AORC Technical meeting 2014

Size: px
Start display at page:

Download "AORC Technical meeting 2014"

Transcription

1 http : // B AORC Technical meeting kv Long Distance Underground HVAC Cable Circuit NAVEED RAHMAN Nexans Olex Melbourne, Australia SUMMARY In 2009, the Victorian state government decided to a build an AUD 3.5 billion water desalination plant east of Melbourne on the coast in Wonthaggi, Victoria. The desalination plant was designed to deliver up to 150 billion litres of desalinated water per year and required 165MW of power to operate the plant. After evaluating the possible options, e.g. building a Power Generating Plant, transferring electricity via Overhead Lines, DC Link to supply electrical energy to the desalination plant, it was decided to supply the power using a single 220kV AC underground cable system, which makes it the world s longest 220kV HVAC land cable link. Nexans Olex was awarded the contract to design, manufacture and supply of 220kV underground cable and accessories together with jointing and testing services from Cranbourne Terminal Station (CBTS) to the Wonthaggi Desalination Plant (WDP). The 220kV cable route length is approximately 88km. Based on system design studies; it was decided to build two reactive compensation stations between Cranbourne and the desalination plant, namely Northern Reactive Compensation Station (NRCS) and Southern Reactive Compensation Station (SRCS). This resulted in dividing the entire route into 3 sections as follows: Section Number Section Name Section Length (km) Required Rating (A) Cable Size 1 CBTS to NRCS mm² Cu 220kV Installation Arrangement Laid Direct in Ground in Trefoil 2 NRCS to SRCS mm² Cu 220kV Ducted Trefoil 3 SRCS to WDP mm² Cu 220kV Ducted Trefoil The project works were successfully completed in April 2012 and the desalination plant was commissioned in December Almost all HV underground cable installation projects have unique challenges. This paper presents the Design, Supply & Installation challenges that were encountered during design and construction phase of the new 220kV underground cable circuit delivering power supply to the Wonthaggi Desalination Plant. KEYWORDS 220kV AC Land Cable Link, Underground HV Cable Circuit, System Design, Reactive Compensation, Direct in Ground, Ducted Installation, Cable Installation, Construction Works. naveed.rahman@nexans.com

2 1. INTRODUCTION In 2009, the Victorian state government decided to build a water desalination plant east of Melbourne on the Bass Coast in Wonthaggi, Victoria. The plant was designed to deliver up to 150 billion litres of desalinated water per year to Melbourne. The nearest 500kV and 220kV substation to the desalination plant was approximately 88km North- West in the vicinity of Cranbourne, Victoria. To supply the required power to operate the plant, various options were considered, i.e. Building a dedicated power generation plant which was deemed uneconomical for such a limited power requirement and without a direct energy source. Transmission of electrical power via overhead line (OHL) that was publicly unacceptable. Transmission of AC electrical power via underground cables (UGC) Underground DC cable link was also considered After evaluating the possible options to transfer the required energy to the desalination plant, the State of Victoria decided to supply the power using a single 220kV AC underground cable system. This makes it the world s longest 220 kv HVAC land cable link and it is supplying 165MW of load to the Wonthaggi Desalination Plant. The Victorian government awarded the contract to Aquasure to build the desalination plant and associated infrastructure. Aquasure then subcontracted the construction works to Thiess Degremont Joint Venture (TDJV). TDJV awarded the contract to Nexans Olex to design, manufacture and supply 220kV underground cable circuit from Cranbourne Terminal Station (CBTS) to the Desalination Plant Terminal Station (WDP) in Wonthaggi, Victoria. Nexans Olex contract Scope of Works consisted of: Carrying out the detailed system design Supply and delivery of approx 270km of 220kV XLPE cable Supply and delivery of approximately 235 cable accessories (220kV Joints & Terminations) Supervision of cable installation works Supply and installation of DTS system, which included 3 DTS Units Jointing & Terminating works Carrying out pre-commissioning tests Design verification of as-built cable circuit ratings Project Mile Stones (Key Dates): Contract Signed on: 18 th December 2009 Cable installation completed: August 2011 Jointing works completed: October 2011 Testing completed: November 2011 Cable circuits energised on: o Section 1: 3 rd December 2011 o Section 2: 18 th December 2011 o Section 3: 3 rd March 2012 Practical Completion achieved on: 4 th April 2012 Almost all HV underground cable installation projects have unique challenges, but this being a long underground cable system, special considerations were necessary to design and construct the 88 km of cable system for the desalination plant: Ferranti effect: Cable and accessories insulation design was based on 275 kv to cope with the possible increase in voltage at the receiving end during light load conditions. System design, reactive compensation, losses, harmonics. Supply & logistic issues delivery of 270 km of 220kV cable, 235 joints & terminations, link boxes, bonding & earthing cables, 3 DTS units, optical fibre cables & joints. FAT (cable drums tested at a higher voltage than IEC), sample tests & commissioning tests. Jointing and Termination works. Narrow easement shared with the water transfer pipeline. Constructability and associated civil works. Coordination with major pipeline civil works contractors in restricted corridor widths in widely varying topography. Availability of required resources including qualified jointers to meet the compressed construction timeframes. Project management. 2. PROJECT CHALLENGES 2.1. DESIGN CHALLENGES Due to compressed construction program the original design was carried out as a desk top study based on preliminary cable route survey without carrying out route proving etc. Consequently design modifications & adjustments were required during construction stage as per site conditions. Nexans Olex design team performed these design modifications in a timely manner as required to meet the project completion date. 1

3 Deep crossing designs exact details/long section drawings were developed by the customer and made available to Nexans Olex during construction works. Nexans Olex prepared and verified designs for these deep crossings on a case-by-case basis during construction works. During construction phase, high native soil TR values were measured in sections 1-3 of CBTS to NRCS Circuit, which required adjustment to the system design to maintain circuit ratings. Modifications to other special crossing which needed to meet third party requirements were verified by Nexans Olex in a timely manner, e.g. railway crossings, Melbourne Water crossings, various road-crossing. Adjustments to Joint Bay locations due to site conditions and rebalancing the circuits were also carried out during construction works. Providing Safe Work Method Statements (SWMS) to work under induced voltage conditions in 500kV transmission lines easement SUPPLY CHALLENGES Supply of 270 km of 220 kv cables within 11 months was a challenging task for a single supplier. Nexans Olex supplied the cables from manufacturing Plants in Australia and Belgium. Supply of 235 cable accessories to complete the project in compressed timeframes. Supplying additional cable drums and accessories due to various reasons, e.g. cable damaged during transportation, cable damage during installation, design changes as the project progressed INSTALLATION CHALLENGES Wet weather conditions, site access issues, monitoring multiple sites along 88 km cable route. Verifying cable pulling methodologies and providing pulling tension calculations. Accelerating jointing works by maintaining adequate qualified jointing resources on site to meet the project completion dates. Completing pre-commissioning tests on time, adhering to strict safety requirements and coordinating with numerous contractors. 3. DESIGN CONSIDERATIONS Ferranti effect results in increased voltage at receiving end compared to the sending end voltage in long transmission lines. This occurs when transmission line is either lightly loaded or load is disconnected. Ferranti effect was considered during design. The 220kV cable system is designed to operate at 275kV to cope with the possible increase in voltage at the receiving end during light load conditions. High Voltage Insulated cables are predominantly capacitive in nature. Due to the presence of this capacitance, a current (charging current) will flow through the insulation to the ground via the cable metallic sheath. For a given cable, the total charging current required from the source is proportional to the length of the transmission line. The effect of charging current is generally neglected for short underground transmission lines. However for long underground transmission lines the impact of charging current is considerable and this should be taken into account as it limits the active power transmission capacity. Load flow and system studies suggested providing 2 compensation stations, NRCS & SRCS, along the cable route as per the single line diagram below (Fig 1). Fig. 1 Single line diagram for the 220kV transmission line BP = Booster Pump Station, DPTS = Desalination Plant 3.1. REACTIVE POWER COMPENSATION When designing a transmission or distribution system, designers must take into account the load requirement and the inductive and capacitive elements of the cable circuit, which consume reactive power. This requires the reactive compensation to minimise the charging current component in the cable so the conductor is efficiently used to transfer the power required by the load. To achieve this it is necessary to balance various factors to optimise the management of the reactive power, e.g. optimise capital investment in plant for reactive compensation, minimise system losses to maintain system security and stability. It should be noted that the capacitive charging current will almost overload the cable by itself without carrying any load current. 2

4 Figure 2 shows the typical variation of active power transmission capability against the length of the circuit PRELIMINARY DESIGN Due to the extremely fast track nature of the project, the preliminary design was carried out as a desktop study based on preliminary cable route survey without carrying out route proving and verifying other actual installation conditions. Fig. 2 Variation of active power transmission capability vs circuit length for a given circuit System studies carried out by TDJV had identified two worst case circuit operating scenarios. First scenario was 110% of system voltage at CBTS (sending end) with no reactive compensation at both NRCS and SRCS. Second scenario was 90% of system voltage at CBTS (sending end) with reactive compensation at both NRCS and SRCS at 100% (See Table 1 for details). Studies done by TDJV suggested 500mm² copper cables for CBTS to NRCS section and 400mm² copper cables for cable sections between NRCS & WDP via SRCS to carry both active and reactive power under various cases. Description System Voltage at CBTS Item (Unit) Case 1 Case 2 Comment Un (%) % of Un Load at NRCS BP (MW) Power factor 0.95 Reactive Compensation at NRCS Reactive Compensation at SRCS Load at Desalination Plant Q (%) % of Q Q (%) % of Q DP (MW) Power factor 0.95 Table 1: Most Onerous Cable Operating Scenarios Nexans Olex then carried out detailed load flow studies to verify that the proposed cable system design fulfils the most onerous cable operating scenarios. Load flow studies confirmed that the cable circuits will have the following maximum currents in the cable. Cable Maximum Designed Continuous Current Carrying Capacity, A 500 mm² Cu 220 kv XLPE Cable mm² Cu 220 kv XLPE Cable 475 Consequently design adjustments had to be made during construction works to suit site conditions, e.g. deep crossings, high native soil TR values were found, design of special crossings gas pipes, water mains road crossings, creek crossings, relocation of joint bays OVERALL SYSTEM DESIGN The cable route length between the CBTS and WDP is approx 88 km, which is divided into 3 cable sections / circuits as follows: SECTION 1 - CTBS to NRCS Route length of approximately 13 km 500mm² Cu 220 kv cable Cable supplied by Nexans Belgium plant 3 major cross bonding & 9 minor sections. 3 minor sections (or 1 major section) have 2 sub-sections connected by straight joints Total of 12 sections and each section length of approx 1000 metres. SECTION 2 - NRCS to SRCS Route length of approximately 37 km. 400mm² Cu 220 kv cable Cable supplied by Nexans Australia Plant 5 major cross bonding & 15 minor sections. Each minor section has 2 sub-sections connected by straight joints Total of 30 sections and each section length of approx 1235 metres. SECTION 3 - SRCS to WDP Route length of approximately 38 km. 400mm² Cu 220 kv cable Cable supplied by Nexans Australia Plant 5 major cross bonding & 15 minor sections. Each minor section has 2 sub-sections connected by straight joints Total of 30 sections and each section length of approx 1270 metres. Each section was economically optimised by utilising straight through joints in minor cross bonding sections. This eliminated the necessity of link boxes / pits and concentric bonding cables by half. 3

5 3.4. THERMO-MECHANICAL FORCES Excessive thermo-mechanical forces on cable joints and sealing ends during service conditions can lead to pre-mature failure of accessories during service life of an underground cable system. Thermomechanical behaviour of a high voltage cable system basically depends on thermo-mechanical properties of the cable, type of installation (rigid, flexible or a combination of both) and temperature variations. Table 3: Maximum EMF at ground level The thrust force generated by a cable can be calculated by the formulas presented in Cigre publication TB194. To reduce these thrust forces, Nexans Olex designed and optimised the snaking and clamping arrangement outside the joint bays to minimise the thermal expansion / thrust force of cable on the joints. See below typical snaking arrangements. Fig 4: Maximum EMF level for 500mm² Cable Trefoil Touching Fig. 3 Typical Snaking arrangement at Joint Bays 3.5. INDUCED VOLTAGE AND ELECTRO- MAGNETIC FIELD CALCULATIONS The cable system was designed to keep the induced sheath voltage within acceptable limits. Detailed analysis and calculations were performed for both normal operation and fault condition as follows. Fig 5: Maximum EMF level for 400mm² Cable Trefoil Touching ARPANSA is the Australian Radiation Protection and Nuclear Safety Agency 3.6. CABLE TEMPERATURE MONITORING Table 2: Typical Induced voltages To minimise the EMF levels a trefoil arrangement of cable/ducts installation method was utilised. EMF calculations were carried out for the various cable arrangements used for the cable route. Calculations were based on the design continuous loads. Distributed Temperature Sensing (DTS) system was designed and installed to monitor the cable temperatures between CBTS and WDP. Nexans Olex installed 3 DTS units at NRCS, SRCS and WDP and a dedicated single mode fibre cable to measure the temperature of entire cable route. Fig. 6 DTS Unit arrangement 4

6 installation to ensure that curing temperatures and pumping pressures were controlled so as not to damage the PE ducts. Figure 7: Typical conductor temperatures versus fibre temperature Rise (established using Nexans Olex finite element program Sirolex Fig 8: Typical Micro-Tunnel arrangement 4. INSTALLATION CONSIDERATIONS Civil & cable installation works were carried out by TDJV & their contractors. Nexans Olex monitored the cable installation works to ensure that the cable was installed as per design requirements. Installing 88 km route of 220kV cable required optimal utilisation of the available resources and innovative project management. The typical cable section length between two consecutive joint bays was between 1100m to 1300m. Pulling tension calculations were carried out for each cable section and combination of nose (winches) and bond pulling (caterpushers) techniques were utilised to ensure that the maximum cable pulling tension and the maximum side wall pressure did not exceed the recommended limits. The direction of pulling was determined after giving due consideration to the specific route profile and location of joint bays. During cable installation the pulling tension was monitored and recorded for future reference. Fig 9: Deep crossing under bore 4.1. DEEP CROSSINGS There were a number of locations where 220kV power cables had to cross an existing service or a river. These crossings were classified as deep crossings. Five deep crossings were done by utilising the micro tunnel installation technique. Micro-tunnelling is the special installation technique utilising a small horizontal bore (approx 1.5 to 2.0m diameter) sleeved with a concrete pipe and containing the cable ducts in the desired arrangement. The micro-tunnel was filled with grout encasing the ducts, this was done by filling the void between the bore sleeve and cable ducts with a specially designed thermal backfill material to maintain cable ratings. The material in nature was low shrinkage and pumpable and of low viscosity making it easy to fill. Appropriate measures were taken during Fig 10: Deep crossing under bore filled with grout Due to the depth, special considerations were given to the thermal properties of the surrounding soils. At each crossing, core samples were taken (max depth & half depth) to establish TR values including moisture content to finalise design ratings / installation details / trench cross-section WORKING UNDER EXISTING 500KV OHL The 220kV cable section between CBTS & NRCS shared the same easement with an existing 500kV overhead transmission line, which caused safety concerns. In some cases the induced voltages were 5

7 measured up to 120V, which was considered as a safety hazard for the jointers and the other project site staff. A safe working method statement (SWMS) was prepared to outline the additional safety precautions required during jointing/terminating works, e.g. isolating the far end of the cables during jointing, cables earthed during jointing works, using insulating mats, use of appropriate (7.5kV) insulating gloves during jointing works JOINTING AND TERMINATION WORKS Nexans Olex installed approx 235 joints and terminations within 18 months utilising 4 jointing teams. Special consideration was given to fatigue, health and safety issues when performing repetitive work for a long time, such as the repetitive installation of the same type of joint PRE-COMMISSIONING TESTING The following tests were performed as part of the Pre-Commissioning Tests: Visual Inspection. Sheath Integrity Test (Sheath IR). Main Insulation IR Test. Phase sequence check. Cross Bonding Verification test. SVL test. Positive and Negative Sequence Impedance test. High Voltage AC test 24 hour soak test at system voltage was carried out CONCLUSION LESSONS LEARNT On successful completion of this project, we believe that there are some valuable lessons learnt during the design and project execution, which should be considered when planning such large projects with compressed programs. Allow adequate time for design approvals from all stakeholders. Maintain adequate design resources during project execution to provide solutions for unforeseen events and services found during construction. Maintain adequate site resources to conduct QA Audits of multiple sites during construction works. Cable installation methodologies and installation equipment should be tested prior to commencement of cable installation works on site. Implement a project management system, which controls and records all critical aspects of the project and achieves better communication between various contractors and client staff. Acknowledgment The author would like to acknowledge that this project using the latest developments in cable and installation design technology was successfully implemented through the significant co-operation between various contractors and the client s project management team. REFERENCES [1] Nexans Olex, Design Report for 220kV Underground T/L Cranbourne Terminal Station to Victorian Desalination Plant, 2010 [2] Technical specification for 220kV Underground T/L Cranbourne Terminal Station to Victorian Desalination Plant, 2009 [3] Nexans Olex, System Design and Verification Report for 220kV Underground T/L Cranbourne Terminal Station to Victorian Desalination Plant The successful completion of this project demonstrates that underground HVAC cable system is also a viable option for long distance power transmission. It is important to establish the requirements of reactive power compensation for long distance transmission system. Site access requirements should be clearly understood to avoid delays during project execution. The safety regulations and the legal requirements should be carefully considered by the contractors as they can vary from one state to another in Australia and in other countries. 6

HV Submarine Cable Systems Design, Testing and Installation

HV Submarine Cable Systems Design, Testing and Installation HV Submarine Cable Systems Design, Testing and Installation CIGRE Ireland Technical Seminar 6 th October 2010 Robert Donaghy Senior Consultant Engineer, ESB International Presentation Overview Applications

More information

Undergrounding high voltage electricity transmission. The technical issues

Undergrounding high voltage electricity transmission. The technical issues Undergrounding high voltage electricity transmission The technical issues This is an interactive PDF document with clickable links from the contents to all sections and back and also to URL and email links.

More information

PB POWER ISLAND OF IRELAND CAVAN-TYRONE AND MEATH-CAVAN 400KV PROJECTS PRELIMINARY BRIEFING NOTE OVERHEAD AND UNDERGROUND ENERGY TRANSMISSION OPTIONS

PB POWER ISLAND OF IRELAND CAVAN-TYRONE AND MEATH-CAVAN 400KV PROJECTS PRELIMINARY BRIEFING NOTE OVERHEAD AND UNDERGROUND ENERGY TRANSMISSION OPTIONS ISLAND OF IRELAND CAVAN-TYRONE AND MEATH-CAVAN 400KV PROJECTS PRELIMINARY BRIEFING NOTE OVERHEAD AND UNDERGROUND ENERGY TRANSMISSION OPTIONS FEBRUARY 2008 PB POWER PB Power Page i EXECUTIVE SUMMARY General

More information

ENERGY NETWORKS ASSOCIATION. Electricity Industry EMF Measurement Protocol for High Field Areas

ENERGY NETWORKS ASSOCIATION. Electricity Industry EMF Measurement Protocol for High Field Areas ENERGY NETWORKS ASSOCIATION Electricity Industry EMF Measurement Protocol for High Field Areas Contents 1 Introduction 1.1 Background 1.2 High Field Areas 2 High Field Area - Generation Businesses 2.1

More information

Gulf Cable & Electrical Ind. Co.

Gulf Cable & Electrical Ind. Co. CONTENTS INTRODUCTION PRODUCT RANGE I PRODUCT DATA TABLES XLPE INSULATED 600/1000V CABLES Two Core Cables CU/XLPE/PVC/LC/PVC/SWA/PVC 1 Three Core Cables CU/XLPE/PVC/LC/PVC/SWA/PVC 2 Four Core Cables CU/XLPE/PVC/LC/PVC/SWA/PVC

More information

Utility Services. Increasing efficiency across the utilities network

Utility Services. Increasing efficiency across the utilities network Utility Services Increasing efficiency across the utilities network Sustainable engineering and design consultants Specialising in complex, infrastructure, process and built environments // UTILITY SERVICES

More information

EDS 02-0027 11KV TRIPLEX CABLE

EDS 02-0027 11KV TRIPLEX CABLE THIS IS AN UNCONTROLLED DOCUMENT, THE READER MUST CONFIRM ITS VALIDITY BEFORE USE Document Number: EDS 02-0027 ENGINEERING DESIGN STANDARD EDS 02-0027 11KV TRIPLEX CABLE Network(s): EPN, LPN, SPN Summary:

More information

environment briefing02

environment briefing02 PRODUCED BY THE SAFETY, HEALTH & ENVIRONMENT GROUP OF THE ENERGY NETWORKS ASSOCIATION - JULY 2006 environment briefing02 transporting electricity Overhead Lines or Underground Cables? Introduction The

More information

ELECTRICAL INSULATION TESTING OF HV EQUIPMENT UP TO 33kV

ELECTRICAL INSULATION TESTING OF HV EQUIPMENT UP TO 33kV 1. SCOPE This document details PowerSystems requirements for electrical testing of HV Equipment up to and including 33kV. 2. ISSUE RECORD This is a Reference document. The current version of Controlled

More information

CHAPTER VIII LINE PLANT SYSTEM COMMUNICATION THROUGH RE CABLE

CHAPTER VIII LINE PLANT SYSTEM COMMUNICATION THROUGH RE CABLE CHAPTER VIII LINE PLANT SYSTEM COMMUNICATION THROUGH RE CABLE 8.1 SYSTEM 8.1.1 Armoured, screened underground cables are used for control communication in electrified areas to limit induction effect. 8.2

More information

Respecting the environment

Respecting the environment MAIN FEATURE CHAPTER I RESEARCH WITH AN EYE ON THE FUTURE Respecting the environment Low power losses and a lesser visual impact on the landscape make Gas-Insulated Lines (GIL) a very environmentally friendly

More information

An Introduction to High Voltage Direct Current (HVDC) Underground Cables

An Introduction to High Voltage Direct Current (HVDC) Underground Cables Page 1 An Introduction to High Voltage Direct Current (HVDC) Underground Cables Brussels, 10 October 2011 An Introduction to High Voltage Direct Current (HVDC) Underground Cables Page 2 Table of content

More information

AMSC s Superconductor Cable Technologies for Electric Utilities

AMSC s Superconductor Cable Technologies for Electric Utilities International Workshop 2014 AMSC s Superconductor Cable Technologies for Electric Utilities Michael Ross, P.E. Managing Director of Superconductor Power Systems AMSC Corporate Facts Headquartered in MA,

More information

Network Standard Advice No. 1420C 9/6/2011

Network Standard Advice No. 1420C 9/6/2011 Network Standard Advice No. 1420C 9/6/2011 TO: Customers, Service Providers and Ausgrid Staff. Advisory Note on Changes to the Use of 11kV Cable Types. Introduction This Network Standard Advice (NSA) provides

More information

State, trends and evolutions of HV/EHV power cables systems and contributions of SC B1 to their ongoing progress

State, trends and evolutions of HV/EHV power cables systems and contributions of SC B1 to their ongoing progress 0611-048-Mep229 12/12/06 6:44 Page 22 State, trends and evolutions of HV/EHV power cables systems and contributions of SC B1 to their ongoing progress Reinhard SCHROTH, Chairman of SC B1 2002-2006 High

More information

High Voltage Systems. Today. The history of cables

High Voltage Systems. Today. The history of cables High Voltage Cables High Voltage Systems Today Prysmian Cables and Systems B.V. is part of the Prysmian Group, a leading player in the industry of high-technology cables and systems for energy and telecommunications,

More information

MEASUREMENTS OF THRUST LOAD IN CABLE SYSTEMS SEMI-RIGIDLY INSTALLED IN DUCT / MANHOLE STRUCTURES

MEASUREMENTS OF THRUST LOAD IN CABLE SYSTEMS SEMI-RIGIDLY INSTALLED IN DUCT / MANHOLE STRUCTURES MEASUREMENTS OF THRUST LOAD IN CABLE SYSTEMS SEMI-RIGIDLY INSTALLED IN DUCT / MANHOLE STRUCTURES Riccardo BODEGA, Prysmian Cables and Systems, The Netherlands, riccardo.bodega@prysmian.com Henk GEENE,

More information

M. GELDON Brugg Kabel CZ. Ing. D. RÚŽEK PREdistribuce. Switzerland Czech Rep. Czech Rep. Czech Rep., Switzerland Germany

M. GELDON Brugg Kabel CZ. Ing. D. RÚŽEK PREdistribuce. Switzerland Czech Rep. Czech Rep. Czech Rep., Switzerland Germany 21, rue d Artois, F-75008 PARIS Paper number CIGRE 2012 http : //www.cigre.org 6 characters (to be provided later) Correlation between calculated transmission capacity and actual one D. WALD* Eifelkabel

More information

Cable Consulting International

Cable Consulting International Cable Consulting International Brian Gregory BSc, CEng, MIEEE, FIEE Technical Director www.cableconsulting.net Alan Williams BSc, CEng, MIEE Senior Consultant 1 FEASIBILITY STUDY for 500 kv AC UNDERGROUND

More information

Submarine Power Cables. State-of-the-art production facility, more than 100 years of experience and reference installations around the world.

Submarine Power Cables. State-of-the-art production facility, more than 100 years of experience and reference installations around the world. Submarine Power Cables State-of-the-art production facility, more than 100 years of experience and reference installations around the world. Reliable submarine power cables ABB is one of the world s most

More information

Removal of EP 20 10 00 02 SP High Voltage Cable

Removal of EP 20 10 00 02 SP High Voltage Cable TN 018: 2014 Technical Note For queries regarding this document standards@asa.transport.nsw.gov.au www.asa.transport.nsw.gov.au TN 018: 2014 Issued date 12 March 2014 Effective dates 12 March 2014 Subject:

More information

THE PATHWAY TO POWER HIGH-VOLTAGE CABLES

THE PATHWAY TO POWER HIGH-VOLTAGE CABLES THE PATHWAY TO POWER HIGH-VOLTAGE CABLES TABLE OF CONTENTS HIGH-VOLTAGE CABLES 3 Advantages of XLPE-insulated cable systems 3 PROPOSAL 4 Cable systems 4 Providing System Solutions 4 Continuous temperature

More information

Fault location on power cables. Fault location on power cables

Fault location on power cables. Fault location on power cables Fault location on power cables Fault location on power cables Contents: 1. Introduction 2. Construction of power cables 3. Cable faults 01. Introduction Fault location on communication and power cables

More information

E-Highway2050 WP3 workshop April 15 th, 2014 Brussels

E-Highway2050 WP3 workshop April 15 th, 2014 Brussels E-Highway2050 WP3 workshop April 15 th, 2014 Brussels High voltage underground and subsea cable technology options for future transmission in Europe Ernesto Zaccone, Chairman Europacable High Voltage Systems

More information

Presentation to CIGRE Next Generation Network. Visit of Seine substation

Presentation to CIGRE Next Generation Network. Visit of Seine substation Presentation to CIGRE Next Generation Network Visit of Seine substation Projet Seine 30 août 2012 Contents 0. Presentation of RTE 1. Power supply of «Ile-de-France» and Paris 2. 225 kv Paris substations

More information

CONFLEX ELECTRIC CABLE

CONFLEX ELECTRIC CABLE CONFLEX ELECTRIC CABLE CONFLEX - 0.6/1kV Flexible VSD/EMC Cables Applications WW VSD/EMC cables are manufactured for use where electrical interference distorts signal transmission in electric motors. Standard

More information

EMTP STUDIES PERFORMED TO INSERT LONG AC CABLES IN THE FRENCH GRID

EMTP STUDIES PERFORMED TO INSERT LONG AC CABLES IN THE FRENCH GRID Tension (kv) Impedance (Ohms) EMTP STUDIES PERFORMED TO INSERT LONG AC CABLES IN THE FRENCH GRID frequency (Hz) Simon DESCHANVRES Yannick VERNAY RTE, CNER, Substations Department t (ms) EMTP-RV Users Group

More information

Cables, Cable Laying & Accessories Manual

Cables, Cable Laying & Accessories Manual Distribution Business Cables, Cable Laying & Accessories Manual Database ref: File Ref: Title Page & Revision Log For Cables & Access v4 - Nov 2003.doc Manual Name: Cables & Accessories Manual Version

More information

DELHI METRO RAIL CORPORATION LIMITED. (A Joint Venture of Govt. of India & GNCTD) MASS RAPID TRANSPORT SYSTEM PHASE III. Contract: - CE -16 VOLUME-6

DELHI METRO RAIL CORPORATION LIMITED. (A Joint Venture of Govt. of India & GNCTD) MASS RAPID TRANSPORT SYSTEM PHASE III. Contract: - CE -16 VOLUME-6 DELHI METRO RAIL CORPORATION LIMITED (A Joint Venture of Govt. of India & GNCTD) MASS RAPID TRANSPORT SYSTEM PHASE III TURNKEY PROJECT OF DESIGN, SUPPLY, LAYING, JOINTING, TESTING AND COMMISSIONING OF

More information

SHE Transmission. 2015_10_30 Transmission Losses Strategy Rev 2.0 October 2015

SHE Transmission. 2015_10_30 Transmission Losses Strategy Rev 2.0 October 2015 SHE Transmission 2015_10_30 Transmission Losses Strategy Rev 2.0 October 2015 Summary This paper presents SHE Transmission s views and approach on the impact of transmission losses on the transmission

More information

Code of Practice Electricity transmission and distribution asset management. February 2009

Code of Practice Electricity transmission and distribution asset management. February 2009 Code of Practice Electricity transmission and distribution asset management February 2009 CONTENTS 1 PREFACE...4 2 APPLICATION AND OBJECTIVES...5 3 SCOPE...6 4 DEFINITIONS...7 5 DESIGN AND CONSTRUCTION...11

More information

Integrated Development and Assessment of New Thermoplastic High Voltage Power Cable Systems

Integrated Development and Assessment of New Thermoplastic High Voltage Power Cable Systems 21, rue d Artois, F-75008 PARIS B1-215 CIGRE 2012 http : //www.cigre.org Integrated Development and Assessment of New Thermoplastic High Voltage Power Cable Systems Mike FAIRHURST (1), Ankit GOWADIA (1),

More information

RGI Cable Workshop Understanding Underground Cables 13 and 14 February in Spreitenbach, Switzerland A workshop kindly hosted by Swissgrid

RGI Cable Workshop Understanding Underground Cables 13 and 14 February in Spreitenbach, Switzerland A workshop kindly hosted by Swissgrid RGI Cable Workshop Understanding Underground Cables 13 and 14 February in Spreitenbach, Switzerland A workshop kindly hosted by Swissgrid During the 1.5 day workshop, more than 70 participants from industry,

More information

Interfacing electrification and system reliability. Earthing of AC and DC railways 4,10,13

Interfacing electrification and system reliability. Earthing of AC and DC railways 4,10,13 Interfacing electrification and system reliability Roger White Professional Head of Electrification and Plant Rail Abstract Integration is the term given to ensuring that the different elements of an electrified

More information

Offshore Wind China 2010 Bergen, 15th March 2010. Olivier Angoulevant Nexans Norway AS

Offshore Wind China 2010 Bergen, 15th March 2010. Olivier Angoulevant Nexans Norway AS Offshore Wind China 2010 Bergen, 15th March 2010 Olivier Angoulevant Nexans Norway AS At the core of performance At the core of performance : a worldwide leader Worldwide leader in cables, cabling systems

More information

NW000-S0006 1 Chief Engineer 25/06/2015 25/06/2018 (Supersedes Network Standard (Network) NW000-S0006. Amendment No.0)

NW000-S0006 1 Chief Engineer 25/06/2015 25/06/2018 (Supersedes Network Standard (Network) NW000-S0006. Amendment No.0) Network Standard Document No Amendment No Approved By Approval Date Review Date : : : : : NW000-S0006 1 Chief Engineer 25/06/2015 25/06/2018 (Supersedes Network Standard (Network) NW000-S0006. Amendment

More information

Stephen G. Whitley, Senior Vice President & Chief Operating Officer

Stephen G. Whitley, Senior Vice President & Chief Operating Officer Peter T. Brandien Vice President, System Operations To: Stephen G. Whitley, Senior Vice President & Chief Operating Officer From: Peter T. Brandien Re: Discussion of Cable Technologies Under Evaluation

More information

HIGH-CAPACITY HIGH TEMPERATURE SUPERCONDUCTING POWER CABLES

HIGH-CAPACITY HIGH TEMPERATURE SUPERCONDUCTING POWER CABLES HIGH-CAPACITY HIGH TEMPERATURE SUPERCONDUCTING POWER CABLES Jean-Maxime SAUGRAIN NEXANS Corporate VP Technical IASS Workshop Postdam May 13, 2011 Rationale High-capacity High Temperature Superconducting

More information

Overhead lines in Ireland

Overhead lines in Ireland Overhead lines in Ireland The value in Cigré Jarlath Doyle Abstract The main theme of my presentation is to give a brief overview of the valuable information and influence Cigré has and is having on the

More information

How To Monitor Water Penetration In A Cable Screen

How To Monitor Water Penetration In A Cable Screen Detection and location of high voltage cable sheath damage with Water Penetration Monitoring*) Purpose of Monitoring System The expected lifetime of high voltage underground cables is more than 40 years,

More information

XLPE Land Cable Systems User s Guide. Rev 5

XLPE Land Cable Systems User s Guide. Rev 5 XLPE Land Cable Systems User s Guide Rev 5 CONTENT XLPE Land Cable Systems Introduction... 3 Design, installation and testing... 4 XLPE cables... 4 Cable accessories... 4 Installation of XLPE cable systems...

More information

Handling and Installation of Cables up to and including 33kV

Handling and Installation of Cables up to and including 33kV 1 SCOPE This document details ScottishPower EnergyNetworks (SPEN) technical requirements for the handling and installation of power cables up to onto the Company network. 2 ISSUE RECORD This is a maintained

More information

Current Ratings. TABLE BEC 107. (Continued) Current ratings for 6350/11000 volts grade PILC/SWA/PVC cable to BS6480/69

Current Ratings. TABLE BEC 107. (Continued) Current ratings for 6350/11000 volts grade PILC/SWA/PVC cable to BS6480/69 Ratings TBLE BEC 107. (Continued) ratings for 60/11000 volts grade PILC/SW/PVC cable to BS64/69 CBLES LID IN IR: The ratings given in the foregoing tables are based on an ambient of C. It is recommended

More information

6 ELECTRICAL PARAMETERS

6 ELECTRICAL PARAMETERS 6 ELECTRICAL PARAMETERS For power, low voltage and medium voltage cables, cross section nominal areas are calculated in taking into account several parameters as: permissible current carrying capacities

More information

Undergrounding high voltage electricity transmission lines. The technical issues

Undergrounding high voltage electricity transmission lines. The technical issues Undergrounding high voltage electricity transmission lines The technical issues Contents Introduction 03 National Grid electricity transmission 03 an overview Section 1 Insulating underground cables 04

More information

SUPERCONDUCTING CABLE SYSTEMS

SUPERCONDUCTING CABLE SYSTEMS SUPERCONDUCTING CABLE SYSTEMS INTRODUCTION An aging and inadequate power grid is widely seen as one of the greatest obstacles to the restructuring of power markets in the United States, Europe and elsewhere.

More information

Q: PLEASE STATE YOUR NAME AND BUSINESS ADDRESS. A: Gerry Sheerin. Sheerin Technical, 25 Eastville Avenue, Toronto, Ontario Canada

Q: PLEASE STATE YOUR NAME AND BUSINESS ADDRESS. A: Gerry Sheerin. Sheerin Technical, 25 Eastville Avenue, Toronto, Ontario Canada DIRECT TESTIMONY OF GERRY SHEERIN, P. ENG ON BEHALF OF PIEDMONT ENVIRONMENTAL COUNCIL BEFORE THE STATE CORPORATION COMMISSION OF VIRGINIA CASE NOS. PUE-00-0001 AND PUE-00-000 1 1 1 1 1 1 1 1 1 Q: PLEASE

More information

CABLE MONITORING SOLUTION

CABLE MONITORING SOLUTION POWER CABLE MONITORING SOLUTION Kuljit Singh BSc Honours MIEE(IET,UK) Dan Watley Ph. D, B.A MEng (UK), MIEEE, UK 8-9 November 2011 PREDICT WITH CERTAINTY Definition DTS: Distributed Temperature Sensor

More information

Triton Knoll Offshore Wind Farm Limited Electrical System. Outline Traffic Management Plan

Triton Knoll Offshore Wind Farm Limited Electrical System. Outline Traffic Management Plan Triton Knoll Offshore Wind Farm Limited Electrical System Outline Traffic Management Plan October 2014 RWE Innogy UK Triton Knoll TMP Copyright 2014 RWE Innogy UK Ltd All pre-existing rights reserved.

More information

Konti Skan Replacement of Cable 1

Konti Skan Replacement of Cable 1 Konti Skan Replacement of Cable 1 Presentation of the project 1 Agenda Background for the project Scope of Work for the cable delivery Eletrical Requirements Type Test Route description Time Schedule 2

More information

Max. Length of HTS Cables in the Future

Max. Length of HTS Cables in the Future Max. Length of HTS Cables in the Future K. Schippl, Nexans Deutschland Industries, Hannover, Germany TOPICS: Limitation of the cable design: 1. Physical limitations 2. Shipping limitations 3. Maintenance

More information

EARTHING AND BONDING AT SECONDARY SUBSTATIONS

EARTHING AND BONDING AT SECONDARY SUBSTATIONS DISTRIBUTION CONSTRUCTION MANUAL SECTION 4 - SUBSTATIONS ISSUE B SEPT 1996 4.4.4 EARTHING AND BONDING AT SECONDARY SUBSTATIONS 1 SCOPE This section of the Distribution Construction Manual lays down the

More information

GUIDELINES FOR UTILITY INSTALLATIONS Part 1 - Wire Lines and Communications Cables

GUIDELINES FOR UTILITY INSTALLATIONS Part 1 - Wire Lines and Communications Cables Engineering Department SEPTEMBER, 2007 GUIDELINES FOR UTILITY INSTALLATIONS Part 1 - Wire Lines and Communications Cables General Requirements This section applies to all public and private utilities,

More information

KNOW YOUR OPTIONS: 69 KV XLPE POWER CABLE

KNOW YOUR OPTIONS: 69 KV XLPE POWER CABLE Know Your Options: 69 kv XLPE Power Cable 3 material and size material is a matter of both customer preference and required current carrying capacity Copper conductor common for larger loads When both

More information

KNOW YOUR OPTIONS: 230 KV POWER CABLES

KNOW YOUR OPTIONS: 230 KV POWER CABLES KNOW YOUR OPTIONS: 230 KV POWER CABLES 71 CONDUCTOR MATERIAL AND SIZE Conductor material is a matter of both customer preference and required current carrying capacity At 230 kv, copper is most common

More information

MV CABLE TYPE C 33-226

MV CABLE TYPE C 33-226 MV CABLE TYPE C 33-226 Standards : CENELEC HD 620 C 33-226 Rated voltage Rated voltage : 12/20 (24) kv Design 1 Stranded aluminium, class 2 conductor 2 Extruded conducting screen on conductor 3 XLPE insulation

More information

Technical Guidance Note 287. Third-party guidance for working near National Grid Electricity Transmission equipment

Technical Guidance Note 287. Third-party guidance for working near National Grid Electricity Transmission equipment Technical Guidance Note 287 Third-party guidance for working near National Grid Electricity Transmission equipment 02 Purpose and scope... 3 Part 1 Electricity Transmission infrastructure... 4 Overhead

More information

Electric Engineering Division FIBER CONDUIT RULES AND REGULATIONS

Electric Engineering Division FIBER CONDUIT RULES AND REGULATIONS Electric Engineering Division FIBER CONDUIT RULES AND REGULATIONS TABLE OF CONTENTS I. RULES AND REGULATIONS A. TABLE OF CONTENTS... 2 B. TERMS AND DEFINITIONS... 3 C. DEVELOPER S/CONTRACTOR S RESPONSIBILITIES...

More information

APPLICATION PROCEDURES FOR PLACEMENT OF UNDERGROUND TELECOMMUNICATION CABLES IN THE VICINITY OF TRANSPORTATION FACILITIES

APPLICATION PROCEDURES FOR PLACEMENT OF UNDERGROUND TELECOMMUNICATION CABLES IN THE VICINITY OF TRANSPORTATION FACILITIES APPLICATION PROCEDURES FOR PLACEMENT OF UNDERGROUND TELECOMMUNICATION CABLES IN THE VICINITY OF TRANSPORTATION FACILITIES UNDER THE JURISDICTION OF ALBERTA TRANSPORTATION 1.0 Application Procedures 2.0

More information

Summary of Electric Transmission Assessment Report

Summary of Electric Transmission Assessment Report Summary of Electric Transmission Assessment Report January 2010 Assessment and Analysis of the State-Of-the-Art High-Voltage Electric Transmission Systems with Specific Focus on High-Voltage Direct Current

More information

Section 5 161 kv Power Cables

Section 5 161 kv Power Cables Know Your Options: 161 kv Power Cable 61 material and size material is a matter of both customer preference and required current carrying capacity Copper conductor common for larger loads When both copper

More information

Cable Condition Monitoring to Improve Reliability

Cable Condition Monitoring to Improve Reliability Cable Condition Monitoring to Improve Reliability by Hilary Marazzato, Ken Barber, Mark Jansen, and Graeme Barnewall Olex Australia Page 1-1 - Cable Condition Monitoring of Improve Reliability Hilary Marazzato,

More information

EHV Cable Installation Technology for Tunnels and Ducts in Japan. S. TSUCHIYA T. IIDA Y. MORISHITA Tokyo Electric Power Company

EHV Cable Installation Technology for Tunnels and Ducts in Japan. S. TSUCHIYA T. IIDA Y. MORISHITA Tokyo Electric Power Company 21, rue d Artois, F-75008 PARIS B1_109_2012 CIGRE 2012 http : //www.cigre.org EHV Installation Technology for Tunnels and Ducts in Japan S. TSUCHIYA T. IIDA Y. MORISHITA Tokyo Electric Power Company Kansai

More information

Feasibility Study of Deep Water Power Cable Systems. Enrico Colombo CESI S.p.A

Feasibility Study of Deep Water Power Cable Systems. Enrico Colombo CESI S.p.A Feasibility Study of Deep Water Power Cable Systems Enrico Colombo CESI S.p.A Layout of Presentation The Study Context, Objectives, Participants Study Approach & Methodology Assessments and Findings Implementation

More information

Overview of the 500MW EirGrid East-West Interconnector, considering System Design and Execution-Phase Issues

Overview of the 500MW EirGrid East-West Interconnector, considering System Design and Execution-Phase Issues Overview of the 500MW EirGrid East-West Interconnector, considering System Design and Execution-Phase Issues J Egan, P O Rourke EirGrid Plc, Republic of Ireland john.egan@eirgrid.com paul.o rouke@eirgrid.com

More information

Achievement and experience in service of long length High Voltage AC electrical links by insulated power cables

Achievement and experience in service of long length High Voltage AC electrical links by insulated power cables Achievement and experience in service of long length High Voltage AC electrical links by insulated power cables Ken Barber Introduction to Long length AC Cable systems Why is there now such a significant

More information

MINISTERIE VAN ECONOMISCHE ZAKEN GENERAL COST COMPARISON BETWEEN UNDERGROUND CABLES AND O.H. LINE SYSTEMS FOR H.V. TRANSMISSION

MINISTERIE VAN ECONOMISCHE ZAKEN GENERAL COST COMPARISON BETWEEN UNDERGROUND CABLES AND O.H. LINE SYSTEMS FOR H.V. TRANSMISSION MINISTERIE VAN ECONOMISCHE ZAKEN GENERAL COST COMPARISON BETWEEN UNDERGROUND CABLES AND O.H. LINE SYSTEMS FOR H.V. TRANSMISSION REPORT ON NETWORK RELIABILITY ASPECTS OF THE CHOICE LINE VERSUS CABLE FOR

More information

HVDC Light Cables. Submarine and land power cables

HVDC Light Cables. Submarine and land power cables HV Light Cables Submarine and land s The HV Light s to offshore platform The light and robust HV Light s can be laid with very cost effecient methods HV Light System HV Light is a transmission system in

More information

CABLE ASSET MANAGEMENT PREDICT WITH CERTAINTY. Kuljit Singh BSc Honours MIEE(IET,UK) 5 June 2014

CABLE ASSET MANAGEMENT PREDICT WITH CERTAINTY. Kuljit Singh BSc Honours MIEE(IET,UK) 5 June 2014 CABLE ASSET MANAGEMENT PREDICT WITH CERTAINTY Kuljit Singh BSc Honours MIEE(IET,UK) 5 June 2014 Definitions International Workshop 2014 DTS: Distributed Temperature Sensor DCR: Dynamic Cable Ratings (

More information

The electrical energy produced at the gen

The electrical energy produced at the gen 300 300 Principles of Power System CHAPTER CHAPTER 12 Distribution Systems General 12.1 Distribution System 12.2 Classification of Distribution Systems 12.3 A.C. Distribution 12.4 D.C. Distribution 12.5

More information

Assessment of the Technical Issues relating to Significant Amounts of EHV Underground Cable in the All-island Electricity Transmission System

Assessment of the Technical Issues relating to Significant Amounts of EHV Underground Cable in the All-island Electricity Transmission System Assessment of the Technical Issues relating to Significant Amounts of EHV Underground Cable in the All-island Electricity Transmission System Summary Report November 2009 Technical Report on using EHV

More information

Earthing Guidance Notes

Earthing Guidance Notes Central Networks Earthing Manual Section E2 Earthing Guidance Notes Version: 2 Date of Issue: September 2007 Author: Nigel Johnson Job Title: Earthing Specialist Approver: John Simpson Job Title: Head

More information

HVDC Light, a tool for electric power transmission to distant loads

HVDC Light, a tool for electric power transmission to distant loads Presented at VI Sepope Conference, Salvador, Brazil, May 1998 HVDC Light, a tool for electric power transmission to distant loads by Gunnar Asplund Kjell Eriksson* Ove Tollerz ABB Power Systems AB ABB

More information

SP Energy Networks 2015 2023 Business Plan

SP Energy Networks 2015 2023 Business Plan SP Energy Networks 2015 2023 Business Plan Updated March 2014 Annex 132kV Cable Strategy SP Energy Networks 27 March 2014 132kV Cable Strategy March 2014 Issue Date Issue No. Document Owner Amendment Details

More information

Session 14 Cable Support Systems

Session 14 Cable Support Systems Session 14 Cable Support Systems Cable Support Systems in the IEC World A new IEC Standard, IEC61537 2001 has been developed If full details of the cabling layout are available then the likely cable load

More information

DESCRIPTION DWG DESCRIPTION DWG

DESCRIPTION DWG DESCRIPTION DWG DESCRIPTION DWG DESCRIPTION DWG Ferroresonance 3451/1 3451/2 3451/3 Electro-magnetic Fields (EMF) 3462/1 HV & LV Insulators (Links) 3463/1 A ORIGINAL ISSUE B 14.07.09 APPROVED DATE J. Brooks 25.02.03 INDEX

More information

ScottishPower Distribution Cables & Equipment. Metal Theft

ScottishPower Distribution Cables & Equipment. Metal Theft ScottishPower Distribution Cables & Equipment Metal Theft April 2012 As an aid to deterring to metal theft this booklet has been put together to help identify the types of utility power cables and associated

More information

ELECTRICAL PLANNING AND DESIGN FOR GEOTHERMAL POWER PROJECTS.

ELECTRICAL PLANNING AND DESIGN FOR GEOTHERMAL POWER PROJECTS. ELECTRICAL PLANNING AND DESIGN FOR GEOTHERMAL POWER PROJECTS. Ivan Hunt PB Power, GENZL Division. PO Box 668, Wellington, New Zealand. Key Words: design, electrical, geothermal, planning ABSTRACT This

More information

Lucien Antonissen Key Account Manager LIOS Technology Germany

Lucien Antonissen Key Account Manager LIOS Technology Germany Lucien Antonissen Key Account Manager LIOS Technology Germany Content Company Markets DTS Controller Software Configuration RTTR Demonstration Q&A NKT Holding 2013 NKT Holding Nilfisk-Advance NKT Cables

More information

Distributed Temperature Monitoring of Energy Transmission and Distribution Systems

Distributed Temperature Monitoring of Energy Transmission and Distribution Systems 1 m 40000m0 range 61850 IEC spatial resolution Distributed Temperature Monitoring of Energy Transmission and Distribution Systems Ensuring a Reliable Supply of Electrical Power for Today s World www.en-sure.pro

More information

Power transformers. Generator step-up and system intertie power transformers Securing high-quality AC transmission

Power transformers. Generator step-up and system intertie power transformers Securing high-quality AC transmission Power transformers Generator step-up and system intertie power transformers Securing high-quality AC transmission Generator step-up transformers Built to withstand continuous full load Generator step-up

More information

CONNECTING YOU TO SPECIALIST ELECTRICAL SUPPORT services

CONNECTING YOU TO SPECIALIST ELECTRICAL SUPPORT services CONNECTING YOU TO SPECIALIST ELECTRICAL SUPPORT services SpecialistS IN ELECTRICAL SUPPORT SERVICES TO MINING, UTILITIES & industry Ampcontrol is committed to supporting our customers to maintain efficient

More information

APPLICATION PROCEDURES FOR PLACEMENT OF UNDERGROUND WATER AND SEWER PIPELINES IN THE VICINITY OF TRANSPORTATION FACILITIES UNDER THE

APPLICATION PROCEDURES FOR PLACEMENT OF UNDERGROUND WATER AND SEWER PIPELINES IN THE VICINITY OF TRANSPORTATION FACILITIES UNDER THE APPLICATION PROCEDURES FOR PLACEMENT OF UNDERGROUND WATER AND SEWER PIPELINES IN THE VICINITY OF TRANSPORTATION FACILITIES UNDER THE JURISDICTION OF ALBERTA TRANSPORTATION 1.0 Application Procedures 2.0

More information

www.klmtechgroup.com TABLE OF CONTENT

www.klmtechgroup.com TABLE OF CONTENT Page : 1 of 13 Project Engineering Standard www.klmtechgroup.com KLM Technology #03-12 Block Aronia, Jalan Sri Perkasa 2 Taman Tampoi Utama 81200 Johor Bahru Malaysia ELECTIRAL GROUNDING TABLE OF CONTENT

More information

Underground Cable Temperature Monitoring in the Real World

Underground Cable Temperature Monitoring in the Real World Underground Cable Temperature Monitoring in the Real World Executive Summary Background Brain Storming Possible Causes to Duct Bank Over Heating Mitigating Duct Bank Overheating DTS Installation for Duct

More information

Hyperlinks are Inactive

Hyperlinks are Inactive Prepared by: NIB/EOB PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES 05503 Department: Electric T&D Section: T&D Engineering and Technical Support Approved by: G.O. Duru (GOD)

More information

METHOD STATEMENT INSTALLATION OF INSULATING FLANGE KITS

METHOD STATEMENT INSTALLATION OF INSULATING FLANGE KITS METHOD STATEMENT INSTALLATION OF INSULATING FLANGE KITS Revision Date Prepared By Approved By Method Statement IF Kits BAC Corrosion Control Limited Stafford Park 11 Telford TF3 3AY Tel: 01952 290321 Fax:

More information

Svenska Kraftnät s requirements for documentation in cable projects

Svenska Kraftnät s requirements for documentation in cable projects UNIT, BUSINESS AREA AD, Plant documentation OUR DESIGNATION TR08-05 DATE CONSULTATION 2014-09-08 NT, NK, NL, AS, AFL, KI TECHNICAL GUIDELINES ISSUE 3 Td APPROVED Svenska Kraftnät s requirements for documentation

More information

4 IX D N E P P A Installation methods Current-carrying capacity and voltage drop for cables Reference method IET Wiring Matters

4 IX D N E P P A Installation methods Current-carrying capacity and voltage drop for cables Reference method IET Wiring Matters 8 Appendix 4 of BS 7671 by Mark Coles Appendix 4, Current-carrying capacity and voltage drop for cables and flexible cords, has seen significant changes with the publishing of BS 7671:2008. This article

More information

Direction of current flow through conductor. Fig. 1 Magnetic field generated by current flow

Direction of current flow through conductor. Fig. 1 Magnetic field generated by current flow ingle Conductor Cable Copper heathed Cable heath Currents ingle conductor cables present certain application considerations that do not arise in multiconductor cable installations. These considerations

More information

TS 813 GROUNDING AND BONDING TTD 813.001 TRAFFIC SIGNAL INSTALLATION AND CONTROLLER CABINET GROUNDING SYSTEM TTD 813.005 CONTROLLER CABINET GROUNDING

TS 813 GROUNDING AND BONDING TTD 813.001 TRAFFIC SIGNAL INSTALLATION AND CONTROLLER CABINET GROUNDING SYSTEM TTD 813.005 CONTROLLER CABINET GROUNDING TORONTO TRANSPORTATION January 2012 TS 813 GROUNDING AND BONDING TABLE OF CONTENTS 1. DRAWINGS TTD 813.001 TRAFFIC SIGNAL INSTALLATION AND CONTROLLER CABINET GROUNDING SYSTEM TTD 813.005 CONTROLLER CABINET

More information

XLPE PRODUCTION PLANT FOR THIRUVALLA UNIT OF TRACO CABLE LTD

XLPE PRODUCTION PLANT FOR THIRUVALLA UNIT OF TRACO CABLE LTD PROJECT PROFILE ON XLPE PRODUCTION PLANT FOR THIRUVALLA UNIT OF TRACO CABLE LTD Prepared by: TRACO CABLE COMPANY LIMITED IV TH FLOOR, KSHB OFFICE COMPLEX PANAMPILLY NAGAR KOCHI-682036 September 2012 PROJECT

More information

Assessing, Maintaining & Replacing Fluid Filled Cable Systems at PEPCO

Assessing, Maintaining & Replacing Fluid Filled Cable Systems at PEPCO April 2, 2014 Assessing, Maintaining & Replacing Fluid Filled Cable Systems at PEPCO Todd Goyette, P.E., POWER Engineers Mousa Hejazi, P.E., Pepco Holdings Inc. 1 Pepco Quick Facts First incorporated in

More information

Introduction to The Trans Bay Cable Project

Introduction to The Trans Bay Cable Project Introduction to The Trans Bay Cable Project We ve come a long way 1 But thanks to the advances of two men and 2 The Battle of Currents 3 Utilities are able to choose the most effective and efficient means

More information

- 33 - This paper describes an instrumentation system concept which should be capable of early detection of a leak-before* break in main steam lines.

- 33 - This paper describes an instrumentation system concept which should be capable of early detection of a leak-before* break in main steam lines. - 33 - DETECTION OF LEAKS IN STEAM LINES BY DISTRIBUTED FIBRE-OPTIC TEMPERATURE SENSING (DTS) Author; Neil G.Craik, Nuclear Generation Consultant, Frederic ton, N.B., Canada ABSTRACT This paper describes

More information

ENERGY. TECWATER S1BN8-F 0,6/1 kv. Cable for Water Application

ENERGY. TECWATER S1BN8-F 0,6/1 kv. Cable for Water Application ENERGY TECWATER S1BN8-F 0,6/1 kv Cable for Water Application Technical Data Electrical parameters Thermal parameters Trademark Type designation Specification Approval Application Rated voltage Maximum

More information

ECS 02-0019 INSTALLATION OF UNDERGROUND CABLES - LV TO 132KV

ECS 02-0019 INSTALLATION OF UNDERGROUND CABLES - LV TO 132KV THIS IS AN UNCONTROLLED DOCUMENT, THE READER MUST CONFIRM ITS VALIDITY BEFORE USE Document Number: ECS 02-0019 ENGINEERING CONSTRUCTION STANDARD ECS 02-0019 INSTALLATION OF UNDERGROUND CABLES - LV TO 132KV

More information

AS COMPETITION PAPER 2008

AS COMPETITION PAPER 2008 AS COMPETITION PAPER 28 Name School Town & County Total Mark/5 Time Allowed: One hour Attempt as many questions as you can. Write your answers on this question paper. Marks allocated for each question

More information

ACCESSORIES FOR HV CABLES WITH EXTRUDED INSULATION

ACCESSORIES FOR HV CABLES WITH EXTRUDED INSULATION ACCESSORIES FOR HV CABLES WITH EXTRUDED INSULATION Ref: WG 21.06 (TB 177) JTF 21.15 (TB 210) TF B1.10 (Electra 212) Henk Geene Presentation overview Accessories function Accessory design Accessory types

More information

DISCUSSION OF CROSS-LINKED POLYETHYLENE INSULATED CABLES FOR UNDERGROUND PORTIONS OF THE MIDDLETOWN-NORWALK 345 kv PROJECTS.

DISCUSSION OF CROSS-LINKED POLYETHYLENE INSULATED CABLES FOR UNDERGROUND PORTIONS OF THE MIDDLETOWN-NORWALK 345 kv PROJECTS. DISCUSSION OF CROSS-LINKED POLYETHYLENE INSULATED CABLES FOR UNDERGROUND PORTIONS OF THE MIDDLETOWN-NORWALK 345 kv PROJECTS December 20, 2004 David W. Forrest Rachel I. Mosier 1. EXECUTIVE SUMMARY CL&P

More information