1 April 2, 2014 Assessing, Maintaining & Replacing Fluid Filled Cable Systems at PEPCO Todd Goyette, P.E., POWER Engineers Mousa Hejazi, P.E., Pepco Holdings Inc. 1
2 Pepco Quick Facts First incorporated in 1896 Service territory: 640 square miles Customers served: 793,000 Washington, D.C.: 260,000 Montgomery County: 309,000 Prince George s County: 225,000 Population served: 2.2 million 2
3 Purpose Comprehensive review of PHI s oil impregnated paper insulated cable systems Limited & decreasing number of manufacturers of cable Limited & decreasing number of manufacturers of cable accessories (reservoirs, pumping plants, etc.) Decreasing numbers of qualified splicers to work with these types of cables Environmental impact of fluid leaks 3
4 Approach Review separated into 3 tasks Task1: Industry Survey Determine current trend of industry with regards to maintaining or replacing these legacy cables systems Task 2: Cataloging Existing Systems Develop a complete list of the cable systems on PHI s system o Identify components and key drivers (type, voltage, length, age, etc.) for use in future studies and planning 4
5 Approach Task 3: Risk & Condition Assessment Develop risk matrix to qualitatively and quantitatively identify areas of risk for these types of cable systems Identify areas of possible improvements to mitigate risks 5
6 Background: Self Contained Fluid Filled Cables (SCFF) Developed in 1920s Uses dielectric fluid under pressure to maintain insulation integrity Pressure maintained by reservoirs installed in manholes and substations Cable sheath acts as pressure vessel & hermetic seal 6
7 Background: Self Contained Fluid Filled Cables (SCFF) Relies heavily on no air or moisture entrainment Two subcategories Low Pressure Fluid Filled (LPFF) Operating pressures 1-15 psig Typically lead sheath Medium Pressure Fluid Filled (MPFF) Operating pressures 5-70 psig Typically aluminum sheath or reinforced lead 7
8 Sample SCFF Cables 8
9 PHI Self Contained Fluid Filled Cables # of Circuits 69kV 115kV 138kV 230kV Total Low Pressure Fluid Filled Medium Pressure Fluid Filled Total Mileage 69kV 115kV 138kV 230kV Total Low Pressure Fluid Filled Medium Pressure Fluid Filled Total PHI has 32 SCFF systems and Approximately 103 circuit miles of SCFF cable 9
10 Background: High Pressure Pipe Type Cables (HPPT) Historically most common type of transmission cable installed in the United States Gained popularity after World War II Three cables installed in a coated steel pipe Requires pressurizing plants to maintain a nominal pressure of 200 psig Courtesy of the Okonite Company 10
11 Background: High Pressure Pipe Type Cables (HPPT) Requires active cathodic protection to prevent pipe corrosion Two subcategories High Pressure Fluid Filled (HPFF) High Pressure Gas Filled (HPGF) Courtesy of the Okonite Company 11
12 PHI High Pressure Pipe Type Cables # of Circuits 69kV 115kV 138kV 230kV Total High Pressure Gas Filled High Pressure Fluid Filled Total Mileage 69kV 115kV 138kV 230kV Total Low Pressure Fluid Filled Medium Pressure Fluid Filled Total PHI has 90 HPPT systems and Approximately 322 circuit miles of HPPT cable 12
13 Task 1: Industry Survey 13
14 Industry Survey Questionnaire sent to utilities across the United States 29 questions covering a range of topics Existing Cable Systems New Cable Systems Proposed Cable Systems Replacement Cable Projects Electrical Failures Circuit Availability Maintenance Practices Contractor Usage Spare Material Future Risk Concerns 14
15 Industry Survey Results PHI has one of the larger inventories of active SCFF & HPPT cable systems (both by number and mileage) Utilities are actively seeking to reduce their self contained fluid filled cable inventory Age, reliability concerns, capacity Utilities are not actively seeking to replace their high pressure pipe type circuits High Voltage Extruded Dielectric (XLPE & EPR) is becoming more popular for new installations HPPT cable is still considered a viable option for certain conditions There is a growing industry concern with the limited number of manufacturers & contractors for oil impregnated paper insulated cables & accessories 15
16 Task 3: Risk Matrix Development & Evaluation 16
17 Risk Matrix Development Cable systems evaluated on various criteria Cable Construction Installation Conditions Planning Drivers O&M Practices Operation Spare Material Physical Condition Assessment Criteria further separated into various subtopics 17
18 Self Contained Fluid Filled Cables Condition Assessment, Risk Evaluation & Recommendations 18
19 SCFF Condition Assessment April 15 19, 2013 Visual inspection of cables and accessories Terminations Splices Reservoirs Pressure Gauges & Alarms Exposed Cable Fluid Leaks and other possible problems noted Equipment & overall location condition given a ranking of good, fair or poor based on observations 19
20 SCFF Condition Review Sample of Issues Observed 20
21 SCFF Condition Review continued 21
22 SCFF Cable & Terminations Condition Majority of Terminations are in good condition 22
23 SCFF Reservoirs Condition Very few problems with fluid reservoirs were observed 23
24 SCFF Overall Condition Overall condition of SCFF cables is fair to good 24
25 PHI SCFF Cable Risk Results 25
26 Conclusions / Recommendations PHI SCFF cable systems are considered to be in fair to good condition PHI still encouraged to develop a system program to replace these oil filled cable systems Current industry trend is to install extruded dielectric at these lower voltages (69kV & 138kV) Limited availability of manufacturers and qualified workers Expected further decrease in these numbers 26
27 Conclusions / Recommendations Increased costs of operation & maintenance Increase risk of circuit unavailability due to leaks & electrical failures Increased risk of environmental impacts cause by fluid leaks Increased risk of potential health impacts due to working with identified hazardous material (lead). 27
28 Replacement Strategy Use Risk Matrix rankings to prioritize projects High Priority circuits should have projects initiated within 5 years Medium Priority circuits should have projects initiated within years Low Priority circuits should be targeted for after 15 years 28
29 Replacement Options Three Options Considered Option 1: Replace with HVED cable systems Eliminates ongoing environmental concerns with dielectric fluid Reduces future O&M needs and costs Requires significant civil infrastructure improvements o New manhole and duct system required Estimated order of magnitude costs: $312M 29
30 Replacement Options Option 2: Re-Conductor with SCFF cables Eliminates any concerns with existing age or condition of cables Least cost solution o Can Utilize existing manhole & duct system Does not eliminate environmental concerns with dielectric fluid Does not reduce future O&M needs or costs Estimated order of magnitude costs: $90M 30
31 Replacement Options Continued Option 3: Develop direct replacement HVED cable Partner with a high voltage cable manufacturer to develop a 3/C HVED cable that will fit in the existing manhole & duct system Combines the advantages of both Option 1 & Option 2 Requires some engineering & developmental costs for cable & accessory design and testing Various cable manufacturers have expressed intent to develop solid dielectric cables capable of direct replacement 31
32 High Pressure Fluid Filled Cables Condition Assessment, Risk Evaluation & Recommendations 32
33 HPFF Condition Assessment May & July 8 10, 2013 Visual inspection of cables and accessories Terminations Pressurizing Systems Cathodic Protection System Exposed Pipe Fluid Leaks and other possible problems noted Equipment given a ranking of good, fair or poor based on observations 33
34 HPFF Condition Review Sample of Issues Observed 34
35 HPFF Condition Review Sample of Issues Observed 35
36 HPFF Terminations Condition Majority of Terminations are in good condition 36
37 HPFF Terminations Condition Majority of Terminations are in good condition 37
38 HPFF Terminations Condition Majority of Terminations are in good condition 38
39 HPFF Pressurizing Plants Condition Majority of Pressurizing Plants are in fair to good condition 39
40 PHI 69kV HPFF Cable Risk Results 40
41 PHI 115kV & 138kV HPFF Cable Risk Results 41
42 PHI 230kV HPFF Cable Risk Results 42
43 Conclusions / Recommendations PHI HPFF cable systems are considered to be in good to very good condition Small number of 69kV circuits are considered at a medium risk Mostly attributable to condition of pressurizing plants Continue with ongoing replacement program for pressurizing plants Consider adding additional pressurizing plants to list 43
44 Conclusions / Recommendations Continue with good maintain practices Active cathodic protection systems to prevent pipe corrosion Oil sampling and DGA analysis on periodic basis to identify incipient problems Continue to monitor pipe type cable replacement options for future consideration Re-evaluate cable condition on periodic basis 44
45 PHI s Additional Replacement Factor Considerations Replacement factor increase for SCFF Cable failure Outage within past 5 years warrants increase in replacement factor Feeders with short lengths increase replacement factor due to increased feasibility and lower cost Redundancy increases the replacement factor 45
46 PHI Replacement Strategy Coordinate risk matrix rankings with strategic plans from other departments Transmission Planning Electric Construction & Maintenance System Operations Look for synergy between circuits with common routes to maximize efficiencies of design & construction 46
47 Questions This concludes the educational content of this activity Thank you for your time! Todd Goyette P.E. Senior Project Engineer POWER Engineers Mousa Hejazi, PE. Senior Supervising Engineer Pepco Holdings Inc
Vision 2050 An Asset Management Strategy. Jaclyn Cantler Manager, Transmission Planning, PHI
1 Vision 2050 An Asset Management Strategy Jaclyn Cantler Manager, Transmission Planning, PHI 2 Agenda Case for Change About Vision 2050 Status Closing System Design Cybersecurity Interface with distributed/dispersed
More informationStephen G. Whitley, Senior Vice President & Chief Operating Officer
Peter T. Brandien Vice President, System Operations To: Stephen G. Whitley, Senior Vice President & Chief Operating Officer From: Peter T. Brandien Re: Discussion of Cable Technologies Under Evaluation
More informationDISCUSSION OF CROSS-LINKED POLYETHYLENE INSULATED CABLES FOR UNDERGROUND PORTIONS OF THE MIDDLETOWN-NORWALK 345 kv PROJECTS.
DISCUSSION OF CROSS-LINKED POLYETHYLENE INSULATED CABLES FOR UNDERGROUND PORTIONS OF THE MIDDLETOWN-NORWALK 345 kv PROJECTS December 20, 2004 David W. Forrest Rachel I. Mosier 1. EXECUTIVE SUMMARY CL&P
More informationII. CABLE COMPONENTS AND SYSTEM TYPES
Underground Power Cable Considerations: Alternatives to Overhead Presented at 47 th Minnesota Power Systems Conference (MIPSYCON) 1-3 November 2011 Earle Brown Heritage Center 6155 Earle Brown Drive Brooklyn
More informationSOUTHERN MARYLAND ELECTRIC COOPERATIVE, INC. HUGHESVILLE, MD
SOUTHERN MARYLAND ELECTRIC COOPERATIVE, INC. HUGHESVILLE, MD HOLLAND CLIFF HEWITT ROAD 230 KV TRANSMISSION LINE PROJECT ELECTRIC ALTERNATIVE EVALUATION STUDY BLACK & VEATCH CORPORATION B&V Project 146026(G)
More information345 kv Underground Report
POWER ENGINEERS, INC. February 24, 2010 345 kv Underground Report PROJECT NUMBER: 117910 PROJECT CONTACT: Mike Mueller Richard C. Mues, PE EMAIL: mike.mueller@powereng.com rmues@powereng.com PHONE: 314-851-4050
More informationSpring 2016 Industry Event - CABLES
Spring 2016 Industry Event - CABLES 3 Tracks - 1 Venue Mitigation Techniques on Corrosion and Oil Leaks and Advanced Diagnostic Techniques for Underground Transmission Cable Systems March 8-9, 2016 Indian
More informationTHE OKONITE COMPANY Ramsey, Ramsey New Jersey 07446. 201.825.0300. Fax: 201.825.3524. www.okonite.com www
THE OKONITE COMPANY Ramsey, New Jersey 07446. 201.825.0300. Fax: 201.825.3524. www.okonite.com 3 Pipe-type The purpose of this brochure is to acquaint the reader with Pipe Type Cables which are by far
More informationREQUIREMENTS AND SPECIFICATIONS FOR HIGH VOLTAGE CUSTOMER BUILT FACILITIES PEPCO ENGINEERING
REQUIREMENTS AND SPECIFICATIONS FOR HIGH VOLTAGE CUSTOMER BUILT FACILITIES PEPCO ENGINEERING Revised October, 2013 TABLE OF CONTENTS 1.0 INTRODUCTION... 3 2.0 REQUIRED DRAWINGS... 3 2.1 Site Plan... 3
More informationCable Consulting International
Cable Consulting International Brian Gregory BSc, CEng, MIEEE, FIEE Technical Director www.cableconsulting.net Alan Williams BSc, CEng, MIEE Senior Consultant 1 FEASIBILITY STUDY for 500 kv AC UNDERGROUND
More informationHeat Trace Fundamentals. Monte Vander Velde, P.E. President, Interstates Instrumentation
Heat Trace Fundamentals Monte Vander Velde, P.E. President, Interstates Instrumentation Contents Introduction... 3 Purpose of Heat Trace... 3 Types of Heat Trace... 4 Steam Trace vs. Electric Trace...
More informationCorporate Profile ROYAL. MODERN ROYAL ELECTRIC Ideal Power Solution MRE ELECTRICAL, INSTRUMENTATION & COMMUNICATION SYSTEMS
Corporate Profile MODERN ROYAL ELECTRIC Ideal Power Solution ROYAL MRE ELECTRICAL, INSTRUMENTATION & COMMUNICATION SYSTEMS MAJOR STOCKIST >>> CATHODIC PROTECTION CABLES >>> LOW VOLTAGE CABLES >>> MEDIUM
More informationFault location on power cables. Fault location on power cables
Fault location on power cables Fault location on power cables Contents: 1. Introduction 2. Construction of power cables 3. Cable faults 01. Introduction Fault location on communication and power cables
More informationUnderground Electric Transmission Lines Introduction
Underground Electric Transmission Lines Introduction This overview contains information about electric transmission lines which are installed underground, rather than overhead on poles or towers. Underground
More informationHV Submarine Cable Systems Design, Testing and Installation
HV Submarine Cable Systems Design, Testing and Installation CIGRE Ireland Technical Seminar 6 th October 2010 Robert Donaghy Senior Consultant Engineer, ESB International Presentation Overview Applications
More informationSummary of Electric Transmission Assessment Report
Summary of Electric Transmission Assessment Report January 2010 Assessment and Analysis of the State-Of-the-Art High-Voltage Electric Transmission Systems with Specific Focus on High-Voltage Direct Current
More informationQ: PLEASE STATE YOUR NAME AND BUSINESS ADDRESS. A: Gerry Sheerin. Sheerin Technical, 25 Eastville Avenue, Toronto, Ontario Canada
DIRECT TESTIMONY OF GERRY SHEERIN, P. ENG ON BEHALF OF PIEDMONT ENVIRONMENTAL COUNCIL BEFORE THE STATE CORPORATION COMMISSION OF VIRGINIA CASE NOS. PUE-00-0001 AND PUE-00-000 1 1 1 1 1 1 1 1 1 Q: PLEASE
More informationTAN δ (DELTA) CABLE TESTING OVERVIEW AND ANSWERS TO FREQUENTLY ASKED QUESTIONS. What Is Tan δ, Or Tan Delta?
TAN δ (DELTA) CABLE TESTING OVERVIEW AND ANSWERS TO FREQUENTLY ASKED QUESTIONS What Is Tan δ, Or Tan Delta? Tan Delta, also called Loss Angle or Dissipation Factor testing, is a diagnostic method of testing
More informationComEd Grid Renewal Terence R. Donnelly
ComEd Grid Renewal Terence R. Donnelly Executive Vice President and Chief Operating Officer September 23, 2013 COMED S GRID MODERNIZATION VISION ComEd will fulfill the promise of grid modernization for
More informationHow To Test For Safety On A Power Cable
T H E M A G A Z I N E O F 7 x 2 4 E X C H A N G E I N T E R N AT I O N A L A Green Approach to Building a Superior Data Center S P R I N G 0 9 BUILD FOR TODAY. EXPAND ON DEMAND. Modularity in the data
More informationRCP2 Portfolio Overview Document
RCP2 Portfolio Overview Document Portfolio: Expenditure Class: Base Capex Expenditure Category: Grid Replacement & Refurbishment As at date: 15 November 2013 Expenditure Forecast Real 2012/13 NZ$ (m) 2015-2016
More informationCABLE ACCESSORIES 110-220 kv
CABLE ACCESSORIES 110-220 kv Termination 110 kv Technical description Termination MKB 126 / 145 with composite type insulator uses for cable line joints with other elements of power-supply systems. Termination
More informationUndergrounding high voltage electricity transmission. The technical issues
Undergrounding high voltage electricity transmission The technical issues This is an interactive PDF document with clickable links from the contents to all sections and back and also to URL and email links.
More informationProactive Asset Management for GIS A six step process for reducing risk, cost, and improving reliability
White paper Proactive Asset Management for GIS A six step process for reducing risk, cost, and improving reliability Gas Insulated Substations (GIS) are often critical assets for most organizations. GIS
More informationPower Voltage Transformers for Air Insulated Substations. THE PROVEN POWER.
Power Voltage Transformers for Air Insulated Substations THE PROVEN POWER. Introduction Trench Power Voltage Transformers (Power VTs) combine the attributes of an inductive voltage transformer with the
More informationCentral Hudson Gas & Electric
Central Hudson Gas & Electric Gas Operations Emergency System Operating Plan Stephen Burger Manager Customer Service & Operations 1 About Central Hudson Customers 300,000 electric 74,000 natural gas 2,600
More informationSMALL GAS OPERATOR OPERATION AND MAINTENANCE PLAN
SMALL GAS OPERATOR OPERATION AND MAINTENANCE PLAN Facility Name: Address: QUALIFIED PERSONNEL All tasks shall be completed by a person that is qualified to that task (see operators qualification of individuals
More information5IF /$4$# *OD IBT CFFO FTUBCMJTIFE GPS DFSUJmDBUJPO QVSQPTFT POMZ BOE UIFSFGPSF EPFT OPU PGGFS BOZ QSFQBSBUPSZ USBJOJOH )PXFWFS UIJT MJTU PG
5IF /$4$# *OD IBT CFFO FTUBCMJTIFE GPS DFSUJmDBUJPO QVSQPTFT POMZ BOE UIFSFGPSF EPFT OPU PGGFS BOZ QSFQBSBUPSZ USBJOJOH )PXFWFS UIJT MJTU PG TVHHFTUFE USBJOJOH EPDVNFOUT NBZ IFMQ ZPV LOPX XIBU UP FYQFDU
More informationDry-type transformers. Dry-type transformers from ABB The ideal solution for the oil and gas industry
Dry-type transformers Dry-type transformers from ABB The ideal solution for the oil and gas industry 2 Dry-type transformers for the oil and gas industry ABB s products and solutions for the oil and gas
More informationCathodic Protection Use On Tank Bottoms & Underground Piping In Power Generation Plants
Cathodic Protection Use On Tank Bottoms & Underground Piping In Power Generation Plants PG&E Office San Francisco January 18, 2007 Craig K. Meier Corrosion Control Incorporated Corrosion process for tanks
More informationMEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS
MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS Meher Capacitors offers reliable and innovative products and solutions in the fields of Reactive Power Compensation, Power Quality and Energy
More informationUniversity of Maryland College Park District Energy System. IDEA Campus Energy Conference February 9, 2012
University of Maryland College Park District Energy System IDEA Campus Energy Conference February 9, 2012 UMCP District Energy System The University of Maryland district energy system consists of a well
More informationWATER / WASTEWATER & POWER PROJECTS LAST 5 YEARS. No of Staff Provided by BCE. Overall Project Value (SR)
WATER / WASTEWATER & POWER PROJECTS LAST 5 YEARS A. Completed December 2001 Shedgum Debottlenecking # 45943/00 47.34 Million Total 600.8 Million 154 n American Oil Co. (ARAMCO) ARAMCO Feb. 1998 to Dec.
More informationSection 21. Telecommunication Hardware. www.geindustrial.com BuyLog Catalog 21-1
Introduction...21-1 Fiber Closure Hardware...21-2 Cable Location Surge Protectors...21-4 Introduction GE has been manufacturing Telecommunication Hardware products for over 20 years and has become a leader
More informationThe Contractor shall furnish and install all shielded power cable suitable for use on this project.
Section 16122 PRIMARY POWER CABLES PART 1 GENERAL: WORK INCLUDED The Contractor shall furnish and install all shielded power cable suitable for use on this project. RELATED WORK Section 16020: Tests SUBMITTALS
More informationInspection and Testing of Water-Based Systems
Inspection and Testing of Water-Based Systems Standard Model/Computer-Based Testing Level III Content Outline The candidate for NICET certification at Level III in the Inspection and Testing of Water-Based
More informationPUBLIC UTILITIES COMMISSIO~t~ Docket No. DE 15-
Th~NALZZ~ Exhibit STATE OF NEW HAMPSHIRE t~~eeee BEFORE THE FROM FILE PUBLIC UTILITIES COMMISSIO~t~ Liberty Utilities (Granite State Electric) Corp. dibla Liberty Utilities Calendar Year 2014 Reliability
More informationScottishPower Distribution Cables & Equipment. Metal Theft
ScottishPower Distribution Cables & Equipment Metal Theft April 2012 As an aid to deterring to metal theft this booklet has been put together to help identify the types of utility power cables and associated
More informationIndependent analysis methods for Data Centers
Bilfinger HSG Facility Management GmbH Independent analysis methods for Data Centers Max Altmeyer / Marvin Köhler August 19 th, 2015 Agenda 1. Weak point analysis 2. Energy efficiency analysis 3. Combined
More informationSP Energy Networks 2015 2023 Business Plan
SP Energy Networks 2015 2023 Business Plan Updated March 2014 Annex 132kV Cable Strategy SP Energy Networks 27 March 2014 132kV Cable Strategy March 2014 Issue Date Issue No. Document Owner Amendment Details
More informationPFT Solutions. Fluid Filled Cable Leak Detection
PFT Solutions Fluid Filled Cable Leak Detection Linking the future As the worldwide leader in the cable industry, Prysmian Group believes in the effective, efficient and sustainable supply of energy and
More informationOPERATIONS & MAINTENANCE (O&M) FOR PROPANE STORAGE FACILITIES
OPERATIONS & MAINTENANCE (O&M) FOR PROPANE STORAGE FACILITIES Reference: National Fire Protection Association (NFPA) Pamphlet No. 58 Liquefied Petroleum Gas Code, 2001, Chapter 11 Type of Facility: Petroleum
More informationTprove and maintain supply standards
PD Monitoring A Critical Tool For Condition-Based Assessments As medium-voltage facilities age, utilities leverage diagnostics to aid in asset management decisions. By Cliff Walton, EDF Energy Networks,
More informationCable Accessories. for Extruded Dielectric Cable 69kV - 230kV Rated. Catalog Python13
Cable Accessories for Extruded Dielectric Cable 69kV - 230kV Rated Components used in cable systems 100% Tested Factory Molded For outdoor applications through 230kV For gas insulated substations and transformers
More informationHIGH-CAPACITY HIGH TEMPERATURE SUPERCONDUCTING POWER CABLES
HIGH-CAPACITY HIGH TEMPERATURE SUPERCONDUCTING POWER CABLES Jean-Maxime SAUGRAIN NEXANS Corporate VP Technical IASS Workshop Postdam May 13, 2011 Rationale High-capacity High Temperature Superconducting
More informationCONSOLIDATED EDISON CO. OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY 10003 DISTRIBUTION ENGINEERING DEPARTMENT SUBSTATION & EQUIPMENT SECTION
CONSOLIDATED EDISON CO. OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY 10003 DISTRIBUTION ENGINEERING DEPARTMENT SUBSTATION & EQUIPMENT SECTION SPECIFICATION EO-5023 REVISION 3 MARCH 2003 REQUIREMENTS FOR
More informationSUPERCONDUCTING CABLE SYSTEMS
SUPERCONDUCTING CABLE SYSTEMS INTRODUCTION An aging and inadequate power grid is widely seen as one of the greatest obstacles to the restructuring of power markets in the United States, Europe and elsewhere.
More informationUniversity of Iowa Main Power Plant 2008 Flood Preparations, Event, & Recovery
University of Iowa Main Power Plant 2008 Flood Preparations, Event, & Recovery Yellow Alert for Mayflower Residence hall Peak at 31.5 feet Power Plant floods from steam tunnel and shuts down 1993 Flood
More informationELECTRODE BOILERS VAPOR POWER INTERNATIONAL
ELECTRODE BOILERS WITH JET-FLO Technology VAPOR POWER INTERNATIONAL ELECTRODE boilers The Electrode Steam Boiler with Jet-Flo technology consists of an insulated pressure vessel and is fully enclosed in
More information5.0 Reference: Application, Volume I, Chapter 5, Heritage Contract
1 5.0 Reference: Application, Volume I, Chapter 5, Heritage Contract 1.5.30 5-27: Provide a comprehensive explanation of the application of the Equipment Health Rating process to transformers and generators
More informationQualitative Analysis of Power Distribution Configurations for Data Centers
Qualitative Analysis of Power Distribution Configurations for Data Centers White Paper #4 2007 The Green Grid. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted,
More informationMokeWISE Program Scope of Work: Project 8b: Rehabilitation of Transmission Main
MokeWISE Program Scope of Work: April 2015 Abstract... 2 Background Information... 2 Calaveras Public Utility District... 2 Water Rights... 2 Water Supply... 2 Project Information... 3 Project Description...
More informationHyperlinks are Inactive
Prepared by: NIB/EOB PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES 05503 Department: Electric T&D Section: T&D Engineering and Technical Support Approved by: G.O. Duru (GOD)
More informationHendrix Spacer Cable
Hendrix Spacer Cable What is Spacer Cable? Covered Conductor Withstands temporary branch contact Eliminates temporary faults Protects wildlife Less clearance issues Compact Configuration Multiple Circuits
More informationGet Into Energy Math Quiz 12 Answer Key Fractions and Decimals
Name: Date: Get Into Energy Math Quiz 12 Answer Key Fractions and Decimals math 1. Kemen is pulling wire for an upgrade project. Kemen and the crew have pulled 400 feet of the 500 feet required to complete
More informationUptown Campus, Primary Electric Master Plan - Program Study State University of New York At Albany, SUCF Project No. 01832 V.
V. DESIGN STANDARDS i. Medium Voltage Cables ii. iii. iv. Separable Connectors Splices & Fault Indicators Manholes & Ductbanks Primary Switches & Medium Voltage Transformers v. Metering, Monitoring, &
More informationTHE OKONITE COMPANY. Ramsey, New Jersey 07446. 201.825.0300. Fax: 201.825.3524. www.okonite.com
THE OKONITE COMPANY Ramsey, New Jersey 07446. 201.825.0300. Fax: 201.825.3524. www.okonite.com Since its founding in 1878, the cornerstone of The Okonite Company s philosophy has been the complete evaluation
More informationHIGH- AND EXTRA-HIGH-VOLTAGE GLOBAL CABLE SYSTEM SOLUTIONS Rely On Our Experience... Experience Our Capabilities
HIGH- AND EXTRA-HIGH-VOLTAGE GLOBAL CABLE SYSTEM SOLUTIONS Rely On Our Experience... Experience Our Capabilities RELY ON OUR EXPERIENCE... EXPERIENCE OUR CAPABILITIES For close to half a century, Silec
More informationWhat Are the Qualifications to Conduct Arc Flash Studies? Where Do You Begin?
What Are the Qualifications to Conduct Arc Flash Studies? Where Do You Begin? Comparing apples-to-apples bids Plant Services Special Report A shock hazard analysis should be included as part of an arc
More informationPrimary and Secondary Electrical Distribution Systems
Primary and Secondary Electrical Distribution Systems Critical Facilities Round Table 12th Quarterly Membership Meeting June 2, 2006 David D. Roybal. P.E. Eaton Electrical Cutler-Hammer Products Utility
More informationCables, Cable Laying & Accessories Manual
Distribution Business Cables, Cable Laying & Accessories Manual Database ref: File Ref: Title Page & Revision Log For Cables & Access v4 - Nov 2003.doc Manual Name: Cables & Accessories Manual Version
More informationSUMMARY OF DISTRIBUTION INTEGRITY MANAGEMENT PROGRAM
Page 1 of 9 SUMMARY OF DISTRIBUTION INTEGRITY MANAGEMENT PROGRAM Program Overview: The Distribution Integrity Management Program ( DIMP ) activities are focused on obtaining and evaluating information
More informationAMSC s Superconductor Cable Technologies for Electric Utilities
International Workshop 2014 AMSC s Superconductor Cable Technologies for Electric Utilities Michael Ross, P.E. Managing Director of Superconductor Power Systems AMSC Corporate Facts Headquartered in MA,
More informationFundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components
Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components Course No: E02-010 Credit: 2 PDH Boris Shvartsberg, Ph.D., P.E., P.M.P. Continuing Education
More informationAssessment of the Underground Distribution System of the Potomac Electric Power Company. Final Report
Assessment of the Underground Distribution System of the Potomac Electric Power Company Final Report December 7, 2001 Formal Case No. 991 Investigation into Explosions Occurring in or Around the Underground
More informationHeating Cable. Construction
Mineral Insulated High Temperature A C Constant Wattage Series Resistance Heating Cable Sets Process Temperature Maintenance to F (593 C) Maximum Exposure Temperature 4 F (76 C) (Power Off) Corrosion Resistant
More informationRadial Distribution Test Feeders
Radial Distribution Test Feeders Distribution System Analysis Subcommittee Report Abstract: Many computer programs are available for the analysis of radial distribution feeders. In 1992 a paper was published
More informationBCTC/BC Hydroʹs operational experience with Distributed Temperature Sensing (DTS) Systems for Transmission Cables. Presented by
BCTC/BC Hydroʹs operational experience with Distributed Temperature Sensing (DTS) Systems for Transmission Cables Presented by S. Cherukupalli Transmission Cables Design BC Hydro at the ICC Spring Meeting,
More informationUnderground Transmission Lines
Underground Transmission Lines INTRODUCTION In today s urban, environmentally sensitive environment, how are you going to get power to the people who need it? In many cities, overhead transmission lines
More informationScrew Plug Immersion Heaters
Immersion Heaters Overview Immersion Heaters consist of hairpin bent tubular elements brazed or welded into a screw plug and provided with terminal enclosures for electrical connections. Immersion Heaters
More informationTransmission Silicone Insulators Line Post 69 kv to 161 kv
K-LINE INSULATORS LIMITED Catalogue T-LP Transmission Silicone Insulators Line Post 69 kv to 161 kv ISO9001 SAI GLOBAL FILE No. 000117 Transmission Silicone Insulators Line Post Today transmission lines
More informationWIRE AND CABLE ENGINEERING GUIDE
DC Hi Pot Testing Excerpt from PRYSMIAN S WIRE AND CABLE ENGINEERING GUIDE (FOR INFORMATIONAL PURPOSES ONLY) Page 1 of 6 DC HIGH POTENTIAL TESTING DC Hi-Pot testing can be applied as a withstand test (a
More information16300 MEDIUM VOLTAGE DISTRIBUTION
16300 MEDIUM VOLTAGE PART 1: GENERAL 1.01 SYSTEM DESCRIPTION A. Most new loads will be served from the underground electric distribution system. This system is a primary open loop configuration served
More informationState, trends and evolutions of HV/EHV power cables systems and contributions of SC B1 to their ongoing progress
0611-048-Mep229 12/12/06 6:44 Page 22 State, trends and evolutions of HV/EHV power cables systems and contributions of SC B1 to their ongoing progress Reinhard SCHROTH, Chairman of SC B1 2002-2006 High
More informationMaintenance Report MEDIUM VOLTAGE POWER STATION 500SC / 630SC / 800SC / 900SC / 1000 1SC / 1000 2SC / 1250SC / 1600SC / 1800SC / 2000SC
Maintenance Report MEDIUM VOLTAGE POWER STATION 500SC / 630SC / 800SC / 900SC / 1000 1SC / 1000 2SC / 1250SC / 1600SC / 1800SC / 2000SC Project name: Customer: Address, location of the system: Serial number
More informationMinimizing Impact of Electric Utility Outages with Backup Generation
Minimizing Impact of Electric Utility Outages with Backup Generation Introduction of the Speaker Michael Dempsey, PE Senior Electrical Engineer Carter & Burgess, Inc. Energy & Power Solutions Facility
More informationMAR 23 2012. Sincerely,
MAR 23 2012 Mr. Terry Gottberg President Merit Energy Company, LLC 1327 Noel Road, Suite 500 Dallas, TX 75240 Re: CPF No. 5-2011-6001 Dear Mr. Gottberg: Enclosed please find the Final Order issued in the
More informationDistribution Voltage Regulators
Distribution Voltage Regulators Type JFR Single Phase 2.5 to 19.9 kv Type SFR Three Phase 13.2 to 34.5 kv Power Transmission & Distribution Siemens JFR & SFR Voltage Regulators Improving Quality of Service
More informationWhite Paper. www.geodecisions.com
White Paper www.geodecisions.com A Geo Spatial Total Asset Management System (TAMS) To Improve Asset Management Decision Making Fall 2013 Abstract This paper describes a Geospatial Total Asset Management
More informationSOCALGAS APROACH TO PIPELINE INTEGRITY
SUMMER 2011 SOCALGAS APROACH TO PIPELINE INTEGRITY Southern California Gas Company (SoCalGas ) is committed to providing clean, safe and reliable natural gas to its customers and takes important steps
More informationAPPLICATION ORIENTED DESIGN OF CABLES
APPLICATION ORIENTED DESIGN OF CABLES Mrs. Rohini Bhattacharyya, Dubai cables Ltd.P. O. Box 11529,Dubai. rohinib@ducab.com Mr. Nawaf Ahmad Al Mohaideb Dubai Cables Ltd. P. O. Box 11529, Dubai. Nawaf@ducab.com
More informationAGENDA ITEM C9. COST/FUNDING SOURCE: $431,847.40/ Uniform Rate
AGENDA ITEM C9 DATE: February 2, 2015 TO: FROM: SUBJECT: Matt Jordan, General Manager Charles Carden, Chief Operating Officer South Pasco Transmission Main Condition Assessment Services with Pure Technologies
More informationWHY CABLE TRAY? BECAUSE A CABLE TRAY WIRING SYSTEM PROVIDES SAFE AND DEPENDABLE WAYS TO SAVE NOW AND LATER
Large numbers of electrical engineers have limited detail knowledge concerning wiring systems. There is the tendency by engineers to avoid becoming involved in the details of wiring systems, leaving the
More informationCertificate of Registration
Certificate of Registration This is to certify that Clancy Docwra Limited Supplier Number: 061973 are now fully registered as a supplier on UVDB for the following products/services 1.4.25 Communication
More informationThe Office of Pipeline Safety does not object to the granting of these waivers if the following conditions are included:
Mr. Charles C. Constantine Executive Secretary Maryland Public Service Commission 301 West Preston Street Baltimore, Maryland 21201 Dear Mr. Constantine: This will acknowledge receipt of Case No. 6533
More informationPotomac Electric Power Company. Comprehensive Reliability Plan. For. District of Columbia. Including
Potomac Electric Power Company Comprehensive Reliability Plan For District of Columbia Including Distribution System Overview, Reliability Initiatives and Response to Public Service Commission of the District
More informationControlling Risks Risk Assessment
Controlling Risks Risk Assessment Hazard/Risk Assessment Having identified the hazards, one must assess the risks by considering the severity and likelihood of bad outcomes. If the risks are not sufficiently
More informationSECTION 18370 SIGNAL WIRE AND CABLE
SECTION 18370 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for all cable and wire required for signal and signal power system wiring to wayside shelters, junction boxes, and factory
More informationDistributed Temperature Sensing - DTS
Intelligent Solutions Distributed Temperature Sensing - DTS Enabling fast, reliable and cost-effective sensing through highly integrated optical measurement systems Fire detection Power cable monitoring
More informationSewer Pipe Lining An Economic Solution for Pipe Rehabilitation By Tawana Albany Nicholas, Virgin Islands Waste Management Authority
Sewer Pipe Lining An Economic Solution for Pipe Rehabilitation By Tawana Albany Nicholas, Virgin Islands Waste Management Authority Abstract The United States Virgin Islands Waste Management Authority
More informationAORC Technical meeting 2014
http : //www.cigre.org B1-1055 AORC Technical meeting 2014 220 kv Long Distance Underground HVAC Cable Circuit NAVEED RAHMAN Nexans Olex Melbourne, Australia SUMMARY In 2009, the Victorian state government
More informationEffectively Harnessing Data Analytics to Maximize Utility and Customer Benefit
Analyst Meeting 2013 Effectively Harnessing Data Analytics to Maximize Utility and Customer Benefit Gregg Borachok, Duke Energy Electricity Symposium, Purdue University August 28, 2013 Duke Energy Electric
More informationErgo-Pro Single Line Solar Station Installation and Operating Instructions
Rp 3/4 Ergo-Pro Single Line Solar Station Installation and Operating Instructions Item No Pump type 677.21.70 WILO ST 15/6 13 2 4 11 Technical Specifications Max. operating pressure: 6 bar Max. operating
More informationUndergrounding high voltage electricity transmission lines. The technical issues
Undergrounding high voltage electricity transmission lines The technical issues Contents Introduction 03 National Grid electricity transmission 03 an overview Section 1 Insulating underground cables 04
More informationMETHOD STATEMENT INSTALLATION OF INSULATING FLANGE KITS
METHOD STATEMENT INSTALLATION OF INSULATING FLANGE KITS Revision Date Prepared By Approved By Method Statement IF Kits BAC Corrosion Control Limited Stafford Park 11 Telford TF3 3AY Tel: 01952 290321 Fax:
More informationINTERNATIONAL STANDARD
INTERNATIONAL STANDARD IEC 60502-1 Second edition 2004-04 Power cables with extruded insulation and their accessories for rated voltages from 1 kv (U m = 1,2 kv) up to 30 kv (U m = 36 kv) Part 1: Cables
More informationLeast Cost Cable System. Strategies to Reduce Cable and Infrastructure Costs When Transitioning to an All Conduit Systems
Least Cost Cable System Strategies to Reduce Cable and Infrastructure Costs When Transitioning to an All Conduit Systems Cost Sharing of Cable Systems Underground Extensions The Company will construct
More information261000 Medium Voltage Electrical Distribution
Sections Included In This Standard: 1.1 General 1.2 Underground Cable 1.3 Medium Voltage Switches 1.4 Transformers 1.5 Electrical Manholes 1.6 Switch Vaults 1.7 Distribution Switchgear/Switchboards This
More informationNSW Submarine Power. Cables for the future, delivered today
NSW Submarine Power Cables for the future, delivered today NORDDEUTSCHE SEEKABELWERKE GMBH (NSW) The submarine competence center within the General Cable Group After NSW was founded in 1899 by Felten &
More informationGUIDELINES FOR UTILITY INSTALLATIONS Part 1 - Wire Lines and Communications Cables
Engineering Department SEPTEMBER, 2007 GUIDELINES FOR UTILITY INSTALLATIONS Part 1 - Wire Lines and Communications Cables General Requirements This section applies to all public and private utilities,
More information