Conversion From Constant Flow System To Variable Flow
|
|
|
- Kristina Williamson
- 9 years ago
- Views:
Transcription
1 White Paper Conversion From Constant Flow System To Variable Flow By: Tony Egan /29/ S.A. Armstrong Limited 2010 S.A. Armstrong Limited 23 Bertrand Avenue Toronto, Ontario Canada, M1L 2P3 T: F: Armstrong Pumps Inc. 93 East Avenue North Tonawanda, New York U.S.A T: (716) F: (716) Armstrong Holden Brooke Pullen Ltd. Wenlock Way Manchester United Kingdom, M12 5JL T: +44 (0) F: +44 (0)
2 HOW TO SAVE PUMPING ENERGY IN HYDRONIC HVAC SYSTEMS Hydronic HVAC equipment is typically oversized; even for design day conditions. Design day conditions are the design flow and head losses necessary to meet system heat loss calculations based on the listed highest design and lowest temperature periods for the geography. Many times equipment is oversized by design to lessen the risk of an equipment redesign being necessary due to system calculation errors and/or building changes during construction. CONSTANT FLOW SYSTEM TO VARIABLE FLOW SYSTEM SUPPLY VARIABLE FLOW SECONDARY 3-WAY VALVES BECOME 2-WAY VALVES To reduce power costs, it may be decided to change the system from a Constant Flow type to Variable Flow. With 3-way valves installed there is no opportunity to reduce the pump flow, as the valve bypass port is design to open as the load is reduced; resulting in constant pump flow. Should the bypass line valve be closed, the 3-way valves would effectively become a 2-way valves. As the valve then modulates closed to reduce a load coil flow on mild days, the excess flow would no longer be bypassed; thus the loop differential head would increase as the control valve throttles the flow. As this throttling reduces the system flow, pumping power needs are reduced. THE VALUE OF VARIABLE SPEED PUMPS IN VARIABLE FLOW SYSTEMS There are two major decisions to be made to derive full benefits from variable flow systems. The first is whether to make the system design suitable for variable flow and the second is to understand the value of investing in variable speed pumps. Converting the system to variable flow alone while retaining constant speed pumps will save pumping energy; typically 20% to 30%. This energy saving does not come easily however. As the flow from constant speed pumps is throttled by 2-way valves the pressure across the pumps and the control valves increases. This leads to some reduction in the pump life due to higher bearing loads and, perhaps more important- CBV CBV CBV CBV CLOSED VALVE CBV CLOSED VALVE CBV CLOSED VALVE SECONDARY PUMPS CONSTANT SPEED LOAD LOAD LOAD RETURN Page 2 of 12
3 ly, makes the conditioned spaces temperature harder to maintain. As the pressure across control valves increases the valves must close to a greater extent to allow a given amount of water to pass through the load. With higher differential pressures a small change in the valve lift results in a large change in the flow; this can cause hunting of the valve stem position resulting in loss of effective control with fluctuating conditioned space temperatures. Variable speed pumps, combined with a control system that recognizes current system conditions, will reduce pump speed during part-load periods, reducing pressure in the system to a value that satisfies the current load flow requirements with minimum over-pumping. This will reduce pumping energy use to a minimum, extends the life of the pumps and motors and increase the effectiveness of the control valves by reducing the differential pressure across them. BENEFITS FROM CONVERTING CONSTANT FLOW SYSTEMS TO VARIABLE FLOW WITH VARIABLE SPEED PUMPS Reductions in absorbed pumping power that are realised when a heating or cooling system runs under 2-way control with variable speed pumps Reduction in total operating costs, which can often payback the change costs expended in the first year. If the payback is in the first year, then no new capital is required and the conversion costs can be expended out of the revenue budget Armstrong have published an easy to use Opportunity Calculator for easy return on investment calculations which is used to demonstrate to the user/operator in a transparent way the cost savings and payback time for the new equipment Reduced water borne noise, as water velocity is reduced Longer product life, as it is no longer operating at full speed No check valve chatter, as the pumps work on soft start and soft stop under the variable speed control In the UK a newly converted system may help the building qualify for a higher grade Energy Performance Certificate. If the modified building is run through the SBEM energy model software, a reduced input power will be evident In North America a newly converted system will help the building achieve a desired LEED certification Armstrong is able to supply a unique Sensorless control, for duty standby systems, integrated within Vertical In-Line pumps, where the pumping unit will react to the needs of the system without the resources required to acquire, install and wire a remotely mounted system feedback sensor. The pump curve data is mapped into the control software which can precisely place the operating position on the pump curve Page 3 of 12
4 by monitoring the motor power and speed. This enables the unit to react to system condition in precisely the same manner as conventional controls react to a remotely mounted system feedback sensor. VARIABLE FLOW SYSTEM CONVERSION PIPING CONSIDERATIONS A challenge for many hydronic system designers is to correct a misunderstanding by some building owners/operators that a system can be converted to variable speed with all its implied energy and cost savings merely by installing an adjustable frequency drive onto the pump motor. In reality the system piping inside and/or outside of the Plant Room may require modifications. In the following sections 3-way and thermostatic radiator valves are discussed in addition to compensated heating systems with mixing valves, fan coil unit systems and primary pumps. The need for a bypass line on 2-Way valve control systems is also discussed. VARIABLE FLOW SYSTEM CONVERSION RADIATOR SYSTEMS Radiator heating systems are easily converted to variable flow systems. Many radia tors are already fitted with Thermostatic Radiator Valves. (TRV) If not, they can be readily and inexpensively installed. They do not require an electrical supply and can be easily set to provide effective room temperature control. TRVs interrupt the water flow when the room reaches design temperature. A self-regulating variable speed pump such as the Armstrong IVS Sensorless pump will recognise this reduc tion in water flow demand and reduce speed; saving power and energy costs. VARIABLE FLOW SYSTEM CONVERSION - VALVE CONVERSION. 3-way valves are the work-horses for heating and cooling control of conventional constant flow systems. Connected through the Building Automation System (BAS) to thermostats located in conditioned spaces, the 3-way motorised valve either directs the heating or cooling water through the coil in the Air Handling Unit (AHU), or, if the space being served is at normal operating temperature, the flow is directed through the bypass line to the return piping. The bypass line is normally fitted with a regulating valve, set so that the bypass pressure drop matches that of the coil in the AHU. Thus, which ever way the water is being directed, the pump sees little change in flow or head and continues to operate at full speed. Current state of the art variable flow energy saving pumping systems use a 2-way motorised control valve and are installed without a bypass line. Page 4 of 12
5 Air Handling unit Bypass regulating valve Shut this off Close off the bypass 3-way Control valve To convert existing 3-way valve systems to 2-way valve configuration is relatively easy. Simply close the regulating valves in the bypass lines. With the bypass closed, when the 3-way valve modulates attempts to divert the flow around the load and through the bypass, it will restrict the flow rate instead. An Armstrong IVS Sensorless pump will sense this deviation from its control curve and reduce speed until the pre-set control curve, the system resistance curve and the pump performance curve at a new speed converge for the new operating point. Thus power is saved and operating costs reduced. Water velocity is reduced, noise is reduced and equipment time between repairs is extended. This conversion can be applied to most AHUs as they are generally installed with these 3-way valves and have easily accessible bypass lines, fitted with regulating valves. It gets more challenging with systems feeding Fan Coil Units (FCU) as they are often supplied without motorized valves. VARIABLE FLOW SYSTEM CONVERSION - FAN COIL UNITS Fan Coil Units (FCUs) are almost smaller versions of AHUs. They are generally located in the conditioned space being served; typically in a ceiling or wall space. An FCU is served by pipes to feed chilled water and heating water and may have ductwork from the HVAC air system. Older FCU are controlled by a room thermostat and control their output by a combination of a multispeed fan and/or a damper which throttles the air flow into the space being served. Modern fan coil units may be fitted with 4-way control valves, either the rotary type, or the vertical acting type shown in the picture. Both provide an internal bypass from the supply to the return line. Converting these valves to 2-way is not simple and involves getting access to the FCU, of which there may be many, opening them up and chang- Picture courtesy of Actionair Page 5 of 12
6 ing out the valve. This expense will make the payback period very long. An alternative strategy to convert to variable flow systems is required. Variable flow system conversion - Control of return temperature for FCUs One alternative strategy is to leave the FCU and controls in place unchanged and investigate an alternate control opportunity. When the FCU is operating on bypass, the water leaves the FCU at the same temperature that it enters, no heat is being supplied into or taken from the conditioned space as the temperature setting has been reached. This means that pumps can be controlled by measuring the return temperature and can reduce the flow rate/operating speed until the return temperature is back to design return temperature range. To prevent the possibility that certain zones may be underpumped when others zones are satisfied, multiple sensors need be applied to return pipework around the building so that all areas are served. Currently the Armstrong IPS system would serve for pump control for up to 18-zones. Armstrong is further developing a controls package for this application. VARIABLE FLOW SYSTEM CONVERSION PRIMARY PUMPS Primary pumps typically operate at constant speed to produce a constant flow of water through the chiller or boiler and serve a low loss recirculation header. The secondary pumps take water from this low loss header to circulate through heating or cooling building load heat exchangers. As boilers and chillers need minimum flow requirements; secondary pumps have the highest opportunity for energy savings. On the other hand, many primary pumps are over-sized for the low resistance of the system they serve. As a result many are throttled back, which wastes power and money. One solution is to fit a drive to the motor, open up the throttling valve and manually reduce the pump speed until design flow rate is achieved. No automatic controls are required. Speed is reduced and energy is saved for the life of the system. Noise will be reduced if the throttle valve were noisy. Many modern chillers can accept a variable flow through their heat exchangers. Request minimum flow data from the chiller or boiler manufacturer and any controls advice before proceeding with any changes to primary pumps. Armstrong can supply IVS Sensorless rotating assemblies for existing Armstrong VIL pumps, which will make primary pump energy savings a real possibility with little capital cost. VARIABLE FLOW SYSTEM CONVERSION - THE BYPASS Variable flow HVAC systems converted from 3-way control to 2-way valve control Page 6 of 12
7 will find certain challenges when all of the 2-way valves are shut off: 1) The pump may overheat when it continues to run against a closed valve at its minimum speed. This may lead to premature seal failure or thermal shock cracking issues if cold water is suddenly allowed into a hot cast iron casing 2) The temperature of the conditioned water in the headers and remote risers, now stationary, will decay to ambient. This means that when a space eventually requires heating or cooling, there will be a delay as the freshly heated or cooled water from the boiler or chiller finds its way from the plant room, up the riser and along the floor to the terminal. This may cause user discomfort, generating complaints 3) One solution for 2-way motorised valve control systems is to fit a remotely mounted bypass line with a control valve. This, suitably engineered and controlled, will maintain a minimum flow rate in the header, keeping the system pipework at the correct temperature and prolonging pump and pump seal life 4) The bypass flow required is generally between 5 and 10% of a single pump design flow rate. However, as the pump will be operating at the lowest speed required to maintain the minimum system pressure, this flow should be calculated based on minimum speed Best Efficiency Point (BEP) from the variable speed pump curve 5) Several methods of providing a suitable bypass are discussed in the following sections: VARIABLE FLOW SYSTEM CONVERSION - BYPASS CONTROL I One easy method for bypass control that Armstrong recommends is that, when converting a 3-way valve system to 2-way configuration, simple leave the most remote 3-way valve bypass line open on each riser. If there are only few loads in the zone, close the most remote 3-way valve bypass regulating valve 50% so that energy is not wasted with too much conditioned water being returned unused to the chiller or boiler. In this manner, water will only be bypassed when the remote load is satisfied and, as the remote load is typically the least served in the system, this would probably be when all loads are satisfied and bypass flow is required. Other bypass opportunities are discussed in the following sections: Page 7 of 12
8 VARIABLE FLOW SYSTEM CONVERSION - BYPASS CONTROL II Static light load design load flow Source Sub circuit Sub circuit Sub circuit pressure return rise in head at index can operate bypass valve distance Change in head at index circuit can be used to open bypass at low loads This example shows how a bypass valve is installed and controlled for variable speed pumps where the differential pressure controller is located at the pump. The pump in the picture is controlled to produce constant pressure local to the pump in the plant room. This design does not produce the largest value of energy savings, however it can expain the operation of the bypass easily. The diagram below the system schematic shows how the pressure varies around the system. The pressure is highest across the pump (on the left of the diagram) and then reduces as the water flow passes around the system supply piping. The pressure drops again through the index leg (On the right) and continues to fall as it returns to the pump through the return piping. When all the 2-way valves in the system are open, the water velocity is greatest and the friction / pressure losses are the greatest so that the differential pressure at the index leg is lowest. However, at low load, when all the 2-way valves are closed, the friction loss in the supply and return pipework is reduced, causing the differential pressure at the index leg to increase. This change in pressure can be used by a pressure controlled valve to open and allow water to pass through the bypass line, located at the end of the system. The understanding of where the differential pressure controller is located and the concept of friction loss reducing drastically in the distribution piping at low flows is fundamental in understanding Bypass Control sections II, III & IV. VARIABLE FLOW SYSTEM CONVER- SION - BYPASS CON- TROL III DPC The installation illustrated has a differential pressure (DP) controller mounted on the index circuit for highest energy savings. The Source Bypass Differential Pressure Controller load load DPT Page 8 of 12
9 pressure will be constant at the remote point and will vary closer to the pump in the plant room as the loads vary and the pump speed adjusts to match the DP setting and the actual friction loss in the distribution piping. The pressure actuated bypass valve is located in the plant room. Normally closed, it senses the fall in differential pressure in a part load situation and opens, allowing a minimum flow through the pump. While simple and easy to install, it does not provide the minimum flow needed to keep the water in the distribution piping at the operating temperature. VARIABLE FLOW SYSTEM CONVERSION BYPASS CONTROL IV design load Static Invertor flow light load corresponding to minimum pump speed controlled head Source Sub circuit Sub circuit Sub circuit DPT pressure return differential to which head can rise at no load without bypass This bypass example provides a good bypass functionality; however the set up is more complicated. In this case both the bypass and the differential pressure transducer are mounted remote to the pump on the index line. This produces the best energy savings and the pipework maintains the required operating temperature. For this to operate effectively the minimum frequency on the drive control must be set high enough that at low load, where the losses in the distribution piping are small as the flow rate is very low, the pump will operate at its minimum set speed and move left, up the performance curve, increasing the pressure at the index, causing the bypass valve to open. The closed valve pressure of the pump at its minimum frequency must be 25% higher (12% higher frequency) than the control pressure setting of the pressure transducer at the index. distance Change in head at index circuit can be used to open bypass at low loads VARIABLE FLOW SYSTEM CONVERSION - BYPASS CON- TROL IV PUMP OPERATION The above diagram illustrates how the pump performance tracks the load on the system, when set up to open a bypass valve mounted on the index. Beginning at the design operating Page 9 of 12
10 point, the pump will track the quadratic control curve down to the minimum speed setting. As the system 2-way motorised control valves continue to close, reducing the system flow, the controls will not allow the drive to reduce speed further so the operating point must move to the left along the minimum set speed performance curve, causing a rise in pressure as it approaches zero flow rate. This rise in pressure actuates the bypass valve, which will open, permiting the minimum flow to pass through the bypass line. VARIABLE FLOW SYSTEM CONVERSION - PUMP TOPICS If the existing motors are going to be re-used and will be fitted with drives for the first time, checking the suitability of the motor for inverter use with the manufacturer s representative in your area. High voltage spikes from adjustable frequency drives apply more stress to the insulation systems of motors than constant speed application. Motor insulation not suitable for inverter use may break down, causing motor failure. Generally, older motors with Class B insulation may not be suitable for inverter use and modern motors with Class F insulation should be checked also. Generally the motor manufacturer will need to know the drive carrier frequency setting and the cable length between the drive and motor. If in doubt, it makes sense to change out the motor if supplying a new drive. If the pumping unit is an Armstrong vertical in-line type, a new complete rotating assembly, supplied with Sensorless Controls can probably be supplied to fit directly into the existing pump casing. Ask your local Armstrong representative for more information. VARIABLE FLOW SYSTEM CONVERSION - ELECTRICAL TOPICS In a plant room, the conversion work involves fitting the new rotating assemblies to the existing pump bodies or supplying stand-alone controls, Sensorless or not, for exisiting pumps. The existing pump control panels and the contactors inside them are now redundant and may now be removed from site. If the owner prefers to retain the existing control panel as is contains other equipment and is already set up for BAS interface, the power cables can be wired into the new drives instead of the old motors. Trying to fit the drives inside a central panel with long cable to the motors is not the best solution. This can lead to harmonics problems causing noise and motor insulation damage and is to be avoided. Decentralized controls are common today and Armstrong can supply integrated controls on Vertical Inline pumps up to 75hp (55kW) Page 10 of 12
11 VARIABLE FLOW SYSTEM CONVERSION - CONTROLS TOPICS Once the mechanical and electrical installation is complete, the controls company can if necessary or desired connect the controls to the BAS / BMS. They can monitor the drive status and deliver an enable or disable signal. Armstrong drives are compatible as standard or with optional cards to all the usual communications protocols; such as Lonworks, BACnet, Modbus, Metasys N2 or Apogee FLN. VARIABLE FLOW SYSTEM CONVERSION - SUMMARY The VARIABLE FLOW SYSTEM conversion saves money The heating / cooling system works better Building regulation compliance is enhanced Pumps and drives are easily installed - often with no change to pipework Control valve changes are easy to do often closing the bypass line to convert 3 way valve systems to 2 way systems is best done by the building maintenance staff who are familar with their location. The plant room is cleaned up with fewer control panels SENSORLESS PUMP TECHNOLOGY Issues relating to sensors: For best energy savings the sensor needs to installed remotely Mechanical and electrical installation costs incurred Exact position for sensor in system is often difficult to determine If installed remotely loads closer to the pump may be under-pumped when needing flow and remote loads are satisfied Bringing the sensor closer to the pump is expensive and prevents highest energy savings Sensors are prone to failure and are regularly damages or installed incorrectly Placing the DP sensor remotely facilitates greater turndown and hence greater energy savings although some capital and installation costs will be incurred by installing the sensor at a location distant from the pump and controls. To save on direct cable runs back to the drive it is possible to put the signal through the BAS / BMS and bring it back out in the plant room; however cost for extra BAS / BMS points will still be incurred. If the sensor is placed across the most remote load leg and remote loads are satisfied and loads closer to the pump need full flow, the pump speed and back pressure in the piping may not be sufficient to supply full flow to the closer loads; resulting in under-pumping. BSRIA in the UK and others recommend that the sensor be placed 2/3rd the way down the system as a trade off between energy savings and satisfactory system operation. Sensors are electro me- Page 11 of 12
12 chanical devices and can fail in the system. If you read Benefits of variable speed pumps with Sensoless Control on above you may now know that Sensorless Control can do everything a remote sensor can do, without the cost of supplying, installing and wiring the sensor. Ask your local Armstrong representative for more details. VARIABLE FLOW CONVERSION IVS OPPORTUNITY CALCULATOR The calculator is on-line at: The Opportunity Calculator helps the user estimate the potential energy savings in the system and how long the payback period will be. A system lifetime cost savings estimate is also detailed. Simply complete the data input on the first screen; including system flow rate, head losses, operational hours per year, pump efficiency and local electricity cost. The cost of the Sensorless pumping unit is entered later on the IVS pump cost screen. This cost would be the incremental cost of the sensorless unit over a constant speed pump for a new system (Constant pump cost entered on the appropriate screen) or the full cost of the sensorless unit if the unit is to pay for itself soley from energy savings (Use constant speed pump cost of zero). The minimum system pressure defaults to 40% of the design pump head and the partload flow defaults to the ASHRAE 90.1 part load benchmark of 50% of design flow. Each screen takes you step by step through the constant speed continuous power usage and the variable speed power usage under normal part load conditions. Later screens compare the two running costs and calculates the payback. This calculator is quite conservative and estimates the payback from energy savings only. Sensor costs are not included which could easily remove $2,000 ( 1200) from the investment total. These are exciting times with energy saving fruits low-hanging in many hydronic HVAC systems just waiting to be picked. Your local Armstrong representative will be pleased to help you understand the true value of variable speed HVAC pumping and how it can easily reduce your energy costs and pay for the conversion quickly from your own savings. Page 12 of 12
HVAC Processes. Lecture 7
HVAC Processes Lecture 7 Targets of Lecture General understanding about HVAC systems: Typical HVAC processes Air handling units, fan coil units, exhaust fans Typical plumbing systems Transfer pumps, sump
Water cooled chiller plant (cp/vs)
Data Center Water cooled chiller plant (cp/vs) Design Envelope File No: 9.573 Date: december 16, 2014 Supersedes: 9.573 Date: november 14, 2014 design envelope s performance improvements are among the
Data Center. Ultra-Efficient chilled water system optimization. White paper. File No: 9.236 Date: december 03, 2015 Supersedes: new Date: new
Data Center Ultra-Efficient chilled water system optimization White paper File No: 9.236 Date: december 03, 2015 Supersedes: new Date: new Data Center - Ultra-Efficient white paper 3 abstract The primary
Design Guide. Retrofitting Options For HVAC Systems In Live Performance Venues
Design Guide Retrofitting Options For HVAC Systems In Live Performance Venues Heating, ventilation and air conditioning (HVAC) systems are major energy consumers in live performance venues. For this reason,
ENHANCED LABORATORY HVAC SYSTEM
ENHANCED LABORATORY HVAC SYSTEM INTRODUCTION Since the early 1980's the attention to more energy efficient laboratory designs has been on the rise due to the increase in energy cost and the emergence of
- White Paper - Data Centre Cooling. Best Practice
- White Paper - Data Centre Cooling Best Practice Release 2, April 2008 Contents INTRODUCTION... 3 1. AIR FLOW LEAKAGE... 3 2. PERFORATED TILES: NUMBER AND OPENING FACTOR... 4 3. PERFORATED TILES: WITH
Commissioning - Construction Documents (Page 1 of 6)
Commissioning - Construction Documents (Page 1 of 6) A. General Information Climate Zone: Building Type: Conditioned Area (sf): Reviewer's Name: Reviewer's Agency: Note: Design Review for each system/subsystem
SAM HOUSTON STATE UNIVERSITY
PART 1: GENERAL 1.01 General Requirements A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the
Frequently Asked Questions
Frequently Asked Questions System and Valve Basics: 1. Q: What is good cooling coil performance? A: The temperature range is controlled within +/- 0.5 F (0.28 C) off the cooling coil at set point or below.
Liquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED.
Liquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED. Presentation Goals & Outline Power Density Where we have been- where we are now - where we are going Limitations of Air Cooling
Drives and motors. A guide to using variable-speed drives and motors in data centres
Drives motors A guide to using variable-speed drives motors in data centres The power behind the data Private public businesses, from banks to supermarkets, to telecommunications companies internet providers
Centrifugal Fans and Pumps are sized to meet the maximum
Fans and Pumps are sized to meet the maximum flow rate required by the system. System conditions frequently require reducing the flow rate. Throttling and bypass devices dampers and valves are installed
HVAC Systems: Overview
HVAC Systems: Overview Michael J. Brandemuehl, Ph.D, P.E. University of Colorado Boulder, CO, USA Overview System Description Secondary HVAC Systems Air distribution Room diffusers and air terminals Duct
UNIFIED FACILITIES GUIDE SPECIFICATIONS
USACE / NAVFAC / AFCEC / NASA UFGS-23 09 93 (November 2015) ----------------------------- Preparing Activity: USACE Superseding UFGS-23 09 23 (May 2011) UNIFIED FACILITIES GUIDE SPECIFICATIONS References
Continuous flow direct water heating for potable hot water
Continuous flow direct water heating for potable hot water An independently produced White Paper for Rinnai UK 2013 www.rinnaiuk.com In the 35 years since direct hot water systems entered the UK commercial
Applying Pressure Independent Control Valves in H.V.A.C. Systems. A Presentation to: Orange Empire ASHRAE Santa Ana Nov. 17, 2009
Applying Pressure Independent Control Valves in H.V.A.C. Systems A Presentation to: Orange Empire ASHRAE Santa Ana Nov. 17, 2009 1 Introduction I know, as building design consultants, so much of your effort
GAS HEATING IN COMMERCIAL PREMISES
ENERGY EFFICIENCY OFFICES GAS HEATING IN COMMERCIAL PREMISES www.energia.ie www.energia.ie Typically, energy reductions of 10% or more can be made easily through maintenance and low cost improvements.
NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES
NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES 8.1 INTRODUCTION Testing, adjusting, and balancing of HVAC systems can best be accomplished by following a series of systematic procedures. The NEBB TAB
Tour of new eircom Data Centre Blanchardstown by Dervan Engineering Consultants 11 th March 2015
Tour of new eircom Data Centre Blanchardstown by Dervan Engineering Consultants 11 th March 2015 Presentation Outline Mechanical Overview Chillers and Pumps Pipework and Ancillaries In Row Cooling Units
State of the Art Energy Efficient Data Centre Air Conditioning
- White Paper - State of the Art Energy Efficient Data Centre Air Conditioning - Dynamic Free Cooling - Release 2, April 2008 Contents ABSTRACT... 3 1. WHY DO I NEED AN ENERGY EFFICIENT COOLING SYSTEM...
Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia
Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia Prepared for the U.S. Department of Energy s Federal Energy Management Program
Heating and Hot Water Services Controls General Technical Specification
Construction Services Heating and Hot Water Services Controls General Technical Specification Version 1.0 Environment Heating and Hot Water Services Controls General Technical Specification Contents 1.
Advanced Energy Design Guide LEED Strategies for Schools. and High Performance Buildings
Advanced Energy Design Guide LEED Strategies for Schools and High Performance Buildings Today s Presenters Stephen Koontz, LEED AP Energy Services Leader Tampa Bay Trane Allen Irvine General Sales Manager
Automated Commissioning for Energy (ACE) Platform for Large Retail Property. Overview
Automated Commissioning for Energy (ACE) Platform for Large Retail Property $62,900 dollars of energy savings identified during the first 6 weeks Overview The ability to pull large amounts of complex data
Your tool for designing efficient balancing solutions for heating and cooling systems
Application guide Your tool for designing efficient balancing solutions for heating and cooling systems 18 applications Our recommended applications for heating and cooling systems will improve comfort
HVAC Applications. VFD considerations for HVAC systems...
HVAC Applications VFD considerations for HVAC systems... 1 COMMON TERMINOLOGY VFD (VARIABLE FREQUENCY DRIVES) AFC (ADJUSTABLE FREQ. CONTOLLER) ASD (ADJUSTABLE SPEED DRIVES) VSD (VARIABLE SPEED DRIVES)
Building Performance With District Cooling
Reprinting this proof for distribution or posting on web sites is not permitted. Authors may request permission to reprint or post on their web site once the fi nal version has been published. A reprint
Energy and Flow Measurement for Hydronic Systems
Energy and Flow Measurement for Hydronic Systems Presented By: George Szyszko Applications Consultant MCR for ONICON Incorporated Why Measure Thermal Energy? To control something, you must first measure
Hot Water Boilers and Controls Why Condensing Boilers are Different. Presented Oct. 14, 2008 Long Island Chapter, ASHRAE
Hot Water Boilers and Controls Why Condensing Boilers are Different Presented Oct. 14, 2008 Long Island Chapter, ASHRAE H.W. Boilers and Controls Major types of boilers Advantages and disadvantages Resistance
Drives and motors. A guide to using variable speed drives and motors in data centres Meeting your Carbon Reduction Commitment (CRC)
Drives and motors A guide to using variable speed drives and motors in data centres Meeting your Carbon Reduction Commitment (CRC) The power behind the data Private and public businesses, from banks to
Design Consultant (Electrical Services) Design Deliverables and Responsibilities Allocation (Stage E+)
Design Consultant (Electrical Services) Design Deliverables and Responsibilities Allocation (Stage E+) 1. In addition to the information scheduled below, the pre-tender designer is responsible for: (i)
Condensing Boiler Efficiency
Condensing Boiler Efficiency Date: July 17, 2012 PRES E NT ED BY DO N L E O NA RDI LE O N A RD I I NC. HV AC T RAI N I N G & C ON SU LT IN G Concepts 1 The current state of evolution in boiler design 2
The Business Case Annual fuel cost savings of 26% worth more than 28,000 Annual fuel savings of 1.3million kwh Annual CO2 savings of over 245 tonnes
North Lanarkshire Council The Business Case Annual fuel cost savings of 26% worth more than 28,000 The Sir Matt Busby Sports Complex is an important local facility for the people of Bellshill, North Lanarkshire.
ENERGY SAVING STUDY IN A HOTEL HVAC SYSTEM
ENERGY SAVING STUDY IN A HOTEL HVAC SYSTEM J.S. Hu, Philip C.W. Kwong, and Christopher Y.H. Chao Department of Mechanical Engineering, The Hong Kong University of Science and Technology Clear Water Bay,
COMMISSIONING OF HVAC SYSTEMS
FORM CL-01 SYSTEMS / EQUIPMENT INCLUDED : SYSTEM STARTUP CHECKLIST I - PRE - STARTUP INSPECTION EQUIPMENT MOUNTING & SETTING CONTROL, INTERLOCK & POWER WIRING ALIGNMENT OF MOTORS & DRIVES PIPING, CONNECTIONS
Fundamentals of HVAC Control Systems
ASHRAE Hong Kong Chapter Technical Workshop Fundamentals of HVAC Control Systems 18, 19, 25, 26 April 2007 2007 ASHRAE Hong Kong Chapter Slide 1 Chapter 5 Control Diagrams and Sequences 2007 ASHRAE Hong
CGC s Hybrid System Loop Control
verview The CGC Group Hybrid Heat Pump System does NT operate with the same fluid loop temperatures as a conventional reversing Water Source Heat Pump system. The CGC system differs from a WSHP system
Fully Pumped Systems
Fully Pumped Systems (also see the picture gallery and System Basics) The term for any boiler that uses a pump to move all the heat from the boiler to every part of the system is fully pumped. As a rule
HERZ-Thermal Actuators
HERZ-Thermal Actuators Data Sheet 7708-7990, Issue 1011 Dimensions in mm 1 7710 00 1 7710 01 1 7711 18 1 7710 80 1 7710 81 1 7711 80 1 7711 81 1 7990 00 1 7980 00 1 7708 11 1 7708 10 1 7708 23 1 7709 01
INSTALLATION AND OPERATION MANUAL
RCS MODEL ZC4 4 ZONE HVAC INSTALLATION AND OPERATION MANUAL DCN: 141-0020-02 /0/03 INTRODUCTION The 4 Zone HVAC Controller series allows up to 4 standard electronic thermostats to independently control
REAL OPERATING COST SAVINGS FROM RETRO- COMMISSIONING OPPORTUNITIES FOR SAVINGS IN ACADEMIC MEDICAL CENTERS
REAL OPERATING COST SAVINGS FROM RETRO- COMMISSIONING OPPORTUNITIES FOR SAVINGS IN ACADEMIC MEDICAL CENTERS Ken L. Hansen P.E. University of Nebraska Medical Center [email protected] 402-559- 5301 402-630-
KU DESIGN GUIDELINES APPENDIX XVI RECOMMENDED BAS I/O CONTROL POINTS BY EQUIPMENT / SYSTEM
KU DESIGN GUIDELINES APPENDIX XVI RECOMMENDED BAS I/O CONTROL POINTS BY EQUIPMENT / SYSTEM AIR HANDLING UNITS... 1 CHILLERS... 2 COOLING TOWERS... 2 CLOSED LOOP COOLERS... 2 MISCELLANEOUS SUPPLY FANS...
Scope of Work. See www.sei.ie for resources available
HVAC SWG Summary Background Pool energy-efficiency knowledge Increase cost-competitiveness Develop resources aimed at assisting in reducing HVAC energy consumption Address barriers to energy-saving HVAC
SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP
research journal 2013 / VOL 05.01 www.perkinswill.com SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP ARCHITECTURE AND ENGINEERING OF SUSTAINABLE BUILDINGS Current Trends in Low-Energy HVAC Design
APC APPLICATION NOTE #112
#112 Best Practices for Deploying the InfraStruXure InRow SC By David Roden Abstract The InfraStruXure InRow SC (ACSC100 and ACSC101) is a self-contained air conditioner for server rooms and wiring closets.
Why and How we Use Capacity Control
Why and How we Use Capacity Control On refrigeration and air conditioning applications where the load may vary over a wide range, due to lighting, occupancy, product loading, ambient weather variations,
Lesson 36 Selection Of Air Conditioning Systems
Lesson 36 Selection Of Air Conditioning Systems Version 1 ME, IIT Kharagpur 1 The specific objectives of this chapter are to: 1. Introduction to thermal distribution systems and their functions (Section
Heat Trace Fundamentals. Monte Vander Velde, P.E. President, Interstates Instrumentation
Heat Trace Fundamentals Monte Vander Velde, P.E. President, Interstates Instrumentation Contents Introduction... 3 Purpose of Heat Trace... 3 Types of Heat Trace... 4 Steam Trace vs. Electric Trace...
Butterfly Valves PN 6/10/16 for flanged connection
4 136 ACVATIX Butterfly Valves PN 6/10/16 for flanged connection tight-closing VKF46.. VKF46..TS Grey cast iron housing EN-GJL-250 (to DN 300) nodular cast iron housing EN-GJS-400-15 (from DN 350) DN 40
Federal Wage System Job Grading Standards for Air Conditioning Equipment Operating, 5415. Table of Contents
Federal Wage System Job Grading Standards for Air Conditioning Equipment Operating, 5415 Table of Contents WORK COVERED... 2 WORK NOT COVERED...2 TITLES... 2 GRADE LEVELS... 2 HELPER AND INTERMEDIATE JOBS...
Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw
4 937 DESIO Current valve for AC 24 V pulse/pause control of electrical loads up to 30 kw SEA45.1 Use The current valve is used for the control of electric heating elements in heating, ventilation and
News in Data Center Cooling
News in Data Center Cooling Wednesday, 8th May 2013, 16:00h Benjamin Petschke, Director Export - Products Stulz GmbH News in Data Center Cooling Almost any News in Data Center Cooling is about increase
Chilled Water System Commissioning: Variable Primary Flow. John D. Villani, P.E. Associate Grumman/Butkus Associates
Chilled Water System Commissioning: Variable Primary Flow John D. Villani, P.E. Associate Grumman/Butkus Associates AIA Quality Assurance Learning Objectives 1. History of chilled water system configurations
Element D Services Heating, Ventilating, and Air Conditioning
PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer
XE70 SERIES VC SERIES BALANCED HYDRONIC VALVES 2-WAY AND 3-WAY
XE70 SERIES VC SERIES BALANCED HYDRONIC VALVES 2-WAY AND 3-WAY PRODUCT SPECIFICATION SHEET switched off. This results in energy savings during mild weather. Normal control will resume when T3 fails to
UNDERSTANDING CENTRAL HEATING SYSTEMS
UNDERSTANDING CENTRAL HEATING SYSTEMS This advice guide is part of a series of free guides produced by the Association of Plumbing & Heating Contractors Ltd. which provide consumers with essential basic
Energy Efficiency Opportunities in Federal High Performance Computing Data Centers
Energy Efficiency Opportunities in Federal High Performance Computing Data Centers Prepared for the U.S. Department of Energy Federal Energy Management Program By Lawrence Berkeley National Laboratory
1. What percent of a commercial business s energy usage comes from their HVAC system? A. 13% B. 23% C. 33% D. 43% E. 53%
1 1. What percent of a commercial business s energy usage comes from their HVAC system? A. 13% B. 23% C. 33% D. 43% E. 53% 2. How much money do commercial facilities spend per square foot on energy costs
Creating Efficient HVAC Systems
Creating Efficient HVAC Systems Heating and Cooling Fundamentals for Commercial Buildings Heating, ventilating, and air conditioning (HVAC) systems account for nearly half of the energy used in a typical
EHDC. Cooling system for Data Center and server cabinets.
EHDC Cooling system for Data Center and server cabinets. EHDC PEN LP EHDC L is a High Density Cooling module for an pen Loop configuration. It is ideally installed with Enoc Systems cold corridor containment
Link-Up. Solid Fuel Association Guide to Central Heating. www.solidfuel.co.uk
Solid Fuel Association Guide to Central Heating Link-Up Combining solid fuel with other central heating technologies using various methods ranging from a simple link-up to a fully integrated thermal store
The main steam enters the building in the basement mechanical room; this is where the condensate line also leaves the building.
MSV: Square Footage: 24,844 No. of Floors: 1 Year Built: 1963 Type of Use: Lounge and dining area open all night for snacks Steam Water-cooled condenser, 50-Ton York unit with a 6 cylinder-reciprocating
Leveraging the Power of Intelligent Motor Control to Maximize HVAC System Efficiency
Leveraging the Power of Intelligent Motor Control to Maximize HVAC System Efficiency Because HVAC systems comprise a large amount of a building s operating costs, it makes sense to ensure these systems
Ener.co & Viridian Energy & Env. Using Data Loggers to Improve Chilled Water Plant Efficiency. Randy Mead, C.E.M, CMVP
Ener.co & Viridian Energy & Env. Using Data Loggers to Improve Chilled Water Plant Efficiency Randy Mead, C.E.M, CMVP Introduction Chilled water plant efficiency refers to the total electrical energy it
Impact of Control System Technologies on Industrial Energy Savings
Impact of Control System Technologies on Industrial Energy Savings Priyam Parikh Industrial Assessment Center Texas A&M University Bryan P. Rasmussen Industrial Assessment Center Texas A&M University http://farolconsulting.com/?page_id=110
HVAC For Schools How to purchase an HVAC system that meets your school s unique requirements and stays within your budget
A PRIMER Educational HVAC For Schools How to purchase an HVAC system that meets your school s unique requirements and stays within your budget Contents: Introduction: The best HVAC system is durable, reliable
Failure code manual. content
Failure code manual content 一 wall split AC series 2 二 floor standing AC series. 4 三 portable AC series.. 5 四 dehumidifer 6 五 DC inverter single split series...7 六 DC inverter multi-split series 10 1 一
S & P COIL PRODUCTS LTD SPC HOUSE, EVINGTON VALLEY ROAD, LEICESTER. LE5 5LU. Electrical layouts for EC Motors in Fan Convector units
S & P COI PRODUCTS TD SPC HOUSE, EVIGTO VAEY ROAD, EICESTER. E5 5U Guidance Document Electrical layouts for EC Motors in Fan Convector units Hasnain Merchant Richard Meskimmon 4/9/0 This document is intended
OPTIMIZING CONDENSER WATER FLOW RATES. W. A. Liegois, P.E. Stanley Consultants, Inc. Muscatine, Iowa
OPTIMIZING CONDENSER WATER FLOW RATES W. A. Liegois, P.E. Stanley Consultants, Inc. Muscatine, Iowa T.A. Brown, P.E. Thermal Energy Corporation Houston, Texas ABSTRACT Most chillers are designed for a
The HVAC SOLUTION DELIVERING POWER...SAVING ENERGY
The HVAC SOLUTION DELIVERING POWER...SAVING ENERGY PowerGate - Cost effective solutions for F 1 Horsepower Rating 001 1-40 HP (208V) 075 1-75 HP (480V) Input Voltage 2V 208-240V 4V 380-480V Disconnect
Oil and Coolant Circulating Heating System. Model - OCSM
Oil and Coolant Circulating Heating System Model - OCSM Installation & Operation Manual 216280-000 REV 2 Identifying Your System The HOTSTART heating system is designed to heat fluids for use in marine
ASPE Seminar Water Heater Piping Strategies. Presented by Joe Kalarickal, EIT Regional Sales Manager AERCO International
ASPE Seminar Water Heater Piping Strategies Presented by Joe Kalarickal, EIT Regional Sales Manager AERCO International Presentation Overview Water Heater Piping Strategies How to size a water heater?
Data Centre Testing and Commissioning
Data Centre Testing and Commissioning What is Testing and Commissioning? Commissioning provides a systematic and rigorous set of tests tailored to suit the specific design. It is a process designed to
Overview. Introduction Cooling Tower Basics Principles of Operation Types of Cooling Towers Common Applications Design Considerations
Stephen Lowe ASHRAE Hampton Roads Chapter Past President AECOM Design Mechanical Engineering Discipline Manager, Virginia Beach Division Professional Engineer Commonwealth of Virginia, NCEES BSME University
T7560A,B,C Digital Wall Module
T7560A,B,C Digital Wall Module HONEYWELL EXCEL 5000 OPEN SYSTEM BEFORE INSTALLATION All wiring must comply with local electrical codes and ordinances or as specified on installation wiring diagrams. Digital
Demand Based Static Pressure Reset Control for Laboratories
LLC Demand Based Static Pressure Reset Control for Laboratories Laboratories are generally the largest users of energy in any facility. Whether in a pharmaceutical research facility, a university or a
Drives and motors. A guide to using variable-speed drives and motors in retail environments
Drives and motors A guide to using variable-speed drives and motors in retail environments Improving energy efficiency and lowering the carbon footprint Retailers across the UK take their corporate responsibility
Example Retrocommissioning Measure: Opening Throttled Discharge Valves
Opening Throttled Discharge Valves This 21-story building, constructed in 1997, is located in Oregon and contains 589,000 gross square feet of mostly office occupancy. The HVAC system includes six large
RVH/BCH Data Centres Proposals for Surge Protection and Ventilation
REPORT Proposals for Surge Protection and Ventilation BELFAST HEALTH AND SOCIAL CARE TRUST ROYAL GROUP OF HOSPITALS GROSVENOR ROAD BELFAST BT12 6BA Rev. 01 6th September 2013 Table of Contents 1.0 Ventilation
SIRIUX. SINGLE AND DOUBLE HIGH EFFICIENCY CIRCULATORS Heating Air-conditioning OPERATING LIMITS APPLICATIONS. 28 m 3 /h* Heads up to: Flows up to:
OPERATING LIMITS Flows up to: m /h* Heads up to: m C Max operating pressure: bars Temperature range: - à + C Max ambient temperature: + C ND of orifices: à * m /h: parallel operation SIRIUX SINGLE AND
HIGH PERFORMANCE CHILLED WATER SYSTEMS. EarthWise HVAC. EarthWise HVAC High Performance CHW Plants
HIGH PERFORMANCE CHILLED WATER SYSTEMS EarthWise HVAC Simon Ho e: [email protected] 2012 EarthWise HVAC High Performance CHW Plants Low Flow Low Temperature Systems Variable Flow Systems Variable CHW Variable
VC Series Zone Valves BALANCED 2-WAY AND 3-WAY HYDRONIC VALVES
VC Series Zone Valves BALANCED 2-WAY AND 3-WAY HYDRONIC VALVES PRODUCT DATA Design VC Series zone valves consist of: 2-way or 3-way valve housing available with various connection ends Spindle and cartridge
GE Energy Industrial Solutions. New. AF-6 Series Drives. Built-in features Built-in simplicity. GE imagination at work
GE Energy Industrial Solutions New AF-6 Series Drives Built-in features Built-in simplicity GE imagination at work AF-6 Series Built-in simplicity speeds set-up The removable keypad, common to all AF-6
VARIABLE VOLUME / VARIABLE SPEED SYSTEMS APPLICATIONS
Bulletin D-120B Pages D120-115 to D120-118 VARIABLE SPEED PRIMARY CHILLED WATER PUMP CONTROL WITH TWO WAY VALVE DIRECT RETURN SYSTEM DESCRIPTION: The volume of water supplied to the system is varied in
AABC Specifications for Testing and Balancing HVAC Systems
AABC Specifications for Testing and Balancing HVAC Systems The Associated Air Balance Council (AABC) Total System Balancing Specifications for HVAC Testing, Balancing and Performance Verification TOTAL
THERMAL ANALYSIS OF A DATA CENTRE COOLING SYSTEM UNDER FAULT CONDITIONS
Eleventh International IBPSA Conference Glasgow, Scotland July 27-30, 2009 THERMAL ANALYSIS OF A DATA CENTRE COOLING SYSTEM UNDER FAULT CONDITIONS Michaël Kummert 1, William Dempster 1, and Ken McLean
IDEA Presentation SMALL CAMPUS CHILLED WATER PLANT OPTIMIZATION.
IDEA Presentation SMALL CAMPUS CHILLED WATER PLANT OPTIMIZATION. Pre-Project Details Hawaiian Community College Campus consisting of 16 individual buildings totaling 308,000 sq.ft of conditioned space.
Product Data Bulletin
Product Data Bulletin Adjustable Frequency Drives and HVAC Systems An Application Guide September, 1994 Raleigh, NC, U.S.A. INTRODUCTION All buildings pose the same problem: how to heat or cool the air
Glossary of HVAC Terms
Glossary of HVAC Terms Heating, Ventilation and Air Conditioning (HVAC) is a major sub- discipline of mechanical engineering. The goal of HVAC design is to balance indoor environmental comfort with other
UNIVERSITY OF MISSOURI 23 0000 - Heating Ventilating and Air-Conditioning (HVAC) March 2015.01
GENERAL: This section provides general standards for overall sizing and design of Heating, Ventilating, and Air Conditioning (HVAC) systems. Other sections contain specific standards for each system per
Data Center Rack Level Cooling Utilizing Water-Cooled, Passive Rear Door Heat Exchangers (RDHx) as a Cost Effective Alternative to CRAH Air Cooling
Data Center Rack Level Cooling Utilizing Water-Cooled, Passive Rear Door Heat Exchangers (RDHx) as a Cost Effective Alternative to CRAH Air Cooling Joshua Grimshaw Director of Engineering, Nova Corporation
Case Study -Sandy Grove Middle School First Net Positive Energy P3 School In North Carolina
Case Study -Sandy Grove Middle School First Net Positive Energy P3 School In North Carolina Public-Private Partnership (P3) Government - provides incentive(s): transfer of asset (land), one time grant,
presents Hydraulic Separation Beyond Primary / Secondary Piping
presents Hydraulic Separation Beyond Primary / Secondary Piping This Webinar is exclusively sponsored and the property of Caleffi Hydronic Solutions. All rights reserved. October 2007 Modern compact boilers
Heating Water by Direct Steam Injection
Heating Water by Direct Steam Injection Producing hot water by direct steam injection provides a solution where large volumes of hot water at precise temperatures are required, and where energy and space
RVL470. Heating Controller. Building Technologies HVAC Products. Series B
2 522 Heating Controller Series B RVL470 Multifunctional heating controller for use in residential and non-residential buildings; suitable for weather-dependent flow temperature control of heating zones
HVAC SYSTEM (AUTO A/C) (DIAGNOSTICS) AC
HVAC SYSTEM (AUTO A/C) (DIAGNOSTICS) AC Page. Basic Diagnostic Procedure.... General Description...3 3. Electrical Components Location...6 4. A/C Control Module I/O Signal...8 5. Self-diagnosis...0 6.
Vaillant s plain English guide to. simple, concise and precise
Vaillant s plain English guide to simple, concise and precise Introduction Contents Installing a new boiler 05 Servicing and repairing 13 What s a diverter valve? Why do you need a TRV? And happens when
POLK STATE COLLEGE CHILLER PLANT EVALUATION WINTER HAVEN, FLORIDA APRIL 2, 2014. C arastro & A ssociates, C&A# 5747
POLK STATE COLLEGE WINTER HAVEN, FLORIDA CHILLER PLANT EVALUATION APRIL 2, 2014 C&A# 5747 C arastro & A ssociates, c o n s u l t i n g e n g i n e e r s inc. 2609 W. De Leon Street, Tampa, Florida 33609
