 1 7990 00 1 7980 00 1 7708 11 1 7708 10 1 7708 23 1 7709 01
SERVICE INSTRUCTION R410A. WALL MOUNTEDtype INVERTER SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit
SERVICE INSTRUCTION SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTEDtype INVERTER Models Indoor unit Outdoor unit ASYG07LECA ASYG09LECA ASYG12LECA ASYG14LECA AOYG07LEC AOYG09LEC AOYG12LEC AOYG14LEC R410A CONTENTS
How To Design A Refrigeration System
AIRAH Refrigeration (in HVAC) Back to Basics For the First Time Terms of Reference What this session is NOT about Detailed Refrigeration Design Detailed analysis of various Refrigants properties Comparison
User s Information/Installation Instructions
Outdoor Heat Pump User s Information/Installation Instructions 13 SEER R-410A High Efficiency Split System These units have been designed and tested for capacity and effi ciency in accordance with A.R.I.
Troubleshooting HVAC/R systems using refrigerant superheat and subcooling
Troubleshooting HVAC/R systems using refrigerant superheat and subcooling Application Note Troubleshooting and servicing refrigeration and air conditioning systems can be a challenging process for both
PANASONIC TROUBLE SHOOTING GUIDE
A General Guide To Room Style Products Pipework Pipe sizes and lengths should be as the relevant Technical Guide Both lines should be insulated No line accessories or oil traps should be fitted In cooling
Glossary of Heating, Ventilation and Air Conditioning Terms
Glossary of Heating, Ventilation and Air Conditioning Terms Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment
AIR-COOLED CHILLERS APPLIED SYSTEMS. www.daikin.eu EUWA*5-24KAZW - EUWY*5-24KAZW -
AIR-COOLED CHILLERS APPLIED SYSTEMS www.daikin.eu Cooling Only Heat pump EUWA*5-24KAZW - EUWY*5-24KAZW - Environmental Awareness Daikin and the Environment In recent years, motivated by a global awareness
Characteristics of Evaporators
Characteristics of Evaporators Roger D. Holder, CM, MSME 10-28-2003 Heat or Energy In this paper, we will discuss the characteristics of an evaporator coil. The variance of the operational condenses of
ice 3 FLUID TO FLUID HEAT PUMP
ice 3 FLUID TO FLUID HEAT PUMP SUBMITTAL DATA (888) 530-7713 P O Box 5, Wentworth, H 03282 Rev.3 (5-30-14) ice 3, IC-2040 Fluid-to-Fluid R-410a Heat Pump Engineering Guide Specifications General otes:
Application Engineering
Application Engineering February 2012 Digital Capacity Control for Copeland Scroll Refrigeration Compressors INDEX Page 1. Introduction... 1 2. Theory of Operation... 1 3. Nomenclature... 1 4. Digital
2004 Standard For Performance Rating Of Positive Displacement Refrigerant Compressors And Compressor Units
2004 Standard For Performance Rating Of Positive Displacement Refrigerant Compressors And Compressor Units ANSI/AHRI Standard 540 (formerly ARI Standard 540) IMPORTANT SAFETY RECOMMENDATIONS ARI does not
Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller
Overview/Modes of Operation Bulletin 150 Smart Motor Controller The SMC-3 is a compact, simple to use, solid-state motor controller designed to operate 3-phase motors. It features a built-in overload relay
Refrigeration System Installation & Operation Manual
Refrigeration System Installation & Operation Manual Manitowoc Foodservice Walk-In Division 2915 Tennessee Avenue North P.O. Box 550 Parsons, TN 38363 Phone: 800-225-9916 www.manitowocfsusa.com 550001058-3
REMOTE RACK SYSTEM OWNERS MANUAL INSTALLATION OPERATIONS - MAINTENANCE
REMOTE RACK SYSTEM OWNERS MANUAL INSTALLATION OPERATIONS - MAINTENANCE 4401 Blue Mound Rd. Fort Worth, TX 76106 Phone: (714) 870-8661 Toll-Free: (800) 833-1106 Fax: (714) 870-6473 www.kairak.com KAIRAK,
Split System Cooling Product Data
Split System Cooling Product Data 4TTB3018-060 1½ 5 Tons PUB. NO. 22-1843-14 Features and Benefits Efficiency up to 13.25 SEER All aluminum Spine Fin coil WeatherGuard fasteners Quick-Sess cabinet, easy
Split System Cooling Product Data
Split System Cooling Product XL16i 1½ 5 Tons PUB. NO. 22-1890-01 Features and Benefits Climatuff compressor Efficiency up to 16.0 SEER and 9.0 HSPF All aluminum Spine Fin coil WeatherGuard fasteners Quick-Sess
Cool Design for Homes and Offices
AIR BLUE AIR BLUE air conditioning Homes Easy to install and use, quiet, attractive, and designed to fit any space: there are Cool Design for Homes and Offices a lot of reasons why Air Blue air conditioners
Condensing unit type EPSILON-ECHOS LE Technical information manual
Condensing unit type EPSILON-ECHOS LE Technical information manual 2 > EPSILON ECHOS Water chiller > EPSILON ECHOS /HP Reversible heat pump > EPSILON ECHOS /ST Water chiller with storage tank and pumps
*.ppt 11/2/2009 12:48 PM 1
Digital Compressor Controller *.ppt 11/2/2009 12:48 PM 1 Copeland Scroll Digital Controller Simple Controller That Enables OEM s To Use Digital Scrolls Relieves OEM From Developing Special Controllers
AIR CONDITIONER INSTALLATION MANUAL
INSTALLATION MANUAL AIR CONDITIONER Please read this installation manual completely before installing the product. Installation work must be performed in accordance with the national wiring standards by
Energy savings in commercial refrigeration. Low pressure control
Energy savings in commercial refrigeration equipment : Low pressure control August 2011/White paper by Christophe Borlein AFF and l IIF-IIR member Make the most of your energy Summary Executive summary
Refrigerant Changeover Guidelines R-22 to R-407C. Leading the Industry with Environmentally Responsible Refrigerant Solutions
Refrigerant Changeover Guidelines R-22 to R-407C Leading the Industry with Environmentally Responsible Refrigerant Solutions Emerson Climate CFC Technologies, Inc. does not advocate the HCFC wholesale
INSTALLATION INSTRUCTIONS Fan Coil Replacement Coil Kit EBX & EBXX
Fan Coil Replacement Coil Kit EBX & EBXX These instructions must be read and understood completely before attempting installation. These instructions covers the installation of replacement coil kit into
SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT
SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT PART 1 - GENERAL 1.1 DESCRIPTION A. The Work specified in this Section consists of designing, furnishing and installing factory-assembled
AIR-CONDITIONER SPLIT TYPE
FILE NO. A08-016 SERVICE MANUAL AIR-CONDITIONER SPLIT TYPE RAS-M10PKVP-E, RAS-M13PKVP-E, RAS-M16PKVP-E, RAS-M18PKVP-E / RAS-M10PKVP-ND, RAS-M13PKVP-ND, RAS-M16PKVP-ND, RAS-M18PKVP-ND / RAS-3M26GAV-E1,
AFE424 SERVICE PARTS
This is the parts list for the AFE. When looking up part numbers, always check the complete model and serial numbers to be certain of ordering the correct parts. The Air Cooled model has also been manufactured
DESIGN STANDARDS SECTION 23 60 00
PART 1 - GENERAL 1.01 Work included: A. Piping, tubing and fittings. B. Piping specialties. C. Special duty valves. D. Refrigerants. E. Chillers. F. Refrigerant monitors. 1.02 General requirements: A.
PRE-ASSEMBLED REMOTE REFRIGERATION SYSTEMS
NOR-LAKE, INCORPORATED 727 Second Street P.O. Box 248 Hudson, Wisconsin 54016 800-955-5253 715-386-2323 866-961-5253 Parts 800-388-5253 Service 715-386-4291 FAX www.norlake.com Split-Pak Pre-Assembled
TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: AW52AL AW64AL AW52AL 387030095 AW64AL 0.8180.463.0 07/05
TECHNICAL DATA & SERVICE MANUAL INDOOR UNIT: AW52AL AW64AL SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. AW52AL 387030095 AW64AL 387030096 0.8180.463.0 07/05 IMPORTANT! Please read before installation
Holdover Plates Transport Refrigeration Systems
Holdover Plates Transport Refrigeration Systems Hercules Manufacturing Company 800 Bob Posey Street PO Box 497 Henderson, KY 42419-0497 1-800-633-3031 270-826-9501 www.herculesvanbodies.com FAX: 270-826-0439
HENRY TECHNOLOGIES - OIL LEVEL REGULATORS (CONVENTIONAL)
HENRY TECHNOLOGIES - OIL LEVEL REGULATORS (CONVENTIONAL) The oil level regulator controls the oil level in the compressor crankcase with a float operated valve. Oil level regulators are designed to attach
SERVICE INSTRUCTION R410A. WALL MOUNTEDtype SPLIT TYPE ROOM AIR CONDITIONER INVERTER. Models Indoor unit Outdoor unit AOU 9RLFW AOU12RLFW AOU15RLS
SERVICE INSTRUCTION SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTEDtype INVERTER Models Indoor unit Outdoor unit ASU 9RLF ASURLF ASU5RLS AOU 9RLFW AOURLFW AOU5RLS R40A CONTENTS. DESCRIPTION OF EACH CONTROL
Technical Training Associates Presents. Commercial Refrigeration Equipment Servicing Part 1
Technical Training Associates Presents Commercial Refrigeration Equipment Servicing Part 1 By Jim Johnson A Practical Approach To The Fundamentals Of Walk-Ins, Reach-In and, Display Cases: Restaurant,
TWE+TTA TWE+TWA 6.25-20 T.R.
TWE+TTA TWE+TWA 6.25-20 T.R. Main features : TWE indoor unit : Convertible cabinet, vertical or horizontal. Adjustable speed pulley-belt drive centrifugal fan motor. Aluminium fin coil with copper-tubes.
System Trouble Shooting Fault Location REFRIGERATION AND AIR CONDITIONING. Fitters notes
System Trouble Shooting Fault Location REFRIGERATION AND AIR CONDITIONING Fitters notes Contents Page Faults on refrigeration systems, general...3 Fault location without the use of instruments...3 Categorisation...3
Accumulators and Receivers
aerospace climate control electromechanical filtration fluid & gas handling hydraulics pneumatics process control sealing & shielding Accumulators and Receivers Catalog C-1, October 2007 Page 2 / Catalog
Appendix - Controllers 179
Version: 200703 Appendix - Controllers 179 -3- -4- -5- -6- -7- -8- 2. Specifications 2.1 Specifications for inverter units item Model AB182ACERA Function cooling heating Capacity kw 5.01.8--5.8 5.22.0---6.2
14. Troubleshooting Guide
14. Guide 14.1 Refrigeration Cycle System In order to diagnose malfunctions, ensure the air conditioner is free from electrical problems before inspecting the refrigeration cycle. Such problems include
NO-FROST CUSTOMER SUPPORT INFORMATION INFORMATION ON THE NO-FROST TECHNOLOGY WHITE GOODS
INFORMATION INFORMATION ON THE TECHNOLOGY The -Frost refrigerators are different from the other static refrigerators in terms of their operational system. In normal refrigerators, in the freezing section,the
Solenoid valves Type EVU
Data sheet Solenoid valves EVU EVU solenoid valves are designed to fit into compact refrigeration systems. Available in direct and pilot operated versions, they can be applied in liquid, suction, and hot
Troubleshooting an Air Conditioning system. R D Holder Eng. Roger D Holder MSME
Troubleshooting an Air Conditioning system R D Holder Eng. Roger D Holder MSME Troubleshooting of an air conditioning system is a step by step procedure. I have found that a 4 step procedure is the best
COMPRESSOR REPLACEMENT PROCEDURE
COMPRESSOR REPLACEMENT PROCEDURE Bard Manufacturing Company Bryan, Ohio 43506 Since 1914...Moving ahead just as planned Manual No.: 2100-003E Supersedes 2100-003D File: Volume I, Tab 1 Date: 06-25-02 Copyright
..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark...
..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark... TIME MARK CORPORATION 11440 EAST PINE STREET TULSA, OK 74116 USA tel 918 438-1220 fax 918 437-7584 www.time-mark.com
SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS
SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS UNIT OBJECTIVES After studying this unit, the reader should be able to explain the purpose of the condenser in a refrigeration system. describe differences
Solenoid Valves and Their Importance in Refrigeration Systems. October 2007
Solenoid Valves and Their Importance in Refrigeration Systems October 2007 Overview Introduction Solenoid valves play an important role within refrigeration and air conditioning systems, controlling the
Hoshizaki America, Inc.
Hoshizaki America, Inc. Stackable Crescent Cuber Models KM-1301SAH/3, SWH/3, SRH/3 KM-1400SWH-M, SWH3-M KM-1601SAH/3, SWH/3, SRH/3 KM-1900SAH/3, SWH/3, SRH/3 KM-2100SWH3, SRH3 KM-2500SWH3, SRH3 KMH-2000SWH/3,
SEWER CHEWER Wastewater / Sludge Grinder Submersible Gearmotor
INSTALLATION, OPERATION AND MAINTENANCE MANUAL For SEWER CHEWER Wastewater / Sludge Grinder Submersible Gearmotor Yeomans Chicago Corporation 3905 Enterprise Court P.O. Box 6620 Aurora, IL 60598-0620 Phone:
SECTION 23 81 43 HEAT PUMPS
SECTION 23 81 43 HEAT PUMPS PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop heat pumps. 1.2 REFERENCES A. American Society of Heating, Refrigerating and Air-Conditioning Engineers:
Model: AC-S13CG x 2. Model No: AC-S13CGx2.doc Version 1.0
Air Conditioner Service Manual 2 3 Model: AC-S13CG x 2 3 Content Technical specification.. 4 Performance curve.5 Outline & dimension of indoor unit..10 Outline & dimension of outdoor unit 11 Exploded view
Failure code manual. content
Failure code manual content 一 wall split AC series 2 二 floor standing AC series. 4 三 portable AC series.. 5 四 dehumidifer 6 五 DC inverter single split series...7 六 DC inverter multi-split series 10 1 一
Series P215PR/RM Direct- and Remote-Mount Pressure-Actuated Condenser Fan Speed Controllers for Single-Phase Motors
European Refrigeration Controls Catalogue Catalogue Section 4 Product Bulletin P215PR/RM Issue 01/03/2013 Series P215PR/RM Direct- and Remote-Mount Pressure-Actuated Condenser Fan Speed Controllers for
COMMERCIAL HVAC CHILLER EQUIPMENT. Air-Cooled Chillers
COMMERCIAL HVAC CHILLER EQUIPMENT Air-Cooled Chillers Technical Development Programs (TDP) are modules of technical training on HVAC theory, system design, equipment selection and application topics. They
Service Guide 12/27/03 TESTING, SERVICE & REPAIR GUIDE (For SH Space Heating Models & RA Water Heating Models)
TESTING, SERVICE & REPAIR GUIDE (For SH Space Heating Models & RA Water Heating Models) WARNING - HIGH VOLTAGE AC electrical circuits are connected to this heater. Do not attempt any service work on the
ASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014
ASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014 Explanation of the refrigeration cycle. Compressors. Benefits and operating characteristics. -Reciprocating
ACS-30-EU-EMDR-10-MOD
Multi-application heat tracing Control and Monitoring in commercial and residential buildings Roof & Gutter de-icing sensor module Technical Information Approvals Module IP rating Ambient operating temperature
INSTALLATION INSTRUCTIONS HOT GAS BYPASS SYSTEM DESIGN MANUAL
INSTALLATION INSTRUCTIONS HOT GAS BYPASS SYSTEM DESIGN MANUAL MODELS: WA/WL44H WA/WLH WA/WL70*H NOTE: Electrical data presented in this manual supersedes any other data f the above listed models. Bard
Scroll Compressor Development for Air-Source Heat Pump Water Heater Applications
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2008 Scroll Compressor Development for Air-Source Heat Pump Water Heater Applications
HEAT PUMP FREQUENTLY ASKED QUESTIONS HEAT PUMP OUTDOOR UNIT ICED-UP DURING COLD WEATHER:
HEAT PUMP FREQUENTLY ASKED QUESTIONS HEAT PUMP OUTDOOR UNIT ICED-UP DURING COLD WEATHER: It is normal for a heat pump to have a build up of white frost on the outside coil during cold damp weather. The
